In addition to what is explained below, the safety and installation information provided in the
installation manual must be read and followed. The technical documentation and the interface
and management software for the product are available at the website.
The device must be used in the manner described in the manual. If this is not the case the
safety devices guaranteed by the inverter might be ineffective.
Quick Installation Guide
PVI-6.0/8.0/10.0/12.5-TL-OUTD
ABB Solar inverters
1.
Labels and Symbols
Inverter Models and Components
2.
Lifting and transport
4.
Choice of installation location
EN
Assembly Instruction
6.
List of supplied components
3.
Choice of installation location
5.
Input configuration (DC)
7.
The labels on the inverter have the Agency marking, main technical data and identification of the equipment and manufacturer
01
05
PVI-X-TL-OUTD-Y
The labels attached to the equipment must NOT be removed, damaged, dirtied, hidden,etc...
If the service password is requested, the field to be used is the serial number -SN: YYWWSSSSSS-
In the manual and/or in some cases on the equipment, the danger or hazard zones are indicated with signs, labels, symbols or icons.
Always refer to instruction
manual
General warning - Important
safety information
Hazardous voltage
Hot surfaces
IP65
Protection rating of
equipment
Temperature range
Without isolation
transformer
Direct and alternating
currents, respectively
Positive pole and negative
pole of the input voltage
(DC)
Always use safety clothing
and/or personal safety
devices
Point of connection for
grounding protection
Time need to discharge
stored energy
10
01 Inverter model
02 Inverter Part Number
03 Inverter Serial Number
04 Week/Year of manufacture
05 Main technical data
The models of inverter to which this guide refers are available in 4 power ratings: 6.0 kW, 8.0 kW, 10.0 kW and 12.5 kW. Three types are available for each
model: Standard, with DC disconnect switch (Version -S) or with DC input protection fuses combined with DC disconnect switch (Version -FS).
03
04
05
06
02
01
07
10
09
08
11
12
10
09
08
11
12
10
11
12
09
-FS
VERSION
-S
VERSION
STANDARD
VERSION
14
13
15
17
16
18
19
20
Main components
01
Bracket
05
Display
09
Input connectors (MPPT1)
13
fuse board (*only version -FS)
17
Internal battery
02
Heatsink
06
Keyboard
10
Input connectors (MPPT2)
14
DC Input terminal block
18
Signal terminal block
03
Front cover
07
Handles
11
AC cable gland
15
AC Output terminal block
19
RJ45 Connectors
04
LED Panel
08
DC Disconnect
switch
12
Service cable glands
16
Channel configuration switch
20
RS485 line termination
switch
Transport and handling
Transport of the equipment, especially by road, must be carried out with by suitable ways and means for
protecting the components from violent shocks, humidity, vibration, etc.
Lifting
The means used for lifting must be suitable to bear the weight of the equipment.
Unpacking and checking
The components of the packaging must be disposed on in accordance with the regulations in force in the
country of installation.
When you open the package, check that the equipment is undamaged and make sure all the components
are present. If you find any defects or damage, stop unpacking and consult the carrier, and also promptly
inform the Service ABB.
Equipment weight
Model
Mass
weight
PVI-6.0-TL-OUTD
PVI-6.0-TL-OUTD-S
PVI-6.0-TL-OUTD-FS
PVI-8.0-TL-OUTD
PVI-8.0-TL-OUTD-S
PVI-8.0-TL-OUTD-FS
PVI-10.0-TL-OUTD
PVI-10.0-TL-OUTD-S
PVI-10.0-TL-OUTD-FS
PVI-12.5-TL-OUTD
PVI-12.5-TL-OUTD-S
PVI-12.5-TL-OUTD-FS
<41.0 Kg
Environmental checks
- Consult the technical data to check the environmental parameters to be observed
- Installation of the unit in a location exposed to direct sunlight must be avoided as it may cause:
1. power limitation phenomena in the inverter (with a resulting decreased energy production by the system)
2. premature wear of the electrical/electromechanical components
3. premature wear of the mechanical components (gaskets) and of the user interface (display)
- Do not install in small closed rooms where air cannot circulate freely
- To avoid overheating, always make sure the flow of air around the inverter is not blocked
- Do not install in places where gases or flammable substances may be present
- Do not install in rooms where people live or where the prolonged presence of people or animals is expected,
because of the noise (about 50dB(A) at 1 m) that the inverter makes during operation
Installations above 2000 metres
On account of the rarefaction of the air (at high altitudes), particular conditions may occur:
- Less efficient cooling and therefore a greater likelihood of the device going into derating because of high internal
temperatures
- Reduction in the dielectric resistance of the air that, in the presence of high operating voltages (DC input), can
create electric arcs (discharges) that can reach the point of damaging the inverter
All installations at altitudes of over 2000 metres must be assessed case by case with the ABB Service
department.
Installation position
- Install on a wall or strong structure capable of bearing the weight of the equipment
- Install in safe, easy to reach places
- If possible, install at eye-level so that the display and status LEDs can be seen easily
- Install at a height that considers the heaviness of the equipment
- Install vertically with a maximum inclination of +/- 5°
- Choose a place with enough space around the unit to permit easy installation and
removal of the object from the mounting surfaces; comply with the indicated minimum
distances
- For a multiple installation, position the inverters side by side; if the space available does
not allow this arrangement, position the inverters in a staggered arrangement as shown
in the figure so that heat dissipation is not affected by other inverters
Final installation of the inverter must not compromise access to any disconnection
devices that may be located externally.
Please refer to the warranty terms and conditions available on the website and
evaluate any possible exclusion due to improper installation.
15
cm
20
cm
10cm
10cm
Wall mounting
During installation, do not place the inverter with its front facing towards the ground.
- Position the bracket 01 so that it is perfectly level on the wall and use it as a boring template.
- Drill the 3 holes required using a drill with 10mm bit. The holes must be about 70mm deep. On bracket 01
there are 3 fastening holes.
- Fix the bracket to the wall with the 3 wall anchors, 10mm in diameter, supplied. (Step 1).
- Hook the inverter to the bracket springs in correspondence with the insertion points in the bracket on
the back of the inverter (Step 2).
- Drill 2 holes in correspondence with the slots on the inverter lower bracket, using a drill with a 10 mm
diameter bit. The holes must be approximately 70 mm deep.
- Anchor the lower part of the inverter using No. 2 plugs with a diameter of 10 mm, supplied (Step 3).
- Unscrew the 6 screws and open the front cover 03 in order to make all the necessary connections.
- Once the connections have been made, close the cover by tightening the 6 screws on the front to a
minimum tightening torque of 1.5 Nm.
1
3
2
Available components
Quantity
Bracket for wall mounting
1
Bolts and screws for wall mounting
5 + 5
D.18 Washer
5
L-key, TORX TX20
1
M20 Cable gland
1
M40 Cable gland
1
Two-hole gasket for M20 signal cable
glands and cap TGM58
1 + 1
Available components
Quantity
Jumpers for configuration of the
parallel input channels
2
Connector for connecting the confi-
gurable relay
2
Connector for the connection of the
communication and control signals
2
Male quick fit connectors
*
Female quick fit connectors
*
In addition to what is explained in this guide, the safety and installation information provided in the installation manual must be read and followed.
The technical documentation and the interface and management software for the product are available at the website.
XXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXX
ABB solar inverters
Technical documentations
1
* For PVI-6.0/8.0/10.0/12.5-TL-OUTD-S models: 4 pieces
for PVI-6.0/8.0/10.0/12.5-TL-OUTD and PVI-6.0/8.0/10.0/12.5-TL-OUTD-FS models: 6 pieces
All versions of the inverter are equipped with two input channels (therefore with double maximum power point tracker MPPT) independent of each other,
which can however be connected in parallel using a single MPPT.
Configuration of independent channels (default configuration)
This configuration involves the use of the two input channels (MPPT) in independent mode.
This means that the jumpers between the two channels (positive and negative) of the DC input terminal block 14 must
not be installed and the switch 16 located on the main board must be set to “IND”.
Configuration of parallel-connected channels
This configuration uses the two input channels (MPPT) connected in parallel. This means that the jumpers between the
two channels (positive and negative) of the DC input terminal block 14 must be installed and the switch 16 located on
the main board must be set to “PAR”.
14
16
16
PVI-X-TL-OUTD-Y
P/N:PPPPPPPPPPP
WO:XXXXXXX
SO:SXXXXXXXX Q1
SN:YYWWSSSSSS WK:WWYY
01
02
04
03
11.
Connection of the communication and control signals
12.
Commissioning
13.
Instruments
PVI-6.0_8.0_10.0_12.5-TL-OUTD-Quick installation guide EN-RevB
EFFECTIVE 2014-03-06
© Copyright 2014 ABB. All Rights Reserved.
Specifications subject to change without notice.
8.
Input connection (DC)
9.
Line cable and protection devices
10.
Output connection (AC)
14.
Structure of the display menu
15.
Characteristics and technical data
Contact us
www.abb.com/solarinverters
LEDs and BUTTONS, in various combinations, can be used to view the status or carry out complex actions that are described more fully in the manual.
06
05
04
LED
POWER
GREEN On if the inverter is working correctly. Flashes when
checking the grid or if there is insufficient sunlight.
ESC
It is used to access the main menu, to go back to the previous menu
or to go back to the previous digit to be edited
LED
ALARM
YELLOW The inverter has detected an anomaly. The anomaly
is shown on the display.
UP
It is used to scroll up the menu options or to shift the numerical scale
in ascending order
LED
GFI
RED Ground fault on the DC side of the PV generator. The
error is shown on the display.
DOWN
It is used to scroll down the menu options or to shift the numerical
scale in descending order
ENTER
It can be used to confirm an action, to access the submenu for the
selected option (indicated by the > symbol) or to switch to the next
digit to be edited
ABB inverters are equipped with a graphic Display 05 , consisting of 2 lines of 16 characters each, which can be used to:
- Display the operating state of the inverter and the statistical data
- Display the service messages for the operator
- Display the alarm and fault messages for the operator
- Changing the settings of the inverter
During the normal operation of the inverter the display cycles through the GENERAL INFORMATION. This information relates to the input and output parame-
ters and the inverter identification parameters. By pressing ENTER it is possible to lock scrolling on a screen to be constantly displayed.
Press ESC to access the three main menus, which have the following functions:
- STATISTICS:
Displays the statistics
- SETTINGS:
Modify the settings of the inverter
- INFO:
View service messages for the operator
Refer to the manual for details regarding use and functions available in the menu
Check for correct polarity in the input strings and absence of any leakage to ground in
the PV generator. When exposed to sunlight, the PV panels supply DC direct voltage to
the inverter.
The inside of the inverter may only be accessed after the equipment has been discon-
nected from the grid and from the photovoltaic generator.
Warning! The inverters to which this document relates to are WITHOUT ISOLATION
TRANSFORMER (transformer-less). This type involves the use of insulated photovoltaic
panels (IEC61730 Class A Rating) and the need to maintain the photovoltaic generator
floating with respect to earth: no pole of the generator must be connected to earth.
Each input is equipped with protection fuses on the -FS model: check that the fuse
current rating is the correct size for the photovoltaic modules installed.
For the string connections it is necessary to use the quick fit connectors (multicontact or weidmüller)
located on the bottom of the mechanic 09 10 .
The number of quick fit connectors changes based on the model of inverter.
STANDARD VERSION
-FS VERSION
-S VERSION
No. of input channels
2
2
No. of quick fit connectors
12 (6 pairs)
8 (4 pairs)
- Crimp the Multicontact/Weidmüller MC4/WM4 quick fit connector counterparts (supplied) to the string
cables or to the cables wired to the DC disconnect switches (external)
- Connect all the strings included in the design of the system and always check the tightness of the
connectors
- If some of the string inputs should not be used you must proceed to verify the presence of covers on
DC input connectors and then install them should they be absent: this operation is necessary for the
tightness of the inverter and to avoid damaging the free connector that could be used at a later date.
STANDARD VERSION
09
10
-S VERSION
09
10
-FS VERSION
09
10
Load protection breaker (AC disconnect switch) and line cable sizing
To protect the AC connection line of the inverter, we recommend installing a device for protection against over current and leakage with the following characteristics:
PVI-6.0-TL-OUTD
PVI-8.0-TL-OUTD
PVI-10.0-TL-OUTD
PVI-12.5-TL-OUTD
Type
Automatic circuit breaker with differential thermal magnetic protection
Nominal Voltage / Nominal Current
400 Vac / 16 A
400 Vac / 16 A
400 Vac / 20 A
400 Vac / 25 A
Magnetic protection characteristic
B/C
Number of poles
3/4
Type of differential protection
A/AC
Differential sensitivity
300 mA
ABB declares that the ABB transformerless inverters, in terms of their construction, do not inject continuous ground fault currents and therefore there is no requirement
that the differential protection installed downstream of the inverter be type B in accordance with IEC 60755 / A 2.
Characteristics and sizing of the line cable
For the connection of the inverter to the grid, you can choose between a star connection (3 phases + neutral) and a
delta connection (3 phases). The cross-section of the AC line conductor must be sized in order to prevent unwanted
disconnections of the inverter from the grid due to high impedance of the line that connects the inverter to the power
supply point.
Cross-section of the line
conductor
Maximum length of the line conductor
The values are calculated in nominal power condi-
tions, taking into account:
1. a power loss of not more than 1% along the line
2. copper cable, with HEPR rubber insulation, laid
in free air
PVI-6.0-TL
PVI-8.0-TL
PVI-10.0-TL
PVI-12.5-TL
4 mm²
55 m
43 m
34 m
28 m*
6 mm²
80 m
65 m
51 m
42 m
10 mm²
135 m
108 m
85 m
70 m
16 mm²
210 m
173 m
136 m
113 m
* Up to 45 °C Ambient temperature
max 16 mm
19 ÷ 28 mm
2
Warning! Before performing any of the operations described below, ensure the AC line downstream the
inverter has been correctly disconnected
- Remove the protective film located on the hole to be used for the AC cables 11
- Insert the M40 cable gland in the hole and secure it using the special M40 lock nut (supplied)
Warning! To ensure environmental protection IP65 it is necessary to fix the cable gland to the inverter
chassis with a minimum tightening torque of 8.0 Nm
- Strip 10 mm of sheathing from the AC grid connection cables
- Plug the AC line cable into the inverter, passing it through the previously installed cable gland
- Connect the protective earth (yellow-green) cable to the contact labelled with the
symbol on the terminal block 15
Warning! ABB inverters should be earthed (PE) via the terminal with the protective earth label
, using a cable with an appropriate cross-
section of the conductor for the maximum ground fault current that the generating system might experience
- Connect the neutral cable (normally blue) to the terminal labelled with the letter N
- Connect the phase cables to the terminals labelled with the letters R, S and T
Warning! The AC cables must be tightened on the terminal block with a minimum torque of 1.5 Nm
Once the connection to the terminal board 15 is complete, screw in the cable gland firmly (tightening torque 5.0Nm) and check the tightness.
15
Each cable which must be connected to the connectors of the communication and control signals must pass through one of the five service cable glands 12 .
An M20 cable gland (that takes cables from 7 mm to 13 mm in diameter) and a gasket with two holes to insert into the cable gland which enables two sepa-
rate cables of a maximum diameter of 5 mm to be accommodated, are available
Warning! To ensure environmental protection IP65 it is necessary to fix the cable glands to the inverter chassis with a minimum tightening
torque of 7 Nm
Connection to the RS485 communication line
The RS485 communication port is the inverter’s communication port. The
ABB inverters use an RS485 HALF-DUPLEX communication line made up of
two transmission and reception cables (+T/R and –T/R) and a communication
reference cable (RTN): all three cables must be connected in daisy-chain
configuration. The chain connection can be made without distinction by using
the RJ45 connector couples 19 (one for in and one for out) or the terminal
block 18 .The last inverter in the daisy chain must be “terminated” or the 120
Ohm communication line termination resistance must be activated by switching
the dip-switch 20 .
Using the alarm terminal block
Terminal block 18 connecting to the configurable relay that allows connection
of external devices which, according to the mode selected in the menu “SET-
TINGS > Alarm” can, for example, signal malfunctions. The operating modes
that can be set are: Production, Alarm, Alarm (Configurable) and Crepuscolar.
19
20
18
The ALARM contact can be used only with systems that ensure a safety isolating additional at least (supplementary insulation in relation
to the DC input voltage)
Using the REMOTE terminal block
The REMOTE terminal block 18 , if suitably configured, allows the “Remote ON/OFF” function to be used: this function allows remote disconnection of the
inverter from the grid
For further information regarding the configuration and use of the communication and control signals terminal block, please see the
manual
The inverter commissioning procedure is as follows:
- Switch the integrated switch 08 (versions –S and –FS) to the ON position or close the external switches: If the input voltage applied to one of the two input
channels is greater than the minimum starting voltage, the inverter will start up.
- When the inverter is turned on for the first time you will be asked to select the “Country” of installation. This selection allows the inverter to automatically
configure its parameters to ensure that compliance with local standards; the default language corresponding to the selected “Country” will also be set.
Warning! After the grid standard was set you have 24 hours to make any changes to the grid standard value; 24 hours later the “Country
Select.” functionality will be blocked, and any subsequent changes can only be made using a password provided on request by ABB
- After you have set the “Country” value, the message “Inizializing...Please Wait” is displayed. Depending on the input voltage value, the inverter will show
various messages on the display and change the behaviour of the three LED 04 :
INPUT VOLTAGE
DISPLAY MESSAGE
LED STATUS
DESCRIPTION
Vin < Vstart
Waiting Sun
Green = FLASHING
Yellow = OFF
Red = OFF
The input voltage is not sufficient to permit connection to the grid.
Vin > Vstart
Missing Grid
Green = FLASHING
Yellow = ON
Red = OFF
There is sufficient input voltage to permit connection to the grid:
the inverter waits until there is grid voltage to carry out the parallel
connection.
The inverter is powered ONLY by the voltage coming from the photovoltaic generator: presence of grid voltage alone IS NOT SUFFICIENT to permit
the inverter to start up.
- With the inverter in “Missing Grid” status, close the AC switch downstream the inverter so as to supply the grid voltage to the inverter: the inverter performs
the grid voltage check, measures the photovoltaic generator insulation resistance against earth and carries out other self-diagnosis checks. During the
checks before the parallel with the grid, the green LED keeps flashing, the others are off.
During the grid voltage check and measurement of the insulation resistance, the values for the grid voltage and frequency and the insulation resis-
tance measured by the inverter are shown on the display. The inverter completes parallel connection with the grid SOLELY if the grid parameters
meet the ranges provided for by the regulations in force and if the insulation resistance is greater than 1Mohm.
- If the preliminary checks for parallel connection to the grid are successful, the inverter connects to the grid and begins to export power to the grid. At this
stage, the display shows the inverter’s parameters in cycles. The green LED stays lit whereas the others are off.
PVI-6.0-TL-OUTD
PVI-8.0-TL-OUTD
PVI-10.0-TL-OUTD
PVI-12.5-TL-OUTD
Input
Absolute Maximum Input Voltage (Vmax,abs)
900 V
Input Activation Voltage (Vstart)
360 V (adj. 250...500 V)
Input Operating Range (Vdcmin...Vdcmax)
0.7 x Vstart...850 V
Rated DC Input Power (Pdcr)
6200 Wp
8250 Wp
10300 Wp
12800 Wp
Number of Independent MPPTs
2
Maximum Input Power for each MPPT (PMPPT max)
4200 W
5500 W
6500 W
8000 W
MPPT Input DC Voltage Range (VMPPT min,f ... VMPPT max,f) at Pacr
200...750 V
270...750 V
300...750 V
360...750 V
Maximum DC Input Current (Idc max) / for each MPPT (IMPPT max)
34.0 A / 17.0 A
34.0 A / 17.0 A
34.0 A / 17.0 A
36.0 A / 18.0 A
Maximum Input Short Circuit Current for each MPPT
22.0 A
Maximum Backfeed current (from AC to DC side)
Negligible
Number of DC Inputs Pairs for each MPPT
2 (-S Version), 3 (Standard and -FS Version)
DC Connection Type
Tool Free PV Connector WM / MC4
Input protection
Reverse Polarity Protection
Inverter protection only, from limited current source, for standard and -S versions, and for -FS version when
max 2 strings are connected
Input Overvoltage Protection for each MPPT - Varistor
2
Photovoltaic Array Isolation Control
According to local standard
DC Switch Rating (-S Version)
Max. 25.0 A / 1000 V
Fuse Rating (-FS Version)
Max. 12.0 A / 1000 V
Output
AC Grid Connection Type
Three phase 3W or 4W+PE
Rated AC Power (Pacr)
6000 W
8000 W
10000 W
12500 W
Maximum AC Output Power (Pac max)
6600 W (6)
8900 W (1)
11000 W (2)
13800 W (3)
Rated AC Grid Voltage (Vacr)
400 V
AC Voltage Range
320...480 Vac (4)
Maximum AC Output Current (Iac max)
10.0 A
13.0 A
16.6 A
20.0 A
Inrush Current
Negligible
Maximum Output Fault Current
<25Arms (100mS)
Rated Output Frequency (fr)
50 Hz / 60 Hz
Output Frequency Range (fmin...fmax)
47...53 / 57...63 Hz (5)
Nominal Power Factor (Cosphiacr)
>0.995 (adj. ± 0.9
with Pacr= 8.0 kW,
± 0.8 with max 6.67kVA)
>0.995 (adj. ± 0.9
with Pacr= 8.0 kW,
± 0.8 with max 8.9kVA)
>0.995 (adj. ± 0.9
with Pacr= 10.0 kW,
± 0.8 with max 11.5kVA)
>0.995 (adj. ± 0.9
with Pacr= 12.5 kW,
± 0.8 with max 13.8kVA)
Total Harmonic Distortion of Current
< 2%
AC Connection Type
Screw terminal block
Output protection
Anti-Islanding Protection
According to local standard
Maximum AC Overcurrent Protection
12.0 A
15.0 A
19.0 A
22.0 A
Output Overvoltage Protection - Varistor
3, plus gas arrester
Operating performance
Maximum Efficiency (ηmax)
97.6%
97.6%
97.8%
97.8%
Weighted Efficiency (EURO/CEC)
96.5% /-
96.8% /-
97.1% /-
97.2% /-
Power Input Treshold
30.0 W
Stand-by Consumption
< 10.0 W
Communication
Wired Local Monitoring
PVI-USB-RS232_485 (opt.), PVI-DESKTOP (opt.)
Remote Monitoring
PVI-AEC-EVO (opt.), VSN700 Data Logger(opt.)
Wireless Local Monitoring
PVI-DESKTOP (opt.) with PVI-RADIOMODULE (opt.)
User Interface
LCD Display with 16 characters x 2 line
Environmental
Ambient Temperature Range
-25...+60°C /-13...140°F
with derating above 55°C/131°F
-25...+60°C /-13...140°F with
derating above 50°C/122°F
Storage Temperature
-40...80°C (-40...+176°F)
Relative Humidity
0...100% condensing
Environmental pollution classification for external environment
3
Noise Emission
< 50 dB(A) @ 1 m
Maximum Operating Altitude without Derating
2000 m / 6560 ft
Environmental Category
External
Physical
Environmental Protection Rating
IP 65
Cooling
Natural
Dimension (H x W x D)
716 x 645 x 224 mm / 28.2 x 25.4 x 8.8 inch
Weight
<41 kg / 90.4 lb
Mounting System
Wall bracket
Overvoltage Category in accordance with IEC 62109-1
II (DC input) III (AC output)
Safety
Isolation Level
Transformerless (TL)
Safety Class
I
Marking
CE (50Hz only)
1. Limited to 8000 W for Germany
2. Limited to 10000 W for Belgium and Germany
3. Limited to 12500 W for Germany
4. The AC voltage range may vary depending on specific country grid standard
5. The Frequency range may vary depending on specific country grid standard
6. Limited to 6000 W for Germany
Remark. Features not specifically listed in the present data sheet are not included in the product