Operation & user’s manual [PDF] (20 pages)
- Brand: SymCom
- Model: Motor Saver RM-2000-RTDW
- Format: PDF
- Key Aspects: Technical Data and Parameters, User Training Recommendations, System Connectivity and Wiring Basics
- Updated: 05.09.2026
- Source File: 2244292.pdf
- Pages: 20
- Description: Product usage manual for the SymCom Motor Saver RM-2000-RTDW.
Document Preview & Text Transcription
The RM-2000-RTDW motor-monitoring device can be used to monitor and/or control
SymCom’s Model 777 via an RS-485 Modbus network. Two form C output relays are
available for an RTD alarm and a warning alarm. Alarm and trip levels can be set for each
RTD to activate the RTD alarm and deactivate the 777 output relay respectively.
In addition, the RM-2000-RTDW has two inputs: one to connect to a ground-fault module
and the other for connection to a remote reset button.
A second communication port allows monitoring and control of up to 99 RM-2000-RTDW
devices from a computer with SymCom’s Solutions software, or a PLC, DCS, or SCADA
system. The RM-2000-RTDW is environmentally protected and can easily be mounted on
the front of a panel or MCC.
The RM-2000-RTDW displays the following
motor information:
• Real-time line currents, average current
and current unbalance
• Current to ground
• Line-to-line voltages, average voltage
and voltage unbalance
• Instantaneous power
• Power factor
• Last four faults
• All programmed 777 settings
• Remaining restart delay times
• 8 RTD temperatures
• Warning settings
The RM-2000-RTDW is also equipped with a
real-time clock, which allows access to the
following motor management information:
• Total motor run-time (reset capable)
• Time and date of last four faults, with voltage and current at time of trip
• Time and date of last ten motor starts
• Total number of motor restarts (reset capable)
• Minimum time between any two starts with time and date
• Run-time since last start (reset capable)
• KWhs consumed
• KVARs consumed
RM-2000-RTDW
Remote Monitor
User’s Guide
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
4
PART I ± INSTALLATION AND OPERATION
FEATURES
The RM-2000-RTDW is a motor management device used in conjunction with any
SymCom Model 777. The RM-2000-RTDW provides the following features:
Information Displayed
·
Run-Time Information: the RM-2000-RTDW can display all of the information
the Model 777 displays as well as information that the Model 777 maintains but
does not display, such as current unbalance, voltage unbalance and power
factor; see page 1 for a complete list of viewable parameters.
·
Real time clock: the RM-2000-RTDW has a real time clock so it can track
time-dependent data such as power draw (KW), energy consumption (KWH),
and run-hours.
·
Detailed information about fault conditions: the RM-2000-RTDW can store
information about power conditions just before the Model 777 tripped in
addition to the date and time of the fault.
·
Historical data: the RM-2000-RTDW can display historical data about the
motor being monitored by the Model 777 such as the total number of starts, the
number of trips, and the date and time of the last 10 starts.
Installation
·
Panel mounting: a model 777 is often mounted inside a motor control panel
and its display is not visible. The RM-2000-RTDW can be mounted on the
outside of the panel which allows all of the information from the Model 777 to
be displayed.
·
Remote mounting: the RM-2000-RTDW communicates with the Model 777 by
an RS485 cable which can be up to 4000 feet long. This allows the RM-2000-
RTDW to remotely monitor a Model 777.
·
Ease of installation: the RM-2000-RTDW only requires drilling 4 mounting
holes and punching out two 2” OD round holes using a standard knock out
punch or drilling 1 15/16” – 2 3/16” holes for the terminals to protrude through
to the inside of the panel.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
5
INSTALLING THE RM-2000-RTDW
1. Attach the template drawing to the panel where the RM-2000-RTDW is to be mounted.
2. Take caution when drilling the holes to mount the RM-2000-RTDW. Use an 11/64” drill
bit for the four corner mounting screws. Drill a 1 15/16” – 2 3/16” hole for the terminals
to protrude through to the inside of the panel.
3. Verify the gasket is in place on the back of the RM-2000-RTDW. Attach the RM-2000-
RTDW to the panel using the four screws provided.
4. Run the appropriate wires to the back of the RM-2000-RTDW and terminate the wires
in the provided screw-type, depluggable connectors; see the wiring diagram on the
following page. This should include at least 120VAC control power, one set of
communication wires to the 777, and ground wire to case ground on the panel.
NOTE: When connecting a Benshaw remote RTD module, terminal A of the RTD
module must be connected to B1 of the RM-2000—B must be connected to A1.
5. It is important to have the A phase of the breaker connected to L1 on the 777, B phase
to L2 and C to L3. Equally important, is to have the A phase conductor through the A
phase hole, B through the B phase hole, and C through the C phase hole of the 777.
6. The 777, when used with the RM-2000-RTDW, should be connected according the
following wiring diagram.
M
L1 L2
L3
INPUTVAC
CONTROL POWER
240VAC OR LESS
MOMENTARY
START BUTTON
OR CONTACT
GROUNDFAULT
MONITOR
STOP
M
Figure 1: Typical 777 Wiring Diagram
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
6
Figure 2: RM-2000-RTDW Wiring Diagram
ADDRESS
#1
ADDRESS
#2
UP TO 99
RM-2000s
IMPORTANT! If using a Benshaw RTD module, terminal A must be
connected to B1 of the RM-2000, and B must be connected toA1.
NOTE: All network shielding connections are omitted for clarity.
RS-485 MODBUS
MASTER: PC, PLC,
DCS, or SCADA
SETPOINT
SETUP
CHANGE
SETUP
FAULT
ENTER
MODE
STOP
SCROLL
RUN/RESET
COMM
STATUS
RUN
REAL TIME
FAULT
HISTORY
DISPLAY / PROGRAM
+
RD2
UCTD
CUB
LV
MULT
UC
OC
HV
VUB
RD1
TC
GF
RUN
#RU / ADDR
RD3
#RF
MODE SELECT
L1
L2
L3
NO
C
NC
RESET/
PROGRAM
MODEL 777
OVERLOAD RELAY
IND . CON
T. EQ.
LIST ED
784X
A
B
S
V+
R
R
REMOTE
RTD MODULE
REMOTE
RTD MODULE
MODEL RS485MS-2W
115VAC
L1
NO2 C2
NC2
NO1 C1
NC1
L2
A1
A
B
B1
REMOTE
RESET
GROUND FAULT
MONI TOR
RTD
ALARM
WARNING
ALARM
GF
C
RR
SETPOINT
SETUP
CHANGE
SETUP
FAULT
ENTER
MODE
STOP
SCROLL
RUN/RESET
COMM
STATUS
RUN
REAL TIME
FAULT
HISTORY
DISPLAY / PROGRAM
+
RD2
UCTD
CUB
LV
MULT
UC
OC
HV
VUB
RD1
TC
GF
RUN
#RU / ADDR
RD3
#RF
MODE SELECT
L1
L2
L3
NO
C
NC
RESET/
PROGRAM
MODEL 777
OVERLOAD RELAY
IND . CON
T. EQ.
LIST ED
784X
A
B
S
V+
R
R
MODEL 777
ADDRESS #1
MODEL 777
ADDRESS #1
MODEL RS485MS-2W
115VAC
L1
NO2 C2
NC2
NO1 C1
NC1
L2
A2
B2
A1
B1
A2
B2
24VDC
REMOTE
RESET
GROUND FAULT
MONI TOR
RTD
ALARM
WARNING
ALARM
GF
C
RR
A
B
24VDC
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]