Manual [PDF] (59 pages)
- Brand: CLIVET
- Model: TALK
- Format: PDF
- Key Aspects: Information on Regular Maintenance, Unpacking and Inspection Guidelines, Standard Operating Procedures
- Updated: 09.09.2026
- Source File: 1862790.pdf
- Pages: 59
- Description: Quick start guide for the CLIVET TALK.
Document Preview & Text Transcription
Data creazione 10/09/03
DS03I009GB--00
Pagina 1 di 59
CONTROLLER MANUAL
SPINCHILLER C.D.A
Data creazione 10/09/03
DS03I009GB--00
Pagina 2 di 59
SUMMARY
CLIVET TALK LOCAL INTERFACE................................................................................................................. 3
DESCRIPTION OF THE BUTTONS ................................................................................................................................4
DESCRIPTION OF THE MAIN SCREEN.........................................................................................................................5
SYSTEM COMPOSITION.................................................................................................................................. 6
CENTRAL MODULE CLIVETTALK.LOCAL.M1...............................................................................................................6
DESCRIPTION OF THE JUMPERS.............................................................................................................................7
I/O CLIVETTALK.LOCAL.M1 .......................................................................................................................................7
EVAPORATOR MODULE CLIVETTALK.LOCAL.EX1.....................................................................................................9
DESCRIPTION OF THE JUMPERS.............................................................................................................................9
I/O CLIVETTALK.LOCAL.EX1....................................................................................................................................10
TANDEM COMPRESSOR MODULE CLIVETTALK.LOCAL.C2....................................................................................11
TRIO COMPRESSOR MODULE CLIVETTALK.LOCAL.C3...........................................................................................11
DESCRIPTION OF THE JUMPERS...........................................................................................................................11
CLIVETTALK.LOCAL.C2 AND CLIVETTALK.LOCAL.C3 ..........................................................................................12
INITIALISING THE MODULES ....................................................................................................................... 13
BASIC RULES FOR CONFIGURATION........................................................................................................................13
SETTING THE HARDWARE ADDRESS....................................................................................................................13
SETTING THE SOFTWARE ADDRESS ....................................................................................................................14
SETTING THE HARDWARE ADDRESS OF THE CENTRAL MODULE....................................................................15
SETTING THE HARDWARE ADDRESS OF THE EVAPORATOR MODULE ...........................................................15
SETTING THE HARDWARE ADDRESS OF THE TRIO AND TANDEM MODULES.................................................15
TABLE FOR SETTING THE HARDWARE ADDRESS...............................................................................................16
LOCAL INTERFACE ADDRESS .................................................................................................................... 17
REMOTE INTERFACE ADDRESS ................................................................................................................................17
CONFIGURATION EXAMPLE ........................................................................................................................ 18
SETTING THE HARDWARE ADDRESS .......................................................................................................................18
SETTING THE SOFTWARE ADDRESS........................................................................................................................19
PARAMETER MENU TREE ............................................................................................................................ 20
OPERATING STATUS MENU TREE.............................................................................................................................39
GENERAL UNIT STATUS MENU..................................................................................................................................40
LIST OF ALARMS........................................................................................................................................... 42
CENTRAL MODULE ALARMS ......................................................................................................................................42
COMPRESSOR MODULE ALARMS .............................................................................................................................43
EVAPORATOR MODULE ALARMS ..............................................................................................................................44
OPERATION OF THE TEMPERATURE CONTROLLER............................................................................... 45
COOLING ......................................................................................................................................................................45
DETERMINING THE TEMPERATURE DIFFERENCE FOR EACH COMPRESSOR ................................................45
FREECOOLING .........................................................................................................................................................46
HEATING.......................................................................................................................................................................51
DETERMINING THE TEMPERATURE DIFFERENCE FOR EACH COMPRESSOR ................................................51
STEP ACTIVATION – SCAN TIMES .............................................................................................................. 52
STEP DEACTIVATION ..................................................................................................................................................52
COMPENSATION............................................................................................................................................ 52
SET POINT CORRECTION IN COOLING ...................................................................................................... 53
SET POINT CORRECTION IN HEATING....................................................................................................... 54
SECOND SET POINT FROM DIGITAL INPUT............................................................................................... 55
DEMAND LIMIT............................................................................................................................................... 56
MAINTENANCE SET POINT .......................................................................................................................... 58
RESOURCE MANAGEMENT ALGORITHM .................................................................................................. 59
BALANCING OF THE CAPACITY DELIVERED............................................................................................................59
Data creazione 10/09/03
DS03I009GB--00
Pagina 3 di 59
CLIVET TALK LOCAL INTERFACE
Figure 1
Clivet code C5110612
Figure 1 represents the layout of the control keypad corresponding to the ClivetTalk modular control system.
The functions of the buttons and the meaning of the configuration screens are described below.
Data creazione 10/09/03
DS03I009GB--00
Pagina 4 di 59
DESCRIPTION OF THE BUTTONS
F1
F4
F3
F2
?
ESC
I
HOME
ALARM
MODE
SETUP
STATE
ON
C O O L
STEP:
03 / 12
15 / 02 / 03 08:03:51
7.0
°C SET
9.3
°C OUT
12.2
°C IN
2
7
3
1
4
6
8
5
9
NUMBER
SYMBOL
MEANING
1
LED = on when unit ON
LED = off when unit OFF
2
I
“ON-OFF” button: holding this for at least 3 seconds turns the unit on or off
3
F1
F1 = Button that runs the associated function indicated in bold, “MODE”
4
?
“HELP” button: depending on the menu selected, pressing this button provides
brief descriptions to help the user interpret the parameters, status variables and
alarms
5
F2
F2 = Button that runs the associated function indicated in bold, “ALARM”
6
ESC
“ESC” key: when navigating the menus, this key can be used to go back to the
previous screen
7
F3
F3 = Button that runs the associated function indicated in bold, “SETUP”
8
HOME
“HOME” button: during navigation, returns to the main menu from any screen
9
F4
F4 = Button that runs the associated function indicated in bold, “STATE”