Panasonic CS-E9DKEW Service Manual
Text of the manual
2.1. Remote Control
3
2.2. Indoor Unit
4
2.3. Outdoor Unit
6
3 Product Specifications
7
3.1. CS-E9DKEW CU-E9DKE
7
3.2. CS-E12DKEW CU-E12DKE
9
4 Dimensions
11
4.1. Indoor Unit & Remote Control
11
4.2. Outdoor Unit
12
5 Refrigeration Cycle Diagram
13
6 Block Diagram
14
7 Wiring Diagram
15
8 Operation Details
16
8.1. Basic Function
16
© 2004 Panasonic HA Air-Conditioning (M) Sdn Bhd
(11969-T). All rights reserved. Unauthorized copying
and distribution is a violation of law.
CS-E9DKEW CU-E9DKE
CS-E12DKEW CU-E12DKE
8.2. Protection Control Features
35
9 Operating Instructions
44
10 Installation Instructions
50
10.1. Safety Precautions
50
10.2. Indoor Unit
53
10.3. Outdoor Unit
57
11 Installation And Servicing Air Conditioner Using R410A
61
11.1. Outline
61
11.2. Tools For Installing/Servicing Refrigerant Piping
62
11.3. Refrigerant Piping Work
66
11.4. Installation, Transferring, Servicing
68
12 Servicing Information
72
12.1. Troubleshooting
72
12.2. Breakdown Self Diagnosis Function
74
12.3. Remote Control
76
Air Conditioner
CONTENTS
Page
Page
Order No: MAC0412064C2
3 Product Specifications
3.1.
CS-E9DKEW CU-E9DKE
Unit
CS-E9DKEW
CU-E9DKE
Cooling Capacity
kW
kcal/h
BTU/h
2.6 (0.80 - 3.00)
2,240 (690 - 2,580)
8,870 (2,050 - 10,200)
Heating Capacity
kW
kcal/h
BTU/h
3.6 (0.80 - 5.00)
3,100 (690 - 4,300)
12,300 (2,050 - 17,100)
Moisture Removal
l/h
Pint/h
1.6
(3.4)
Power Source (Phase, Voltage, Cycle)
ø
V
Hz
Single
230
50
Airflow Method
OUTLET
INTAKE
SIDE VIEW
TOP VIEW
Air Volume
Lo
m3/min (cfm)
Cooling; 6.2 (220)
—
Heating; 6.6 (230)
Me
m3/min (cfm)
Cooling; 7.9 (280)
—
Heating; 8.6 (300)
Hi
m3/min (cfm)
Cooling; 9.6 (340)
Cooling; 29.8 (1,050)
Heating; 10.5 (370)
SHi
m3/min (cfm)
Cooling; 9.9 (350)
—
Heating; 10.8 (380)
dB (A)
Cooling; High 39, Low 26
Cooling; 46
Heating; High 40, Low 27
Heating; 47
Noise Level
Power level dB
Cooling; High 50
Cooling; High 59
Heating; High 51
Heating; High 60
Electrical Data
Input
W
Cooling; 600 (175 - 780)
Heating; 845 (165 - 1,360)
Running Current
A
Cooling; 2.9
Heating; 4.0
EER
W/W (kcal/hw), BTU/hw
Cooling; 4.33 (3.73), 14.8
COP
W/W (kcal/hw), BTU/hw
Heating; 4.26 (3.67), 14.6
Starting Current
A
4.0
Piping Connection Port
(Flare piping)
inch
inch
G ; Half Union 3/8”
L ; Half Union 1/4”
G ; 3-way valve 3/8”
L ; 2-way valve 1/4”
Pipe Size
(Flare piping)
inch
inch
G (gas side) ; 3/8”
L (liquid side) ; 1/4”
G (gas side) ; 3/8”
L (liquid side) ; 1/4”
Drain
Hose
Inner diameter
mm
12
—
Length
m
0.65
—
7
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
Power Cord Length
Number of core-wire
—
—
—
—
Dimensions
Height
inch (mm)
11 - 1/32 (280)
21 - 1/4 (540)
Width
inch (mm)
31 - 15/32 (799)
30 - 23/32 (780)
Depth
inch (mm)
7 - 7/32 (183)
11 - 3/8 (289)
Net Weight
lb (kg)
20 (9.0)
82 (37)
Compressor
Type
—
Hermetic Rotary
Motor
Type
—
Brushless (6-pole)
Rated
Output
W
—
700
Air Circulation
Type
Cross-flow Fan
Propeller Fan
Material
ASG20k1
P.P
Motor
Type
Transistor (8-poles)
Induction (6-poles)
Input
W
—
61.3
Rate Output
W
30
28
Fan Speed
Lo (Cool/Heat)
rpm
820/880
—
Me (Cool/Heat)
rpm
1,050/1,140
—
Hi (Cool/Heat)
rpm
1,280/1,400
770
SHi (Cool/Heat)
rpm
1,320/1,440
—
Heat Exchanger
Description
Evaporator
Condenser
Tube material
Copper
Copper
Fin material
Aluminium (Pre Coat)
Aluminium
Fin Type
Slit Fin
Corrugated Fin
Row / Stage
(Plate fin configuration, forced draft)
2 / 15
2 / 24
FPI
21
17
Size (W × H × L)
mm
610 × 315 × 25.4
718.4
689.8
× 504 × 36.4
Refrigerant Control Device
—
Capillary Tube
Refrigeration Oil
(cm3)
—
RB68A (320)
Refrigerant (R410A)
g (oz)
—
965 (34.1)
Thermostat
Electronic Control
—
Protection Device
Electronic Control
Electronic Control
Length
mm
—
C1, C2 ; 950, C3 ; 411
Capillary Tube
Flow Rate
l/min
—
C1, C2 ; 4.1, C3 ; 18.8
Inner Diameter
mm
—
C1, C2 ; 1.1, C3 ; 1.7
Air Filter
Material
Style
P.P.
Honeycomb
—
Fan Motor Capacitor
µF, VAC
—
2.0 µF, 440 VAC
Compressor Capacitor
µF, VAC
—
65 µF, 350 VAC
• Specifications are subject to change without notice for further improvement.
8
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
3.50 (0.80 - 4.00)
3,010 (690 - 3,440)
11,950 (2,730 - 13,600)
Heating Capacity
kW
kcal/h
BTU/h
4.80 (0.80 - 6.50)
4,130 (690 - 5,590)
16,400 (2,730 - 22,200)
Moisture Removal
l/h
Pint/h
2.0
(4.2)
Power Source (Phase, Voltage, Cycle)
ø
V
Hz
Single
230
50
Airflow Method
OUTLET
INTAKE
SIDE VIEW
TOP VIEW
Air Volume
Lo
m3/min (cfm)
Cooling; 6.9 (240)
—
Heating; 8.1 (290)
Me
m3/min (cfm)
Cooling; 8.8 (310)
—
Heating; 9.7 (340)
Hi
m3/min (cfm)
Cooling; 10.7 (380)
Cooling; 31.0 (1,090)
Heating; 11.2 (400)
SHi
m3/min (cfm)
Cooling; 11.0 (390)
—
Heating; 11.6 (410)
dB (A)
Cooling; High 42, Low 29
Cooling; 48
Heating; High 42, Low 33
Heating; 50
Noise Level
Power level dB
Cooling; High 53
Cooling; High 61
Heating; High 53
Heating; High 63
Electrical Data
Input
W
Cooling; 965 (185 - 1,200)
Heating; 1,260 (175 - 1,890)
Running Current
A
Cooling; 4.5
Heating; 5.8
EER
W/W (kcal/hw), BTU/hw
Cooling; 3.63 (3.12), 12.4
COP
W/W (kcal/hw), BTU/hw
Heating; 3.81 (3.28), 13.0
Starting Current
A
5.8
Piping Connection Port
(Flare piping)
inch
inch
G ; Half Union 1/2”
L ; Half Union 1/4”
G ; 3-way valve 1/2”
L ; 2-way valve 1/4”
Pipe Size
(Flare piping)
inch
inch
G (gas side) ; 1/2”
L (liquid side) ; 1/4”
G (gas side) ; 1/2”
L (liquid side) ; 1/4”
Drain
Hose
Inner diameter
mm
12
—
Length
m
0.65
—
Power Cord Length
Number of core-wire
—
—
—
—
9
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
11 - 1/32 (280)
21 - 1/4 (540)
Width
inch (mm)
31 - 15/32 (799)
30 - 23/32 (780)
Depth
inch (mm)
7 - 7/32 (183)
11 - 3/8 (289)
Net Weight
lb (kg)
20 (9.0)
82 (37)
Compressor
Type
—
Hermetic Rotary
Motor
Type
—
Brushless (6-pole)
Rated
Output
W
—
700
Air Circulation
Type
Cross-flow Fan
Propeller Fan
Material
ASG20k1
P.P
Motor
Type
Transistor (8-poles)
Induction (6-poles)
Input
W
—
65.9
Rate Output
W
30
29
Fan Speed
Lo (Cool/Heat)
rpm
910/1,080
—
Me (Cool/Heat)
rpm
1,165/1,290
—
Hi (Cool/Heat)
rpm
1,420/1,500
830
SHi (Cool/Heat)
rpm
1,460/1,540
—
Heat Exchanger
Description
Evaporator
Condenser
Tube material
Copper
Copper
Fin material
Aluminium (Pre Coat)
Aluminium
Fin Type
Slit Fin
Corrugated Fin
Row / Stage
(Plate fin configuration, forced draft)
2 / 15
2 / 24
FPI
21
17
Size (W × H × L)
mm
610 × 315 × 25.4
718.4
689.8
× 504 × 36.4
Refrigerant Control Device
—
Capillary Tube
Refrigeration Oil
(cm3)
—
RB68A (320)
Refrigerant (R410A)
g (oz)
—
980 (34.6)
Thermostat
Electronic Control
—
Protection Device
Electronic Control
Electronic Control
Length
mm
—
C1, C2 ; 1,120, C3 ; 370
Capillary Tube
Flow Rate
l/min
—
C1, C2 ; 4.9, C3 ; 19.6
Inner Diameter
mm
—
C1, C2 ; 1.2, C3 ; 1.7
Air Filter
Material
Style
P.P.
Honeycomb
—
Fan Motor Capacitor
µF, VAC
—
2.0 µF, 440 VAC
Compressor Capacitor
µF, VAC
—
65 µF, 350 VAC
• Specifications are subject to change without notice for further improvement.
10
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
Indoor Unit & Remote Control
4.1.1.
CS-E9DKEW CS-E12DKEW
11
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
Applicable piping kit
CZ-3F5, 7BP (E9DK)
CZ-4F5, 7, 10BP (E12DK)
SELECT THE BEST LOCATION
INDOOR UNIT
• There should not be any heat source or steam near the
unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A
place
where
noise
prevention
is
taken
into
consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
• Recommended installation height for indoor unit shall be
at least 2.3 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short
circuit of the discharged air.
• If piping length is over the rated length, additional
refrigerant should be added as shown in the table.
Indoor/Outdoor Unit Installation Diagram
• This illustration is for explanation purposes only.
The indoor unit will actually face a different way.
52
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
1. Rated Frequency Operation
12 Servicing Information
Caution:
• Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use
a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C).
• Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
12.1. Troubleshooting
During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the
specification and technical data. Below are the methods used to obtain rated compressor operating specification.
(a) Cooling
(i) Press the Auto button continuously for 5 seconds or less than 8 seconds, the air conditioner starts operation at Cooling rated frequency.
(“beep” will be heard at the 5th second.)
(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of air conditioner is Cooling rated frequency.
(b) Heating
Press the Auto button continuously for 8 seconds or less than 11 seconds, the air conditioner starts operation at Heating rated
frequency. (“beep” “beep” will be heard at the 8th second.)
72
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
2. Troubleshooting Air Conditioner
Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are
no electrical problems before inspecting the refrigeration
cycle.
Such
problems
include
insufficient
insulation,
problem
with
the
power
source,
malfunction
of
a
compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the
standard values for them are shown in the table to the right.
73
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
1. Relationship between the condition of the air conditioner and pressure and electric current
Cooling Mode
Heating Mode
Condition of the air
conditoner
Low Pressure
High Pressure
Electric current
during operation
Low Pressure
High Pressure
Electric current
during operation
Insufficient refrigerant
(gas leakage)
Clogged capillary tube
or Strainer
Short circuit in the
indoor unit
Heat radiation
deficiency of the
outdoor unit
Inefficient compression
• Carry on the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
12.2. Breakdown Self Diagnosis Function
Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of
three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below
breakdown diagnosis method:
• Press “CHECK” button at remote controller continuously for more than five seconds to turn on the diagnosis mode, “H11” will
be displayed at remote controller.
• By pressing the TMER “
” button once, next error code will be displayed; press “V” button once, previous error code will be
displayed.
• If error code displayed matches the error code saved in unit memory (abnormality detected), “beep, beep, beep....” sounds will
be heard for 4 seconds and Power LED will light on. Otherwise, one “beep” sound is heard.
If “CHECK” button is press again or without any operation for 30 seconds, the diagnosis mode will turn off.
74
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
Error Codes Table
Diagnosis
display
Abnormality / Protection control
Abnormality
Judgement
Emergency
operation
Primary location to verify
H11
Indoor / outdoor abnormal
communication
> 1 min after starting
operation
Indoor fan operation
only
• Internal / external cable connections
• Indoor / Outdoor PCB
H12
Connection capability rank abnormal
—
—
—
H14
Indoor intake air temperature sensor
abnormality
Continue for 5 sec.
—
• Intake air temperature sensor
(detective or disconnected)
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
—
• Compressor temperature sensor
(detective or disconnected)
H16
Outdoor Current Transformer open
circuit
—
—
• Outdoor PCB
• IPM (Power transistor) module
H19
Indoor fan motor merchanism lock
—
—
• Indoor PCB
• Fan motor
H23
Indoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
O
(Cooling only)
• Heat exchanger temperature sensor
(defective or disconnected)
H26
Ionizer breakdown
—
—
• Ionizer
H27
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
O
• Outdoor temperature sensor
(defective or disconnected)
H28
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
O
• Outdoor heat exchanger
temperature sensor (defective or
disconnected)
H33
Indoor/Outdoor wrong connection
—
—
• Indoor/Outdoor supply voltage
H38
Indoor / outdoor mismatch (brand code)
—
—
—
H98
Indoor high pressure protection
—
—
• Air filter dirty
• Air circulation short circuit
H99
Indoor heat exchanger anti-freezing
protection
—
—
• Insufficient refrigerant
• Air filter dirty
F11
Cooling / Heating cycle changeover
abnormality
4 times occurance
within 30 minutes
—
• 4-way valve
• V-coil
F90
PFC control
4 times occurance
within 10 minutes
—
• Voltage at PFC
F91
Refrigeration cycle abnormality
2 times occurance
within 20 minutes
—
• No refrigerant
(3-way valve is closed)
F93
Compressor rotation failure
—
—
• Compressor
F95
Cool high pressure protection
4 times occurance
within 20 minutes
—
• Outdoor refrigerant circuit
F96
IPM (power transistor) overheating
protection
—
—
• Excess refrigerant
• Improper heat radiation
• IPM (Power transistor)
F97
Outdoor compressor overheating
protection
4 times occurance
within 10 minutes
—
• Insufficient refrigerant
• Compressor
F98
Total running current protection
3 times occurance
within 20 minutes
—
• Excess refrigerant
• Improper heat radiation
F99
Outdoor Direct Current (DC) peak
detection
7 times occurance
continuously
—
• Outdoor PCB
• IPM (Power transistor)
• Compressor
Note:
“O” - Frequency measured and fan speed fixed.
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard
following by pressing the “RESET” button at remote controller.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error
Codes Table) by using remote controller or Auto Switch at indoor unit. However, the remote controller signal receiving sound is
changed from one “beep” to four “beep” sounds.
75
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
• Remote Control Reset
When the batteries are inserted for the first time, or the
batteries are replaced, all the indications will blink and the
remote control might not work.
If this happen, remove the cover of the remote control and
push the reset point once to clear the memory data.
• Changing the wireless remote control transmission
code
When there are more than one indoor units installed in the
same room, it is possible to set different remote control
receiving signal by modifying the jumpers inside remote
controller.
12.3. Remote Control
76
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
1 Technical Data (Page: 80 - 81)
1.1.
Operation Characteristics
1.1.1.
CS-E9DKEW CU-E9DKE
2
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
[PHAAM] Printed in Malaysia
13.2. Sensible Capacity Chart
●CS-E9DKEW CU-E9DKE
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
2.58
1.96
0.55
2.41
1.88
0.59
2.24
1.80
0.63
2.04
1.71
0.68
19.0°C
2.60
0.60
19.5°C
2.83
2.05
0.56
2.65
1.97
0.60
2.46
1.89
0.64
2.24
1.80
0.69
22.0°C
3.09
2.12
0.57
2.88
2.04
0.61
2.68
1.97
0.66
2.44
1.88
0.71
●CS-E12DKEW CU-E12DKE
230V
Outdoor Temp. (°C)
Indoor wet
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0°C
3.47
2.63
0.88
3.24
2.52
0.95
3.02
2.43
1.02
2.74
2.30
1.10
19.0°C
3.50
0.97
19.5°C
3.81
2.76
0.90
3.56
2.65
0.97
3.31
2.55
1.04
3.01
2.43
1.12
22.0°C
4.15
2.86
0.92
3.88
2.75
0.99
3.61
2.65
1.05
3.28
2.53
1.14
82
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
14 Exploded View (Indoor Unit)
14.1. CS-E9DKEW CS-E12DKEW
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
83
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
15 Replacement Parts List (Indoor Unit)
15.1. CS-E9DKEW CS-E12DKEW
REF. NO.
PART NAME & DESCRIPTION
QTY.
CS-E9DKEW
CS-E12DKEW
REMARKS
1
CHASSY COMPLETE
1
CWD50C1431
←
2
FAN MOTOR
1
CWA981149
←
0
3
CROSS FLOW FAN COMPLETE
1
CWH02C1031
←
4
BEARING ASS’Y
1
CWH64K007
←
5
SCREW - CROSS FLOW FAN
1
CWH4580304
←
6
EVAPORATOR
1
CWB30C1597
CWB30C1726
7
FLARE NUT
1
CWT25086 (1/4”)
←
8
FLARE NUT
1
CWT25087 (3/8”)
CWT25096 (1/2”)
9
HOLDER SENSOR
1
CWH32143
←
10
DISCHARGE GRILLE COMPLETE
1
CWE20C2343
←
11
VERTICAL VANE
9
CWE241150
←
12
CONNECTING BAR
1
CWE261072
←
13
CONNECTING BAR
1
CWE261065
←
14
AIR SWING MOTOR
2
CWA98260
←
0
15
LEAD WIRE - AIR SWING MOTOR
1
CWA67C3849
←
16
CAP - DRAIN TRAY
1
CWH521096
←
17
HORIZONTAL VANE
1
CWE241173
←
18
BACK COVER CHASSIS
1
CWD932454
←
19
CONTROL BOARD CASING
1
CWH102259
←
20
TERMINAL BOARD COMPLETE
1
CWA28C2082
←
0
21
POWER SUPPLY CORD
1
-
-
22
ELECTRONIC CONTROLLER - MAIN
1
CWA73C1667
CWA73C1668
0
23
LEAD WIRE - AIR SWING MOTOR
1
CWA67C3977
←
0
24
SENSOR COMPLETE
1
CWA50C2122
←
0
25
CONTROL BOARD FRONT COVER
1
CWH13C1120
←
26
INDICATOR COMPLETE
1
CWE39C1126
←
0
27
INDICATOR HOLDER
1
CWD932429
←
28
INDICATOR HOLDER
1
CWD932430
←
29
CONTROL BOARD TOP COVER
1
CWH131207
←
30
REMOTE CONTROL COMPLETE
1
CWA75C2616
←
0
31
FRONT GRILLE COMPLETE
1
CWE11C3138
←
0
32
INTAKE GRILLE
1
CWE22C1154
←
33
GRILLE DOOR
1
CWE141073
←
34
AIR FILTER
2
CWD001144
←
35
SCREW - FRONT GRILLE
2
XTT4+16C
←
36
CAP - FRONT GRILLE
2
CWH521109
←
37
DRAIN HOSE
1
CWH851063
←
38
INSTALLATION PLATE
1
CWH361067
←
39
BAG COMPLETE - INSTALLATION SCREW
1
CWH82C067
←
40
FULCRUM
1
CWH621046
←
41
ELECTRONIC CONTROLLER - IONIZER
1
CWA743675
←
0
42
CASING - IONIZER
1
CWD932464
←
43
CASING - IONIZER
1
CWD932431
←
44
ION GENERATOR
1
CWH94C0001
←
45
SUPERSONIC AIR PURIFYING DEVICE
1
CWH91C1013
←
46
ELECTRONIC CONTROLLER SUPERSONIC
1
CWA743874
←
0
47
SUPER ALLERU BUSTER FILTER
1
CWD00C1133
←
48
FRAME FR AIR FILTER SUPERSONIC
1
CWD011026
←
49
FRAME FR AIR FILTER SUPERSONIC
1
CWD011027
←
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
84
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
16 Exploded View (Outdoor Unit)
16.1. CU-E9DKE CU-E12DKE
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
85
CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE
17 Replacement Parts List (Outdoor Unit)
17.1. CU-E9DKE CU-E12DKE
REF NO.
DESCRIPTION & NAME
QTY.
CU-E9DKE
CU-E12DKE
REMARKS
1
CHASSY ASSY
1
CWD50K2073
←
2
ANTI-VIBRATION BUSHING
3
CWH50077
←
3
COMPRESSOR
1
5RS102XBC01
←
O
4
NUT-COMPRESSOR MOUNT
3
CWH56000
←
5
SOUND PROOF MATERIAL
1
CWG302293
←
6
FAN MOTOR BRACKET
1
CWD541030
←
7
FAN MOTOR
1
CWA951418
CWA951309
O
8
SCREW - FAN MOTOR BRACKET
2
CWH551060
←
9
SCREW - FAN MOTOR MOUNT
4
CWH55406
←
10
PROPELLER FAN ASSY
1
CWH03K1006
←
11
NUT - PROPELLER FAN
1
CWH56053
←
12
CONDENSER
1
CWB32C1560
CWB32C1599
13
TUBE ASS’Y CO (CAP./CHK VALVE)
1
CWT01C3257
CWT01C3258
14
HOLDER-COUPLING COMPLETE
1
CWH351023
←
15
3 WAYS VALVE
1
CWB011296
CWB011297
O
16
4 WAYS VALVE
1
CWB001037
←
O
17
SOUND PROOF MATERIAL
1
CWG302292
←
18
2 WAYS VALVE
1
CWB021255
←
O
19
DRYER
1
CWB101017
←
O
20
V-COIL COMPLETE
1
CWA43C2143
←
O
21
REACTOR
1
CWA421050
-
22
SENSOR COMPLETE
1
CWA50C2196
←
23
CONTROL BOARD CASING
1
CWH102273
←
24
TERMINAL BOARD ASSY
1
CWA28K1110
←
25
FUSE HOLDERS
1
K5D203BBA002
←
26
CONTROL BOARD
1
CWH102114
←
27
CONTROL BOARD
1
CWH102115
←
28
ELECTRONIC CONTROLLER
1
CWA73C1672R
CWA73C1673R
O
29
CONTROL BOARD COVER
1
CWH131104
←
30
SENSOR COMPLETE
1
CWA50C2066
←
31
HOLDER SENSOR
1
CWH321010
←
32
TERMINAL COVER
1
CWH171001
←
33
NUT-TERMINAL COVER
1
CWH7080300
←
34
CABINET SIDE PLATE CO.
1
CWE04C1011
←
35
CABINET SIDE PLATE (LEFT)
1
CWE041031A
←
36
HANDLE
1
CWE161010
←
37
WIRE NET
1
CWD041054A
←
38
CABINET FRONT PLATE CO.
1
CWE06C1039
←
39
CABINET TOP PLATE
1
CWE031014A
←
40
CONTROL BOARD COVER
1
CWH131110
←
41
CONTROL BOARD COVER
1
CWH131093
←
42
OPERATING
INSTRUCTION
(ENG.,
ESP.,
ITA.,
NED.,
POR., GRE., BUL.)
1
CWF564451
←
43
INSTALLATION INSTRUCTION (ENG., ESP., FRA., DEU.)
1
CWF612674
←
44
L-TUBE
1
CWH5850080
←
45
INSTALLATION INSTRUCTION (NED., GRE., ITA., POR.)
1
CWF612675
←
46
INSTALLATION INSTRUCTION (BUL.)
1
CWF612676
←
47
OPERATING INSTRUCTION (FRA., DEU., SWE., NOR.)
1
CWF564445
←
48
PACKING-L.TUBE
1
CWB81012
←
49
SOUND PROOF BOARD
1
CWH151025
←
(Note)
• All parts are supplied from PHAAM Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
86