© Munters AB, 2013 P/N: 110538
Ag/MIS/IGB-229310/15 Rev. 1.5
Relay Expansion Box for Platinum Pro and
Platinum Touch
(P/N: 900-07-XXXXX)
(P/N: 900-14-XXXXX)
© Munters AB, 2013 P/N: 110538
Ag/MIS/IGB-229310/15 Rev. 1.5
Wiring Diagrams
1. Wire the Platinum Pro PP-485ISO-485/PP232ISO-485 card to the Platinum Expansion RS-485
card.
Figure 1: Platinum Pro to Platinum Expansion Wiring
Figure 2: Platinum Pro to Platinum 30 Expansion Wiring
2. To ensure proper termination, place a:
•
A terminator on the EXP jumpers on the Platinum Pro communication card (if the Platinum
Pro is located at the end of a daisy chain)
© Munters AB, 2013 P/N: 110538
Ag/MIS/IGB-229310/15 Rev. 1.5
•
A 120 ohm resistor on the Platinum Expansion communication card
3. The Controller and Expansion RS-485 cards each have dip switches that define the unit's function
and address.
•
Define the Controller's RS-485 card dip switches as Main.
•
Define the Expansion units dip switches as required.
Table 1: Dip Switch Settings
SWO Position
SW1 Position
Main
Off
Off
Extension 1
Off
On
Extension 2
On
Off
Extension 3
On
On
Figure 3: Platinum Pro Address Dip Switches
4. Connect the relays as required. Refer to the Platinum Pro/Touch Installation manual for details.
5. Attach the power wiring to the Expansion as shown below.