iBall NIRANTAR 1006B Operation & User’s Manual

Text of the manual

Table of Contents

1. Important Safety Warning ....................................................................................................... 1 1-1. Transportation ................................................................................................................. 1 1-2. Preparation ..................................................................................................................... 1 1-3. Installation ....................................................................................................................... 1 1-4. Operation ........................................................................................................................ 1 1-5. Maintenance, service and faults ...................................................................................... 2 2. Installation and Setup ............................................................................................................. 3 2-1. Rear panel view .............................................................................................................. 3 2-2. Setup the UPS ................................................................................................................ 3 3. Operations .............................................................................................................................. 5 3-1. Button operation .............................................................................................................. 5 3-2. LCD Panel ...................................................................................................................... 5 3-3. Audible Alarm .................................................................................................................. 7 3-4. LCD display wordings index ............................................................................................ 7 3-5. UPS Setting .................................................................................................................... 7 3-6. Operating Mode Description ......................................................................................... 12 3-7. Faults Reference Code ................................................................................................. 13 3-8. Warning indicator .......................................................................................................... 13 4. Troubleshooting .................................................................................................................... 14 5. Storage and Maintenance .................................................................................................... 15 6. Specifications ....................................................................................................................... 16

1. Important Safety Warning

Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully 1-1. Transportation  Please transport the UPS system only in the original package to protect against shock and impact. 1-2. Preparation  Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.  Do not install the UPS system near water or in moist environments.  Do not install the UPS system where it would be exposed to direct sunlight or near heater.  Do not block ventilation holes in the UPS housing. 1-3. Installation  Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.  Place cables in such a way that no one can step on or trip over them.  Do not connect domestic appliances such as hair dryers to UPS output sockets.  The UPS can be operated by any individuals with no previous experience.  Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.  Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shockproof outlet).  Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.  When installing the equipment, it should ensure that the sum of the leakage current of the UPS and the connected devices does not exceed 3.5mA. 1-4. Operation  Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.  The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.  In order to fully disconnect the UPS system, first press the OFF/Enter button to disconnect the mains.  Prevent no fluids or other foreign objects from inside of the UPS system.

1-5. Maintenance, service and faults

 The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.  Caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.  Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.  Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.  Caution - risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!  Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries: -remove wristwatches, rings and other metal objects -use only tools with insulated grips and handles.  When changing batteries, install the same number and same type of batteries.  Do not attempt to dispose of batteries by burning them. This could cause battery explosion.  Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.  Please replace the fuse only with the same type and amperage in order to avoid fire hazards.  Do not dismantle the UPS system.

2. Installation and Setup

NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. NOTE: There are two different types of Online UPS: standard and long-run models. Please refer to the following model table. Model Type Capacity 1006B With Battery 1KVA 1012E Without Battery 1KVA 3001E Without Battery 3KVA 2-1. Rear panel view iBall Nirantar Online UPS – 1006B / 1012E iBall Nirantar Online UPS – 3001E 1. AC Input 2. Input Circuit Breaker 3. USB Communication Port 4. RS-232 Communication Port 5. SNMP Intelligent Slot 6. External Battery Connection (only available for E model) 7. Output Receptacles 2-2. Setup the UPS Step 1: UPS input connection Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. The power cord is supplied in the UPS package. Step 2: UPS output connection  For socket-type outputs, simply connect devices to the outlets.  For terminal-type input or outputs, please follow below steps for the wiring configuration: a) Remove the small cover of the terminal block b) Suggest using AWG14 or 2.1mm2 power cords. c) Upon completion of the wiring configuration, please check whether the wires are securely affixed. d) Put the small cover back to the rear panel.

Step 3: Communication connection

Communication port: USB port RS-232 port Intelligent slot To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC. The UPS is equipped with intelligent slot perfect for SNMP card. When installing SNMP card in the UPS, it will provide advanced communication and monitoring options. Please note: USB port and RS-232 port can’t work at the same time. Step 4: Turn ON the UPS Press the ON/Mute button on the front panel for two seconds to power on the UPS. Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period. Step 5: Install software For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If not, please click on below link to download and install monitoring software from the internet: http://www.iBall.co.in/File/Product/Drivers/iBall%20ViewPower%20For%20Windows.rar 1. Follow the on-screen instructions to install the software. 2. When your computer restarts, the monitoring software will appear as an orange plug icon located in the system tray, near the clock. Note: For Linux or Mac software, please visit www.iBall.co.in website or write us at [email protected] Step 6: External battery connection (for E models only) Follow the right chart to make external battery connection.

3-1. Button operation

Button Function ON/Mute Button  Turn on the UPS: Press and hold ON/Mute button for at least 2 seconds to turn on the UPS.  Mute the alarm: When the UPS is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system. But it’s not applied to the situations when warnings or errors occur.  Up key: Press this button to display previous selection in UPS setting mode.  Switch to UPS self-test mode: Press and hold ON/Mute button for 5 seconds to enter UPS self-testing while in AC mode, ECO mode, or converter mode. OFF/Enter Button  Turn off the UPS: Press and hold this button at least 2 seconds to turn off the UPS. UPS will be in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button.  Confirm selection key: Press this button to confirm selection in UPS setting mode. Select Button  Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery voltage, output voltage and output frequency. It will return back to default display when pausing for 10 seconds.  Setting mode: Press and hold this button for 5 seconds to enter UPS setting mode when UPS is in standby mode or bypass mode.  Down key: Press this button to display next selection in UPS setting mode. ON/Mute + Select Button  Switch to bypass mode: When the main power is normal, press ON/Mute and Select buttons simultaneously for 5 seconds. Then UPS will enter to bypass mode. This action will be ineffective when the input voltage is out of acceptable range. 3-2. LCD Panel

Remaining backup time information

Indicates the remaining backup time in pie chart. Indicates the remaining backup time in numbers. H: hours, M: minute, S: second Fault information Indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes are listed in details in 3-5 section. Mute operation Indicates that the UPS alarm is disabled. Output & Battery voltage information Indicates the output voltage, frequency or battery voltage. Vac: output voltage, Vdc: battery voltage, Hz: frequency Load information Indicates the load level by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates overload. Indicates the load or the UPS output is short circuit. Mode operation information Indicates the UPS connects to the mains. Indicates the battery is working. Indicates the bypass circuit is working. Indicates the ECO mode is enabled. Indicates the Inverter circuit is working. Indicates the output is working. Battery information Indicates the Battery level by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the battery is fault. Indicates low battery level and low battery voltage. Input & Battery voltage information Indicates the input voltage or frequency or battery voltage. Vac: Input voltage, Vdc: battery voltage, Hz: input frequency

3-3. Audible Alarm

Battery Mode Beeping every 4 seconds Low Battery Beeping every second Overload Beeping twice every second Fault Continuously Beeping Bypass Mode Beeping every 10 seconds 3-4. LCD display wordings index Abbreviation Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss BAT Battery CF Converter TP Temperature CH Charger FU Bypass frequency unstable EE EEPROM error 3-5. UPS Setting There are three parameters to set up the UPS. Parameter 1: It’s for program alternatives. Refer to below table. Parameter 2 and parameter 3 are the setting options or values for each program. Parameter 1 Parameter 2 Parameter 3

01: Output voltage setting

Interface Setting Parameter 3: Output voltage For 200/208/220/230/240 VAC models, you may choose the following output voltage: 200: presents output voltage is 200Vac 208: presents output voltage is 208Vac 220: presents output voltage is 220Vac 230: presents output voltage is 230Vac (Default) 240: presents output voltage is 240Vac For 100/110/115/120/127 VAC models, you may choose the following output voltage: 100: presents output voltage is 100Vac 110: presents output voltage is 110Vac 115: presents output voltage is 115Vac 120: presents output voltage is 120Vac (Default) 127: presents output voltage is 127Vac 02: Frequency Converter enable/disable Interface Setting Parameter 2 & 3: Enable or disable converter mode. You may choose the following two options: CF ENA: converter mode enable CF DIS: converter mode disable(Default) 03: Output frequency setting Interface Setting Parameter 2 & 3: Output frequency setting. You may set the initial frequency on battery mode: BAT 50: presents output frequency is 50Hz BAT 60: presents output frequency is 60Hz If converter mode is enabled, you may choose the following output frequency: CF 50: presents output frequency is 50Hz CF 60: presents output frequency is 60Hz 04: ECO enable/disable Interface Setting Parameter 3: Enable or disable ECO function. You may choose the following two options: ENA: ECO mode enable DIS: ECO mode disable (Default)

05: ECO voltage range setting

Interface Setting Parameter 2 & 3: Set the acceptable high voltage point and low voltage point for ECO mode by pressing Down key or Up key. HLS: High loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to +24V of the nominal voltage. (Default: +12V) For 100/110/115/120/127 VAC models, the setting range in parameter 3 is from +3V to +12V of the nominal voltage. (Default: +6V) LLS: Low loss voltage in ECO mode in parameter 2. For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to -24V of the nominal voltage. (Default: -12V) For 100/110/115/120/127 VAC models, the setting voltage in parameter 3 is from -3V to -12V of the nominal voltage. (Default: -6V) 06: Bypass enable/disable when UPS is off Interface Setting Parameter 3: Enable or disable Bypass function. You may choose the following two options: ENA: Bypass enable DIS: Bypass disable (Default) 07: Bypass voltage range setting Interface Setting Parameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage point for Bypass mode by pressing the Down key or Up key. HLS: Bypass high voltage point For 200/208/220/230/240 VAC models: 230-264: setting the high voltage point in parameter 3 from 230Vac to 264Vac. (Default: 264Vac) For 100/110/115/120/127 VAC models: 120-140: setting the high voltage point in parameter 3 from 120Vac to 140Vac. (Default: 132Vac) LLS: Bypass low voltage point For 200/208/220/230/240 VAC models: 170-220: setting the low voltage point in parameter 3 from 170Vac to 220Vac. (Default: 170Vac) For 100/110/115/120/127 VAC models: 85-115: setting the low voltage point in parameter 3 from 85Vac to 115Vac. (Default: 85Vac)

08: Autonomy limitation setting

Interface Setting Parameter 3: Set up backup time on battery mode for general outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode. 0: When setting as “0”, the backup time will be only 10 seconds. 999: When setting as “999”, the backup time setting will be disabled. (Default) 00: Exit setting Battery Group Number Setting For proper backup time details, please set Battery group number details as per below method 1. Open iBall View Power software, if you have not installed, then download and Install from provided link below www.iBall.co.in/File/Product/Drivers/iBall%20ViewPower%20For%20Windows.rar 2. Before setting the Battery group of UPS, make sure that Batteries should be connected and the UPS is ON 3. Use USB cable to connect the UPS with Computer 4. It will get detect and configured automatically, no need to install any driver. 5. Double click and open application. The main window Figure will be shown as under

6. Click the “UPS Setting” option and select “Parameters Setting”. (Please see images below)

7. The parameters setting windows will be shown as below.

8. Input the group number to the box of marked in above image, and click the right side “Apply” button.

Note: Please follow below steps to calculate Battery group number to insert into “Number in marked box. a. Battery group number = External battery AH / Standard UPS battery AH For example,If you have connected 100AH batteries Standard UPS battery AH for 3KVA is 9AH; means Battery group number = 100/9 ~=11. 9. Insert “11” in Battery number setting, under “Number in Parallel” box, If the password dialog will popup. Please enter the password (default password is “administrator”). If the password is ok, please click the “Apply” button once again, and then the setting will be saved. 10. Disconnect the AC input and wait until the LCD display is off. The setting of ups is finish. 3-6. Operating Mode Description Operating mode Description LCD display Online mode When the input voltage is within acceptable range, UPS will provide pure and stable AC power to output. The UPS will also charge the battery at online mode. ECO mode Energy saving mode: When the input voltage is within voltage regulation range, UPS will bypass voltage to output for energy saving. Frequency Converter mode When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60 Hz. The UPS will still charge battery under this mode.

When the input voltage is beyond the

acceptable range or power failure and alarm is Beeping every 4 second, UPS will backup power from battery. Bypass mode When input voltage is within acceptable range but UPS is overload, UPS will enter bypass mode or bypass mode can be set by front panel. Alarm is Beeping every 10 second. Standby mode UPS is powered off and no output supply power, but still can charge batteries. 3-7. Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon Bus start fail 01 x Inverter voltage Low 13 x Bus over 02 x Inverter output short 14 Bus under 03 x Battery voltage too high 27 Bus unbalance 04 x Battery voltage too low 28 Bus short 05 x Over temperature 41 x Inverter soft start fail 11 x Over load 43 Inverter voltage high 12 x 3-8. Warning indicator Warning Icon (flashing) Alarm Low Battery Beeping every second Overload Beeping twice every second Battery is not connected Beeping every second Over Charge Beeping every second Over temperature Beeping every second Charger failure Beeping every second Battery fault Beeping every second Out of bypass voltage range Beeping every second Bypass frequency unstable Beeping every second EEPROM error Beeping every second

If the UPS system does not operate correctly, please solve the problem by using the table

below. Symptom Possible cause Remedy No indication and alarm even though the mains is normal. The AC input power is not connected well. Check if input power cord firmly connected to the mains. The AC input is connected to the UPS output. Plug AC input power cord to AC input correctly. The icon and flashing on LCD display and alarm is Beeping every second. The external or internal battery is incorrectly connected. Check if all batteries are connected well. Fault code is shown as 27 and the icon is lighting on LCD display and alarm is continuously Beeping. Battery voltage is too high or the charger is fault. Contact your dealer. Fault code is shown as 28 and the icon is lighting on LCD display and alarm is continuously Beeping. Battery voltage is too low or the charger is fault. Contact your dealer. The icon and is flashing on LCD display and alarm is Beeping twice every second. UPS is overload Remove excess loads from UPS output. UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass. Remove excess loads from UPS output. After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains. Remove excess loads from UPS output first. Then shut down the UPS and restart it. Fault code is shown as 43 and The icon is lighting on LCD display and alarm is continuously Beeping. The UPS shut down automatically because of overload at the UPS output. Remove excess loads from UPS output and restart it. Fault code is shown as 14 and the icon is lighting on LCD display and alarm is continuously Beeping. The UPS shut down automatically because short circuit occurs on the UPS output. Check output wiring and if connected devices are in short circuit status.

Fault code is shown as 01,

02, 03, 04, 05, 11, 12, 13 and 41 on LCD display and alarm is continuously Beeping. A UPS internal fault has occurred. There are two possible results: 1. The load is still supplied, but directly from AC power via bypass. 2. The load is no longer supplied by power. Contact your dealer Battery backup time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity. If the problem still persists, consult your dealer. Batteries defect Contact your dealer to replace the battery. UPS Backup is proper, but remaining time Indication on display is not proper Battery Group number setting is wrong Please refer Battery Group number setting, and follow steps. Contact iBall Support team / Nearest iBall Service Centre. Fault code is shown as 05 on LCD display. At the same time, alarm is continuously Beeping and output is cut off. A UPS internal fault has occurred and BUS is short circuited. Consult your dealer. If the UPS power is on again before repair, the DC/DC mosfet will damage. 5. Storage and Maintenance Operation The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case, please contact your dealer. Storage Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: Storage Temperature Recharge Frequency Charging Duration -25°C - 40°C Every 3 months 1-2 hours 40°C - 45°C Every 2 months 1-2 hours Be sure to deliver the spent battery to a recycling facility or ship it to your dealer in the replacement battery packing material.

iBall Nirantar Online UPS

1006B (1KVA - W Battery) 1012E (1KVA - W/O Battery) 3001E (3KVA - W/O Battery) INPUT Capacity 1000 VA / 800 W 3000 VA / 2400 W Voltage Range Low Line Transfer 160 VAC / 140 VAC / 120 VAC / 110 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) Low Line Comeback 168 VAC / 148 VAC / 128VAC / 118 VAC ± 5 % ( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0) High Line Transfer 300 VAC ± 5 % or 150 VAC ± 5 % High Line Comeback 290 VAC ± 5 % or 145 VAC ± 5 % Frequency Range 40Hz ~ 70 Hz Phase Single phase with ground Power Factor ≧ 0.99 @ Nominal Voltage (Full load) OUTPUT Output Voltage 200/208/220/230/240VAC Voltage Regulation ± 1% Frequency Range (Synchronized Range) 47~ 53 Hz or 57 ~ 63 Hz Frequency Range (Batt. Mode) 50 Hz ± 0.2 Hz or 60Hz ± 0.2 Hz Current Crest Ratio 3:1 Harmonic Distortion ≦ 2 % THD (Linear Load) ≦ 4 % THD (Non-linear Load) Transfer Time AC to DC Zero Inverter to Bypass 4 ms (Typical) Waveform (Batt. Mode) Pure Sinewave EFFICIENCY To AC Mode 87% 90% To Battery Mode 83% 89% BATTERY Battery Type 12 V / 9 AH NA NA Numbers 3 3 6 Typical Recharge Time 4 hours recover to 90% capacity Depending on the capacity of external batteries Charging Current (max.) 1.0 A 1.0A/2.0A/4.0A/6.0 A Charging Voltage 41.0VDC ± 1% 82.1 VDC ±1% INDICATORS LCD or LED Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators ALARM

Beeping every 4 seconds

Low Battery Beeping every second Overload Beeping twice every second Fault Continuously Beeping PHYSICAL Dimension, D X W X H (mm) 397 X 145 X 220 419 X 190 X 318 Net Weight (kgs) 13 6 13 ENVIRONMENT Humidity 20-90 % RH @ 0- 40°C (non-condensing) Noise Level Less than 45dBA @ 1 Meter MANAGEMENT Smart RS-232 Supports Windows 2000/2003/XP/Vista/2008/7, Linux, Unix, and MAC Optional USB Optional SNMP Power management from SNMP manager and web browser *Derate to 80% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 100/200/208VAC * Product specifications are subject to change without further notice

 Warranty: All iBall products are governed by iBall Warranty terms. Refer www.iBall.co.in for details.

 Product specifications are subject to change without notice,  all trademarks, logos, brands & product names are properties of their respective owners,  For any technical help on iBall products, please contact [email protected] www.iBall.co.in

Other UPS Manuals