ACP 106 D • Setup Guide
The Extron ACP 106 D Audio Control Panel is a fully configurable control interface for use with any Extron ACP-enabled device.
Each ACP 106 D includes two ACP ports, which support power and communication between the host device and the ACP 106 D.
Up to eight ACP panels can be used per host device for more demanding control needs.
Front Panel Features
Extron
Extron
PROGRAM
MIC
VOLUME
MUTE
F
E
C
A
B
D
G
GX
P
A Mute Buttons
B Transmit LED
C Volume Buttons
D Volume LED Meter
E Function Button 1
F Function Button 2
Figure 1. ACP 106 D Rear Panel
Rear Panel Features
+V
ACP
PWR LOAD = 1.5W
+S -S G
+V +S -S G
STATUS
GREEN
AMBER
RED
LINK
COM ERROR
ID ERROR
A
B
B
C
D
A ACP Ports (2)
B Connection Status LED
C Reset Button
D Bus ID DIP Switches
Figure 2. ACP 106 D Front Panel
Planning the System and Installation
When planning to install an ACP system, consider how many ACP panels to use, maximum cable distance, and mounting (see the
ACP 106 D product page at www.extron.com for more information about the ACP 106 D).
Installation
Step 1: Get Ready
Use the following checklist to prepare for the installation:
�
Download and install the latest version of software, firmware, and device drivers needed to configure the host device and
configure the connected ACP products (see the host device user guide, available on www.extron.com, for details on
software and drivers).
�
Obtain cables, mounting hardware, and any other supplies required for ACP 106 D installation.
2
ACP 106 D • Setup Guide (Continued)
Step 2: Prepare the Installation Site
ATTENTION:
•
Installation and service must be performed by authorized personnel only.
•
L’installation et l’entretien doivent être effectués par le personnel autorisé uniquement.
•
Extron recommends installing the ACP 106 D into a grounded, UL Listed electrical junction box.
•
Extron recommande d’installer le ACP 106 D dans un boîtier d’encastrement électrique mis à la terre, listé UL.
•
If the ACP 106 D will be installed into fine furniture, it is best to hire a licensed, bonded craftsperson to cut the access
hole and perform the physical installation so the surface will not be damaged.
•
S’il est prévu d’installer le ACP 106 D dans du beau mobilier, il est préférable de faire appel à un artisan autorisé et
qualifié pour couper le trou d’accès et réaliser l’installation de telle façon que la surface ne soit pas endommagée.
•
Follow all national and local building and electrical codes that apply to the installation site.
•
Respectez tous les codes électriques et du bâtiment, nationaux et locaux, qui s’appliquent au site de l’installation.
NOTE:
For the installation to meet UL requirements and to comply with National Electrical Code (NEC), the ACP 106 D must
be installed in a UL Listed junction box. The end user or installer must furnish the junction box. It is not included with the
ACP 106 D.
Americans with Disabilities ACT (ADA) Compliance
When planning where to install these devices, consider factors affecting accessibility of the button panel such as height
from the floor, distance from obstructions, and how far a user must reach to press the buttons. For guidelines, see sections
307 (“Protruding Objects”) and 308 (“Reach Ranges”) of the 2010 ADA Standards for Accessible Design available at
http://www.ada.gov/regs2010/2010ADAStandards/2010ADAStandards.pdf.
Site Preparation
Extron offers an assortment of mud rings, optional UL Listed in-wall junction boxes, external wall boxes (EWBs), and surface or
tabletop mounting boxes for use with the ACP button panels. The ACP 106 D is a US 1-gang size device.
Step 3: Removing the Plastic Faceplate, Button Panel, and Changing the Buttons
The plastic faceplate and buttons can be replaced. Additional buttons ship with the
device and others can be ordered from www.extron.com.
To change the buttons:
1.
Remove the two screws holding the plastic faceplate to the metal mounting
plate and separate the faceplate from the button plate (see 1 in the figure to
the right).
2.
Insert a small flat-bladed screw driver into the notch at the top of the button
plate. Release the catch holding the button plate to the metal mounting plate
(2).
3.
Repeat step 2 to release the catch at the bottom of the plate.
4.
Tilt the top of the button plate forward as it is removed to prevent the buttons
from falling out.
Extron
VOLUME
MUTE
X
MIC
PROGRAM
ACP 106 D
Face plate
1
2
3
5.
To remove a button, press a button backward through its slot in the
button plate until the membrane containing the button is free (see 1 in
the figure to the right).
6.
To replace a button, align the two pegs in the button membrane with the
holes located at opposite corners of the empty slot on the back of the
button faceplate and push the button forward so it fits in the desired slot
(see 2 in the figure to the right). Ensure the button text orientation is
correct.
7.
Repeat steps 5 and 6 to replace any other buttons.
8.
Align the button plate with the metal mounting plate using the pegs on
the rear of the button plate as guides.
9.
Snap the button plate into place.
10. Reattach the plastic faceplate using the two screws removed in step 1.
2
1
X
Step 4: Set Bus ID Addresses
+V
+S -S G
+V
G
+S -S
ACP
PWR LOAD = 1.5W
STATUS
GREEN
AMBER
RED
LINK
COM ERROR
ID ERROR
+ V + S
G
– S
ACP port on a
DMP Plus, or on
another ACP
endpoint
ACP Ports
• Connect up to eight (8) ACP endpoint devices per
DMP Plus.
• Wire the connectors the same at both ends.
• These ports are identical. You can connect devices
interchangeablly to either port.
• Do not exceed a total of 1000 feet (305 meters) of cable for
connections between the DMP Plus and all of the ACP
panels.
• Power is provided by the IPCP Pro, a PS 1220EB power
inserter, or an Extron 12 VDC power supply.
0 1 0 0 1 0
ON
1 2 3 4 5 6
0 0 0 0 0 1
1
ON
1 2 3 4 5 6
18
Unit address
DIP switches
Binary address
Bus ID Address DIP Switches
• Use these DIP switches to set the six-bit, binary
bus address for the ACP 106 D.
• Each ACP connected to the same DMP Plus
must have a unique address.
• Switch 1 (on the left) is the highest value (32, the
the most signifcant bit [labeled “MSB”]).
• Switch 6 (on the right) is the lowest (1, the least
signifcant bit [labeled “LSB”]).
• Up = on = 1, Down = off = 0
Examples:
Figure 3. ACP 106 D Rear Panel and Side Bus ID DIP Switch Assembly
Set the bus identification (bus ID) DIP switches for the ACP 106 D
and any other ACP panels being connected to the system. Each ACP
device must have a unique bus ID. If multiple panels have the same bus
ID, address conflicts may cause one or more of the panels to not be
recognized in DSP Configurator or by the host device. Up to eight ACP
devices can be connected in the same system.
Each ACP device in a system must have a unique six-digit binary bus ID.
ACP bus IDs are set using the DIP switch assembly on the left side of the
ACP 106 D (see figure 3).
Switch 1 on the left sets the most significant bit (highest number, 32)
while switch 6 on the right sets the least significant bit (the lowest
number, 1). See the example addresses to the right.
Slide
1
2
3
4
5
6
ON
M
S
B
L
S
B
BUS ID
Example Addresses
Bus ID
(Decimal)
Binary
Address
DIP Switch
Setting
0
000000*
1
2
3
4
5
6
ON
M
S
B
L
S
B
1
000001
1
2
3
4
5
6
ON
M
S
B
L
S
B
2
000010
1
2
3
4
5
6
ON
M
S
B
L
S
B
3
000011
1
2
3
4
5
6
ON
M
S
B
L
S
B
4
000100
1
2
3
4
5
6
ON
M
S
B
L
S
B
5
000101
1
2
3
4
5
6
ON
M
S
B
L
S
B
6
000110
1
2
3
4
5
6
ON
M
S
B
L
S
B
7
000111
1
2
3
4
5
6
ON
M
S
B
L
S
B
8
001000
1
2
3
4
5
6
ON
M
S
B
L
S
B
*Address 000000 is reserved for the control processor and cannot be used by any ACP devices.