AAON CB-024 Installation Operation & Maintenance

Specifications

Brand: AAON
Category: Heat Pump
Model: CB-024 (Installation Operation & Maintenance)
File Type: PDF
File Size: —
Pages: 56

Read Online

Read the AAON CB-024 Installation Operation & Maintenance online using the built-in PDF viewer.

Text of the manual

FOR YOUR SAFETY

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WARNING If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit. WARNING

Table of Contents

AAON® CB Series Features and Options Introduction .................................................................. 5 Safety .............................................................................................................................................. 6 CB Base Model and Features Description .................................................................................... 10 General Description ...................................................................................................................... 11 Codes and Ordinances .............................................................................................................. 11 Receiving Unit .......................................................................................................................... 11 Storage ...................................................................................................................................... 12 Direct Expansion (DX) Condensing Units ............................................................................... 12 Wiring Diagrams ....................................................................................................................... 13 General Maintenance ................................................................................................................ 13 Installation..................................................................................................................................... 14 Lifting the Unit ......................................................................................................................... 14 Locating Unit ............................................................................................................................ 14 Mounting Isolation .................................................................................................................... 15 Access Panel ............................................................................................................................. 15 Electrical ................................................................................................................................... 16 Thermostat ................................................................................................................................ 17 Refrigerant Piping ..................................................................................................................... 18 General .................................................................................................................................. 18 Determining Refrigerant Line Size ....................................................................................... 18 Liquid Line Sizing ................................................................................................................ 19 Suction Line Sizing ............................................................................................................... 20 Hot Gas Bypass Line ............................................................................................................ 22 Hot Gas Reheat ..................................................................................................................... 22 Predetermined Line Sizes ..................................................................................................... 23 Startup ........................................................................................................................................... 26 Compressors .............................................................................................................................. 26 Charging Refrigerant & Adjusting Refrigerant Charge ............................................................ 27 Before Charging .................................................................................................................... 27 Checking Liquid Sub-cooling ............................................................................................... 27 Checking Evaporator Superheat ........................................................................................... 28 Adjusting Sub-cooling and Superheat Temperatures ........................................................... 28 Air Flow .................................................................................................................................... 29 Operation....................................................................................................................................... 31 Thermostat Operation ............................................................................................................... 31 Compressor ............................................................................................................................... 31 Variable Capacity Compressor Controller ................................................................................ 31 Low Ambient Operation ........................................................................................................... 34 LAC Valve ................................................................................................................................ 35 Condenser Flooding .................................................................................................................. 36

Compressor Lockouts ............................................................................................................... 36

Maintenance .................................................................................................................................. 37 Coils .......................................................................................................................................... 37 E-Coated Coil Cleaning ............................................................................................................ 37 DX Cooling ............................................................................................................................... 39 Condenser Fan Motor ............................................................................................................... 39 Replacement Parts ..................................................................................................................... 39 Warranty, Service, and Parts Department ................................................................................. 39 Refrigerant Piping Diagrams ........................................................................................................ 40 CB Series Startup Form ................................................................................................................ 52 Literature Change History............................................................................................................. 55

Index of Tables and Figures

Tables: Table 1 - Recommended Elevation Minimums ............................................................................ 15 Table 2 - Predetermined Line sizes for CB units with two step compressors and R-410A .......... 25 Table 3 - Acceptable Refrigeration Circuit Values ....................................................................... 28 Table 4 - Performance Testing Air Flow Setpoints ...................................................................... 29 Table 5 - R-410A Refrigerant Temperature-Pressure Chart ......................................................... 30 Table 6 - Demand Signal vs. Compressor Capacity Modulation.................................................. 32 Table 7 - Thermistor Temperature vs. Resistance Values ............................................................ 33 Table 8 - Condenser Flooding....................................................................................................... 36 Figures: Figure 1 – Forklift Channels & Access Panel ............................................................................... 14 Figure 2 – Condensing Unit Clearances ....................................................................................... 15 Figure 3 – Utility Entry ................................................................................................................. 16 Figure 4 – Heat Pump Piping Schematic of Suction Vapor Flow Down in Double Riser ........... 21 Figure 5 – Heat Pump Piping Schematic of Discharge Vapor Flow Up in Double Riser ............ 21 Figure 6 - Riser height versus total equivalent line length ........................................................... 25 Figure 7 - Variable Capacity Compressor Controller ................................................................... 32 Figure 8 - Compressor Controller Flash Code Details.................................................................. 33 Figure 9 - Adjustable Fan Cycling Switch .................................................................................... 34 Figure 10 - Piping Schematic of Example System using the LAC Valve .................................... 35 Figure 11 - Adjustable compressor lockout .................................................................................. 36 Figure 12– A/C only piping, AHU above CU .............................................................................. 40 Figure 13 – A/C only piping, AHU below CU ............................................................................. 41 Figure 14 – Modulating hot gas reheat piping, AHU above CU .................................................. 42 Figure 15 – Modulating hot gas reheat piping, AHU below CU .................................................. 43 Figure 16 – Hot gas bypass piping, AHU above CU .................................................................... 44 Figure 17 – Hot gas bypass piping, AHU below CU .................................................................... 45 Figure 18 – Modulating hot gas reheat with hot gas bypass piping, AHU above CU .................. 46 Figure 19 – Modulating hot gas reheat with hot gas bypass piping, AHU below CU.................. 47 Figure 20 – Heat pump piping, AHU above CU .......................................................................... 48 Figure 21 – Heat pump piping, AHU below CU .......................................................................... 49 Figure 22 – Heat pump with modulating hot gas reheat piping, AHU above CU ........................ 50 Figure 23 – Heat pump with modulating hot gas reheat, AHU below CU ................................... 51 R57611 · Rev. A · 161221 (ACP J00187)

AAON® CB Series Features and Options Introduction

Energy Efficiency  Two Step or Variable Capacity Scroll Compressor  Air-Source Heat Pump  Variable Speed Condenser Fans for Head Pressure Control Humidity Control  Modulating Hot Gas Reheat Safety  Suction Pressure Transducer  Heavy Duty Wire Guards or Louvered Panels for Condenser Coils  Automatic Low Pressure and Manual reset High Pressure Safety Cut-outs  Suction and Liquid Line Schrader Valves Installation and Maintenance  Easily Removable Panel Access to Service Compartment  Run Test Report and Installation Manuals Included in Controls Compartment  Color Coded Wiring and Wiring Diagrams  24V Control Circuit Transformer Option System Integration  Split System Matching  Modulating Head Pressure Control  Single Point Power  High Density Foam Compressor Sound Suppression Blanket Environmentally Friendly  R-410A Refrigerant Extended Life  2,500 Hour Salt Spray Tested Exterior Corrosion Paint  Optional 5 Year Non-Prorated Compressor Warranty  Polymer E-Coated Condenser Coils

servicing, shut off all electrical power

to the unit, including remote disconnects, to avoid shock hazard or injury from rotating parts. Follow proper Lockout-Tagout procedures. WARNING Safety Attention should be paid to the following statements: NOTE - Notes are intended to clarify the unit installation, operation and maintenance. CAUTION - Caution statements are given to prevent actions that may result in equipment damage, property damage, or personal injury. WARNING - Warning statements are given to prevent actions that could result in equipment damage, property damage, personal injury or death. DANGER - Danger statements are given to prevent actions that will result in equipment damage, property damage, severe personal injury or death. ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death, or property damage.  When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.  Verify proper operation after servicing. Secure all doors with key-lock or nut and bolt. WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. A copy of this IOM should be kept with the unit. WARNING

FIRE, EXPLOSION OR CARBON

MONOXIDE POISONING HAZARD Failure to replace proper controls could result in fire, explosion or carbon monoxide poisoning. Failure to follow safety warnings exactly could result in serious injury, death or property damage. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this appliance. WARNING LIVE ELECTRICAL During installation, testing, servicing, and troubleshooting of the equipment it may be necessary to work with live electrical components. Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks. Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn, should be followed. WARNING GROUNDING REQUIRED All field installed wiring must be completed by qualified personnel. Field installed wiring must comply with NEC/CEC, local and state electrical code requirements. Failure to follow code requirements could result in serious injury or death. Provide proper unit ground in accordance with these code requirements. WARNING ROTATING COMPONENTS Unit contains fans with moving parts that can cause serious injury. Do not remove grill containing fans until the power to the unit has been disconnected and fan has stopped rotating. WARNING 3-PHASE ROTATION Rotation must be checked on all MOTORS AND COMPRESSORS of 3 phase units at startup by a qualified service technician. Scroll compressors are directional and can be damaged if rotated in the wrong direction. Compressor rotation must be checked using suction and discharge gauges. Fan motor rotation should be checked for proper operation. Alterations should only be made at the unit power connection CAUTION

Compartments containing hazardous

voltage or rotating parts are equipped with a panel requiring tooled access. Always re-install screws on the panel after installation or service is completed. CAUTION UNIT HANDLING To prevent injury or death lifting equipment capacity shall exceed unit weight by an adequate safety factor. Always test-lift unit not more than 24 inches high to verify proper center of gravity lift point to avoid unit damage, injury or death. WARNING LEAK TESTING Do not use oxygen, acetylene or air in place of refrigerant and dry nitrogen for leak testing. A violent explosion may result causing injury or death. WARNING COMPRESSOR LUBRICANT Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants used in hydrofluorocarbon (HFC) refrigeration systems. Refer to the compressor label for the proper compressor lubricant type. CAUTION PVC PIPING PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings and complete piping system failure. CAUTION COIL CLEANERS To prevent damage to the unit, do not use acidic chemical coil cleaners. Do not use alkaline chemical coil cleaners with a pH value greater than 8.5, after mixing, without first using an aluminum corrosion inhibitor in the cleaning solution. CAUTION COIL CLEANERS Some chemical coil cleaning compounds are caustic or toxic. Use these substances only in accordance with the manufacturer’s usage instructions. Failure to follow instructions may result in equipment damage, injury or death. WARNING

1. Startup and service must be performed

by a Factory Trained Service Technician. 2. The unit is for outdoor use only. See General Information section for more unit information. 3. Every unit has a unique equipment nameplate with electrical, operational and unit clearance specifications. Always refer to the unit nameplate for specific ratings unique to the model you have purchased. 4. READ THE ENTIRE INSTALLATION, OPERATION AND MAINTENANCE MANUAL. OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL. 5. Keep this manual and all literature safeguarded near or on the unit. COIL CLEANING Do not clean DX refrigerant coils with hot water or steam. The use of hot water or steam on refrigerant coils will cause high pressure inside the coil tubing and damage to the coil. CAUTION ENCLOSED AREA Do not work in an enclosed area where refrigerant or nitrogen gases may be leaking. A sufficient quantity of vapors may be present and cause injury or death. WARNING COMPRESSOR CYCLING 5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes. 5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes. The cycle rate must not exceed 6 starts per hour. WARNING

CB Series Feature String Nomenclature

Model Options : Unit Feature Options GEN MJREV UNIT SIZE VLT COMP CKTS 1 2 3 4 5 6 7 CB - B - 060 - 3 - B - 1 : B D 0 0 D A 0 10 CB Base Model and Features Description BASE MODEL SERIES AND GENERATION CB REVISION B = Design Sequence UNIT SIZE 024 = 24 MBH - 2 Ton - Vertical Discharge 036 = 36 MBH - 3 Ton - Vertical Discharge 048 = 48 MBH - 4 Ton - Vertical Discharge 060 = 60 MBH - 5 Ton - Vertical Discharge VOLTAGE 1 = 230V/1Φ/60Hz 2 = 230V/3Φ/60Hz 3 = 460V/3Φ/60Hz 4 = 575V/3Φ/60Hz 8 = 208V/3Φ/60Hz 9 = 208V/1Φ/60Hz COMPRESSOR TYPE B = R-410A Two Step Scroll Compressor D = R-410A Variable Capacity Scroll Compressor F = R-410A Two Step Scroll Compressor with Sound Blanket H = R-410A Variable Capacity Scroll Compressor with Sound Blanket NUMBER OF CIRCUITS 1 = One Circuit FEATURE 1: AMBIENT CONTROL 0 = Standard (55°F Ambient) B = Adjustable Fan Cycling (35°F Ambient) D = Modulating Fan Pressure Control (35°F Ambient) F = Flooded Condenser Ambient Controls (0°F) + Option B G = Flooded Condenser Ambient Controls (0°F) + Option D FEATURE 2: REFRIGERATION OPTIONS 0 = Standard - Split System Air Conditioner A = External Hot Gas Bypass B = Split System Heat Pump D = Modulating Hot Gas Reheat F = Options A + D G = Options B + D FEATURE 3: CONTROLS 0 = Standard - Terminal Block A = Suction Pressure Transducer (F1- Wattmaster Reheat) H = Control Circuit Transformer S = Suction Pressure Transducer (Not F1 - Wattmaster Controls) T = Control Circuit Transformer w/ Suction Pressure Transducer FEATURE 4: COIL PROTECTION 0 = Standard A = Polymer E-Coated Coil FEATURE 5: CABINET OPTIONS D = Standard – Louvered Panels + 2500 Hour Salt- Spray Tested Exterior Paint G = Wire Grille + 2500 Hour Salt-Spray Tested Exterior Paint FEATURE 6: WARRANTY 0 = Standard A = Second to Fifth Year Extended Compressor Warranty FEATURE 7: TYPE 0 = Standard X = Special Pricing Authorization

AAON CB Series condensing units have

been designed for outdoor installation only. Startup and service must be performed by a Factory Trained Service Technician. Codes and Ordinances CB Series units have been tested and certified, by ETL, in accordance with UL Safety Standard 1995/CSA C22.2 No. 236. System should be sized in accordance with the American Society of Heating, Refrigeration and Air Conditioning Engineers Handbook. Installation of CB Series units must conform to the ICC standards of the International Mechanical Code, the International Building Code, and local building, plumbing and waste water codes. All appliances must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1. Receiving Unit When received, the unit should be checked for damage that might have occurred in transit. If damage is found it should be noted on the carrier’s Freight Bill. A request for inspection by carrier’s agent should be made in writing at once. Nameplate should be checked to ensure the correct model sizes and voltages have been received to match the job requirements. If repairs must be made to damaged goods, then the factory should be notified before any repair action is taken in order to protect the warranty. Certain equipment alteration, repair, and manipulation of equipment without the manufacturer’s consent may void the product warranty. Contact AAON Warranty Department for assistance with handling damaged goods, repairs, and freight claims: (903) 236-4403. NOTE: Upon receipt check shipment for items that ship loose. Consult order and shipment documentation to identify potential loose-shipped items. Loose-shipped items The Clean Air Act of 1990 bans the intentional venting of refrigerant as of July 1, 1992. Approved methods of recovery, recycling, or reclaiming must be followed. CAUTION QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a Factory Trained Service Technician. WARNING SHARP EDGES Coils and sheet metal surfaces present sharp edges and care must be taken when working with equipment. WARNING Failure to observe the following instructions will result in premature failure of your system and possible voiding of the warranty. WARNING

may have been placed inside the unit cabinet

for security. Installers and owners should secure all doors with locks or nuts and bolts to prevent unauthorized access. The warranty card must be completed in full and returned to AAON not more than 3 months after the unit is delivered. Storage If installation will not occur immediately following delivery, store equipment in a dry protected area away from construction traffic and in the proper orientation as marked on the packaging with all internal packaging in place. Secure all loose-shipped items. Direct Expansion (DX) Condensing Units CB Series condensing units are factory assembled and wired, including a full charge of R-410A refrigerant for up to 25 feet of line set. Systems with the modulating hot gas reheat option will require refrigerant to be field added because of the additional refrigerant components and piping associated with the system. Failure to observe the following instructions may result in premature failure of your system, and possible voiding of the warranty. Never cut off the main power supply to the unit, except for servicing, emergency, or complete shutdown of the unit. When power is cut off from the unit, compressors using crankcase heaters cannot prevent refrigerant migration. This means the compressor may cool down and liquid refrigerant may accumulate in the compressor. Since the compressor is designed to pump refrigerant gas, damage may occur when power is restored. If power to the unit must be off for more than an hour, turn the thermostat system switch to “Off”, or turn the unit off at the control panel, and then cut off the main power supply. Leave the unit off until the main power supply has been turned on again for at least 24 hours. This will give the crankcase heater time to clear any liquid accumulation out of the compressor before it is required to run. Always control the system from the thermostat, or control panel, never at the main power supply, except for servicing, emergency, or complete shutdown of the unit. The standard compressors must be on a minimum of 5 minutes and off for a minimum of 5 minutes. The cycle rate must be no more than 6 starts per hour. The variable capacity compressors must be on a minimum of 3 minutes and off for a minimum of 3 minutes. The cycle rate must be no more than 10 starts per hour. The compressor life will be seriously shortened by reduced lubrication, and the pumping of excessive amounts of liquid oil and liquid refrigerant. CRANKCASE HEATER OPERATION Units are equipped with compressor crankcase heaters, which should be energized at least 24 hours prior to cooling operation, to clear any liquid refrigerant from the compressors. CAUTION

Note: Low Ambient Operation

Units without a low ambient option, such as condenser fan cycling or the 0°F low ambient option, will not operate in the cooling mode of operation properly when the outdoor temperature is below 55°F. Low ambient and/or air handling unit economizer options are recommended if cooling operation below 55°F is expected. Note: Multiple Systems with Multiple Thermostats When several heating and cooling split systems are used to condition a space all thermostat switches must be set in either heating mode, cooling mode or off. Do not leave part of the systems switched to the opposite mode. Cooling only systems should be switched off at the thermostat during the heating season. Wiring Diagrams Unit specific wiring diagram is laminated in plastic and located inside the controls compartment door. General Maintenance When the initial startup is made, and on a periodic schedule during operation, it is necessary to perform routine service checks on the performance of the condensing unit. This includes reading and recording suction pressures and checking for normal sub- cooling and superheat. COMPRESSOR CYCLING 5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes. 5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes. The cycle rate must not exceed 6 starts per hour. WARNING

AAON equipment has been designed for

quick and easy installation. Lifting the Unit CB Series condensing units have channels underneath the base which provide lifting access to the underside of the equipment and allow moving and placement without physical damage. Figure 1 – Forklift Channels & Access Panel Dollies and/or carts are recommended to lift and place the unit to prevent damage to the equipment and injury to the installer. Care should be taken if using spreader bars, blocking, or other lifting devices to prevent any damage to the cabinet, coil or condensing fans. Before lifting unit, be sure that all shipping material has been removed from unit. Hoist unit to a point directly above the condenser pad, and lower unit into the proper place. Unit may also be positioned with a dolly. When the unit is in place, remove the dolly or lifting device. Make sure the unit is properly seated and level. Locating Unit CB Series condensing units are designed for outdoor application and placement at ground level or on a rooftop. Units must be placed on a level and solid foundation that can support the unit’s weight. When rooftop mounted, a steel frame must be provided that will support the unit above the roof itself for load distribution. When installed at ground level, a one-piece concrete slab or composite condenser pad should be used with footings that extend below the frost line (a substantial base that will not settle). Slab should be surrounded by a graveled area for proper drainage and should not adjoin the building as sound and vibration may be transmitted to the structure. Care must also be taken to protect the coils and fins from damage due to vandalism or other hazards. Airflow to and from the condensing unit must not be restricted. Coils and fans must be free of any obstructions and debris in order to start and operate properly with a correct amount of airflow. Obstruction to air flow will result in decreased performance and efficiency. The installation position must provide at least one foot of clearance from the wall for proper air flow to the coils. When multiple units are mounted adjacent to each other, the clearance required between them is three feet. Service compartment must be accessible for periodic servicing of controls, safety devices, and refrigerant service/shutoff valves. At least two feet of clearance on this Incorrect lifting can cause damage to the unit. CAUTION

corner of the unit is recommended for

service. Figure 2 – Condensing Unit Clearances Condensing units should not be installed in an enclosure or pit that is deeper than the height of the unit. When recessed installation is necessary, the clearance to maintain proper airflow is at least three feet. CB Series condensing units are single circuited with vertical air discharge. There must be no obstruction above the equipment. Do not place the unit under an overhang. Placement relative to the building air intakes and other structures must be carefully selected. Consider the effects of outdoor fan noise on conditioned space and any adjacent occupied space. It is recommended that the unit be placed so that discharge does not blow toward windows less than 25 feet away. Heat pumps require special location consideration in areas where snow accumulation can become an obstruction and in areas with prolonged continuous subfreezing temperatures. Heat pump unit bases are cutout under the outdoor coil to permit drainage of frost accumulation. The unit must be situated to permit free unobstructed drainage of the defrost water and ice. A minimum 3 inches clearance under the outdoor coil is required in the milder climates. In more severe weather locations, it is recommended that the unit be elevated to allow unobstructed drainage and airflow. Table 1 - Recommended Elevation Minimums Design Temperature Suggest Minimum Elevation +15 F and above 3” -5 F to +17 F 8” Below -5 F 12” Mounting Isolation For roof mounted applications or anytime vibration transmission is a factor, vibration isolators may be used. Access Panel Access panel is provided to electrical compartment. To remove the panel, unscrew the four screws PVC PIPING PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are vulnerable to attack by certain chemicals. Polyolester (POE) oils used with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping system will result in stress cracking of the piping and fittings and complete piping system failure. CAUTION

Verify the unit nameplate agrees with the

power supply. Connect power and control field wiring as shown on the unit wiring diagram provided with the unit. Route power and control wiring, separately, through the utility entry right above the service valves. Do not run power and signal wires in the same conduit. Figure 3 – Utility Entry Size supply conductors based on the unit MCA rating. Supply conductors must be rated a minimum of 75°C. Protect the branch circuit in accordance with code requirements. The unit must be electrically grounded in accordance with local codes, or in the absence of local codes, the current National Electric Code, ANSI/NFPA 70 or the current Canadian Electrical Code CSA C22.1. Note: Units are factory wired for 208V, 230V, 460V or 575V. In some units, the 208V and 230V options may also be provided in single or three phase configurations. The transformer configuration must be checked by a qualified technician prior to startup. Wire power leads to the unit terminal block. All wiring beyond this point has been done by the manufacturer and cannot be modified without affecting the unit's agency/safety certification. All units require field supplied electrical overcurrent and short circuit protection. Device must not be sized larger than the Maximum Overcurrent Protection (MOP) shown on the unit nameplate. Codes may require a disconnect switch be within sight of the unit. 3-PHASE ROTATION Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. Condenser fan motors should be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection. CAUTION ELECTRIC SHOCK Electric shock hazard. Before attempting to perform any installation, service, or maintenance, shut off all electrical power to the unit at the disconnect switches. Unit may have multiple power supplies. Failure to disconnect power could result in dangerous operation, serious injury, death or property damage. WARNING

It is recommended that the field installed

overcurrent protection or disconnect switch not be installed on the unit. Supply voltage must be within the min/max range shown on the unit nameplate. Available short circuit current should not exceed the short circuit current rating (SCCR) shown on the unit nameplate. Three phase voltage imbalance will cause motor overheating and premature failure. The maximum allowable imbalance is 2.0%. Voltage imbalance is defined as 100 times the maximum deviation from the average voltage divided by the average voltage. Example: (221V+230V+227V)/3 = 226V, then 100*(226V-221V)/226V = 2.2%, which exceeds the allowable imbalance. Check voltage imbalance at the unit disconnect switch and at the compressor terminal. Contact your local power company for line voltage corrections. Installing contractor must check for proper motor rotation and check blower motor amperage listed on the motor nameplate is not exceeded. Wire control signals to the unit’s low voltage terminal block located in the controls compartment. If any factory installed wiring must be replaced, use a minimum 105°C type AWM insulated conductors. Thermostat If a thermostat is used for unit control, thermostat should be located on an inside wall 4-5 feet above the floor where it will not be subjected to drafts, sun exposure, or heat from electrical fixtures or appliances. Follow thermostat manufacturer’s instructions for general installation procedure. Thermostat control wiring size must be large enough to prevent excess voltage drop and ensure proper operation. All external devices must be powered via a separate external power supply. Units with the modulating hot gas reheat dehumidification feature must use a humidistat or a thermostat with a normally closed (NC) dehumidification option. The following thermostats have been approved for usage with the dehumidification feature, Robertshaw® 9825i2 Thermostat Honeywell VisionPRO® IAQ Thermostat AAON Mini Controller Three phase voltage imbalance will cause motor overheating and premature failure. CAUTION

(See back of the manual for refrigerant

piping diagrams.) General Piping from the condensing unit to the air handler is the responsibility of the installing contractor. Use only clean type “ACR” copper tubing that has been joined with high temperature brazing alloy. The pipe or line sizes must be selected to meet the actual installation conditions and not simply based on the connection sizes at the condensing unit or air handler. All CB Series condensing units are provided with in-line shutoff valves on both the liquid and suction lines. These should remain closed until the system is ready for start-up after installation. Piping should conform to generally accepted practices and codes. Upon completion of piping connection, the interconnecting piping and air handler MUST BE evacuated to 500 microns or less; leak checked and charged with refrigerant. Determining Refrigerant Line Size The piping between the condenser and low side must ensure: 1. Minimum pressure drop, and 2. Continuous oil return, and 3. Prevention of liquid refrigerant slugging, or carryover Minimizing the refrigerant line size is favorable from an economic perspective, reducing installation costs, and reducing the potential for leakage. However, as pipe diameters narrow, pressure-reducing frictional forces increase. Excessive suction line pressure drop causes loss of compressor capacity and increased power usage resulting in reduced system efficiency. Excessive pressure drops in the liquid line can cause the liquid refrigerant to flash, resulting in faulty Thermal Expansion Valve (TXV) operation and improper system performance. In order to operate efficiently and cost effectively, while avoiding malfunction, refrigeration systems must be designed to minimize both cost and pressure loss. REFRIGERANT PIPING This section is for information only and is not intended to provide all details required by the designer or installer of the refrigerant piping between the condenser or condensing unit and the air handling unit. AAON, Inc. is not responsible for interconnecting refrigerant piping. Consult ASHRAE Handbook – Refrigeration and ASME Standards. CAUTION REFRIGERANT PIPING Line sizes must be selected to meet actual installation conditions, not simply based on the connection sizes at the condensing unit or air handling unit. CAUTION

Equivalent Line Length

All line lengths discussed in this manual, unless specifically stated otherwise, are Equivalent Line Lengths. The frictional pressure drop through valves, fittings, and accessories is determined by establishing the equivalent length of straight pipe of the same diameter. Always use equivalent line lengths when calculating pressure drop. Special piping provisions must be taken when lines are run underground, up vertical risers, or in excessively long line runs. Liquid Line Sizing When sizing the liquid line, it is important to minimize the refrigerant charge to reduce installation costs and improve system reliability. This can be achieved by minimizing the liquid line diameter. However, reducing the pipe diameter will increase the velocity of the liquid refrigerant which increases the frictional pressure drop in the liquid line, and causes other undesirable effects such as noise. Maintaining the pressure in the liquid line is critical to ensuring sufficient saturation temperature, avoiding flashing upstream of the TXV, and maintaining system efficiency. Pressure losses through the liquid line due to frictional contact, installed accessories, and vertical risers are inevitable. Maintaining adequate sub- cooling at the condenser to overcome these losses is the only method to ensure that liquid refrigerant reaches the TXV. Liquid refrigerant traveling upwards in a riser loses head pressure. If the evaporator is below the condenser, and the liquid line does not include risers, the gravitational force will increase the pressure of the liquid refrigerant. This will allow the refrigerant to withstand greater frictional losses without the occurrence of flashing prior to the TXV. A moisture-indicating sight glass may be field installed in the liquid line to indicate the occurrence of premature flashing or moisture in the line. The sight glass should not be used to determine if the system is properly charged. Use temperature and pressure measurements to determine liquid sub-cooling, not the sight glass. Liquid Line Routing Care should be taken with vertical risers. When the system is shut down, gravity will pull liquid down the vertical column, and back to the condenser when it is below the evaporator. This could potentially result in compressor flooding. A check valve can be installed in the liquid line where the liquid column rises above the condenser to prevent this. The liquid line is typically pitched along with the suction line, or hot gas line, to minimize the complexity of the configuration. Liquid Line Insulation When the liquid line is routed through regions where temperature losses are expected, no insulation is required, as this may provide additional sub-cooling to the refrigerant. When routing the liquid line through high temperature areas, insulation of the line is appropriate to avoid loss of sub- cooling through heat gain. Liquid Line Guidelines In order to ensure liquid at the TXV, the sum of frictional losses and pressure loss due to vertical rise must not exceed available sub-cooling. A commonly used guideline to consider is a system design with pressure losses due to friction through the line not to exceed a corresponding 1-2°F change in saturation temperature. An additional recommendation is that the sum of frictional losses and pressure loss due to vertical rise should not exceed 5°F.

If the velocity of refrigerant in the liquid line

is too great, it could cause excessive noise or piping erosion. The recommended maximum velocities for liquid lines are 100 fpm from the condenser to a receiver tank to discourage fluid backup, and 300 fpm from receiver tank to the evaporator to minimize valve induced liquid hammer. Liquid Line Accessories Liquid line shut off valves and filter driers are factory provided. Filter driers must be field installed. The total length equivalent of pressure losses through valves, elbows and fittings must be considered when adding additional components in the field. It is a good practice to utilize the fewest elbows that will allow the mating units to be successfully joined. A solenoid valve is recommended on lines over 100ft in length to prevent liquid migration when the compressors are off. The solenoid needs to be wired so that it is open when the compressors turn on, and closed when the compressors turn off. Suction Line Sizing The suction line is more critical than the liquid line from a design and construction standpoint. More care must be taken to ensure that adequate velocity is achieved to return oil to the compressor at minimum loading conditions. However, reducing the piping diameter to increase the velocity at minimal load can result in excessive pressure losses, capacity reduction, and noise at full load. Suction Line Routing Pitch the suction line in the direction of flow (about 1 foot per 120 feet of length) to maintain oil flow towards the compressor, and keep it from flooding back into the evaporator. Crankcase heaters are provided to keep any condensed refrigerant that collects in the compressor from causing damage or wear. Make sure to provide support to maintain suction line positioning, and insulate completely between the evaporator and condensing unit. It is important to consider part load operation when sizing suction lines. At minimum capacity, refrigerant velocity may not be adequate to return oil up the vertical riser. Decreasing the diameter of the vertical riser will increase the velocity, but also the frictional loss. For difficult line routing applications, a double suction riser can be applied to the situation of part load operation with a suction riser. A double suction riser is designed to return oil at minimum load while not incurring excessive frictional losses at full load. A double suction riser consists of a small diameter riser in parallel with a larger diameter riser, and a trap at the base of the large riser. At minimum capacity, refrigerant velocity is not sufficient to carry oil up both risers, and it collects in the trap, effectively closing off the larger diameter riser, and diverting refrigerant up the small riser where velocity of the refrigerant is sufficient to maintain oil flow. At full load, the mass flow clears the trap of oil, and refrigerant is carried through both risers. The smaller diameter pipe should be sized to return oil at minimum load, while the larger diameter pipe should be sized so that flow through both pipes provides acceptable pressure drop at full load. SUCTION LINE SIZING Suction line must be sized in accordance to the minimum capacity of the variable speed compressor. CAUTION

A double riser used for heat pump operation

works differently than that described above. The specific volume (ft3/lb) of refrigerant at the discharge temperature (heating mode line conditions) is significantly lower than the specific volume at the suction temperature (cooling mode line conditions). To compound the issue, the capacity in heating mode is lower than the capacity in cooling mode. The discharge velocity in the riser during heating mode is much lower than the suction velocity during cooling mode. Often, a double riser is necessary to get acceptable velocities for the discharge mode and acceptable velocities for the suction mode. A solenoid valve must be added to the second riser. The solenoid valve must be wired to the reversing valve so that the solenoid valve opens in cooling mode, and closes in heating mode. See the diagrams below: Figure 4 – Heat Pump Piping Schematic of Suction Vapor Flow Down in Double Riser Figure 5 – Heat Pump Piping Schematic of Discharge Vapor Flow Up in Double Riser Suction Line Insulation The entire suction line should be insulated with a minimum 1 inch thick Armaflex insulation. This prevents condensation from forming on the line, and reduces any potential loss in capacity associated with heat gain placing additional load on the system. Suction Line Guidelines For proper performance, suction line velocities less than a 4,000 fpm maximum are recommended. The minimum velocity required to return oil is dependent on the pipe diameter, however, a general guideline of 1,000 fpm minimum may be applied. When suction flow is up, variable capacity compressors require a minimum velocity of 2,000 fpm. Heat pump vapor lines must be checked for suction flow (cooling mode operation) and discharge flow (heating mode operation). The same line must be used for both modes of operation.

In a fashion similar to the liquid line, a

common guideline to consider is a system design with pressure losses due to friction through the line not to exceed a corresponding 1-2°F change in saturation temperature. At points where small pipe size can be used to provide sufficient velocity to return oil in vertical risers at part loads, greater pressure losses are incurred at full loads. This can be compensated for by over sizing the horizontal runs and vertical drop sections. This will however require additional refrigerant charge. Circuits with variable capacity scroll compressors require suction riser traps every 10 feet. Suction Line Accessories If the job requirements specify suction accumulators, they must be separately purchased and field installed. Hot Gas Bypass Line Hot Gas Bypass (HGB) is available for use with DX systems that may experience low suction pressure during the operating cycle. This may be due to varying load conditions associated with VAV applications or units supplying a large percentage of outside air. The system is designed to divert refrigerant from the compressor discharge to the low pressure side of the system in order to keep the evaporator from freezing and to maintain adequate refrigerant velocity for oil return at minimum load. Hot discharge gas is redirected to the evaporator inlet via an auxiliary side connector (ASC) to false load the evaporator when reduced suction pressure is sensed. Field piping between the condensing unit and the evaporator is required. Hot Gas Bypass Piping Considerations for Evaporator above Condensing Unit Pitch the hot gas bypass line downward in the direction of refrigerant flow, toward the evaporator. When installing hot gas bypass risers, an oil drip line must be provided at the lowest point in the system. The oil drip line must be vertical, its diameter should be the same as the diameter of the riser, and it should be 1 foot long. Install a sight glass in the oil drip line for observation. Run an oil return line, using 1/8 inch capillary tube, 10 feet in length, from the oil drip line to the suction line. Connect the oil return line below the sight glass and 1 inch above the bottom of the oil drip line. HGB valves are adjustable. Factory HGB valve settings will be sufficient for most applications, but may require slight adjustments for some applications, including some make up air applications. Insulate the entire length of the HGB line with a minimum 1 inch thick Armaflex insulation. Hot Gas Bypass Piping Considerations for Evaporator Below Condensing Unit The line must slope downward from the HGB valve toward the evaporator. Hot Gas Bypass Line Guidelines Choose a small size line to ensure oil return, and minimize refrigerant charge. Maintain velocities below a maximum of 4,000 fpm. A general minimum velocity guideline to use is approximately 900 fpm. Hot Gas Reheat The AAON modulating hot gas reheat system diverts hot discharge gas from the condenser to the air handling unit through

the hot gas line. Field piping between the

condensing unit and the air handler is required. The line delivers the hot discharge gas to the reheat coil and/or the hot gas bypass valve, so it is sized as a discharge line. Discharge lines should be sized to ensure adequate velocity of refrigerant to ensure oil return, avoid excessive noise associated with velocities that are too high, and to minimize efficiency losses associated with friction. Pitch the hot gas line in the direction of flow for oil return. When installing hot gas reheat risers, an oil drip line must be provided at the lowest point in the system. The oil drip line must be vertical, its diameter should be the same as the diameter of the riser, and it should be 1 foot long. Run a drip line, using 1/8 inch capillary tube, 10 feet in length, from the oil drip line to the suction line. Connect the oil return line below the sight glass and 1 inch above the bottom of the oil drip line. Insulate the entire length of the hot gas line with a minimum 1 inch thick Armaflex insulation. Hot Gas Reheat Guidelines Maintain velocities below a maximum of 4,000 fpm. A general minimum velocity guideline is 900 fpm. Predetermined Line Sizes To aid in line sizing and selection, AAON has predetermined line sizes for the liquid, suction, and hot gas lines in comfort cooling applications. In order to generate this information, the following cycle assumptions are made: Saturated suction temperature = 50°F, Saturated condensing temperature = 125°F, Sub-cooling = 10°F, Superheat = 15°F. The liquid lines have been chosen to maintain velocities between 100 and 350 fpm. The suction line diameters are selected to limit velocities to a 4,000 fpm maximum, while a minimum velocity restriction is imposed by the ability to entrain oil up vertical suction risers (ASHRAE Handbook - Refrigeration). Acceptable pressure loss criteria are applied to each of the lines: The total equivalent length of the liquid line available is determined such that 3°F of liquid sub- cooling remain at the TXV. This includes the pressure losses in horizontal and vertical sections, accessories, elbows, etc. Recall that the available sub-cooling for the cycle is assumed as 10°F. To maintain at least 3°F sub-cooling as a factor of safety to avoid flashing at the TXV, we consider a maximum pressure loss equivalent to a 7°F change in saturation temperature. Pressure losses in the suction line are not to exceed 2°F. When to Use Predetermined Line Sizing The line sizes presented are not the only acceptable pipe diameters, they are however appropriate for general comfort cooling applications, and satisfy common job requirements. Examine the conditions, assumptions, and constraints used in the generation of the predetermined pipe diameters to ensure that this method is applicable to a particular case. Do not assume that these line sizes are appropriate for every case. Consult ASHRAE Handbook – Refrigeration for generally accepted system piping practices.

How to Use Predetermined Line Sizing

First, read the previous section, When to Use Predetermined Line Sizing, to decide if this method is applicable. Next, consult Table 2 below for pipe diameters. Examine Figure 6 below to determine the acceptable line dimensions associated with the pipe diameters determined in Table 2 below. The figure is shown as total available riser height versus total equivalent line length for the liquid line. The curve identifies a region of acceptable piping configuration when the predetermined line sizes are selected for any model in the table. A piping configuration above the curve falls outside the assumptions used to determine the line size and will result in a loss of sub- cooling, and additional pressure losses in the suction and hot gas lines. The total equivalent line length definition includes the height of vertical rise, pressure drop through elbows and accessories, and horizontal line length, so elbows, accessories, and vertical rise must be considered when determining horizontal length available from the total equivalent line length. The figure below is presented in terms of the liquid line, but it assumes that the suction line length is similar, as these lines are commonly routed together to minimize the space and cost required for split system installation. Before using this table read the When to Use Predetermined Line Sizes section. Do not assume that these line sizes are appropriate for every case. Consult ASHRAE Handbook – Refrigeration for generally accepted system piping practices. The AAON Refrigerant Piping Calculator in Ecat32 can be used for job specific line sizing. CAUTION

Table 2 - Predetermined Line sizes for CB units with two step compressors and R-410A

Model Connection Sizes Predetermined Line Size Liquid Suction Hot Gas Liquid Suction HGBP* HGRH** CB-024 3/8” 3/4” 3/8” 3/8” 3/4” 3/8” 3/8” CB-036 3/8” 3/4” 3/8” 3/8” 3/4” 3/8” 1/2” CB-048 3/8” 7/8” 1/2” 1/2” 7/8” 1/2” 1/2” CB-060 3/8” 7/8” 1/2” 1/2” 7/8” 1/2” 1/2” * Hot Gas Bypass line ** Hot Gas Reheat line Figure 6 - Riser height versus total equivalent line length Note: Figure 6 is for R-410A split system applications with two step compressor CB-024 through CB-060 units. The region of acceptable riser height is the lighter area. Select the corresponding predetermined line size from Table 2 above. Total Equivalent Line Length in this figure is limited to 160 equivalent feet. CAUTION

(See back of the manual for startup form.)

Before startup of the condenser or condensing unit, make sure that the following items have been checked. 1. Verify that electrical power is available to the unit. 2. Verify that any remote stop/start device connected to the unit controller is requesting the unit to start. Confirm the compressor is operating within tolerance. While performing the check, use the startup form to record observations of amps and refrigerant pressures. When all is running properly, place the controller in the Run mode and observe the system until it reaches a steady state of operation. Compressors All compressors are equipped with crankcase heaters, which should be energized at least 24 hours prior to cooling operation of the compressor. 3-PHASE ROTATION Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. Condenser fan motors should all be checked by a qualified service technician at startup and any wiring alteration should only be made at the unit power connection. CAUTION COMPRESSOR ROTATION Scroll compressors are directional and will be damaged by operation in the wrong direction. Low pressure switches on compressors have been disconnected after factory testing. Rotation should be checked by a qualified service technician at startup using suction and discharge pressure gauges and any wiring alteration should only be made at the unit power connection. CAUTION ELECTRIC SHOCK Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts. WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Startup and service must be performed by a Factory Trained Service Technician. WARNING

Charging Refrigerant & Adjusting

Refrigerant Charge The unit comes with full charge based on a 25 foot line set. Charging a system in the field must be based on determination of liquid sub-cooling and evaporator superheat. On a system with a TXV, liquid sub-cooling is more representative of the charge than evaporator superheat but both measurements must be taken. Before Charging Refer to the Unit Nameplate to determine which refrigerant must be used to charge the system. Unit being charged must be at or near full load conditions before adjusting the charge. Units equipped with hot gas bypass must have the hot gas bypass valve closed to get the proper charge. Units equipped with hot gas reheat must be charged with the hot gas valves closed while the unit is in cooling mode. After charging, unit should be operated in reheat (dehumidification) mode to check for correct operation. Units equipped with heat pump options should be charged in heating mode to get the proper charge. After charging, unit should be operated in cooling mode to check for correct charge. Charge may need to be adjusted for cooling mode. If adjustments are made in the cooling mode, heating mode must be rerun to verify proper operation. After adding or removing charge the system must be allowed to stabilize, typically 10-15 minutes, before making any other adjustments. The type of unit and options determine the ranges for liquid sub-cooling and evaporator superheat. Refer to the table of acceptable refrigerant circuit values when determining the proper sub-cooling. Checking Liquid Sub-cooling Measure the temperature of the liquid line as it leaves the condenser coil. Read the gauge pressure reading of the liquid line close to the point where the temperature was taken. You must use liquid line pressure as it will vary from discharge pressure due to condenser coil pressure drop. Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart or Table 5 below. CLEAN AIR ACT The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for non-compliance. CAUTION COMPRESSOR LUBRICANT Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants used in hydrofluorocarbon (HFC) refrigeration systems. Refer to the compressor label for the proper compressor lubricant type. CAUTION

temperature from the saturated temperature

to determine the liquid sub-cooling. Compare calculated sub-cooling to Table 3 below for the appropriate unit type and options. Checking Evaporator Superheat Measure the temperature of the suction line close to the compressor. Read gauge pressure at the suction line close to the compressor. Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart. Subtract the saturated temperature from the measured suction line temperature to determine the evaporator superheat. Compare calculated superheat to Table 3 below for the appropriate unit type and options. Table 3 - Acceptable Refrigeration Circuit Values Air-Cooled Cond./Air-Source Heat Pump Sub-Cooling** 12-18°F / 2-4°F (HP)* Sub-Cooling with Hot Gas Reheat** 15-22°F / 2-6°F (HP)* Superheat*** 8-15°F *In cooling mode operation **Sub-cooling must be increased by 2°F per 20 feet of vertical liquid line rise for R-410A ***Superheat will increase with long suction line runs. Adjusting Sub-cooling and Superheat Temperatures The system is overcharged if the sub-cooling temperature is too high and the evaporator is fully loaded (low loads on the evaporator result in increased sub-cooling) and the evaporator superheat is within the temperature range as shown in Table 3 (high superheat results in increased sub-cooling) Correct an overcharged system by reducing the amount of refrigerant in the system to lower the sub-cooling. The system is undercharged if the superheat is too high and the sub-cooling is too low Correct an undercharged system by adding refrigerant to the system to reduce superheat and raise sub-cooling. If the sub-cooling is correct and the superheat is too high, the TXV may need adjustment to correct the superheat. Special Low Ambient Option Charging Instructions For units equipped with low ambient control (LAC) refrigerant flood back option being charged when the ambient temperature is warm: Once enough charge has been added to get the evaporator superheat and sub-cooling values to the correct setting, more charge must be added. Add approximately 80% of the receiver tank volume to the charge to help fill the receiver tank. The additional charge is required for the system when running in cold ambient conditions. DO NOT OVERCHARGE! Refrigerant overcharging leads to excess refrigerant in the condenser coils resulting in elevated compressor discharge pressure. CAUTION

For units equipped with low ambient

refrigerant flood back option being charged when the ambient temperature is cold: Once enough charge has been added to get the evaporator superheat and sub-cooling values to the correct setting, more charge may need to be added. If the ambient temperature is 0°F no more charge is required. If the ambient temperature is around 40°F add approximately 40% of the receiver tank volume. The unit will have to be checked for proper operation once the ambient temperature is above 80°F. Air Flow Table 4 - Performance Testing Air Flow Setpoints Model Cooling Stage 2 (cfm) Cooling Stage 1 (cfm) Heating Stage 2 (cfm) Heating Stage 1 (cfm) CB-B-024-*-*-1 885 663.75 885 796.5 CB-B-036-*-*-1 1250 937.5 1250 1125 CB-B-048-*-*-1 1500 1125 1500 1350 CB-B-060-*-*-1 1545 1158.75 1545 1390.5 Before completing startup and leaving the unit a complete operating cycle should be observed to verify that all components are functioning properly. CAUTION

Table 5 - R-410A Refrigerant Temperature-Pressure Chart

°F PSIG °F PSIG °F PSIG °F PSIG °F PSIG 20 78.3 47 134.7 74 213.7 101 321.0 128 463.2 21 80.0 48 137.2 75 217.1 102 325.6 129 469.3 22 81.8 49 139.7 76 220.6 103 330.2 130 475.4 23 83.6 50 142.2 77 224.1 104 334.9 131 481.6 24 85.4 51 144.8 78 227.7 105 339.6 132 487.8 25 87.2 52 147.4 79 231.3 106 344.4 133 494.1 26 89.1 53 150.1 80 234.9 107 349.3 134 500.5 27 91.0 54 152.8 81 238.6 108 354.2 135 506.9 28 92.9 55 155.5 82 242.3 109 359.1 136 513.4 29 94.9 56 158.2 83 246.0 110 364.1 137 520.0 30 96.8 57 161.0 84 249.8 111 369.1 138 526.6 31 98.8 58 163.8 85 253.7 112 374.2 139 533.3 32 100.9 59 166.7 86 257.5 113 379.4 140 540.1 33 102.9 60 169.6 87 261.4 114 384.6 141 547.0 34 105.0 61 172.5 88 265.4 115 389.9 142 553.9 35 107.1 62 175.4 89 269.4 116 395.2 143 560.9 36 109.2 63 178.4 90 273.5 117 400.5 144 567.9 37 111.4 64 181.5 91 277.6 118 405.9 145 575.1 38 113.6 65 184.5 92 281.7 119 411.4 146 582.3 39 115.8 66 187.6 93 285.9 120 416.9 147 589.6 40 118.1 67 190.7 94 290.1 121 422.5 148 596.9 41 120.3 68 193.9 95 294.4 122 428.2 149 604.4 42 122.7 69 197.1 96 298.7 123 433.9 150 611.9 43 125.0 70 200.4 97 303.0 124 439.6 44 127.4 71 203.6 98 307.5 125 445.4 45 129.8 72 207.0 99 311.9 126 451.3 46 132.2 73 210.3 100 316.4 127 457.3

Unit operations should be controlled with

thermostat, or unit controller, never at the main power supply, except for emergency, servicing, or complete shutdown of the unit. Thermostat Operation Heating Thermostat system switch - "Heat" Thermostat fan switch - "Auto" or "On" Thermostat temperature set to desired point. Cooling Thermostat system switch - "Cool" Thermostat fan switch - "Auto" or "On" Thermostat temperature set to desired point. Air Circulation Thermostat system switch - "Off" Thermostat fan switch - "Auto" or "On" No change of the thermostat temperature. With these settings, the air handler’s supply fan will run continuously but the supply air will not be heated, cooled, or dehumidified. System Off Thermostat system switch - "Off" Thermostat fan switch - "Auto" No change of the thermostat temperature. With these settings, the system is shut down, with the exception of the control system power (24 VAC), and the crankcase heaters (about 60 watts/compressor). Night and Weekend Unoccupied Operation To reduce the operating time of the unit when the space is unoccupied, such as nights and weekends, it is recommended that the temperature setting be raised about 5°F while unoccupied during the cooling season and lowered about 10°F during the heating season. Compressor The compressors must be off for a minimum of 5 minutes and on for a minimum of 5 minutes. Short cycling of the compressors can causes undue stress and wear. Variable Capacity Compressor Controller Units with variable capacity scroll compressors may include variable capacity compressor controller. The following is an explanation of the terminals and troubleshooting of the alert flash codes on the controller. For more information on the compressor controller, see Emerson Climate Bulletin AE8-1328. COMPRESSOR CYCLING 5 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle off for a minimum of 5 minutes. 5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must cycle on for a minimum of 5 minutes. The cycle rate must not exceed 6 starts per hour. WARNING

Figure 7 - Variable Capacity Compressor

Controller Low Voltage Terminals 24COM Module Common 24VAC Module Power C1 & C2 Demand Input P1 Pressure Common P2 Pressure Input P3 Pressure Power 5VDC P4 Pressure Shield P5 & P6 Pressure Output T1 & T2 Discharge Temperature Sensor High Voltage Terminals A1 & A2 Alarm Relay Out M1 & M2 Contactor L1 Control Voltage N L2 Control Voltage L U1 & U2 Digital Unloader Solenoid V1 & V2 Vapor Injection Solenoid The compressor controller modulates the compressor unloader solenoid in an on/off pattern according the capacity demand signal of the system. The following table shows the linear relationship between the demand signal and compressor capacity modulation. The compressor controller also protects the compressor against high discharge temperature. Refer to Table 7 for the relationship between thermistor temperature readings and resistance values. Table 6 - Demand Signal vs. Compressor Capacity Modulation Demand Signal (VDC) Loaded % Unloaded % Time Loaded Time Unloaded % Compressor Capacity 1.00 Off Off Off Off 0% 1.44 10% 90% 1.5 sec 13.5 sec 10% 3.00 50% 50% 7.5 sec 7.5 sec 50% 4.20 80% 20% 12 sec 3 sec 80% 5.00 100% 0% 15 sec 0 sec 100% To avoid damaging the compressor controller, DO NOT connect wires to terminals C3, C4, T3, T4, T5, or T6. WARNING

Figure 8 - Compressor Controller Flash Code Details

Table 7 - Thermistor Temperature vs. Resistance Values °C °F kΩ °C °F kΩ -40 -40 2889.60 75 167 12.73 -35 -31 2087.22 80 176 10.79 -30 -22 1522.20 85 185 9.20 -25 -13 1121.44 90 194 7.87 -20 -4 834.72 95 203 6.77 -15 5 627.28 100 212 5.85 -10 14 475.74 105 221 5.09 -5 23 363.99 110 230 4.45 0 32 280.82 115 239 3.87 5 41 218.41 120 248 3.35 10 50 171.17 125 257 2.92 15 59 135.14 130 266 2.58 20 68 107.44 135 275 2.28 25 77 86.00 140 284 2.02 30 86 69.28 145 293 1.80 35 95 56.16 150 302 1.59 40 104 45.81 155 311 1.39 45 113 37.58 160 320 1.25 50 122 30.99 165 329 1.12 55 131 25.68 170 338 1.01 60 140 21.40 175 347 0.92 65 149 17.91 180 356 0.83 70 158 15.07

Low Ambient Operation

During low ambient temperatures, the vapor refrigerant will migrate to the cold part of the system (condenser) and condense into liquid. All CB Series compressors are provided with factory installed crankcase heaters to help prevent liquid refrigerant from slugging the compressors during startup in low ambient conditions. The condenser or condensing unit must have continuous power 24 hours prior to startup. This ensures the compressor will receive sufficient refrigerant vapor at startup. Standard units can operate down to 55°F ambient temperature. AAON head pressure control units can operate down to 35°F ambient temperature. Two different head pressure control options available are adjustable fan cycling or ECM condenser fan. See detailed information following. The AAON low ambient (condenser flood- back) system is used to operate a refrigerant system down to 0°F outside air temperature. See detailed information below. Fan Cycling Low Ambient Adjustable fan cycling is a low ambient head pressure control option that cycles the condenser fans to maintain refrigerant circuit head pressures at acceptable levels during cooling operation. The head pressure set point (100-470 psi) and pressure differential (35-200 psi) can be field adjusted using a flathead screwdriver. For example, if the head pressure is set to 300psi, and the differential is set to 100psi, then fans will cut in at 300psi and cut out at 200psi. Fan cycling and variable speed condenser fan head pressure control options allow mechanical cooling with ambient temperatures down to 35°F. Figure 9 - Adjustable Fan Cycling Switch Variable Speed Low Ambient Variable speed condenser fan head pressure control is a low ambient head pressure control option that sends to an electronically commutated motor a variable signal in relation to the refrigerant circuit head pressure of the system. The motor either speeds up or slows down air flow accordingly in order to maintain constant head pressure. Fan cycling and variable speed condenser fan head pressure control options allow mechanical cooling with ambient temperatures down to 35°F. Flooded Condenser Low Ambient Flooded Condenser low ambient control maintains normal head pressure during periods of low ambient. When the ambient temperature drops, the condensing temperature and therefore pressure drops. Without ambient control, the system would shut down on low discharge pressure. The flooded condenser method of low ambient control fills the condenser with liquid refrigerant, decreasing the heat transfer capacity of the coil, which allows the coil to operate at an acceptable discharge pressure. The condenser coil will not be flooded during summer ambient temperatures, so a receiver is included to store the additional liquid refrigerant required to flood the condenser in low ambient.

The low ambient system maintains normal

head pressure during periods of low ambient by restricting liquid flow from the condenser to the receiver, and at the same time bypassing hot gas around the condenser to the inlet of the receiver. This reduces liquid refrigerant flow from the condenser, reducing its effective surface area, which in turn increases the condensing pressure. At the same time the bypassed hot gas raises liquid pressure in the receiver, allowing the system to operate properly. CF Series condensers and condensing units use an LAC valve for low ambient operation. LAC Valve The Low Ambient Control (LAC) valve is a non-adjustable three way valve that modulates to maintain receiver pressure. As the receiver pressure drops below the valve setting (295 psig for R-410A), the valve modulates to bypass discharge gas around the condenser. The discharge gas warms the liquid in the receiver and raises the pressure to the valve setting. The following schematic shows an example system using the LAC valve. Figure 10 - Piping Schematic of Example System using the LAC Valve

In order to maintain head pressure in the

refrigeration system, liquid refrigerant is kept in the condenser to reduce condenser surface. The following chart shows the percentage that a condenser must be flooded in order to function properly at the given ambient temperature. During higher ambient temperatures the entire condenser is required to condense refrigerant. During these higher ambient temperatures, a receiver tank is used to contain the refrigerant that was required to flood the condenser during low ambient operation. The receiver is factory-sized to contain all of the flooded volume. Without a receiver there would be high head pressures during higher ambient conditions. Table 8 - Condenser Flooding PERCENTAGE OF CONDENSER TO BE FLOODED Ambient Temperature (°F) Evaporating Temperature (°F) 0° 10° 20° 30° 35° 40° 45° 50° 70° 40 24 0 0 0 0 0 0 0° 60 47 33 17 26 20 10 4 50° 70 60 50 38 45 40 33 28 40° 76 68 60 50 56 52 46 42 30° 80 73 66 59 64 60 55 51 20° 86 77 72 65 69 66 62 59 0° 87 83 78 73 76 73 70 68 Compressor Lockouts Some units include adjustable compressor lockouts. The compressor lockout in the picture below can be set to any temperature between -10°F and 70°F. The ambient temperature sensor hangs right outside the unit with a cover. Figure 11 - Adjustable compressor lockout Heat pump units include a non-adjustable compressor lockout for the cooling mode set to 55°F, and an adjustable compressor lockout for the heating mode that can be set between 20°F to 95°F. If a heat pump is selected with the compressor lockout feature, the adjustable compressor lockout will change to the -10°F to 70°F range.

(See back of the manual for maintenance

log.) At least once each year, a qualified service technician should check out the unit. This includes reading and recording suction pressures and checking for normal sub- cooling and superheat. Only trained and qualified service technicians experienced in both condensing units and air conditioning are permitted to service the CB Series units to keep warranties in effect. Coils The condenser coils should be inspected yearly to ensure unrestricted airflow. If the coils contain a large amount of airborne dust or other material, they should be cleaned. Care must be taken to prevent bending of the aluminum fins on the coils. Before attempting to clean the coils; set thermostat to the "OFF" position; turn the electrical power to the unit to the "OFF" position at the disconnect switch. The condenser coil can be cleaned by washing from the inside out with water and a coil cleaner. If coil is extremely dirty with clogged fins, a service professional specializing in coil cleaning should be called. E-Coated Coil Cleaning Documented routine cleaning of e-coated coils is required to maintain coating warranty coverage. Surface loaded fibers or dirt should be removed prior to water rinse to prevent restriction of airflow. If unable to back wash the side of the coil opposite of the coils entering air side, then surface loaded fibers or dirt should be removed with a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic bristle brush may be used. In either case, the tool should be applied in the direction of the fins. Coil surfaces can be easily damaged (fin edges bent over) if the tool is applied across the fins. Use of a water stream, such as a garden hose, against a surface loaded coil will drive the fibers and dirt into the coil. This will make cleaning efforts more difficult. Surface loaded fibers must be completely removed prior to using low velocity clean water rinse. A monthly clean water rinse is recommended for coils that are applied in coastal or industrial environments to help to remove chlorides, dirt, and debris. It is very important when rinsing, that water temperature is less than 130°F and pressure is than 100 psig to avoid damaging the fin edges. An elevated water temperature (not to exceed 130°F) will reduce surface tension, increasing the ability to remove chlorides and dirt. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a trained, qualified installer. WARNING Electric shock hazard. Shut off all electrical power to the unit to avoid shock hazard or injury from rotating parts. WARNING

Quarterly cleaning is essential to extend

the life of an e-coated coil and is required to maintain coating warranty coverage. Coil cleaning shall be part of the unit’s regularly scheduled maintenance procedures. Failure to clean an e-coated coil will void the warranty and may result in reduced efficiency and durability. For routine quarterly cleaning, first clean the coil with the below approved coil cleaner. After cleaning the coils with the approved cleaning agent, use the approved chloride remover to remove soluble salts and revitalize the unit. Recommended Coil Cleaner The following cleaning agent, assuming it is used in accordance with the manufacturer’s directions on the container for proper mixing and cleaning, has been approved for use on e-coated coils to remove mold, mildew, dust, soot, greasy residue, lint, and other particulate: Enviro-Coil Concentrate, Part Number H- EC01. Recommended Chloride Remover CHLOR*RID DTS™ should be used to remove soluble salts from the e-coated coil, but the directions must be followed closely. This product is not intended for use as a degreaser. Any grease or oil film should first be removed with the approved cleaning agent. Remove Barrier - Soluble salts adhere themselves to the substrate. For the effective use of this product, the product must be able to come in contact with the salts. These salts may be beneath any soils, grease or dirt; therefore, these barriers must be removed prior to application of this product. As in all surface preparation, the best work yields the best results. Apply CHLOR*RID DTS - Apply directly onto the substrate. Sufficient product must be applied uniformly across the substrate to thoroughly wet out surface, with no areas missed. This may be accomplished by use of a pump-up sprayer or conventional spray gun. The method does not matter, as long as the entire area to be cleaned is wetted. After the substrate has been thoroughly wetted, the salts will be soluble and is now only necessary to rinse them off. Rinse - It is highly recommended that a hose be used, as a pressure washer will damage the fins. The water to be used for the rinse is recommended to be of potable quality, though a lesser quality of water may be used if a small amount of CHLOR*RID DTS is added. Check with CHLOR*RID High velocity water from a pressure washer or compressed air should only be used at a very low pressure to prevent fin and/or coil damages. The force of the water or air jet may bend the fin edges and increase airside pressure drop. Reduced unit performance or nuisance unit shutdowns may occur. CAUTION Harsh chemicals, household bleach, or acid cleaners should not be used to clean outdoor or indoor e-coated coils. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion and attack the e-coating. If there is dirt below the surface of the coil, use the recommended coil cleaners. CAUTION

International, Inc. for recommendations on

lesser quality rinse water. DX Cooling Set unit controls to cooling mode of operation with supply fans on. Check compressor operation, rotation, amperage and voltage to the unit nameplate (check the amperage on the load side of the compressor contactor). The scroll compressors are fully hermetic and require no maintenance except for keeping the shell clean. Refrigerant circuit includes factory provided and field installed line filter drier. The unit does not include a liquid line solenoid valve. This must be field furnished and installed if required by job conditions. Condenser Fan Motor All original motors and bearings are furnished with factory lubrication. They require no lubrication. The electrically commutated condenser fan motor (ECM) is factory preprogrammed and requires no maintenance. Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative. Reference the unit serial number and part number when ordering parts. AAON – Longview Warranty, Service, and Parts Department 203 Gum Springs Rd. Longview, TX 75602 Ph: 903-236-4403 Fax: 903-247-9219 www.aaon.com Note: Before calling, technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit.

CB Series Startup Form

Date:______________ Job Name:_____________________________________________________________________ Address:______________________________________________________________________ Model Number:_________________________________________________________________ ______________________________________________________________________________ Serial Number:_____________________________________________ Tag:_______________ Startup Contractor:______________________________________________________________ Address:__________________________________________________ _________________________________________________________ Phone:_____________ Pre Startup Checklist Installing contractor should verify the following items. 1. Is there any visible shipping damage? Yes No 2. Is the unit level? Yes No 3. Are the unit clearances adequate for service and operation? Yes No 4. Do all access doors open freely and are the handles operational? Yes No 5. Have all shipping braces been removed? Yes No 6. Have all electrical connections been tested for tightness? Yes No 7. Does the electrical service correspond to the unit nameplate? Yes No 8. On 208/230V units, has transformer tap been checked? Yes No 9. Has overcurrent protection been installed to match the unit nameplate requirement? Yes No 10. Have all set screws on the fans been tightened? Yes No 11. Do all fans and pumps rotate freely? Yes No 12. Is all copper tubing isolated so that it does not rub? Yes No Ambient Temperature Ambient Dry Bulb Temperature ________°F Ambient Wet Bulb Temperature ________°F Refrigeration System 1 - Cooling Mode Pressure Saturated Temperature Line Temperature Sub-cooling Superheat Discharge Suction Liquid

Refrigeration System 1 - Heating Mode (Heat Pump Only)

Pressure Saturated Temperature Line Temperature Sub-cooling Superheat Discharge Suction Liquid Air-Cooled Condenser Fan Alignment_____ Check Rotation_____ Nameplate Amps________ Number hp L1 L2 L3 1

This log must be kept with the unit. It is the responsibility of the owner and/or

maintenance/service contractor to document any service, repair or adjustments. AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts. The responsibility for proper start-up, maintenance and servicing of the equipment falls to the owner and qualified licensed technician. Entry Date Action Taken Name/Tel.

Literature Change History

November 2009 Update of manual formatting to match with other IOMs and adding variable capacity scroll compressor information. April 2012 Added oil drip note below piping diagrams. Updated the Startup Form. May 2012 Updated the Table of Contents. March 2013 Update of the manual revising Table S1 - Sub-Cooling and Superheat, adding Table S2 - Performance Testing Air Flow Setpoints, adding information about compressor cycling. June 2013 Updated piping diagrams to show internal modulating hot gas reheat and hot gas bypass valves. New part number assigned. July 2014 Updated service clearance drawing. February 2015 Updated Feature 5 options to reflect standard exterior corrosion protection. July 2015 Updated Replacement Parts instructions. Added Features and Options section. August 2016 Added Storage information. Added guidelines for variable capacity compressors in the line sizing section. Added double riser schematics and discussion for heat pump operation. Added a section about oil level under the refrigerant line sizing section. Added a section on compressor lockouts. Included heat pump charging guidelines in the Acceptable Refrigeration Circuit Values Table. Added Special Low Ambient Option Charging Instructions. Changed e-coated coil cleaning to100 psi water pressure. December 2016 Fixed a reference error.

203 Gum Springs Rd.

Longview, TX 75602-1721 Phone: 903-236-4403 Fax: 903-236-4463 www.aaon.com CB Series Installation, Operation & Maintenance R57611 · Rev. A · 161221 (ACP J00187) It is the intent of AAON to provide accurate and current product information. However, in the interest of product improvement, AAON reserves the right to change pricing, specifications, and/or design of its product without notice, obligation, or liability. Copyright © AAON, all rights reserved throughout the world. AAON® and AAONAIRE® are registered trademarks of AAON, Inc., Tulsa, OK.