AAON CB-024 Installation Operation & Maintenance
Read Online
Read the AAON CB-024 Installation Operation & Maintenance online using the built-in PDF viewer.
Text of the manual
FOR YOUR SAFETY
Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
WARNING
If the information in this manual is not
followed exactly, a fire or explosion
may result causing property damage,
personal injury or loss of life.
WARNING
QUALIFIED INSTALLER
Improper
installation,
adjustment,
alteration, service or maintenance
can
cause
property
damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WARNING
Table of Contents
AAON® CB Series Features and Options Introduction .................................................................. 5
Safety .............................................................................................................................................. 6
CB Base Model and Features Description .................................................................................... 10
General Description ...................................................................................................................... 11
Codes and Ordinances .............................................................................................................. 11
Receiving Unit .......................................................................................................................... 11
Storage ...................................................................................................................................... 12
Direct Expansion (DX) Condensing Units ............................................................................... 12
Wiring Diagrams ....................................................................................................................... 13
General Maintenance ................................................................................................................ 13
Installation..................................................................................................................................... 14
Lifting the Unit ......................................................................................................................... 14
Locating Unit ............................................................................................................................ 14
Mounting Isolation .................................................................................................................... 15
Access Panel ............................................................................................................................. 15
Electrical ................................................................................................................................... 16
Thermostat ................................................................................................................................ 17
Refrigerant Piping ..................................................................................................................... 18
General .................................................................................................................................. 18
Determining Refrigerant Line Size ....................................................................................... 18
Liquid Line Sizing ................................................................................................................ 19
Suction Line Sizing ............................................................................................................... 20
Hot Gas Bypass Line ............................................................................................................ 22
Hot Gas Reheat ..................................................................................................................... 22
Predetermined Line Sizes ..................................................................................................... 23
Startup ........................................................................................................................................... 26
Compressors .............................................................................................................................. 26
Charging Refrigerant & Adjusting Refrigerant Charge ............................................................ 27
Before Charging .................................................................................................................... 27
Checking Liquid Sub-cooling ............................................................................................... 27
Checking Evaporator Superheat ........................................................................................... 28
Adjusting Sub-cooling and Superheat Temperatures ........................................................... 28
Air Flow .................................................................................................................................... 29
Operation....................................................................................................................................... 31
Thermostat Operation ............................................................................................................... 31
Compressor ............................................................................................................................... 31
Variable Capacity Compressor Controller ................................................................................ 31
Low Ambient Operation ........................................................................................................... 34
LAC Valve ................................................................................................................................ 35
Condenser Flooding .................................................................................................................. 36
Compressor Lockouts ............................................................................................................... 36
Maintenance .................................................................................................................................. 37
Coils .......................................................................................................................................... 37
E-Coated Coil Cleaning ............................................................................................................ 37
DX Cooling ............................................................................................................................... 39
Condenser Fan Motor ............................................................................................................... 39
Replacement Parts ..................................................................................................................... 39
Warranty, Service, and Parts Department ................................................................................. 39
Refrigerant Piping Diagrams ........................................................................................................ 40
CB Series Startup Form ................................................................................................................ 52
Literature Change History............................................................................................................. 55
Index of Tables and Figures
Tables:
Table 1 - Recommended Elevation Minimums ............................................................................ 15
Table 2 - Predetermined Line sizes for CB units with two step compressors and R-410A .......... 25
Table 3 - Acceptable Refrigeration Circuit Values ....................................................................... 28
Table 4 - Performance Testing Air Flow Setpoints ...................................................................... 29
Table 5 - R-410A Refrigerant Temperature-Pressure Chart ......................................................... 30
Table 6 - Demand Signal vs. Compressor Capacity Modulation.................................................. 32
Table 7 - Thermistor Temperature vs. Resistance Values ............................................................ 33
Table 8 - Condenser Flooding....................................................................................................... 36
Figures:
Figure 1 – Forklift Channels & Access Panel ............................................................................... 14
Figure 2 – Condensing Unit Clearances ....................................................................................... 15
Figure 3 – Utility Entry ................................................................................................................. 16
Figure 4 – Heat Pump Piping Schematic of Suction Vapor Flow Down in Double Riser ........... 21
Figure 5 – Heat Pump Piping Schematic of Discharge Vapor Flow Up in Double Riser ............ 21
Figure 6 - Riser height versus total equivalent line length ........................................................... 25
Figure 7 - Variable Capacity Compressor Controller ................................................................... 32
Figure 8 - Compressor Controller Flash Code Details.................................................................. 33
Figure 9 - Adjustable Fan Cycling Switch .................................................................................... 34
Figure 10 - Piping Schematic of Example System using the LAC Valve .................................... 35
Figure 11 - Adjustable compressor lockout .................................................................................. 36
Figure 12– A/C only piping, AHU above CU .............................................................................. 40
Figure 13 – A/C only piping, AHU below CU ............................................................................. 41
Figure 14 – Modulating hot gas reheat piping, AHU above CU .................................................. 42
Figure 15 – Modulating hot gas reheat piping, AHU below CU .................................................. 43
Figure 16 – Hot gas bypass piping, AHU above CU .................................................................... 44
Figure 17 – Hot gas bypass piping, AHU below CU .................................................................... 45
Figure 18 – Modulating hot gas reheat with hot gas bypass piping, AHU above CU .................. 46
Figure 19 – Modulating hot gas reheat with hot gas bypass piping, AHU below CU.................. 47
Figure 20 – Heat pump piping, AHU above CU .......................................................................... 48
Figure 21 – Heat pump piping, AHU below CU .......................................................................... 49
Figure 22 – Heat pump with modulating hot gas reheat piping, AHU above CU ........................ 50
Figure 23 – Heat pump with modulating hot gas reheat, AHU below CU ................................... 51
R57611 · Rev. A · 161221
(ACP J00187)
AAON® CB Series Features and Options Introduction
Energy Efficiency
Two Step or Variable Capacity Scroll
Compressor
Air-Source Heat Pump
Variable Speed Condenser Fans for Head
Pressure Control
Humidity Control
Modulating Hot Gas Reheat
Safety
Suction Pressure Transducer
Heavy Duty Wire Guards or Louvered
Panels for Condenser Coils
Automatic Low Pressure and Manual
reset High Pressure Safety Cut-outs
Suction and Liquid Line Schrader Valves
Installation and Maintenance
Easily Removable Panel Access to
Service Compartment
Run Test Report and Installation Manuals
Included in Controls Compartment
Color Coded Wiring and Wiring
Diagrams
24V Control Circuit Transformer Option
System Integration
Split System Matching
Modulating Head Pressure Control
Single Point Power
High Density Foam Compressor Sound
Suppression Blanket
Environmentally Friendly
R-410A Refrigerant
Extended Life
2,500 Hour Salt Spray Tested Exterior
Corrosion Paint
Optional 5 Year Non-Prorated
Compressor Warranty
Polymer E-Coated Condenser Coils
servicing, shut off all electrical power
to
the
unit,
including
remote
disconnects, to avoid shock hazard
or injury from rotating parts. Follow
proper Lockout-Tagout procedures.
WARNING
Safety
Attention should be paid to the following statements:
NOTE - Notes are intended to clarify the unit installation, operation and maintenance.
CAUTION - Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING - Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER - Danger statements are given to prevent actions that will result in equipment
damage, property damage, severe personal injury or death.
ELECTRIC
SHOCK,
FIRE
OR
EXPLOSION HAZARD
Failure to follow safety warnings
exactly could result in dangerous
operation, serious injury, death or
property damage.
Improper servicing could result in
dangerous operation, serious injury,
death, or property damage.
When servicing controls, label all
wires
prior
to
disconnecting.
Reconnect wires correctly.
Verify
proper
operation
after
servicing. Secure all doors with
key-lock or nut and bolt.
WARNING
QUALIFIED INSTALLER
Improper
installation,
adjustment,
alteration, service or maintenance
can
cause
property
damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
A copy of this IOM should be kept
with the unit.
WARNING
FIRE, EXPLOSION OR CARBON
MONOXIDE POISONING HAZARD
Failure to replace proper controls
could result in fire, explosion or
carbon monoxide poisoning. Failure
to follow safety warnings exactly
could result in serious injury, death or
property damage. Do not store or use
gasoline or other flammable vapors
and liquids in the vicinity of this
appliance.
WARNING
LIVE ELECTRICAL
During installation, testing, servicing,
and troubleshooting of the equipment
it may be necessary to work with live
electrical
components.
Only
a
qualified
licensed
electrician
or
individual properly trained in handling
live
electrical
components
shall
perform these tasks.
Standard
NFPA-70E,
an
OSHA
regulation requiring an Arc Flash
Boundary to be field established and
marked for identification of where
appropriate
Personal
Protective
Equipment (PPE) be worn, should be
followed.
WARNING
GROUNDING REQUIRED
All field installed wiring must be
completed by qualified personnel.
Field installed wiring must comply
with NEC/CEC, local and state
electrical code requirements. Failure
to follow code requirements could
result in serious injury or death.
Provide
proper
unit
ground
in
accordance
with
these
code
requirements.
WARNING
ROTATING COMPONENTS
Unit contains fans with moving parts
that can cause serious injury. Do not
remove grill containing fans until the
power
to
the
unit
has
been
disconnected and fan has stopped
rotating.
WARNING
3-PHASE ROTATION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
3 phase units at startup by a qualified
service
technician.
Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be
checked
using
suction
and
discharge gauges. Fan motor rotation
should
be
checked
for
proper
operation. Alterations should only be
made at the unit power connection
CAUTION
Compartments containing hazardous
voltage or rotating parts are equipped
with a panel requiring tooled access.
Always re-install screws on the panel
after
installation
or
service
is
completed.
CAUTION
UNIT HANDLING
To prevent injury or death lifting
equipment capacity shall exceed unit
weight by an adequate safety factor.
Always test-lift unit not more than 24
inches high to verify proper center of
gravity lift point to avoid unit damage,
injury or death.
WARNING
LEAK TESTING
Do not use oxygen, acetylene or air
in place of refrigerant and dry
nitrogen for leak testing. A violent
explosion may result causing injury or
death.
WARNING
COMPRESSOR LUBRICANT
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION
PVC PIPING
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable
to
attack
by
certain
chemicals. Polyolester (POE) oils
used
with
R-410A
and
other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
COIL CLEANERS
To prevent damage to the unit, do not
use acidic chemical coil cleaners. Do
not
use
alkaline
chemical
coil
cleaners with a pH value greater than
8.5, after mixing, without first using
an aluminum corrosion inhibitor in the
cleaning solution.
CAUTION
COIL CLEANERS
Some
chemical
coil
cleaning
compounds are caustic or toxic. Use
these substances only in accordance
with
the
manufacturer’s
usage
instructions.
Failure
to
follow
instructions may result in equipment
damage, injury or death.
WARNING
1. Startup and service must be performed
by
a
Factory
Trained
Service
Technician.
2. The unit is for outdoor use only. See
General Information section for more
unit information.
3. Every unit has a unique equipment
nameplate with electrical, operational
and
unit
clearance
specifications.
Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.
4. READ THE ENTIRE INSTALLATION,
OPERATION AND MAINTENANCE
MANUAL.
OTHER
IMPORTANT
SAFETY
PRECAUTIONS
ARE
PROVIDED
THROUGHOUT
THIS
MANUAL.
5. Keep this manual and all literature
safeguarded near or on the unit.
COIL CLEANING
Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.
CAUTION
ENCLOSED AREA
Do not work in an enclosed area
where refrigerant or nitrogen gases
may be leaking. A sufficient quantity
of vapors may be present and cause
injury or death.
WARNING
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
CB Series Feature String Nomenclature
Model Options
: Unit Feature Options
GEN
MJREV
UNIT
SIZE
VLT
COMP
CKTS
1
2
3
4
5
6
7
CB - B - 060 - 3 - B - 1 : B D 0 0 D A 0
10
CB Base Model and Features Description
BASE MODEL
SERIES AND GENERATION
CB
REVISION
B = Design Sequence
UNIT SIZE
024 = 24 MBH - 2 Ton - Vertical Discharge
036 = 36 MBH - 3 Ton - Vertical Discharge
048 = 48 MBH - 4 Ton - Vertical Discharge
060 = 60 MBH - 5 Ton - Vertical Discharge
VOLTAGE
1 = 230V/1Φ/60Hz
2 = 230V/3Φ/60Hz
3 = 460V/3Φ/60Hz
4 = 575V/3Φ/60Hz
8 = 208V/3Φ/60Hz
9 = 208V/1Φ/60Hz
COMPRESSOR TYPE
B = R-410A Two Step Scroll Compressor
D = R-410A Variable Capacity Scroll Compressor
F = R-410A Two Step Scroll Compressor with Sound
Blanket
H = R-410A Variable Capacity Scroll Compressor
with Sound Blanket
NUMBER OF CIRCUITS
1 = One Circuit
FEATURE 1: AMBIENT CONTROL
0 = Standard (55°F Ambient)
B = Adjustable Fan Cycling (35°F Ambient)
D = Modulating Fan Pressure Control (35°F
Ambient)
F = Flooded Condenser Ambient Controls (0°F) +
Option B
G = Flooded Condenser Ambient Controls (0°F) +
Option D
FEATURE 2: REFRIGERATION
OPTIONS
0 = Standard - Split System Air Conditioner
A = External Hot Gas Bypass
B = Split System Heat Pump
D = Modulating Hot Gas Reheat
F = Options A + D
G = Options B + D
FEATURE 3: CONTROLS
0 = Standard - Terminal Block
A = Suction Pressure Transducer (F1- Wattmaster
Reheat)
H = Control Circuit Transformer
S = Suction Pressure Transducer (Not F1 -
Wattmaster Controls)
T = Control Circuit Transformer w/ Suction Pressure
Transducer
FEATURE 4: COIL PROTECTION
0 = Standard
A = Polymer E-Coated Coil
FEATURE 5: CABINET OPTIONS
D = Standard – Louvered Panels + 2500 Hour Salt-
Spray Tested Exterior Paint
G = Wire Grille + 2500 Hour Salt-Spray Tested
Exterior Paint
FEATURE 6: WARRANTY
0 = Standard
A = Second to Fifth Year Extended Compressor
Warranty
FEATURE 7: TYPE
0 = Standard
X = Special Pricing Authorization
AAON CB Series condensing units have
been designed for outdoor installation only.
Startup and service must be performed by a
Factory Trained Service Technician.
Codes and Ordinances
CB Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236.
System should be sized in accordance with
the
American
Society
of
Heating,
Refrigeration
and
Air
Conditioning
Engineers Handbook.
Installation of CB Series units must conform
to the ICC standards of the International
Mechanical Code, the International Building
Code, and local building, plumbing and
waste water codes. All appliances must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the
current
National
Electric
Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit
When received, the unit should be checked
for damage that might have occurred in
transit. If damage is found it should be noted
on the carrier’s Freight Bill. A request for
inspection by carrier’s agent should be made
in writing at once.
Nameplate should be checked to ensure the
correct model sizes and voltages have been
received to match the job requirements.
If repairs must be made to damaged goods,
then the factory should be notified before
any repair action is taken in order to protect
the warranty. Certain equipment alteration,
repair, and manipulation of equipment
without the manufacturer’s consent may
void the product warranty. Contact AAON
Warranty Department for assistance with
handling damaged goods, repairs, and
freight claims: (903) 236-4403.
NOTE: Upon receipt check shipment for
items that ship loose. Consult order and
shipment documentation to identify potential
loose-shipped items. Loose-shipped items
The Clean Air Act of 1990 bans the
intentional venting of refrigerant as of
July 1, 1992. Approved methods of
recovery, recycling, or reclaiming
must be followed.
CAUTION
QUALIFIED INSTALLER
Improper
installation,
adjustment,
alteration, service or maintenance
can
cause
property
damage,
personal injury or loss
of life.
Installation and service must be
performed by a Factory Trained
Service Technician.
WARNING
SHARP EDGES
Coils and sheet metal surfaces
present sharp edges and care must
be
taken
when
working
with
equipment.
WARNING
Failure to observe the following
instructions will result in premature
failure of your system and possible
voiding of the warranty.
WARNING
may have been placed inside the unit cabinet
for security. Installers and owners should
secure all doors with locks or nuts and bolts
to prevent unauthorized access.
The warranty card must be completed in full
and returned to AAON not more than 3
months after the unit is delivered.
Storage
If installation will not occur immediately
following delivery, store equipment in a dry
protected area away from construction
traffic and in the proper orientation as
marked on the packaging with all internal
packaging in place. Secure all loose-shipped
items.
Direct Expansion (DX) Condensing Units
CB Series condensing units are factory
assembled and wired, including a full charge
of R-410A refrigerant for up to 25 feet of
line set. Systems with the modulating hot
gas reheat option will require refrigerant to
be field added because of the additional
refrigerant
components
and
piping
associated with the system.
Failure to observe the following instructions
may result in premature failure of your
system, and possible voiding of the
warranty.
Never cut off the main power supply to the
unit, except for servicing, emergency, or
complete shutdown of the unit. When power
is cut off from the unit, compressors using
crankcase heaters cannot prevent refrigerant
migration. This means the compressor may
cool down and liquid refrigerant may
accumulate in the compressor. Since the
compressor is designed to pump refrigerant
gas, damage may occur when power is
restored.
If power to the unit must be off for more
than an hour, turn the thermostat system
switch to “Off”, or turn the unit off at the
control panel, and then cut off the main
power supply. Leave the unit off until the
main power supply has been turned on again
for at least 24 hours. This will give the
crankcase heater time to clear any liquid
accumulation out of the compressor before it
is required to run.
Always control the system from the
thermostat, or control panel, never at the
main power supply, except for servicing,
emergency, or complete shutdown of the
unit.
The standard compressors must be on a
minimum of 5 minutes and off for a
minimum of 5 minutes. The cycle rate must
be no more than 6 starts per hour.
The variable capacity compressors must be
on a minimum of 3 minutes and off for a
minimum of 3 minutes. The cycle rate must
be no more than 10 starts per hour.
The compressor life will be seriously
shortened by reduced lubrication, and the
pumping of excessive amounts of liquid oil
and liquid refrigerant.
CRANKCASE HEATER
OPERATION
Units are equipped with compressor
crankcase heaters, which should be
energized at least 24 hours prior to
cooling operation, to clear any liquid
refrigerant from the compressors.
CAUTION
Note: Low Ambient Operation
Units without a low ambient option, such as
condenser fan cycling or the 0°F low
ambient option, will not operate in the
cooling mode of operation properly when
the outdoor temperature is below 55°F. Low
ambient and/or air handling unit economizer
options
are
recommended
if
cooling
operation below 55°F is expected.
Note: Multiple Systems with Multiple
Thermostats
When several heating and cooling split
systems are used to condition a space all
thermostat switches must be set in either
heating mode, cooling mode or off. Do not
leave part of the systems switched to the
opposite mode. Cooling only systems should
be switched off at the thermostat during the
heating season.
Wiring Diagrams
Unit specific wiring diagram is laminated in
plastic and located inside the controls
compartment door.
General Maintenance
When the initial startup is made, and on a
periodic schedule during operation, it is
necessary to perform routine service checks
on the performance of the condensing unit.
This includes reading and recording suction
pressures and checking for normal sub-
cooling and superheat.
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
AAON equipment has been designed for
quick and easy installation.
Lifting the Unit
CB Series condensing units have channels
underneath the base which provide lifting
access to the underside of the equipment and
allow moving and placement without
physical damage.
Figure 1 – Forklift Channels & Access Panel
Dollies and/or carts are recommended to lift
and place the unit to prevent damage to the
equipment and injury to the installer.
Care should be taken if using spreader bars,
blocking, or other lifting devices to prevent
any damage to the cabinet, coil or
condensing fans.
Before lifting unit, be sure that all shipping
material has been removed from unit.
Hoist unit to a point directly above the
condenser pad, and lower unit into the
proper place. Unit may also be positioned
with a dolly. When the unit is in place,
remove the dolly or lifting device. Make
sure the unit is properly seated and level.
Locating Unit
CB Series condensing units are designed for
outdoor application and placement at ground
level or on a rooftop. Units must be placed
on a level and solid foundation that can
support the unit’s weight.
When rooftop mounted, a steel frame must
be provided that will support the unit above
the roof itself for load distribution.
When installed at ground level, a one-piece
concrete slab or composite condenser pad
should be used with footings that extend
below the frost line (a substantial base that
will not settle). Slab should be surrounded
by a graveled area for proper drainage and
should not adjoin the building as sound and
vibration may be transmitted to the
structure. Care must also be taken to protect
the coils and fins from damage due to
vandalism or other hazards.
Airflow to and from the condensing unit
must not be restricted. Coils and fans must
be free of any obstructions and debris in
order to start and operate properly with a
correct amount of airflow. Obstruction to air
flow will result in decreased performance
and efficiency.
The installation position must provide at
least one foot of clearance from the wall for
proper air flow to the coils. When multiple
units are mounted adjacent to each other, the
clearance required between them is three
feet.
Service compartment must be accessible for
periodic
servicing
of
controls,
safety
devices, and refrigerant service/shutoff
valves. At least two feet of clearance on this
Incorrect lifting can cause damage to
the unit.
CAUTION
corner of the unit is recommended for
service.
Figure 2 – Condensing Unit Clearances
Condensing units should not be installed in
an enclosure or pit that is deeper than the
height
of
the
unit.
When
recessed
installation is necessary, the clearance to
maintain proper airflow is at least three feet.
CB Series condensing units are single
circuited with vertical air discharge. There
must be no obstruction above the equipment.
Do not place the unit under an overhang.
Placement relative to the building air intakes
and other structures must be carefully
selected. Consider the effects of outdoor fan
noise on conditioned space and any adjacent
occupied space. It is recommended that the
unit be placed so that discharge does not
blow toward windows less than 25 feet
away.
Heat
pumps
require
special
location
consideration
in
areas
where
snow
accumulation can become an obstruction
and in areas with prolonged continuous
subfreezing temperatures. Heat pump unit
bases are cutout under the outdoor coil to
permit drainage of frost accumulation. The
unit must be situated to permit free
unobstructed drainage of the defrost water
and ice. A minimum 3 inches clearance
under the outdoor coil is required in the
milder climates. In more severe weather
locations, it is recommended that the unit be
elevated to allow unobstructed drainage and
airflow.
Table 1 - Recommended Elevation
Minimums
Design
Temperature
Suggest Minimum
Elevation
+15 F and above
3”
-5 F to +17 F
8”
Below -5 F
12”
Mounting Isolation
For roof mounted applications or anytime
vibration transmission is a factor, vibration
isolators may be used.
Access Panel
Access panel is provided to electrical
compartment. To remove the panel,
unscrew the four screws
PVC PIPING
PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable
to
attack
by
certain
chemicals. Polyolester (POE) oils
used
with
R-410A
and
other
refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.
CAUTION
Verify the unit nameplate agrees with the
power supply. Connect power and control
field wiring as shown on the unit wiring
diagram provided with the unit.
Route power and control wiring, separately,
through the utility entry right above the
service valves. Do not run power and signal
wires in the same conduit.
Figure 3 – Utility Entry
Size supply conductors based on the unit
MCA rating. Supply conductors must be
rated a minimum of 75°C.
Protect the branch circuit in accordance with
code requirements. The unit must be
electrically grounded in accordance with
local codes, or in the absence of local codes,
the
current
National
Electric
Code,
ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Note: Units are factory wired for 208V,
230V, 460V or 575V. In some units, the
208V and 230V options may also be
provided
in
single
or
three
phase
configurations.
The
transformer
configuration must be checked by a
qualified technician prior to startup.
Wire power leads to the unit terminal block.
All wiring beyond this point has been done
by the manufacturer and cannot be modified
without affecting the unit's agency/safety
certification.
All units require field supplied electrical
overcurrent and short circuit protection.
Device must not be sized larger than the
Maximum Overcurrent Protection (MOP)
shown on the unit nameplate.
Codes may require a disconnect switch be
within sight of the unit.
3-PHASE ROTATION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. Condenser fan
motors should be checked by a
qualified service technician at startup
and any wiring alteration should only
be
made
at
the
unit
power
connection.
CAUTION
ELECTRIC SHOCK
Electric
shock
hazard.
Before
attempting to perform any installation,
service, or maintenance, shut off all
electrical power to the unit at the
disconnect switches. Unit may have
multiple power supplies. Failure to
disconnect power could result in
dangerous operation, serious injury,
death or property damage.
WARNING
It is recommended that the field installed
overcurrent protection or disconnect switch
not be installed on the unit.
Supply voltage must be within the min/max
range shown on the unit nameplate.
Available short circuit current should not
exceed the short circuit current rating
(SCCR) shown on the unit nameplate.
Three phase voltage imbalance will cause
motor overheating and premature failure.
The maximum allowable imbalance is 2.0%.
Voltage imbalance is defined as 100 times
the maximum deviation from the average
voltage divided by the average voltage.
Example:
(221V+230V+227V)/3
=
226V,
then
100*(226V-221V)/226V = 2.2%, which
exceeds the allowable imbalance.
Check voltage imbalance at the unit
disconnect switch and at the compressor
terminal. Contact your local power company
for line voltage corrections.
Installing contractor must check for proper
motor rotation and check blower motor
amperage listed on the motor nameplate is
not exceeded.
Wire control signals to the unit’s low
voltage terminal block located in the
controls compartment.
If any factory installed wiring must be
replaced, use a minimum 105°C type AWM
insulated conductors.
Thermostat
If a thermostat is used for unit control,
thermostat should be located on an inside
wall 4-5 feet above the floor where it will
not be subjected to drafts, sun exposure, or
heat from electrical fixtures or appliances.
Follow
thermostat
manufacturer’s
instructions
for
general
installation
procedure.
Thermostat control wiring size must be large
enough to prevent excess voltage drop and
ensure proper operation.
All external devices must be powered via a
separate external power supply.
Units with the modulating hot gas reheat
dehumidification
feature
must
use
a
humidistat or a thermostat with a normally
closed (NC) dehumidification option. The
following thermostats have been approved
for usage with the dehumidification feature,
Robertshaw® 9825i2 Thermostat
Honeywell VisionPRO® IAQ Thermostat
AAON Mini Controller
Three phase voltage imbalance will
cause
motor
overheating
and
premature failure.
CAUTION
(See back of the manual for refrigerant
piping diagrams.)
General
Piping from the condensing unit to the air
handler is the responsibility of the installing
contractor.
Use only clean type “ACR” copper tubing
that has been joined with high temperature
brazing alloy.
The pipe or line sizes must be selected to
meet the actual installation conditions and
not simply based on the connection sizes at
the condensing unit or air handler.
All CB Series condensing units are provided
with in-line shutoff valves on both the liquid
and suction lines. These should remain
closed until the system is ready for start-up
after installation.
Piping should conform to generally accepted
practices and codes.
Upon completion of piping connection, the
interconnecting piping and air handler
MUST BE evacuated to 500 microns or less;
leak checked and charged with refrigerant.
Determining Refrigerant Line Size
The piping between the condenser and low
side must ensure:
1. Minimum pressure drop, and
2. Continuous oil return, and
3. Prevention of liquid refrigerant slugging,
or carryover
Minimizing the refrigerant line size is
favorable from an economic perspective,
reducing installation costs, and reducing the
potential for leakage. However, as pipe
diameters
narrow,
pressure-reducing
frictional forces increase.
Excessive suction line pressure drop causes
loss of compressor capacity and increased
power usage resulting in reduced system
efficiency. Excessive pressure drops in the
liquid line can cause the liquid refrigerant to
flash, resulting in faulty Thermal Expansion
Valve (TXV) operation and improper
system performance. In order to operate
efficiently and cost effectively, while
avoiding malfunction, refrigeration systems
must be designed to minimize both cost and
pressure loss.
REFRIGERANT PIPING
This section is for information only
and is not intended to provide all
details required by the designer or
installer of the refrigerant piping
between
the
condenser
or
condensing unit and the air handling
unit. AAON, Inc. is not responsible for
interconnecting
refrigerant
piping.
Consult
ASHRAE
Handbook
–
Refrigeration and ASME Standards.
CAUTION
REFRIGERANT PIPING
Line sizes must be selected to meet
actual installation conditions, not
simply based on the connection sizes
at the condensing unit or air handling
unit.
CAUTION
Equivalent Line Length
All line lengths discussed in this manual,
unless specifically stated otherwise, are
Equivalent Line Lengths. The frictional
pressure drop through valves, fittings, and
accessories is determined by establishing the
equivalent length of straight pipe of the
same diameter. Always use equivalent line
lengths when calculating pressure drop.
Special piping provisions must be taken
when lines are run underground, up vertical
risers, or in excessively long line runs.
Liquid Line Sizing
When sizing the liquid line, it is important to
minimize the refrigerant charge to reduce
installation costs and improve system
reliability. This can be achieved by
minimizing
the
liquid
line
diameter.
However, reducing the pipe diameter will
increase the velocity of the liquid refrigerant
which increases the frictional pressure drop
in the liquid line, and causes other
undesirable effects such as noise.
Maintaining the pressure in the liquid line is
critical to ensuring sufficient saturation
temperature, avoiding flashing upstream of
the
TXV,
and
maintaining
system
efficiency. Pressure losses through the
liquid line due to frictional contact, installed
accessories,
and
vertical
risers
are
inevitable.
Maintaining
adequate
sub-
cooling at the condenser to overcome these
losses is the only method to ensure that
liquid refrigerant reaches the TXV.
Liquid refrigerant traveling upwards in a
riser loses head pressure. If the evaporator is
below the condenser, and the liquid line
does not include risers, the gravitational
force will increase the pressure of the liquid
refrigerant. This will allow the refrigerant to
withstand greater frictional losses without
the occurrence of flashing prior to the TXV.
A moisture-indicating sight glass may be
field installed in the liquid line to indicate
the occurrence of premature flashing or
moisture in the line. The sight glass should
not be used to determine if the system is
properly charged. Use temperature and
pressure measurements to determine
liquid sub-cooling, not the sight glass.
Liquid Line Routing
Care should be taken with vertical risers.
When the system is shut down, gravity will
pull liquid down the vertical column, and
back to the condenser when it is below the
evaporator. This could potentially result in
compressor flooding. A check valve can be
installed in the liquid line where the liquid
column rises above the condenser to prevent
this. The liquid line is typically pitched
along with the suction line, or hot gas line,
to
minimize
the
complexity
of
the
configuration.
Liquid Line Insulation
When the liquid line is routed through
regions
where
temperature
losses
are
expected, no insulation is required, as this
may provide additional sub-cooling to the
refrigerant. When routing the liquid line
through high temperature areas, insulation of
the line is appropriate to avoid loss of sub-
cooling through heat gain.
Liquid Line Guidelines
In order to ensure liquid at the TXV, the
sum of frictional losses and pressure loss
due to vertical rise must not exceed
available sub-cooling. A commonly used
guideline to consider is a system design with
pressure losses due to friction through the
line not to exceed a corresponding 1-2°F
change in saturation temperature. An
additional recommendation is that the sum
of frictional losses and pressure loss due to
vertical rise should not exceed 5°F.
If the velocity of refrigerant in the liquid line
is too great, it could cause excessive noise or
piping
erosion.
The
recommended
maximum velocities for liquid lines are 100
fpm from the condenser to a receiver tank to
discourage fluid backup, and 300 fpm from
receiver tank to the evaporator to minimize
valve induced liquid hammer.
Liquid Line Accessories
Liquid line shut off valves and filter driers
are factory provided. Filter driers must be
field installed. The total length equivalent of
pressure losses through valves, elbows and
fittings must be considered when adding
additional components in the field. It is a
good practice to utilize the fewest elbows
that will allow the mating units to be
successfully joined.
A solenoid valve is recommended on lines
over 100ft in length to prevent liquid
migration when the compressors are off.
The solenoid needs to be wired so that it is
open when the compressors turn on, and
closed when the compressors turn off.
Suction Line Sizing
The suction line is more critical than the
liquid line from a design and construction
standpoint. More care must be taken to
ensure that adequate velocity is achieved to
return oil to the compressor at minimum
loading conditions. However, reducing the
piping diameter to increase the velocity at
minimal load can result in excessive
pressure losses, capacity reduction, and
noise at full load.
Suction Line Routing
Pitch the suction line in the direction of flow
(about 1 foot per 120 feet of length) to
maintain oil flow towards the compressor,
and keep it from flooding back into the
evaporator. Crankcase heaters are provided
to keep any condensed refrigerant that
collects in the compressor from causing
damage or wear. Make sure to provide
support to maintain suction line positioning,
and
insulate
completely
between
the
evaporator and condensing unit.
It is important to consider part load
operation when sizing suction lines. At
minimum capacity, refrigerant velocity may
not be adequate to return oil up the vertical
riser. Decreasing the diameter of the vertical
riser will increase the velocity, but also the
frictional loss.
For difficult line routing applications, a
double suction riser can be applied to the
situation of part load operation with a
suction riser. A double suction riser is
designed to return oil at minimum load
while not incurring excessive frictional
losses at full load. A double suction riser
consists of a small diameter riser in parallel
with a larger diameter riser, and a trap at the
base of the large riser. At minimum
capacity, refrigerant velocity is not sufficient
to carry oil up both risers, and it collects in
the trap, effectively closing off the larger
diameter riser, and diverting refrigerant up
the small riser where velocity of the
refrigerant is sufficient to maintain oil flow.
At full load, the mass flow clears the trap of
oil, and refrigerant is carried through both
risers. The smaller diameter pipe should be
sized to return oil at minimum load, while
the larger diameter pipe should be sized so
that flow through both pipes provides
acceptable pressure drop at full load.
SUCTION LINE SIZING
Suction line must be sized in
accordance to the minimum capacity
of the variable speed compressor.
CAUTION
A double riser used for heat pump operation
works differently than that described above.
The specific volume (ft3/lb) of refrigerant at
the discharge temperature (heating mode
line conditions) is significantly lower than
the
specific
volume
at
the
suction
temperature (cooling mode line conditions).
To compound the issue, the capacity in
heating mode is lower than the capacity in
cooling mode. The discharge velocity in the
riser during heating mode is much lower
than the suction velocity during cooling
mode. Often, a double riser is necessary to
get acceptable velocities for the discharge
mode and acceptable velocities for the
suction mode. A solenoid valve must be
added to the second riser. The solenoid
valve must be wired to the reversing valve
so that the solenoid valve opens in cooling
mode, and closes in heating mode. See the
diagrams below:
Figure 4 – Heat Pump Piping Schematic of
Suction Vapor Flow Down in Double Riser
Figure 5 – Heat Pump Piping Schematic of
Discharge Vapor Flow Up in Double Riser
Suction Line Insulation
The entire suction line should be insulated
with a minimum 1 inch thick Armaflex
insulation. This prevents condensation from
forming on the line, and reduces any
potential loss in capacity associated with
heat gain placing additional load on the
system.
Suction Line Guidelines
For
proper
performance,
suction
line
velocities less than a 4,000 fpm maximum
are recommended. The minimum velocity
required to return oil is dependent on the
pipe diameter, however, a general guideline
of 1,000 fpm minimum may be applied.
When suction flow is up, variable capacity
compressors require a minimum velocity of
2,000 fpm.
Heat pump vapor lines must be checked for
suction flow (cooling mode operation) and
discharge flow (heating mode operation).
The same line must be used for both modes
of operation.
In a fashion similar to the liquid line, a
common guideline to consider is a system
design with pressure losses due to friction
through
the
line
not
to
exceed
a
corresponding 1-2°F change in saturation
temperature.
At points where small pipe size can be used
to provide sufficient velocity to return oil in
vertical risers at part loads, greater pressure
losses are incurred at full loads. This can be
compensated for by over sizing the
horizontal runs and vertical drop sections.
This
will
however
require
additional
refrigerant charge.
Circuits
with
variable
capacity
scroll
compressors require suction riser traps every
10 feet.
Suction Line Accessories
If the job requirements specify suction
accumulators, they must be separately
purchased and field installed.
Hot Gas Bypass Line
Hot Gas Bypass (HGB) is available for use
with DX systems that may experience low
suction pressure during the operating cycle.
This may be due to varying load conditions
associated with VAV applications or units
supplying a large percentage of outside air.
The system is designed to divert refrigerant
from the compressor discharge to the low
pressure side of the system in order to keep
the evaporator from freezing and to maintain
adequate refrigerant velocity for oil return at
minimum load.
Hot discharge gas is redirected to the
evaporator inlet via an auxiliary side
connector (ASC) to false load the evaporator
when reduced suction pressure is sensed.
Field piping between the condensing unit
and the evaporator is required.
Hot Gas Bypass Piping Considerations for
Evaporator above Condensing Unit
Pitch the hot gas bypass line downward in
the direction of refrigerant flow, toward the
evaporator.
When installing hot gas bypass risers, an oil
drip line must be provided at the lowest
point in the system. The oil drip line must be
vertical, its diameter should be the same as
the diameter of the riser, and it should be 1
foot long. Install a sight glass in the oil drip
line for observation. Run an oil return line,
using 1/8 inch capillary tube, 10 feet in
length, from the oil drip line to the suction
line. Connect the oil return line below the
sight glass and 1 inch above the bottom of
the oil drip line.
HGB valves are adjustable. Factory HGB
valve settings will be sufficient for most
applications,
but
may
require
slight
adjustments for some applications, including
some make up air applications.
Insulate the entire length of the HGB line
with a minimum 1 inch thick Armaflex
insulation.
Hot Gas Bypass Piping Considerations for
Evaporator Below Condensing Unit
The line must slope downward from the
HGB valve toward the evaporator.
Hot Gas Bypass Line Guidelines
Choose a small size line to ensure oil return,
and minimize refrigerant charge.
Maintain velocities below a maximum of
4,000 fpm. A general minimum velocity
guideline to use is approximately 900 fpm.
Hot Gas Reheat
The AAON modulating hot gas reheat
system diverts hot discharge gas from the
condenser to the air handling unit through
the hot gas line. Field piping between the
condensing unit and the air handler is
required.
The line delivers the hot discharge gas to the
reheat coil and/or the hot gas bypass valve,
so it is sized as a discharge line.
Discharge lines should be sized to ensure
adequate velocity of refrigerant to ensure oil
return, avoid excessive noise associated with
velocities that are too high, and to minimize
efficiency losses associated with friction.
Pitch the hot gas line in the direction of flow
for oil return.
When installing hot gas reheat risers, an oil
drip line must be provided at the lowest
point in the system. The oil drip line must be
vertical, its diameter should be the same as
the diameter of the riser, and it should be 1
foot long. Run a drip line, using 1/8 inch
capillary tube, 10 feet in length, from the oil
drip line to the suction line. Connect the oil
return line below the sight glass and 1 inch
above the bottom of the oil drip line.
Insulate the entire length of the hot gas line
with a minimum 1 inch thick Armaflex
insulation.
Hot Gas Reheat Guidelines
Maintain velocities below a maximum of
4,000 fpm. A general minimum velocity
guideline is 900 fpm.
Predetermined Line Sizes
To aid in line sizing and selection, AAON
has predetermined line sizes for the liquid,
suction, and hot gas lines in comfort cooling
applications.
In order to generate this information, the
following cycle assumptions are made:
Saturated suction temperature = 50°F,
Saturated condensing temperature = 125°F,
Sub-cooling = 10°F, Superheat = 15°F.
The liquid lines have been chosen to
maintain velocities between 100 and 350
fpm. The suction line diameters are selected
to limit velocities to a 4,000 fpm maximum,
while a minimum velocity restriction is
imposed by the ability to entrain oil up
vertical suction risers (ASHRAE Handbook
- Refrigeration).
Acceptable pressure loss criteria are applied
to each of the lines: The total equivalent
length of the liquid line available is
determined such that 3°F of liquid sub-
cooling remain at the TXV. This includes
the pressure losses in horizontal and vertical
sections, accessories, elbows, etc.
Recall that the available sub-cooling for the
cycle is assumed as 10°F. To maintain at
least 3°F sub-cooling as a factor of safety to
avoid flashing at the TXV, we consider a
maximum pressure loss equivalent to a 7°F
change in saturation temperature. Pressure
losses in the suction line are not to exceed
2°F.
When to Use Predetermined Line Sizing
The line sizes presented are not the only
acceptable pipe diameters, they are however
appropriate for general comfort cooling
applications, and satisfy common job
requirements.
Examine
the
conditions,
assumptions, and constraints used in the
generation
of
the
predetermined
pipe
diameters to ensure that this method is
applicable to a particular case. Do not
assume that these line sizes are appropriate
for
every
case.
Consult
ASHRAE
Handbook – Refrigeration for generally
accepted system piping practices.
How to Use Predetermined Line Sizing
First, read the previous section, When to Use
Predetermined Line Sizing, to decide if this
method is applicable. Next, consult Table 2
below for pipe diameters.
Examine Figure 6 below to determine the
acceptable line dimensions associated with
the pipe diameters determined in Table 2
below. The figure is shown as total available
riser height versus total equivalent line
length for the liquid line. The curve
identifies a region of acceptable piping
configuration when the predetermined line
sizes are selected for any model in the table.
A piping configuration above the curve falls
outside the assumptions used to determine
the line size and will result in a loss of sub-
cooling, and additional pressure losses in the
suction and hot gas lines.
The total equivalent line length definition
includes the height of vertical rise, pressure
drop through elbows and accessories, and
horizontal
line
length,
so
elbows,
accessories, and vertical rise must be
considered when determining horizontal
length available from the total equivalent
line length.
The figure below is presented in terms of the
liquid line, but it assumes that the suction
line length is similar, as these lines are
commonly routed together to minimize the
space and cost required for split system
installation.
Before using this table read the
When to Use Predetermined Line
Sizes section. Do not assume that
these line sizes are appropriate for
every
case.
Consult
ASHRAE
Handbook
–
Refrigeration
for
generally accepted system piping
practices. The AAON Refrigerant
Piping Calculator in Ecat32 can be
used for job specific line sizing.
CAUTION
Table 2 - Predetermined Line sizes for CB units with two step compressors and R-410A
Model
Connection Sizes
Predetermined Line Size
Liquid
Suction
Hot Gas
Liquid
Suction
HGBP*
HGRH**
CB-024
3/8”
3/4”
3/8”
3/8”
3/4”
3/8”
3/8”
CB-036
3/8”
3/4”
3/8”
3/8”
3/4”
3/8”
1/2”
CB-048
3/8”
7/8”
1/2”
1/2”
7/8”
1/2”
1/2”
CB-060
3/8”
7/8”
1/2”
1/2”
7/8”
1/2”
1/2”
* Hot Gas Bypass line
** Hot Gas Reheat line
Figure 6 - Riser height versus total equivalent line length
Note: Figure 6 is for R-410A split system applications with two step compressor CB-024
through CB-060 units. The region of acceptable riser height is the lighter area. Select the
corresponding predetermined line size from Table 2 above.
Total Equivalent Line Length in this
figure is limited to 160 equivalent
feet.
CAUTION
(See back of the manual for startup form.)
Before
startup
of
the
condenser
or
condensing unit, make sure that the
following items have been checked.
1. Verify that electrical power is available
to the unit.
2. Verify that any remote stop/start device
connected to the unit controller is
requesting the unit to start.
Confirm the compressor is operating within
tolerance.
While performing the check, use the startup
form to record observations of amps and
refrigerant pressures.
When all is running properly, place the
controller in the Run mode and observe the
system until it reaches a steady state of
operation.
Compressors
All
compressors
are
equipped
with
crankcase
heaters,
which
should
be
energized at least 24 hours prior to cooling
operation of the compressor.
3-PHASE ROTATION
Rotation must be checked on all
MOTORS AND COMPRESSORS of
three phase units. Condenser fan
motors should all be checked by a
qualified service technician at startup
and any wiring alteration should only
be
made
at
the
unit
power
connection.
CAUTION
COMPRESSOR ROTATION
Scroll compressors are directional
and will be damaged by operation in
the wrong direction. Low pressure
switches on compressors have been
disconnected after factory testing.
Rotation should be checked by a
qualified service technician at startup
using suction and discharge pressure
gauges and any wiring alteration
should only be made at the unit
power connection.
CAUTION
ELECTRIC SHOCK
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
QUALIFIED INSTALLER
Improper
installation,
adjustment,
alteration, service or maintenance
can
cause
property
damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
WARNING
Charging Refrigerant & Adjusting
Refrigerant Charge
The unit comes with full charge based on a
25 foot line set. Charging a system in the
field must be based on determination of
liquid sub-cooling and evaporator superheat.
On a system with a TXV, liquid sub-cooling
is more representative of the charge than
evaporator superheat but both measurements
must be taken.
Before Charging
Refer to the Unit Nameplate to determine
which refrigerant must be used to charge the
system.
Unit being charged must be at or near full
load conditions before adjusting the charge.
Units equipped with hot gas bypass must
have the hot gas bypass valve closed to get
the proper charge.
Units equipped with hot gas reheat must be
charged with the hot gas valves closed while
the unit is in cooling mode. After charging,
unit
should
be
operated
in
reheat
(dehumidification) mode to check for
correct operation.
Units equipped with heat pump options
should be charged in heating mode to get the
proper charge. After charging, unit should
be operated in cooling mode to check for
correct charge. Charge may need to be
adjusted for cooling mode. If adjustments
are made in the cooling mode, heating mode
must be rerun to verify proper operation.
After adding or removing charge the system
must be allowed to stabilize, typically 10-15
minutes,
before
making
any
other
adjustments.
The type of unit and options determine the
ranges for liquid sub-cooling and evaporator
superheat. Refer to the table of acceptable
refrigerant circuit values when determining
the proper sub-cooling.
Checking Liquid Sub-cooling
Measure the temperature of the liquid line as
it leaves the condenser coil.
Read the gauge pressure reading of the
liquid line close to the point where the
temperature was taken. You must use liquid
line pressure as it will vary from discharge
pressure due to condenser coil pressure
drop.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart or Table 5 below.
CLEAN AIR ACT
The Clean Air Act of 1990 bans the
intentional
venting
of
refrigerant
(CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery,
recycling or reclaiming must be
followed. Fines and/or incarceration
may be levied for non-compliance.
CAUTION
COMPRESSOR LUBRICANT
Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.
CAUTION
temperature from the saturated temperature
to determine the liquid sub-cooling.
Compare calculated sub-cooling to Table 3
below for the appropriate unit type and
options.
Checking Evaporator Superheat
Measure the temperature of the suction line
close to the compressor.
Read gauge pressure at the suction line close
to the compressor.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.
Subtract the saturated temperature from the
measured
suction
line
temperature
to
determine the evaporator superheat.
Compare calculated superheat to Table 3
below for the appropriate unit type and
options.
Table 3 - Acceptable Refrigeration Circuit
Values
Air-Cooled Cond./Air-Source Heat Pump
Sub-Cooling**
12-18°F / 2-4°F (HP)*
Sub-Cooling with
Hot Gas Reheat**
15-22°F / 2-6°F (HP)*
Superheat***
8-15°F
*In cooling mode operation
**Sub-cooling must be increased by 2°F per
20 feet of vertical liquid line rise for R-410A
***Superheat will increase with long
suction line runs.
Adjusting Sub-cooling and Superheat
Temperatures
The system is overcharged if the sub-cooling
temperature is too high and the evaporator is
fully loaded (low loads on the evaporator
result in increased sub-cooling) and the
evaporator
superheat
is
within
the
temperature range as shown in Table 3 (high
superheat results in increased sub-cooling)
Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.
The system is undercharged if the superheat
is too high and the sub-cooling is too low
Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.
If the sub-cooling is correct and the
superheat is too high, the TXV may need
adjustment to correct the superheat.
Special Low Ambient Option Charging
Instructions
For units equipped with low ambient control
(LAC) refrigerant flood back option being
charged when the ambient temperature is
warm:
Once enough charge has been added to get
the evaporator superheat and sub-cooling
values to the correct setting, more charge
must be added. Add approximately 80% of
the receiver tank volume to the charge to
help fill the receiver tank. The additional
charge is required for the system when
running in cold ambient conditions.
DO NOT OVERCHARGE!
Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.
CAUTION
For units equipped with low ambient
refrigerant flood back option being charged
when the ambient temperature is cold:
Once enough charge has been added to get
the evaporator superheat and sub-cooling
values to the correct setting, more charge
may need to be added. If the ambient
temperature is 0°F no more charge is
required. If the ambient temperature is
around 40°F add approximately 40% of the
receiver tank volume.
The unit will have to be checked for proper
operation once the ambient temperature is
above 80°F.
Air Flow
Table 4 - Performance Testing Air Flow Setpoints
Model
Cooling Stage 2
(cfm)
Cooling Stage 1
(cfm)
Heating Stage 2
(cfm)
Heating Stage 1
(cfm)
CB-B-024-*-*-1
885
663.75
885
796.5
CB-B-036-*-*-1
1250
937.5
1250
1125
CB-B-048-*-*-1
1500
1125
1500
1350
CB-B-060-*-*-1
1545
1158.75
1545
1390.5
Before
completing
startup
and
leaving the unit a complete operating
cycle should be observed to verify
that all components are functioning
properly.
CAUTION
Table 5 - R-410A Refrigerant Temperature-Pressure Chart
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
°F
PSIG
20
78.3
47
134.7
74
213.7
101
321.0
128
463.2
21
80.0
48
137.2
75
217.1
102
325.6
129
469.3
22
81.8
49
139.7
76
220.6
103
330.2
130
475.4
23
83.6
50
142.2
77
224.1
104
334.9
131
481.6
24
85.4
51
144.8
78
227.7
105
339.6
132
487.8
25
87.2
52
147.4
79
231.3
106
344.4
133
494.1
26
89.1
53
150.1
80
234.9
107
349.3
134
500.5
27
91.0
54
152.8
81
238.6
108
354.2
135
506.9
28
92.9
55
155.5
82
242.3
109
359.1
136
513.4
29
94.9
56
158.2
83
246.0
110
364.1
137
520.0
30
96.8
57
161.0
84
249.8
111
369.1
138
526.6
31
98.8
58
163.8
85
253.7
112
374.2
139
533.3
32
100.9
59
166.7
86
257.5
113
379.4
140
540.1
33
102.9
60
169.6
87
261.4
114
384.6
141
547.0
34
105.0
61
172.5
88
265.4
115
389.9
142
553.9
35
107.1
62
175.4
89
269.4
116
395.2
143
560.9
36
109.2
63
178.4
90
273.5
117
400.5
144
567.9
37
111.4
64
181.5
91
277.6
118
405.9
145
575.1
38
113.6
65
184.5
92
281.7
119
411.4
146
582.3
39
115.8
66
187.6
93
285.9
120
416.9
147
589.6
40
118.1
67
190.7
94
290.1
121
422.5
148
596.9
41
120.3
68
193.9
95
294.4
122
428.2
149
604.4
42
122.7
69
197.1
96
298.7
123
433.9
150
611.9
43
125.0
70
200.4
97
303.0
124
439.6
44
127.4
71
203.6
98
307.5
125
445.4
45
129.8
72
207.0
99
311.9
126
451.3
46
132.2
73
210.3
100
316.4
127
457.3
Unit operations should be controlled with
thermostat, or unit controller, never at the
main power supply, except for emergency,
servicing, or complete shutdown of the unit.
Thermostat Operation
Heating
Thermostat system switch - "Heat"
Thermostat fan switch - "Auto" or "On"
Thermostat temperature set to desired point.
Cooling
Thermostat system switch - "Cool"
Thermostat fan switch - "Auto" or "On"
Thermostat temperature set to desired point.
Air Circulation
Thermostat system switch - "Off"
Thermostat fan switch - "Auto" or "On"
No change of the thermostat temperature.
With these settings, the air handler’s supply
fan will run continuously but the supply air
will not be heated, cooled, or dehumidified.
System Off
Thermostat system switch - "Off"
Thermostat fan switch - "Auto"
No change of the thermostat temperature.
With these settings, the system is shut down,
with the exception of the control system
power (24 VAC), and the crankcase heaters
(about 60 watts/compressor).
Night and Weekend Unoccupied Operation
To reduce the operating time of the unit
when the space is unoccupied, such as nights
and weekends, it is recommended that the
temperature setting be raised about 5°F
while unoccupied during the cooling season
and lowered about 10°F during the heating
season.
Compressor
The compressors must be off for a minimum
of 5 minutes and on for a minimum of 5
minutes. Short cycling of the compressors
can causes undue stress and wear.
Variable Capacity Compressor
Controller
Units with variable capacity scroll
compressors may include variable capacity
compressor controller. The following is an
explanation of the terminals and
troubleshooting of the alert flash codes on
the controller. For more information on the
compressor controller, see Emerson Climate
Bulletin AE8-1328.
COMPRESSOR CYCLING
5 MINUTE MINIMUM OFF TIME
To
prevent
motor
overheating
compressors must cycle off for a
minimum of 5 minutes.
5 MINUTE MINIMUM ON TIME
To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.
The cycle rate must not exceed 6
starts per hour.
WARNING
Figure 7 - Variable Capacity Compressor
Controller
Low Voltage Terminals
24COM
Module Common
24VAC
Module Power
C1 & C2
Demand Input
P1
Pressure Common
P2
Pressure Input
P3
Pressure Power 5VDC
P4
Pressure Shield
P5 & P6
Pressure Output
T1 & T2
Discharge Temperature Sensor
High Voltage Terminals
A1 & A2
Alarm Relay Out
M1 & M2
Contactor
L1
Control Voltage N
L2
Control Voltage L
U1 & U2
Digital Unloader Solenoid
V1 & V2
Vapor Injection Solenoid
The compressor controller modulates the
compressor unloader solenoid in an on/off
pattern according the capacity demand
signal of the system. The following table
shows the linear relationship between the
demand signal and compressor capacity
modulation. The compressor controller also
protects
the
compressor
against
high
discharge temperature. Refer to Table 7 for
the
relationship
between
thermistor
temperature readings and resistance values.
Table 6 - Demand Signal vs. Compressor Capacity Modulation
Demand
Signal (VDC)
Loaded %
Unloaded %
Time Loaded
Time
Unloaded
% Compressor
Capacity
1.00
Off
Off
Off
Off
0%
1.44
10%
90%
1.5 sec
13.5 sec
10%
3.00
50%
50%
7.5 sec
7.5 sec
50%
4.20
80%
20%
12 sec
3 sec
80%
5.00
100%
0%
15 sec
0 sec
100%
To avoid damaging the compressor
controller, DO NOT connect wires to
terminals C3, C4, T3, T4, T5, or T6.
WARNING
Figure 8 - Compressor Controller Flash Code Details
Table 7 - Thermistor Temperature vs. Resistance Values
°C
°F
kΩ
°C
°F
kΩ
-40
-40
2889.60
75
167
12.73
-35
-31
2087.22
80
176
10.79
-30
-22
1522.20
85
185
9.20
-25
-13
1121.44
90
194
7.87
-20
-4
834.72
95
203
6.77
-15
5
627.28
100
212
5.85
-10
14
475.74
105
221
5.09
-5
23
363.99
110
230
4.45
0
32
280.82
115
239
3.87
5
41
218.41
120
248
3.35
10
50
171.17
125
257
2.92
15
59
135.14
130
266
2.58
20
68
107.44
135
275
2.28
25
77
86.00
140
284
2.02
30
86
69.28
145
293
1.80
35
95
56.16
150
302
1.59
40
104
45.81
155
311
1.39
45
113
37.58
160
320
1.25
50
122
30.99
165
329
1.12
55
131
25.68
170
338
1.01
60
140
21.40
175
347
0.92
65
149
17.91
180
356
0.83
70
158
15.07
Low Ambient Operation
During low ambient temperatures, the vapor
refrigerant will migrate to the cold part of
the system (condenser) and condense into
liquid. All CB Series compressors are
provided with factory installed crankcase
heaters to help prevent liquid refrigerant
from slugging the compressors during
startup in low ambient conditions. The
condenser or condensing unit must have
continuous power 24 hours prior to startup.
This ensures the compressor will receive
sufficient refrigerant vapor at startup.
Standard units can operate down to 55°F
ambient temperature.
AAON head pressure control units can
operate down to 35°F ambient temperature.
Two different head pressure control options
available are adjustable fan cycling or ECM
condenser fan. See detailed information
following.
The AAON low ambient (condenser flood-
back) system is used to operate a refrigerant
system down to 0°F outside air temperature.
See detailed information below.
Fan Cycling Low Ambient
Adjustable fan cycling is a low ambient
head pressure control option that cycles the
condenser fans to maintain refrigerant
circuit head pressures at acceptable levels
during cooling operation. The head pressure
set point (100-470 psi) and pressure
differential (35-200 psi) can be field
adjusted using a flathead screwdriver. For
example, if the head pressure is set to
300psi, and the differential is set to 100psi,
then fans will cut in at 300psi and cut out at
200psi. Fan cycling and variable speed
condenser fan head pressure control options
allow mechanical cooling with ambient
temperatures down to 35°F.
Figure 9 - Adjustable Fan Cycling Switch
Variable Speed Low Ambient
Variable speed condenser fan head pressure
control is a low ambient head pressure
control option that sends to an electronically
commutated motor a variable signal in
relation to the refrigerant circuit head
pressure of the system. The motor either
speeds up or slows down air flow
accordingly in order to maintain constant
head pressure. Fan cycling and variable
speed condenser fan head pressure control
options allow mechanical cooling with
ambient temperatures down to 35°F.
Flooded Condenser Low Ambient
Flooded Condenser low ambient control
maintains normal head pressure during
periods of low ambient. When the ambient
temperature
drops,
the
condensing
temperature and therefore pressure drops.
Without ambient control, the system would
shut down on low discharge pressure. The
flooded condenser method of low ambient
control fills the condenser with liquid
refrigerant, decreasing the heat transfer
capacity of the coil, which allows the coil to
operate at an acceptable discharge pressure.
The condenser coil will not be flooded
during summer ambient temperatures, so a
receiver is included to store the additional
liquid refrigerant required to flood the
condenser in low ambient.
The low ambient system maintains normal
head pressure during periods of low ambient
by restricting liquid flow from the condenser
to the receiver, and at the same time
bypassing hot gas around the condenser to
the inlet of the receiver. This reduces liquid
refrigerant
flow
from
the
condenser,
reducing its effective surface area, which in
turn increases the condensing pressure. At
the same time the bypassed hot gas raises
liquid pressure in the receiver, allowing the
system to operate properly. CF Series
condensers and condensing units use an
LAC valve for low ambient operation.
LAC Valve
The Low Ambient Control (LAC) valve is a
non-adjustable
three
way
valve
that
modulates to maintain receiver pressure. As
the receiver pressure drops below the valve
setting (295 psig for R-410A), the valve
modulates to bypass discharge gas around
the condenser. The discharge gas warms the
liquid in the receiver and raises the pressure
to
the
valve
setting.
The
following
schematic shows an example system using
the LAC valve.
Figure 10 - Piping Schematic of Example System using the LAC Valve
In order to maintain head pressure in the
refrigeration system, liquid refrigerant is
kept in the condenser to reduce condenser
surface. The following chart shows the
percentage that a condenser must be flooded
in order to function properly at the given
ambient temperature.
During higher ambient temperatures the
entire condenser is required to condense
refrigerant. During these higher ambient
temperatures, a receiver tank is used to
contain the refrigerant that was required to
flood the condenser during low ambient
operation. The receiver is factory-sized to
contain all of the flooded volume. Without a
receiver there would be high head pressures
during higher ambient conditions.
Table 8 - Condenser Flooding
PERCENTAGE OF CONDENSER TO BE
FLOODED
Ambient
Temperature
(°F)
Evaporating Temperature (°F)
0° 10° 20° 30° 35° 40° 45° 50°
70°
40 24
0
0
0
0
0
0
0°
60 47
33
17
26
20
10
4
50°
70 60
50
38
45
40
33
28
40°
76 68
60
50
56
52
46
42
30°
80 73
66
59
64
60
55
51
20°
86 77
72
65
69
66
62
59
0°
87 83
78
73
76
73
70
68
Compressor Lockouts
Some units include adjustable compressor
lockouts. The compressor lockout in the
picture below can be set to any temperature
between -10°F and 70°F. The ambient
temperature sensor hangs right outside the
unit with a cover.
Figure 11 - Adjustable compressor lockout
Heat pump units include a non-adjustable
compressor lockout for the cooling mode set
to 55°F, and an adjustable compressor
lockout for the heating mode that can be set
between 20°F to 95°F. If a heat pump is
selected with the compressor lockout
feature, the adjustable compressor lockout
will change to the -10°F to 70°F range.
(See back of the manual for maintenance
log.)
At least once each year, a qualified service
technician should check out the unit. This
includes reading and recording suction
pressures and checking for normal sub-
cooling and superheat.
Only
trained
and
qualified
service
technicians experienced in both condensing
units and air conditioning are permitted to
service the CB Series units to keep
warranties in effect.
Coils
The condenser coils should be inspected
yearly to ensure unrestricted airflow. If the
coils contain a large amount of airborne dust
or other material, they should be cleaned.
Care must be taken to prevent bending of the
aluminum fins on the coils.
Before attempting to clean the coils; set
thermostat to the "OFF" position; turn the
electrical power to the unit to the "OFF"
position at the disconnect switch. The
condenser coil can be cleaned by washing
from the inside out with water and a coil
cleaner. If coil is extremely dirty with
clogged
fins,
a
service
professional
specializing in coil cleaning should be
called.
E-Coated Coil Cleaning
Documented routine cleaning of e-coated
coils is required to maintain coating
warranty coverage.
Surface loaded fibers or dirt should be
removed prior to water rinse to prevent
restriction of airflow. If unable to back wash
the side of the coil opposite of the coils
entering air side, then surface loaded fibers
or dirt should be removed with a vacuum
cleaner. If a vacuum cleaner is not available,
a soft non-metallic bristle brush may be
used. In either case, the tool should be
applied in the direction of the fins. Coil
surfaces can be easily damaged (fin edges
bent over) if the tool is applied across the
fins.
Use of a water stream, such as a garden
hose, against a surface loaded coil will drive
the fibers and dirt into the coil. This will
make cleaning efforts more difficult. Surface
loaded fibers must be completely removed
prior to using low velocity clean water rinse.
A
monthly
clean
water
rinse
is
recommended for coils that are applied in
coastal or industrial environments to help to
remove chlorides, dirt, and debris. It is very
important
when
rinsing,
that
water
temperature is less than 130°F and pressure
is than 100 psig to avoid damaging the fin
edges. An elevated water temperature (not to
exceed 130°F) will reduce surface tension,
increasing the ability to remove chlorides
and dirt.
Improper
installation,
adjustment,
alteration, service or maintenance
can
cause
property
damage,
personal injury or loss
of life.
Installation and service must be
performed by a trained, qualified
installer.
WARNING
Electric shock hazard. Shut off all
electrical power to the unit to avoid
shock hazard or injury from rotating
parts.
WARNING
Quarterly cleaning is essential to extend
the life of an e-coated coil and is required
to maintain coating warranty coverage.
Coil cleaning shall be part of the unit’s
regularly
scheduled
maintenance
procedures. Failure to clean an e-coated coil
will void the warranty and may result in
reduced efficiency and durability.
For routine quarterly cleaning, first clean the
coil
with
the
below
approved
coil
cleaner. After cleaning the coils with the
approved cleaning agent, use the approved
chloride remover to remove soluble salts and
revitalize the unit.
Recommended Coil Cleaner
The following cleaning agent, assuming it is
used in accordance with the manufacturer’s
directions on the container for proper mixing
and cleaning, has been approved for use on
e-coated coils to remove mold, mildew,
dust, soot, greasy residue, lint, and other
particulate:
Enviro-Coil Concentrate, Part Number H-
EC01.
Recommended Chloride Remover
CHLOR*RID DTS™ should be used to
remove soluble salts from the e-coated coil,
but the directions must be followed closely.
This product is not intended for use as a
degreaser. Any grease or oil film should first
be removed with the approved cleaning
agent.
Remove Barrier - Soluble salts adhere
themselves to the substrate. For the effective
use of this product, the product must be able
to come in contact with the salts. These salts
may be beneath any soils, grease or dirt;
therefore, these barriers must be removed
prior to application of this product. As in all
surface preparation, the best work yields the
best results.
Apply CHLOR*RID DTS - Apply directly
onto the substrate. Sufficient product must
be applied uniformly across the substrate to
thoroughly wet out surface, with no areas
missed. This may be accomplished by use of
a pump-up sprayer or conventional spray
gun. The method does not matter, as long as
the entire area to be cleaned is wetted. After
the substrate has been thoroughly wetted,
the salts will be soluble and is now only
necessary to rinse them off.
Rinse - It is highly recommended that a hose
be used, as a pressure washer will damage
the fins. The water to be used for the rinse is
recommended to be of potable quality,
though a lesser quality of water may be used
if a small amount of CHLOR*RID DTS is
added.
Check
with
CHLOR*RID
High velocity water from a pressure
washer or compressed air should
only be used at a very low pressure
to prevent fin and/or coil damages.
The force of the water or air jet may
bend the fin edges and increase
airside pressure drop. Reduced unit
performance
or
nuisance
unit
shutdowns may occur.
CAUTION
Harsh chemicals, household bleach,
or acid cleaners should not be used
to clean outdoor or indoor e-coated
coils. These cleaners can be very
difficult to rinse out of the coil and
can accelerate corrosion and attack
the e-coating. If there is dirt below the
surface
of
the
coil,
use
the
recommended coil cleaners.
CAUTION
International, Inc. for recommendations on
lesser quality rinse water.
DX Cooling
Set unit controls to cooling mode of
operation with supply fans on. Check
compressor operation, rotation, amperage
and voltage to the unit nameplate (check the
amperage on the load side of the compressor
contactor).
The scroll compressors are fully hermetic
and require no maintenance except for
keeping the shell clean.
Refrigerant circuit includes factory provided
and field installed line filter drier. The unit
does not include a liquid line solenoid valve.
This must be field furnished and installed if
required by job conditions.
Condenser Fan Motor
All original motors and bearings are
furnished with factory lubrication. They
require no lubrication.
The electrically commutated condenser fan
motor (ECM) is factory preprogrammed and
requires no maintenance.
Replacement Parts
Parts for AAON equipment may be obtained
from your local AAON representative.
Reference the unit serial number and part
number when ordering parts.
AAON – Longview
Warranty, Service, and Parts Department
203 Gum Springs Rd.
Longview, TX 75602
Ph: 903-236-4403
Fax: 903-247-9219
www.aaon.com
Note: Before calling, technician should have
model and serial number of the unit
available for the service department to help
answer questions regarding the unit.
CB Series Startup Form
Date:______________
Job Name:_____________________________________________________________________
Address:______________________________________________________________________
Model Number:_________________________________________________________________
______________________________________________________________________________
Serial Number:_____________________________________________ Tag:_______________
Startup Contractor:______________________________________________________________
Address:__________________________________________________
_________________________________________________________
Phone:_____________
Pre Startup Checklist
Installing contractor should verify the following items.
1. Is there any visible shipping damage?
Yes
No
2. Is the unit level?
Yes
No
3. Are the unit clearances adequate for service and operation?
Yes
No
4. Do all access doors open freely and are the handles operational?
Yes
No
5. Have all shipping braces been removed?
Yes
No
6. Have all electrical connections been tested for tightness?
Yes
No
7. Does the electrical service correspond to the unit nameplate?
Yes
No
8. On 208/230V units, has transformer tap been checked?
Yes
No
9. Has overcurrent protection been installed to match the unit nameplate
requirement?
Yes
No
10. Have all set screws on the fans been tightened?
Yes
No
11. Do all fans and pumps rotate freely?
Yes
No
12. Is all copper tubing isolated so that it does not rub?
Yes
No
Ambient Temperature
Ambient Dry Bulb Temperature ________°F
Ambient Wet Bulb Temperature ________°F
Refrigeration System 1 - Cooling Mode
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
Suction
Liquid
Refrigeration System 1 - Heating Mode (Heat Pump Only)
Pressure
Saturated
Temperature
Line
Temperature
Sub-cooling
Superheat
Discharge
Suction
Liquid
Air-Cooled Condenser Fan
Alignment_____
Check Rotation_____
Nameplate Amps________
Number
hp
L1
L2
L3
1
This log must be kept with the unit. It is the responsibility of the owner and/or
maintenance/service contractor to document any service, repair or adjustments. AAON Service
and Warranty Departments are available to advise and provide phone help for proper operation
and replacement parts. The responsibility for proper start-up, maintenance and servicing of the
equipment falls to the owner and qualified licensed technician.
Entry Date
Action Taken
Name/Tel.
Literature Change History
November 2009
Update of manual formatting to match with other IOMs and adding variable capacity scroll
compressor information.
April 2012
Added oil drip note below piping diagrams. Updated the Startup Form.
May 2012
Updated the Table of Contents.
March 2013
Update of the manual revising Table S1 - Sub-Cooling and Superheat, adding Table S2 -
Performance Testing Air Flow Setpoints, adding information about compressor cycling.
June 2013
Updated piping diagrams to show internal modulating hot gas reheat and hot gas bypass valves.
New part number assigned.
July 2014
Updated service clearance drawing.
February 2015
Updated Feature 5 options to reflect standard exterior corrosion protection.
July 2015
Updated Replacement Parts instructions. Added Features and Options section.
August 2016
Added Storage information. Added guidelines for variable capacity compressors in the line
sizing section. Added double riser schematics and discussion for heat pump operation. Added a
section about oil level under the refrigerant line sizing section. Added a section on compressor
lockouts. Included heat pump charging guidelines in the Acceptable Refrigeration Circuit
Values Table. Added Special Low Ambient Option Charging Instructions. Changed e-coated
coil cleaning to100 psi water pressure.
December 2016
Fixed a reference error.
203 Gum Springs Rd.
Longview, TX 75602-1721
Phone: 903-236-4403
Fax: 903-236-4463
www.aaon.com
CB Series
Installation, Operation &
Maintenance
R57611 · Rev. A · 161221
(ACP J00187)
It is the intent of AAON to provide accurate and current product information. However, in the
interest of product improvement, AAON reserves the right to change pricing, specifications,
and/or design of its product without notice, obligation, or liability.
Copyright © AAON, all rights reserved throughout the world.