30303451 Issue 4.03
Features
Driving 220VAC devices.
Providing normally open, normally closed output
contacts.
Cable checking.
Insulated feedback signal from 220VAC devices.
Plug-in structure.
Description
C-9302C Interposing Relay Module is non-addressable,
designed to start/stop the devices driven by heavy DC
and 220VAC. The module is used together with
fireman’s Control Panel (FCP) featuring cable checking,
such as GST014FCP.
Connection and Cabling
Fig. 1 shows terminals on the module.
9
10
15
16
8
7
2
1
C+
C-
Mounting
Hole
Mounting
Hole
Mounting
Direction
COM
N
NO
NC
AN
A1
A2
65mm
6mm
Fig. 1
C+, C-: Input terminals of start command signal
(24VDC), connecting with output control terminal of
fireman’s control panel.
A1, A2: Input terminals of normally open volt-free
feedback signal, connecting with volt-free feedback
terminals of controlled device.
AN, N: Voltage feedback input terminals (220VAC),
connecting
with
voltage
feedback
terminals
of
controlled device.
COM, NO, NC: Output control terminals, volt-free
normally open, normally closed contacts (5A, 220VAC),
connecting with control terminals of the controlled
device.
Recommended Cabling
1.5mm2 or above fire cable for each terminal, subject to
local codes.
Installation
The module is simply plugged onto the base after
corresponding terminals are connected.
If the cable conduit is inside the wall, the base is
installed onto the Back Box (Fig. 2). If the cable conduit
is on the surface of the wall, B-9310 Back Box is
available (Fig. 3).
Conduit
B-9310
Back Box
Conduit
Module
Module
Back Box
Fig. 2 Fig. 3
Note the upward arrow for mounting direction (Fig. 1).
Applications
1.
Fig. 4 shows that the module controls the devices
by volt-free input mode. .
FCP
Device
NO
COM
C+
C-
C1-
C1+
A1
A2
Feedback
C-9302C
Interposing Relay Module
Fig. 4
2.
Fig. 5 shows that the module controls the devices
by voltage input mode.
FCP
N
AN
C1+
C1-
C-
C+
C-9302C
Interposing Relay Module
COM
NO
Device
Feedback
Fig. 5
The Intelligent Solution
C-9302C
Interposing Relay Module
30303451 Issue 4.03
3. It occupies two channels of fireman’s control panel
for the control of device needing start/stop. One
channel is to start, and the other is to stop. Output
device is pulse mode. Fig. 6 shows that two channels
of fireman’s control panel control the device.
Device
Device
C-9302C
Interposing Relay Module
NC2
COM2
C-
C+
NO1
COM1
C-9302C
Interposing Relay Module
C+
C-
C2+
C2-
C1-
C1+
FCP
Fig. 6
Note: In Fig. 6, voltage or volt-free feedback can
also be connected based on requirements,
please refer to Fig. 4 or Fig. 5 for the specific
connections.
Specification
Operating Voltage
24VDC (20VDC~28VDC)
Standby Current
≤4.5mA
Action Current
≤26mA
Output Capacity
5A/220VAC or 5A/24VDC
Ingress Protection
Rating
IP30
Operating
Temperature
-10℃~+50℃
Relative Humidity
≤95%, non condensing
Material and Color
of Enclosure
ABS, white (RAL 9016)
Dimension
(L×W×H)
120mm×80mm×43mm
(with base)
Weight
About 187g (with base)
Tools and Accessories
Model
Name
Remark
B-9310
Back box
Order separately
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design,
materials and workmanship during warranty period.
This warranty shall not apply to any product that is
found to have been improperly installed or used in any
way not in accordance with the instructions supplied
with the product. Anybody, including the agents,
distributors or employees, is not in the position to
amend the contents of this warranty. Please contact
your local distributor for products not covered by this
warranty.
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
[email protected] www.gst.com.cn
Pages Preview: