FireClass DUO-CEL Installation & Commissioning Manual
Text of the manual
WRITTEN BY: RKP
PUBLICATION:
OM_FC_DUO-CEL_INST
CHECKED BY: AP
ISSUE No. & DATE:
0 01/03/12
APPROVED BY: JBJ
PAGE 1 of 29
DUO-CEL
FIRE DETECTION/ALARM PANEL
Installation & Commissioning Manual
FIRECLASS DUO -CEL
WRITTEN BY: RKP
PUBLICATION:
OM_FC_DUO-CEL_INST
CHECKED BY: AP
ISSUE No. & DATE:
0 01/03/12
PAGE 2 of 29
List of Contents
1. INTRODUCTION ...................................................... 3
1.1 PANEL IDENTIFICATION .................................... 3
2. PANEL CIRCUIT DETAILS ....................................... 3
2.1 AUXILIARY SUPPLY .......................................... 3
2.2 FIRE SIGNAL OUTPUT ...................................... 3
2.3 FIRE RELAY OUTPUT ....................................... 3
2.4 FAULT RELAY OUTPUT ..................................... 3
2.5 REMOTE CONTROL INPUT ................................ 4
2.5.1
Class Change .................................. 4
2.5.2
Alert ................................................. 4
2.5.3
Evacuate ......................................... 4
2.5.4
Silence Alarms ................................ 4
2.5.5
Reset ............................................... 4
2.6 OPEN COLLECTOR OUTPUTS ........................... 5
2.6.1
Disabled Output .............................. 5
2.6.2
Evacuate Output ............................. 5
2.6.3
Buzzer Active Output ...................... 5
2.7 SOUNDER CIRCUITS ........................................ 5
2.8 ELECTRICAL DESIGN OF DETECTION ZONES ..... 5
2.8.1
Standard Panel Default Zone
Configuration ................................................... 5
2.8.2
Standard Panel Resistor Zone
Configuration ................................................... 6
2.8.3
Twin-Wire Panel Zone Configuration
6
2.8.4
Maximum Number of Devices on a
Zone
6
2.9 PANEL TO REPEATER WIRING .......................... 9
3. INSTALLATION AND COMMISSIONING PROCEDURE
OVERVIEW ......................................................... 10
4. INSTALLATION ..................................................... 10
4.1 ELECTRICAL SAFETY ..................................... 10
4.2 PRE-INSTALLATION CHECKS ........................... 12
4.2.1
DUO-CEL Panel Installation
Instructions .................................................... 12
4.2.2
Battery removal & Replacement ... 14
4.2.3
DUO-CEL Repeater Installation
Instructions .................................................... 16
5. PANEL COMMISSIONING ....................................... 16
5.1 INTRODUCTION .............................................. 16
5.2 COMMISSIONING CHECKLIST .......................... 16
5.3 AN OVERVIEW OF THE COMMISSIONING
PROCEDURE................................................ 16
5.4 PRE-COMMISSIONING WIRING CHECK ............ 16
5.5 POWERING UP ............................................... 17
5.6 PANEL CONFIGURATION. ................................ 17
5.6.1
Basic Default Configuration .......... 17
5.6.2
Site-Specific Configuration ............ 17
6. OPERATING THE ENGINEER’S FUNCTIONS ............. 18
6.1 ZONE DEPENDENCY (COINCIDENCE) ............... 18
6.1.1
Zone Dependency selection ......... 18
6.2 REPEATER CONFIGURATION ........................... 18
6.2.1
Repeater selection ........................ 18
6.3 INVALID CONFIGURATION CONDITIONS: ........... 18
6.4 ZONE 1 NON-LATCH OPERATION ..................... 19
6.5 RESISTOR EOL ............................................. 19
6.6 ALERT MODE ................................................ 19
6.7 SELECTABLE ZONAL OR GENERAL ALARM
SOUNDER OPERATION .................................. 19
6.8 BUZZER DISABLE .......................................... 19
6.9 EARTH FAULT MONITORING. ........................... 19
7. COMMISSIONING THE PANEL ................................ 20
7.1 GENERAL ALARM CIRCUITS ........................... 20
7.2 DETECTION ZONES ........................................ 20
7.2.1
Zone Fault Indications .................. 20
7.2.2
Zone Fire Indications .................... 20
7.3 REMOTE CONTROL INPUT .............................. 20
7.4 FIRE SIGNAL OUTPUT .................................... 21
7.5 ANCILLARY OUTPUTS ..................................... 21
7.6 REPEATERS .................................................. 21
7.6.1
Repeater Testing .......................... 22
7.7 POWER SUPPLY UNIT. ................................... 22
7.8 FINAL DRESSING OF THE CABLES ................... 22
7.9 SITE CONFIGURATION ................................... 23
8. SYSTEM HANDOVER ............................................ 23
9. SYSTEM MAINTENANCE ....................................... 23
10. USER INDICATIONS ............................................ 24
11. USER CONTROLS .............................................. 25
12. PCB LAYOUTS ................................................. 26
13. GENERAL ASSEMBLY DRAWING ........................ 28
14. ALARM COUNT DISPLAY ................................... 29
List of Figures
FIGURE 1 – FIRE SIGNAL OUTPUT CONNECTIONS ....... 3
FIGURE 2 – RELAY CONTACT CONNECTION DETAILS .... 4
FIGURE 3 – REMOTE CONTROL I/P CONNECTIONS ...... 5
FIGURE 4 – ALARM CIRCUIT CONFIGURATION .............. 5
FIGURE 5 – TWIN-WIRE EOL DEVICE ......................... 6
FIGURE 6 – STANDARD ZONE WIRING DIAGRAM ......... 6
FIGURE 7 – RESISTOR EOL ZONE WIRING DIAGRAM .. 7
FIGURE 8 – TWIN-WIRE ZONE WIRING DIAGRAM ........ 7
FIGURE 9 – ALARM CIRCUIT WIRING DIAGRAM ........... 8
FIGURE 10 – REMOTE INDICATORS WIRING DIAGRAM . 8
FIGURE 11 – REPEATER WIRING DIAGRAM ................. 9
FIGURE 12 – BAQ35T24 1.5A POWER SUPPLY
CONNECTIONS ...................................... 15
FIGURE 13 – PANEL CONTROL BOARD AND PCB COVER
............................................................ 26
FIGURE 14 – REPEATER CONTROL BOARD AND PCB
COVER .................................................. 27
FIGURE 15 – ALARM COUNT LED ASSIGNMENT ........ 29
FIRECLASS DUO -CEL
WRITTEN BY: RKP
PUBLICATION:
OM_FC_DUO-CEL_INST
CHECKED BY: AP
ISSUE No. & DATE:
0 01/03/12
PAGE 3 of 29
1. Introduction
This
document
contains
all
the
information
necessary for the installation, commissioning and
maintenance of the FIRECLASS DUO-CEL panel
and repeater.
Please
read
this
manual
fully
before
commencing installation.
The following supporting documentation is also
available:
FIRECLASS DUO-CEL Sales Literature
FIRECLASS DUO-CEL Panel Application Guide
FIRECLASS DUO-CEL User Manual
FIRECLASS DUO-CEL Log Book
References are made throughout this document to
“Fire Signal Output”. This is an output used to send
a common fire warning signal to a remote fire
monitoring station. It should not be used for any
other purpose.
1.1 Panel Identification
The DUO-CEL panel & Repeater type can be
identified from the Part Number on the side of the
enclosure (see section 13. for location details).
The table below shows the part numbers.
Panel/Repeater Type
Part Number
1 Zone Standard Panel
508.031.701
2 Zone Standard Panel
508.031.702
4 Zone Standard Panel
508.031.703
8 Zone Standard Panel
508.031.704
8 Zone Repeater – C/W PSE
508.031.705
8 Zone Repeater – No PSE
508.031.706
1 Zone Twin-Wire Panel
508.031.707
2 Zone Twin-Wire Panel
508.031.708
4 Zone Twin-Wire Panel
508.031.709
8 Zone Twin-Wire Panel
508.031.710
2. Panel Circuit Details
2.1 Auxiliary Supply
An auxiliary supply output is available to power the
repeaters and other external field equipment from
the panel. This voltage is nominally 27.15Vdc but
varies during mains-failed conditions, depending on
battery voltage.
The output is electronically fused and fuse
activation will be indicated as Fuse Failed on the
panel display. The fuse can be reset after removal
of the fault by operating the Reset button on the
display.
The auxiliary supply terminals are labelled AUX
0.25A 24V and 0V.
An additional UNFUSED 24V output is provided on
repeaters for connection to additional DC powered
repeaters.
Note: If equipment draws current from the
auxiliary
supply
during
the
mains-failed
condition this must be included in the battery
capacity calculations.
2.2 Fire Signal Output
The Fire Signal output is fault-monitored in the non-
energised condition. It is designed to operate a
signalling relay at the routing equipment. The Relay
coil must be polarised and suppressed, because
the 10k end-of-line device is reverse-polarity
monitored for open & short circuit faults. See Figure
1 for details.
Figure 1 – Fire Signal Output Connections
+
-
Field Wiring
Panel Terminals
Output conditions:
Quiescent: -5V DC
[open circuit voltage]
Active [fire]: 24V
[nominal]
DIODE
1N4002
10k
EOL
DIODE
1N4002
2.3 Fire Relay Output
The Fire Relay output is a single pole relay with
volt-free change-over contacts. The relay is
normally de-energised and energises for any fire
alarm condition. The relay remains energised until
panel reset. This relay will not energise if zone 1 is
configured as non-latching and only zone 1 is in
alarm. See Figure 2 for details.
2.4 Fault Relay Output
The Fault Relay output is a single pole relay with
volt-free change-over contacts. The relay is fail-safe
and is therefore normally energised, de-energising
for any faults. The marking on the control board
terminals is for the energised condition. See Figure
2 for details.
NOTE:
FIRECLASS DUO -CEL
WRITTEN BY: RKP
PUBLICATION:
OM_FC_DUO-CEL_INST
CHECKED BY: AP
ISSUE No. & DATE:
0 01/03/12
PAGE 4 of 29
The volt-free relay contacts are rated at
30Vdc with a maximum current of 1A. Do
not exceed the rated voltage and current.
Figure 2 – Relay contact connection details
P
N/C
Fire Relay
Fire Relay shown in
de-energised condition.
Field Wiring
Panel Circuit
N/O
P
N/C
Fault Relay
Fault Relay shown in
energised condition.
N/O
2.5 Remote Control Input
A single 2-terminal input allows remote operation of
the following functions:
Control Level 1 is lowest priority, 5 is highest
priority.
The input is monitored for open and short circuit
faults. Each control level requires a different
resistor load as shown in the above table. A 10K
resistor acts as the end-of-line device for fault
monitoring. See Figure 3 for wiring details.
2.5.1 Class Change
The Class Change function allows all sounder
circuits to be operated for a maximum of 5 seconds.
When the Class Change resistor is applied, the
sounders will operate continuously and then
automatically
silence
after
5
seconds.
No
indications will be given on the panel. The resistor
needs to be removed and applied again if the signal
needs to be repeated.
2.5.2 Alert
The Alert function allows all sounder circuits to be
operated in pulsing mode.
When the Alert resistor is applied, the sounders will
pulse until the resistor is removed. The Alert/Evac
On LED will illuminate on the panel and the internal
buzzer will sound.
2.5.3 Evacuate
The Evacuate function allows all sounder circuits to
be operated in continuous mode.
When the Evacuate resistor is applied, the
sounders will operate continuously until the resistor
is removed. The Alert/Evac On LED will illuminate
on the panel and the internal buzzer will sound. The
Evacuate output will also operate.
2.5.4 Silence Alarms
The Silence Alarms function allows all active
sounder circuits to be deactivated.
When the Silence Alarms resistor is applied, any
active sounder circuits will be deactivated. The
Silence Alarms function is momentary and the
resistor needs to be removed and applied again in
order to re-operate the Silence Alarms function.
2.5.5 Reset
The Reset function allows all standing alarms and
faults to be cleared, returning the panel to the
quiescent state. The Auxiliary 24VDC supply may
also be switched off for 10 seconds if configured to
do so.
When the Reset resistor is applied with the panel in
the alarm condition, any active sounder circuits will
be deactivated, all zone circuits will reset the
detectors, the fire relay will de-energise, the fault
relay will deactivate and all fire and fault indications
will clear. The Reset function is momentary and the
resistor needs to be removed and applied again in
order to re-operate the Reset function.
Control
Level
Function
Control
Resistor
1
Class Change
4k7
2
Alert
2k2
3
Evacuate
1k
4
Remote Silence
Alarms
470R
5
Remote Reset
220R
FIRECLASS DUO -CEL
WRITTEN BY: RKP
PUBLICATION:
OM_FC_DUO-CEL_INST
CHECKED BY: AP
ISSUE No. & DATE:
0 01/03/12
PAGE 5 of 29
Figure 3 – Remote Control I/P connections
220R ¼ W
RESET
470 ¼ W
SILENCE
ALARMS
1k ¼ W
EVACUATE
10k ¼ W EOL
REMOTE
I/P
0V
2k2 ¼ W
ALERT
4k7 ¼ W
CLASS
CHANGE
Note:
To prevent unauthorised operation of the
system, any manually operated function must
be operated by a key-switch. The key to the
switch should be held with the panel’s access
control key.
For
the
SILENCE
ALARMS
and
RESET
functions, the Keyswitch should be spring-
biased so that it automatically returns to the off
position when released.
2.6 Open Collector Outputs
Three open collector outputs are provided:
1. Disabled (DIS.)
2. Evacuate (EVAC.)
3. Buzzer Active (BUZ.)
They are referred to as „open collector‟ because
each output is connected to the open collector pin
of a transistor.
In the deactivated state, each open collector output
is floating and is effectively open circuit. When the
output is activated, the transistor allows current to
flow from the open collector pin down to 0V. Each
output is able to sink 50mA when active. Higher
currents will damage the transistor driver.
If the output is used to drive a relay then a
suppression diode should be used across the relay
coil to avoid damaging the output driver circuit.
2.6.1 Disabled Output
The Disabled output is activated when any
disablements exist on the panel. The only
exceptions are Buzzer Disable and Earth Fault
Disable, both of which produce no indications on
the panel.
2.6.2 Evacuate Output
The Evacuate output is activated when the panel is
in the Evacuate state, either due to the button on
the display or due to the Remote Control input.
2.6.3 Buzzer Active Output
The Buzzer Active output duplicates the panel
buzzer for alarm and fault conditions. It does not
operate for button presses.
2.7 Sounder Circuits
The panel has up to 4 standard sounder circuits,
each rated at 0.5 Amps (not including twin-wire
sounders).
The
circuits
are
reverse
polarity
monitored for open and short circuit faults. All
connected field devices must be polarised to allow
correct fault monitoring. To prevent damage to the
control panel, any solenoid devices such as bells
must also have a suppression diode fitted as shown
in Figure 4.
The circuit must be terminated with a 10K end of
line resistor.
Figure 4 – Alarm circuit configuration
Polarising
diode
[1N4002S]
Suppression
diode
[1N4002S]
Bell
Electronic
sounder
10K
EOL
Resistor
Alarm +
Alarm -
2.8 Electrical Design of Detection Zones
To allow the panel to correctly monitor for fault
conditions, the wiring for each zone must be
installed as a continuous pair with no spurs or tees.
The end-of-line monitoring device will depend on
the zone configuration of the panel. Correct polarity
must be strictly observed throughout.
2.8.1 Standard Panel Default Zone
Configuration
The Default Zone Configuration (factory Default) on
the standard panel uses active fault monitoring,
with a 10uF capacitor as the EOL device. This
allows the maximum number of detectors to be
used (up to 32 per zone) and maintains line