Model MT
Sizes 500 - 1825
IMPORTANT: Store these instructions in the
pocket provided on the heater
Installation and Operation
Instructions for
MegaTherm
Pool Heating Boiler
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed by
a qualified installer, service agency, or gas
supplier.
FOR YOUR SAFETY: This product must be installed and serviced by a
professional service technician, qualified in hot water boiler installation and
maintenance. Improper installation and/or operation could create carbon
monoxide gas in flue gases which could cause serious injury, property
damage, or death. Improper installation and/or operation will void the
warranty.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inflammables dans
le voisinage de cet appareil ou de tout autre
appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
•
Ne pas tenter d’allumer d’appareils.
•
Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
vous trouvez.
•
Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
•
Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
P/N 472643 Rev A - 05/22/06
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
®
TM
Pentair Water Commercial Pool and Spa
Page 2
TABLE OF CONTENTS
SECTION 1.
General Information
1.1
Introduction................................................... 3
1.2
Heater Identification ..................................... 3
1.3
Primary/Secondary Pump and Piping........... 3
1.4
Certifications................................................. 3
1.5
Engineering Assistance ................................ 3
SECTION 2.
Installation
2.1
Boiler Placement .......................................... 4
2.2
Installation of Indoor Boilers ......................... 4
2.2.1
Combustion Air Supply ................................. 4
2.2.2
Venting ......................................................... 5
2.2.3
Common Venting System
Test Procedure ............................................. 6
2.2.3
Instructions Relatives au Test des
Systèmes à Évent Commun ......................... 6
2.3
Installation of Outdoor Boilers ...................... 7
2.4
Gas Supply and Piping ................................. 7
2.5
Electrical Wiring............................................ 8
2.6
General Piping Instructions .......................... 9
2.7
Boiler By-Pass Piping ................................... 9
2.8
Temperature Sensor Placement
and Installation ............................................ 10
2.9
Automatic Chlorinators ............................... 10
SECTION 3.
Operation
3.1
Controls - General ...................................... 11
3.2
Initial Start-Up............................................. 11
3.3
Safety Shutoff Component Checkout ......... 12
3.4
Inlet Temperature and
Temperature Rise Adjustment .................... 12
3.5
Heater Shut Down ...................................... 13
3.6
Spring and Fall Operation
Stand-by Service ........................................ 13
3.7
Winter Operation Complete Shutdown ....... 14
3.8
Time Clock Operation................................. 14
3.9
Therapeutic Pools (Spas) ........................... 14
SECTION 4.
Maintenance..............................................15
SECTION 5.
Troubleshooting .......................................16
SECTION 6.
Parts Description and Order Numbers ................ 17
Pentair Technical Support
Sanford, North Carolina (8 A.M. to 5 P.M.)
Phone: (800) 831-7133
Fax: (919) 566-8920
Moorpark, California (8 A.M. to 5 P.M.)
Phone: (800) 831-7133
Fax: (800) 284-4151
Web sites: visit www.pentairpool.com and www.staritepool.com
MegaTherm Commercial Pool Heating Boiler
Page 3
SECTION 1.
General Information
1.1 Introduction
This manual provides information for the
installation and operation of MegaTherm model MT
pool heating boilers. It is strongly recommended that
all application and installation procedures be reviewed
completely before proceeding with the installation.
Consult Pentair Commercial Pool and Spa, or your
local sales representative, with any problems or
questions regarding this equipment. Experience has
shown that most problems are caused by improper
installation, not system design.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on the
packing slip. Inspect everything for possible damage
upon delivery, and inform the carrier of any shortages
or impairments. Any such claims should be filed with
the carrier. The carrier, not the shipper, is responsible
for shortages and damage to the shipment whether
visible or concealed.
The warranty does not apply to heaters not
installed or operated in accordance with these
procedures. Consult local building and safety codes
before proceeding with work. The installation must
conform to the requirements of the authority having
jurisdiction or, in the absence of such requirements, to
the latest edition of the National Fuel Gas Code; ANSI
Z223.1, National Electrical Code ANSI/NFPA 70. In
Canada, the installation must conform with the latest
edition of CSA-B149.1 requirements.
When required by the authority having
jurisdiction, the installation must conform to
Figure 1. Heater Identification (model nomenclature).
WARNING
The MegaTherm model MT commercial pool
heating boiler must be used on potable water
only. For heating pools containing salt water, a
specially equipped heater must be used;
consult your distributor or factory
representative. The pool heating boiler must be
installed in accordance with the procedures
MODEL
MT-POOL
REVISION
P-PUMP (U.S.)
Q-PUMP (CAN)
HEAT EXCHANGER
C-GLASS LINED/COPPER
N-GLASS LINES/CU-NI
K-BRONZE/COPPER
S-BRONZE/CU-NI
VERSION
1 - 8 TUBE
B-10 TUBE
I-INDOOR
E-OUTDOOR
FUEL
N-NATURAL
P-PROPANE
IGNITION
04-SPARK 110V
09-SPARK 24V
11-SPARK 24V
16-STND. PILOT
SIZE
BTU/HR X 1000
0500
0600
0715
0850
0999
1010
1200
1430
1670
1825
C
FIRING MODE
ON/OFF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
American Society of Mechanical Engineers safety
codes for controls and safety devices for automatically
fired heaters No. CSD-1, and in Canada CGA 3.3.
Any modification of the heater, its gas controls, gas
orifices, wiring or drafter diverter may void the
warranty. If field conditions require such
modifications, consult factory.
1.2 Heater Identification
Consult rating plate on the heating boiler. Shown
below is a breakdown of the model nomenclature.
Commercial pool heating boilers are available in two
configurations: an indoor version and an outdoor
version. Outdoor models are not available in Canada.
1.3 Primary/Secondary Pump and Piping
All models are supplied with integrally mounted
pumps. The 1825 models use a 3/4 HP pump and all
other models are supplied with 1/2 HP pumps. These
pumps are sized for the pressure drop through the heat
exchanger and through the bypass piping as shown in
Figure 10.
Any deviations from the arrangement shown may
increase the head on the pump, reduce flow and hinder
performance (see Section 2.7). For spas see Section
3.9.
This piping arrangement and the integral pump
allow hot water to be recirculated to the heater inlet,
thus raising the inlet temperature and greatly reducing
condensation.
1.4 Certifications
All models are design-certified by CSA for
natural or propane gas and conform to ASME Code
requirement for 160 PSI water pressure.
1.5 Engineering Assistance
Consult the factory or distributor regarding any
questions or problems which arise in the specification,
installation or operation of this equipment. An
experienced engineering staff is ready to assist in
assuring the proper performance and application of
this products.
Pentair Water Commercial Pool and Spa
Page 4
SECTION 2.
Installation
2.1 Boiler Placement
The pool heating boiler must be placed to
provide specific clearances on all sides for
maintenance and inspections. There must also be
minimum distances maintained from combustible
surfaces. These clearances also apply to
noncombustible materials because the pool heating
boiler requires air circulation for proper operation.
The pool heating boiler should be mounted on a
level surface. An integral base for an installation on
combustible flooring is provided as standard
equipment on outdoor models. For indoor models,
special base rails part number 10539000 must be used
for combustible flooring.
Do not install a pool heating boiler on carpeting.
Under the national Fuel Gas Code, ANSI
Z223.1, it is permissible to place the boiler on floors
other than noncombustible when the installation
complies with the American Insurance Code. Figures
2, 3, 4 and 5 show common installation on
combustible flooring.
2.2 Installation of Indoor Boilers
Locate the pool heating boiler to provide
adequate clearance for inspection and service on all
sides. See Table 1. For alcove installation, see
Figure 6.
Install indoor heaters on a waterproof floor with
an adequate floor drain and a 6" (152mm) minimum
curb on all four sides to protect the building if heater
repairs are required. The manufacturer will not be
held liable for any water damage in connection
with this boiler.
2.2.1 Combustion Air Supply
The heater location must provide sufficient air
supply for proper combustion and ventilation of the
surrounding area as outlined in the latest edition of
ANSI standard Z223.1, and any local codes that may
be applicable. Inadequate combustion air supply may
result in incomplete combustion, sooting of the heat
exchanger, and unsafe operation of the boiler.
a. Conventional Ventilation
In the United States, the most common of these
requirements specify that boiler rooms should be
provided with two permanent air supply openings
communicating directly through the wall to outside air
one within 12 inches (305mm) of the ceiling, and the
other within
12 inches (305mm) of the floor. Each opening should
have a minimum free area of one square inch
(6.5 sq. cm) per 4,000 BTU/hr input of the total input
rating of all appliances in the enclosed area. See Table
2 for recommended air supply for each model. An
Clearance
Indoor
Outdoor
from
in.
mm
in.
mm
Top
30
762
unobstructed
Water Conn. side
12*
305
24
610
Pump side
6*
152
24
610
Front
Alcove*
unobstructed
Rear
8
203
24
610
Vent pipe**
6
152
- - -
Hot water pipes
per code
per code
* Water connection and pump side clearances of 24" (610mm)
and front clearances of 48" (1219mm) will allow easier
service access.
** Using type B vent (refer to Manufacturer's Instructions).
Table 1. Minimum boiler clearances from
adjacent surfaces.
Figure 2.
Typical Boiler Installation on Concrete Slab.
Figure 3.
Typical Boiler Installation on Roof Using
Raised Platform (wood).
improperly ventilated equipment room can get
excessively hot and cause accelerated deterioration
of controls and electrical components.
In Canada, Table 2 does not apply. Consult local
building codes or, in the absence of such
requirements, follow CSA-B149.1 standard.