CRL Comfort ventilation unit with
thermal wheel heat exchanger
(Translation of the original)
2
3064361_201710
Table�of�contents
Table�of�contents
1. General / safety information ..................................................................... 3
2. Standards, regulations / disposal ............................................................. 5
3. CRL-iD unit layout .................................................................................... 6
4. CRL-iD appliance versions ....................................................................... 8
5. CRL-iH unit layout .................................................................................... 9
6. CRL-iH appliance versions ......................................................................11
7. CRL-iDH unit layout ................................................................................ 12
8. CRL-iDH appliance versions .................................................................. 14
9. CRL-A unit layout.................................................................................... 15
10. CRL-A appliance versions .................................................................... 17
11. Delivery / handling ................................................................................ 18
12. Unit splitting for handling purposes ...................................................... 20
13. Installation information for external units .............................................. 25
14. Positioning ............................................................................................ 26
15. Electrical connection............................................................................. 28
16. Commissioning ..................................................................................... 29
17. Maintenance shutdown......................................................................... 36
18. Hygiene checklist.................................................................................. 37
19. Maintenance ......................................................................................... 38
20 Notes ..................................................................................................... 41
3
3064361_201710
1.�General�/�safety�information
General�information
These installation and maintenance instructions only apply to WOLF CRL
ventilation units. Authorised personnel should read these instructions before
any commissioning or maintenance work. Observe the instructions given in
this document. Installation, commissioning and maintenance work must only
be carried out by trained personnel.
These�instructions�should�be�considered�an�integral�part�of�the�unit�
supplied,�and�should�always�be�easily�accessible.
Failure to observe these installation and maintenance instructions voids any
WOLF GmbH warranty.
Reference�symbols
The�following�symbols�are�used�in�these�instructions.�This�important�
information�concerns�personal�as�well�as�operational�safety.
"Safety�information"�is�a�set�of�instructions�which�you�must�follow�exactly,�
to�prevent�risks�or�injuries�to�individuals,�and�damage�to�the�unit.
Danger�through�"live"�electrical�components.
Caution:�Turn�off�the�ON/OFF�switch�before�removing�the�casing.
Never�touch�electrical�components�or�contacts�when�the�ON/OFF�switch�
is�in�the�ON�position.�This�carries�a�risk�of�electrocution�that�could�result�
in�injury�or�death.
The�main�terminals�are�"live",�even�when�the�ON/OFF�switch�is�in�the�
OFF�position.
"Please�note"�designates�technical�instructions�which�you�must�observe�
to�prevent�the�unit�malfunctioning�or�atng�damaged.
Please�
note
Only qualified and trained personnel may be appointed for the installation,
commissioning, maintenance and operation of the unit.
Only qualified electricians are permitted to work on the electrical system.
VDE regulations [or local regulations] and those of your local power supply
utility are applicable to electrical installation work.
Only operate the unit within its output range, which is stated in the technical
documentation supplied by WOLF.
Only operate the unit when it is in perfect technical condition. Any faults or
damage which impact or might impact upon the safety or correct function of
the unit must be remedied immediately by qualified personnel.
Only replace faulty components and equipment with original WOLF spare parts.
The�unit�may�only�be�used�for�handling�air.�This�air�must�not�contain�
any�harmful,�combustible,�explosive,�aggressive,�corrosive�or�otherwise�
dangerous�substances,�as�these�would�be�distributed�throughout�the�
duct�system�or�building,�where�they�could�cause�a�risk�to�the�health�of,�
or�even�kill�the�occupants,�animals�or�plants�living�there.
Please�
note
Safety�information
In addition to installation and maintenance instructions, there are notes attached
to the unit in the form of labels. These must also be observed.
4
3064361_201710
1.�General�/�safety�information
Fire
The unit does not present a direct risk of fire. The small numbers of seals fitted
inside the unit can burn away if subjected to external influences. Wear respiratory
equipment if you fight a fire. The usual extinguishing agents such as water,
extinguishing foam or extinguishing powder can be used to extinguish fires. As
there are only a small number of flammable seals, the level of pollutants that
could be released in a fire is minimal.
Recommended�temperatures
The ventilation unit is designed for air intake temperatures between -20 °C
and +40 °C. For safety reasons, the room temperature in technical equipment
rooms must not fall below 5 °C (risk of frost) or exceed 40 °C. The unit should
be operated in room conditions of between 22 °C and 28 °C at approx. 55 %
relative humidity.
Other�technical�
documents
- WRS-K operating instructions
- MicroMax 370W TWHE control unit operating instructions
- Wiring diagram
- WRS-K configuration wizard
- Commissioning report / Parameter list
Electrical�connection
Make the electrical connection in accordance with local regulations.
Once electrical connection work is complete, the installation must be subjected
to a safety test in accordance with VDE 0701-0702 and VDE 0700 part 500,
as otherwise there would be a risk of electric shock that could result in injury
or death.
Before�working�on�the�unit,�shut�it�down�via�the�isolator.
Even when the unit has been shut down, voltage will still be present at terminals
and connections of the EC fans. This means there is a risk of electric shock
that could result in injury or death.
Do not touch the EC fans for five minutes after disconnecting the power across
all poles.
Intended�use
WOLF CRL ventilation units are designed to heat and filter normal air. Max. air
intake temperature: +40 °C. The use of these units in wet rooms or rooms with
explosive atmospheres is not permissible. Handling very dusty or aggressive
media is not permissible.
Any on-site modification or improper use of the unit is not permissible and
WOLF GmbH accepts no liability for any damage caused as a result.
Ventilation units intended for internal installation must be placed in rooms that
meet the requirements of VDI 2050 (VDI 2050, Requirements for technical
equipment rooms - Planning and execution).
According to DIN 1886, tools must be used to open the unit. Wait for the fan to
reach standstill (2 minutes). When the doors are opened, negative pressure
may draw in loose objects, which could destroy the fan or even cause a risk to
life if items of clothing are drawn in.
Removal and disabling of safety and monitoring equipment is prohibited.
Only operate the system in perfect technical condition. Ensure that any faults
or damage that may impact on safety are rectified immediately.
Warnings