Eaton BladeUPS Maintenance Bypass Module (MBM) User’s Guide 164201785—Rev 2

www.eaton.com/powerquality Table 12. Environmental and Safety BladeUPS MBM LV BladeUPS MBM HV Surge Suppression ANSI C62.41 Category B3 EN 61000-4-6 Safety Conformance UL 1778 4th edition; CSA C22.2, No. 107.3 EN and IEC 62040-1-1 Agency Markings cULus, ICES cULus, CE EMC (Class A) N/A N/A Operating Temperature 0C to 40C (32F to 104F) Storage Temperature 0C to 25C (32F to 77F) Transit Temperature -25C to 55C (-13F to 131F) Relative Humidity Operating: 595% no ...

Eaton BladeUPS Maintenance Bypass Module (MBM) User’s Guide

164201785—Rev 2 www.eaton.com/powerquality 29 Installing a Remote Emergency Power-off The REPO is used to shut down the MBM bypass from a distance. When the REPO is activated, the MBM opens the Bypass breaker and removes power from the critical load if the MBM is in Bypass mode. If the MBM is in Normal mode, the load will continue to be powered by the UPS. To remove power from the load, the REPO connected to the UPS must be activated. CAUTION l The REPO switch must have a minimum rating of 250 Vac at 20 mA and be a n ...

Eaton BladeUPS Maintenance Bypass Module (MBM) User’s Guide

164201785—Rev 2 www.eaton.com/powerquality 27 3. Configure signal input 2: a. Select INPUT 2 and press the button to enter the setting mode. b. Select request bypass and press the button to save the setting. c. Logic 1 is the default. The following screen text displays: Signal: INPUT 2 Logic: 1 d. Press the button to save the setting. 4. Configure the relay: a. Press the button until USER SETTINGS appears. b. Select RELAY CONFIG and Relay. c. Select ALARM-1 and press the button to enter the setting m ...

Eaton BladeUPS Maintenance Bypass Module (MBM) User’s Guide

164201785—Rev 2 www.eaton.com/powerquality 33 Normal Mode Current Flow When the Bypass breaker is open and the UPS Output breaker is closed, conditioned and protected power from the UPS is routed through the UPS Output breaker to the critical load. The UPS is supplied mains power through the UPS Input breaker. Figure 21 shows the path of electrical power through the MBM when operating in UPS mode. Figure 21. Path of Current Through the MBM in UPS Mode Bypass Mode Current Flow A bypass circuit with a Bypass breaker is use ...

Eaton BladeUPS Maintenance Bypass Module (MBM) User’s Guide 164201785—Rev 2

www.eaton.com/powerquality Figure 20. BladeUPS MBM Controls and Indicators Operating Modes WARNING Power is present inside the UPS cabinet until the UPS battery breakers are turned off. The MBM enables power to completely bypass and isolate the UPS so that the UPS can be safely serviced or replaced without interrupting power to critical systems. The MBM consists of a UPS Input breaker, a UPS Output breaker, and a Bypass breaker. The Bypass breaker transfers the load from the UPS output to the mains inp ...

Eaton BladeUPS Maintenance Bypass Module (MBM) User’s Guide

164201785—Rev 2 www.eaton.com/powerquality 1 Chapter 1 Introduction The Eaton® BladeUPS® Maintenance Bypass Module (MBM) is a three-breaker maintenance bypass. The MBM is designed to operate with the BladeUPS 12 kVA three-phase uninterruptible power supply (UPS) in a fully populated 60 kW N+1 system. The MBM enables power to completely bypass and isolate the UPS so that the UPS can be safely serviced, upgraded, or replaced without interrupting power to critical systems. Figure 1 shows the BladeUPS MBM and Figure 2 shows a typica ...

Eaton BladeUPS Maintenance Bypass Module (MBM) User’s Guide 164201785—Rev 2

www.eaton.com/powerquality Table 12. Environmental and Safety BladeUPS MBM LV BladeUPS MBM HV Surge Suppression ANSI C62.41 Category B3 EN 61000-4-6 Safety Conformance UL 1778 4th edition; CSA C22.2, No. 107.3 EN and IEC 62040-1-1 Agency Markings cULus, ICES cULus, CE EMC (Class A) N/A N/A Operating Temperature 0C to 40C (32F to 104F) Storage Temperature 0C to 25C (32F to 77F) Transit Temperature -25C to 55C (-13F to 131F) Relative Humidity Operating: 595% no ...

Eaton BladeUPS user guide recommended for: 5SC 1000i Rack2U, Power Xpert 9395 550, 9135, Power Xpert 9395 Plus, 9E-IN 1K.

⚠️ Download Safety

The UPS Operation & user’s manual (58 pages) is completely safe to download (last scan date: 07/01/2026).

Related PDF Instructions for Eaton BladeUPS:

UPS Equipment: Frequently Requested

Have some Questions about Eaton BladeUPS Device?

Get valuable and actionable advices from other Eaton BladeUPS device users. Describe your problem or question, regarding the using of BladeUPS, in as much detail as possible, and other users will be able to answer you.