E6581169
- 1 -
TOSVERT VF-A7/P7
The function manual of the parameter
“F451” “F452” “F453”
This manual is intended only to describe the typical operation and application of the
product. The technical information contained in this manual does not guarantee the
intellectual proprietary rights or other rights of, or grant a license to, the Toshiba
Schneider Inverter Corporation or third parties, for the use of the technical information or
of the product.
© Toshiba Schneider Inverter Corporation 2003
All rights reserved.
E6581169
- 2 -
1. Introduction
Thank you for your purchase of our industrial inverter “TOSVERT VF-A7/P7”.
This manual gives explanations of parameters “H, H, H” for the VF-A7/P7 inverter.
2. Functions
In the case the inverter is applied to lifting machines (crane, hoist, etc.), these parameters are used for
cooperation with the mechanical brake operation (H) and load falling prevention in winding up/down
operation (H, H).
3. Related parameters
Vector control
Title
Commu-
nication
No
Function
Adjustment range
Min. unit (panel/
communication)
Default
setting
Write during
running
Speed
control
Torque
control
Position
control
V/f
Constant
H
0451
Torque limit mode
0: Standard,
1: without speed
cooperation
-
0
Enabled
●/●
-
-
●
H
0452
Continuous stall trip
detection
time during power running
0.0~1.0 [s]
0.01/0.01
0.0
Enabled
●/●
-
-
●
H
0453
Stall prevention during
regeneration
0: Stall
1: Stall is prevented
-
0
Enabled
●/●
-
-
●
Sensorless vector/vector with sensor (●: Valid,-: Invalid)
E6581169
- 3 -
4. Function of parameter H
H = 0 mode (standard)
H = 1 mode (without speed cooperation)
Operation frequency is controlled
when torque limit is activated.
Therefore, actual speed is
controlled to follow the operation
frequency always.
Since the operation frequency is
raised after torque declines with
release of the mechanical brake,
the time that the actual speed
corresponds to the operation
frequency is time lag in
mechanical brake operation +
acceleration time.
When the inverter is used in combination with the mechanical brake of a lifting machine (crane, hoist,
etc.), the load fall by torque reduction can be prevented by carrying out the shortest acceleration of the
mechanical brake operation delay time.
Moreover, this parameter raises response in inching operation in order to control the load not to slip
down.
Frequency [Hz]
Time [s]
Torque [N⋅m]
Time [s]
Torque limit
level
Actual speed
When torque limit is
not activated
Operation frequency
Time [s]
Mechanical
brake
ON
OFF
(Released)
Operation frequency becomes
high ahead of torque limit even
when it is activated.
When torque declines with release
of the mechanical brake, it is
sustained at the limit level and
actual speed is controlled to follow
the operation frequency.
This mode functions not only to
prevent the load from falling but to
raise response in inching
operation.
Frequency [Hz]
Torque [N⋅m]
Time [s]
Torque limit
level
Actual speed
(Acceleration rate is determined
by torque limit.)
Operation frequency
Time [s]
Time [s]
Mechanical
brake
ON
OFF
(Released)
Torque limit is sustained after
the mechanical brake is
released.