DSE 335 Operator's Manual
Read Online
Read the DSE 335 Operator's Manual online using the built-in PDF viewer.
Text of the manual
057-233 ISSUE: 1
DEEP SEA ELECTRONICS PLC
DSE335 Operator Manual
(Applicable to module version 4.2 and upwards)
Document Number: 057-233
Author: Fady Atallah
DSE335 Operator Manual
057-233 ISSUE: 1
Page 2 of 90
DEEP SEA ELECTRONICS PLC
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND
Sales Tel: +44 (0) 1723 890099
Sales Fax: +44 (0) 1723 893303
E-mail: [email protected]
Website: www.deepseaplc.com
DSE335 Operator Manual
© Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents
Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
must be addressed to Deep Sea Electronics Plc at the address above.
The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.
Amendments List
Issue
Comments
Minimum Module
Version Required
Minimum
Configuration Suite
Version Required
1
Initial release
V4.2.22
2014.101 V1.212.3
Typeface: The typeface used in this document is Arial. Care must be taken not to mistake the upper
case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.
Clarification of notation used within this publication.
NOTE
Highlights an essential element of a procedure to ensure correctness.
CAUTION!
Indicates a procedure or practice, which, if not strictly observed, results in
damage or destruction of equipment.
WARNING!
Indicates a procedure or practice, which results in injury to personnel or
loss of life if not followed correctly.
DSE335 Operator Manual
Page 3 of 90
057-233 ISSUE: 1
TABLE OF CONTENTS
SECTION
PAGE
1
INTRODUCTION .................................................................................................. 6
1.1
BIBLIOGRAPHY ................................................................................................................. 7
1.1.1
INSTALLATION INSTRUCTIONS ................................................................................. 7
1.1.2
TRAINING GUIDES ...................................................................................................... 7
1.1.3
MANUALS .................................................................................................................... 7
1.1.4
THIRD PARTY DOCUMENTS ...................................................................................... 7
2
SPECIFICATIONS ............................................................................................... 8
2.1
SHORT NAMES .................................................................................................................. 8
2.2
REQUIREMENTS FOR UL CERTIFICATION ...................................................................... 8
2.3
TERMINAL SPECIFICATION .............................................................................................. 9
2.4
POWER SUPPLY REQUIREMENTS................................................................................... 9
2.4.1
MODULE SUPPLY INSTRUMENTATION DISPLAY ..................................................... 9
2.5
S1 & S2 VOLTAGE / FREQUENCY SENSING................................................................. 10
2.6
GENERATOR CURRENT SENSING ................................................................................. 10
2.6.1
V A RATING OF THE CTS ......................................................................................... 11
2.6.2
CT POLARITY ............................................................................................................ 12
2.6.3
CT PHASING ............................................................................................................. 12
2.6.4
CT CLASS.................................................................................................................. 12
2.7
INPUTS ............................................................................................................................. 13
2.7.1
DIGITAL INPUTS ....................................................................................................... 13
2.8
OUTPUTS ......................................................................................................................... 13
2.8.1
CONFIGURABLE OUTPUTS A & E ............................................................................ 13
2.8.2
CONFIGURABLE OUTPUTS B & F ............................................................................ 13
2.8.3
CONFIGURABLE OUTPUTS B & F ............................................................................ 13
2.8.4
CONFIGURABLE OUTPUTS G, H, I, J, K & L............................................................. 13
2.9
COMMUNICATION PORTS .............................................................................................. 14
2.9.1
COMMUNICATION PORT USAGE ............................................................................ 15
2.9.1.1
USB CONNECTION ............................................................................................ 15
2.9.1.2
RS232 ................................................................................................................. 16
2.9.1.3
RECOMMENDED PC RS232 SERIAL PORT ADD-ONS ..................................... 16
2.9.1.4
RECOMMENDED EXTERNAL MODEMS ............................................................ 17
2.9.1.5
RS485 ................................................................................................................. 18
2.9.1.6
RECOMMENDED PC RS485 SERIAL PORT ADD-ONS ..................................... 18
2.9.2
DSENET® FOR EXPANSION MODULES ................................................................. 19
2.10
ADDING AN EXTERNAL SOUNDER TO THE APPLICATION ...................................... 19
2.11
DIMENSIONS AND MOUNTING .................................................................................... 20
2.11.1
DIMENSIONS............................................................................................................. 20
2.11.2
PANEL CUTOUT ........................................................................................................ 20
2.11.3
WEIGHT ..................................................................................................................... 20
2.11.4
FIXING CLIPS ............................................................................................................ 21
2.11.5
CABLE TIE FIXING POINTS ...................................................................................... 22
2.11.6
SILICON SEALING GASKET ...................................................................................... 22
2.11.8
APPLICABLE STANDARDS ....................................................................................... 23
2.11.9
ENCLOSURE CLASSIFICATIONS ............................................................................. 25
2.11.9.1
IP CLASSIFICATIONS......................................................................................... 25
2.11.9.2
NEMA CLASSIFICATIONS .................................................................................. 26
3
INSTALLATION ................................................................................................. 27
3.1
TERMINAL DESCRIPTION ............................................................................................... 27
3.1.1
DC SUPPLY, OUTPUTS G-L ...................................................................................... 28
3.1.2
CONFIGURABLE DIGITAL INPUTS A-I ...................................................................... 28
3.1.3
CONFIGURABLE DIGITAL INPUTS J-L, DSENET ..................................................... 29
3.1.4
CONFIGURABLE VOLT-FREE OUTPUTS E & F........................................................ 29
3.1.5
LOAD SWITCHING AND S2 VOLTAGE SENSING ..................................................... 29
3.1.6
S1 VOLTAGE SENSING ............................................................................................ 30
DSE335 Operator Manual
057-233 ISSUE: 1
Page 4 of 90
3.1.7
LOAD CURRENT TRANSFORMERS ......................................................................... 30
3.1.7.1
CONNECTION TO TERMINALS 45 & 46/47 ........................................................ 31
3.1.7.2
CT CONNECTIONS ............................................................................................ 31
3.1.8
CONFIGURABLE VOLT-FREE CHANGEOVER OUTPUTS C & D ............................. 32
3.1.9
PC CONFIGURATION INTERFACE CONNECTOR .................................................... 32
3.1.10
RS485 CONNECTOR ................................................................................................. 33
3.1.11
RS232 CONNECTOR ................................................................................................. 33
3.2
TYPICAL WIRING DIAGRAM ........................................................................................... 34
3.2.1
DSE335 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION ....... 35
3.3
ALTERNATIVE TOPOLOGIES ......................................................................................... 36
3.3.1
3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION .................................... 36
3.3.2
SINGLE PHASE WITH RESTRICTED EARTH FAULT ............................................... 37
3.3.3
SINGLE PHASE WITHOUT EARTH FAULT ............................................................... 37
3.3.4
2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT .............................. 38
3.3.5
2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT .............................................. 38
3.3.6
2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT .............................. 39
3.3.7
2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING ........................ 40
3.3.8
3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING .................. 41
3.4
EARTH SYSTEMS ............................................................................................................ 42
3.4.1
NEGATIVE EARTH .................................................................................................... 42
3.4.2
POSITIVE EARTH ...................................................................................................... 42
3.4.3
FLOATING EARTH .................................................................................................... 42
3.5
TYPICAL ARRANGEMENT OF DSENET® ....................................................................... 42
4
DESCRIPTION OF CONTROLS ........................................................................ 43
4.1
CONTROL PUSH-BUTTONS ............................................................................................ 45
4.2
VIEWING THE INSTRUMENT PAGES .............................................................................. 47
4.2.1
STATUS ..................................................................................................................... 48
4.2.2
S1 .............................................................................................................................. 49
4.2.3
S2 .............................................................................................................................. 49
4.2.4
MODULE .................................................................................................................... 49
4.2.5
EXPANSION .............................................................................................................. 50
4.2.6
ALARMS .................................................................................................................... 50
4.2.7
EVENT LOG ............................................................................................................... 50
4.2.8
SERIAL PORT ............................................................................................................ 51
4.2.8.1
RS232 SERIAL PORT ......................................................................................... 51
4.2.8.2
RS485 SERIAL PORT ......................................................................................... 55
4.2.9
SCHEDULER ............................................................................................................. 56
4.2.10
ABOUT....................................................................................................................... 56
4.3
VIEWING LATEST TRANSFER INFORMATION PAGE .................................................... 57
4.4
USER CONFIGURABLE INDICATORS ............................................................................ 58
4.5
OPERATION ..................................................................................................................... 59
4.6
QUICKSTART GUIDE ....................................................................................................... 59
4.6.1
STARTING S2 ............................................................................................................ 59
4.6.2
STOPPING S2 ........................................................................................................... 60
4.7
STOP/RESET ................................................................................................................... 61
4.8
MANUAL MODE ............................................................................................................... 62
4.8.1
STARTING SEQUENCE............................................................................................. 62
4.8.2
S2 AVAILABLE ........................................................................................................... 62
4.8.3
STOPPING SEQUENCE ............................................................................................ 63
4.9
AUTOMATIC MODE ......................................................................................................... 64
4.9.1
WAITING IN AUTO MODE ......................................................................................... 64
4.9.2
STARTING SEQUENCE............................................................................................. 64
4.9.3
S2 AVAILABLE ........................................................................................................... 65
4.9.4
STOPPING SEQUENCE ............................................................................................ 65
4.10
MODE SELECTION ....................................................................................................... 66
4.10.1
TEST ON LOAD ......................................................................................................... 66
4.10.1.1
STARTING SEQUENCE ...................................................................................... 66
4.10.1.2
S2 AVAILABLE .................................................................................................... 66
4.10.1.3
STOPPING SEQUENCE ..................................................................................... 66
DSE335 Operator Manual
Page 5 of 90
057-233 ISSUE: 1
4.10.2
TEST OFF LOAD ....................................................................................................... 67
4.10.2.1
STARTING SEQUENCE ...................................................................................... 67
4.10.2.2
S2 AVAILABLE .................................................................................................... 67
4.10.2.3
STOPPING SEQUENCE ..................................................................................... 67
4.10.3
PROHIBIT RETURN ................................................................................................... 68
4.10.3.1
WAITING IN PROHIBIT RETURN........................................................................ 68
4.10.3.2
STARTING SEQUENCE ...................................................................................... 68
4.10.3.3
S2 AVAILABLE .................................................................................................... 69
4.10.3.4
STOPPING SEQUENCE ..................................................................................... 69
4.11
SCHEDULER ................................................................................................................ 70
4.11.1
STOP MODE .............................................................................................................. 70
4.11.2
MANUAL MODE ......................................................................................................... 70
4.11.3
AUTO MODE.............................................................................................................. 70
4.12
LOAD SHEDDING CONTROL ....................................................................................... 71
4.12.1
LOAD SHEDDING CONTROL .................................................................................... 71
5
PROTECTIONS.................................................................................................. 72
5.1
INDICATIONS ................................................................................................................... 73
5.2
WARNINGS ...................................................................................................................... 74
5.3
ELECTRICAL TRIPS ........................................................................................................ 75
6
FRONT PANEL CONFIGURATION ................................................................... 76
6.1
ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR ............................. 77
6.1.1
EDITING A PARAMETER ........................................................................................... 78
6.2
ADJUSTABLE PARAMETERS ......................................................................................... 79
7
COMMISSIONING.............................................................................................. 82
8
FAULT FINDING ................................................................................................ 83
8.1
STARTING ........................................................................................................................ 83
8.2
LOADING ......................................................................................................................... 83
8.3
ALARMS ........................................................................................................................... 83
8.4
COMMUNICATIONS ......................................................................................................... 84
8.5
INSTRUMENTS ................................................................................................................ 84
8.6
MISCELLANEOUS ........................................................................................................... 85
9
MAINTENANCE, SPARES, REPAIR AND SERVICING ................................... 86
9.1
PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE .................................... 86
9.1.1
PACK OF PLUGS....................................................................................................... 86
9.1.2
INDIVIDUAL PLUGS .................................................................................................. 86
9.2
PURCHASING ADDITIONAL FIXING CLIPS FROM DSE ................................................. 86
9.3
PURCHASING ADDITIONAL SEALING GASKET FROM DSE ......................................... 86
9.4
DSENET EXPANSION MODULES .................................................................................... 87
10
WARRANTY ................................................................................................... 88
11
DISPOSAL ...................................................................................................... 88
11.1
WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ............................... 88
057-233 ISSUE: 1
Page 6 of 90
1 INTRODUCTION
This document details the installation and operation requirements of the DSE335 module version 4.2
and later, part of the DSEATS® range of products.
A separate document covers the DSE335 modules with firmware version prior to version 4.2.
The manual forms part of the product and must be kept for the entire life of the product. If the product
is passed or supplied to another party, ensure that this document is passed to them for reference
purposes.
This is not a controlled document. Updates are not automatically informed. Any future updates of this
document are included on the DSE website at www.deepseaplc.com
The module is designed to provide differing levels of functionality across a common platform. This
allows the OEM greater flexibility in the choice of controller to use for a specific application.
The module has been designed to allow the operator to control the transfer of the load from Source 1
(S1) to Source 2 (S2), typically the mains supply and a standby generator either manually (via fascia
mounted push-buttons) or automatically upon S1 failure. Additionally if configured too, the module
automatically starts and stops the generator set (S2) depending upon the status of S1.
The user also has the facility to view the system operating parameters via the LCD display to monitor
the supplies and indicating the operational status and fault conditions of the module.
The powerful ARM microprocessor contained within the module allows for incorporation of a range of
complex features:
•
Text based LCD display (supporting multiple languages)
•
True RMS Voltage, Current and Power monitoring
•
Communications capability (RS485 or RS232)
•
Multiple AC supply monitoring
•
Fully configurable inputs for use as alarms or a range of different functions.
Using a PC and the DSE Configuration Suite software allows alteration of selected operational
sequences, timers, alarms and operational sequences. Additionally, the module’s integral front panel
configuration editor allows adjustment of this information.
A robust plastic case designed for front panel mounting houses the module. Connections are via
locking plug and sockets.
Access to critical operational sequences and timers for use by qualified engineers, can be protected
by a security code. Module access can also be protected by PIN code. Selected parameters can be
changed from the module’s front panel.
The module is housed in a robust plastic case suitable for panel mounting. Connections to the module
are via locking plug and sockets.
Page 7 of 90
057-233 ISSUE: 1
1.1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications are obtained from the
DSE website: www.deepseaplc.com
1.1.1 INSTALLATION INSTRUCTIONS
Installation instructions are supplied with the product in the box and are intended as a ‘quick start’
guide only.
DSE Part
Description
053-135
DSE335 Installation Instructions
053-032
DSE2548 LED Expansion Annunciator Installation Instructions
053-033
DSE2130 Input Expansion Installation Instructions
053-034
DSE2157 Output Expansion Installation Instructions
1.1.2 TRAINING GUIDES
Training Guides are produced to give ‘handout’ sheets on specific subjects during training sessions.
DSE Part
Description
056-005
Using CTs With DSE Products
056-022
Breaker Control
056-024
GSM Modem
056-030
Module PIN Codes
1.1.3 MANUALS
Product manuals are are downloaded from the DSE website: www.deepseaplc.com.
DSE Part
Description
057-237
DSE335 Configuration Suite PC Software Manual
057-082
DSE2130 Input Expansion Manual
057-083
DSE2157 Output Expansion Manual
057-084
DSE2548 Annunciator Expansion Manual
057-158
DSE335 Operators Manual – prior to v4.2
1.1.4 THIRD PARTY DOCUMENTS
The following third party documents are also referred to:
Reference
Description
ISBN 1-55937-879-4
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device
Function Numbers and Contact Designations. Institute of Electrical and
Electronics Engineers Inc
ISBN 0-7506-1147-2
Diesel generator handbook. L.L.J.Mahon
ISBN 0-9625949-3-8
On-Site Power Generation. EGSA Education Committee.
057-233 ISSUE: 1
Page 8 of 90
2 SPECIFICATIONS
2.1 SHORT NAMES
Short Name
Description
DSE3xx
All modules/controllers in the DSEATS range
DSE335
DSE335 module/controller
2.2 REQUIREMENTS FOR UL CERTIFICATION
Description
Specification
Screw Terminal
Tightening Torque
• 4.5 lb-in (0.5 Nm)
Conductors
• Terminals suitable for connection of conductor size 12 AWG to 26 AWG
(0.5 mm² to 2.0 mm²).
• Conductor protection must be provided in accordance with NFPA 70,
Article 240
• Low voltage circuits (35 V or less) must be supplied from the engine
starting battery or an isolated secondary circuit.
• The communication, sensor, and/or battery derived circuit conductors
shall be separated and secured to maintain at least ¼ ” (6 mm) separation
from the generator and mains connected circuit conductors unless all
conductors are rated 600 V or greater.
Current Inputs
• Must be connected through UL Listed or Recognized isolating current
transformers with the secondary rating of 5 A maximum.
Communication
Circuits
• Must be connected to communication circuits of UL Listed equipment
Output Pilot Duty
• 0.5 A
Mounting
• Suitable for use in type 1 Enclosure Type rating with surrounding air
temperature -22 ºF to +158 ºF (-30 ºC to +70 ºC)
• Suitable for pollution degree 3 environments when voltage sensing inputs
do not exceed 300 V. When used to monitor voltages over 300 V, a
device is to be installed in an unventilated or filtered ventilation enclosure
to maintain a pollution degree 2 environment.
Operating
Temperature
• -22 ºF to +158 ºF (-30 ºC to +70 ºC)
Storage Temperature
• -40 ºF to +176 ºF (-40 ºC to +80 ºC)
Page 9 of 90
057-233 ISSUE: 1
2.3 TERMINAL SPECIFICATION
NOTE: For purchasing additional connector plugs from DSE, see the section entitled
Maintenance, Spares, Repair and Servicing elsewhere in this document.
Description
Specification
Connection Type
Two part connector.
•
Male part fitted to
module
•
Female part supplied in
module packing case -
Screw terminal, rising
clamp, no internal
spring.
Example showing cable entry and screw
terminals of a 10 way connector
Minimum Cable Size
0.5 mm² (AWG 24)
Maximum Cable Size
2.5 mm² (AWG 10)
2.4 POWER SUPPLY REQUIREMENTS
Description
Specification
Minimum supply voltage
8V continuous
Cranking dropouts
Able to survive 0V for 50mS providing the supply was at least 10V
before the dropout and recovers to 5V afterwards.
Maximum supply voltage
35V continuous (60V protection)
Reverse polarity protection
-35V continuous
Maximum operating current
360mA at 24V
480mA at 12V
Maximum standby current
96mA at 24V
126mA at 12V
2.4.1 MODULE SUPPLY INSTRUMENTATION DISPLAY
Description
Specification
Range
0 V to 70 V DC
Maximum continuous operating voltage of 35 V DC
Resolution
0.1 V
Accuracy
1% full scale (±0.7 V)
057-233 ISSUE: 1
Page 10 of 90
2.5 S1 & S2 VOLTAGE / FREQUENCY SENSING
Description
Specification
Measurement type
True RMS conversion
Sample Rate
5KHz or better
Harmonics
Up to 10th or better
Input Impedance
300K Ω ph-N
Phase to Neutral
15V (minimum required for sensing frequency) to 333V AC (absolute
maximum)
Suitable for 110V to 277V nominal
(±20% for under/overvoltage detection)
Phase to Phase
26V (minimum required for sensing frequency) to 576V AC (absolute
maximum)
Suitable for 190V ph-ph to 479V ph-ph nominal
(±20% for under/overvoltage detection)
Common mode offset from
Earth
100V AC (max)
Resolution
1V AC phase to neutral
2V AC phase to phase
Accuracy
±1% of full scale phase to neutral
±2% of full scale phase to phase
Minimum frequency
3.5Hz
Maximum frequency
75.0Hz
Frequency resolution
0.1Hz
Frequency accuracy
±0.2Hz
2.6 CURRENT SENSING
Description
Specification
Measurement type
True RMS conversion
Sample Rate
5KHz or better
Harmonics
Up to 10th or better
Nominal CT secondary
rating
5A
Maximum continuous current
5A
Overload Measurement
15A for 100ms
Absolute maximum overload
50A for 1 second
Burden
0.5VA (0.02Ω current shunts)
common mode offset
±2V peak plant ground to CT common terminal
Resolution
25ma
Accuracy
±1% of Nominal (5A) (excluding CT error)
Page 11 of 90
057-233 ISSUE: 1
2.6.1 V A RATING OF THE CTS
NOTE: Details for 4 mm² cables are shown for reference only. The connectors on the DSE
modules are only suitable for cables up to 2.5 mm².
The V A burden of the module on the CTs is 0.5 V A. However depending upon the type and length of
cabling between the CTs and the module, CTs with a greater V A rating than the module are required.
The distance between the CTs and the
measuring module must be calculated
and cross-referenced against the chart
opposite to find the V A burden of the
cable itself.
If the CTs are fitted within the
alternator top box, the star point
(common) of the CTs must be
connected to system ground (earth) as
close as possible to the CTs. This
minimises the length of cable used to
connect the CTs to the DSE module.
Example.
If 1.5 mm² cable is used and the
distance from the CT to the measuring
module is 20 m, then the burden of the
cable alone is approximately 15 V A.
As the burden of the DSE controller is
0.5 V A, then a CT with a rating of at
least 15 + 0.5 V = 15.5 V A must be
used.
If 2.5 mm² cables are used over the
same distance of 20 m, then the
burden of the cable on the CT is
approximately 7 V A. CT’s required in
this instance is at least 7.5 V A
(7 + 0.5).
057-233 ISSUE: 1
Page 12 of 90
2.6.2 CT POLARITY
NOTE: Take care to ensure correct polarity of the CT primary as shown above. If in doubt,
check with the CT supplier.
Take care to ensure the correct polarity of the CTs. Incorrect CT orientation leads to negative kW
readings when the set is supplying power. Take note that paper stick-on labels on CTs that show the
orientation are often incorrectly placed on the CT (!). It is more reliable to use the labelling in the case
moulding as an indicator to orientation (if available).
To test orientation, run the generator in island mode (not in parallel with any other supply) and load
the generator to around 10% of the set rating. Ensure the DSE module shows positive kW for all three
individual phase readings.
TO GENERATOR
TO LIGHTS
POLARITY OF CT PRIMARY
2.6.3 CT PHASING
Take particular care that the CTs are connected to the correct phases. For instance, ensure that the
CT on phase 1 is connected to the terminal on the DSE module intended for connection to the CT for
phase 1.
Additionally ensure that the voltage sensing for phase 1 is actually connected to generator phase 1.
Incorrect connection of the phases as described above results in incorrect power factor (PF)
measurements, which in turn results in incorrect kW measurements.
One way to check for this is to make use of a single-phase load. Place the load on each phase in turn,
run the generator and ensure the kW value appears in the correct phase. For instance if the load is
connected to phase 3, ensure the kW figure appears in phase 3 display and not in the display for
phase 1 or 2.
2.6.4 CT CLASS
Ensure the correct CT type is chosen. For instance if the DSE module is providing overcurrent
protection, ensure the CT is capable of measuring the overload level required to be protected against,
and at the accuracy level required.
For instance, this may mean fitting a protection class CT (P10 type) to maintain high accuracy while
the CT is measuring overload currents.
Conversely, if the DSE module is using the CT for instrumentation only (current protection is disabled
or not fitted to the controller) then measurement class CTs can be used. Again, bear in mind the
accuracy required. The DSE module is accurate to better than 1% of the full-scale current reading. To
maintain this accuracy fit Class 0.5 or Class 1 CTs.
Check with the CT manufacturer for further advice on selecting the CTs.
Labelled as
p1, k or K
Labelled as
p2, l or L
Page 13 of 90
057-233 ISSUE: 1
2.7 INPUTS
2.7.1 DIGITAL INPUTS
Description
Specification
Number
12 Configurable negative or positive switching inputs in banks of 3
through PC Software
Arrangement
Contact between input terminal and the module’s plant supply
negative or positive terminal.
Low level threshold
3.2V minimum
High level threshold
8.1V maximum
Maximum input voltage
+60V DC with respect to module’s plant supply negative terminal
Minimum input voltage
-2V DC with respect to module’s plant supply negative terminal
Contact wetting current
7mA typical
Open circuit voltage
12V typical for negative activation.
0V typical for positive activation.
2.8 OUTPUTS
NOTE: Refer to Breaker Control Training Document (DSE part 056-022) for further details
on configuring and control different type of load switching devices.
There are twelve outputs fitted to the controller
2.8.1 CONFIGURABLE OUTPUTS A & E
Description
Specification
Number
2
Type
Fully configurable normally closed volt-free contacts.
Rating
8A resistive at 250V AC
2.8.2 CONFIGURABLE OUTPUTS B & F
Description
Specification
Number
2
Type
Fully configurable normally open volt-free contacts.
Rating
8A resistive at 250V AC
2.8.3 CONFIGURABLE OUTPUTS B & F
Description
Specification
Number
2
Type
Fully configurable volt-free changeover contacts.
Rating
8A resistive at 250V AC
2.8.4 CONFIGURABLE OUTPUTS G, H, I, J, K & L
Description
Specification
Number
6
Type
Fully configurable, supplied from DC positive terminal 2
Rating
2 A resistive continuous at 35 V
057-233 ISSUE: 1
Page 14 of 90
2.9 COMMUNICATION PORTS
Description
Specification
USB Port
USB2.0 Device for connection to PC running DSE configuration suite only
Max distance 6m (yards)
Serial
Communication
RS232 and RS485 are both fitted but provide independent operation
RS232 Serial
port
Non – Isolated port
Max Baud rate 115200 baud subject to S/W
TX, RX, RTS, CTS, DSR, DTR, DCD
Male 9 way D type connector
Max distance 15m (50 feet)
RS485 Serial
port
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
Max Baud Rate 115200
External termination required (120Ω)
Max common mode offset 70V (on board protection transorb)
Max distance 1.2km (¾ mile)
Page 15 of 90
057-233 ISSUE: 1
2.9.1 COMMUNICATION PORT USAGE
2.9.1.1
USB CONNECTION
NOTE: The DC supply must be connected to the module for configuration by PC.
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Suite PC Software Manual.
The USB port is provided to give a simple means of connection between a PC and the controller.
Using the DSE Configuration Suite Software, the operator is then able to control the module, starting
or stopping the generator, selecting operating modes, etc.
Additionally, the various operating parameters (such as output volts, oil pressure, etc.) of the remote
generator are available to be viewed or changed.
To connect a module to a PC by USB, the following items are required:
•
DSE335 Controller
•
DSE Configuration Suite PC Software
(Supplied on configuration suite software CD or available from
www.deepseaplc.com).
•
USB cable Type A to Type B.
(This is the same cable as often used between a PC and a USB
printer)
DSE stock this cable:
PC Configuration interface lead (USB type A – type B) DSE Part
No 016-125
057-233 ISSUE: 1
Page 16 of 90
2.9.1.2
RS232
The RS232 port on the controller supports the Modbus RTU protocol.
The Gencomm register table for the controller is available upon request from the DSE Technical
Support Department.
RS232 is for short distance communication (max 15m) and is typically used to connect the controller
to a telephone or GSM modem for more remote communications.
Many PCs are not fitted with an internal RS232 serial port. DSE DOES NOT recommend the use of
USB to RS232 convertors but can recommend PC add-ons to provide the computer with an RS232
port.
2.9.1.3
RECOMMENDED PC RS232 SERIAL PORT ADD-ONS
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
•
Brainboxes PM143 PCMCIA RS232 card (for laptop PCs)
•
Brainboxes VX-001 Express Card RS232 (for laptops and nettops PCs)
•
Brainboxes UC246 PCI RS232 card (for desktop PCs)
•
Brainboxes PX-246 PCI Express 1 Port RS232 1 x 9 Pin (for desktop
PCs)
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: [email protected]
NB DSE Have no business tie to Brainboxes. Over many years, our own engineers have used these
products and are happy to recommend them.
Page 17 of 90
057-233 ISSUE: 1
2.9.1.4
RECOMMENDED EXTERNAL MODEMS
NOTE: For GSM modems a SIM card is required, supplied by your GSM network
provider
•
Multitech Global Modem – MultiModem ZBA (PSTN)
DSE Part Number 020-252
(Contact DSE Sales for details of localisation kits for these modems)
•
Sierra Fastrak Xtend GSM modem kit (PSU, Antenna and modem)*
DSE Part number 0830-001-01
•
For SMS only, a ‘normal’ voice SIM card is required. This enables the controller to send SMS
messages to designated mobile phones upon status and alarm conditions.
•
For a data connection to a PC running the DSE Configuration Suite software, a ‘special’ CSD
(Circuit Switched Data) SIM card is required in order for the modem to answer an incoming
data call. Many ‘pay as you go’ services do not provide a CSD (Circuit Switched Data) SIM
card.
057-233 ISSUE: 1
Page 18 of 90
2.9.1.5
RS485
NOTE: For a single module to PC connection and distances up to 6m (8yds) the USB
connection method is more suitable and provides for a lower cost alternative to RS485 (which
is more suited to longer distance connections).
The RS485 port on the series controller supports the Modbus RTU protocol.
The DSE Gencomm register table for the controller is available upon request from the DSE Technical
Support Department.
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices) and
allows for connection to PCs, PLCs and Building Management Systems (to name just a few devices).
One advantage of the RS485 interface is the large distance specification (1.2km when using Belden
9841 (or equivalent) cable. This allows for a large distance between the module and a PC running the
DSE Configuration Suite software. The operator is then able to control the module, selecting operating
modes, etc.
The various operating parameters (such as output volts, currents, etc.) of the remote ATS can be
viewed or changed.
2.9.1.6
RECOMMENDED PC RS485 SERIAL PORT ADD-ONS
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
•
Brainboxes PM154 PCMCIA RS485 card (for laptops PCs)
Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
•
Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and
nettop PCs)
•
Brainboxes UC320 PCI Velocity RS485 card (for desktop PCs)
Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’
•
Brainboxes PX-324 PCI Express 1 Port RS422/485 (for desktop PCs)
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: [email protected]
NB DSE have no business tie to Brainboxes. Over many years,our own engineers have used these
products and are happy to recommend them.
Page 19 of 90
057-233 ISSUE: 1
2.9.2 DSENET® FOR EXPANSION MODULES
NOTE: As a termination resistor is internally fitted to the host controller, the host
controller must be the ‘first’ unit on the DSENet®. A termination resistor MUST be fitted to the
‘last’ unit on the DSENet®. For connection details, you are referred to the section entitled
‘typical wiring diagram’ elsewhere in this document.
DSENet® is the interconnection cable between the host controller and the expansion module(s) and
must not be connect to any device other than DSE equipment designed for connection to the
DSENet®
Description
Specification
Cable type
Two core screened twisted pair
Cable characteristic
impedance
120Ω
Recommended cable
Belden 9841
Belden 9271
Maximum cable length
1200m (¾ mile) when using Belden 9841 or direct equivalent.
600m (666 yds) when using Belden 9271 or direct equivalent.
DSENet® topology
“Daisy Chain” Bus with no stubs (spurs)
DSENet® termination
120Ω. Fitted internally to host controller. Must be fitted externally to the
‘last’ expansion module by the customer.
Maximum expansion
modules
Total 6 devices made up of DSE2130 (up to 2), DSE2157 (up to 2),
DSE2548 (up to 2)
This gives the possibility of :
Maximum 16 additional inputs (DSE2130)
Maximum 20 additional relay outputs (DSE2157)
Maximum 20 additional LED indicators (DSE2548)
2.10 ADDING AN EXTERNAL SOUNDER TO THE APPLICATION
When an external alarm or indicator is required, this can be achieved by using the DSE Configuration
Suite PC software to configure an auxiliary output for “Audible Alarm”, and by configuring an auxiliary
input for “Alarm Mute” (if required).
The audible alarm output activates and de-activates at the same time as the module’s internal
sounder. The Alarm mute input and internal alarm mute button activate ‘in parallel’ with each other.
Either signal mutes both the internal sounder and audible alarm output.
Example of configuration to achieve external sounder with external alarm mute button:
057-233 ISSUE: 1
Page 20 of 90
2.11 DIMENSIONS AND MOUNTING
2.11.1 DIMENSIONS
240.0 mm x 181.1 mm x 41.7 mm
(9.4 ” x 7.1 ” x 1.6 ”)
2.11.2 PANEL CUTOUT
220 mm x 160 mm
(8.7 ” x 6.3 ”)
2.11.3 WEIGHT
0.7 kg
(1.4 lb)
Page 21 of 90
057-233 ISSUE: 1
2.11.4 FIXING CLIPS
NOTE: In conditions of excessive vibration, mount the module on suitable anti-vibration
mountings.
The module is held into the panel fascia using the supplied fixing clips.
•
Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from
the clip.
•
Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
•
Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of
the clip are inside their allotted slots.
•
Turn the fixing clip screws clockwise until they make contact with the panel fascia.
•
Turn the screws a little more to secure the module into the panel fascia. Care must be taken
not to over tighten the fixing clip screws.
Fixing clip fitted to
module
Fixing clip
057-233 ISSUE: 1
Page 22 of 90
2.11.5 CABLE TIE FIXING POINTS
Integral cable tie fixing points are included on the rear of the module’s case to aid wiring. This
additionally provides strain relief to the cable loom by removing the weight of the loom from the screw
connectors, thus reducing the chance of future connection failures.
Care is to be taken not to over tighten the cable tie (for instance with cable tie tools) to prevent the risk
of damage to the module case.
Cable tie fixing point
With cable and tie in place
2.11.6 SILICON SEALING GASKET
The supplied silicon gasket provides improved sealing between module and the panel fascia.
The gasket is fitted to the module before installation into the panel fascia.
Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal.
Gasket fitted
to module
Sealing gasket
Page 23 of 90
057-233 ISSUE: 1
2.11.8 APPLICABLE STANDARDS
Standard
Description
BS 4884-1
This document conforms to BS4884-1 1992 Specification for presentation
of essential information.
BS 4884-2
This document conforms to BS4884-2 1993 Guide to content
BS 4884-3
This document conforms to BS4884-3 1993 Guide to presentation
BS EN 60068-2-1
(Minimum temperature)
-30 °C (-22 °F)
BS EN 60068-2-2
(Maximum temperature)
+70 °C (158 °F)
BS EN 60950
Safety of information technology equipment, including electrical business
equipment
BS EN 61000-6-2
EMC Generic Immunity Standard (Industrial)
BS EN 61000-6-4
EMC Generic Emission Standard (Industrial)
BS EN 60529
(Degrees of protection
provided by enclosures)
IP65 (front of module when installed into the control panel with the
optional sealing gasket)
IP42 (front of module when installed into the control panel WITHOUT
being sealed to the panel)
UL508
NEMA rating
(Approximate)
12 (Front of module when installed into the control panel with the
supplied sealing gasket).
2 (Front of module when installed into the control panel WITHOUT being
sealed to the panel)
IEEE C37.2
(Standard Electrical
Power System Device
Function Numbers and
Contact Designations)
Under the scope of IEEE 37.2, function numbers can also be used to
represent functions in microprocessor devices and software programs.
The controller is device number 11L-8000 (Multifunction device
protecting Line (generator) –module).
As the module is configurable by the generator OEM, the functions
covered by the module vary. Under the module’s factory configuration,
the device numbers included within the module are :
2 – Time Delay Starting Or Closing Relay
3 – Checking Or Interlocking Relay
8 – Control Power Disconnecting Device
11 – Multifunction Device
23 – Temperature control device (USING EXPANSION MODULE)
26 – Apparatus thermal device (USING EXPANSION MODULE)
27AC – AC Undervoltage Relay
27DC – DC Undervoltage Relay
29 – Isolating Contactor Or Switch
30 – Annunciator Relay
37 – Undercurrent Or Underpower Relay (USING INTERNAL PLC
EDITOR)
42 – Running Circuit Breaker
44 – Unit sequence relay
48 – Incomplete Sequence Relay
Continued overleaf...
057-233 ISSUE: 1
Page 24 of 90
Standard
Description
IEEE C37.2
(Standard Electrical
Power System Device
Function Numbers and
Contact Designations)
Continued…
49 – Machine Or Transformer Thermal Relay (USING EXPANSION
MODULE)
50 – Instantaneous Overcurrent Relay
52 – AC Circuit Breaker
55 – Power Factor Relay (USING INTERNAL PLC EDITOR)
59AC – AC Overvoltage Relay
59DC – DC Overvoltage Relay
62 – Time Delay Stopping Or Opening Relay
63 – Pressure Switch
71 – Level Switch
74 – Alarm Relay
78 – Phase-angle measuring relay
79 – Reclosing relay (USING INTERNAL PLC EDITOR)
81 – Frequency Relay
83 – Automatic Selective Control Or Transfer Relay
86 – Lockout Relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.
Page 25 of 90
057-233 ISSUE: 1
2.11.9 ENCLOSURE CLASSIFICATIONS
2.11.9.1 IP CLASSIFICATIONS
The modules specification under BS EN 60529 Degrees of protection provided by enclosures
IP65 (Front of module when module is installed into the control panel with the optional sealing
gasket).
IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the
panel)
First Digit
Second Digit
Protection against contact and ingress of
solid objects
Protection against ingress of water
0 No protection
0
No protection
1 Protected against ingress solid objects
with a diameter of more than 50 mm. No
protection against deliberate access, e.g.
with a hand, but large surfaces of the
body are prevented from approach.
1
Protection against dripping water falling
vertically. No harmful effect must be produced
(vertically falling drops).
2 Protected against penetration by solid
objects with a diameter of more than 12
mm. Fingers or similar objects prevented
from approach.
2
Protection against dripping water falling
vertically. There must be no harmful effect
when the equipment (enclosure) is tilted at an
angle up to 15° from its normal position (drops
falling at an angle).
3 Protected against ingress of solid objects
with a diameter of more than 2.5 mm.
Tools, wires etc. with a thickness of more
than 2.5 mm are prevented from
approach.
3
Protection against water falling at any angle up
to 60° from the vertical. There must be no
harmful effect (spray water).
4 Protected against ingress of solid objects
with a diameter of more than 1 mm.
Tools, wires etc. with a thickness of more
than 1 mm are prevented from approach.
4
Protection against water splashed against the
equipment (enclosure) from any direction.
There must be no harmful effect (splashing
water).
5 Protected against harmful dust deposits.
Ingress of dust is not totally prevented
but the dust must not enter in sufficient
quantity to interface with satisfactory
operation of the equipment. Complete
protection against contact.
5
Protection against water projected from a
nozzle against the equipment (enclosure) from
any direction. There must be no harmful effect
(water jet).
6 Protection against ingress of dust (dust
tight). Complete protection against
contact.
6
Protection against heavy seas or powerful
water jets. Water must not enter the equipment
(enclosure) in harmful quantities (splashing
over).
057-233 ISSUE: 1
Page 26 of 90
2.11.9.2 NEMA CLASSIFICATIONS
The modules NEMA Rating (Approximate)
12 (Front of module when module is installed into the control panel with the optional sealing gasket).
2 (front of module when module is installed into the control panel WITHOUT being sealed to the
panel)
NOTE: There is no direct equivalence between IP / NEMA ratings. IP figures shown are
approximate only.
1
IP30
Provides a degree of protection against contact with the enclosure equipment and against a
limited amount of falling dirt.
2
IP31
Provides a degree of protection against limited amounts of falling water and dirt.
3
IP64
Provides a degree of protection against windblown dust, rain and sleet; undamaged by the
formation of ice on the enclosure.
3R
IP32
Provides a degree of protection against rain and sleet:; undamaged by the formation of ice
on the enclosure.
4 (X)
IP66
Provides a degree of protection against splashing water, windblown dust and rain, hose
directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion).
12/12K
IP65
Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids.
13
IP65
Provides a degree of protection against dust and spraying of water, oil and non corrosive
coolants.
Page 27 of 90
057-233 ISSUE: 1
3 INSTALLATION
The module is designed to be mounted on the panel fascia. For dimension and mounting details, see
the section entitled Specification, Dimension and mounting elsewhere in this document.
3.1 TERMINAL DESCRIPTION
To aid user connection, icons are used on the rear of the module to help identify terminal functions.
An example of this is shown below.
NOTE: Availability of some terminals depends upon module version. Full details are given
in the section entitled Terminal Description elsewhere in this manual.
Terminals 1-8
Terminals 9-17
Terminals 18-24
Terminals 30-37
Terminals 38-41
Terminals 42-47
Terminals 48-53
USB
PC Configuration
Terminals 25-29
Serial and
part
number
label
057-233 ISSUE: 1
Page 28 of 90
3.1.1 DC SUPPLY, OUTPUTS G-L
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
Pin
No
Description
Cable
Size
Notes
1
DC Plant Supply Input
(Negative)
2.5 mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
Supplies the module and DC Outputs A, B, C, D, E & F
3
Output relay G
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
4
Output relay H
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
5
Output relay I
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
6
Output relay J
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
7
Output relay K
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
8
Output relay L
1.0 mm²
AWG 18
Plant Supply Positive from terminal 2. 2 Amp rated.
3.1.2 CONFIGURABLE DIGITAL INPUTS A-I
Pin
No
Description
Cable
Size
Notes
9
Configurable digital input A
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
10
Configurable digital input B
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
11
Configurable digital input C
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
12
Configurable digital input D
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
13
Configurable digital input E
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
14
Configurable digital input F
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
15
Configurable digital input G
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
16
Configurable digital input H
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
17
Configurable digital input I
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
Page 29 of 90
057-233 ISSUE: 1
3.1.3 CONFIGURABLE DIGITAL INPUTS J-L, DSENET
NOTE: Terminal 24 is not used, do not connect.
Pin
No
Description
Cable
Size
Notes
18
Configurable digital input J
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
19
Configurable digital input K
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
20
Configurable digital input L
0.5 mm²
AWG 20
Switch to negative or positive depending on configuration
21
DSENet expansion B (+)
0.5 mm²
AWG 20
Use only 120 Ω RS485 approved cable
22
DSENet expansion A (-)
0.5 mm²
AWG 20
Use only 120 Ω RS485 approved cable
23
DSENet expansion SCR
0.5 mm²
AWG 20
Use only 120 Ω RS485 approved cable
3.1.4 CONFIGURABLE VOLT-FREE OUTPUTS E & F
NOTE: Terminal 27 is not used, do not connect.
Pin
No.
Description
Cable
Size
Notes
25
Output relay E
1.0 mm²
AWG 18
Normally closed volt-free relay user configured (8 A
resistive at 250 V AC rated)
26
Output relay E
1.0 mm²
AWG 18
Normally closed volt-free relay user configured (8 A
resistive at 250 V AC rated)
28
Output relay F
1.0 mm²
AWG 18
Normally open volt-free relay user configured (8 A
resistive at 250 V AC rated)
29
Output relay F
1.0 mm²
AWG 18
Normally open volt-free relay user configured (8 A
resistive at 250 V AC rated)
3.1.5 LOAD SWITCHING AND S2 VOLTAGE SENSING
NOTE: The above table describes connections to a three phase, four wire alternator. For
alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this
manual.
Pin
No.
Description
Cable
Size
Notes
30
Output relay A
1.0 mm²
AWG 18
Normally configured to control S1 contactor coil
(Recommend 10A fuse)
31
Output relay A
1.0 mm²
AWG 18
Normally configured to control S1contactor coil
32
Output relay B
1.0 mm²
AWG 18
Normally configured to control S2 contactor coil
(Recommend 10A fuse)
33
Output relay B
1.0 mm²
AWG 18
Normally configured to control S2 contactor coil
34
S2 L1 (U) voltage monitoring
1.0 mm²
AWG 18
Connect to S2 L1 (U) output (AC)
(Recommend 2A fuse)
35
S2 L2 (V) voltage monitoring input
1.0 mm²
AWG 18
Connect to S2 L2 (V) output (AC)
(Recommend 2A fuse)
36
S2 L3 (W) voltage monitoring input
1.0 mm²
AWG 18
Connect to S2 L3 (W) output (AC)
(Recommend 2A fuse)
37
S2 Neutral (N) input
1.0 mm²
AWG 18
Connect to S2 Neutral terminal (AC)
057-233 ISSUE: 1
Page 30 of 90
3.1.6 S1 VOLTAGE SENSING
NOTE: The above table describes connections to a three phase, four wire alternator. For
alternative wiring topologies, please see the ALTERNATIVE AC TOPOLOGIES section of this
manual.
Pin
No.
Description
Cable
Size
Notes
38
S1 L1 (R) voltage monitoring
1.0 mm²
AWG 18
Connect to S1 L1 (R) incoming supply (AC)
(Recommend 2A fuse)
39
S1 L2 (S) voltage monitoring
1.0 mm²
AWG 18
Connect to S1 L1 (S) incoming supply (AC)
(Recommend 2A fuse)
40
S1 L3 (T) voltage monitoring
1.0 mm²
AWG 18
Connect to S1 L1 (T) incoming supply (AC)
(Recommend 2A fuse)
41
S1 Neutral (N) input
1.0 mm²
AWG 18
Connect to S1 N incoming supply (AC)
3.1.7 LOAD CURRENT TRANSFORMERS
WARNING!: Do not disconnect this plug when the CTs are carrying current.
Disconnection does open circuit the secondary of the C.T.’s and dangerous voltages may then
develop. Always ensure the CTs are not carrying current and the CTs are short circuit
connected before making or breaking connections to the module.
NOTE: The module has a burden of 0.5VA on the CT. Ensure the CT is rated for the burden
of the controller, the cable length being used and any other equipment sharing the CT. If in
doubt, consult your CT supplier.
Pin
No.
Description
Cable
Size
Notes
42
CT Secondary for Load L1
2.5 mm²
AWG 13
Connect to s1 secondary of L1 monitoring CT
43
CT Secondary for Load L2
2.5 mm²
AWG 13
Connect to s1 secondary of L2 monitoring CT
44
CT Secondary for Load L3
2.5 mm²
AWG 13
Connect to s1 secondary of L3 monitoring CT
Page 31 of 90
057-233 ISSUE: 1
3.1.7.1
CONNECTION TO TERMINALS 45 & 46/47
The function of terminals 45 & 46/47 change position depending upon wiring topology as follows:
Topology
Pin No.
Description
Cable Size
No earth fault measuring
45
DO NOT CONNECT
46/47
Connect to s2 of the CTs connected to
L1,L2,L3,N
2.5 mm²
AWG 13
Restricted earth fault measuring
45
Connect to s2 of the CTs connected to
L1,L2,L3,N
2.5 mm²
AWG 13
46/47
Connect to s1 of the CT on the neutral
conductor
2.5 mm²
AWG 13
Un-restricted earth fault measuring
(Earth fault CT is fitted in the neutral
to earth link)
45
Connect to s1 of the CT on the neutral
to earth conductor.
2.5 mm²
AWG 13
46/47
Connect to s2 of the CT on the neutral
to earth link.
Also connect to the s2 of CTs connected
to L1, L2, L3.
2.5 mm²
AWG 13
3.1.7.2
CT CONNECTIONS
p1, k or K is the primary of the CT that ‘points’ towards the SUPPLY
p2, l or L is the primary of the CT that ‘points’ towards the LOAD
s1 is the secondary of the CT that connects to the DSE Module’s input for the CT measuring
s2 is the secondary of the CT that must be commoned with the s2 connections of all the other CTs
and connected to the CT common terminal of the module.
TO SUPPLY
TO LOAD
POLARITY OF CT PRIMARY
Labelled as
p1, k or K
Labelled as
p2, l or L
057-233 ISSUE: 1
Page 32 of 90
3.1.8 CONFIGURABLE VOLT-FREE CHANGEOVER OUTPUTS C & D
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
Pin
No.
Description
Cable
Size
Notes
48
Output C Normally Open
1.0 mm²
AWG 18
Volts free relay change-over relay user configured (8A resistive
at 250V AC rated)
49
Output C Common
1.0 mm²
AWG 18
50
Output C Normally Closed
1.0 mm²
AWG 18
51
Output D Normally Open
1.0 mm²
AWG 18
Volts free relay change-over relay user configured (8A resistive
at 250V AC rated)
52
Output D Common
1.0 mm²
AWG 18
53
Output D Normally Closed
1.0 mm²
AWG 18
3.1.9 PC CONFIGURATION INTERFACE CONNECTOR
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
NOTE: The USB connection cable between the PC and the module must not be extended
beyond 6 m (20 feet). For distances over 6 m, it is possible to use a third party USB extender.
Typically, they extend USB up to 50 m (55 yards). The supply and support of this type of
equipment is outside the scope of Deep Sea Electronics PLC.
CAUTION!: Care must be taken not to overload the PCs USB system by connecting more
than the recommended number of USB devices to the PC. For further information, consult the
PC supplier.
Description
Cable
Size
Notes
Socket for connection to PC with DSE
Configuration Suite Software
0.5 mm²
AWG 20
This is a standard USB
type A to type B connector.
Page 33 of 90
057-233 ISSUE: 1
3.1.10 RS485 CONNECTOR
Pin No.
Notes
A (-)
Two core screened twisted pair cable.
120Ω impedance suitable for RS485 use.
Recommended cable type - Belden 9841
Max distance 1200 m (1.2 km) when using Belden 9841 or direct equivalent.
B (+)
SCR
3.1.11 RS232 CONNECTOR
Pin No.
Notes
1
Received Line Signal Detector (Data Carrier Detect)
2
Received Data
3
Transmit Data
4
Data Terminal Ready
5
Signal Ground
6
Data Set Ready
7
Request To Send
8
Clear To Send
9
Ring Indicator
View looking into the male connector on the module
Location of RS232
connector
Location of RS485 connector
057-233 ISSUE: 1
Page 34 of 90
3.2 TYPICAL WIRING DIAGRAM
As every system has different requirements, these diagrams show only a typical system and do not
intend to show a complete system.
Genset manufacturers and panel builders may use these diagrams as a starting point; however, refer
to the completed system diagram provided by the system manufacturer for complete wiring detail.
Further wiring suggestions are available in the following DSE publications, available at
www.deepseaplc.com.
DSE Part
Description
056-022
Breaker Control (Training guide)
Page 35 of 90
057-233 ISSUE: 1
3.2.1 DSE335 3 PHASE, 4 WIRE WITH RESTRICTED EARTH FAULT PROTECTION
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read
earth faults ‘after’ the CT only (Restricted to load / downstream of the CT)
Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults
‘before’ the CT only (Restricted to source / upstream of the CT)
057-233 ISSUE: 1
Page 36 of 90
3.3 ALTERNATIVE TOPOLOGIES
NOTE: For further details of module configuration, refer to DSE Publication: 057-237
DSE335 Configuration Software Manual.
The controller is factory configured to connect to a 3 phase, 4 wire Star connected alternator. This
section details connections for alternative AC topologies. Ensure to configure the controller to suit the
required topology.
3.3.1 3 PHASE, 4 WIRE WITHOUT EARTH FAULT PROTECTION
Page 37 of 90
057-233 ISSUE: 1
3.3.2 SINGLE PHASE WITH RESTRICTED EARTH FAULT
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read
earth faults ‘after’ the CT only (Restricted to load / downstream of the CT)
Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults
‘before’ the CT only (Restricted to source / upstream of the CT)
3.3.3 SINGLE PHASE WITHOUT EARTH FAULT
057-233 ISSUE: 1
Page 38 of 90
3.3.4 2 PHASE (L1 & L2) 3 WIRE WITH RESTRICTED EARTH FAULT
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read
earth faults ‘after’ the CT only (Restricted to load / downstream of the CT)
Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults
‘before’ the CT only (Restricted to source / upstream of the CT)
3.3.5 2 PHASE (L1 & L2) 3 WIRE WITHOUT EARTH FAULT
Page 39 of 90
057-233 ISSUE: 1
3.3.6 2 PHASE (L1 & L3) 3 WIRE WITH RESTRICTED EARTH FAULT
NOTE: Earthing the neutral conductor ‘before’ the neutral CT allows the module to read
earth faults ‘after’ the CT only (Restricted to load / downstream of the CT)
Earthing the neutral conductor ‘after’ the neutral CT allows the module to read earth faults
‘before’ the CT only (Restricted to source / upstream of the CT)
057-233 ISSUE: 1
Page 40 of 90
3.3.7 2 PHASE (L1 & L3) 3 WIRE WITHOUT EARTH FAULT MEASURING
Page 41 of 90
057-233 ISSUE: 1
3.3.8 3 PHASE 4 WIRE WITH UNRESTRICTED EARTH FAULT MEASURING
NOTE: Unrestricted Earth Fault Protection detects earth faults in the load and in the
sources. Be sure to measure the natural earth fault of the site before deciding upon an earth
fault alarm trip level.
057-233 ISSUE: 1
Page 42 of 90
3.4 EARTH SYSTEMS
3.4.1 NEGATIVE EARTH
The typical wiring diagrams located within this document show connections for a negative earth
system (the battery negative connects to Earth)
3.4.2 POSITIVE EARTH
When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the
following points must be followed:
•
Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
•
All points shown as Earth on the typical wiring diagram must connect to BATTERY
NEGATIVE (not earth).
3.4.3 FLOATING EARTH
Where neither the battery positive nor battery negative terminals are connected to earth the following
points must to be followed
•
Follow the typical wiring diagram as normal for all sections EXCEPT the earth points
•
All points shown as Earth on the typical wiring diagram must connect to BATTERY
NEGATIVE (not earth).
3.5 TYPICAL ARRANGEMENT OF DSENET®
Six (6) devices can be connected to the DSENet®, made up of the following devices :
Device
Max Number Supported
DSE2130 Input Expansion
2
DSE2157 Relay Output Expansion
2
DSE2548 LED Expansion
2
For part numbers of the expansion modules and their documentation, see section entitled DSENet
Expansion Modules elsewhere in this manual.
Description of Controls
057-233 ISSUE: 1
Page 43 of 90
4 DESCRIPTION OF CONTROLS
NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to the configuration source for the exact
sequences and timers observed by any particular module in the field.
CAUTION: The module may instruct an engine start event due to external influences.
Therefore, it is possible for the engine to start at any time without warning. Prior to performing
any maintenance on the system, it is recommended that steps are taken to remove the battery
and isolate supplies.
Control of the module is via push buttons mounted on the front of the module with
Start Inhibit/Reset
, Manual
, Auto
, Mode
, Alarm Mute
, Latest Transfer
Information
, Close/Open S1
and Close/Open S2
functions. For normal operation, these
are the only controls which need to be operated. Details of their operation are provided later in this
document.
Description of Controls
057-233 ISSUE: 1
Page 44 of 90
Menu navigation
buttons
Four configurable
LEDs
Select Stop
mode
Select
Manual mode
Select mode: Test On
Load, Test Off Load &
Prohibit Return
Alarm Mute /
Lamp Test
Latest Transfer
Information (Info)
Open/Close S2
(manual mode only)
Open/Close S1
(manual mode only)
Main status and
instrumentation display
Select
Auto mode
S2 status LED.
Illuminated when S2
is supplying the load.
S2 Available LED.
Illuminated when the S2 is within
limits and able to take load.
S2 Available LED.
Illuminated when the S2 is within
limits and able to take load.
S1 status LED.
Illuminated when S1
is supplying the load.
Description of Controls
Page 45 of 90
057-233 ISSUE: 1
4.1 CONTROL PUSH-BUTTONS
Icon
Description
Stop / Reset
This button places the module into its Stop / Reset
mode. This clears any
alarm conditions for which the triggering criteria have been removed. If S2 is on
load and the module is placed into Stop mode, the module automatically instructs
the changeover device to unload the S2 source (Close S2 Output becomes
inactive (if used)). If S2 is configured for a generator, the start signal given to the
generator controller is also removed. If a Remote Start signal is present while
operating in this mode, the remote start does not occur.
Manual
This button places the module into its Manual
mode to allow manual control of
the ATS functions. This starts S2 when configured as a generator, and runs it off
load.
For further details, please see the more detailed description of ‘Manual operation’
elsewhere in this document.
Auto
This button places the module into its Auto
mode. This mode allows the
module to control the function of S1 and S2 automatically. The module monitors
the remote start input and S1 supply status and once a start request is made, a
start request is given to S2 if configured to a generator and once available, placed
on load.
Upon removal of the starting signal, the module automatically transfers the load
from S2 and remove the start signal to the generator observing the return delay
timer and cooling timer as necessary. The module then awaits for the next start
event.
For further details, please see the more detailed description of ‘Auto operation’
elsewhere in this manual.
Mode
This button allows the user to cycle through different operating Mode
and
press the Tick
to accept the mode change.
The modes available are:
Test On Load: This mode allows the module to start and load S2 for test purposes.
Test Off Load: This mode allows the module to start S2 and leave off load for test
purposes.
Prohibit Return: This mode is used to prevent the module from returning load the
S1 until instructed.
For further details, please see the more detailed description of ‘Mode operation’
elsewhere in this manual.
Description of Controls
057-233 ISSUE: 1
Page 46 of 90
Icon
Description
Mute / Lamp Test
This button silences the audible alarm if it is sounding and illuminates all of the
LEDs as a lamp test feature.
Latest Transfer Information
Whilst pressing this button, the module displays the reason, time, date and
duration for the latest transfer that occurred, holding this button cycles between the
last S1 transfer and the last S2 transfer.
For further details, please see the more detailed description of ‘Viewing Latest
Transfer Information Page’ elsewhere in this manual.
Close / Open to S1
NOTE: This button only operates in manual mode.
Pressing the Close / Open S1
button when S1 is on load, opens the S1 load
switch.
Pressing the Close / Open S1
button when S2 is on load and S1 is healthy, the
S2 load switch opens, wait for the duration of the transfer delay, then closes the S1
load switch.
For further details, please see the more detailed description of ‘Manual operation’
elsewhere in this document.
Close/Open to S2
NOTE: This button only operates in manual mode.
Pressing the Close / Open S2
button when S2 is on load, opens the S2 load
switch.
Pressing the Close / Open S2
button when S1 is on load and S2 is healthy, the
S1 load switch opens, wait for the duration of the transfer delay, then closes the S2
load switch.
For further details, please see the more detailed description of ‘Manual operation’
elsewhere in this document.
Menu navigation
Used for navigating the instrumentation, event log and configuration screens.
For further details, please see the more detailed description of these items
elsewhere in this manual.
Description of Controls
Page 47 of 90
057-233 ISSUE: 1
4.2 VIEWING THE INSTRUMENT PAGES
It is possible to scroll to display the different pages of information by repeatedly operating the Next /
Previous page buttons
.
Example
Status
S1
S2
Further presses of the Next Page Button
returns the display to the Status page.
The complete order and contents of each information page are given in the following sections
Once selected the page remains on the LCD display until the user selects a different page, or after an
extended period of inactivity (LCD Page Timer), the module reverts to the status display.
If no buttons are pressed upon entering an instrumentation page, the instruments are displayed
automatically subject to the setting of the LCD Scroll Timer.
The LCD Page and LCD Scroll timers are configurable using the DSE Configuration Suite Software or
by using the Front Panel Editor.
The screenshot shows the factory
settings for the timers, taken from
the DSE Configuration Suite
Software.
Alternatively, to scroll manually through all instruments on the currently selected page, press the scroll
buttons. The ‘autoscroll’ is disabled.
To re-enable ‘autoscroll’ press the scroll
buttons to scroll to the ‘title’ of the instrumentation
page (ie S1). A short time later (the duration of the LCD Scroll Timer), the instrumentation display
begins to autoscroll.
When scrolling manually, the display automatically returns to the Status page if no buttons are
pressed for the duration of the configurable LCD Page Timer.
If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw
the operator’s attention to the alarm condition.
If you want to view one of the
instruments towards the end of the list,
it may be quicker to scroll up through
the instruments rather than down!
If you want to view one of the
instrument pages towards the
end of the list, it may be quicker
to scroll left through the pages
rather than right!
Description of Controls
057-233 ISSUE: 1
Page 48 of 90
4.2.1 STATUS
This is the ‘home’ page, which is displayed when no other page has been selected, and the page that
is automatically displayed after a period of inactivity (LCD Page Timer) of the module control buttons.
Contains summary information of both supplies along with different module status display.
•
Main Summary (Backup source)
•
Main Summary (Primary source)
•
Source supply summary
•
Supervisors summary
•
Monitors summary
This page changes with the action of the controller, when S1 is on load, S1 parameters are seen and
when changing to S2 on load, the S2 parameters are shown.
No Start Request
Example of the first status screen showing no start request to S2 and
S1 closed supplying the load…
S1 Closed
L-N 230V 40A
L-L 400V 50.0Hz
S2 Available
… and showing S2 on load.
S2 Closed
L-N 229V 40A
L-L 399V 50.1Hz
Press
to access more status information about two supplies.
Description of Controls
Page 49 of 90
057-233 ISSUE: 1
4.2.2 S1
Contains electrical values of S1 measured or derived from the module’s voltage and current inputs.
•
S1 Configuration
•
S1 State
•
S1 Summary
•
S1 Voltage (ph-N)
•
S1 Voltage (ph-ph)
•
S1 Frequency
•
S1 Current
•
S1 Earth Current
•
S1 Load (ph-N kW)
•
S1 Load (Total kW)
•
S1 Load (ph-N kV A)
•
S1 Load (Total kV A)
•
S1 Power Factor
•
S1 Power Factor Average
•
S1 Load (ph-N kvar)
•
S1 Load (Total kvar)
•
S1 Load (kW h, kV A h, kvar h)
4.2.3 S2
Contains electrical values of S2 measured or derived from the module’s voltage and current inputs.
•
S2 Configuration
•
S2 State
•
S2 Summary
•
S2 Voltage (ph-N)
•
S2 Voltage (ph-ph)
•
S2 Frequency
•
S2 Current
•
S2 Earth Current
•
S2 Load (ph-N kW)
•
S2 Load (Total kW)
•
S2 Load (ph-N kV A)
•
S2 Load (Total kV A)
•
S2 Power Factor
•
S2 Power Factor Average
•
S2 Load (ph-N kvar)
•
S2 Load (Total kvar)
•
S2 Load (kW h, kV A h, kvar h)
•
Load Control
4.2.4 MODULE
Contains information on the module configuration.
•
S1 Configuration
•
S2 Configuration
•
Date and Time
•
Battery Voltage
Description of Controls
057-233 ISSUE: 1
Page 50 of 90
4.2.5 EXPANSION
Contains the measured value of the expansion module’s analogue inputs, this is pressure, percentage
or temperature for example ‘Bulk Fuel Level’.
4.2.6 ALARMS
Contains the alarms currently active on the module. For more information please see the section
entitled ‘Protections’ else where in this manual.
4.2.7 EVENT LOG
The module maintains a log of past alarms and/or selected status changes.
At the time of writing, the modules log is capable of storing the last 250 log entries.
Under default factory settings, the event log only includes electrical trip alarms (The event log does
not contain Warning alarms); however, this is configurable by the system designer using the DSE
Configuration Suite software.
Once the log is full, any subsequent shutdown alarms overwrites the oldest entry in the log.
Hence, the log always contains the most recent alarms.
The module logs the alarm, along with the date and time of the event (or engine running hours if
configured to do so).
If the module is configured and connected to send SMS text
To view the event log, repeatedly press the next page button
until the LCD screen displays the
Event log :
1 Event log
S1 Failure
Warning
23 Mar 2014, 08:25:46
Press down
to view the next most recent shutdown alarm:
Continuing to press down
cycles through the past alarms after which the display shows the
most recent alarm and the cycle begins again.
To exit the event log and return to viewing the instruments, press the next page
button to
select the next instrumentation page.
Example showing the
possible configuration of the
modules event log (DSE
Configuration Suite Software)
This also shows the factory
settings of the module.
This is event 1.
Description of Controls
Page 51 of 90
057-233 ISSUE: 1
4.2.8 SERIAL PORT
4.2.8.1
RS232 SERIAL PORT
NOTE: Factory Default settings are for the RS232 port to be enabled with no modem
connected, operating at 19200 baud, Modbus slave address 10.
This section is included to give information about the RS232 serial port and external modem (if
connected).
The items displayed on this page change depending upon configuration of the module. Refer to the
system supplier for further details.
Module Connected To an RS232 Telephone Modem
NOTE: Not all alarms generate a dial out command; this is dependant upon module
configuration of the event log. Any event configured to be recorded in the event log causes the
modem to dial out to a PC.
When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the
modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the
Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is
dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is
established, all data is passed between the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out
whenever an alarm is generated.
Press the Scroll Down
button view the modem
status....
Indicates that the RS232 port is
configured for modem use. It displays
‘RS232’ if no modem is configured.
Description of Controls
057-233 ISSUE: 1
Page 52 of 90
Module Connected To an RS232 GSM Modem
NOTE: Not all alarms generate a dial out command; this is dependant upon module
configuration of the event log. Any event configured to be recorded in the event log causes the
modem to dial out to a PC.
NOTE: In the case of GSM modems, it is important that a DATA ENABLED SIM is used.
This is often a different number than the ‘voice number’ and is often called Circuit Switched
Data (CSD) by the SIM provider.
When the module is powered up, it sends ‘initialisation strings’ to the connected modem. It is
important therefore that the modem is already powered, or is powered up at the same time as the
module. At regular intervals after power up, the modem is reset, and reinitialised, to ensure the
modem does not ‘hang up’.
If the module does not correctly communicate with the modem, “Modem initialising’ appears on the
Serial Port instrument screen as shown overleaf.
If the module is set for “incoming calls” or for “incoming and outgoing calls”, once the modem is
dialled, it answers after two rings (using the factory setting ‘initialisation strings). Once the call is
established, all data is passed between the dialling PC and the module.
If the module is set for “outgoing calls” or for “incoming and outgoing calls”, then the module dials out
whenever an alarm is generated.
Many GSM modems are fitted with a status LED to show operator cell status and ringing indicator.
These are a useful troubleshooting tool.
In the case of GSM connection problems, try calling the DATA number of the SIMCARD with an
ordinary telephone. After two rings, the modem answers the call and then starts ‘squealing’. If this
does not happen, check all modem connections and double check with the SIM provider that it is a
DATA SIM and can operate as a data modem. DATA is NOT the same as FAX or GPRS and is often
called Circuit Switched Data (CSD) by the SIM provider.
Press the Scroll Down
button view the modem GSM
status....
If the GSM modem is not purchased from DSE, ensure that it has been correctly set to operate at
9600 baud.
Currently connected GSM
operator and signal strength.
Description of Controls
Page 53 of 90
057-233 ISSUE: 1
Modem Initialisation Sequence
1) The modem attempts to communicate to the module
2) If the Modem and module communicate successfully:
3) In case of communication failure between the modem and module, the modem is automatically
reset and initialisation is attempted once more:
In the case of a module that is unable to communicate with the modem, the display continuously
cycles between ‘Modem Reset’ and ‘Modem Initialising’ as the module resets the modem and
attempts to communicate with it again, this continues until correct communication is established
with the modem. In this instance, check connections and verify the modem operation.
Module Modem Diagnostics
Modem diagnostic screens are included; press the Scroll Down
button when viewing the
RS232 Serial Port instruments to cycle to the available screens. If modem communication problems
are experiencied, this information aids troubleshooting.
Serial Port
RTS
CTS
DSR
DTR
DCD
Line
Description
RTS
Request to Send
Flow Control
CTS
Clear to Send
Flow Control
DSR
Data Set Ready
Ready to Communicate
DTR
Data Terminal Ready
Ready to Communicate
DCD
Data Carrier Detect
Modem is Connected
Modem Commands
Rx: OK
Tx: AT+IPR=9600
Rx: OK
Shows the state of the modem communication lines. These can
help diagnose connection problems.
Example:
RTS A dark background shows the line is active.
RTS A grey background shows that the line is toggling high and low
RTS No background indicates that the line is inactive
Shows the last command sent to the
modem and the result of the command.
Description of Controls
057-233 ISSUE: 1
Page 54 of 90
Module RS232 Port Configured For Connection to A Modbus Master
The modules operate as a modbus RTU slave device. In a modbus system, there is only one Master,
typically a PLC, HMI system or PC SCADA system.
This master requests for information from the modbus slave (The module) and may (in control
systems) also send request to change operating modes etc. Unless the Master makes a request, the
slave is ‘quiet’ on the data link.
The factory settings are for the module to
communicate at 19200 baud, modbus slave
address 10.
To use the RS232 port, ensure that ‘port usage’
is correctly set using the DSE Configuration
Suite Software.
‘Master inactivity timeout’ must be set to at least
twice the value of the system scan time. For
example if a modbus master PLC requests data
from the module once per second, the timeout
must be set to at least 2 seconds
The DSE MODBUS document containing register mappings inside the DSE module is available upon
request from [email protected]. Email the request along with the serial number of the DSE
module to ensure the correct information is sent.
Description of Controls
Page 55 of 90
057-233 ISSUE: 1
4.2.8.2
RS485 SERIAL PORT
NOTE: Factory Default settings are for the RS485 port to operate at 19200 baud, modbus
slave address 10.
This section is included to give information about the currently selected serial port
The items displayed on this pagel change depending upon configuration of the module. Refer to the
system supplier for further details.
Module RS485 Port Configured For Connection to A Modbus Master
The modules operate as a modbus RTU slave device.
In a modbus system, there is only one Master, typically a PLC,
HMI system or PC SCADA system.
This master requests for information from the modbus slave
(The module) and may (in control systems) also send request
to change operating modes etc. Unless the Master makes a request, the slave is ‘quiet’ on the data
link.
The factory settings are for the module to
communicate at 19200 baud, modbus slave
address 10.
‘Master inactivity timeout’ must be set to at least
twice the value of the system scan time. For
example if a modbus master PLC requests data
from the module once per second, the timeout
must be set to at least 2 seconds.
The DSE MODBUS document containing register mappings inside the DSE module is available upon
request from [email protected]. Email the request along with the serial number of the DSE
module to ensure the correct information is sent.
Typical Requests (Using Pseudo Code)
BatteryVoltage=ReadRegister(10,0405,1): reads register (hex) 0405 as a single register (battery
volts) from slave address 10.
WriteRegister(10,1008,2,35701, 65535-35701): Puts the module into AUTO mode by writing to
(hex) register 1008, the values 35701 (auto mode) and register 1009 the value 65535-35701 (the
bitwise opposite of auto mode)
Shutdown=(ReadRegister(10,0306,1) >> 12) & 1): reads (hex) 0306 and looks at bit 13
(shutdown alarm present)
Warning=(ReadRegister(10,0306,1) >> 11) & 1): reads (hex) 0306 and looks at bit 12 (Warning
alarm present)
ControlledShutdown=(ReadRegister(10,0306,1) >> 10) & 1): reads (hex) 0306 and looks at
bit 11 (Controlled Shutdown alarm present)
ControlMode=ReadRegister(10,0304,2): reads (hex) register 0304 (control mode).
Description of Controls
057-233 ISSUE: 1
Page 56 of 90
4.2.9 SCHEDULER
Contains the current schedule plan for S2 configured in module.
2/3
Schedule
10:39
Example of the 3rd scheduled operation in bank 2 for S2.
Off Load
Week 3
On 12:00
Run Time 00:30
MMMM T W T F S S
T W T F S S
T W T F S S
T W T F S S
4.2.10 ABOUT
Contains important information about the module and the firmware versions. This information may be
asked for when contacting DSE Technical Support Department for advice.
About
Variant
335
Application
V3.0.20
USB ID
BC614E
Press
to access more information about the module.
About
Bootloader
V1.3.4
Analogue
V2.0.0
•
Variant – 335
•
Application Version – The version of the module’s main
firmware file (Updatable using the Firmware Update
Wizard in the DSE Configuration Suite Software).
•
USB ID – Unique identifier for PC USB connection
•
Bootloader - Firmware Update bootloader software
version
•
Description of Controls
Page 57 of 90
057-233 ISSUE: 1
4.3 VIEWING LATEST TRANSFER INFORMATION PAGE
It is possible to view the reason, time, date and duration of the latest transfer by pressing and holding
the Latest Transfer Information
. Holding this button cycles between the last S1 transfer and the
last S2 transfer.
S1
S1
S1
S1 Latest Transfer
Latest Transfer
Latest Transfer
Latest Transfer 16:53
16:53
16:53
16:53 Example of the Latest Transfer page which shows that there
was a transfer cause by an S1 Under Voltage failure which
lasted for 27 minutes and 13 seconds.
S2
S2
S2
S2 Under Voltage
Under Voltage
Under Voltage
Under Voltage
22
22
22
22 Oct
Oct
Oct
Oct 201
201
201
2014444, 12:59:47
, 12:59:47
, 12:59:47
, 12:59:47
00:27:13
00:27:13
00:27:13
00:27:13
Description of Controls
057-233 ISSUE: 1
Page 58 of 90
4.4 USER CONFIGURABLE INDICATORS
These LEDs can be configured by the user to indicate any one of 100+ different functions based
around the following:
• Indications - Monitoring of a digital input and indicating associated functioning user’s equipment -
Such as Battery Charger On or Louvres Open, etc.
• Warning & Electrical Trips - Specific indication of a particular warning or electrical trip condition,
backed up by LCD indication - Such as S2 Under Voltage Trip, Transformer Over Temperature, etc.
• Status Indications - Indication of specific functions or sequences derived from the modules
operating state - Such as, Panel Locked, S2 Available, etc.
User configurable LEDs
Description of Controls
Page 59 of 90
057-233 ISSUE: 1
4.5 OPERATION
NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to the configuration source for the exact
sequences and timers observed by any particular module in the field.
4.6 QUICKSTART GUIDE
This section provides a quick start guide to the module’s operation.
4.6.1 STARTING S2
NOTE: This only applies when S2 is configured as a generator supply.
First, select manual
mode, this gives the
start request to the
external generator
control…
…when S2 becomes
available, press the
S2 Breaker button to
transfer the load.
Description of Controls
057-233 ISSUE: 1
Page 60 of 90
4.6.2 STOPPING S2
NOTE: This only applies when S2 is configured as a generator supply.
Select Stop/Reset
mode. S2 breaker is
opened and the start
request is removed.
Description of Controls
Page 61 of 90
057-233 ISSUE: 1
4.7 STOP/RESET
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Stop mode is activated by pressing the
button.
In Stop mode
, the module removes S2 from load (if necessary) and removes the start signal
given to the generator controller (if S2 is configured as a generator and it is running).
If S2 is configured as a generator and it does not stop after the cooling down time, the Fail To Stop
alarm is activated (subject to if the Fail To Stop timer is enabled and its duration). To detect the
generator (S2) is at rest the following must occur:
•
S2 Frequency must be zero
•
S2 Voltage must be zero
Any latched alarms that have been cleared are reset when Stop mode
is entered.
S2 is not placed on load (or started if configured as a generator) when in Stop mode
. If remote
start signals are given, the input is ignored until Auto
mode is entered.
Description of Controls
057-233 ISSUE: 1
Page 62 of 90
4.8 MANUAL MODE
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Manual mode is activated by pressing the
button.
In Manual
mode, the module actives an output to give a start signal to an external generator
controller (if S2 is configured as a generator supply), and if required, change the state of the load
switching devices. An LED indicator beside the button confirms this action.
4.8.1 STARTING SEQUENCE
NOTE: There is no start delay in this mode of operation.
As soon as the Manual
mode button is pressed, the output to give a start signal to an external
generator controller is activated (if S2 is configured as a generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved loading voltage and frequency (if configured as a generator).
4.8.2 S2 AVAILABLE
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
In Manual
mode, the load is not transferred to S2 unless a ‘loading request’ is made and the S2
supply is within limits (if configured as a mains supply) or achieve Loading Voltage and Loading
Frequency (if configured as a generator).
A loading request can come from a number of sources.
•
Pressing the Close/Open S2
button
•
S1 supply out of limits
•
Activation of an auxiliary input that has been configured to remote start on load
•
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
Description of Controls
Page 63 of 90
057-233 ISSUE: 1
Once the load has been transferred to S2, it is not automatically transferred back to the S1 supply. To
manually transfer the load back to the mains either:
•
Pressing the Close/Open S1
button
•
Pressing the Auto
button to return to automatic mode.
•
Pressing the Start Inhibit
button to return to start inhibit mode.
For further details of breaker control, see the section entitled “controls and indications” elsewhere in
this manual.
4.8.3 STOPPING SEQUENCE
In manual mode, S2 continues to run until either:
•
Pressing the Start Inhibit
button to return to start inhibit mode.
•
Pressing the Auto
button to return to automatic mode.
Description of Controls
057-233 ISSUE: 1
Page 64 of 90
4.9 AUTOMATIC MODE
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Auto mode is activated by pressing the
button.
In Auto
mode, the module operates fully automatically, changing between the two supplies in
case of failure without user intervention. An LED indicator beside the button confirms this action.
4.9.1 WAITING IN AUTO MODE
If a starting/loading request is made, the starting sequence begins.
Starting/loading requests can be from the following sources:
•
S1 supply out of limits
•
Activation of an auxiliary input that has been configured to remote start on load or remote
start off load.
•
Activation of the inbuilt exercise scheduler.
•
Instruction from external remote telemetry devices using the RS232 or RS485 interface
4.9.2 STARTING SEQUENCE
To allow for ‘false’ start/load requests such as S1 brownouts, the Start Delay timer begins. There are
individual start delay timers for each of the different start/load request types.
When all start/load requests are removed during the Start Delay timer, the unit returns to a stand-by
state.
If a start/load request is still present at the end of the Start Delay timer, an output to give a start signal
to an external generator controller is activated (if S2 is configured as a generator).
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
If a start/load request is present but the starting sequence has not begun, an input configured to ‘Auto
Start Inhibit’ could be active.
Description of Controls
Page 65 of 90
057-233 ISSUE: 1
4.9.3 S2 AVAILABLE
In Auto
mode, the load is automatically transferred to S2 when it is within limits (if configured as a
mains supply) or achieve loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’
could be active.
A loading request can come from a number of sources.
•
S1 supply out of limits
•
Activation of an auxiliary input that has been configured to remote start on load
•
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
If all start/load requests are removed, the stopping sequence begins.
4.9.4 STOPPING SEQUENCE
The Return Delay timer operates to ensure that the start/load request has been permanently removed
and isn’t just a short term removal. In case another start request is made during the Return Delay (or
cooling down period when S2 is configured as a generator), the set returns on load.
If there are no starting requests at the end of the Return Delay timer, the load is transferred back from
the S2 to the S1 supply and the Cooling timer is initiated (when S2 is configured as a generator).
The Cooling timer allows S2 (when configured as a generator) to run off load and cool sufficiently
before the start signal to the external generator control unit is removed. This is particularly important
where turbo chargers are fitted to the engine.
After the Cooling timer has expired, the start signal given to the external generator controller is
removed..
Description of Controls
057-233 ISSUE: 1
Page 66 of 90
4.10 MODE SELECTION
NOTE: If a digital input configured to Panel Lock is active, changing module modes is not
possible. Viewing the instruments and event logs is NOT affected by panel lock.
Pressing the Mode
button sets which of the three modes below to leave the controller in.
4.10.1 TEST ON LOAD
Activate by pressing the Mode
button repeatedly until Test on Load is shown on the display, then
press the Tick
button to confirm the change. An LED indicator beside the button confirms this
action.
The Test on Load mode starts S2 (if configured as a generator) and transfers the load to S2.
4.10.1.1 STARTING SEQUENCE
As soon as the Mode
is selected and confirmed by pressing the Tick
button is pressed, the
output to give a start signal to an external generator controller is activated (if S2 is configured as a
generator)
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
4.10.1.2 S2 AVAILABLE
In Test on Load mode, the load is automatically transferred to S2 when it is within limits (if configured
as a mains supply) or had achieved loading voltage and frequency (if configured as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’
could be active.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
4.10.1.3 STOPPING SEQUENCE
In Test on Load mode, S2 continues to run on load until either:
•
Pressing the Start Inhibit
button to return to start inhibit mode.
•
Pressing the Auto
button to return to automatic mode.
Description of Controls
Page 67 of 90
057-233 ISSUE: 1
4.10.2 TEST OFF LOAD
Activate by pressing the Mode
button repeatedly until Test off Load is shown on the display, then
press the Tick
button to confirm the change. An LED indicator beside the button confirms this
action.
The Test off Load mode only starts S2 (if configured as a generator) and leave it off load.
4.10.2.1 STARTING SEQUENCE
As soon as the Mode
is selected and confirmed by pressing the Tick
button is pressed, the
output to give a start signal to an external generator controller is activated (if S2 is configured as a
generator)
If the generator fails to start during the S2 Fail Delay timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
4.10.2.2 S2 AVAILABLE
In Test Off Load mode, the load is not transferred to S2 unless a ‘loading request’ is made and the S2
supply is within limits (if configured as a mains supply) or has achieved loading voltage and frequency
(if configured as a generator).
A loading request can come from a number of sources.
•
S1 supply out of limits
•
Activation of an auxiliary input that has been configured to remote start on load
•
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
4.10.2.3 STOPPING SEQUENCE
In Test off Load mode, S2 continues to run on load until either:
•
Pressing the Start Inhibit
button to return to Start Inhibit mode.
•
Pressing the Auto
button to return to Automatic mode.
Description of Controls
057-233 ISSUE: 1
Page 68 of 90
4.10.3 PROHIBIT RETURN
Activate by pressing the Mode
button repeatedly until Prohibit Return is shown on the display,
then press the Tick
button to confirm the change. An LED indicator beside the button confirms
this action.
The Prohibit Return mode prevents the load being transfer back to the S1 from the S2 supply until the
module is instructed to do so.
4.10.3.1 WAITING IN PROHIBIT RETURN
If a starting/loading request is made, the starting sequence begins.
Starting/loading requests can be from the following sources:
•
S1 supply out of limits
•
Activation of an auxiliary input that has been configured to Remote Start On Load or Remote
Start Off Load.
•
Activation of the inbuilt exercise scheduler.
•
Instruction from external remote telemetry devices using the RS232 or RS485 interface
4.10.3.2 STARTING SEQUENCE
To allow for ‘false’ start/load requests such as S1 brownouts, the Start Delay timer begins. There are
individual Start Delay timers for each of the different start/load request types.
When all start/load requests are removed during the Start Delay timer, the unit returns to a stand-by
state.
If a start/load request is still present at the end of the Start Delay timer, an output to give a start signal
to an external generator controller is activated (if S2 is configured as a generator).
If the generator fails to start during the ‘S2 Fail Delay’ timer, an alarm appears on the display which
shows Fail to Start. S2 is seen as available once the supply is within limits (if configured as a mains
supply) or had achieved Loading Voltage and Loading Frequency (if configured as a generator).
If a start/load request is present but the starting sequence has not begun, an input configured to ‘Auto
Start Inhibit’ could be active.
Description of Controls
Page 69 of 90
057-233 ISSUE: 1
4.10.3.3 S2 AVAILABLE
In Prohibit Return mode, the load is automatically transferred to S2 when it is within limits (if
configured as a mains supply) or has achieved Loading Voltage and Loading Frequency (if configured
as a generator).
If a start/load request is present but S2 does not go on load, an input configured to ‘S2 Load Inhibit’
could be active.
A loading request can come from a number of sources.
•
S1 supply out of limits
•
Activation of an auxiliary input that has been configured to Remote Start On Load
•
Activation of the inbuilt exercise scheduler if configured for ‘on load’ runs.
NOTE: The load transfer signal remains inactive until S2 is seen as available. This
prevents loading to a supply that has failed or is not yet available.
As the load increases and decreases, the module may (depending upon configuration) remove non-
essential loads. This is configured as part of the Load Shedding control settings in the DSE
Configuration Suite Software.
See section entitled Load Shedding elsewhere in this document for further details.
If all start/load requests are removed, the Stopping sequence begins.
4.10.3.4 STOPPING SEQUENCE
In Return Inhibit mode, S2 continues to run on load even if S1 has return until either:
•
Pressing the Start Inhibit
button to return to start inhibit mode.
•
Pressing the Auto
button to return to automatic mode.
Description of Controls
057-233 ISSUE: 1
Page 70 of 90
4.11 SCHEDULER
The controller contains an inbuilt exercise run scheduler, capable of automatically starting and
stopping the set. Up to 16 scheduled start/stop sequences can be configured in banks of 8 to either
repeat on a 7-day or 28-day cycle.
Scheduled runs may be on load or off load depending upon module configuration.
Example
Screen capture from DSE
Configuration Suite
Software showing the
configuration of the
Exercise Scheduler.
In this example the set
starts at 09:00 on the first
Monday of each month and
run for 5 hours, then start
at 13:30 on every Tuesday
and run for 30 minutes.
4.11.1 STOP MODE
•
Scheduled runs do not occur when the module is in Stop
mode.
4.11.2 MANUAL MODE
•
Scheduled runs do not occur when the module is in Manual
mode.
•
Activation of a Scheduled Run ‘On Load’ when the module is operating Off Load in Manual
mode has no effect, the set continues to run Off Load
4.11.3 AUTO MODE
•
Scheduled runs operate ONLY if the module is in Auto
mode with no Electrical Trip alarm
present.
•
If the module is in Stop
or Manual
mode when a scheduled run begins, S2 is not
started (if configured as generator). However, if the module is moved into Auto
mode
during a scheduled run, S2 is called to start.
•
Depending upon configuration by the system designer, an external input can be used to
inhibit a scheduled run.
•
If S2 is Off Load in Auto
mode and a scheduled run configured to ‘Transfer to S2’ begins,
S2 is placed On Load for the duration of the Schedule.
Description of Controls
Page 71 of 90
057-233 ISSUE: 1
4.12 LOAD SHEDDING CONTROL
This feature may be enabled by the system designer to ensure the loading on S2 is kept to a nominal
amount. Conversely as the load increases towards the maximum rating of the set, non-essential loads
can be shed to prevent overload of S2.
4.12.1 LOAD SHEDDING CONTROL
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
The Load Shedding Control feature (if enabled) allows for a maximum of five load shedding steps.
When S2 is about to take load, the configured number of Load Shedding Control Outputs at Startup
energises. This configurable setting allows (for instance) certain loads to be removed from S2 prior to
the set’s load switch being closed. This can be used to ensure the initial loading of the set is kept to a
minimum, below the Load Acceptance specification of S2.
S2 is then placed on load. The Load Shedding Control scheme begins.
When the load reaches the Load Shedding Trip level the Trip Delay timer starts. If S2 loading is still
high when the timer expires, the first Load shedding Control output energises. When the load has
been above the trip level for the duration of the timer the ‘next’ Load shedding Control output
energises and so on until all Load Shedding Control outputs are energised.
If at any time the load falls back below the Load Shedding Return level, the Return Time starts. If the
load remains below the return level when the timer has expired the ‘highest’ Load Shedding Control
output that has been energised is de-energised. This process continues until all outputs have been
de-energised.
When the set enters a stopping sequence for any reason the Load Shedding control’ outputs are de-
energised at the same time as the S2 load switch is signalled to open.
057-233 ISSUE: 1
Page 72 of 90
5 PROTECTIONS
When an alarm is present, the Audible Alarm sounds and the Common alarm LED if configured
illuminates.
The audible alarm can be silenced by pressing the Alarm Mute
The LCD display jumps from the ‘Information page’ to display the Alarm Page
1/2 Alarm
S1 Failure
Latched
Warning
The LCD displays multiple alarms E.g. “S1 Failure Warning”, “Fail to Stop Warning” and “Digital Input
A Electrical Trip”. These automatically scroll in the order that they occurred.
In the event of a warning alarm, the LCD displays the appropriate text. If an electrical trip then occurs,
the module again displays the appropriate text.
Example:-
Alarm 1/2
Fail to Stop
Unlatched
Warning
Alarm 2/2
Digital Input A
Unlatched
Electrical Trip
The nature of alarm, e.g. S1 Failure
The type of alarm. E.g. Electrical Trip or warning
Number of present alarms. This is alarm 1 of a
total of 2 present alarms
If the alarm automatically resets (unlatched) or
needs to be manually reset (latched).
Page 73 of 90
057-233 ISSUE: 1
5.1 INDICATIONS
Indications are non-critical and often status conditions. They do not appear on the LCD of the module
as a text message. However, an output or LED indicator can be configured to draw the operator’s
attention to the event.
Example
•
Input configured for
indication.
•
The LCD text does not
appear on the module
display but can be added
in the configuration to
remind the system
designer what the input is
used for.
•
As the input is configured
to Indication there is no
alarm generated.
•
LED Indicator to make
LED1 illuminate when
Digital Input A is active.
•
The Insert Card Text
allows the system
designer to print an insert
card detailing the LED
function.
•
Sample showing
operation of the LED.
057-233 ISSUE: 1
Page 74 of 90
5.2 WARNINGS
Warnings are non-critical alarm conditions and do not affect the operation of the system, they serve to
draw the operators attention to an undesirable condition.
Example
1/2 Alarm
S1 Failure
Latched
Warning
In the event of an alarm the LCD jumps to the alarms page, and scroll through all active warnings and
shutdowns.
By default, warning alarms are self-resetting when the fault condition is removed. However some
warning alarms are latched and need to be reset manually.
Display
Reason
Auxiliary Inputs
If an auxiliary input has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
Battery Under Voltage
The DC supply has fallen below the low volts setting level for the
duration of the low battery volts timer
Battery Over Voltage
The DC supply has risen above the high volts setting level for the
duration of the high battery volts timer
Calibration Lost
The module has lost its calibration settings and must be sent back to
DSE to be re-calibrated.
Expansion Inputs
If an expansion input has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
Fail To Start
S2 has not reached the configured limits or loading voltage and
frequency before the S2 Fail Delay timer has expired.
Fail To Stop
The module has detected a condition that indicates that S2 is present
when it has been instructed to stop.
Loading Voltage Not
Reached
Indicates that the S2 voltage is not above the configured loading
voltage. S2 does not take load when the alarm is present after the
safety timer.
NOTE: Only applicable when S2 is configured as a generator
supply.
Loading Frequency Not
Reached
Indicates that the S2 frequency is not above the configured loading
frequency. S2 does not take load when the alarm is present after the
safety timer.
NOTE: Only applicable when S2 is configured as a generator
supply.
Page 75 of 90
057-233 ISSUE: 1
Display
Reason
PLC Functions
If a PLC Function has been configured as a warning the appropriate
LCD message is displayed and the COMMON ALARM LED illuminates.
S1 Breaker Auxiliary Fail
Indicates that the S1 Closed Auxiliary input has not activated along with
the Close S1 Output or Open S1 Output, or the input has activated
when the output was not energised.
S1 Failure Unlatched
The module has detected that S1 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S1 returning to an available state.
S1 Phase Rotation
The module has detected a wrong phase sequence for S1.
S2 Breaker Auxiliary Fail
Indicates that the S2 Closed Auxiliary input has not activated along with
the Close S2 Output or Open S2 Output, or the input has activated
when the output was not energised.
S2 Failure Unlatched
The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S2 returning to an available state.
S2 Phase Rotation
The module has detected a wrong phase sequence for S2.
5.3 ELECTRICAL TRIPS
Electrical trips are latching unload and stop S2 (if configured as a generator) but in a controlled
manner. On initiation of the electrical trip condition the module de-energises the ‘Close S2 Output’ to
remove the load from S2. Once this has occurred the module starts the Cooling timer and allow the
generator to cool down and shut off. The alarm must be accepted and cleared, and the fault removed
to reset the module.
Example
1/2 Alarm
Digital Input A
Latched
Electrical Trip
Electrical trips are latching alarms and unload and stop S2 (if configured as a generator). To clear
these alarms the STOP
button is pressed
Display
Reason
Auxiliary Inputs
If an auxiliary input has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates.
Expansion Inputs
If an expansion input has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates.
PLC Functions
If a PLC Function has been configured as an electrical trip, the
appropriate LCD message is displayed and the COMMON ALARM LED
illuminates.
S1 Breaker Auxiliary Fail
Indicates that the S1 Closed Auxiliary input has not activated along with
the Close S1 Output or Open S1 Output, or the input has activated
when the output was not energised.
S1 Phase Rotation
The module has detected a wrong phase sequence for S1.
S2 Failure Unlatched
The module has detected that S2 has failed for either an under/over
voltage/frequency condition. The unlatched alarm is automatically
cleared upon S2 returning to an available state.
S2 Phase Rotation
The module has detected a wrong phase sequence for S2.
Front Panel Configuration
057-233 ISSUE: 1
Page 76 of 90
6 FRONT PANEL CONFIGURATION
This configuration mode allows the operator limited customising of the way the module operates.
Use the module’s navigation buttons to traverse the menu and make value changes to the
parameters:
Previous page
Increase value / next item
Decrease value / next item
Front Panel Configuration
Page 77 of 90
057-233 ISSUE: 1
6.1 ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR
Press and hold the Stop
and Tick
buttons simultaneously to
enter the editor.
If a module security PIN has been set, the PIN number request is then
shown :
Editor
# # # #
Press the Tick
button, the first ‘#’ changes to ‘0’. Press
(up or down) to adjust it to the correct
value.
Press
(right) when the first digit is correctly entered. The digit entered is now shown as ‘#’ for
security.
Repeat this process for the other digits of the PIN number. Press
(left) to move back and adjust
one of the previous digits.
When the Tick
button is pressed after editing the final PIN digit, the PIN is checked for validity. If the
number is not correct, re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not
been enabled), the editor is displayed :
Editor - Display
Contrast
54 %
NOTE: The PIN number is not set by DSE when the module leaves the factory. If the
module has a PIN code set, this has been affected by the ATS supplier who must be contacted
if the code is required. If the code has been ‘lost’ or ‘forgotten’, the module must be returned
to the DSE factory to have the module’s code removed. A charge is applied for this procedure.
NB - This procedure cannot be performed away from the DSE factory.
Front Panel Configuration
057-233 ISSUE: 1
Page 78 of 90
6.1.1 EDITING A PARAMETER
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details on
configuring, monitoring and control.
Enter the editor as described above.
Press the
(left) or
(right) buttons to cycle to the section to view/change.
Press the
(up or down) buttons to select the parameter to view/change within the currently
selected section.
To edit the parameter, press the Tick
button to enter edit mode. The parameter begins to flash to
indicate that value is being edited.
Press the
(up or down) buttons to change the parameter to the required value.
Press the Tick
button to save the value. The parameter ceases flashing to indicate that it has been
saved.
To exit the editor at any time, press and hold the Tick
button.
Front Panel Configuration
Page 79 of 90
057-233 ISSUE: 1
6.2 ADJUSTABLE PARAMETERS
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
Section
Parameter As Shown On Display
Values
Display
LCD Contrast
0%
Language
English
LCD Page Timer
hh:mm:ss
Scroll Delay
hh:mm:ss
Date and Time
dd-mm-yyyy, hh:mm:ss
S1
S1 Option
Generator, Mains
Immediate S1 Dropout
Inactive, Active
Under Voltage Trip
0 V
Over Voltage Trip
0 V
Under Frequency Trip
0 Hz
Over Frequency Trip
0 Hz
S2
S2 Option
Generator, Mains
Immediate S2 Dropout
Inactive, Active
Under Voltage Trip (Generator Option)
0 V
Over Voltage Trip (Generator Option)
0 V
Under Frequency Trip (Generator Option)
0.0 Hz
Over Frequency Trip (Generator Option)
0.0 Hz
Under Voltage Trip (Mains Option)
0 V
Over Voltage Trip (Mains Option)
0 V
Under Frequency Trip (Mains Option)
0.0 Hz
Over Frequency Trip (Mains Option)
0.0 Hz
Timers
S1 Transient Delay
mm:ss
Start Delay
hh:mm:ss
Warming Up Time
hh:mm:ss
S2 Fail Delay
mm:ss
Elevator Delay
mm:ss
Non-sync Transfer Time
mm:ss.s
Check-Sync Transfer time
mm:ss.s
Return Delay
hh:mm:ss
Cooling Time
hh:mm:ss
Fail to Stop Enable
Inactive, Active
Fail to Stop Delay
mm:ss
S2 Transient Delay
s.s
Parameters continue overleaf...
Front Panel Configuration
057-233 ISSUE: 1
Page 80 of 90
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
Section
Parameter As Shown On Display
Values
Scheduler
Bank 1
Scheduler Enable
Inactive, Active
Bank 1 Run Mode
Do Not Transfer
Transfer to S1
Transfer to S2
S1 Off Load (When S1 = Gen)
S2 Off Load (When S2 = Gen)
Bank 1 Period
Weekly, Monthly
Bank 1 Event 1 Week
1-4
Bank 1 Event 1 Day
Monday to Sunday
Bank 1 Event 1 Start Time
hh:mm
Bank 1 Event 1 Duration
hh:mm
Bank 1 Event 2 Week
1-4
Bank 1 Event 2 Day
Monday to Sunday
Bank 1 Event 2 Start Time
hh:mm
Bank 1 Event 2 Duration
hh:mm
Bank 1 Event 3 Week
1-4
Bank 1 Event 3 Day
Monday to Sunday
Bank 1 Event 3 Start Time
hh:mm
Bank 1 Event 3 Duration
hh:mm
Bank 1 Event 4 Week
1-4
Bank 1 Event 4 Day
Monday to Sunday
Bank 1 Event 4 Start Time
hh:mm
Bank 1 Event 4 Duration
hh:mm
Bank 1 Event 5 Week
1-4
Bank 1 Event 5 Day
Monday to Sunday
Bank 1 Event 5 Start Time
hh:mm
Bank 1 Event 5 Duration
hh:mm
Bank 1 Event 6 Week
1-4
Bank 1 Event 6 Day
Monday to Sunday
Bank 1 Event 6 Start Time
hh:mm
Bank 1 Event 6 Duration
hh:mm
Bank 1 Event 7 Week
1-4
Bank 1 Event 7 Day
Monday to Sunday
Bank 1 Event 7 Start Time
hh:mm
Bank 1 Event 7 Duration
hh:mm
Bank 1 Event 8 Week
1-4
Bank 1 Event 8 Day
Monday to Sunday
Bank 1 Event 8 Start Time
hh:mm
Bank 1 Event 8 Duration
hh:mm
Parameters continue overleaf...
Front Panel Configuration
Page 81 of 90
057-233 ISSUE: 1
NOTE: Refer to DSE335 Configuration Suite Manual (DSE part 057-237) for further details
on configuring, monitoring and control.
Section
Parameter As Shown On Display
Values
Scheduler
Bank 2
Bank 2 Run Mode
Do Not Transfer
Transfer to S1
Transfer to S2
S1 Off Load (When S1 = Gen)
S2 Off Load (When S2 = Gen)
Bank 2 Period
Weekly, Monthly
Bank 2 Event 1 Week
1-4
Bank 2 Event 1 Day
Monday to Sunday
Bank 2 Event 1 Start Time
hh:mm
Bank 2 Event 1 Duration
hh:mm
Bank 2 Event 2 Week
1-4
Bank 2 Event 2 Day
Monday to Sunday
Bank 2 Event 2 Start Time
hh:mm
Bank 2 Event 2 Duration
hh:mm
Bank 2 Event 3 Week
1-4
Bank 2 Event 3 Day
Monday to Sunday
Bank 2 Event 3 Start Time
hh:mm
Bank 2 Event 3 Duration
hh:mm
Bank 2 Event 4 Week
1-4
Bank 2 Event 4 Day
Monday to Sunday
Bank 2 Event 4 Start Time
hh:mm
Bank 2 Event 4 Duration
hh:mm
Bank 2 Event 5 Week
1-4
Bank 2 Event 5 Day
Monday to Sunday
Bank 2 Event 5 Start Time
hh:mm
Bank 2 Event 5 Duration
hh:mm
Bank 2 Event 6 Week
1-4
Bank 2 Event 6 Day
Monday to Sunday
Bank 2 Event 6 Start Time
hh:mm
Bank 2 Event 6 Duration
hh:mm
Bank 2 Event 7 Week
1-4
Bank 2 Event 7 Day
Monday to Sunday
Bank 2 Event 7 Start Time
hh:mm
Bank 2 Event 7 Duration
hh:mm
Bank 2 Event 8 Week
1-4
Bank 2 Event 8 Day
Monday to Sunday
Bank 2 Event 8 Start Time
hh:mm
Bank 2 Event 8 Duration
hh:mm
057-233 ISSUE: 1
Page 82 of 90
7 COMMISSIONING
Before the system is started, it is recommended that the following checks are made:-
•
The unit is adequately cooled and all the wiring to the module is of a standard and rating
compatible with the system. Check all mechanical parts are fitted correctly and that all electrical
connections (including earths) are sound.
•
The unit DC supply is fused and connected to the battery and that it is of the correct polarity.
•
To check the start cycle operation, take appropriate measures to prevent S2 from starting (if
configured as a generator by disconnecting the start output) and press the Manual
mode
button. Check to see if the start signal energises.
•
Set the modules internal clock/calendar to ensure correct operation of the scheduler and event
logging functions. For details of this procedure see section entitled Front Panel Configuration –
Editing the date and time.
•
If, despite repeated checking of the connections between the controller and the customer’s
system, satisfactory operation cannot be achieved, then the customer is requested to contact the
DSE Technical Support Department for further advice.
057-233 ISSUE: 1
Page 83 of 90
8 FAULT FINDING
8.1 STARTING
Symptom
Possible Remedy
Unit is inoperative
Read/Write configuration
does not operate
Check the battery and wiring to the unit. Check the DC supply. Check
the DC fuse.
Unit shuts down
Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70 °C. Check the DC
fuse.
Fail to Start is activated
Check wiring of the S2 sensing cables. Check the start output is
correctly wired into the generator controller.
Continuous starting of S2
when in Auto
mode.
Check that there is no signal present on the “Remote Start” input.
Check configured polarity is correct.
Check the S2 supply available and within configured limits
S2 fails to start or go on load
on receipt of Remote Start
signal.
Check S2 Fail Delay timer has timed out.
Check signal is on “Remote Start” input. Confirm correct configuration
of input is configured to be used as “Remote Start”.
8.2 LOADING
Symptom
Possible Remedy
S2 supply present runs but
does not take load
Ensure S2 is available and within configured limits and a load inhibit
signal is not present on the module inputs. Check connections to the
switching device.
Note that S2 does not take load in manual mode unless there is an
active remote start on load signal.
8.3 ALARMS
Symptom
Possible Remedy
Electrical Trip fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
Warning fault operates
Check relevant switch and wiring of fault indicated on LCD display.
Check configuration of input.
057-233 ISSUE: 1
Page 84 of 90
8.4 COMMUNICATIONS
Symptom
Possible Remedy
RS485 inoperative
Check :
•
Connection cable – Belden 9841 or equivalent
•
120 Ω termination resistors are correctly fitted
•
Baud rate of controller and of master device are the same
•
Slave ID of the controller is the same as configured in the
master device
RS232 connection to PC
inoperative
Check :
•
RS232 maximum of 15 m is not exceeded
•
Direct to PC connection requires a Crossover (NULL modem)
RS232 cable
•
Baud rate of controller and of master device are the same
•
Slave ID of the controller is the same as configured in the
master device
RS232 connection to GSM
modem inoperative
Check :
•
RS232 maximum of 15 m is not exceeded
•
Modem Initialisation strings in the DSE configuration is correct
for the connected modem type
•
Modem is configured to 9600 baud
•
SIM card is CSD (circuit switched data) compatible
•
SIM card is not PIN locked
•
SIM card is correctly inserted
•
Antenna is correctly installed and is not inside an earthed
metal cabinet / control panel
•
A good signal is available in the locality
RS232 connection to
landline modem inoperative
Check :
•
RS232 maximum of 15 m is not exceeded
•
Modem Initialisation strings in the DSE configuration is correct
for the connected modem type
•
Modem is configured to 9600 baud
8.5 INSTRUMENTS
Symptom
Possible Remedy
Inaccurate S1 & S2
measurements on controller
display
Check that the CT primary, CT secondary and VT ratio settings are
correct for the application.
Check that the CTs are wired correctly with regards to the direction of
current flow (p1,p2 and s1,s2) and additionally ensure that CTs are
connected to the correct phase (errors occur if CT1 is connected to
phase 2).
Remember to consider the power factor. Ie (kW = kV A x powerfactor)
The controller is true RMS measuring so gives more accurate display
when compared with an ‘averaging’ meter such as an analogue panel
meter or some lower specified digital multimeters.
Accuracy of the controller is better than 1% of full scale. Ie S1 volts
full scale is 333 V ph-n so accuracy is ±3.33 V (1% of 333 V).
Page 85 of 90
057-233 ISSUE: 1
8.6 MISCELLANEOUS
NOTE: The above fault finding is provided as a guide check-list only. As the module can
be configured to provide a wide range of different features, always refer to the source of the
module configuration if in doubt.
Symptom
Possible Remedy
Module appears to ‘revert’ to
an earlier configuration
When editing a configuration using the PC software it is vital that the
configuration is first ‘read’ from the controller before editing it. This
edited configuration must then be “written” back to the controller for
the changes to take effect.
When editing a configuration using the fascia editor, be sure to press
the Tick
button to save the change before moving to another item
or exiting the fascia editor
Maintenance, Spares, Repairs and Servicing
86
9 MAINTENANCE, SPARES, REPAIR AND SERVICING
The controller is Fit and Forget. As such, there are no user serviceable parts within the controller.
In the case of malfunction, contact the original equipment manufacturer (OEM).
9.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE
If additional plugs are required from DSE, please contact our sales department using the part numbers below.
9.1.1 PACK OF PLUGS
Module type
Plug Pack Part Number
DSE335
100-400-35
9.1.2 INDIVIDUAL PLUGS
Module Terminal Designation
Plug Description
Part No.
1-8
8 way 5.08 mm
007-164
9-17
9 way 5.08 mm
007-167
18-24
7 way 5.08 mm
007-447
25-29
5 way 7.62 mm
007-473
30-37
S2
8 way 7.62 mm
007-454
38-41
S1
4 way 7.62 mm
007-171
42-47
6 way 5.08 mm
007-446
48-53
6 way 7.62 mm
007-162
RS485
3 way 5.08 mm
007-174
NOTE: Terminals 24 and 27 are fitted to controllers but must not be connected.
9.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE
Item
Description
Part No.
Module fixing clips (packet of 4)
020-294
9.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE
Item
Description
Part No.
Module silicon sealing gasket
020-507
Maintenance, Spares, Repairs and Servicing
057-233 ISSUE: 1
Page 87 of 90
9.4 DSENET EXPANSION MODULES
NOTE: A maximum of six (6) expansion modules can be connected to the DSENet®.
NOTE: DSENet® utilises an RS485 connection. Using Belden 9841 (or equivalent) cable
allows for the expansion cable to be extended to a maximum of 1.2 km.
DSE Stock and supply Belden 9841 cable. DSE Part Number 016-030.
Item
Description
DSE Part Numbers
Max No.
supported
Model
order
number
Sales
literature
Operator
manual
Installation
Instructions
2
Model DSE2130 input module provides
additional analogue and digital inputs for
use with the controller.
2130-001-00
055-060
057-082
053-033
2
Model DSE2157 expansion relay module
provides eight additional voltage free
relays for use with the controller
2157-001-00
055-061
057-083
053-034
2
Model DSE2548 expansion LED module
provides additional LED indications,
internal sounder and remote lamp
test/alarm mute for use with the
controller.
2548-001-00
055-062
057-084
053-032
Warranty and Disposal
057-233 ISSUE: 1
Page 88 of 90
10 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any
applicable warranty, refer to the original equipment supplier (OEM).
11 DISPOSAL
11.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of
WEEE separately from your other waste.