WALL HUNG BOILERS
INSTRUCTIONS MANUAL
To be used for
INSTALLATION, USE AND MAINTENANCE
PIXEL 25 N
PIXEL 25 NR
PIXEL 29 F
PIXEL 29 FR
PIXEL 25 F
PIXEL 25 FR
PIXEL IN 25 F
PIXEL IN 25 FR
PIXEL ES 25 F
PIXEL ES 25 FR
IMPORTANT
The first boiler ignition and the warranty have to be carried out by an authorised
personnel
LIB0900P – Rev. 1 - 21/02/2006 - 28 pagine
This instruction book is an integrant and essential part of our product and it is delivered together with our heater.
Read carefully the information about safety, installation and maintenance that are shown in it. The heater installation is to
be carried out by qualified personnel according to the present law and the producer instructions.
After having removed the packaging it is better to control the good state of the product. Don't use the heater if you have
any doubt about this just call your supplier.
IMPORTANT: this heater is aimed to warm water at an inferior temperature than that of the boiling at an atmospheric
pressure; it has to be linked to an heating system and/or a hot water distribution net proper to its capacity and power.
This heater has to be used only according to the usage it was planned for. Every kind of other usage has to be
considered unproper and dangerous. The producer is not to be considered responsible for possible damages caused by
this wrong, unproper and unreasonable usage.
Cut the heater from its supply net off before doing every kind of service operations.
Don't obstruct heater aspiration or dissipation grills.
Put the heater out of work if there is any damage or misfunctioning. The repairing must be carried out by an authorized
service operation centre and it has to use only original spare parts.
In order to grant the highest heater efficiency and for its good functioning it is indispensable to follow the producer
instructions.
If you decide not to use the heater any more make all the dangerous parts became harmless.
Don't wet the heater neither with water nor with other liquid substances.
Don't put other items on the surface of the heater.
Before starting every kind of service operation which forsees the burner dismantling or the opening of inspection holes
you have to cut off the electrical supply and close gas cocks.
If there are chimney service operations turn the heater off. After having finished the operation you should call your
qualified personnel and make the relief duct efficiency control.
Don't clean the heater with inflammable substances.
Don't leave recipients of inflammable substances near the heater.
The electrical safety of the heater is assured only if it is linked to an ground system which is respectful of present laws.
Your qualified personnel must control the efficiency of your net because if there are any problems the producer is not
responsable for damages caused by the lacking of a proper ground system.
Control your electrical system capacity which is to be proper to the power required by your heater.
As far as the heater supply is concerned you cannot use adaptators, multiple plugs and extensions.
The use of electrical items implies the careful observation of fundamental rules such as:
1 do not touch the heater with wet hands;
2 do not tear electrical cables;
3 give not allow children or unused persons to use the heater.
All the following instructions that macaws to be take in mind by the technician on the products of the firm ARCA S.r.l.
The ordinary maintenance and the possible reparation of the products must have nade by a center assistance authorized
from the ARCA S.r.l., exclusively using original pspare parts..
Use only flue gas ducts and electric accessories and furnished by ARCA S.r.l.
Do not replace the supply pipe by your own but only by a qualified person.
You have to assure that safety discharge tubes are linked to a relief valve.
Otherwise, there can be an overfload of the heater site caused by the valves safety action and therefore the producer is
not responsible.
System pipes have not to be used as ground plugs for other systems; not only are they unproper to this use but they can
cause serious problems to the appliances which are linked to them.
Please control:
1 the good functioning of the gas inlet system;
2 the correct gas capacity is the one required by the heater power;
3 that the type of gas used is that the heater was projected for.
4 that the gas supply pressure is within the required values of the heater.
5 that the gas inlet system is proper and has all the required safety caracteristics which are forseen by law.
If you feel gas odour do not turn electrical switches on just open your windows and close gas cocks.
2
GENERAL RULES -----------------------------------------------------------------------------------------------------------------2
1. TECHNICAL DATA ------------------------------------------------------------------------------------- 4
1.1 Dimensions ------------------------------------------------------------------------------------------------------------------------------------- 4
1.2 Hydraulic scheme----------------------------------------------------------------------------------------------------------------------------- 4
1.3 Available head --------------------------------------------------------------------------------------------------------------------------------- 4
1.4 General layout of the main components of models PIXEL 25 N ------------------------------------------------------------------ 5
1.5 General layout of the main components of models PIXEL 25 F, PIXEL ES 25, PIXEL IN 25 F -------------------------- 6
1.6 General layout of the main components of models PIXEL 29 F ------------------------------------------------------------------ 7
1.7 Technical data --------------------------------------------------------------------------------------------------------------------------------- 8
1.8 Electrical scheme of PIXEL 25 N --------------------------------------------------------------------------------------------------------- 9
1.9 Electrical scheme of PIXEL 25 NR ------------------------------------------------------------------------------------------------------- 10
1.10 Electrical scheme of PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F, PIXEL 29 F -------------------------------------------- 11
1.12 Electrical scheme of PIXEL 25 FR, PIXEL ES 25 FR, PIXEL IN 25 FR, PIXEL 29 FR------------------------------------ 12
2. INSTALLATION INSTRUCTIONS ------------------------------------------------------------------- 13
2.1 Combustion product discharge: PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F, PIXEL 29 F ------------------------------- 13
2.1.1 Different venting options - Flue venting --------------------------------------------------------------------------------------- 13
2.1.2 Lenght of discharge ducts: PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F --------------------------------------------- 14
2.1.2.1 Split flue (Ø 80 mm) -------------------------------------------------------------------------------------------------- 14
2.1.2.2 Coaxial flue (Ø 60 x 100 mm)-------------------------------------------------------------------------------------- 14
2.1.3 Lenght of discharge ducts: PIXEL 29 F---------------------------------------------------------------------------------------- 15
2.1.3.1 Split flue (Ø 80 mm) -------------------------------------------------------------------------------------------------- 15
2.1.3.2 Coaxial flue (Ø 60 x 100 mm)-------------------------------------------------------------------------------------- 15
2.2 Combustion product discharge: PIXEL 25 N ----------------------------------------------------------------------------------------- 16
2.2.1 Connection with a cheminey ----------------------------------------------------------------------------------------------------- 16
2.2.2 Outdoor direct discarge ------------------------------------------------------------------------------------------------------------ 16
2.2.3 Venting of the rooms --------------------------------------------------------------------------------------------------------------- 17
2.3 Boiler placing----------------------------------------------------------------------------------------------------------------------------------- 17
2.4 Hydraulic connections ----------------------------------------------------------------------------------------------------------------------- 18
2.5 Electric connections -------------------------------------------------------------------------------------------------------------------------- 18
2.6 Gas connection-------------------------------------------------------------------------------------------------------------------------------- 19
2.7 Setting of control panel ---------------------------------------------------------------------------------------------------------------------- 20
2.8 Adjustement instructions: nominal heat and minimal heat-------------------------------------------------------------------------- 21
2.8.1 Nominal heat adjustment ---------------------------------------------------------------------------------------------------------- 21
2.8.2 Minimal heat adjustment ----------------------------------------------------------------------------------------------------------- 21
2.9 Slow ignition and nominal heat adjustment--------------------------------------------------------------------------------------------- 21
2.9.1 Slow ignition adjustment----------------------------------------------------------------------------------------------------------- 21
2.9.2 Nominal heat adjustment ---------------------------------------------------------------------------------------------------------- 22
2.10 Different gases------------------------------------------------------------------------------------------------------------------------------- 22
2.11 Injectors - pressure table: PIXEL 25 N------------------------------------------------------------------------------------------------- 22
2.11.1 Gas pressure - Heat diagram---------------------------------------------------------------------------------------------------- 22
2.12 Injectors - pressure table: PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F ------------------------------------------------------ 23
2.12.1 Gas pressure - Heat diagram---------------------------------------------------------------------------------------------------- 23
2.13 Injectors - pressure table: PIXEL 29 F ------------------------------------------------------------------------------------------------- 24
2.13.1 Gas pressure - Heat diagram---------------------------------------------------------------------------------------------------- 24
3. MAINTENANCE INSTRUCTIONS------------------------------------------------------------------- 25
3.1 Introduction ------------------------------------------------------------------------------------------------------------------------------------- 25
3.2 Circulation deblocking ----------------------------------------------------------------------------------------------------------------------- 25
4. USER'S INSTRUCTIONS------------------------------------------------------------------------------ 26
4.1 Control panel----------------------------------------------------------------------------------------------------------------------------------- 26
4.2 Ignition ------------------------------------------------------------------------------------------------------------------------------------------- 27
4.3 Summer functioning -------------------------------------------------------------------------------------------------------------------------- 27
4.4 Winter functioning----------------------------------------------------------------------------------------------------------------------------- 27
4.5 Break down signals--------------------------------------------------------------------------------------------------------------------------- 27
4.6 Temporary shut down------------------------------------------------------------------------------------------------------------------------ 27
4.7 Long term shut downi ------------------------------------------------------------------------------------------------------------------------ 27
4.8 Suggestions ------------------------------------------------------------------------------------------------------------------------------------ 27
4.9 Functioning problems ------------------------------------------------------------------------------------------------------------------------ 28
Declaration of conformity ------------------------------------------------------------------------------------------------------------------------- 29
3
1. TECHNICAL DATA
1.1 DIMENSIONS
BOILER
L (mm)
H (mm)
P (mm) A (mm) B (mm)
C (mm)
D (mm)
PIXEL 25 N
400
720
300
200
200
182
118
PIXEL 25 F
400
650
260
235
165
103
157
PIXEL 29 F
400
720
300
200
200
182
118
1.2 HYDRAULIC SCHEME
1 - gas valve
2 - burner
3 - primary exchanger
4 - circulator
5 - flussostat
6 - bypass supply
7 - manometer
8 - safety valve (set to 3 bar)
9 - filter
10 - valve of charging supply
11 - vase of expansion
12 - valve in three streets flussostatica
13 - valve I discharging air
14 - sanitary exchanger
1.3 AVAILABLE HEAD
4
0
0 ,5
1
1 ,5
2
2 ,5
3
3 ,5
4
4 ,5
5
5 ,5
6
6 ,5
F lo w (l/h )
Available head H (m)
P IX E L 2 5 N , F
w ith o u t b y-p a s s
P IX E L 2 5 N , F w ith
b y-p a s s
P IX E L 2 9 F w ith o u t
b y-p a s s
P IX E L 2 9 F w ith b y-
p a s s
L
A
B
H
P
C
D
4
11
7
6
13
14
12
9
5
6
10
1
2
3
HOT
DOMESTICAL
WATER
COLD
DOMESTICAL
WATER
RETURN
SUPPLY
GAS
1.4 General layout of the main components of model
PIXEL 25 N
1. Flue gas thermostat
2. Discharge air valve
3. Limit thermostat (105°C)
4. Copper Primary Exchanger
5. Electrode of lighting and survey
6. Burner
7. Circulator
8. Gas valve
9. Safety valve (3 bar)
10. Supply charge valve
11. Supply descharge valve
12. DHW exchanger
13. Supply sensor
14. Hydraulic valve
15. Flue gas cap
16. DHW sensor
5
1
2
3
4
13
6
7
8
9
10
14
15
5
12
11
16
1.5 General layout of the main components of models:
PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F
1. Air Pressostat
2. Discharge air valve
3. Limit thermostat (105°C)
4. Copper Primary Exchanger
5. Electrode of lighting and survey
6. Burner
7. Circulator
8. Gas valve
9. Safety valve (3 bar)
10. Supply charge valve
11. Sanitary water exchanger
12. Supply sensor
13. Hydraulic valve
14. Proof chamber
15. Fan
6
1
2
12
3
4
5
6
7
8
9
11
13
15
14
10
1.6 General layout of the main components of model
PIXEL 29 F
1
Air Pressostat
2
Discharge air valve
3
Limit thermostat (105°C)
4
Copper Primary Exchanger
5
Electrode of lighting and survey
6
Burner
7
Circulator
8
Gas valve
9
Valvola di sicurezza (3 bar)
10
Supply charge valve
11
Supply descharge valve
12
Sanitary water exchanger
13
Sonda riscaldamento
14
Hydraulic valve
15
Proof chamber
16
Fan
7
1
2
3
13
6
5
4
7
8
10
14
11
9
12
15
16
1.7 TECNICAL DATA
Size
PIXEL 25 N
PIXEL 25 F,
ES 25 F, IN 25 F
PIXEL 29 F
Type
B11BS
C12-C32-C42-C52
C12-C32-C42-C52
Nominal Heat
KW
27
27
31,5
Nominal Heat
Kcal/h
23220
23220
27090
Useful Heat
KW
24,7
25,1
29,3
Useful Heat
Kcal/h
21200
21734
25194
Efficiency
%
91,3
92,9
93
Minimal Heat
KW
10,5
10,5
12,4
Minimal Useful Heat
KW
9,4
9,5
11,3
Efficiency at 30 % of Nominal Heat
%
89,5
90,7
91,2
Nominal Heat Gas Flow
Metano G20 (2E+)
m3/h
2,855
2,855
3,331
Metano G25 (2ELL)
m3/h
3,320
3,320
3,874
GPL G30 (3+)
kg/h
2,128
2,128
2,482
GPL G31 (3P)
kg/h
2,096
2,096
2,445
Inlet pressure
Metano G20 (2E+)
mbar
20/25
20/25
20/25
Metano G25 (2ELL)
mbar
20
20
20
GPL G30 (3+)
mbar
29
29
29
GPL G31 (3P)
mbar
37
37
37
Flue gas temperature
°C
115,3
126,7
131,4
CO2 (G20)
%
6
7,7
7,6
Pondered NOx (according to EN 483 pars 6.2.2)
mg/KWh
----
119 (classe 3)
----
Losses of heat to the cover with burner ignited
%
6,8
6,6
6,5
Losses of heat to the cover with burnernot ignited
%
0,2
0,2
0,1
Losses of heat to the cover ((T = 50 °Cs)
%
1,9
0,3
0,5
Gas flow rate
Nm3/h
58,7
47,0
55,5
CENTRAL HEATING
C.H. Minimum Set point
°C
35
35
35
C.H. Maximum Set point
°C
90
90
90
Volume of water in the boiler
l
1,2
1,2
1,2
Volume of water of the expansion vessel
l
7,5
7,5
7,5
Pressure of the expansion vessel
bar
0,7
0,7
0,7
Least pressure in the primary circuit
bar
0,4
0,4
0,4
Maximum pressure in the primary circuit
bar
3
3
3
Maximum content of heating water
l
150
150
150
Available head at 1000 l/h of flow rate
mbar
230
230
330
Domestical hot water
Minimum set point
°C
30
30
30
Maximum set point
°C
60
60
60
Production continuous warm water (t = 25 °C)
l/min
14,1
14,4
16,8
Production continuous warm water (t = 35 °C)
l/min
10,1
10,3
12,0
Volume water (t = 30 °C in the first 10 minutes)
l
117,8
120
140
Minimum flow
l/min
2,5
2,5
2,5
Maximum pressure
bar
8
8
8
Minimum pressure
bar
0,5
0,5
0,5
Voltage
l
----
----
----
Frequency
V/Hz
230/50
230/50
230/50
Absorbed eletric power
W
90
120
120
CONNECTIONS
Heating
Inch
3/4"
3/4"
3/4"
Sanitary water
Inch
1/2"
1/2"
1/2"
Gas
Inch
1/2"
3/4"
3/4"
Height
mm
720
650
720
Depth
mm
300
260
300
Width
mm
400
400
400
Lenght of flue gas ducts
Coaxial Ø 60 xes 100 mms
m
3
4
4
Doubled Ø 80 mms
m
16
30
30
Doubled Ø 60 mms
m
----
----
----
Weight
Kg
43
40
43
Degree of protection
IP
44
IP4X
44
Homologation CE
0068
0068
0068
8
1.6 ELECTRICAL SCHEME of PIXEL 25 N
9
PHASE
NEUTRAL
GROUND
FUSE:
2 x 3,15 AF 5x20 - 250 V
PUMP
GAS VALVE
N
L
SUPPLY SENSOR
ROSSO
ROSSO
P1
P3
P2
PRESSURE
TRANSDUCTOR OF
HEATING SYSTEM
AMBIENT
THERMOSTAT /
REMOTE CONTROL
(OPTIONAL)
SUPPLY WATER
SAFETY BLOCK
FLUE GAS
THERMOSTAT
GAS VALVE MODULATO
ELECTRODE OF LIGHT
AND SURVEY
EXTERNAL SENSOR
(OPTIONAL)
C N.O.
DHW micro
switch
DHW SENSOR (optional)
1.7 ELECTRICAL SCHEME of PIXEL 25 NR
10
SAN.
RISC.
3 WAYS VALVE
(OPZIONALE)
EXTERNAL SENSOR
(OPTIONAL)
ELECTRODE OF LIGHTING
AND SURVEY
GAS VALVE MODULATOR
FLUE GAS
THERMOSTAT
SUPPLY WATER
SAFETY BLOCK
AMBIENT
THERMOSTAT /
REMOTE CONTROL
(OPTIONAL)
PRESSURE
TRANSDUCTOR OF
HEATING SYSTEM
P2
P3
P1
ROSSO
ROSSO
SUPPLY SENSOR
DHW SENSOR
(OPTIONAL)
L
N
GAS VALVE
BLU
MARRONE
PUMP
FUSE:
2 x 3,15 AF 5x20 - 250 V
GROUND
NEUTRAL
PHASE
1.8 ELECTRICAL SCHEME of PIXEL 25 F, PIXEL ES 25 F,
PIXEL IN 25 F, PIXEL 29 F
11
EXTERNAL SENSOR
ELETTRODE OF LIGHTING
AND SURVEY
GAS VALVE MODULATOR
1
3
AIR PRESSOSTAT
SAFETY THERMOSTAT
(105°C)
AMBIENT
THERMOSTAT/REMOTE
CONTROL (OPTIONAL)
TRANSDUCER OF
PRESSURE OF HEATING
SYSTEM
P2
P3
P1
DHW MICRO SWITCH
SUPPLY SENSOR
SONDA SANITARIO
C
N.O.
L
N
GAS VALVE
FAN
PUMP
FUSE:
2 x 3,15 AF 5x20 - 250 V
GROUND
NEUTRAL
PHASE
1.8 ELECTRICAL SCHEME of PIXEL 25 FR, PIXEL ES 25 FR,
PIXEL IN 25 FR, PIXEL 29 FR
12
DHW
HEATING SYSTEM
3 WAYS VALVE
EXTERNAL SENSOR
ELECTRODE OF LIGHTING
AND SURVEY
GAS VALVE MODULATOR
1
3
AIR PRESSOSTAT
TERMOSTATO LIMITE
TEMPERATURA ACQUA
AMBIENT
THERMOSTAT/
REMOTE CONTROL
(OPTIONAL)
TRANSDUCER OF
PRESSURE OF HEATING
SYSTEM
P2
P3
P1
SUPPLY SENSOR
DHW SENSOR (OPTIONAL)
L
N
GAS VALVE
FAN
PUMP
FUSE:
2 x 3,15 AF 5x20 - 250 V
GROUND
NEUTRAL
PHASE
2 INSTALLATION INSTRUCTIONS
2.1 DIFFERENT VENTING OPTIONS:
PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F, PIXEL 29 F
Proof chamber heaters do not require particular caracteristics as for siting and installation
are concerned.
Take particular attention to discharge and aspiration unions in order to avoid combustion
product leakage.
Use only original spare parts.
2.1.1 Different venting options - Flue Venting
1. Coaxial vent through the roof
2. Coaxial through the wall
3. Split type venting between two
cheminey
4. Split type, discharge into a
cheminey, fresh air from outdoor
wall
5. Coaxial, connection
with coaxial cheminey
CAUTION! - Follow local regulations concerning draught terminals location from windows
and doors.
13
2.1.2 LENGTH OF FLUE GAS DUCT:
PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F
2.1.2.1 SPLIT FLUE
Ø 80 mm
N.B.:
The
flue
and
aspiration duct lenght has
not to exceed 16 m.
For
every
added
90°
elbow
the
maximum
allovable lenght is to be
diminuished by 2 m.
Horizontal aspiration and
discharge duct are to be
placed
slightly
inclined
towards the outside.
2.1.3.2 COAXIAL FLUE
Ø 60 x 100 mm
N.B.: The allowed lenght of coaxial
ducts varies between to 0,5 ms
minimal lenght and to 4 ms maximal
lenght.
By 0 to 1 meters length the
presence is necessary of a
diaphragm Ø 44 in the outlet
of the fan.
By 2 to 3 meters length the
presence is necessary of a
diaphragm Ø 46 in the outlet
of the fan.
Horizontal
aspiration
and
discharge duct are to be
placed
slightly
inclined
towards the outside.
14
MAX 15 m
MAX 15 m +
105 120
175
400
235
650
165
STRAGHT ON
400
650
235
165
MAX 15 m
103
157
260
MAX 4 m
235
165
100
400
650
MAX 4 m
2.1.3 LENGTH OF FLUE GAS DUCT: PIXEL 29 F
2.1.3.1 SPLIT FLUE
Ø 80 mm
N.B.: The flue and aspiration
duct lenght has not to exceed
30 m.
For every added 90° elbow
the maximum allovable lenght
is to be diminuished by 2 m.
By 0 to 4 m of lenght you must
insert in the outlet of the fan a
Ø 44 mm diaphragm.
By 5 to 15 m of lenght you
must insert in the outlett of the
fan a Ø 44 mm diaphragm.
The pipe of aspiration and flue gas
must be climbed on with light
inclination toward the outside.
2.1.3.2 COAXIAL FLUE
Ø 60 x 100 mm
N.B.: The allowed lenght of coaxial
ducts varies between to 0,5 ms
minimal lenght and to 4 ms maximal
lenght.
By 0 to 1 meters length the
presence is necessary of a
diaphragm Ø 44 in the outlet
of the fan.
By 2 to 3 meters length the
presence is necessary of a
diaphragm Ø 46 in the outlet
of the fan.
Horizontal
aspiration
and
discharge duct are to be
placed
slightly
inclined
towards the outside.
15
IN LINEA RETTA
MAX 15 m
MAX 15 m +
105 120
175
235
165
MAX 15 m
235
165
MAX 4 m
100
235
165
103
157
260
MAX 4 m
2.2 COMBUSTION PRODUCT DISCHARGE: PIXEL 25 N
2.2.1 CONNECTION WITH A CHEMINEY
The cheminey has a grat importance for thewell running of the boiler; It must be done according these requests:
• Must be built with a resistant water material and must be resistant
•
must be in material impermeable and resistant to the temperature of the smokes and to their condensation;
•
must have a sufficient mechanical resistance and a weak [conduttività termica];
•
must be perfectly proof;
•
must have a most possible vertical and straight course and the terminal part must be equipped with a static aspirator
that assures an efficient and constant evacuation of the smokes;
•
for avoid that the wind could create around the chimney pot of the zones of such pressure from prevail on the
ascensional strength of the gases of unloaded it is necessary that the orifice of evacuation overhangs of at least 0,4 mt.
any adjacent to structure the same fireplace (inclusive the height of the roof of the building) if distant less of 8mt.;
•
the cheminey must have a diameter not inferior to that of cloack of the boiler to square or rectangular section the
inside section must be plus then 10% as regards that of exit of the same cloak;
•
beginning from the cloak, the link must have a vertical pull of length not inferior to two turned the diameter before the
cheminey
2.2.2 OUTDOOR DIRECT DISCHARGE
The natural draught boilers could unload the smokes directly to the outside through the building wall ; a terminal of
draught to the extremity of the duct must be applied.
The duct must satisfy the followings requisite:
•
the horizontal inside part to the building must be reduced to the minimum ([1mt.) and have an inclination in equal
slope at 3 o'clock% toward the outside;
•
must not have more than two changes of direction;
•
must receive the unloading of an only apparatus;
•
must be protected;
•
the pull external ending before the terminal of draught must stick out from the wall of at least two diameters;
•
the vertical leaving pull from the cloak must be along at least a meter;
•
the terminal of draught must overhang of at least 1,5mt. the attack of the duct on the cloak of the boiler.
la parte orizzontale interna all’edificio deve essere ridotta al minimo (max. 1mt.) ed avere un’inclinazione
2.2.3 VENTING OF THE ROOMS
The natural draught boilers are of open combustion to room and are scheduled for have laced the cheminey:
the combustive air has withdrawn directly from the environment in which the boiler is installed.
The rooms in which the boiler is placed will be able to have a ventilation of direct type (with taking of air in
the same place where the boiler is installed), or have an indirect ventilation (with taking of air in the adjoining
places) provided that they come respect the conditions under suitable:
DIRECT AIRING
• the place must have an opening of equal airing to 6 cm² for each installed [kW] and in all the cases
never inferior to 100cm², practiced directly on the wall toward the outside;
• the opening must be nearest possible to the floor;
16
PIXEL 25 N
300
Ø 130
• the opening must not be closing, but protected from a grate that doesn't reduce the useful section for
the flow rate of the air; that's why motive to the section of the hole is added the section of the closed
part of the grate;
• a correct airing could also be gotten through the add openings more, provided that the adds of the
varied sections it correspond to the necessary one;
• if iss not possible practise the near opening to the floor, it is necessary increase the section of the same
at least of the 50%;
• the presence of a fireplace in the same place requires a feeding of own air, otherwise the installation of
apparatuses of B type has not allowed;
• if in the place there is other apparatuses that require of air for their operation (for instance cloaks or
aspirators), the section of the opening of airing goes calculated adequately.
INDIRECT AIRING
It in the case is not possible effect the airing directly in the place, he/she/it/you could be applied the
ventilation indi-straight line, withdrawing the air from an adjoining place through an adequate opening
practised in the low part of the door. This solution is however only possible if:
· the adjoining place is endowed with direct adequate ventilation;
· the adjoining place is not [adibito] to bedroom;
· the adjoining place is not a common part of the immovable property and is not an environment with danger
of fire (for instance deposits of inflammable substances, garage, etc.).
N.B.: In case of an insufficient ventilation of the place or of an incorrect evacuation of the smokes, flue gas
thermostat provokes a lockout of the boiler. For unblocking is necessary regulate the selector in position of
reset.
2.3 BOILER PLACING
Follow these instructions:
• having considered the boiler dimensions, fix the dimension plate by means of two hook screws;
• make two holes on the dimension plate holes by means of two hook screws;
• fix all terminal pipes such as cold and hot water pipes, system inlet and return pipes, gas pipes and
electrical cables into their proper holes on the dimension plate inferior part;
• after this it is possible to take away the dimension plate and use it other times;
• hang the boiler through the previously set expansion hooks;
• for the hydraulic connections screw iron-copper joints together with previously set connections. Cut
forwarded pipes according to the distance between boiler joints and iron-copper connections that are
placed on the wall;
• tighten them firmly and control there are no losses.
N.B.: please, remember of taking lead plastic coverings away
PIXEL 25 F
PIXEL 25 N, PIXEL 29 F
17
2.4 HYDRAULIC CONNECTIONS
Domestic water
Supply net pressure is to vary from 1 to 6 bar. Install a reduction in case of higher
pressure. Supply water strenght influences the cleaning frequence of the exchange
serpentine pipe. The possibility of installing water treatment adequate appliances depends
on water caracteristics.
System loading
Slowly open the loading cock up to reaching about 1 bar system pressure, which can be
controlled through the pressure gauge situated on the facial panel. Close the evacuation
cock again.
Make the radiator air bleed using the proper manual valves.
When the system is cold set the system temperature at 1 bar.
In case of installation of the boiler in local
where the temperature environment can
go down below 0°C, we recommends you
to fill the heating system with antifreeze
solution.
You advises to use solutions of glicole
already diluted for avoiding the risk of
uncontrolled dilutions.
ETHILIC
GLYCOLE (%)
FREEZING
TEMPERATURE (°C)
6
0,00
10
-3,90
15
-6,10
20
-8,90
25
-11,70
30
-15,60
40
-23,40
50
-35,50
Suggestions and advice to avoid system vibrations and noises.
• avoid the use of pipes with reduced diametres;
• avoid the use of bends with reduced radius;
• it is better to have a hot system cleaning in order to eliminate all the impurities coming from pipes and
radiators - particularly oil and fat substances - which might damage the circulating pump.
e dai radiatori (in particolare oli e grassi) che rischierebbero di danneggiare il circolatore.
2.5 ELECTRIC CONNECTIONS
The boiler is set to work with a 230V / 50Hz single-phase tension. Connections have to be effectuated by
means of proper cables which come out of the boiler.
There is also an external cable for the ambient thermostat. Connect the thermostat after having eliminated
the jumper on the T.A cable terminal.. ( ATTENTION: the T.A. connection works by net tension; therefore,
you should use plastic models or if they are made by metal you shuold connect them to an efficient earth
system).
The boiler connection has to be protected by means of a 2 pole isolator and a proper fuse (1A).
The appliance has to be connected to an efficient earth system.
Follow present local regulations about safety.
N.B.: respect the phase and neutral position: an eventual inversion of these two positions results in a block of
the ignition panel.
N.B.: ARCA srl declines every kind of responsability for damages to persons, animals or things caused by
the lack of a proper earth system connection and local regulation attention.
18
2.6 GAS CONNECTION
Effect it I lace respecting the norms of the country meticulously.
Making sure that the pipeline of the gas has an adequate in operation section of his length.
Before effect the connection check that the characteristics of the distributed gas are equal you to those bring
on the dataplate of the boilerif these differs is necessary new regulations.
Insert a faucet of interception between the net of feeding of the gas and the boiler.
Open doors and windows and avoid the presence of free flames.
Clean the air contained in the plant tuba-uncle-ni-apparatus.
With the out boiler check that they there are not escapes of gas.
In these conditions observe the gas meter counter for at least 10 minutes for verify that it doesn't signal any
pas-wise of gas.
Verify, in each case, all the line of gas with a solution or equivalent product.
CAUTION!: For running with LPG is necessary the installation of a reduction gear of pressure awry of the
boiler.
1 -Presa pressione
bruciatore
2 - Presa pressione gas di
rete
3 -Vent
A -Vite regolazione
pressione minima
B - Dado regolazione
pressione massima
C- Cappuccio di
Protezione
To perform the control of the pressures to the burner, to insert the probes of the manometer in the available
takings of pressure on the valve gas (you see fig.).
N.B. check that the pressure and the course of the gas of net are enough to guarantee the correct
operation of the instrument to perform the measure to power on burner.
19
2
1
3
2.7 SETTING OF CONTROL PANEL
You can set 4 ways of operation:
a) Normal way:
Mode of functioning of the boiler, temperature of supply, level of gas modulation and
presence of flame are visualised. Possible anomalies are visualized as besides from
coding at page 27.
b) Mode of visualization of boiler parameters:
It is activated by pushing P1+P2 for 6s. You can visualize in order:
Heating set
- supply temperature
Domestical hot water set
- domestical hot water temperature
- water supply pressure
- heat of ignition
- nominal heat output
c) Mode of parameters setting:
It is activated by pushing P1+P2 for 9s. You visualise alternatively the number of the
parameter Px and the current value. Pushing the keys P3 and P4 is possible to see in
sequence the modifiable parameters, otherwise with the keys P5 and P6 it is possible to
modify its value.
Pressing P3+P4 you can go out of the function without memorizing the changes.
Pressing P2 for 5s you go out the menu and you memorize the changes.
The available parameters are:
- P1 Power of ignition (by 0 % to 99 % of maximum value of range of regulation)
- P2 Power of heating (by 0 % to 99 % of maximum value of range of regulation)
- P3 Anti heating cicling timer (by 0 % to 99 % of 6 minutes)
- P4 oF = post-ventilation of fan off / on = post ventilation of fan on
- P5 Off = metano / on = GPL
- P6 Not available
- P6 oF = water's lack: boiler stops / on = water's lack: boiler doesn't stop, but you have to
call to call service assistance.
- P7
Minimum heating input
(0 ÷ 100 %)
- P8
oF = external sensor off / on = external sensor on
- P9
K OTC
(0 ÷ 6)
20
type of boiler
(0 = domestical hot water and heating system boiler
without tank and with 2 sensor/ 1 = domestical
hot water and heating system boiler with tank and
with 2 sensor or only heating system boiler with
tank/ 2 = domestical hot water and heating system
boiler without tank or only heating system boiler
without tank and with 1 sensor
- Pb
type oh DHW exchanger
oF = with plates /on = with little tank
-
Pc
miminum of heting supply temperature. (+15 ÷ +50) °C
d) Mode of visualisation of historical failure.
It is activated by pushing P1+P2 for 12s. You visualize alternatively the number of index
failure(look at page 20).
By pushing P3+P4 you go out of the function.
By pushing P2 for 5s you can delete the historical of failure.
2.8. ADJUSTMENT INSTRUCTIONS: NOMINAL HEAT AND
MINIMUM HEAT
The boilers are set you set in our factory and they are predisposed for working with the type of gas of the
data plate.
Check the values of pressure min/max however in how much not all the nets distribute the pressure nominal
gas, value on which the instrument has been regulated in factory.
Check and eventually correct the thresholds of setting to proceed in the following way.
Insert a manometer for gas on the taking of pressure" 1";
Turn on the boiler withdrawing the maximum course of sanitary water;
Make sure that the spool of modulation is fed.
2.8.1 NOMINAL HEAT ADJUSTMENT
1. Turn on the boiler withdrawing the maximum flow of domestical water;
2. Make sure yourself that the spool of modulation is fed;
3. Remove the hood of protection" C";
4. Adjust the maximum pressure acting on the die" B" with the aid of a key from 10 mms; rotating clockwise
the pressure increases, rotating counterclockwise in sense the pressure decreases;
2.8.2 MINIMUM HEAT ADJUSTMENT
1. Set the boiler on “Winter” position (see at page 26);
2. Close the contact of ambient thermostat if you have it;
3. Set heating regulation at maximum;
4. Set heating power at maximum (see at page 26).
5. Rotate the red die" Á." up to the attainment of the suitable least pressure on the book (clockwise it
increases, in sense counterclockwise it decreases);
6. Put again the hood of protection" C."
7. For the values of regulation of the heating power of the boiler see at pages 23,34
8. Withdraw the maximum flow of sanitary water to verify the pressure of the maximum heat.
Remember to always close the takings of pressure after the use and to verify its correct estate
2.9 SLOW IGNITION AND NOMINAL HEAT ADJUSTMENT
2.9.1 SLOW IGNITION ADJUSTMENT
The boiler is delivered already set to the following values:
MET = 30 mm H2O
LPG = 80 mm H2O
Follow these instructions if you have to change these values:
• open the domestic water to its maximal level and turn the boiler off;
• turn the boiler on;
• check the pressure of the gas to the burner during the cycle of ignition (the pressure of slow ignition is
actually maintained to the relevation of the flame).
21
• push for 9 sec P1 and P2 and see c) “Mode of parameters setting” (look at page 20)
Set P2 as you need.
• To reset the value of slow ignition you need to turn off the boiler, to again act on the parameters and to
remake ignitionr verifying the attainment value of desired pressure.
ATTENTION: the slow ignition time for its adjustment is 5 seconds after which the nozzle pressure will
increase or decrease according to the energetical need. If a further change is needed repeate this operation
by turning the boiler on and off.
2.9.2 NOMINAL HEAT ADJUSTMENT
The greatest heating power has to be adjusted according to system needs.
Gas pressure values are shown at pages 23,24 in the table “INJECTORS PRESSURE TABLE”.
For the adjustment of the burner gas pressure follow these indications:
• Set the boiler on “Winter” position;
• create a jumper on the ambient thermostat in order to start the boiler;
• push for 9 sec P1 and P2 and see c) “Mode of parameters setting” (look at page 20)
Set P1 as you need.
N.B.: wait about 10 seconds to allow the pressure stabilisation after the slow ignition.
2.10 DIFFERENT GASES
This is a LPG or natural gas boiler as well. The transformation from one gas type to the other one has to be
carried out as follows:
Transformation from methane to LPG gas
• replace burner injectors
• change the JP1 jumper position and set it to “LPG” position (see the electrical scheme);
• adjust MIN/MAX pressure levels keeping in mind the above shown instructions;
• as far as the injectors diametres and the burner gas pressure are concerned, see the above table;
• after this seal the valve regulator by means of a coat drop.
Transformation from LPG to methane
• replace burner injectors;
• change the JP1 jumper position and set it to “METHANE” position (see the electrical scheme);
• adjust MIN/MAX pressure levels keeping in mind the above shown instructions;
• as far as the injector diametres and the burner gas pressure are concerned, see the above table;
• after this seal the valve regulator by means of a coat drop.
22
2.11 INJECTORS PRESSURE TABLE: PIXEL 25 N
PIXEL 25 N
Injectors diameters Gas diaph.
Burner pressure
P.C.I
Inlet
pressure
Quantity
Φ
Φ
Min. Heat
= 10,5
KW
Nom.
Heat. =
27 KW
Type of gas
MJ/m3
mbar
n°
mm
mm
mbar
mbar
Metano G20 (2H+)
34,02
20
13
1,20
5,9
2,3
13,3
Metano G25 (2H+)
29,25
25
13
1,20
5,9
2,8
15,9
Metano G25 (2LL)
29,25
20
13
1,40
-------
2,2
10,1
Butano G30
116,09
28/30
13
0,75
-------
4,4
27,1
Propano G31
88
37
13
0,75
-------
5,2
33,8
2.11.1 Gas pressure - Heat diagram
8
13
18
23
28
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
Burner pressure (mbar)
Heat (KW)
NAT.GAS H (G20)
NAT.GAS L (G25)
NAT.GAS LL (G25)
BUTANE (G30)
PROPANE (G31)
2.12 INJECTORS PRESSURE TABLE:
PIXEL 25 F, PIXEL ES 25 F, PIXEL IN 25 F
PIXEL 25 F
Injectors diameters Gas diaph.
Burner pressure
P.C.I
Inlet
pressure
Quantity
Φ
Φ
Min. Heat
= 10,5
KW
Nom.
Heat. =
27 KW
Type of gas
MJ/m3
mbar
n°
mm
mm
mbar
mbar
Metano G20 (2H+)
34,02
20
11
1,30
6,5
2,3
14,4
Metano G25 (2H+)
29,25
25
11
1,30
6,5
2,3
14,4
Metano G25 (2LL)
29,25
20
11
1,45
-------
1,6
10,1
Butano G30
116,09
28/30
11
0,8
-------
4,3
28,1
Propano G31
88
37
11
0,8
-------
5,7
35,3
23
2.12.1 Gas pressure - Heat diagram
8
13
18
23
28
0
2
4
6
8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Burner pressure (mbar)
Heat (KW)
NAT.GAS H (G20)
NAT.GAS L (G25)
NAT.GAS LL (G25)
BUTANE (G30)
PROPANE (G31)
2.13 INJECTORS PRESSURE TABLE: PIXEL 29 F
PIXEL 29 F
Injectors diameters Gas diaph.
Burner pressure
P.C.I
Inlet
pressure
Quantity
Φ
Φ
Min. Heat
= 12,4
KW
Nom.
Heat. =
31,5 KW
Type of gas
MJ/m3
mbar
n°
mm
mm
mbar
mbar
Metano G20 (2H+)
34,02
20
n°
mm
mm
mbar
mbar
Metano G25 (2H+)
29,25
25
13
1,30
5,9
1,5
12,7
Metano G25 (2LL)
29,25
20
13
1,30
5,9
2,5
13,5
Butano G30
116,09
28/30
13
1,45
-------
1,7
13,5
Propano G31
88
37
13
0,8
-------
3,8
27,3
• only for Francia and Belgio
24
2 .1 3 .1 G a s p re s s u re - H e a t d ia g ra m
8
1 3
1 8
2 3
2 8
3 3
0
2
4
6
8 1 0 1 2 1 4 1 6 1 8 2 0 2 2 2 4 2 6 2 8 3 0 3 2 3 4 3 6
B u rn e r p re s u u re (m b a r)
Heat (KW)
N A T .G A S H (G 2 0 )
N A T .G A S H (G 2 5 )
N A T .G A S L (G 2 5 )
B U T A N E (G 3 0 )
P R O P A N E (G 3 1 )
3. MAINTENANCE INSTRUCTIONS
3.1 INTRODUCTION
All the maintenance and gas transfomation operations have to be carried out by qualified
personnel.
Moreover, MAINTENANCE operations have to be made at least once a year and
according to local regulations.
Before winter it is necessary to make the boiler be controlled by authorised personnel to
have an always working system.
Control:
• verify the exchanger cleaning;
• verify the burner cleaning;
• verify the hydraulic system pressure;
• verify the expansion vessel heating system efficiency;
• verify the correct functioning of adjustment and safety thermostats;
• verify the cleaning and integrity of sensor and ignition electrodes;
• control the good circulator running;
• control there are no spills (water, gas smoke evacuation);
• control the gas burner pressure;
• control the combustion output;
• control the emission levels of CO, CO2 and NOX;
• in case of a boiler spare part replacement you should use only original spare parts by
ARCA.
Arca refuses every kind of responsability about every damage caused by the installation of
a non original spare part.
ATTENTION: this boiler has a safety thermostat linked to the chimney draught which starts
to work when there is a combustion product coming back in the ambient. This appliance
has never to be placed out of work. If combustion products come back in the ambient, they
can cause severe intoxications with even death risks.
ATTENTION: after any boiler service regarding the gas pipe system it is absolutely
necessary to control that unions are perfectly running and there are no gas spills.
3.2 CIRCULATION DEBLOCKING
When the boiler is new or after a long standstill period you may have a circulator block.
You can comply with this problem as follows:
• unscrew and remove the circulator cap;
• insert the screwdriver and turn it to deblock the circulator;
replace the cap.
25
4. USER’S INSTRUCTIONS
4.1 CONTROL PANEL
Thermometer:
Through the
thermometer it is
possible to verify the
temperature of run of
the circuit of heating,
previously planned
through the relative
regulator.
Manometer:
It visualizes the pressure
of the heating water; the
value of such pressure
doesn't have to be
inferior to
0,8. 1 bar (cooled down
circuit).
If the pressure had to be
inferior to
\ \0,8. 1 bar (cooled down
circuit).
,
it is necessary to handle
the restoration of the
correct value acting on
the charge valve. This
operation must be
performs cooling down
circuit.
.
Regulator temperature
domestical water:
The function of this handle
grip is to fix the value of
the temperature of use of
the domestical water;
acting counterclockwise in
sense the lowest value of
the temperature
impostabile is gotten
Regulator temperature of
heating:
Through this handle grip it is
possible to plan the
temperature desired of the
circuit of heating:
acting counterclockwise in
sense the lowest value of
the available temperature is
gotten
Summer
Winter
Reset
With the changer in position
Summer the boiler is
predisposed to run for the
onlyproduction of domestical
water.
With the changer in position
Winter the boiler is
predisposed to run both for
the heating that for the
production of domestical
water.
Bring the selector in
position of Rearmament
to reactivate the
operation of the boiler
after the intervention of
the device of block of
the burner.
26
Open the manual gas supply line cock, located outside of the boiler. Push to the SUMMER
or WINTER position: the boiler should ignite automatically. If the boiler does not ignite you
will see a failure in the display.
4.3 SUMMER MODE
For domestic hot water only.
Push MENU to SUMMER position. Set the domestic water temperature adjustment to the
desired setting. The domestic hot water production is activated.
4.4 WINTER MODE
For heat and domestic hot water.
Push MENU to WINTER position. Set the heating temperature adjustment to the desired
setting. Room thermostat will keep the desired value.
4.5 BREAK DOWN SIGNALS
CODE
DESCRIPTION
01
LOCKOUT due to not ignition
02
Failure of heating system pressure 1
03
Failure of external sensor
04
Failure of heating sensor
05
Failure of DHW sensor
06
LOCKOUT due to high temperature
08
Air pressostat failure/flue gas thermostat
09
Not water circulation
4.6 TEMPORARILY TURNING BOILER OFF
You can achieve it by means of:
- the room thermostat ;
- the MENU on the instrument panel;
4.7 LONG TERM SHUT DOWN
If the boiler is to remain off for a long period of time, close the gas cock to the boiler. Before start- up,
manually turn the rotating part of the circulator pump in case it froze (slightly stuck) during the down time.
4.8 SUGGESTIONS
Once a year the boiler should be cleaned and checked to make sure that all components are working
properly. Do not adjust the gas valve, this is to be done only by a licensed authorized technician.
If there is a lockout, turn knob to reset position. If the problem happens often, call a
licensed authorized technician.
27
1 Anomaly is visualized and prevented the starting the burner for P < 0,25 bar. The starting of the burner is allowed for P
> 0,4 burner
Subsequently to anomaly the burner starts correctly working after the pressure of heating system is corrected. To return
to the normal visualization press the P2 button.
Through parameter P6 is possible to start the burner however even if it foresees anomaly pressure plant, that comes all
the same visualized.
4.9 FUNCTIONING PROBLEMS
SITUATION
1 The burner flame does not sparkle
POSSIBLE CAUSES
A. The water temperature is higher than
that of the adjustment thermostat;
B. The gas cock is closed;
C. Out of working button;
D. Lack of flame
E. Lack of the ignition electrode sparkle;
F. Air in the pipe system;
G. The safety thermostat has started
working;
H. There is no system pressure .
REMEDIES
A. Bring the adjustment thermostat to an
higher temperature;
B. Open the gas cock;
C. Reset it;
D. Call an expert;
E. Call an expert;
F. Repete the ignition procedure;
G. Call an expert;
H. Open the charge cock and re-establish
the pressure level.
SITUATION
2 Violent ignition
POSSIBLE CAUSES
A. Flame instability;
B. Insufficient gas flow;
C. Uncorrectly placed ignition electrodes.
REMEDIES
A. .Call an expert;
B. Call an expert;
C. Call an expert.
SITUATION
3 Gas odour
POSSIBLE CAUSES
A. Gas system leakage ( of both the
internal and external pipe system).
REMEDIES
A. Close the main gas cock and call an
expert.
SITUATION
4 Boiler condensation
POSSIBLE CAUSES
A. The boiler temperature is too low.
REMEDIES
A. Adjust the boiler thermostat to an
higher temperature.
SITUATION
5 Cold radiators in winter
POSSIBLE CAUSES
A. The selector is to “SUMMER” position;
B. The ambient thermostat is out of
working or it has been adjusted to a
too low temperature;
C. Closed radiator system;
D. Misfunctioning three ways valve.
REMEDIES
A. Bring it to “WINTER” position;
B. Turn the ambient thermostat on and
set an higher temperature;
C. Open system or radiators valves;
D. Call an expert.
SITUATION
6 Domestic warm water little production.
POSSIBLE CAUSES
A. The domestic thermostat temperature
is too low;
B. Too many warm water samples;
C. The burner gas adjustement is not
correct.
REMEDIES
A. Increase in the domestic thermostat
temperature;
B. Partially close the warm water cock;
C. Call an expert.
28
TECNOLOGIE PER L’AMBIENTE
Via Giovanni XXIII, 105 - 20070 S.Rocco al Porto (LODI)
Tel.: 0377/569677 - Fax.: 0377 569456
DECLARATION OF CONFORMITY
The undersigned Michael Cavallini managing director of the ARCA S.r.l. with registered office 1° May, 16,
San Giorgio –Mantova - Italy
declares
that he boilers
BASEL 21 N, BASEL 21 N R, BASEL B 21 N, ECOS 21 N, ECOS 21 N R, ECOS B 21 N,
ECOS B 21 N INOX, POCKET 24 N, POCKET 24 N R, ECOS 120/21 N, ECOfast 25 N, ECOfast 25 N R,
ECOfast B 25 N, ECOfast B 25 N INOX, ECOfast 120/25 N, PIXEL 25 N, PIXEL 25 NR (PIN CODE:
0068AT020),
BASEL 21 F, BASEL 21 F R, BASEL B 21 F, ECOS 21 F, ECOS 21 F R, ECOS B 21 F, ECOS B 21 F INOX,
INOXA 21 F, POCKET 24 F, POCKET 24 F R, ECOfast 25 F, ECOfast 25 F R, ECOfast B 25 F,
ECOfast B 25 F INOX (PIN CODE: 0068AT018),
ECOS 30 F, ECOS 30 F R, ECOS 120/30 F, ECOfast 32 F, ECOfast 32 F R, ECOfast 120/32 F,
MULTIPLA 32 F TR, MULTIPLA 32 F (PIN CODE: 0068AT021),
BASEL 21 F cg, BASEL 21 F R cg, BASEL B 21 F cg, ECOS 21 F cg, ECOS 21 F R cg, ECOS B 21 F cg,
ECOS B 21 F, INOXA 21 F cg, ECOS 120/21 F, STYLO IN 21 F, STYLO ES 21 F, ECOfast 25 F cg,
ECOfast 25 F R cg, ECOfast B 25 F cg, ECOfast B 25 F, ECOfast 120/25 F, STYLOfast IN 25 F, STYLOfast
ES 25 F (PIN CODE: 0068AT019),
BASEL 21 F SUPER, BASEL 21 F R SUPER, BASEL B 21 F SUPER, ECOS 21 F SUPER, ECOS 21 F R
SUPER, ECOS B 21 F SUPER, ECOS B 21 F INOX SUPER, INOXA 21 F SUPER, ECOS 120/21 F SUPER,
STYLO ES 21 F SUPER, STYLO IN 21 F SUPER, POCKET 24 F SUPER, POCKET 24 F R SUPER,
ECOfast 25 F SUPER, ECOfast 25 F R SUPER, ECOfast B 25 F SUPER, ECOfast B 25 F INOX SUPER,
ECOfast 120/25 F SUPER, STYLOfast ES 25 F SUPER, STYLOfast IN 25 F SUPER, PIXEL 25 F SUPER,
PIXEL 25 FR SUPER (PIN CODE: 0068AT025),
BASEL 24 F, BASEL 24 F R, BASEL B 24 F, ECOS 24 F, ECOS 24 F R, ECOS B 24 F, ECOS B 24 F INOX,
INOXA 24 F, ECOS 120/24 F, PANELfast 29 F, PANELfast 29 F R, STYLO ES 24 F, STYLO IN 24 F,
POCKET 28 F, POCKET 28 F R, ECOfast 29 F, ECOfast 29 F R, ECOfast B 29 F, ECOfast B 29 F INOX,
ECOfast 120/29 F, STYLOfast ES 29 F, STYLOfast IN 29 F, PIXEL 29 F, PIXEL 29 FR (PIN CODE:
0068AT026).
PIXEL 25 F, PIXEL 25 FR, PIXEL ES 25 F, PIXEL ES 25 FR, PIXEL IN 25 F, PIXEL IN 25 FR (PIN CODE:
0068BO058
Part number aaBBBxxxxxx
where aa means the year of production,
BBB is ARF and means per ARCA FRANCE,
TRK for Turkish market;
ARC for all the other country,
xxxxxx means a progressive number,
prodotte e commercializzate dall’azienda
ARCA Srl in via Giovanni XXIII, 105, S.Rocco al Porto (LODI) con marchio ARCA
Are produced in conformity with rhe following European Directive:
90/396/CEE (Gas Appliance Directive),
92/42/CEE (Useful output Directive)
73/23/CEE (Low Voltage Directive)
89/336/CEE (Electromagnetic noise)
S.Rocco al Porto, 8 Marzo 2005
Legal center:Via I° Maggio,16
46030 S. Giorgio (Mantova)
(0376) 372206 Fax (0376) 374646
Factory:Via S.Giovanni XXIII,105
26865 S. Rocco al Porto (LODI)
(0377) 569677
(0377) 569456