Installation, Commissioning &
Operating Manual
12 ZONE FULLY FUNCTIONAL REPEATER PANEL
Approved Document UI-ASP-R-01 Issue 3.0
REPEATER PANEL
IMPORTANT NOTE
PLEASE READ THIS MANUAL BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN IN IT
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
E.S.D
The panel is safe to operate provided it has been installed in compliance with the manufacturer’s instructions
and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualified and authorised
to do so. There is no need to open the panel’s enclosure except to carry out commissioning, maintenance
and remedial work. This work must only be carried out by competent service personnel who are fully
conversant with the contents of the panel’s installation manual and have the necessary skills for maintaining
this equipment.
This fire alarm system requires periodic checks as specified in BS 5839 Part 1 It is the responsibility of the
system user to ensure it is regularly serviced and maintained in good working order.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any
misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The
manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to
product specifications at our discretion and without prior notice. E & O E.
IMPORTANT SAFETY NOTES
Haes Systems Ltd, Columbia House, Packet Boat Lane, Cowley Peachey, Uxbridge, UB8 2JP
Model Number
AlarmSense PLUS 12 zone repeater panel ASP-R-12
European Standard EN54-2 : 1997 + A1 : 2006
Control and indicating equipment for fire detection and fire alarm systems for buildings.
European Standard EN54-4 : 1997 + A1 : 2002 + A2 : 2006
Power supply equipment for fire detection and fire alarm systems for buildings.
ATTENTION
ASP-R Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ASP-R-01 Issue 3.0
1
CONTENTS
Page
ABOUT THIS PANEL
2
PRODUCT OVERVIEW
2
CABINET DETAILS
3
CIRCUIT BOARDS
4
MAIN PCB TERMINALS
5
COMMS PCB TERMINALS
5
TECHNICAL SPECIFICATION
6
POWER SUPPLY MODULE
7
INSTALLATION
8
SAFETY
8
ESD PRECAUTIONS
9
GENERAL
9
MOUNTING THE CABINET
9
MAINS CONNECTIONS
10
CONNECTING THE BATTERIES
11
CABLING
12
SETUP & PROGRAMMING
14
INSTALL COMMS PCB
14
SET NUMBER OF REPEATER PANELS
16
REPEATER PANEL ADDRESSING
16
PROGRAMMING REPEATER PANELS
17
OPERATING
18
PANEL CONTROLS & INDICATIONS
18
DISABLE MODE
20
TEST MODE
21
ASP-R Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ASP-R-01 Issue 3.0
2
ABOUT THIS PANEL
PRODUCT OVERVIEW
The AlarmSense PLUS repeater panels have the same, easy to use, controls and indications as the main
control panel but mounted in a smaller cabinet.
The repeaters are fully functional with ‘Silence’, ‘Resound’ and ‘Reset’ controls, as well as Disable and
Test Mode functions. AlarmSense PLUS panels can support up to 8 repeater panels.
Repeater panels are designed to be wired in a fault tolerant (fail safe) loop configuration, from comms A
to B and back to the main panel again. This enables repeater panels to still work if there is a break in the
cables.
If replacing an older system where the existing cabling cannot be configured in a loop as above, it is
possible to re-programme the panel back to legacy RS485 circuit comms monitoring. This then allows any
topology of comms cabling to be utilised.
The main circuit board has 2, switch –ve, inputs which can be used to sound or pulse the alarms. These
inputs can also be re-programmed for use as PSU fault inputs.
The internal comms PCB has 6, switch –ve, programmable outputs.
Different key types are used for the door lock and the ‘activate controls’ key-switch. It is also possible
to enable the controls via a 4 digit code entry if preferred. An eight button keypad is used to control the
system and allow access to the function options (unless disabled).
The control panel comprises of a sheet steel enclosure suitable for wall mounting with a hinged, lockable
front access door. It can be semi recessed, using a suitable recessing bezel. Cable entry is via 20mm
‘knockouts’ located at the top and rear of the cabinet.
The repeaters are supplied with a 1.5 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
Quiesecent and alarm current details for standby battery calculations
Standby Current
Alarm Current
ASP-R-12 repeater panel
63mA
85mA