Advantech WebAccess Device Driver Guide
Sharp JW 10 Serial
Version 6.0 rev 0
Advantech Corp., Ltd.
page 1
Sharp JW10 Serial
Programmable PLC
Device Driver Guide
Advantech WebAccess Device Driver Guide
Sharp JW 10 Serial
Version 6.0 rev 0
Advantech Corp., Ltd.
page 2
Table of Contents
DEVICE DRIVER GUIDE ........................................................................................................................... 1
1.
SHARP JW10 SERIAL DEVICE COMMUNICATIONS................................................................ 3
1.1
SUMMARY: JW10 DEVICE DRIVER .................................................................................................. 3
1.1.1
Wiring and Cabling ................................................................................................................ 3
1.1.2
PLC Settings ........................................................................................................................... 3
2.
WEBACCESS: PARAMETERS ......................................................................................................... 5
3.
CONFIGURE A SHARP JW DEVICE .............................................................................................. 5
3.1
SUMMARY ....................................................................................................................................... 5
3.2
SERIAL COMPORT PROPERTIES ........................................................................................................ 6
3.2.1
Comport Number .................................................................................................................... 7
3.2.2
Description ............................................................................................................................. 7
3.2.3
Baud Rate ............................................................................................................................... 7
3.2.4
Data Bits ................................................................................................................................. 8
3.2.5
Stop Bits .................................................................................................................................. 8
3.2.6
Parity ...................................................................................................................................... 8
3.2.7
Scan Time ............................................................................................................................... 8
3.2.8
Timeout ................................................................................................................................... 8
3.2.9
Retry Count ............................................................................................................................. 8
3.2.10
Auto Recover Time .................................................................................................................. 9
3.2.11
Hand Shake RTS ..................................................................................................................... 9
3.2.12
Hand Shake DTR .................................................................................................................... 9
3.2.13
Backup Port ............................................................................................................................ 9
3.3
DEVICE PROPERTIES - SHARPJW ..................................................................................................... 9
3.3.1
Device Name ..........................................................................................................................10
3.3.2
Description ............................................................................................................................10
3.3.3
Unit Number ..........................................................................................................................10
3.3.4
Device Type ...........................................................................................................................10
4.
CONFIGURE TAGS ...........................................................................................................................11
4.1
ANALOG TAG .................................................................................................................................11
4.2
DIGITAL TAG ..................................................................................................................................12
Advantech WebAccess Device Driver Guide
Sharp JW 10 Serial
Version 6.0 rev 0
Advantech Corp., Ltd.
page 3
1. Sharp JW10 Serial Device
Communications
1.1
Summary: JW10 Device Driver
The WebAccess SCADA Node provides a serial interface to the Sharp New
Satellite JW10 Programmable PLC using the Computer Link.
1.1.1 Wiring and Cabling
There are two physical types of connections to the Sharp JW10:
1. MMI Port (this is the method tested for this manual).
2. 2-wire RS-422 Communication Terminals. This method was not
tested for this manual.
Please refer to the Manufacturer’s Documentation for a description of wiring
and cabling.
1.1.1.1
MMI Port
The MMI Port is a 9-pin port of the front of the PLC. This is the method
tested for this manual.
This is a one-to-one Link (one PLC per com port).
This Guide was tested using a 9-pin to 9-pin cable labeled JW10/TP02 PC.
The Sharp User’s Manual describes a cable from Sharp (model JW-12KC).
This
is a 9 pin to 25-pin cable.
1.1.1.2
2-wire Communications Port
The Computer Link can also be via the Communication Port. This is a two
wire, RS-422A connection on the Lower terminals of the Model JW-1642K
PLC. This is a multiple drop link (up to 63 PLCs per comport). This method
was not tested for this manual.
The Lower Terminals of the JW-1624K used for 2-wire RS-422 are labeled L1,
L2 and SHLD. Shielded twisted pair is required.
1.1.2 PLC Settings
1.1.2.1
MMI Port
The default settings (memory #226 = 00000000) are:
Data Length = 7 bits
Stop Bits = 1
Parity = None
Transfer Rate = 19200
PLC Address = 01
When using the computer link mode of the MMI Port, the following system
memory settings are used to set Data Length, Stop Bit, Parity and Transfer
Rate.
Advantech WebAccess Device Driver Guide
Sharp JW 10 Serial
Version 6.0 rev 0
Advantech Corp., Ltd.
page 4
System Memory Number: #226
Description: Transfer specifications
Format: D7,0,D5,D4,D3,D2,D1,D0
D7=Data Length:
D7=0= 7 bits;
D7=1= 8 Bits
D5=Stop Bits:
D5=0=1 bit;
D5=1=2 bits
D4,D3= Parity:
0,0 = None
0,1 = Odd
1,0 = Even
1,1 = Disabled
D2, D1, D0 = Transfer Rate (Bits / sec):
1,1,1 = 38400
0,0,0 = 19200
0,0,1 = 9600
0,1,0 = 4800
0,1,1 = 2400
1,0,0 = 1200
1,0,1 = 600
1,1,0 = 300
Since only one-to-one communications via the MMI port, the PLC address is
01.
The settings tested for this Device Driver Guide where the default:
Data Length = 7 bits
Stop Bits = 1
Parity = None
Transfer Rate = 19200
1.1.2.2
2-wire Communications Port
The JW10 has a two-wire Communications port for using the computer link,
data link or remote IO. This function is determined by system memory #234:
#234 = 0 = Computer Link Mode (required by WebAccess)
#234 = 1 = Data Link
#234 = 2 = Remote I/O Link.
System Memory #236 sets the Transfer specification for the 2-wire
Communications Port.
The default settings (memory #236 = 00000000) are:
Data Length = 7 bits
Stop Bits = 1
Parity = None
Transfer Rate = 19200
PLC Address = 01
System Memory Number: #236
Description: Transfer specifications
Format: D7,0,D5,D4,D3,D2,D1,D0
D7=Data Length:
D7=0= 7 bits;
D7=1= 8 Bits
D5=Stop Bits: