Installation and maintenance manual [PDF] (110 pages)
- Updated: 23.04.2026
Document Preview & Text Transcription
UMV 2301 AS
Speed controller for asynchronous motors
Installation and maintenance
Réf. 2692 - 4.33 / a - 1.98
This manual must be sent
to the end user
1 - UL LISTING INFORMATION
The Drive conforms to UL listing requirements only when
the following are observed :
• The Drive is installed in a type 1 enclosure, or better,
as defined by UL50.
• UL listed fuses class RK1 600Vac are used in the AC
supply.
• Class 160/75°C (140/167°F) copper wire only is used in
the installation.
• The ambient temperature does not exceed 40°C
(104°F) when the Drive is operating.
• The terminal tightening torques specified in the table in
Terminal sizes and tightening torques in Chapter 2 in-
stalling the Drive are used.
2 - INSTALLING THE DRIVE
• UL listing is valid when the Drive is
installed in a type 1 enclosure, or better,
as defined by UL50.
2.1 - Planning the installation
UL listing is dependent on the use of the correct type
of UL listed fuse, and applies when the symmetrical
short-circuit current does not exceed 5 kA for model
sizes 8T to 50T, and 10 kA for model size 60T to
120T.
2.2 - Terminal sizes and tightening torques
• To avoid a fire hazard and maintain
validity of the UL listing, adhere to the
specified tightening torques for the
power and ground terminals. Refer to
the following tables.
Drive
RFI filter
1
Speed controller
for asynchronous motors
UMV 2301 AS
Ref. 2881 - 4.33 / a - 2.98
ADDENDUM
UL MARKING REQUIREMENTS
Model
Fuse rating
UMV 2301 AS 8T
16A
UMV 2301 AS 11T
20A
UMV 2301 AS 16T
35A
UMV 2301 AS 22T
40A
UMV 2301 AS 27T
50A
UMV 2301 AS 33T
60A
UMV 2301 AS 40T
70A
UMV 2301 AS 50T
80A
UMV 2301 AS 60T
100A
UMV 2301 AS 75T
125A
UMV 2301 AS 100T
160A
UMV 2301 AS 120T
200A
Warning
Warning
Power
Ground
Model
terminals
terminals
Size
Torque
Size
Torque
type
type
UMV 2301 AS
8T to 16T
Plug-in
terminal
block
0.5Nm
4.4 lb.in
M4
(Torx/
slot-head
screw)
3N.m
26.6 lb.in
UMV 2301 AS
22T to 50T
M8
stud
25 N.m
221 lb.in
M8
stud
25 N.m
221 lb.in
UMV 2301 AS
60T to 120T
M10
stud
25 N.m
221 lb.in
M10
stud
25 N.m
221 lb.in
Torque tolerance
± 10 %
Size
Part No.
Torque
A
FLT 3010
0.7 N.m
6 lb.in
B
FLT 3027
1.6 N.m
14 lb.in
C
FLT 1057
12.6 N.m
111 lb.in
D
FLT 1071
12.6 N.m
111 lb.in
E
FLT 1111
25 N.m
221 lb.in
F
FLT 1171
25 N.m
221 lb.in
Torque tolerance
± 10 %
2.3 - Using the gland plate and cable glands
• When the gland plate(s) are not fitted,
objects less than 60 mm (2 1/2 In) wide
can pass through the cable entry
opening and possibly make contact with
live parts inside the Drive.
Fit the gland plate and cable glands as required.
Before fitting cable glands, push out sufficient blanking
caps from the grand plate.
Note that the IP rating of the Drive is reduced if any ho-
les in the gland plate are left open. The rating is affected
as follows :
2
Speed controller
for asynchronous motors
UMV 2301 AS
Warning
Gland plate not fitted
IP00
Gland plate fitted
Unused holes uncovered
IP10
Gland plate and glands fitted
Blanking caps covering unused holes
IP40
Gland plate hole diameter
Model size
Control signal
wiring
Power cables
UMV 2301 AS
8T to 16T
20 mm
3/4 in
20mm
3/4 in
UMV 2301 AS
22T to 50T
20 mm
3/4 in
28mm
11/4 in
UMV 2301 AS
60T to 120T
20 mm
3/4 in
28mm
11/4 in
Pages Preview: