Siemens LAL1.25 Manuals

3 pdf manual(s) Siemens LAL1.25 for free download (Document Types: Manual )

Siemens LAL1.25 Manual  Main Page Preview

Manual  [PDF] (20 pages)

  • Updated: 26.06.2026

Document Preview & Text Transcription

CC1N7153en 14.10.2002 Siemens Building Technologies HVAC Products ISO 9001 7153 Oil Burner Controls LAL... Oil burner controls � With or without air pressure supervision for checked air damper control � Flame supervision with – photoresistive detector QRB1..., or – blue-flame detector QRC1..., or – selenium photocell detector RAR... The LAL... and this Data Sheet are intended for OEMs which integrate the oil burner controls in their products! Use - For the control and supervision of oil atomization burners - For burners of medium to high capacity - For intermittent operation (at least one controlled shutdown every 24 hours) - Can be universally used with multistage or modulating burners - Suited for use with stationary air heaters LAL1... - Yellow- and blue-flame burners without air pressure supervision LAL2... - Yellow-flame burners with air pressure supervision LAL3.25 - For special applications, e.g. burners of incinerator plants (for details, refer to «Type summary» and «Notes») LAL4... - Yellow- and blue-flame burners with air pressure supervision For burner controls used in connection with burners for continuous operation, refer to Data Sheet 7785 (LOK16...). 2/20 Siemens Building Technologies CC1N7153en HVAC Products 14.10.2002 Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes should be observed! Do not open, interfere with or modify the unit! � Before performing any wiring changes in the connection area of the LAL…, com- pletely isolate the burner control from the mains supply (all-polar disconnection) � Ensure protection against electric shock hazard by providing adequate protection for the burner control’s connection terminals � Check to ensure that wiring is in an orderly state and that the wires are firmly con- nected � Press the lockout reset button / operation button only manually (applying a force of no more than 10 N), without using any tools or pointed objects � Do not press the lockout reset button on the unit or the remote reset button for more than 10 seconds since this damages the lockout relay in the unit � Fall or shock can adversely affect the safety functions. Such units may not be put into operation, even if they do not exhibit any damage 3/20 Siemens Building Technologies CC1N7153en HVAC Products 14.10.2002 Engineering notes � Install switches, fuses, earthing, etc., in compliance with local regulations � Connect valves and other plant components as specified in the burner manufac- turer’s documentation H N L EK2 AL 21 1 2 1(3) 3 M1 M2 R 4 5 6 7 BV2 BV1 Z SA 15 16 17 18 a z M 20 19 9 LR 7153a03/0302 24 m LK 11 10 8 22 B v LP 13 12 14 23 LAL2 1 2 3 4 5 6 7 8 9 10 QRB1... 22 24 + RAR... SB W � Connect safety limit thermostats (manual reset) in the line (e.g. «SB») � Remote reset When connecting lockout reset button «EK2» between terminals 21 and - 3: For remote reset only - 1: For remote reset and remote emergency shutdown With LAL…: Required switching capacity of - switching devices connected between terminals 4 and 5 (refer to «Technical data») � With LAL2... / LAL3... / LAL4...: Required switching capacity of - switching devices connected between terminal 12 and «LP» (refer to «Technical data») - «LP» (refer to «Technical data») When using series connection, the control contacts of other devices contained in the burner plant must be con- nected as follows: To terminal 4 or 5 � contacts that must be closed from startup to controlled shutdown � otherwise no startup or shutdown To terminal 12 (not with LAL1...) � contacts that must only be closed on startup � otherwise no startup � To terminal 14 (not with LAL1...) � contacts that must be closed no later than at the beginning of «t3» or «t3´» and that must remain closed until controlled shutdown occurs � otherwise lockout � Maximum current draw, refer to «Technical data» � «Z» connected to terminal 15 � «t3´» and «t3n» � Connection of «BV...» to terminal 20, refer to «Connection examples» � When using burners without air damper, or with an air damper not controlled and monitored by the LAL…, ter- minal 8 must be connected to terminal 6 � Wire link «B» clearly marked on the underside of the LAL… When wire link «B» is fitted, the LAL... initiates lockout if loss of flame occurs during operation. For repetition of the startup sequence, wire link «B» on the plug-in section of the LAL... must be cut away. Just cutting is not permitted! � For the permissible lengths and laying of detector cables, refer to «Flame supervision» Mounting notes � Ensure that the relevant safety regulations are complied with
Siemens LAL1.25 Manual  Main Page Preview

Manual  [PDF] (24 pages)

  • Updated: 27.08.2026

Document Preview & Text Transcription

CC1N7153en 21.09.2016 Building Technologies Division 7 153 Oil Burner Controls LAL... Oil burner controls  For oil atomizing burners of medium to large capacity  For multistage or modulating burners in intermittent operation  With or without air pressure supervision for checked air damper control  Flame supervision – with photoresistive detector QRB – or blue-flame detector QRC1 – or silicon photocell detector RAR9  Suitable for use with air heaters (WLE) The LAL and this Data Sheet are intended for OEMs which integrate the oil burner controls in their products! Use  For the control and supervision of oil atomization burners  For burners of medium to high capacity  For intermittent operation (at least one controlled shutdown every 24 hours)  Can be universally used with multistage or modulating burners  Suited for use with stationary air heaters (WLE) The flame supervision is ensured via a Photoresistive detectors QRB,blue-flame detectors QRC1 or Silicon photocell detectors RAR9. LAL1 - Yellow- and blue-flame burners without air pressure supervision LAL2 - Yellow-flame burners with air pressure supervision LAL3.25 - For special applications, e.g. burners of incinerator plant (for details, refer to «Type summary» and «Notes») 2/24 Building Technologies Division CC1N7153en 21.09.2016 Supplementary documentation Product type Type of documentation Documentation number LOK16 (For burner controls used in connection with burners for continuous operation) Data Sheet N7785 Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes must be observed! Do not open, interfere with or modify the unit!  All activities (mounting, installation and service work, etc.) must be performed by qualified staff  Before making any wiring changes in the connection area, completely isolate the plant from mains supply (all-polar disconnection). Ensure that the plant cannot be inadvertently switched on again and that it is indeed dead. If not observed, there is a risk of electric shock hazard  Ensure protection against electric shock hazard by providing adequate protection for the burner control’s connection terminals  Each time work has been carried out (mounting, installation, service work, etc.), check to ensure that wiring is in an orderly state and make the safety checks as described in «Commissioning notes»  Press the lockout reset button only manually (applying a force of no more than 10 N), without using any tools or pointed objects  Do not press the lockout reset button on the unit or the remote reset button (input 21) for more than 10 seconds since this will damage the lockout relay in the unit  Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage  For safety reasons – self-test of the flame supervision circuit, etc. – at least one controlled shutdown must take place every 24 hours Mounting notes  Ensure that the relevant safety regulations are complied with  Connect the earthing lug inside the terminal base to burner ground using a screw with a lockwasher  Note! In applications involving air heaters (WLE), or in the case of oil burners with a maximum throughput of >30 kW/h, removing wire link B is not permitted. Installation notes  Always run high-voltage ignition cables separately, with the greatest possible distance to the unit and to other cables  Live and neutral conductors must not be mixed up  Install switches, fuses, earthing, etc., in compliance with local regulations  Make certain that the maximum permissible current rating of the connection terminals will not be exceeded  The insulation on internal wiring which is subjected to the mains voltage must withstand the electrical stress occurring during correct use 3/24 Building Technologies Division CC1N7153en 21.09.2016 Electrical connection of the flame detector It is important to achieve practically disturbance- and loss-free signal transmission:  Never run the detector cable together with other cables – Line capacitance reduces the magnitude of the flame signal – Use a separate cable  Observe the permissible cable lengths (refer to «Technical data») Commissioning notes When commissioning the plant or when doing maintenance work, make the following safety checks: Safety check to be carried out Anticipated response a) Burner startup with flame detector darkened Lockout at the end of safety time (TSA) b) Burner startup with flame detector exposed to extraneous light Lockout after 40 seconds at the latest c) With wire strap «B»: Simulation of loss of flame during operation. For that purpose, darken the flame detector during operation and maintain that state Lockout d) Without wire strap «B»: Simulation of loss of flame during operation. For that purpose, darken the flame detector during operation and maintain that state Repetition followed by lockout at the end of «TSA» e) Burner startup with response of air pressure switch Prevention of startup/lockout during prepurge time f) Burner operation with simulated air pressure failure Immediate lockout Engineering notes  Install switches, fuses, earthing, etc., in compliance with local regulations  Connect valves and other plant components as specified in the burner manufacturer’s documentation H N L EK2 AL 21 1 2 1(3) 3 R 4 5 6 7 BV2 BV1 Z SA 15 16 17 18 a z 20 19 9 LR 7153a03/0814 24 m LK 11 10 8 22 B v LP 14 12 13 23 LAL2 1 2 3 4 5 6 7 8 9 10 QRB... 22 24 + RAR... SB W Si
Siemens LAL1.25 Manual  Main Page Preview

Manual  [PDF] (19 pages)

  • Updated: 21.07.2026

Document Preview & Text Transcription

CC1N7153en 22.05.2014 Building Technologies Division Infrastructure & Cities Sector 7 153 Oil Burner Controls LAL... Oil burner controls  With or without air pressure supervision for checked air damper control  Flame supervision – with photoresistive detector QRB... – or blue-flame detector QRC1... – or silicon photocell detector RAR9... The LAL... and this Data Sheet are intended for OEMs which integrate the oil burner controls in their products! Use - For the control and supervision of oil atomization burners - For burners of medium to high capacity - For intermittent operation (at least one controlled shutdown every 24 hours) - Can be universally used with multistage or modulating burners - Suited for use with stationary air heaters LAL1... - Yellow- and blue-flame burners without air pressure supervision LAL2... - Yellow-flame burners with air pressure supervision LAL3.25 - For special applications, e.g. burners of incinerator plant (for details, refer to «Type summary» and «Notes») For burner controls used in connection with burners for continuous operation, refer to Data Sheet 7785 (LOK16...). 2/19 Building Technologies Division CC1N7153en Infrastructure & Cities Sector 23.05.2014 Warning notes To avoid injury to persons, damage to property or the environment, the following warning notes must be observed! Do not open, interfere with or modify the unit!  All activities (mounting, installation and service work, etc.) must be performed by qualified staff  Before making any wiring changes in the connection area, completely isolate the plant from mains supply (all-polar disconnection). Ensure that the plant cannot be inadvertently switched on again and that it is indeed dead. If not observed, there is a risk of electric shock hazard  Ensure protection against electric shock hazard by providing adequate protection for the burner control’s connection terminals  Each time work has been carried out (mounting, installation, service work, etc.), check to ensure that wiring is in an orderly state and make the safety checks as described in «Commissioning notes»  Press the lockout reset button only manually (applying a force of no more than 10 N), without using any tools or pointed objects  Do not press the lockout reset button on the unit or the remote reset button for more than 10 seconds since this will damage the lockout relay in the unit  Fall or shock can adversely affect the safety functions. Such units must not be put into operation, even if they do not exhibit any damage Mounting notes  Ensure that the relevant safety regulations are complied with Installation notes  Always run high-voltage ignition cables separately, with the greatest possible dis- tance to the unit and to other cables  Live and neutral conductors must not be mixed up Electrical connection of the flame detector It is important to achieve practically disturbance-free signal transmission:  Never run the detector cable together with other cables – Line capacitance reduces the magnitude of the flame signal – Use a separate cable  Observe the permissible cable lengths (refer to «Technical data») Commissioning notes When commissioning the plant or when doing maintenance work, make the following safety checks: Safety check to be carried out Anticipated response a) Burner startup with flame detector darkened Lockout at the end of «TSA» b) Burner startup with flame detector exposed to extrane- ous light Lockout after 40 seconds at the latest c) With wire strap «B»: Simulation of loss of flame during operation. For that purpose, darken the flame detector during operation and maintain that state Lockout d) Without wire strap «B»: Simulation of loss of flame during operation. For that purpose, darken the flame detector during operation and maintain that state Repetition followed by lockout at the end of «TSA» 3/19 Building Technologies Division CC1N7153en Infrastructure & Cities Sector 23.05.2014 Engineering notes  Install switches, fuses, earthing, etc., in compliance with local regulations  Connect valves and other plant components as specified in the burner manufactur- er’s documentation H N L EK2 AL 21 1 2 1(3) 3 R 4 5 6 7 BV2 BV1 Z SA 15 16 17 18 a z 20 19 9 LR 7153a03/0814 24 m LK 11 10 8 22 B v LP 13 12 14 23 LAL2 1 2 3 4 5 6 7 8 9 10 QRB... 22 24 + RAR... SB W Si  Connect safety limit thermostats (manual reset) in the line (e.g. «SB»)  Remote reset When connecting lockout reset button «EK2» between terminals 21 and - terminal 3: For remote reset only - terminal 1: For remote reset and remote emergency shutdown  With LAL1…: Required switching capacity of - switching devices connected between terminals 4 and 5 (refer to «Technical data») With LAL2... / LAL3...: Required switching capacity of - switching devices connected between terminal 12 and «LP» (refer to «Technical data») - «LP» (refer to «Technical data»)  When using series connection, the control contacts of other devices contained in the burner plant must be con- nected as follows: - to terminal 4 or 5  contacts that must be closed from startup to controlled shutdown  otherwise no startup or shutdown - to terminal 12 (not with LAL1...)  contacts that must only be closed on startup  otherwise no startup - to terminal 14 (not with LAL1...)  contacts that must be closed no later than at the beginning of short preignition or long preignition and that must remain closed until controlled shutdown occurs  otherwise lockout  Maximum current draw, refer to «Technical data»  «Z» connected to terminal 15  short and long preignition  Connection of «BV...» to terminal 20, refer to «Connection examples»  When using burners without air damper, or with an air damper not controlled and monitored by the LAL…, ter- minal 8 must be connected to terminal 6  Wire link «B» clearly marked on the underside of the LAL… When wire link «B» is fitted, the LAL... initiates lockout if loss of flame occurs during operation. For repetition of the startup sequence, wire link «B» on the plug-in section of the LAL... must be cut away. Just cutting is not permitted!  For the permissible lengths and laying of detector cables, refer to «Flame supervision»