FHP AP025 Installation Manual
Text of the manual
970-292 Revised 5-12
AP SERIES
Table of Contents
Model Nomenclature ..................................................................................................................1
Initial Inspection............................................................................................................................2
General Description.....................................................................................................................2
Moving and Storage....................................................................................................................2
Safety Considerations .................................................................................................................2
Location............................................................................................................................................2
Installation.......................................................................................................................................2
Condensate Drain.........................................................................................................................3
Duct System....................................................................................................................................3
Piping................................................................................................................................................3
Electrical...........................................................................................................................................4
Thermostat Connections ...........................................................................................................4
Safety Devices & the UPM Controller....................................................................................5
Electric Heater Package Option...............................................................................................6
Sequence of Operation Single Stage Units.........................................................................7
Sequence of Operation Two-Stage Units............................................................................7
Well Water Systems .....................................................................................................................7
Installation of Pressure Regulating Valves ..........................................................................7
Cooling Tower / Boiler Application........................................................................................7
Earth Coupled Systems...............................................................................................................8
System Checkout..........................................................................................................................8
Unit Start-Up...................................................................................................................................8
Maintenance...................................................................................................................................8
Wiring Diagrams ...........................................................................................................................9
Trouble Shooting .......................................................................................................................13
Unit Check Out............................................................................................................................14
Operating Pressures & Temperatures.................................................................................15
MODEL NOMENCLATURE
SERIES:
AP-AQUARIUS II
NOMINAL CAPACITY:
VOLTAGE DESIGNATION:
1 - 208/1/60 & 230/1/60
CABINET CONFIGURATION:
VT - VERTICAL
HZ - HORIZONTAL
CF - COUNTERFLOW
HEAT EXCHANGER MATERIAL:
C - COPPER
N - CUPRO-NICKEL
SUPPLY AIR LOCATION:
T - TOP (VT ONLY)
E - END BLOW (HZ ONLY)
B - BOTTOM (CF ONLY)
RETURN AIR LOCATION:
L - LEFT
R - RIGHT
B - BACK
F - FRONT
WATER CONNECTION
LOCATION:
F - FRONT
AP
049
-1
VT
C - F
L
T
Be certain to inspect all cartons or crates on each unit as
received at the job site before signing the freight bill. Verify
that all items have been received and that there are no
visible damages; note any shortages or damages on all
copies of the freight bill. In the event of damage or
shortage, remember that the purchaser is responsible for
filing the necessary claims with the carrier. Concealed
damages not discovered until after removing the units from
the packaging must be reported to the carrier within 24
hours of receipt.
GENERAL DESCRIPTION:
These Water-to-Air Heat Pumps provide the best
combination of performance and efficiency available.
Safety devices are built into each unit to provide the
maximum system protection possible when properly
installed and maintained.
The AP Water-to-Air Heat Pumps are Underwriters
Laboratories (UL) and (cUL) listed for safety. The water-to-
Air Heat Pumps are designed to operate with entering fluid
temperature between 20°F to 80°F in the heating mode and
between 50°F to 110°F in the cooling mode.
NOTE: 50°F Min. EWT for well water applications with
sufficient water flow to prevent freezing. Antifreeze
solution is required for all closed loop applications. Cooling
Tower/Boiler and Earth Coupled (Geo Thermal) applications
should have sufficient antifreeze solution to protect against
extreme conditions and equipment failure. Frozen water
coils are not covered under warranty.
NOTE: This product should not be used for temporarily
heating/cooling during construction. Doing so may effect
the units warranty.
MOVING AND STORAGE:
If the equipment is not needed for immediate installation
upon its arrival at the job site, it should be left in its
shipping carton and stored in a clean, dry area. Units must
only be stored or moved in the normal upright position as
indicated by the "UP" arrows on each carton at all times. If
unit stacking is required, stack units as follows: Vertical
units less than 6 tons, no more than two high. Horizontal
units less than 6 tons, no more than three high. "Do not
stack units larger than 6 tons."
SAFETY CONSIDERATIONS:
Installation and servicing of this equipment can be
hazardous due to system pressure and electrical
components. Only trained and qualified personnel should
install, repair, or service the equipment. Untrained
personnel can perform basic functions of maintenance
such as cleaning coils and replacing filters.
WARNING: Before performing service or maintenance
operations on the system, turn off main power to the unit.
Electrical shock could cause personal injury or death.
When working on equipment, always observe precautions
described in the literature, tags, and labels attached to the
unit. Follow all safety codes. Wear safety glasses and work
gloves. Use a quenching cloth for brazing, and place a fire
extinguisher close to the work area.
LOCATION:
Locate the unit in an indoor area that allows easy removal
of the filter and access panels, and has enough room for
service personnel to perform maintenance or repair.
Provide sufficient room to make fluid, electrical, and duct
connection(s). If the unit is located in a confined space such
as a closet, provisions must be made for return air to freely
enter the space. On horizontal units, allow adequate room
below the unit for a condensate drain trap and do not
locate the unit above supply piping. These units are not
approved for outdoor installation; therefore, they must be
installed inside the structure being conditioned. Do not
locate in areas that are subject to freezing.
INSTALLATION:
NOTE: Remove all shipping blocks under blower housing.
Loosen compressor mounting bolts.
MOUNTING VERTICAL UNITS:
Vertical units up to six tons are available in left, right, front,
or rear air return configurations. Vertical units should be
mounted level on a vibration absorbing pad slightly larger
than the base to minimize vibration transmission to the
building structure. It is not necessary to anchor the unit to
the floor. (See Figure #1).
MOUNTING HORIZONTAL UNITS:
While horizontal units may
be installed on any level
surface strong enough to
hold their weight, they are
typically suspended above a
ceiling by threaded rods.
The rods are usually
attached to the unit corners
by hanger bracket kits (P/N
930-008). (See Figure #2).
The rods must be
securely anchored to the
ceiling and be capable of
supporting the unit weight.
Refer to the
hanging bracket assembly
and installation instructions included with the unit for details.
Horizontal units installed above the ceiling must conform to all
local codes. An auxiliary drain pan if required by code should
be at least four inches larger than the bottom of the heat
pump. Plumbing connected to the heat pump must not come
in direct contact with joists, trusses, walls, etc.
Some applications
require an attic floor
installation of the
horizontal unit. In this
case the unit should be
set in a full size
secondary drain pan on
top of a vibration
absorbing mesh. The
secondary drain pan prevents possible condensate
overflow or water leakage damage to the ceiling. The
970-292 Revised 5-12
AP SERIES
(Figure #2)
(Figure #1)
VIBRATION
PAD
FULL SIZE
2
970-292 Revised 5-12
secondary drain pan is usually placed on a plywood base
isolated from the ceiling joists by additional layers of
vibration absorbing mesh. In both cases, a 3/4" drain
connected to this secondary pan should be run to an eave
at a location that will be noticeable. If the unit is located in
a crawl space, the bottom of the unit must be at least 4"
above grade to prevent flooding of the electrical parts due
to heavy rains.
CONDENSATE DRAIN:
NOTE: If equipped with float style condensate overflow
switch, final adjustment must be made in the field.
A drain line must be connected to the heat pump and
pitched away from the unit a minimum of 1/8" per foot to
allow the condensate to flow away from the unit.
This connection must be in conformance with local
plumbing codes. A trap must be installed in the condensate
line to insure free condensate flow. (Heat Pumps are not
internally trapped). A vertical air vent is sometimes
required to avoid air pockets. (See Figure #3). The length of
the trap depends on the amount of positive or negative
pressure on the drain pan. A second trap must not be
included.
The horizontal unit should be pitched approximately 1/4"
towards the drain in both directions, to facilitate
condensate removal. (See Figure #4)
DUCT SYSTEM:
A supply air outlet collar and return air duct flange are
provided on all units to facilitate duct connections. Refer to
the FHP individual data specification sheet for physical
dimensions of the collar and flange.
A flexible connector is recommended for supply and return
air duct connections on metal duct systems. All metal
ducting should be insulated with a minimum of one inch
duct insulation to avoid heat loss or gain and prevent
condensate forming during the cooling operation.
Application of the unit to uninsulated duct work is not
recommended as the unit’s performance will be adversely
affected. Do not connect discharge ducts directly to the
blower outlet. The factory provided air filter must be
removed when using a filter back return air grill.The factory
filter should be left in place on a free return system.
If the unit will be installed in a new installation which
includes new duct work, the installation should be
designed using current ASHRAE procedures for duct sizing.
If the unit is to be connected to existing ductwork, a check
should be made to assure that the duct system has the
capacity to handle the air required for the unit application.
If the duct system is too small, larger ductwork should be
installed. Check for existing leaks and repair.
The duct system and all diffusers should be sized to handle
the designed air flow quietly. To maximize sound
attenuation of the unit blower, the supply and return air
plenums should be insulated. There should be no direct
straight air path thru the return air grille into the heat
pump. The return air inlet to the heat pump must have at
least one 90 degree turn away from the space return air
grille. If air noise or excessive air flow are a problem, the
blower speed can be changed to a lower speed to reduce
air flow. (Refer to ECM motor interface board section in this
manual and Figure #7)
PIPING:
Supply and return piping must be as large as the unit
connections on the heat pump (larger on long runs). Never
use flexible hoses of a smaller inside diameter than that of
the fluid connections on the unit. AP units are supplied
with either a copper or optional cupro-nickel condenser.
Copper is adequate for ground water that is not high in
mineral content. Should your well driller express concern
regarding the quality of the well water available or should
any known hazards exist in your area, we recommend
proper testing to assure the well water quality is suitable
for use with water source equipment. In conditions
anticipating moderate scale formation or in brackish water
a cupro-nickel heat exchanger is recommended.
Both the supply and discharge water lines will sweat if
subjected to low water temperature. These lines should be
insulated to prevent damage from condensation.
All manual flow valves used in the system must be ball
valves. Globe and gate valves must not be used due to high
pressure drop and poor throttling characteristics. Never
exceed the recommended water flow rates as serious
damage or erosion of the water to refrigerant heat
exchanger could occur.
Always check carefully for water leaks and repair
appropriately. Units are equipped with female pipe thread
fittings. Consult the specification sheets for sizes. Teflon
tape sealer should be used when connecting water piping
connections to the units to insure against leaks and
possible heat exchanger fouling. Do not overtighten the
(Figure #3)
(Figure #4)
AP SERIES
970-292 Revised 5-12
connections. Flexible hoses should be used between the
unit and the rigid system to avoid possible vibration. Ball
valves should be installed in the supply and return lines for
unit isolation and unit water flow balancing.
ELECTRICAL:
(Refer to electrical component box layout, Figure #5)
Field wiring must comply with local and national electric
codes. Power to the unit must be within the operating
voltage range indicated on the unit nameplate or on the
performance data sheet. On three phase units (single stage
units only) phases must be balanced within 2%.
CAUTION: Operation of unit on improper line voltage or
with excessive phase imbalance will be hazardous to the
unit, constitutes abuse and may void the warranty.
Properly sized fuses or HACR circuit breakers must be
installed for branch circuit protection. See unit nameplate
for maximum fuse or breaker size.
The unit is provided with a concentric knock-out in the
front left corner post for attaching common trade sizes of
conduit, route power supply wiring through this opening.
Always connect the ground lead to the grounding lug
provided in the control box and power leads to the power
supply terminal block as indicated on the wiring diagram
and Figure #5.
NOTE: Units supplied with internal electric heat require
two (2) separate power supplies: one for the unit
compressor and one for the electric heater elements,
blower motor and control circuit. Refer to the ELECTRIC
HEATER PACKAGE OPTION section and Figure #9 for wiring
instructions, minimum circuit ampacities and maximum
fuse/breaker sizing.
ECM INTERFACE BOARD:
THERMOSTAT CONNECTIONS:
Thermostat wiring is connected to the 10 pin screw type
terminal block on the lower center portion of the ECM
Interface Board. In addition to providing a connecting point
for thermostat wiring, the interface board also translates
thermostat inputs into control commands for the variable
speed programmable ECM DC fan motor and displays an
LED indication of operating status. The thermostat
connections and their functions are as follows:
Y2
Second Stage Compressor Operation
Y1
First Stage Compressor Operation
G
Fan
O
Reversing Valve (energized in cooling)
W1
Auxiliary Electric Heat
(runs in conjunction with compressor)
EM/W2 Emergency Heat (electric heat only)
NC
Transformer 24 VAC Common
(extra connection)
C1
Transformer 24 VAC Common
(primary connection)
R
Transformer 24 VAC Hot
HUM
Dehumidification Mode
If the unit is being connected to a thermostat with a
malfunction light, this connection is made at the unit
malfunction output or relay.
(Figure #6)
4
(Figure #5)
Electrical Box Component Layout
Single & Two Step
AP SERIES
970-292 Revised 5-12
NOTE: If the thermostat is provided with a malfunction light
powered off of the common (C) side of the transformer, the
unit must be provided with a malfunction relay (FHP option
# 660-006) to properly energize the light. The relay coil will
be wired across the (ALR) and (C) contacts on the unit’s UPM
board and the relay’s normally open contacts across (ALR)
and the malfunction light connection on the thermostat. If
the thermostat is provided with a malfunction light powered
off of the hot (R) side of the transformer, then the thermostat
malfunction light connection should be connected directly
to the (ALR) contact on the unit’s UPM board.
To the left of the thermostat connection block are a row of
2 red and 4 green LED’s. These LED’s indicate the operating
status of the unit. They are labeled as follows:
EM
(red)
Emergency Heat On
W1 (red)
Auxiliary Heat On
O
(green)
Reversing Valve Energized, unit is
in cooling mode
Y2
(green)
Second Stage Compressor On
Y1
(green)
First Stage Compressor On
G
(green)
Fan On
Just above the connector block is a single red LED labeled
CFM that will blink intermittently when the unit is running
and may flicker when the unit is off. This LED indicates the
air delivery of the blower at any given time. Each blink of
the LED represent 100 CFM of air delivery so if the LED
blinks 12 times, pauses, blinks 12 times, etc. the blower is
delivering 1200 CFM. Refer to Figure #7 for factory
programmed air delivery settings for the ES Series.
To the right of the thermostat connection block is a green
LED labeled dehumidify.
Just above and to the right of the thermostat connection
block are four sets of jumper pins labeled ADJ, DELAY, HEAT
and COOL. The ADJ set of pins are labeled NORM, (+), (-)
and TEST. AP units will all be set on the NORM position from
the factory, however, airflow can be increased (+) or
decreased (-) by 15% from the pre-programmed setting by
relocating the jumper in this section. The TEST position is
used to verify proper motor operation. If a motor problem
is suspected, move the ADJ jumper to the TEST position and
energize G on the thermostat connection block. If the
motor ramps up to 100% power, then the motor itself is
functioning normally. Always remember to replace the
jumper to NORM, (+) or (-) after testing and reset the unit
thermostat to restore normal operation.
NOTE: Do not set the ADJ jumper to the (-) setting when
electric heaters are installed. Doing so may cause the
heaters to cycle on their thermal overload switches,
potentially shortening the life of the switches.
The other three sets of jumper pins are used to select the
proper program in the ECM motor for the unit. Refer to
Figure #7 for the proper jumper placement.
NOTE: Always disconnect power before changing jumper
positions on the interface board and reset the unit
afterward.
To the left of the red and green status LED’s is a row
of 1/4” male quick connects. These are used to pass
thermostat inputs on to the rest of the control circuit.
Remember to always turn off unit power at the circuit
breaker before attaching or disconnecting any wiring
from these connections to avoid accidental short
circuits that can damage unit control components.
SAFETY DEVICES AND THE UPM CONTROLLER
Each unit is factory provided with a Unit Protection
Module (UPM) that controls the compressor operation and
monitors the safety controls that protect the unit.
Safety controls include the following:
•
High pressure switch located in the refrigerant discharge
line and wired across the HPC terminals on the UPM
•
Low pressure switch located in the unit refrigerant suction
line and wired across terminals LPC1 and LPC2 on the UPM.
•
Optional freeze protection sensor, mounted close to
condensing water coil, monitors refrigerant temperature
between condensing water coil and thermal expansion
valve. If temperature drops below or remains at freeze
limit trip for 30 seconds, the controller will shut down the
compressor and enter into a soft lockout condition. The
default freeze limit trip is 30°F, however this can be
changed to 15°F by cutting the R42 resistor located on top
of DIP switch SW1.
•
The condensate overflow protection sensor is located
in the drain pan of the unit and connected to the
‘COND’ terminal on the UPM board.
NOTE: If freeze protection sensor is not installed, a jumper
between freeze contacts must be installed on the UPM
board otherwise unit will not start.
The UPM includes the following features:
•
ANTI-SHORT CYCLE TIME—5 minute delay on break
timer to prevent compressor short cycling.
•
RANDOM START—Each controller has a unique
random start delay ranging from 270 to 300 seconds to
reduce the chances of multiple units simultaneously
starting after initial power up or after a power
interruption, creating a large electrical spike.
•
LOW PRESSURE BYPASS TIMER—If the compressor
is running and the low pressure switch opens, then the
control will keep the compressor on for 120 seconds.
MOTOR PROFILE AIR FLOW TABLE CFM
TWO STAGE UNITS
FAN
Y1
Y2
AUX.
EMERG.
PLUS
MINUS
TAP
MODEL
ONLY
COOL/HEAT
COOL/HEAT
HEAT
HEAT
ADJ
ADJ
COOL/HEAT/DELAY
AP025
600
750
950
950
950
1090
800
A
AP035
900
1000
1200
1200
1200
1400
1000
A
AP049
1200
1300
1700
1700
1700
1950
1450
B
AP061
1300
1500
2000
2000
2000
2100
1900
A
AP071
1300
1500
2100
2100
2100
2300
1900
A
(Figure #7)