Installation, start-up and service instructions manual [PDF] (48 pages)
- Updated: 14.06.2026
Document Preview & Text Transcription
1
38AUD
Air Cooled Condensing Units
50 Hz
With PuronR (R---410A) Refrigerant
Sizes 16---25
Installation, Start---Up
and Service Instructions
CONTENTS
SAFETY CONSIDERATIONS
2
. . . . . . . . . . . . . . . . . . . .
INSTALLATION GUIDELINES
2
. . . . . . . . . . . . . . . . . .
Replacement/Retrofit — R--22 to Puron
2
. . . . . . . . . . .
INSTALLATION
8--18
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Jobsite Survey
8
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1 -- Plan for Unit Location
9
. . . . . . . . . . . . . . . . . .
Step 2 -- Complete Pre--Installation Checks
9
. . . . . . . . .
Step 3 – Prepare Unit Mounting Support
9
. . . . . . . . . . .
Step 4 – Rig and Mount the Unit
9
. . . . . . . . . . . . . . . . .
Step 5 – Complete Refrigerant Piping Connections
10
. .
Step 6 – Install Accessories
15
. . . . . . . . . . . . . . . . . . . .
Step 7 – Complete Electrical Connections
15
. . . . . . . . .
PRE-START-UP
19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Check
19
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Turn On Crankcase Heater
19
. . . . . . . . . . . . . . . . . . . . .
Preliminary Charge
19
. . . . . . . . . . . . . . . . . . . . . . . . . . .
START--UP
19--25
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preliminary Checks
19
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Start Unit
20
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
OPERATING SEQUENCE
26
. . . . . . . . . . . . . . . . . . . . . .
Indoor (Supply) Fan
26
. . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling, Unit Without Economizer
26
. . . . . . . . . . . . . .
Cooling, Unit With Economizer
26
. . . . . . . . . . . . . . . . .
Heating
26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ROUTINE SYSTEM MAINTENANCE
27
. . . . . . . . . . . .
Quarterly Inspection
(and 30 days after initial start)
27
. . . . . . . . . . . . . . . . . .
Seasonal Maintenance
27
. . . . . . . . . . . . . . . . . . . . . . . .
SERVICE
27--37
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Refrigeration System
27
. . . . . . . . . . . . . . . . . . . . . . . . .
Compressor Oil
27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Servicing Systems on Roofs with
Synthetic Materials
27
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Liquid Line Filter Drier
28
. . . . . . . . . . . . . . . . . . . . . . .
Field Refrigerant Access Ports
28
. . . . . . . . . . . . . . . . . .
Factory High--Flow Access Ports
28
. . . . . . . . . . . . . . . .
Comfort Alert Diagnostic Module
29
. . . . . . . . . . . . . . .
Compressor Protection
31
. . . . . . . . . . . . . . . . . . . . . . . .
Crankcase Heater
31
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low--Pressure Switch
31
. . . . . . . . . . . . . . . . . . . . . . . . .
High--Pressure Switch
31
. . . . . . . . . . . . . . . . . . . . . . . . .
Outdoor Fans
31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Lubrication
31
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coil Type Identification
35
. . . . . . . . . . . . . . . . . . . . . . .
NOVATIONtCoil Cleaning and Maintenance
35
. . . . .
Repairing NOVATION Condenser Tube Leaks
35
. . . . .
Replacing NOVATION Condenser Coil
36
. . . . . . . . . . .
Routine Cleaning of Round-Tube Plate Fin
(RTPF) Coils
36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fastener Torque Values
37
. . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING
37--38
. . . . . . . . . . . . . . . . . . . . . .
APPENDIX A
Air Conditioner & Heat Pump with PuronR —
Quick Reference Guide
39
. . . . . . . . . . . . . . . . . . . . . . . .
APPENDIX B
Wiring Diagram List
39
. . . . . . . . . . . . . . . . . . . . . . . . . .
APPENDIX C
Low Ambient Option — Factory Installed
40
. . . . . . . . .
START--UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . 47--48
2
SAFETY CONSIDERATIONS
Improper
installation,
adjustment,
alteration,
service,
maintenance, or use can cause explosion, fire, electrical
shock or other conditions which may cause personal
injury or property damage. Consult a qualified installer,
service
agency,
or
your
distributor
or
branch
for
information or assistance. The qualified installer or
agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual
instructions package
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloths for brazing operations and
have a fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the
unit.
Consult
local
building
codes
for
special
requirements.
In
absence
of
local
codes,
it
is
recommended that the USA standard ANSI/NFPA 70,
National Electrical Code (NEC), be followed.
It is important to recognize safety information. This is the
safety--alert symbol
. When you see this symbol on the
unit and in instructions or manuals, be alert to the
potential for personal injury.
Understand the signal words DANGER, WARNING,
CAUTION, and NOTE. These words are used with the
safety-alert symbol. DANGER identifies the most serious
hazards which will result in severe personal injury or
death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify
unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause in personal
injury or death.
Before performing service or maintenance operations
on unit, always turn off main power switch to unit and
install lockout tag. Unit may have more than one
power switch.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause in personal
injury,death and/or equipment damage.
PuronR (R--410A) refrigerant systems
operate at
higher pressures than standard R--22 systems. Do not
use R--22 service equipment or components on Puron
refrigerant equipment.
!
WARNING
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could cause in personal
injury or death.
Relieve pressure and recover all refrigerant before
system repair or final unit disposal.
Wear
safety
glasses
and
gloves
when
handling
refrigerants. Keep torches and other ignition sources
away from refrigerants and oils.
!
WARNING
CUT HAZARD
Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use
care and wear appropriate protective clothing, safety
glasses and gloves when handling parts and servicing
38AUD units.
CAUTION
!
INSTALLATION GUIDELINE
Replacement /Retrofit — R--22 to PuronR
Replacement/retrofit installations require change-out of
outdoor
unit,
metering
device,
and
filter
driers.
Change-out
of
indoor
coil
(evaporator)
and
interconnecting tubing is recommended.
Existing evaporator coil – If the existing evaporator coil
may be re-used, check with the coil manufacturer to verify
the coil construction is suitable for operation with the
higher pressures of PuronR (R-410A). Also determine if
the existing TXV valve is compatible with R-410A,
replace if necessary. The minimum factory test pressure
rating must be 1725 kPa (250 psig). Existing coil will
need to be purged with Nitrogen to remove as much
mineral oil as possible to eliminate cross contamination of
oils.
Acid test – If the existing system is being replaced
because of a compressor electrical failure, assume acid is
in system. If system is being replaced for any other
reason, use an approved acid test kit to determine acid
level. If even low levels of acid are detected, install a 100
percent activated alumina suction-line filter drier in
addition
to
the
replacement
liquid-line
filter
drier.
Remove the suction line filter drier as soon as possible,
with a maximum of 72 hr of operation. Recommendation:
Install a ball valve in the liquid line at the filter drier
location when installing a suction filter in the suction line.
Existing refrigeration piping – Reuse of existing refrigerant
piping involves three issues: quality (strength) of existing
tubing, cleanliness and tube size. Inspect all tube segments
and joints for signs of damage, corrosion or poor brazing.
Flush the interconnecting piping system with dry Nitrogen to
eliminate as much trace of mineral oil as possible.
38AUD
3
Same tube sizes are capable of handling higher flowrates
(expressed
as
tons
of
cooling
capacity)
with
Puron
refrigerant compared to R--22 at constant pressure drops.
For example, a 1/2--inch OD liquid line is rated at 33%
higher tons with PuronR than with R--22 (at 5_F pressure
drop). A 1 1/8--inch OD suction line is rated at 53% higher
tons with Puron than with R--22 (at 2_F pressure drop).
Refrigeration lines selected for R--22 use are typically
oversized for Puron
applications. Carefully
check the
existing suction line size against the table for maximum size
(see Table 5); replace vertical riser segments if necessary.
Check existing liquid line size against sizing data in Table 4;
replace with smaller lines when feasible.
Installation –
1. Remove the existing evaporator coil or fan coil and
install the replacement coil when appropriate.
2. Drain oil from low points and traps in suction line
tubing (and hot gas bypass tubing if appropriate) and
evaporator if they were not replaced. Removing oil
from evaporator coil may require purging of the
tubing with dry nitrogen.
3. Unless indoor unit is equipped with a Puron ap-
proved metering device, change the metering device
to a thermal expansion valve (TXV) designed for
PuronR (R-410A).
4. Remove the existing outdoor unit. Install the new out-
door unit according to these installation instructions.
5. Install a new field-supplied liquid-line filter drier at
the indoor coil just upstream of the TXV or fix orifice
metering device.
6. If a suction line filter drier is also to be installed, in-
stall suction line drier downstream of suction line ser-
vice valve at condensing unit.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never install suction--line filter drier in the liquid--line
of a PuronR system.
CAUTION
!
7. If required, install a 100% activated alumina suction
line filter drier at the outdoor unit.
8. Evacuate and charge the system according to the in-
structions in this installation manual.
9. Operate the system for 10 hr. Monitor the pressure
drop across the suction line filter drier. If pressure
drop exceeds 21kPa (3 psig), replace suction-line and
liquid-line filter driers. Be sure to purge system with
dry nitrogen and evacuate when replacing filter
driers. Continue to monitor the pressure drop across
suction-line filter drier. Repeat filter changes is neces-
sary. Never leave suction-line filter drier in system
longer than 72 hr (actual time).
38AUD