NMX24-LON
LonWorks®, Non-Spring Return, 24 V
Torque min. 90 in-lb for control of damper surfaces up to 22 sq ft.
Application
Direct coupled actuators for direct link to LonWorks network. Actuators are easily
installed by direct shaft mounting on air dampers in ventilation and air conditioning
systems. Actuator can be controlled by any compatible LON controller or automation
system.
For proportional modulation of dampers in HVAC systems. Actuator sizing should be
done in accordance with the damper manufacturer’s specifications.
The actuator is mounted directly to a damper shaft up to 1.05" in diameter by means
of its universal clamp, 1/2” self centered default. A crank arm and several mounting
brackets are available for applications where the actuator cannot be direct coupled to
the damper shaft.
Operation
The actuator is not provided with and does not require any limit switches, but is
electronically protected against overload. The anti-rotation strap supplied with the
actuator will prevent lateral movement.
The NMX24-LON series provides 95° of rotation and a visual indicator indicates
position of the actuator. When reaching the damper or actuator end position, the
actuator automatically stops. The gears can be manually disengaged with a button on
the actuator cover.
The NMX24-LON actuators use a brushless DC motor, which is controlled by an
Application Specific Integrated Circuit (ASIC). The ASIC monitors and controls the
actuator’s rotation and provides a digital rotation sensing (DRS) function to prevent
damage to the actuator in a stall condition. Power consumption is reduced in holding
mode.
Add-on auxiliary switches or feedback potentiometers are easily fastened directly onto
the actuator body for signaling and switching functions.
Dimensions (Inches [mm])
0.98" [25]
4.74" [120.4]
3.66" [93]
2" [50.8]
2.42" [61.4]
3.15" [80]
7.7" [196.2]
1/2” to 1.05” [12.7 to 26.67]
2/5” to 1.05” [10 to 26.67]
D142
Technical Data
NMX24-LON
Power supply
24 VAC ± 20% 50/60 Hz
24 VDC ± 10%
Power consumption
3.5 W (1.3 W)
Transformer sizing
6 VA (Class 2 power source)
Electrical connection
18 GA plenum rated cable
1/2” conduit connector
protected NEMA 2 (IP54)
3 ft [1m]
Overload protection
electronic throughout 0 to 95° rotation
Angle of rotation
max. 95°, adjustable with mechanical stop
electronically variable
Torque
90 in-lb [10 Nm]
Direction of rotation
reversible with
switch
Position indication
reflective visual indicator (snap-on)
Manual override
external push button
Running time
150 seconds (default)
Humidity
5 to 95% RH non condensing (EN 60730-1)
Ambient temperature
-22°F to 122°F [-30°C to 50°C]
Storage temperature
-40°F to 176°F [-40°C to 80°C]
Housing
NEMA 2, IP54, UL enclosure type 2
Housing material
UL94-5VA
Agency listings†
cULus acc. to UL 60730-1A/-2-14,
CAN/CSA E60730-1:02,
CE acc. to 2004/108/EEC and 2006/95/EC
Noise level
<45dB(A)
Servicing
maintenance free
Quality standard
ISO 9001
Weight
2.1 lbs [0.95 kg]
† Rated Impulse Voltage 800V, Type of action 1, Control Pollution Degree 3.
LonWorks®
Certified
according to LonMARK® 3.3
Processor
Neuron 3120
Transceiver
FTT-10A, compatible with LPT-10
Functional profile
according to LonMARK® Damper
actuator object #8110
open loop sensor object #1
LNS plug-in for actuator/sensor can be run with any LNS based integration
tool (min. for LNS 3.x)
Service button and status LED
according to LonMARK® guidelines
Conductors, cables
conductor lengths, cable specifications and
topology of the LonWorks® network according to
the Echelon® directives
LonWorks and LonMARK © 2007-2009 LonMark International
M40024 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
276
Accessories
K-NA
Reversible Clamp
ZG-100
Universal Mounting Bracket
ZG-101
Universal Mounting Bracket
ZG-103
Universal Mounting Bracket
ZG-104
Universal Mounting Bracket
ZG-NMA
Crank arm Adaptor Kit
AV8-25
Universal Shaft Extension
ZG-NMSA-1
Shaft Adaptor
ZS-100
Weather Shield - Steel
ZS-150
Weather Shield - Polycarbonate
Tool-06
8 mm & 10 mm Wrench
S1A, S2A
Auxiliary Switch (es)
P370
Shaft Mount Auxiliary Switch
P…A
Feedback Potentiometers
SGA24
Min positioners in NEMA 4 housing
SGF24
Min positioners for flush panel mounting
ADS-100
Analog to Digital Switch
NSV24 US
Battery Back-Up Module
ZG-X40
Transformer
NOTE: When using NMX24-LON actuators, only use accessories listed on this page.
Typical Specification
Proportional control damper actuators shall be electronic direct-coupled type, which
require no crank arm and linkage and be capable of direct mounting to a shaft up to
1.05” diameter. Actuators shall have brushless DC motor technology and be protected
from overload at all angles of rotation. Actuators shall have reversing switch and
manual override on the cover. Run time shall be constant and independent of torque.
Actuators shall be cULus listed, have a 5-year warranty, and be manufactured under
ISO 9001 International Quality Control Standards. Actuators shall be as manufactured
by Belimo.
Wiring Diagrams
V
Possible connection of a
voltmeter for checking
the position feedback U.
5
6
7
3
2
1
MFT
LON
LON
T
~
+
–
T
~
+
–
V
Schema_LON_01
Connection without Sensor
NMX24-LON
LonWorks®, Non-Spring Return, 24 V
5
6
7
3
2
1
MFT
LON
LON
T
~
+
–
T
~
+
–
Sensor scaling:
The sensors can be scaled with the sensor plug-in (sensor table).
Sensor
Temperature range
Resistance range
Resolution
Ni1000
–28 ... +98°C
850 ... 1600 Ω
1 Ω
PT1000
–35 ... +155°C
850 ... 1600 Ω
1 Ω
NTC
–10 ... +160°C
(depending on type)
200 ... 60 kΩ
1 Ω
Schema_LON_02
Connection with Passive Sensor, e.g. Pt1000, Ni1000, NTC
5
6
7
3
2
1
MFT
LON
LON
T
~
+
–
T
~
+
–
Requirements for
switching contact:
The switching contact must be
able to accurately switch a cur-
rent of 16 mA @ 24 V.
Schema_LON_03
Connection with Switching Contact, e.g. Δp-monitor
5
6
7
3
2
1
MFT
LON
LON
T
~
+
–
T
~
+
–
Possible input voltage range:
0 ... 32 V (resolution 30 mV)
Sensor scaling:
The sensors can be scaled with the
sensor plug-in (sensor table)
Schema_LON_04
Connection with Active Sensor, e.g. 0...10 V @ 0...50° C
M40024 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
277
NMX24-LON
LonWorks®, Non-Spring Return, 24 V
Node object #0
The node object contains the object status and object request functions.
nviRequest
SNVT_obj_request
Input variable for requesting the status of a particular object in the node.
nvoStatus
SNVT_obj_status
Output variable that outputs the current status of a particular object in the node.
nvoFileDirectory
SNVT_address
Output variable that shows information in the address range of the Neuron chip.
Damper actuator object #8110
The actuator object is used to map the functions of the MP actuators to the
LONWORKS® network.
nviRelStpt
SNVT_lev_percent
The nominal position is assigned to the actuator via this input variable. This variable is
normally linked to the output variable of an HVAC controller.
nviActuateState
SNVT_switch
A preset position is assigned to the actuator via this input variable. Note on priority:
The last variable that was active, either nviActuatorState or nviRelStpt, has priority.
nviManOvrd
SNVT_hvac_overid
These input variables can be used to manually override the actuator into a particular
position.
nvoActualValue
SNVT_lev_percent
This output variable shows the current actual position of the actuator and can be used
for control circuit feedback or for displaying positions.
nvoAbsAngle
SNVT_angle_deg
This output variable shows the current angle of rotation of the actuator
or the valve and can be used to display the position or for service purposes.
nvoAbsAirFlow
SNVT_flow
This output variable is inactive with the SR24ALON-5 rotary actuator and shows a
constant value of 65535 (this variable is only active in conjunction with LON-capable
VAV controllers).
Open loop sensor object #1
A sensor can be connected to the rotary actuator. A passive resistance sensor (e.g.
Ni1000), an active sensor (output 0 ... 32 V) or a switch (on/off) can be connected. The
open loop sensor object transfers the measured sensor values to the LONWORKS®
network.
nvoSensorValue
SNVT_xxx
This output variable shows the current sensor value. Depending on the connected
sensor, the output variable can be configured via the sensor plug-in and specifically
adapted to the system.
The SNVT_... can be configured as:
SNVT_temp_p
SNVT_lev_percent
SNVT_lux
SNVT_temp
SNVT_abs_humid
SNVT_press_p
SNVT_switch
SNVT_enthalpy
SNVT_smo_obscur
SNVT_flow
SNVT_ppm
SNVT_power
SNVT_flow_p
SNVT_rpm
SNVT_elec_kwh
Notes
Detailed information on the functional profiles can be found on the website of
LonMARK®
K (www.lonmark.org).
Functional Profile according to LonMARK®
K
The LON-capable damper actuator is certified by LonMARK®. The actuator functions
are supplied with the LonWorks® network as standardized network variables
according to LonMARK®. The Node Object #0, the Damper Actuator Object #8110
and the Open Loop SensorObject #1 are implemented in the actuator.
M40024 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
278
NMX24-LON
LonWorks®, Non-Spring Return, 24 V
1
Direction of rotation switch
Switching over
Direction of rotation changes
2
Pushbutton and green LED display
Off
No voltage supply or malfunction
Green, on
Operation
Press button
Switches on angle of rotation adaption followed
by standard operation
3
Service button for commissioning LONWORKS® and
yellow LED display for the LON status
Off
The SR24ALON-5 rotary actuator is connected
and ready for operation in the
LONWORKS®network.
Yellow, on
No application software is loaded in the
SR24ALON-5.
Yellow, flashing
(flashing interval 2 seconds)
The SR24ALON-5 is ready for operation but not
integrated in the LONWORKS® network
(unconfigured).
Other flashing codes
A fault is present in the SR24ALON-5.
Press button
Service Pin Message is sent to the
LONWORKS®network.
4
Gear disengagement switch
Press button
Gear disengaged, motor stops, manual operation
possible
Release button
Gear engaged, synchronisation starts, followed
by standard operation
5
Service plug
For connecting MFT parameterizing and service tools
1
2
3
4
5
M40024 - 05/10 - Subject to change. © Belimo Aircontrols (USA), Inc.