INSTALLATION, COMMISSIONING AND SERVICING INSTRUCTIONS
WALL HUNG RSF GAS FIRED CONDENSING SYSTEM BOILER
GREENSTAR 30/35 CDi CLASSIC SYSTEM
6 720 812 176-00.1O
FOR CENTRAL HEATING SYSTEMS AND INDIRECT FED DOMESTIC HOT WATER
6 720 812 175 (2014/07)
The appliance is for use with:
Natural Gas or L.P.G. (CAT II 2H3P type C13 & C33)
Natural Gas:
30CDi GC number 41-406-37
35CDi GC number 41-406-39
L.P.G:
30CDi GC number 41-406-38
35CDi GC number 41-406-40
CONTENTS
6 720 812 175 (2014/07)
2
CONTENTS
1
KEY TO SYMOLS AND SAFETY PRECAUTIONS . . . . . . . . . . . . . 3
1.1
Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2
Safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2
APPLIANCE INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1
General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2
Layout & components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3
PRE-INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1
Cleaning primary systems . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2
Mains supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2.1
Gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3
Water systems & pipe work . . . . . . . . . . . . . . . . . . . . . 10
3.4
Condensate pipe work . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4.1
Internal connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.4.2
External connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.5
Boiler internal drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.6
Pressure relief pipe work . . . . . . . . . . . . . . . . . . . . . . . 13
3.7
Boiler location & clearances . . . . . . . . . . . . . . . . . . . . . 14
3.8
Plumbing manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.9
Flue options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.10
Flue terminal positions . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.11
Plume management terminal positions . . . . . . . . . . . . 19
4
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
4.1
Unpacking wall frame and ancillary items . . . . . . . . . . 20
4.2
Wall mounting plate and flue opening . . . . . . . . . . . . . 21
4.3
Unpacking the appliance . . . . . . . . . . . . . . . . . . . . . . . . 22
4.4
Fitting the appliance/boiler connections . . . . . . . . . . . 23
4.5
Flue installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.5.1
Ø 60/100 mm Telescopic flue kit . . . . . . . . . . . . . . . . . 24
4.5.2
Ø 60 mm Plume management kit . . . . . . . . . . . . . . . . . 24
4.5.3
Adjusting the standard terminal length: . . . . . . . . . . . . 24
4.5.4
Installing the standard flue . . . . . . . . . . . . . . . . . . . . . . 25
4.5.5
Flue terminal plume re-direction: . . . . . . . . . . . . . . . . . 25
4.6
Condensate connection . . . . . . . . . . . . . . . . . . . . . . . . 26
4.7
Electrical (without diverter valve) . . . . . . . . . . . . . . . . 27
4.8
Electrical (with optional diverter valve) . . . . . . . . . . . . 28
4.9
Position of wired components . . . . . . . . . . . . . . . . . . . 29
5
COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.1
Pre- commissioning checks . . . . . . . . . . . . . . . . . . . . . 30
5.2
Filling the system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
5.3
Starting the appliance . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.4
Water treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.5
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.5.1
Checking the gas inlet pressure . . . . . . . . . . . . . . . . . . 32
5.5.2
Checking the gas rate . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.6
CO and Combustion checks . . . . . . . . . . . . . . . . . . . . . 34
5.7
Finishing commissioning . . . . . . . . . . . . . . . . . . . . . . . 35
6
SERVICING AND SPARES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1
Inspection and spares . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.1
Checking flue integrity . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.2
Component access . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.3
Fan pressure test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.1.4
To Clean the Heat Exchanger . . . . . . . . . . . . . . . . . . . . 38
6.1.5
To Clean the Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.1.6
To Check the Diaphragm in Burner Cover . . . . . . . . . . 39
6.1.7
To Clean the Siphon/Condensate Trap . . . . . . . . . . . . 40
6.2
Setting the air/gas ratio . . . . . . . . . . . . . . . . . . . . . . . . 40
6.3
Replacement of parts . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.4
Short parts list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7
FAULT FINDING & DIAGNOSIS . . . . . . . . . . . . . . . . . . . . . . . . 51
7.1
Fault finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
7.2
Central heating function . . . . . . . . . . . . . . . . . . . . . . . . 52
7.3
Cylinder heat function . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.4
Protection function . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
KEY TO SYMOLS AND SAFETY PRECAUTIONS
6 720 812 175 (2014/07)
3
1
KEY TO SYMOLS AND SAFETY
PRECAUTIONS
1.1
KEY TO SYMBOLS
WARNINGS
The following keywords are defined and can be used in this document:
• NOTE indicates a situation that could result in damage to property or
equipment.
• CAUTION indicates a situation that could result in minor to medium
injury.
• WARNING indicates a situation that could result in severe injury or
death.
• DANGER indicates a situation that will result in severe injury or death.
IMPORTANT INFORMATION
ADDITIONAL SYMBOLS
SYMBOLS USED IN THIS MANUAL
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE
STARTING INSTALLATION.
Warnings in this document are identified by a warning
triangle printed against a grey background.
Keywords at the start of a warning indicate the type and
seriousness of the ensuing risk if measures to prevent
the risk are not taken.
This symbol indicates important information where
there is no risk to people or property.
Symbol
Explanation
▶
Step in an action sequence
Cross-reference to another part of the document
•
List entry
–
List entry (second level)
Table 1
Domestic Hot Water
Central Heating
Hot Water Storage Cylinder
Domestic Cold Water Supply
Electrical Supply
Gas Supply
Table 2 Commonly used symbols
These instructions are applicable to the Worcester appliance model(s)
stated on the front cover of this manual only and must not be used with
any other make or model of appliance.
These instructions apply in the UK and Ireland only and must be
followed except for any statutory obligations.
This appliance must be installed by a GAS SAFE registered,
competent person. Failure to install correctly could lead to
prosecution.
If you are in any doubt, contact the Worcester Technical helpline
(0330 123 3366).
Please leave these instructions with the completed BENCHMARK
CHECKLIST, (or a certificate confirming compliance with IS 813, Eire
only) and the user manual with the owner or at the gas meter after
installation or servicing.
Distance learning and training courses are available from Worcester.
The BENCHMARK CHECKLIST can be found in the back of this
Installation manual.
Table 3
Ø
Diameter
NG
Natural Gas
LPG
Liquid Petroleum Gas
CH
Central Heating
DHW
Domestic Hot Water
DCW
Domestic Cold Water
PRV
Pressure Relief Valve
NTC
Negative Temperature Coefficient (sensor)
IP
Ingress Protection
RCD
Residual Current Device
TRV
Thermostatic Radiator Valve
ECV
Emergency Control Valve
WRAS
Water Regulations Advisory Scheme
SEDBUK
Seasonal Efficiency of Domestic Boilers in the United
Kingdom
Table 4 Abbreviations use in this manual
KEY TO SYMOLS AND SAFETY PRECAUTIONS
6 720 812 175 (2014/07)
4
1.2
SAFETY PRECAUTIONS
IF YOU SMELL GAS
A gas leak could potentially cause an explosion. If you smell gas, observe
the following rules.
▶ Prevent flames or sparks:
– Do not smoke, use a lighter or strike matches.
– Do not operate any electrical switches or unplug any equipment.
– Do not use the telephone or ring doorbells.
▶ Turn off the gas at the meter.
▶ Open windows and doors.
▶ Warn your neighbours and leave the building.
▶ Prevent anyone from entering the building.
▶ Well away from the building: call the National Gas Emergency Service
on 0800 111 999.
BOILER OPERATION:
This boiler must only be operated by a responsible adult who has
been instructed in, understands and is aware of the boiler’s
operating conditions and effects.
Benchmark places
responsibilities on both
manufacturers and
installers. The purpose is to
ensure that customers are
provided with the correct equipment for their needs, that it is installed,
commissioned and serviced in accordance with the manufacturer's
instructions by competent persons and that it meets the requirements of
the appropriate Building Regulations. The Benchmark Checklist can be
used to demonstrate compliance with Building Regulations and should
be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and
servicing work in accordance with the Benchmark Code of Practice
which is available from the Heating and Hotwater Industry Council who
manage and promote the scheme.
Visit centralheating.co.uk for more information.
HEALTH AND SAFETY
The appliance contains no asbestos and no substances have been used
in the construction process that contravene the COSHH Regulations
(Control of Substances Hazardous to Health Regulations 1988).
COMBUSTIBLE AND CORROSIVE MATERIALS:
Do not store or use any combustible materials (paper, thinners, paints
etc.) inside or within the vicinity of the boiler.
Chemically aggressive substances can corrode the appliance and
invalidate any warranty.
FITTING & MODIFICATIONS
Fitting the appliance and any controls to the appliance may only be
carried out by a competent engineer in accordance with the current Gas
Safety (Installation and Use) Regulations.
Flue systems must not be modified in any way other than as described in
the fitting instructions. Any misuse or unauthorised modifications to the
appliance, flue or associated components and systems could invalidate
the warranty. The manufacturer accepts no liability arising from any
such actions, excluding statutory rights.
SERVICING
Advise the user to have the system serviced annually by a competent,
qualified Gas Safe registered engineer. Approved spares must be used
to help maintain the economy, safety and reliability of the appliance.
IMPORTANT
The service engineer must complete the Service Record on the
Benchmark Checklist after each service.
INSTALLATION REGULATIONS
Current Gas Safety (Installation & Use) Regulations:
All gas appliances must be installed by a competent person in
accordance with the above regulations. Failure to install appliances
correctly could lead to prosecution.
The appliance must be installed in accordance with, and comply to, the
current: Gas Safety Regulations, IEE Regulations, Building Regulations,
Building Standards (Scotland) (Consolidation), Building Regulations
(Northern Ireland), local water by-laws, Health & Safety Document 635
(The Electricity at Work Regulations 1989) and any other local
requirements.
British Standards:
Where no specific instruction is given, reference should be made to the
relevant British Standard codes of Practice.
BS7074:1 - Code of practice for domestic and hot water supply
BS6891 - Installation of low pressure gas pipe work up to 28mm (R1)
BS5546 - Installation of gas hot water supplies for domestic purposes
EN12828 - Central heating for domestic premises
BS5440:1 - Flues and ventilation for gas appliances of rated heating not
exceeding 70kW (net): Flues
BS5440:2 - Flues and ventilation for gas appliances of rated heating not
exceeding 70kW (net): Air Supply
BS7593 - Treatment of water in domestic hot water central heating
systems
BS6798 - Installation of gas fired boilers of rated input up to 70kW (net)
Irish Standards
The relevant Irish standards should be followed, including:
• ECTI National rules for electrical installations
• IS 813:2002 for Domestic Gas Installations.
LPG Installations
An appliance using L.P.G. must not be installed in a room or internal
space below ground level unless one side of the building is open to the
ground.
Timber framed building:
Where the boiler is to be fitted to a timber framed building the guidelines
laid down in BS5440: Part 1 and IGE "Gas Installations in Timber Frame
Buildings” should be adhered to.
Potable water:
All seals, joints and compounds (including flux and solder) and
components used as part of the secondary domestic water system must
be approved by WRAS.
CH Water:
Artificially softened water must not be used to fill the central heating
system.