Document Preview & Text Transcription
Catalog No.: 2100.50P
Effective: 11-01-99
Replaces: 6-01-99
P/N 240488
THIS MANUAL SHOULD BE MAINTAINED IN LEGIBLE CONDITION
AND KEPT ADJACENT TO THE BOILER OR KEPT IN A SAFE PLACE
FOR FUTURE REFERENCE.
®
OPERATING AND
INSTALLATION
INSTRUCTIONS
Models
0030B, 0042B, 0066B, 0090B
0135B, 0180B
Type H
RESIDENTIAL BOILERS
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and liquids or other combustible materials
in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause
property damage, personal injury or loss of life. Refer to the user's information manual provided
with this boiler. Installation and service must be performed by a qualified installer, service agency
or the gas supplier.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
*Do not try to light any appliance.
*Do not touch any electrical switch; do not use any phone in your building.
*Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's
instructions.
*If you cannot reach your gas supplier, call the fire department.
These instructions are provided to assure the proper
installation and operation of Raypak boilers. Should
questions arise regarding the specifications, installa-
tion, operation or servicing of these boilers, we suggest
that the local Sales representative or the factory be
consulted.
2
3
1. RECEIVING EQUIPMENT
3
2. GENERAL SPECIFICATIONS AND DIMENSIONS
4
3. INSTALLATION PROCEDURES
4
- Code Requirements
4
- Mounting Base
4
- Clearance Requirements
4
- Combustion/Ventilation Air
5
- Venting Connections
7
- Vent Damper Installation
10
- Gas Supply Connections
10
- Water Connections & System Piping
14
- Electrical Wiring
22
4. SERVICING PROCECURES
22
- General Locations of Controls
22
- Sequence of Operation
23
- Start Up Procedures
28
- Safe Shutdown Test
28
- Normal Inspection Procedures
29
- Repair Section
31
5. TROUBLE SHOOTING GUIDE
33
- Adjustments/Replacements of Components
34
6. REPLACEMENT PARTS LIST
Contents
1. RECEIVING EQUIPMENT
On receipt of your equipment it is suggested that
you visually check for external damage to the carton. If
the carton is damaged, it is suggested that a note be
made on the Bill of Lading when signing for equipment.
Remove the boiler from the carton and if it is damaged
report the damage to the carrier immediately. Be
sure that you receive the number of packages indicated
on the Bill of Lading. Claims for shortages and
damages must be filed with carrier by consignee.
Purchased parts are subject to replacement only
under the manufacturer's warranty. Debits for defective
replacement parts will not be accepted and defective
parts will be replaced in kind only per our standard
warranties.
When ordering parts, you must specify Model and
Serial Number of boiler. When ordering under warranty
conditions, you must also specify date of installation.
Raypak recommends that this manual be re-
viewed thoroughly before installing your Raypak
Boiler. If there are any questions which this manual
does not answer, please contact your local Raypak
representative.
2. GENERAL SPECIFICATIONS
The Raypak hydronic boilers are design certified by
the American Gas Association, and tested under the
requirements of the American National Standard, ANSI
Z21.13. Each boiler has been constructed and pressure
tested in accordance with the requirements of Section
IV of the American Society of Mechanical Engineers
Code, and factory fire tested.
The boilers are designed for indoor installation with
a built-in drafthood, and a built-in sub-base for combus-
tible flooring. Models are available with standing pilot,
or with intermittent ignition device (I.I.D.). The boilers
are equipped with the following components: water
circulation pump, pressure relief valve, temperature/
pressure gauge, adjustable high limit switch, drain
valve, fast response temperature sensor, 40 VA trans-
former, pump relay, vent thermal switch, flame roll-out
switch, and redundant combination gas valve for use
with either natural or propane gases. Two-staged gas
valve (50% firing on 1st stage) is standard on models
H-0090, H-0135 and H-0180.
The automatic ignition models and some standing
pilot models are provided with a plug-in connector that
is compatible with the Honeywell D80D vent damper.
Similar type vent dampers made by other manufactur-
ers, and design certified by a nationally-recognized
testing Agency, under the ANSI Z21.66 standards, may
also be used.
Follow the installation instructions furnished with the
vent damper package. The plug-in connector can also
be used with power venters. Refer to the specific
installation instructions supplied by the power vent
manufacturer.
SPECIFICATIONS AND DIMENSIONS
3
K
16
41/2
331/4
221/8
121/2
5
18
31/4
261/2
C
THERMOSTAT CONN
(ELECTRICAL CONN
ON OTHER SIDE)
GAS
CONN
3/4 NPT PIPE
TO DRAIN
A
117/8
6
INLET
OUTLET
31/8
MIN
19
AUTOMATIC
VENT DAMPER
(FIELD INSTALLED)
B
HEATING
NET
K
INPUT CAPACITY
I=B=R WATER
GAS
VENT
MODEL MBH
MBH
RATING NPT.
NPT.
A
B
C
DIA.
H-0030
30
25
22
1"
1/2"
11"
5 3/4
5 1/2
4"
H-0042
42
35
30
1"
1/2"
11"
5 3/4
5 1/2
4"
H-0066
66
54
47
1"
1/2"
11"
5 3/4
5 3/4
5"
H-0090
90
74
64
1"
1/2"
11"
5 3/4
5 3/4
5"
H-0135
135
109
95
1 1/4"
1/2"
18"
6 1/4
6 1/4
6"
H-0180
180
148
129
1 1/4"
1/2"
18"
6 1/4
8.0
7"
CONNECTIONS
PIPING
Fig. #8978.1
3. INSTALLATION PROCEDURES
CODE REQUIREMENTS
Installation must be in accordance with local
codes, or, in the absence of local codes, with the latest
editions of the National Fuel Gas Code, ANSI Z223.1,
and the National Electrical Code, ANSI/NFPA 70. In
Canada installations must conform with the current
CAN/CGA B149.1 or .2 and the Canadian Electrical
Code Part 1 CSA C22.2 No.1. Where required by the
authority having jurisdiction, the installation must con-
form to American Society of Mechanical Engineers
Safety Code for Controls and Safety Devices for Auto-
matically Fired Boilers, No. CSD-1.
MOUNTING BASE
Boiler should be mounted on a level surface. Each
boiler is designed with a built-in sub-base approved for
mounting the boiler on combustible flooring. Boiler
must NOT be installed on carpet flooring.
CARPET
NOTE: The boiler should be located in an area where
water leakage will not result in damage to the area
adjacent to the appliance or to the structure. When
such locations cannot be avoided, it is recommended
that a suitable drain pan, adequately drained, be in-
stalled under the appliance. The pan must not restrict
air flow.
In addition, the boiler shall be installed such that
the gas ignition system components are protected from
water (dripping, spraying, rain, etc.) during appliance
operation and service (circulator replacement, control
replacement, etc.)
4
CLEARANCE REQUIREMENTS
1) Minimum Clearances From Combustible Materials
Model Floor Front Back Right Left Top Flue
No.
Vent
0030
0042 Comb. 4" 6" 6" 6" 16" 6"
0066
0090
0135 Comb. Alcove 6" 6" 6" 16" 6"
0180
2) A front clearance of at least 24" is recommended for
adequate service of burner-tray and controls.
3) Except for carpeted flooring, boilers are certified for
installation on combustible floors.
4) For un-insulated hot water pipes, maintain a 2"
clearance, or consult local authority having jurisdic-
tion.
COMBUSTION/VENTILATION AIR
WARNING: Air supply to the boiler room must not be
affected by mechanical exhaust vents located in other
parts of the house, such as kitchen or bathroom fans,
or attic blowers. Mechanical exhaust vents may create
a negative pressure condition in the boiler room that
can become a hazard of asphyxiation, explosion or fire.
CAUTION: Combustion air must not be contaminated
by corrosive chemical fumes which can damage the
boiler. Measures must be taken to prevent the entry of
corrosive chemical fumes to the combustion and ven-
tilation air supply. Such chemicals include, but are not
limited to, chlorinated and/or fluorinated hydrocarbons
such as found in refrigerants, aerosol propellants, dry-
cleaning fluids, degreasers, and paint removers. Other
harmful elements may come from bleaches, air fresh-
eners, or mastics. Vapors from these types of products
can form corrosive acid compounds when burned in a
gas flame. The resulting acid condensate can damage
or substantially reduce the life of the heater. It may be
necessary to provide outside air directly to the heater in
order to avoid this problem.
1) The boiler must be provided with adequate supply of
air for proper combustion and ventilation in accor-
dance with Sec. 5.3, of the latest edition of the
National Fuel Gas Code, ANSI Z223.1, or appli-
cable provisions of the local building codes.
CARPET
Fig.# 8196.0p