ECONOFLAME R2200
GAS FIRED BOILERS
INSTALLATION, OPERATION & MAINTENANCE
DOCUMENTATION
STOKVIS ENERGY SYSTEMS
96R WALTON ROAD
EAST MOLESEY
SURREY
KT8 0DL
TEL: 020 8783 3050 / 08707 707 747
FAX: 020 8783 3051 / 08707 707 767
E-MAIL:
[email protected]
WEBSITE: www.stokvisboilers.com
22CV22D - 160703
22CV22D
II
Edition D, 12-12-2000
© 2000 STOKVIS
All rights reserved.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted in
any form or by any means, electronic, mechanical, photocopying, recording or otherwise,
without the prior permission in writing of STOKVIS.
We aim to achieve continuous improvement in our products. Therefore, specifications are
subject to change without prior notice.
Due to changes the product can deviate from the information specified in this document.
Therefore STOKVIS rejects any responsibility for the differences between the
product delivered and the information mentioned in this document.
22CV22D
III
R2200 TECHNICAL DATA
Type
2207
2210
2213
2216
2220
2224
2228
Heat output
kW
81,3
116,4
151,5
186,7
233,9
280,9
328,5
Heat input
kW
88,2
126,0
163,8
201,6
252,0
302,4
352,8
Maximum gas rate
m /h
9,3
13,3
17,3
21,3
26,7
32,0
37,3
3
Gas pressure (inlet)
natural gas minimum
mbar
20
20
20
20
20
20
20
natural gas maximum
mbar
120
120
120
120
120
120
120
Water capacity
dm
6,2
6,9
7.7
8,5
9,6
10,5
11,4
Maximum working pressure
bar
6
6
6
6
6
6
6
3
Gas connection (G)
1"
1¼”
1¼”
1¼”
1¼”
1½”
1½”
Water connection (W)
DN50 PN6 DN50 PN6 DN50 PN6 DN50 PN6 DN50 PN6 DN65 PN6 DN65 PN6
Chimney diameter (D)
mm
150
180
200
200
250
250
300
Safety valve
connection
½”
½”
¾”
¾”
1"
1"
1"
blow-off
½”
½”
¾”
¾”
1¼”
1¼”
1¼”
standard setting
bar
3
3
3
3
3
3
3
Electrical supply
V
230
230
230
230
230
230
230
Frequency
Hz
50
50
50
50
50
50
50
Fuse
A
6
6
6
6
6
6
6
Max. electrical consumption
boiler
kW
0,10
0,10
0,12
0,12
0,15
0,15
0,15
pump maximum
kW
0,07
0,14
0,20
0,24
0,30
0,35
0,44
total
kW
0,17
0,24
0,32
0,36
0,45
0,50
0,59
Boiler weight empty
kg
165
200
245
285
340
375
440
Sizes
height (H)
mm
1440
1440
1440
1440
1440
1440
1440
width (B)
mm
786
786
786
786
786
786
786
length (L)
mm
1016
1226
1436
1646
1926
2206
2486
Table 1
Technical Data
22IP22/T0001EE
- Heat output measured at
: 60 - 80 C.
- Gas consumption at
: 1013 mbar, 15 C, dry.
- Gas specification
: I .
2H
-
Appliance category
: B14
- Protection degree
: IP20
22IP22/000103DE
Pump and by pass = option