Installation Instructions
Multiplex Photoelectric
Duct Smoke Detector
D7050DH
D7050DH | Installation Instructions | 1.0 Description
2
Bosch Security Systems, Inc. | 9/06 | 49325E
Notices
These instructions cover the installation of the
D7050DH Multiplex Photoelectric Duct Smoke
Detector on a D7024 or a DS9400M 24 VDC Fire
Alarm Control Panel (FACP) with a D7039 or DS9431
Multiplex Expansion Module installed. The D7024 and
DS9400M requires ROM version 2.0 or greater.
Install, test, and maintain the D7050DH according to
these instructions, NFPA 72, local codes, and authority
having jurisdiction (AHJ).
Follow the procedures in these instructions
to avoid personal injury and damage to the
equipment. Failure to follow these
instructions can result in the D7050DH not
operating properly. Bosch is not
responsible for improperly installed, tested,
or maintained devices.
The D7050DH complies with Part 15 of the Federal
Communications Commission (FCC) Rules and with
the RSS-210 of Industry and Science Canada.
D7050DH operation is subject to the following two
conditions:
1. It does not cause harmful interference.
2. It must accept any interference it receives,
including interference that might cause undesirable
operation.
1.0 Description
The D7050DH (Figure 1) is Underwriters Laboratories,
Inc. (UL) Listed and requires a D343 Duct Detector
Housing. Use this detector with the D7024 or a
DS9400M that includes a D7039 or DS9431 Multiplex
Expansion Module.
An LED indicator on the head flashes every 3 to 8 sec
to ensure the D7050DH has power and the smoke
sampling circuitry functions. This LED flashes at least
once each second during an alarm confirming
individual detector alarms. The D7050DH
automatically resets after the alarm condition clears.
2.0 Installation
For installation details, refer to the D7024 FACP
Operation and Installation Guide (P/N: 31499), the
D9400M Reference Guide (P/N: 44578), the D7039
Installation Guide (P/N: 38685), or the DS9431
Installation Instructions (P/N: 41381).
Do not exceed the maximum line resistance
of 50Ω.
Figure 1:
D7050DH
4 in.
(10.2 cm)
1.5 in.
(3.8 cm)
1
2
3
4
5
6
1 - Side view
2 - Top view
3 - Alarm/Test LED
4 - Magnetic test locator
5 - Calibration voltage pins
6 - Tamper screw hole
Table 1: Maximum Wire Length Allowed for
each Multiplex Bus
Wire Gauge
Maximum 50 Ω for each
Bus Loop
18 AWG (1.02 mm)
3800 ft (1170 m)
16 AWG (1.29 mm)
5950 ft (1810 m)
14 AWG (1.63 mm)
5950 ft (1810 m)
12 AWG (2.05 mm)
5950 ft (1810 m)
Table 2: Maximum Number of Detectors
Allowed for each Multiplex Bus
With Remote Test
40
With Remote LED
50
Without Annunciator
70
Do not use shielded cable.
D7050DH | Installation Instructions | 3.0
Wiring the D343
.
Bosch Security Systems, Inc. | 9/06 | 49325E
3
3.0 Wiring the D343
You can wire the D343 in series as shown in Figure 2.
Figure 2:
Wiring the D343 Duct Housing
(-)
Tamper
Disable
Reset
Disable
14 13 12 11 10 9
1
2
3
4
5
6
7
8
B
B
R
L
R
E
K
N
D
B
L
U
G
R
N
Y
E
L
O
R
N
Tamper
Disable
Reset
Disable
14 13 12 11 1 0 9
1
2
3
4
5
6
7
8
B
B
R
L
R
E
K
N
D
B
L
U
G
R
N
Y
E
L
O
R
N
(+)
1
2
1 - Input output module for the D7039 or DS9431
2 - Multiplex bus connections
4.0 Setting the Address
Set the D7050DH address before
connecting to the control panel and
applying power. The address number is the
same as the input point or zone number.
Set the D7050DH’s address using a flat-blade
screwdriver to position the rotary switches
(Figure 3) located on the back. Note that the switches
click when turned.
The valid address range is from 009 to 255. Refer to
the D7024 Operation and Installation Guide (P/N: 31499)
or the DS9400M Reference Guide (P/N: 44578) for
additional address limitations.
Figure 3:
Setting the D7050DH Address
0
5
1
2
3
4
6
7
8
9
0
5
1
2
3
4
6
7
8
9
0
2
1
2
0
1
A
B
1
2
3
1 - Hundreds 2 - Tens 3 - Ones
A = D7024 FACP, B = DS9400 FACP
For example:
0 hundreds, 9 tens, 5 ones = Address 95 on
the D7024 FACP
The A address range works on the D7039
Multiplex Expansion Module with the
D7024 FACP. The B address range works
on the DS9431 Multiplex Expansion
Module with the DS9400M FACP.
Figure 3 shows the A address range set at 095, allowing
the D7039 to work with the D7024 FACP.
5.0 Mounting
1. Remove the tamper screw located in the recess
on the top of the dust cover.
2. Remove the dust cover.
3. Mount and wire the duct housing according to the
D343 Installation Instructions (P/N: 48199).
4. Mount the D7050DH to the base by turning it
clockwise until it clicks into place (Figure 4).
Figure 4:
Mounting the D7050DH on the Base
+1
R2
3-
1
2
2
1 - Base contacts (three sets)
2 - Set detector contact here and rotate clockwise
The detector is keyed. Do not force the
detector onto the base.
D7050DH | Installation Instructions | 6.0 Programming
4
Bosch Security Systems, Inc. | 9/06 | 49325E
6.0 Programming
For multiplex programming, refer to the D7024 FACP
Operation and Installation Guide (P/N: 31499) or the
DS9400M Reference Guide (P/N: 44578).
7.0 Testing
Test detection devices immediately after installation.
Test the D7050DH according to NFPA Chapter 7-1.6.2
(1999) or more often as required by local code.
7.1
Operational Testing
Notify all concerned parties before and
after completing maintenance on or testing
the
fire alarm system.
1. Apply power to the system and check for alarms.
2. If a D7050DH is in alarm, shut down the system.
3. Remove the D7050DH and recheck for proper
wiring. If the problems persist, replace the affected
D7050DH or exchange it with a known good
detector. This determines if the problem is caused
by the D7050DH.
4. When the system is free of alarms, check each
D7050DH to ensure the red LED indicator on the
head flashes. This confirms the detector is
operating properly.
5. Test each D7050DH to ensure it causes a control
panel alarm.
6. Alarm the D7050DH by doing one of the
following:
a. Place a magnet horizontally against the recess
in the duct cover, centering it over the “T”
marked on the head to activate an internal
reed switch.
b. Remove the duct cover and use a UL Listed
aerosol smoke detector tester such as the
Home Safeguard Industries’ 25S to simulate
an alarm. Follow the instructions included in
the aerosol smoke detector tester.
7. When a D7050DH alarms, the red LED indicator
on the head flashes at least once per second. Clear
the alarm by initiating a system reset before
proceeding to the next detector.
7.2
Sensitivity Testing
Calibration is important in determining a
detector’s continued operation. Depending
on local regulations, calibration testing
might be required more than once a year.
According to NFPA72, perform a
Calibration Test at installation and every
other year thereafter. Perform a Functional
Test monthly.
Test the D7050DH’s sensitivity to meet NFPA 72
requirements by conducting a Magnet Test (refer to
Section 7.3 Magnet Test). You can also test sensitivity by
measuring the calibration voltage pins with D1005 Test
Cable, D344-RL, or D344-RT (refer to Section 7.4
Voltage Measurement Test). Calibration can be quickly
determined by visually inspecting the D7050DH’s LED
(refer to Section 7.2.2 Visual Check). These tests confirm
whether or not the detector is within its factory marked
calibration range.
7.2.1
Sensitivity Test
The control panel constantly monitors the D7050DH.
If the detector exceeds the limits of the sensitivity
thresholds, the control panel reports the detector in
question and generates a fault condition.
7.2.2
Visual Check
The D7050DH includes the Chamber Check
Automatic Trouble Indication that allows it to
automatically show if its calibration is out of the
factory-listed range. You can meet the NFPA guidelines
for sensitivity testing by visually inspecting the
D7050DH and checking the Alarm LED flash rate.
If the calibration is out of range during power up or
longer than 24 h, the Alarm LED double flashes. This
LED single flashes when the detector is operating
normally.
Visually check all detectors before
disconnecting the multiplex bus.
Disconnecting the bus erases the
calibration indication. If the detector was
disconnected or the control panel lost
power within the
last 24 h, perform a Magnet Test or Voltage
Measurement Test to confirm sensitivity.