1. Description
The CAN-Repeater is used for electrical isolation of two segments of a CAN-
network, to increase the number of possible CAN nodes, for signal regeneration
and for setting up star or tree topologies. A special feature of the IXXAT
Repeater is an error detection mechanism with which a defective segment is
detected and shut down. The remaining network can thus continue
communicating without faults. The segment is reconnected to the network
automatically after the problem has been solved.
The automatic separation of a defective network segment is made after
reception of a permanent dominant level for more than 20 bit times. The
separated network will be reconnected after reception of a recessive bit.
2. LEDs
The status of the CAN Repeater and the CAN communication lines are indicated
by four LEDs mounted at the front of the housing.
Transmitting CAN 2 (green)
Status LEDs
Transmitting CAN 1 (green)
CAN 2 segment defect (red)
CAN 1 segment defect (red)
CAN 1
CAN 2
figure 2-1: Status LEDs of the CAN Repeater
Automation GmbH
Copyright IXXAT Automation GmbH
CAN Repeater - Manual, Version 3.6
2
3. Power and CAN Connectors
At the left and right side of the housing are screw connectors for the power
supply and CAN line. The pinning of these connectors is as shown in figure 3-1.
1: +9 - 35 V DC
2: GND
Power supply
First CAN line
6: CAN High
7: CAN Low
8: GND
Second CAN line
3: CAN High
4: CAN Low
5: GND
figure 3-1: Terminal allocation.
Copyright IXXAT Automation GmbH
CAN Repeater - Manual, Version 3.6
3
4. Bus termination configuration
For optimum communication, the individual electrical CAN-segment is to be
terminated at both ends with the impedance of the line. The termination
resistors prevent reflections on the line ends and ensure a current path for
discharging the dominant to the recessive level. Termination resistors are
mounted on the repeater and could be activated or deactivated by soldering
jumper.
Attention:
Open the device only on electrostatic safe areas!
Bus termination:
Default configuration:
Order number 1.01.0064.44000, 1.01.0064.90001:
Termination CAN1 and CAN2 Rt=120 Ω active
(Soldering jumper closed at „120R Term.“).
Order number 1.01.0064.90003:
No termination at CAN1
Termination at CAN 2 Rt = 120 Ω active.
Order number: 1.01.0064.46000:
Termination Rt= 120 Ω at CAN 1 active.
No termination at CAN2 allowed (Low Speed- CAN).
To close the soldering jumper means to activate the
termination resistor of Rt= 120 Ω between CAN_H and
CAN_L at the described CAN segment
To disable the bus termination open the soldering jumper.