Manual [PDF] (20 pages)
- Updated: 26.06.2026
Document Preview & Text Transcription
CC1N7153en
14.10.2002
Siemens Building Technologies
HVAC Products
ISO 9001
7153
Oil Burner Controls
LAL...
Oil burner controls
�
With or without air pressure supervision for checked air damper control
�
Flame supervision with
– photoresistive detector QRB1..., or
– blue-flame detector QRC1..., or
– selenium photocell detector RAR...
The LAL... and this Data Sheet are intended for OEMs which integrate the oil
burner controls in their products!
Use
-
For the control and supervision of oil atomization burners
-
For burners of medium to high capacity
-
For intermittent operation (at least one controlled shutdown every 24 hours)
-
Can be universally used with multistage or modulating burners
-
Suited for use with stationary air heaters
LAL1...
- Yellow- and blue-flame burners without air pressure supervision
LAL2...
- Yellow-flame burners with air pressure supervision
LAL3.25
- For special applications, e.g. burners of incinerator plants
(for details, refer to «Type summary» and «Notes»)
LAL4...
- Yellow- and blue-flame burners with air pressure supervision
For burner controls used in connection with burners for continuous operation, refer to
Data Sheet 7785 (LOK16...).
2/20
Siemens Building Technologies
CC1N7153en
HVAC Products
14.10.2002
Warning notes
To avoid injury to persons, damage to property or the environment, the following
warning notes should be observed!
Do not open, interfere with or modify the unit!
�
Before performing any wiring changes in the connection area of the LAL…, com-
pletely isolate the burner control from the mains supply (all-polar disconnection)
�
Ensure protection against electric shock hazard by providing adequate protection
for the burner control’s connection terminals
�
Check to ensure that wiring is in an orderly state and that the wires are firmly con-
nected
�
Press the lockout reset button / operation button only manually (applying a force of
no more than 10 N), without using any tools or pointed objects
�
Do not press the lockout reset button on the unit or the remote reset button
for more than 10 seconds since this damages the lockout relay in the unit
�
Fall or shock can adversely affect the safety functions. Such units may not be put
into operation, even if they do not exhibit any damage
3/20
Siemens Building Technologies
CC1N7153en
HVAC Products
14.10.2002
Engineering notes
�
Install switches, fuses, earthing, etc., in compliance with local regulations
�
Connect valves and other plant components as specified in the burner manufac-
turer’s documentation
H
N
L
EK2
AL
21
1
2
1(3)
3
M1
M2
R
4
5
6
7
BV2
BV1
Z
SA
15
16 17 18
a
z
M
20
19
9
LR
7153a03/0302
24
m
LK
11 10
8
22
B
v
LP
13 12 14
23
LAL2
1
2
3
4
5
6
7
8
9
10
QRB1...
22
24
+
RAR...
SB
W
�
Connect safety limit thermostats (manual reset) in the line (e.g. «SB»)
�
Remote reset
When connecting lockout reset button «EK2» between terminals 21 and
- 3: For remote reset only
- 1: For remote reset and remote emergency shutdown
With LAL…: Required switching capacity of
- switching devices connected between terminals 4 and 5 (refer to «Technical data»)
�
With LAL2... / LAL3... / LAL4...: Required switching capacity of
- switching devices connected between terminal 12 and «LP» (refer to «Technical data»)
- «LP» (refer to «Technical data»)
When using series connection, the control contacts of other devices contained in the burner plant must be con-
nected as follows:
To terminal 4 or 5 � contacts that must be closed from startup to controlled shutdown � otherwise no startup
or shutdown
To terminal 12 (not with LAL1...) � contacts that must only be closed on startup � otherwise no startup
�
To terminal 14 (not with LAL1...) � contacts that must be closed no later than at the beginning of «t3» or «t3´»
and that must remain closed until controlled shutdown occurs � otherwise lockout
�
Maximum current draw, refer to «Technical data»
�
«Z» connected to terminal 15 � «t3´» and «t3n»
�
Connection of «BV...» to terminal 20, refer to «Connection examples»
�
When using burners without air damper, or with an air damper not controlled and monitored by the LAL…, ter-
minal 8 must be connected to terminal 6
�
Wire link «B» clearly marked on the underside of the LAL…
When wire link «B» is fitted, the LAL... initiates lockout if loss of flame occurs during operation. For repetition of
the startup sequence, wire link «B» on the plug-in section of the LAL... must be cut away. Just cutting is not
permitted!
�
For the permissible lengths and laying of detector cables, refer to «Flame supervision»
Mounting notes
�
Ensure that the relevant safety regulations are complied with