A I R C O N D I T I O N E R S
XC21
DAVE LENNOX SIGNATURE® COLLECTION
R-410A - Two-Stage Compressor - SilentComfort™ Technology
Bulletin No. 210586
October 2010
Supersedes September 2010
E N G I N E ER I N G D ATA
SEER up to 21.00
2 to 5 Tons
Cooling Capacity - 23,200 to 59,500 Btuh
MODEL NUMBER IDENTIFICATION
x c 21 - 036 - 230 - 5
Nominal SEER
Unit Type
C = Air Conditioner
Refrigerant Type
X = R-410A
Nominal Cooling Capacity
024 = 2 tons
036 = 3 tons
048 = 4 tons
060 = 5 tons
Minor Revision Number
Voltage
230 = 208/230V-1ph-60hz
XC21 - 2 to 5 Ton Air Conditioner / Page 2
FEATURES
Equipment Warranty
Compressor - ten year limited warranty in residential
installations and five years in non-residential installations.
All other covered components - ten years in
residential installations and one year in non-residential
installations.
Refer to Lennox Equipment Limited Warranty certificate
included with unit for specific details.
ApplicationS
SEER up to 21.00.
2 through 5 ton.
Single phase power supply.
Sound levels as low as 69 dB.
Vertical air discharge allows concealment behind shrubs
at grade level or out of sight on a roof.
Matching add-on furnace indoor coils or air handlers
provide a wide range of cooling capacities and
applications. See AHRI System Matches.
See Indoor Coils and Air Handlers tab sections for data.
Units shipped completely factory assembled, piped, and
wired. Each unit is test operated at the factory insuring
proper operation.
Installer must set air conditioner, connect refrigerant
lines, and make electrical connections to complete job.
Approvals
Certified in accordance with USE certification program
which is based on AHRI Standard 210/240-2008.
Sound rated in Lennox reverberant sound test room
in accordance with test conditions included in AHRI
Standard 270-2008.
Tested in the Lennox Research Laboratory
environmental test room.
Rated according to U.S. Department of Energy (DOE)
test procedures.
Air conditioners and components within bonded for
grounding to meet safety standards for servicing
required by ETL, NEC, and CEC.
Units are ETL listed for the US and Canada.
ISO 9001 Registered Manufacturing Quality System.
Energy Star® certified units are designed to use less
energy, help save money on utility bills, and help protect
the environment.
All models are listed in the GreenSpec® Directory, a
leading resource of environmentally responsible products.
For expanded ratings, see www.lennoxdavenet.com.
REFRIGERATION SYSTEM
R-410A Refrigerant
Non-chlorine, ozone friendly, R-410A.
Unit pre-charged with refrigerant.
See Specification table.
Outdoor Coil Fan with SilentComfort™ Technology
Specially-designed, SilentComfort™ fan guard uses
Passive Vortex Suppression to reduce air noise.
Constructed of corrosion-resistant PVC (polyvinyl
chloride) coated steel.
Specially designed fan
blades reduce operating
sound levels. Direct drive fan
moves large air volumes
uniformly through entire
condenser coil for high
refrigerant cooling capacity.
Vertical air discharge
minimizes operating sounds
and eliminates damage to
lawn and shrubs.
Fan motor is inherently protected.
All models have a variable-speed outdoor fan motor for
quiet operation.
Motor totally enclosed for maximum protection from
weather, dust and corrosion.
Fan service access accomplished by removal of fan
guard.
A
B
C
B
C
D
E
F
G
H
K
Contents
AHRI System Matches................................................14
Dimensions..................................................................12
Electrical Data ............................................................10
Features........................................................................2
Field Wiring..................................................................11
Installation Clearances................................................11
Model Number Identification..........................................1
Optional Accessories...................................................10
Outdoor Sound Data....................................................11
Specifications..............................................................10
Sunsource® Home Energy System - Components........7
I
J
XC21 - 2 to 5 Ton Air Conditioner / Page 3
Copper Tube/Enhanced Fin Coil
Lennox designed and fabricated coil.
Ripple-edged aluminum fins.
Copper tube construction.
Lanced fins provide maximum exposure of fin surface to
air stream resulting in excellent heat transfer.
Fin collars grip tubing for maximum contact area.
Flared shoulder tubing connections/silver soldering
construction.
Coil is factory tested under high pressure to insure
leakproof construction.
Entire coil is accessible for cleaning.
High Pressure Switch
Shuts off unit if abnormal operating conditions cause the
discharge pressure to rise above setting.
Protects compressor from excessive condensing
pressure.
Automatic reset.
Low Pressure Switch
Shuts off unit if suction pressure falls below setting.
Provides loss of charge and freeze-up protection.
Automatic reset.
Hi-Capacity Liquid Line Drier
Factory installed in the liquid line, the drier traps
moisture or dirt that could contaminate the refrigerant
system.
100% molecular-sieve bead type drier.
OPTIONS
Expansion Valve Kits
Must be ordered extra and field installed on certain
indoor units. See TXV Usage table on page 13.
Chatleff style fitting.
Freezestat
Installs on or near the discharge line of the indoor coil or
on the suction line.
Senses suction line temperature and cycles the
compressor off when suction line temperature falls
below it’s setpoint.
Opens at 29°F and closes at 58°F.
Refrigerant Line Kits
Refrigerant lines (suction & liquid) are shipped
refrigeration clean. Lines are cleaned, dried,
pressurized, and sealed at factory.
Suction line fully insulated.
L15 lines are stubbed at both ends.
See Specifications table for selection.
Not available for -060 model and must be field
fabricated.
D
E
F
G
COMPRESSOR
Copeland Scroll Ultra Tech™ Two-Stage Compressor
Compressor features high
efficiency with uniform
suction flow, constant
discharge flow and high
volumetric efficiency and
quiet operation.
Compressor consists of
two involute spiral scrolls
matched together to generate
a series of crescent shaped
gas pockets between them.
During compression, one
scroll remains stationary
while the other scroll orbits
around it.
Gas is drawn into the outer
pocket, the pocket is sealed
as the scroll rotates.
As the spiral movement continues, gas pockets are
pushed to the center of the scrolls. Volume between the
pockets is simultaneously reduced.
When pocket reaches the center, gas is now at high
pressure and is forced out of a port located in the
center of the fixed scrolls. During compression, several
pockets are compressed simultaneously resulting in a
smooth continuous compression cycle.
Continuous flank contact, maintained by centrifugal
force, minimizes gas leakage and maximizes efficiency.
Scroll compressor is tolerant to the effects of slugging
and contaminants. If this occurs, scrolls separate,
allowing liquid or contaminants to to be worked toward
the center and discharged.
On the fixed scroll there are two bypass ports in the first
suction pocket. On the
outside of the fixed scroll
there is a “slider ring” that
is controlled by an internal
solenoid that will rotate and
cover the bypass ports.
When the thermostat calls
for first-stage cooling, the
bypass ports are open and
the compressor operates
at 67% capacity, creating
more cost-effective and efficient compressor operation.
The bypassed refrigerant is returned to the compressor
housing through the bypass ports. When the thermostat
calls for second-stage cooling, the internal solenoid is
energized, the slider ring rotates and covers the bypass
ports, and the compressor operates at full capacity.
Low gas pulses during compression reduces
operational sound levels.
Compressor motor is internally protected from
excessive current and temperature.
H
FEATURES
XC21 - 2 to 5 Ton Air Conditioner / Page 4
COMPRESSOR (CONTINUED)
Compressor is installed in the unit on specially
formulated, resilient rubber mounts for better sound
dampening and vibration free operation.
Crankcase Heater
Crankcase heater prevents migration of liquid
refrigerant into compressor and ensures proper
compressor lubrication.
CONTROLS
icomfort™ Control
Advanced control communicates
information about various
operating parameters in
the air conditioner to the
optional icomfort Touch™
Communicating Thermostat to
constantly maintain the highest
level of comfort, performance and
efficiency available.
Connections for connecting a
conventional heating/cooling
thermostat are also provided on
the control.
Auto Configuration - On start-up the control
automatically sends a description of the unit to
the optional icomfort Touch™ Communicating
Thermostat to automatically configure the number of
stages and features available.
Control also features:
• Compressor anti-short cycle delay. User selectable
with communicating thermostat - 1, 2, 3, 4 or 5
minutes. Default setting is 5 minutes.
Compressor must operate in first stage a minimum
of 5 seconds before second stage operation is
permitted.
• Low voltage protection prevents 2nd stage
compressor operation when voltage is not within the
specified range.
• High and low pressure switch monitoring with
provisions for lockout.
• Five-Strike lockout protection protects compressor.
• Discharge line temperature and sensor monitoring.
• Lennox Humiditrol® Whole Home Dehumidification
System (EDA) compatible.
• EEPROM storage of all local configurations.
I
Lennox Systems Operations Monitor
(icomfort™ Control Feature)
Onboard Lennox® Systems Operations Monitor (LSOM)
provides detailed information for proper preventative
maintenance and fast, easy servicing.
Displays the most common fault conditions (electrical
and mechanical) through the icomfort Touch™
Communicating Thermostat or through the ALERT
and TRIP lights on the control. ALERT LED (yellow) -
communicates an abnormal system condition through a
unique flash code. The ALERT LED will flash a number
of times consecutively, pause and then repeat the
process. The number of consecutive flashes, defined
as the Flash Code, correlates to a particular abnormal
condition. The codes can indicate one of the following:
long run time, system pressure trip (discharge or suction
pressure out-of-limits or compressor overloaded), short
cycling, locked rotor, open circuit, open start circuit
(current present only in run circuit), open run circuit
(current present only in start circuit), welded contactor
(compressor runs continuously), or low voltage (control
circuit < 17VAC). TRIP LED (red) - indicates there is a
demand signal from the thermostat but no current to the
compressor is detected by the monitor.
OPTIONS
Compressor Low Ambient Cut-Off
Non-adjustable switch (low ambient cut-out) prevents
compressor operation when outdoor temperature is
below 35°F.
Compressor Hard Start Kit
Single-phase units are equipped with a PSC
compressor motor.
This type of motor normally does not need a potential
relay and start capacitor.
In conditions such as low voltage, kit may be required to
increase the compressor starting torque.
Indoor Blower Off Delay Relay
Delays the indoor blower-off time during the cooling
cycle. Required if outdoor unit is used with a
conventional heating-cooling thermostat and air handler
(not icomfort™ control). See furnace or air handler
specifications to determine if relay is needed.
Indoor Blower Speed Relay Kit
Relay kit provides optimum humidity control conditions
by automatically reducing indoor blower speed during
continuous fan or first-stage compressor operation.
Low Ambient Kit
Air conditioner will operate satisfactorily down to 45°F
outdoor air temperature without any additional controls.
Kit can be added in the field enabling unit to operate
properly down to 30°F.
A Freezestat should be installed on compressors
equipped with a low ambient kit.
A Compressor Low Ambient Cut-Off should be added to
terminate compressor operation below recommended
operation conditions.
FEATURES