Panasonic CS-E9DKEW Service Manual

Text of the manual

2.1. Remote Control

3 2.2. Indoor Unit 4 2.3. Outdoor Unit 6 3 Product Specifications 7 3.1. CS-E9DKEW CU-E9DKE 7 3.2. CS-E12DKEW CU-E12DKE 9 4 Dimensions 11 4.1. Indoor Unit & Remote Control 11 4.2. Outdoor Unit 12 5 Refrigeration Cycle Diagram 13 6 Block Diagram 14 7 Wiring Diagram 15 8 Operation Details 16 8.1. Basic Function 16 © 2004 Panasonic HA Air-Conditioning (M) Sdn Bhd (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law. CS-E9DKEW CU-E9DKE CS-E12DKEW CU-E12DKE 8.2. Protection Control Features 35 9 Operating Instructions 44 10 Installation Instructions 50 10.1. Safety Precautions 50 10.2. Indoor Unit 53 10.3. Outdoor Unit 57 11 Installation And Servicing Air Conditioner Using R410A 61 11.1. Outline 61 11.2. Tools For Installing/Servicing Refrigerant Piping 62 11.3. Refrigerant Piping Work 66 11.4. Installation, Transferring, Servicing 68 12 Servicing Information 72 12.1. Troubleshooting 72 12.2. Breakdown Self Diagnosis Function 74 12.3. Remote Control 76 Air Conditioner CONTENTS Page Page Order No: MAC0412064C2

3 Product Specifications

3.1. CS-E9DKEW CU-E9DKE Unit CS-E9DKEW CU-E9DKE Cooling Capacity kW kcal/h BTU/h 2.6 (0.80 - 3.00) 2,240 (690 - 2,580) 8,870 (2,050 - 10,200) Heating Capacity kW kcal/h BTU/h 3.6 (0.80 - 5.00) 3,100 (690 - 4,300) 12,300 (2,050 - 17,100) Moisture Removal l/h Pint/h 1.6 (3.4) Power Source (Phase, Voltage, Cycle) ø V Hz Single 230 50 Airflow Method OUTLET INTAKE SIDE VIEW TOP VIEW Air Volume Lo m3/min (cfm) Cooling; 6.2 (220) — Heating; 6.6 (230) Me m3/min (cfm) Cooling; 7.9 (280) — Heating; 8.6 (300) Hi m3/min (cfm) Cooling; 9.6 (340) Cooling; 29.8 (1,050) Heating; 10.5 (370) SHi m3/min (cfm) Cooling; 9.9 (350) — Heating; 10.8 (380) dB (A) Cooling; High 39, Low 26 Cooling; 46 Heating; High 40, Low 27 Heating; 47 Noise Level Power level dB Cooling; High 50 Cooling; High 59 Heating; High 51 Heating; High 60 Electrical Data Input W Cooling; 600 (175 - 780) Heating; 845 (165 - 1,360) Running Current A Cooling; 2.9 Heating; 4.0 EER W/W (kcal/hw), BTU/hw Cooling; 4.33 (3.73), 14.8 COP W/W (kcal/hw), BTU/hw Heating; 4.26 (3.67), 14.6 Starting Current A 4.0 Piping Connection Port (Flare piping) inch inch G ; Half Union 3/8” L ; Half Union 1/4” G ; 3-way valve 3/8” L ; 2-way valve 1/4” Pipe Size (Flare piping) inch inch G (gas side) ; 3/8” L (liquid side) ; 1/4” G (gas side) ; 3/8” L (liquid side) ; 1/4” Drain Hose Inner diameter mm 12 — Length m 0.65 — 7 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

Power Cord Length

Number of core-wire — — — — Dimensions Height inch (mm) 11 - 1/32 (280) 21 - 1/4 (540) Width inch (mm) 31 - 15/32 (799) 30 - 23/32 (780) Depth inch (mm) 7 - 7/32 (183) 11 - 3/8 (289) Net Weight lb (kg) 20 (9.0) 82 (37) Compressor Type — Hermetic Rotary Motor Type — Brushless (6-pole) Rated Output W — 700 Air Circulation Type Cross-flow Fan Propeller Fan Material ASG20k1 P.P Motor Type Transistor (8-poles) Induction (6-poles) Input W — 61.3 Rate Output W 30 28 Fan Speed Lo (Cool/Heat) rpm 820/880 — Me (Cool/Heat) rpm 1,050/1,140 — Hi (Cool/Heat) rpm 1,280/1,400 770 SHi (Cool/Heat) rpm 1,320/1,440 — Heat Exchanger Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium Fin Type Slit Fin Corrugated Fin Row / Stage (Plate fin configuration, forced draft) 2 / 15 2 / 24 FPI 21 17 Size (W × H × L) mm 610 × 315 × 25.4 718.4 689.8 × 504 × 36.4 Refrigerant Control Device — Capillary Tube Refrigeration Oil (cm3) — RB68A (320) Refrigerant (R410A) g (oz) — 965 (34.1) Thermostat Electronic Control — Protection Device Electronic Control Electronic Control Length mm — C1, C2 ; 950, C3 ; 411 Capillary Tube Flow Rate l/min — C1, C2 ; 4.1, C3 ; 18.8 Inner Diameter mm — C1, C2 ; 1.1, C3 ; 1.7 Air Filter Material Style P.P. Honeycomb — Fan Motor Capacitor µF, VAC — 2.0 µF, 440 VAC Compressor Capacitor µF, VAC — 65 µF, 350 VAC • Specifications are subject to change without notice for further improvement. 8 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

3.50 (0.80 - 4.00)

3,010 (690 - 3,440) 11,950 (2,730 - 13,600) Heating Capacity kW kcal/h BTU/h 4.80 (0.80 - 6.50) 4,130 (690 - 5,590) 16,400 (2,730 - 22,200) Moisture Removal l/h Pint/h 2.0 (4.2) Power Source (Phase, Voltage, Cycle) ø V Hz Single 230 50 Airflow Method OUTLET INTAKE SIDE VIEW TOP VIEW Air Volume Lo m3/min (cfm) Cooling; 6.9 (240) — Heating; 8.1 (290) Me m3/min (cfm) Cooling; 8.8 (310) — Heating; 9.7 (340) Hi m3/min (cfm) Cooling; 10.7 (380) Cooling; 31.0 (1,090) Heating; 11.2 (400) SHi m3/min (cfm) Cooling; 11.0 (390) — Heating; 11.6 (410) dB (A) Cooling; High 42, Low 29 Cooling; 48 Heating; High 42, Low 33 Heating; 50 Noise Level Power level dB Cooling; High 53 Cooling; High 61 Heating; High 53 Heating; High 63 Electrical Data Input W Cooling; 965 (185 - 1,200) Heating; 1,260 (175 - 1,890) Running Current A Cooling; 4.5 Heating; 5.8 EER W/W (kcal/hw), BTU/hw Cooling; 3.63 (3.12), 12.4 COP W/W (kcal/hw), BTU/hw Heating; 3.81 (3.28), 13.0 Starting Current A 5.8 Piping Connection Port (Flare piping) inch inch G ; Half Union 1/2” L ; Half Union 1/4” G ; 3-way valve 1/2” L ; 2-way valve 1/4” Pipe Size (Flare piping) inch inch G (gas side) ; 1/2” L (liquid side) ; 1/4” G (gas side) ; 1/2” L (liquid side) ; 1/4” Drain Hose Inner diameter mm 12 — Length m 0.65 — Power Cord Length Number of core-wire — — — — 9 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

11 - 1/32 (280)

21 - 1/4 (540) Width inch (mm) 31 - 15/32 (799) 30 - 23/32 (780) Depth inch (mm) 7 - 7/32 (183) 11 - 3/8 (289) Net Weight lb (kg) 20 (9.0) 82 (37) Compressor Type — Hermetic Rotary Motor Type — Brushless (6-pole) Rated Output W — 700 Air Circulation Type Cross-flow Fan Propeller Fan Material ASG20k1 P.P Motor Type Transistor (8-poles) Induction (6-poles) Input W — 65.9 Rate Output W 30 29 Fan Speed Lo (Cool/Heat) rpm 910/1,080 — Me (Cool/Heat) rpm 1,165/1,290 — Hi (Cool/Heat) rpm 1,420/1,500 830 SHi (Cool/Heat) rpm 1,460/1,540 — Heat Exchanger Description Evaporator Condenser Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium Fin Type Slit Fin Corrugated Fin Row / Stage (Plate fin configuration, forced draft) 2 / 15 2 / 24 FPI 21 17 Size (W × H × L) mm 610 × 315 × 25.4 718.4 689.8 × 504 × 36.4 Refrigerant Control Device — Capillary Tube Refrigeration Oil (cm3) — RB68A (320) Refrigerant (R410A) g (oz) — 980 (34.6) Thermostat Electronic Control — Protection Device Electronic Control Electronic Control Length mm — C1, C2 ; 1,120, C3 ; 370 Capillary Tube Flow Rate l/min — C1, C2 ; 4.9, C3 ; 19.6 Inner Diameter mm — C1, C2 ; 1.2, C3 ; 1.7 Air Filter Material Style P.P. Honeycomb — Fan Motor Capacitor µF, VAC — 2.0 µF, 440 VAC Compressor Capacitor µF, VAC — 65 µF, 350 VAC • Specifications are subject to change without notice for further improvement. 10 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

Indoor Unit & Remote Control

4.1.1. CS-E9DKEW CS-E12DKEW 11 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

Applicable piping kit

CZ-3F5, 7BP (E9DK) CZ-4F5, 7, 10BP (E12DK) SELECT THE BEST LOCATION INDOOR UNIT • There should not be any heat source or steam near the unit. • There should not be any obstacles blocking the air circulation. • A place where air circulation in the room is good. • A place where drainage can be easily done. • A place where noise prevention is taken into consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles. • Recommended installation height for indoor unit shall be at least 2.3 m. OUTDOOR UNIT • If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed. • There should not be any animal or plant which could be affected by hot air discharged. • Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles. • Do not place any obstacles which may cause a short circuit of the discharged air. • If piping length is over the rated length, additional refrigerant should be added as shown in the table. Indoor/Outdoor Unit Installation Diagram • This illustration is for explanation purposes only. The indoor unit will actually face a different way. 52 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

1. Rated Frequency Operation

12 Servicing Information Caution: • Pb free solder has a higher melting point than standard solder; Typically the melting point is 50 - 70°F (30 - 40°C) higher. Please use a high temperature soldering iron. In case of the soldering iron with temperature control, please set it to 700 ± 20°F (370 ± 10°C). • Pb free solder will tend to splash when heated too high (about 1100° F/600°C). 12.1. Troubleshooting During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the specification and technical data. Below are the methods used to obtain rated compressor operating specification. (a) Cooling (i) Press the Auto button continuously for 5 seconds or less than 8 seconds, the air conditioner starts operation at Cooling rated frequency. (“beep” will be heard at the 5th second.) (ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The operation of air conditioner is Cooling rated frequency. (b) Heating Press the Auto button continuously for 8 seconds or less than 11 seconds, the air conditioner starts operation at Heating rated frequency. (“beep” “beep” will be heard at the 8th second.) 72 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

2. Troubleshooting Air Conditioner

Refrigeration cycle system In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table to the right. 73 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

1. Relationship between the condition of the air conditioner and pressure and electric current

Cooling Mode Heating Mode Condition of the air conditoner Low Pressure High Pressure Electric current during operation Low Pressure High Pressure Electric current during operation Insufficient refrigerant (gas leakage) Clogged capillary tube or Strainer Short circuit in the indoor unit Heat radiation deficiency of the outdoor unit Inefficient compression • Carry on the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started. 12.2. Breakdown Self Diagnosis Function Once abnormality detected during operation, the unit will immediately stop its operation (Timer LED is blinking) and maximum of three error codes (abnormality) will be saved in memory. The abnormality of the operation can be identified through the below breakdown diagnosis method: • Press “CHECK” button at remote controller continuously for more than five seconds to turn on the diagnosis mode, “H11” will be displayed at remote controller. • By pressing the TMER “ ” button once, next error code will be displayed; press “V” button once, previous error code will be displayed. • If error code displayed matches the error code saved in unit memory (abnormality detected), “beep, beep, beep....” sounds will be heard for 4 seconds and Power LED will light on. Otherwise, one “beep” sound is heard. If “CHECK” button is press again or without any operation for 30 seconds, the diagnosis mode will turn off. 74 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

Error Codes Table

Diagnosis display Abnormality / Protection control Abnormality Judgement Emergency operation Primary location to verify H11 Indoor / outdoor abnormal communication > 1 min after starting operation Indoor fan operation only • Internal / external cable connections • Indoor / Outdoor PCB H12 Connection capability rank abnormal — — — H14 Indoor intake air temperature sensor abnormality Continue for 5 sec. — • Intake air temperature sensor (detective or disconnected) H15 Outdoor compressor temperature sensor abnormality Continue for 5 sec. — • Compressor temperature sensor (detective or disconnected) H16 Outdoor Current Transformer open circuit — — • Outdoor PCB • IPM (Power transistor) module H19 Indoor fan motor merchanism lock — — • Indoor PCB • Fan motor H23 Indoor heat exchanger temperature sensor abnormality Continue for 5 sec. O (Cooling only) • Heat exchanger temperature sensor (defective or disconnected) H26 Ionizer breakdown — — • Ionizer H27 Outdoor air temperature sensor abnormality Continue for 5 sec. O • Outdoor temperature sensor (defective or disconnected) H28 Outdoor heat exchanger temperature sensor abnormality Continue for 5 sec. O • Outdoor heat exchanger temperature sensor (defective or disconnected) H33 Indoor/Outdoor wrong connection — — • Indoor/Outdoor supply voltage H38 Indoor / outdoor mismatch (brand code) — — — H98 Indoor high pressure protection — — • Air filter dirty • Air circulation short circuit H99 Indoor heat exchanger anti-freezing protection — — • Insufficient refrigerant • Air filter dirty F11 Cooling / Heating cycle changeover abnormality 4 times occurance within 30 minutes — • 4-way valve • V-coil F90 PFC control 4 times occurance within 10 minutes — • Voltage at PFC F91 Refrigeration cycle abnormality 2 times occurance within 20 minutes — • No refrigerant (3-way valve is closed) F93 Compressor rotation failure — — • Compressor F95 Cool high pressure protection 4 times occurance within 20 minutes — • Outdoor refrigerant circuit F96 IPM (power transistor) overheating protection — — • Excess refrigerant • Improper heat radiation • IPM (Power transistor) F97 Outdoor compressor overheating protection 4 times occurance within 10 minutes — • Insufficient refrigerant • Compressor F98 Total running current protection 3 times occurance within 20 minutes — • Excess refrigerant • Improper heat radiation F99 Outdoor Direct Current (DC) peak detection 7 times occurance continuously — • Outdoor PCB • IPM (Power transistor) • Compressor Note: “O” - Frequency measured and fan speed fixed. The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until “beep” sound heard following by pressing the “RESET” button at remote controller. Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors (refer to Error Codes Table) by using remote controller or Auto Switch at indoor unit. However, the remote controller signal receiving sound is changed from one “beep” to four “beep” sounds. 75 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

• Remote Control Reset

When the batteries are inserted for the first time, or the batteries are replaced, all the indications will blink and the remote control might not work. If this happen, remove the cover of the remote control and push the reset point once to clear the memory data. • Changing the wireless remote control transmission code When there are more than one indoor units installed in the same room, it is possible to set different remote control receiving signal by modifying the jumpers inside remote controller. 12.3. Remote Control 76 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

1 Technical Data (Page: 80 - 81)

1.1. Operation Characteristics 1.1.1. CS-E9DKEW CU-E9DKE 2 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

[PHAAM] Printed in Malaysia

13.2. Sensible Capacity Chart

●CS-E9DKEW CU-E9DKE 230V Outdoor Temp. (°C) Indoor wet bulb temp. 30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 2.58 1.96 0.55 2.41 1.88 0.59 2.24 1.80 0.63 2.04 1.71 0.68 19.0°C 2.60 0.60 19.5°C 2.83 2.05 0.56 2.65 1.97 0.60 2.46 1.89 0.64 2.24 1.80 0.69 22.0°C 3.09 2.12 0.57 2.88 2.04 0.61 2.68 1.97 0.66 2.44 1.88 0.71 ●CS-E12DKEW CU-E12DKE 230V Outdoor Temp. (°C) Indoor wet bulb temp. 30 35 40 46 TC SHC IP TC SHC IP TC SHC IP TC SHC IP 17.0°C 3.47 2.63 0.88 3.24 2.52 0.95 3.02 2.43 1.02 2.74 2.30 1.10 19.0°C 3.50 0.97 19.5°C 3.81 2.76 0.90 3.56 2.65 0.97 3.31 2.55 1.04 3.01 2.43 1.12 22.0°C 4.15 2.86 0.92 3.88 2.75 0.99 3.61 2.65 1.05 3.28 2.53 1.14 82 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

14 Exploded View (Indoor Unit)

14.1. CS-E9DKEW CS-E12DKEW Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. 83 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

15 Replacement Parts List (Indoor Unit)

15.1. CS-E9DKEW CS-E12DKEW REF. NO. PART NAME & DESCRIPTION QTY. CS-E9DKEW CS-E12DKEW REMARKS 1 CHASSY COMPLETE 1 CWD50C1431 ← 2 FAN MOTOR 1 CWA981149 ← 0 3 CROSS FLOW FAN COMPLETE 1 CWH02C1031 ← 4 BEARING ASS’Y 1 CWH64K007 ← 5 SCREW - CROSS FLOW FAN 1 CWH4580304 ← 6 EVAPORATOR 1 CWB30C1597 CWB30C1726 7 FLARE NUT 1 CWT25086 (1/4”) ← 8 FLARE NUT 1 CWT25087 (3/8”) CWT25096 (1/2”) 9 HOLDER SENSOR 1 CWH32143 ← 10 DISCHARGE GRILLE COMPLETE 1 CWE20C2343 ← 11 VERTICAL VANE 9 CWE241150 ← 12 CONNECTING BAR 1 CWE261072 ← 13 CONNECTING BAR 1 CWE261065 ← 14 AIR SWING MOTOR 2 CWA98260 ← 0 15 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3849 ← 16 CAP - DRAIN TRAY 1 CWH521096 ← 17 HORIZONTAL VANE 1 CWE241173 ← 18 BACK COVER CHASSIS 1 CWD932454 ← 19 CONTROL BOARD CASING 1 CWH102259 ← 20 TERMINAL BOARD COMPLETE 1 CWA28C2082 ← 0 21 POWER SUPPLY CORD 1 - - 22 ELECTRONIC CONTROLLER - MAIN 1 CWA73C1667 CWA73C1668 0 23 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3977 ← 0 24 SENSOR COMPLETE 1 CWA50C2122 ← 0 25 CONTROL BOARD FRONT COVER 1 CWH13C1120 ← 26 INDICATOR COMPLETE 1 CWE39C1126 ← 0 27 INDICATOR HOLDER 1 CWD932429 ← 28 INDICATOR HOLDER 1 CWD932430 ← 29 CONTROL BOARD TOP COVER 1 CWH131207 ← 30 REMOTE CONTROL COMPLETE 1 CWA75C2616 ← 0 31 FRONT GRILLE COMPLETE 1 CWE11C3138 ← 0 32 INTAKE GRILLE 1 CWE22C1154 ← 33 GRILLE DOOR 1 CWE141073 ← 34 AIR FILTER 2 CWD001144 ← 35 SCREW - FRONT GRILLE 2 XTT4+16C ← 36 CAP - FRONT GRILLE 2 CWH521109 ← 37 DRAIN HOSE 1 CWH851063 ← 38 INSTALLATION PLATE 1 CWH361067 ← 39 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C067 ← 40 FULCRUM 1 CWH621046 ← 41 ELECTRONIC CONTROLLER - IONIZER 1 CWA743675 ← 0 42 CASING - IONIZER 1 CWD932464 ← 43 CASING - IONIZER 1 CWD932431 ← 44 ION GENERATOR 1 CWH94C0001 ← 45 SUPERSONIC AIR PURIFYING DEVICE 1 CWH91C1013 ← 46 ELECTRONIC CONTROLLER SUPERSONIC 1 CWA743874 ← 0 47 SUPER ALLERU BUSTER FILTER 1 CWD00C1133 ← 48 FRAME FR AIR FILTER SUPERSONIC 1 CWD011026 ← 49 FRAME FR AIR FILTER SUPERSONIC 1 CWD011027 ← (Note) • All parts are supplied from PHAAM, Malaysia (Vendor Code: 061). • “O” marked parts are recommended to be kept in stock. 84 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

16 Exploded View (Outdoor Unit)

16.1. CU-E9DKE CU-E12DKE Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts. 85 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE

17 Replacement Parts List (Outdoor Unit)

17.1. CU-E9DKE CU-E12DKE REF NO. DESCRIPTION & NAME QTY. CU-E9DKE CU-E12DKE REMARKS 1 CHASSY ASSY 1 CWD50K2073 ← 2 ANTI-VIBRATION BUSHING 3 CWH50077 ← 3 COMPRESSOR 1 5RS102XBC01 ← O 4 NUT-COMPRESSOR MOUNT 3 CWH56000 ← 5 SOUND PROOF MATERIAL 1 CWG302293 ← 6 FAN MOTOR BRACKET 1 CWD541030 ← 7 FAN MOTOR 1 CWA951418 CWA951309 O 8 SCREW - FAN MOTOR BRACKET 2 CWH551060 ← 9 SCREW - FAN MOTOR MOUNT 4 CWH55406 ← 10 PROPELLER FAN ASSY 1 CWH03K1006 ← 11 NUT - PROPELLER FAN 1 CWH56053 ← 12 CONDENSER 1 CWB32C1560 CWB32C1599 13 TUBE ASS’Y CO (CAP./CHK VALVE) 1 CWT01C3257 CWT01C3258 14 HOLDER-COUPLING COMPLETE 1 CWH351023 ← 15 3 WAYS VALVE 1 CWB011296 CWB011297 O 16 4 WAYS VALVE 1 CWB001037 ← O 17 SOUND PROOF MATERIAL 1 CWG302292 ← 18 2 WAYS VALVE 1 CWB021255 ← O 19 DRYER 1 CWB101017 ← O 20 V-COIL COMPLETE 1 CWA43C2143 ← O 21 REACTOR 1 CWA421050 - 22 SENSOR COMPLETE 1 CWA50C2196 ← 23 CONTROL BOARD CASING 1 CWH102273 ← 24 TERMINAL BOARD ASSY 1 CWA28K1110 ← 25 FUSE HOLDERS 1 K5D203BBA002 ← 26 CONTROL BOARD 1 CWH102114 ← 27 CONTROL BOARD 1 CWH102115 ← 28 ELECTRONIC CONTROLLER 1 CWA73C1672R CWA73C1673R O 29 CONTROL BOARD COVER 1 CWH131104 ← 30 SENSOR COMPLETE 1 CWA50C2066 ← 31 HOLDER SENSOR 1 CWH321010 ← 32 TERMINAL COVER 1 CWH171001 ← 33 NUT-TERMINAL COVER 1 CWH7080300 ← 34 CABINET SIDE PLATE CO. 1 CWE04C1011 ← 35 CABINET SIDE PLATE (LEFT) 1 CWE041031A ← 36 HANDLE 1 CWE161010 ← 37 WIRE NET 1 CWD041054A ← 38 CABINET FRONT PLATE CO. 1 CWE06C1039 ← 39 CABINET TOP PLATE 1 CWE031014A ← 40 CONTROL BOARD COVER 1 CWH131110 ← 41 CONTROL BOARD COVER 1 CWH131093 ← 42 OPERATING INSTRUCTION (ENG., ESP., ITA., NED., POR., GRE., BUL.) 1 CWF564451 ← 43 INSTALLATION INSTRUCTION (ENG., ESP., FRA., DEU.) 1 CWF612674 ← 44 L-TUBE 1 CWH5850080 ← 45 INSTALLATION INSTRUCTION (NED., GRE., ITA., POR.) 1 CWF612675 ← 46 INSTALLATION INSTRUCTION (BUL.) 1 CWF612676 ← 47 OPERATING INSTRUCTION (FRA., DEU., SWE., NOR.) 1 CWF564445 ← 48 PACKING-L.TUBE 1 CWB81012 ← 49 SOUND PROOF BOARD 1 CWH151025 ← (Note) • All parts are supplied from PHAAM Malaysia (Vendor Code: 061). • “O” marked parts are recommended to be kept in stock. 86 CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKE