Installation, use and maintenance manual [PDF] (52 pages)
- Updated: 01.09.2026
Document Preview & Text Transcription
IWC
INSTALLATION, USE AND MAINTENANCE MANUAL
GB
MANUALE INSTALLAZIONE, USO E MANUTENZIONE
I
VENTILCONVETTORI A CASSETTA
WATER CASSETTE
IWC
2
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
WC66000101 - Rev 04
INFORMATION FOR CORRECT DISPOSAL OF THE PRODUCT
IN ACCORDANCE WITH THE EUROPEAN DIRECTIVE
2002/96/EC
At the end of its working life this equipment must not be disposed of
as an household waste. It must be taken to special local community
waste collection centres or to a dealer providing this service.
Disposing of an electrical and electronic equipment separately avoids
possible negative effects on the environment and human health
deriving from an inappropriate disposal and enables its components to
be recovered and recycled to obtain significant savings in energy and
resources. In order to underline the duty to dispose of this equipment
separately, the product is marked with a crossed-out dustbin.
Codifica cassette IWC
1
2
3
4
5
6
7
8
9
I
W
C
0
3
2
F
0
1
Nome della serie
Taglia
n° Tubi
Comando
Motore
Revisione
INFORMAZIONE PER IL CORRETTO SMALTIMENTO DEL
PRODOTTO AI SENSI DELLA DIRETTIVA EUROPEA
2002/96/CE
Alla fine della sua vita utile questo apparecchio non deve essere
smaltito insieme ai rifiuti domestici. Deve essere consegnato presso
appositi centri di raccolta differenziata oppure presso i rivenditori che
forniscono questo servizio. Smaltire separatamente un apparecchio
elettrico ed elettronico consente di evitare possibili effetti negativi
sull’ambiente e sulla salute umana derivanti da uno smaltimento
inadeguato e permette di recuperare e riciclare i materiali di cui è
composto, con importanti risparmi di energia e risorse. Per sottolineare
l’obbligo di smaltire separatamente queste apparecchiature, sul
prodotto è riportato il simbolo del cassonetto barrato. Lo smaltimento
abusivo del prodotto da parte dell’utente comporta l’applicazione
delle sanzioni amministrative di cui al D.Lgs. n. 22/1997 (articolo 50
e successivi).
DICHIARAZIONE DI CONFORMITÀ
La Galletti S.p.A. dichiara sotto la sua responsabilità, che i
ventilconvettori a cassetta IWC sono stati progettati, costruiti
e collaudati in conformità a quanto prescritto dalle Direttive
comunitarie: 2006/42/CE, 2004/108/CE, 2006/95/CE
Bentivoglio, 27/09/2011
Galletti S.p.A.
Luca Galletti
DECLARATION OF CONFORMITY
Galletti S.p.A. hereby declares, under its sole responsibility, that
IWC water cassette series have been designed, built and tested in
conformity with the specifications of European Directives:
2006/42/CE, 2004/108/CE, 2006/95/CE
Bentivoglio, 27/09/2011
Galletti S.p.A.
Luca Galletti
IWC water cassette codes
1
2
3
4
5
6
7
8
9
I
W
C
0
3
2
F
0
1
Range
Size
n° Pipes
Controller
Motor
rev. Index
IWC
3
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
WC66000101 - Rev 04
NOTE IWC 2 TUBI:
1 = temperatura acqua 7/12°C, temperatura aria B.S. 27°C, B.U. 19°C
2 = temperatura acqua ingresso 50°C, portata acqua come funzionamento in raffreddamento,
temperatura aria 20°C
3 = temperatura acqua 60/50°C, temperatura aria 20°C
4 = potenza sonora in conformità con ISO 3741 e ISO 3742
5 = pressione sonora calcolata per una distanza di 1 metro, fattore di direzionalità pari a 4
* Velocità aggiuntiva disponibile da Luglio 2012 Galletti SpA partecipa
al Programma di Certificazione EUROVENT. I prodotti interessati
compaiono nel sito www.eurovent-certification.com
NOTE IWC 4 TUBI:
1 = temperatura acqua 7/12°C, temperatura aria B.S. 27°C, B.U. 19°C
3= temperatura acqua 70/60°C, temperatura aria 20°C
4= potenza sonora in conformità con ISO 3741 e ISO 3742
5 = pressione sonora calcolata per una distanza di 1 metro, fattore di direzionalità pari a 4
* Velocità aggiuntiva disponibile da Luglio 2012 Galletti SpA partecipa al Programma di
Certificazione EUROVENT. I prodotti interessati compaiono nel sito www.eurovent-certification.
com
TABELLA PRESTAZIONI UNITÀ
Caratteristiche tecniche nominali ventilconvettori IWC modelli a 1 batteria
Modello
32
42
52
Velocità
1 *
2
3
4
1 *
2
3
4
1 *
2
3
4
Resa raffreddamento totale (1)
kW
1,24
2,15
2,35
2,60
1,70
3,50
4,00
4,60
2,46
3,80
4,42
5,06
Resa raffreddamento sensibile (1)
kW
0,92
1,78
2,00
2,23
1,15
2,63
3,06
3,56
1,82
2,87
3,33
3,80
Portata acqua (1)
l/h
213
368
404
445
291
600
687
789
422
653
758
869
Perdita di carico (1)
kPa
3
8
9
11
3
11
14
17
7
14
18
23
Resa riscaldamento (2)
kW
1,55
2,83
3,11
3,49
1,87
4,35
4,85
5,70
3,35
5,33
6,14
6,75
Perdita di carico (2)
kPa
3
7
8,00
10
3
10
13
17
6
14
18
23
Resa riscaldamento (3)
kW
2,02
3,72
4,09
4,61
2,42
5,7
6,32
7,46
4,46
7,11
8,17
8,91
Portata acqua (3)
l/h
175
323
355
400
210
495
549
648
387
617
710
774
Perdita di carico (3)
kPa
2
6
7
8
2
7
9
12
5
12
16
18
Contenuto acqua
dm3
0,43
0,86
0,86
Portata aria
m3/h
180
400
460
520
200
530
630
750
370
630
760
880
Potenza assorbita
W
17
40
50
60
20
60
70
90
26
71
85
98
Potenza sonora (4)
dB/A
30
41
44
46
32
48
51
55
41
53
57
61
Pressione sonora (5)
dB/A
25
36
39
41
27
43
46
50
36
48
52
56
Attacchi idraulici
pollici
1 / 2
1 / 2
1 / 2
Dimensioni unità H x L x P
mm
273 x 575 x 575
273 x 575 x 575
273 x 575 x 575
Dimensioni pannello H x L x P
mm
64 x 730 x 730
64 x 730 x 730
64 x 730 x 730
Caratteristiche tecniche nominali ventilconvettori IWC modelli a 1 batteria
Modello
62
82
102
Velocità
1
2
3 *
4
1
2
3
4 *
1
2
3 *
4
Resa raffreddamento totale (1)
kW
4,20
5,00
5,40
6,00
5,50
6,50
8,00
9,10
6,23
8,09
8,90
9,92
Resa raffreddamento sensibile (1)
kW
3,13
3,70
3,99
4,40
4,11
5,08
6,10
6,84
4,69
6,17
6,87
7,71
Portata acqua (1)
l/h
720
859
930
1.029
944
1.116
1.373
1.561
1.070
1.389
1.529
1.702
Perdita di carico (1)
kPa
16
22
25
30
21
28
41
51
27
42
50
60
Resa riscaldamento (2)
kW
5,40
6,40
7,10
7,70
6,28
8,52
9,42
10,19
7,34
9,53
10,59
11,69
Perdita di carico (2)
kPa
15
21
25
30
21
29
39
48
26
42
49
60
Resa riscaldamento (3)
kW
7,08
8,39
9,33
10,08
8,14
11,24
12,26
13,18
9,52
12,34
13,73
15,11
Portata acqua (3)
l/h
615
729
810
875
707
976
1.065
1.145
827
1.072
1.192
1.312
Perdita di carico (3)
kPa
12
16
19
22
12
21
24
27
16
26
31
37
Contenuto acqua
dm3
1,00
1,50
1,50
Portata aria
m3/h
850
1.060
1.160
1.300
830
190
1.270
1.400
1.200
1.700
1.980
2.300
Potenza assorbita
W
80
90
100
120
80
100
120
140
110
130
155
180
Potenza sonora (4)
dB/A
43
48
49
51
37
46
50
53
43
49
53
57
Pressione sonora (5)
dB/A
38
43
44
46
32
41
45
48
38
44
48
52
Attacchi idraulici
pollici
3 / 4
3 / 4
3 / 4
Dimensioni unità H x L x P
mm
273 x 776 x 776
290 x 1066 x 776
290 x 1066 x 776
Dimensioni pannello H x L x P
mm
64 x 860 x 860
64 x 1150 x 860
64 x 1150 x 860
Caratteristiche tecniche nominali ventilconvettori IWC modelli a 2 batterie
Modello
34
44
Velocità
1 *
2
3
4
1 *
2
3
4
Resa raffreddamento totale (1)
kW
1,03
1,72
1,88
2,05
1,52
2,88
3,28
3,76
Resa raffreddamento sensibile (1)
kW
0,81
1,51
1,66
1,82
1,07
2,27
2,60
3,00
Portata acqua (1)
l/h
177
295
323
351
295
494
563
645
Perdita di carico (1)
kPa
3
8
9
11
8
11
13
17
Resa riscaldamento (3)
kW
1,1
1,78
1,95
2,2
1,48
2,87
3,14
3,76
Portata acqua (3)
l/h
96
155
169
191
129
249
273
327
Perdita di carico (3)
kPa
11
25
29
36
7
22
26
36
Contenuto acqua
dm3
0,43
0,86
Portata aria
m3/h
180
400
460
520
200
530
630
750
Potenza assorbita
W
17
40
50
60
20
60
70
90
Potenza sonora (4)
dB/A
30
41
44
46
32
48
51
55
Pressione sonora (5)
dB/A
25
36
39
41
27
43
46
50
Attacchi idraulici batteria fredda
pollici
1 / 2
1 / 2
Attacchi idraulici batteria calda
pollici
1 / 2
1 / 2
Dimensioni unità H x L x P
mm
273 x 575 x 575
273 x 575 x 575
Dimensioni pannello H x L x P
mm
64 x 730 x 730
64 x 730 x 730
IWC
4
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
WC66000101 - Rev 04
UNITS’ PERFORMANCE TABLE
NOTES IWC WITH 2 PIPES:
1 = water temperature 7/12°C, air temperature dry bulb 27°C, wet bulb 19°C
2 = inlet water temperature 50°C, water flow rate same as in cooling mode, air inlet tempera-
ture 20°C
3 = water temperature 60/50°C, air temperature 20°C
4= sound power conforming to ISO 3741 and ISO 3742
5 = Sound pressure level measured at a distance of 1 m with a directivity factor of 4
* Additional speed available from July 2012
Galletti SpA takes part in the EUROVENT Certification Programme.
The products involved can be seen at www.eurovent-certification.com
Ratings and technical data of IWC fan coil units with 1 heat exchanger
Model
32
42
52
Speed
1 *
2
3
4
1 *
2
3
4
1 *
2
3
4
Total cooling capacity (1)
kW
1,24
2,15
2,35
2,60
1,70
3,50
4,00
4,60
2,46
3,80
4,42
5,06
Sensible cooling capacity (1)
kW
0,92
1,78
2,00
2,23
1,15
2,63
3,06
3,56
1,82
2,87
3,33
3,80
Water flow (1)
l/h
213
368
404
445
291
600
687
789
422
653
758
869
Pressure drop (1)
kPa
3
8
9
11
3
11
14
17
7
14
18
23
Heating capacity (2)
kW
1,55
2,83
3,11
3,49
1,87
4,35
4,85
5,70
3,35
5,33
6,14
6,75
Pressure drop (2)
kPa
3
7
8,00
10
3
10
13
17
6
14
18
23
Heating capacity (3)
kW
2,02
3,72
4,09
4,61
2,42
5,7
6,32
7,46
4,46
7,11
8,17
8,91
Water flow (3)
l/h
175
323
355
400
210
495
549
648
387
617
710
774
Pressure drop (3)
kPa
2
6
7
8
2
7
9
12
5
12
16
18
Water content
dm3
0,43
0,86
0,86
Air flow
m3/h
180
400
460
520
200
530
630
750
370
630
760
880
Power input
W
17
40
50
60
20
60
70
90
26
71
85
98
Sound power level (4)
dB/A
30
41
44
46
32
48
51
55
41
53
57
61
Sound pressure level (5)
dB/A
25
36
39
41
27
43
46
50
36
48
52
56
Water connections
inches
1 / 2
1 / 2
1 / 2
Dimensions H x L x P
mm
273 x 575 x 575
273 x 575 x 575
273 x 575 x 575
Dimensions H x L x P
mm
64 x 730 x 730
64 x 730 x 730
64 x 730 x 730
Ratings and technical data of IWC fan coil units with 1 heat exchanger
Model
62
82
102
Speed
1
2
3 *
4
1
2
3
4 *
1
2
3 *
4
Total cooling capacity (1)
kW
4,20
5,00
5,40
6,00
5,50
6,50
8,00
9,10
6,23
8,09
8,90
9,92
Sensible cooling capacity (1)
kW
3,13
3,70
3,99
4,40
4,11
5,08
6,10
6,84
4,69
6,17
6,87
7,71
Water flow (1)
l/h
720
859
930
1.029
944
1.116
1.373
1.561
1.070
1.389
1.529
1.702
Pressure drop (1)
kPa
16
22
25
30
21
28
41
51
27
42
50
60
Heating capacity (2)
kW
5,40
6,40
7,10
7,70
6,28
8,52
9,42
10,19
7,34
9,53
10,59
11,69
Pressure drop (2)
kPa
15
21
25
30
21
29
39
48
26
42
49
60
Heating capacity (3)
kW
7,08
8,39
9,33
10,08
8,14
11,24
12,26
13,18
9,52
12,34
13,73
15,11
Water flow (3)
l/h
615
729
810
875
707
976
1.065
1.145
827
1.072
1.192
1.312
Pressure drop (3)
kPa
12
16
19
22
12
21
24
27
16
26
31
37
Water content
dm3
1,00
1,50
1,50
Air flow
m3/h
850
1.060
1.160
1.300
830
190
1.270
1.400
1.200
1.700
1.980
2.300
Power input
W
80
90
100
120
80
100
120
140
110
130
155
180
Sound power level (4)
dB/A
43
48
49
51
37
46
50
53
43
49
53
57
Sound pressure level (5)
dB/A
38
43
44
46
32
41
45
48
38
44
48
52
Water connections
inches
3 / 4
3 / 4
3 / 4
Dimensions H x L x P
mm
273 x 776 x 776
290 x 1066 x 776
290 x 1066 x 776
Dimensions H x L x P
mm
64 x 860 x 860
64 x 1150 x 860
64 x 1150 x 860
Ratings and technical data of IWC fan coil units with 2 heat exchangers
Model
34
44
Speed
1 *
2
3
4
1 *
2
3
4
Total cooling capacity (1)
kW
1,03
1,72
1,88
2,05
1,52
2,88
3,28
3,76
Sensible cooling capacity (1)
kW
0,81
1,51
1,66
1,82
1,07
2,27
2,60
3,00
Water flow (1)
l/h
177
295
323
351
295
494
563
645
Pressure drop (1)
kPa
3
8
9
11
8
11
13
17
Heating capacity (3)
kW
1,1
1,78
1,95
2,2
1,48
2,87
3,14
3,76
Water flow (3)
l/h
96
155
169
191
129
249
273
327
Pressure drop (3)
kPa
11
25
29
36
7
22
26
36
Water content
dm3
0,43
0,86
Air flow
m3/h
180
400
460
520
200
530
630
750
Power input
W
17
40
50
60
20
60
70
90
Sound power level (4)
dB/A
30
41
44
46
32
48
51
55
Sound pressure level (5)
dB/A
25
36
39
41
27
43
46
50
Cooling heat exchanger water connections
inches
1 / 2
1 / 2
Heating heat exchanger water connections
inches
1 / 2
1 / 2
Dimensions H x L x P
mm
273 x 575 x 575
273 x 575 x 575
Dimensions H x L x P
mm
64 x 730 x 730
64 x 730 x 730
NOTES IWC WITH 4 PIPES:
1 = water temperature 7/12°C, air temperature dry bulb 27°C, wet bulb 19°C
3 = Water temperature 70 - 60°C; air temperature 20°C
4 = sound power conforming to ISO 3741 and ISO 3742
5 = Sound pressure level measured at a distance of 1 m with a directivity factor of 4
* Additional speed available from July 2012
Galletti SpA takes part in the EUROVENT Certification Programme.
The products involved can be seen at www.eurovent-certification.com