Operation & user’s manual [PDF] (52 pages)
- Updated: 23.07.2026
Document Preview & Text Transcription
Optidrive ODV-2 User Guide Revision 2.00
www.invertekdrives.com
1
1
Introduction
AC Variable Speed Drives
0.75 - 160kW / 1HP - 250HP
200-480V Single and 3 Phase Input
Installation and Operating Instructions
User Guide
IP20
IP66 / NEMA 4X
IP55 / NEMA 12
IP40
Optidrive HVAC User Guide V2.00
Optidrive HVAC Start Up Guide
OPTIDRIVE HVAC (IP55 Enclosure).
Supply Voltage
Keypad Operation can be found in
section 5.5 on page 27
Run / Stop 10K Pot
HVAC Display
(Status, Diagnostics, and Programming)
Motor Cable
For correct cable size, see Technical
Data on page 47
Observe the maximum permissible
motor cable length.
For Motor cable lengths > 50 metres, an
output filter is recommended.
Use a screened (shielded cable). The
shield should be bonded to earth at
both ends.
Motor Connection
Check for Star or Delta connection
according to the motor voltage rating in
section 4.5.
Motor Nameplate Details
Motor Rated Voltage: P1-07
Motor Rated Current: P1-08
Motor Rated Frequency: P1-09
Motor Rated Speed (Optional): P1-10
Fuses or MCB
Check Drive
Rating info in
section 13.4
AC Supply Connection
200 – 240 Volts + / - 10%
380 – 380 Volts + / - 10%
Check Drive Input Voltage
Ranges on page 47
PE L1 L2 L3
Control Terminal
Configuration based on factory settings
Mechanical Mounting
Information can be found in section 3.7
on page 16
Hardware Enable Circuit
Link the terminals as shown, optionally
through contacts to enable drive
operation.
Close the switch to run (enable)
Open the switch to stop
Optidrive HVAC Start Up Guide
OPTIDRIVE HVAC (IP66 Enclosure).
HVAC Display
(Status, Diagnostics, and Programming)
Motor Cable Sizes
Check the rating information in
section 11.3 on page 47
Motor Connections
Check for Star or Delta connection
according to the motor voltage rating –
se section 4.5 on page 23
Motor Nameplate Details
Motor Rated Voltage: P1-07
Motor Rated Current: P1-08
Motor Rated Frequency: P1-09
Motor Rated Speed (Optional): P1-10
Mechanical Mounting
Information can be found in section 3.8
on page 16
Control Terminal
Configuration based on factory settings
Hardware Enable Circuit
Link the terminals as shown, optionally
through switch contacts to enable drive
operation.
Close the switch to run (enable)
Open the switch to stop
Keypad Operation can be found in
section 5.5 on page 27
Applies to Switched version only
In-built Isolator:
Mains Power On / Off
Fuses or MCB
Check Drive
Rating info in
section 13.4.
AC Supply Connection
200 – 240 Volts + / - 10%: 1 / 3 Phase
380 – 380 Volts + / - 10%: 3 Phase
Check Drive Input Voltage Ranges on
page 47
PE L1 L2 L3
Run / Stop 10K Pot