Installation, Maintenance and
Operating Instructions
7 VG9H 70 en • 1/2019
2
7 VG9H 70 en
READ THESE INSTRUCTIONS FIRST!
These instructions provide information about the safe handling and operation of the ValvGuard.
If you require additional assistance, please contact the manufacturer or manufacturer's representative.
Addresses and phone numbers are printed on the back cover.
See also www.metso.com/valves for the latest documentation.
SAVE THESE INSTRUCTIONS!
Subject to change without notice.
All trademarks are property of their respective owners.
Table of Contents
1
NELES VALVGUARD VG9000H
INTELLIGENT SAFETY SOLENOID WITH HART
COMMUNICATION ................................................ 3
1.1
General........................................................................3
1.2
Technical description of VG9000H....................3
1.3
System architecture ...............................................4
1.4
Markings.....................................................................4
1.5
Technical specifications........................................5
1.6
Recycling and disposal.........................................8
1.7
Safety precautions..................................................8
2
TRANSPORTATION, RECEPTION AND
STORAGE ............................................................... 9
3
MOUNTING............................................................ 9
3.1
General........................................................................9
3.2
Mounting on Metso actuators with
VDI/VDE mounting face........................................9
3.3
Mounting on linear actuator with
IEC 60534 mounting face.....................................9
3.4
Mounting and installation of VG9300 ..........10
3.5
Piping .......................................................................11
3.6
Electrical connections.........................................15
4
LOCAL USER INTERFACE (LUI)............................16
4.1
Measurement monitoring.................................16
4.2
Guided start-up.....................................................17
4.3
Configuration menu...........................................17
4.4
Configuration parameters ................................17
4.5
Valve travel calibration.......................................19
4.6
Testing, TESt...........................................................19
4.7
Advance parameters...........................................20
4.8
Special displays.....................................................20
4.9
HART burst mode.................................................21
5
MAINTENANCE....................................................21
5.1
Opening and closing of the cover..................21
5.2
Prestage ..................................................................21
5.3
Spool valve ............................................................22
5.4
Communication circuit board ........................22
6
MESSAGES...........................................................23
7
TROUBLE SHOOTING.......................................... 24
8
VG9_H/D_, VG9_H/R_, VG9_H/I_, VG9_H/K_,
VG9_H/T01
(WITH LIMIT SWITCHES OR SIL PT).................... 24
8.1
Introduction............................................................24
8.2
Installing limit switches on ValvGuard..........27
8.3
Electrical connections.........................................27
8.4
Adjustment of limit switches............................27
8.5
Position transmitter (T01) calibration
instructions .............................................................27
8.6
Removal of the limit switches and position
transmitter for accessing the ValvGuard.....28
8.7
Circuit diagrams....................................................28
8.8
Maintenance...........................................................28
9
TOOLS.................................................................. 28
10
ORDERING SPARE PARTS................................... 28
11
DRAWINGS AND PARTS LISTS ........................... 29
11.1
Exploded view and parts list, VG9000H .......29
11.2
Exploded view and parts list,
VG9_/D_, VG9_/R_, VG9_/I_, VG9_/K_,
VG9_/T01 .................................................................31
11.3
Mounting parts for Metso B_U-series
actuators .................................................................33
11.4
Mounting parts for Quadra-Powr®
actuators .................................................................33
11.5
Mounting parts for linear actuators...............34
11.6
Connection diagrams..........................................35
12
DIMENSIONS ................................................... 42
13
CONFIGURATION PARAMETERS........................ 49
14
EC DECLARATION OF CONFORMITY ................. 50
15
TYPE CODING...................................................... 51
7 VG9H 70 en
3
1
NELES VALVGUARD VG9000H
INTELLIGENT SAFETY SOLENOID WITH
HART COMMUNICATION
1.1
General
This manual incorporates Installation, Maintenance and Oper-
ation Instructions for the Metso’s Neles ValvGuard VG9000H.
The VG9000H may be used with either cylinder or diaphragm
type pneumatic actuators for rotary or linear valves.
1.2
Technical description of VG9000H
Neles ValvGuard VG9000H is a 4–20 mA loop-powered
microcontroller-based intelligent safety solenoid and par-
tial stroke test device with HART communication. Device is
suitable to be used in safety related application up to and
including SIL 3 acc. to IEC 61508.
See Safety Manual for functional safety figures and other
safety related details.
The device safety position is 6.0 mA or below. When VG9_L3
version is used, the safety position is 10.0 mA or below. The
device stays alive even at 3.7 mA input signal (at 7.7 mA
when VG9_L3 is used) and communicates via HART.
Optional Remote Communication Interface RCI9H2 is
required if the safety system output is binary (DO) 24 V DC.
See separate RCI9H2 technical bulletin (9RCI21EN) for
detailed instructions.
Main components of ValvGuard are spool valve (SV), pre-
stage unit (PR) and micro controller (μC). Spool valve and
prestage unit are the only components, which takes part of
the safety action. Spool valve controls the main airflow
between supply- (S), actuator- (C1, C2) and exhaust (EXH)
connections. The spool is operated by spring force to fail
safe position and by pneumatic force generated by the pre-
stage valve to the normal position. The prestage valve is
coil operated flapper valve (normally open). Coil of the pre-
stage is energized with the safety control part and it is con-
trolled by the micro controller. Micro controller cannot
prevent the safety action. Pressure sensors (Px) and position
sensor (α) are used to getting the measurements for con-
trolling the PST and other tests. Measurements from the
sensors are used for the device diagnostics.
The VG9000H contains a Local User Interface enabling local
configuration. A PC with Metso Valve ManagerTM software
together with Metso's FieldCare or any other FDT frame soft-
ware can be used for advanced configuration and diagnostics.
The powerful 32-bit microcontroller controls the valve posi-
tion during partial stroke and other special testing. The
measurements include:
Input signal
Valve position with contactless sensor
Actuator pressures, 2 independent measurements
Supply pressure
Device temperature
Housing pressure
Advanced self-diagnostics guarantees that all measure-
ments operate correctly. Failure of any measurement does
not cause the valve to go to fail-safe position. After connec-
tions of electric signal and pneumatic supply the micro con-
troller (μC) reads the input signal, position sensor (α) and
pressure sensors (Ps, P1, P2 and P3). This information is used
to run the partial stroke tests and other tests.
1.2.1
Technical description of VG9000H_P
Neles ValvGuard VG9000H with P-option (VG9000H_P) is a
4–20 mA
loop-powered
microcontroller-based
partial
stroke test device with HART communication. This device is
for partial stroke test (PST) only and must be used together
with an additional solenoid valve for the safety action.
The prestage valve of the device is coil operated flapper
valve (normally open). Coil of the prestage is normally de-
energized and it is controlled by the micro controller for
testing and calibration. Signal failure does not affect to the
valve position.
NOTE:
The selection and use of the ValvGuard in a specific appli-
cation requires close consideration of detailed aspects.
Due to the nature of the product, this manual cannot
cover all the likely situations that may occur when install-
ing, using or servicing the ValvGuard.
If you are uncertain about the use of the controller or its
suitability for your intended use, please contact local
Metso office for more information.
NOTE:
HART communication can be used for informational pur-
poses, but is not safety certified for diagnostic annunciation.
NOTE:
RCI9H2 includes the Ex-isolator, so there is no need for
separate Ex-isolator in intrinsically safe installations.
NOTE:
Micro controller is only able to control the prestage if
safety control part is energized. Micro controller can never
prevent the safety action to happen since safety action is
the same as there’s no voltage in the safety control part.
Fig. 1
The principle of operation
NOTE:
VG9000H_P version has fundamentally different function-
ality to other VG9000H versions. This version can be iden-
tified by the green cover.
4
7 VG9H 70 en
The device stays alive even at 3.7 mA input signal and com-
municates via HART. 4 mA is a normal state of the device.
When input signal is 6 mA and above, PST is possible. When
input signal is 8 mA and above, PST and travel calibration
are possible. The valve cannot be driven from the normal
position by any input signal. Thus the safety action needs to
be done with an additional solenoid valve.
1.3
System architecture
VG9000H can be connected directly to safety system
analog output module (AO, 4-20 mA). See Fig. 2 for the gen-
eral wiring principle.
VG9000H can also be connected to safety system digital
output module (DO, 0/24 V DC) via RCI unit. See Fig. 3 for
the wiring principle with RCI unit.
There is also a Local Control Panel option (LCP9H_). It can
be used together with VG9000H or VG9000H with RCI unit.
See Fig. 4. for the wiring principles with Local Control Panel.
See Section 3.5 for wiring details. See LCP manual
(7LCP9H70en) for further LCP details. See RCI bulletin
(9RCI21en) for further RCI details.
VG9000H_P must be used together with an additional sole-
noid valve (SOV). See Fig. 5 for the general wiring principle.
1.4
Markings
The ValvGuard is equipped with an identification plate
(Fig. 6).
Identification plate markings include:
Type designation of the ValvGuard
Enclosure class
Revision number
Input signal (voltage range)
Input resistance
Maximum supply voltage
Supply pressure range
Operational temperature
CE mark
Manufacturing serial number TTYYWWNNNN*)
*) Manufacturing serial number explained:
TT = device and factory sign
YY = year of manufacturing
WW = week of manufacturing
NNNN = consecutive number
Example: PH13011234 = controller, year 2013, week 1,
consecutive number 1234.
Fig. 2
General wiring principle of VG9000H
Fig. 3
VG9000H wiring principle with RCI unit
Fig. 4
VG9000H wiring with Local Control Panel
Air supply
1. ValvGuard VG9000H
2. Pneumatic actuator
AO (mA) from safety system
Air supply
1. ValvGuard VG9000H
2. Pneumatic actuator
3. RCI9H2
DO (0/24 V DC) from safety system
24 V DC supply
Air supply
1. ValvGuard VG9000H
2. Pneumatic actuator
3. Local Control Panel LCP9H_
AO (mA)
from safety system
or from RCI unit
24 V DC or 4 mA
supply depending
on the LCP type
Serial
communication
Fig. 5
VG9000H_P wiring with additional solenoid valve
Fig. 6
Examples of identification plates
1. ValvGuard VG9000H_P
2. Pneumatic actuator
3. Solenoid Valve
3
2
1
TYPE VG9215HE6
REV 2.0
METSO AUTOMATION OY VANHA PORVOONTIE 229, 01380 VANTAA, FINLAND
NO:
PH11020005
ID:
SO519559001POS
II 2 G Ex d IIC T6...T4 Gb
II 2 D Ex tb IIIC T80 °C...T105 °C Db IP66
SIRA 11 ATEX 1006X / IECEx SIR 11.0001X
4 - 20 mA INPUT: (9.7 V DC / 20 mA / 485 Ohm) Ui: 30 V DC
Tamb. T6: -20 ... +60 °C, T5: -20 ... +75 °C, T4: -20 ... +85 °C
SUPPLY PRESSURE: 3 - 7.5 bar / 44 - 109 psi
CONDUIT ENTRY M20X1.5
WARNING: DO NOT OPEN WHILE ENERGIZED!
0575