IB01602046E
For more information visit: www.eaton.com
O & M Manual for 2-Position Contactor
Based Non-Automatic Transfer Switch
Instruction Booklet
Description
Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Receiving, Handling, and Storage . . . . . . . . . . . . . . . . . . . 6
Equipment Description . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installation and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Testing and Problem Solving . . . . . . . . . . . . . . . . . . . . . . .17
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Renewal Parts Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Non-Automatic Transfer Switch Quick Start Instructions . . .20
For more information visit: www.eaton.com
IB01602046E
Instruction Booklet
Page 2
Effective: July 2010
2-Position Contactor Based
Non-Automatic Transfer Switch
READ AND UNDERSTAND THE INSTRUCTIONS CONTAINED HEREIN-
AFTER BEFORE ATTEMPTING TO UNPACK, ASSEMBLE, OPERATE,
OR MAINTAIN THIS EQUIPMENT.
HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH
ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL
INJURY. FOLLOW PROPER INSTALLATION, OPERATION, AND MAIN-
TENANCE PROCEDURES TO AVOID THESE VOLTAGES.
TRANSFER SWITCH EQUIPMENT COVERED BY THIS INSTRUCTION
BOOK IS DESIGNED AND TESTED TO OPERATE WITHIN ITS NAME-
PLATE RATINGS. OPERATION OUTSIDE OF THESE RATINGS MAY
CAUSE THE EQUIPMENT TO FAIL RESULTING IN DEATH, SERIOUS
BODILY INJURY, AND/OR PROPERTY DAMAGE. ALL RESPONSIBLE
PERSONNEL SHOULD LOCATE THE DOOR MOUNTED EQUIPMENT
NAMEPLATE AND BE FAMILIAR WITH THE INFORMATION PROVIDED
ON THE NAMEPLATE. A TYPICAL EQUIPMENT NAMEPLATE IS
SHOWN IN FIGURE 1.
Figure 1. Typical Non-Automatic Transfer Switch Equipment
Nameplate.
All possible contingencies that may arise during installation, oper-
ation, or maintenance, and all details and variations of this equip-
ment do no purport to be covered by these instructions. If further
information is desired by the purchaser regarding a particular
installation, operation, or maintenance of particular equipment,
please contact an authorized Eaton Sales Representative or the
installing contractor.
Section 1: Introduction
1.1 Preliminary Comments and Safety Precautions
This technical document is intended to cover most aspects asso-
ciated with the installation, application, operation, and mainte-
nance of the contactor based 2-position non-automatic transfer
switch with ratings from 40 through 400 amperes (A). It is pro-
vided as a guide for authorized and qualified personnel only.
Please refer to the specific WARNING and CAUTION in Section
1.1.2 before proceeding. If further information is required by the
purchaser regarding a particular installation, application, or main-
tenance activity, please contact an authorized Eaton sales repre-
sentative or the installing contractor.
1.1.1 Warranty and Liability Information
No warranties, expressed or implied, including warranties of fit-
ness for a particular purpose of merchantability, or warranties
arising from course of dealing or usage of trade, are made regard-
ing the information, recommendations and descriptions contained
herein. In no event will Eaton be responsible to the purchaser or
user in contract, in tort (including negligence), strict liability or
otherwise for any special, indirect, incidental or consequential
damage or loss whatsoever, including but not limited to damage
or loss of use of equipment, plant or power system, cost of capi-
tal, loss of power, additional expenses in the use of existing
power facilities, or claims against the purchaser or user by its
customers resulting from the use of the information and descrip-
tions contained herein.
1.1.2 Safety Precautions
All safety codes, safety standards, and/or regulations must be
strictly observed in the installation, operation, and maintenance
of this device.
THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO-
CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONAL SAFETY
AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE
OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE TO
FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION.
THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO
WARNINGS, WHICH APPEAR THROUGHOUT THE DOCUMENT. IN
ADDITION, WARNINGS AND CAUTIONS ARE ALL UPPER CASE AND
BOLDFACE.
COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED
IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERA-
TION, OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY
QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM ANY
WORK ASSOCIATED WITH THIS EQUIPMENT. ANY WIRING
INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL-
LOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMANENT
EQUIPMENT DAMAGE.
WARNING
Cat No: NTCEC2X20400WRU
Style No:
ASSEMBLED IN MEXICO
WITH U.S. COMPONENTS 30 - 43465
ITEM: 001
PIECE: 001
CS#: 123456
J050412234
Volts: 240
Poles: 2
Amps: 400
Phase: 1
Hertz: 60
Wire: 3
GO No: ABC0123
OF: 001
WARNING
CAUTION
IB01602046E
For more information visit: www.eaton.com
Instruction Booklet
Effective: July 2010
Page 3
2-Position Contactor Based
Non-Automatic Transfer Switch
1.2 General Information
Transfer switches are used to protect critical electrical loads
against loss of power. The load’s Source 1 power source is
backed up by a Source 2 power source. A transfer switch is
connected to both the Source 1 and Source 2 power sources and
supplies the load with power from one of the two sources. In the
event that power is lost from Source 1, the transfer switch trans-
fers the load to the Source 2 power source. This transfer is non-
automatic (electrically operated). Once Source 1 power is
restored, the transfer back to the Source 1 power source is non-
automatic (electrically operated). See Figure 2.
Figure 2. Typical Load Transfer Switch Schematic (Contactor
Type).
In the event the Source 1 power source fails, non-automatic
transfer switch will remain connected to the Source 1 power
source. When Source 2 power source with sufficient voltage and
frequency appears, transfer switch can be transferred to Source
2 non-automatically (electrical operation). Conversely, if con-
nected to Source 2 and Source 2 power source fails, non-auto-
matic transfer switch will remain connected to the Source 2
power source. When Source 1 power source with sufficient volt-
age and frequency appears, transfer switch can be transferred to
Source 1 non-automatically (electrical operation).
Non-automatic transfer switches perform the transfer function
and include three basic elements:
1.
A power contactor to connect and disconnect the load to
and from either power source.
2.
Solenoids to make the transfer of the main contacts from
source to source.
3.
Supervisory circuits constantly monitor sources available and
source to which the transfer switch is connected..
1.2.1 Design Configuration
The Eaton contactor based non-automatic transfer switch is a
compact design that uses a power contactor to transfer essential
loads from one power source to another (Figure 3 [100A]).
Figure 3. Typical Power Panel for a 100A Model.
The Eaton contactor based non-automatic transfer switch is
designed with easy installation and simplified maintenance in
mind. Three main panels comprise the contactor based non-
automatic transfer switch design:
1. Power panel;
2. Voltage selection and transformer panel (if required); and
3. Electromechanical logic panel.
Source 1
Source 2
Load