IVS1000
Pure Sinewave Inverter
IMPORTANT & SAFETY INSTRUCTIONS
1) SAVE THESE INSTRUCTIONS — This manual contains important safety and operating
instructions for inverter.
2) Do not expose inverter to rain or snow.
3) Use of an attachment not recommended or sold by the inverter manufacturer may result in a
risk of fire, electric shock, or injury to persons.
4) Do not disassemble inverter; take it to a qualified serviceman when service or repair is re-
quired. Incorrect reassembly may result in a risk of electric shock or fire.
5) To reduce risk of electric shock, unplug inverter from outlet before attempting any mainte-
nance or cleaning. Turning off controls will not reduce this risk.
6) Never place inverter directly above battery; gases from battery will corrode and damage marine
inverter.
7) Never allow battery acid to drip on inverter when reading gravity or filling battery.
GROUNDING AND AC POWER CORD CONNECTION INSTRUCTIONS — Inverters should be
grounded to reduce risk of electric shock. Inverter is equipped with electric receptacles capable of accepting
an equipment-grounding conductor and a grounding plug.
DANGER — Never alter AC cord or plug provided — if it will not fit outlet, have proper cord installed by a
qualified electrician. Improper connection can result in a risk of an electric shock.
Analytic Systems does not recommend the use of the IVS2500 Series Inverters in life support applications
where failure or malfunction of this product can be reasonably expected to cause failure of the life support
device or to significantly affect its safety or effectiveness. Analytic Systems does not recommend the use of
any of its products in direct patient care.
Examples of devices considered to be life support devices are neonatal oxygen analyzers, nerve stimulators
(whether used for anesthesia, pain relief, or other purposes), autotransfusion devices, blood pumps, defibril-
lators, arrhythmia detectors and alarms, pacemakers, hemodialysis systems, peritoneal dialysis systems,
neonatal ventilator incubators, ventilators for both adults and infants, anesthesia ventilators, and infusion
pumps as well as any other devices designated as “critical” by the U.S. FDA.
The IVS1000 inverter series was designed electrically and mechanically to achieve optimal ruggedness
required for industrial, telecommunications, military and airborne applications.
Electrical Connections
The input can be grounded either on the positive or negative, or may be left floating. The output is normally
grounded, although it can be floating if required for specific applications.
Mount the unit as close to the battery as possible to avoid voltage drop and losses on the wires. The input
connections are via a 3-pole terminal block. GND, POS and NEG are clearly labeled. Although the unit
is reverse polarity protected, ensure that input is connected correctly. (On some models, the internal fuse
blows when reverse polarity occurs).
If operating the inverter from a power supply (instead of a battery), ensure that this source is capable of sup-
plying a significantly higher current than is actually required. It is preferable to turn on the inverter first, and
connect the load after the inverter is already running.
Input Wire Sizes
Input wire size is crucial for maximum efficiency and safety. For best results, the shortest length and largest
gauge wire should be used. Marine type battery terminals are recommended for attaching connectors to the
battery. Keep all connectors clean and free of corrosion. Refer to the following table for proper sizing. The
following values are to be used for guidelines only! The actual application must be considered for selecting
wire gauge, insulation, as well as EMI considerations for wire routing and shielding where necessary. For
longer wire lengths, larger gauge wire may be needed to minimize line losses.
RECOMMENDED INPUT WIRE SIZES
DISTANCE FROM BATTERY
MODEL
5’
10’
15’
20’
IVS1000-24V to 36V
AWG 4
AWG 2
AWG 0
AWG 00
IVS1000-48V
AWG 8
AWG 8
AWG 6
AWG 6
IVS1000-125V
AWG 10
AWG 10
AWG 10
AWG 10
IVS1000-250V
AWG12
AWG12
AWG12
AWG12
The unit should be mounted securely to a flat surface with a minimum of one-inch clearance to provide
ample airflow and to achieve maximum continuous power. Cooling is enhanced if the unit is installed on a
metal surface to allow for additional conduction cooling.
Electronic Protection
The inverter has a number of protection circuits designed to provide full electronic protection:
Grounding - The input can be either positively or negatively grounded, or may be left floating. The output is
normally grounded, although it can be left floating if required.
Thermal shutdown - In the event of overheating due to high ambient temperature, blocked air flow or over-
load conditions, the internal thermal protection circuit will shut the unit down. Operation will automatically
resume when the temperature reaches the specified operating level.
Overload and short-circuit protection - In case of an overload or short circuit, the inverter will go into “hic-
cup” mode. This means that the unit will automatically shut down and will periodically test whether or not
the overload condition still exists.
Reversed Input Polarity Protection – The IVS1000 inverter series has sophisticated protection to ensure that
no damage occurs whilst reverse polarizing the input. (On some models, the internal input fuse may blow
when reverse polarity occurs).
Input and output filtering - All IVS1000 series inverters have a double stage input filter to restrict EMI emis-
sions. Filtering also provides immunity against voltage spikes and other disturbances on the input power
line. The inverters meet FCC 20780 Class B and EN 55022 Class B conducted emission requirements.
On/off Switch
The IVS1000 inverter series has an on/off switch, which disables the inverter’s control circuit. Turning the
switch to the ‘OFF’ position cuts the power to the AC output. A minimal current drain will continue on
the DC input side. Always disconnect the inverter when not in use for an extended period of time to avoid
draining the battery and to prolong battery life.
Operating
Before plugging any appliance into the inverter, please refer to its power requirements. Power requirements
are indicated in watts (W), volt-amps (VA) or amps (A). Ensure that the rating does not exceed the inverter’s
capacity.
Safety Considerations
WARNING: The IVS1000 inverter series generate 115VAC power – the same voltage coming out of a
standard wall outlet. This voltage can be hazardous and has to be treated with the same caution as a regular
electrical outlet.
As with any other electrical equipment, the inverter unit must be protected from water and moisture at all
times.
Designed and manufactured by: ANALYTIC SYSTEMS WARE (1993) LTD.
8128 River Way, Delta, B.C., V4G 1K5, Canada
phone (604) 946-9981
fax (604) 946-9983 toll free 800-668-3884 US/Canada
email: [email protected] web site: www.analyticsystems.com Revised Mar 2004
* Specifications subjects to change without notice.
INPUT
Input Voltage:
24Vdc
36Vdc
48Vdc
125Vdc
250Vdc
Input Protection:
Inrush current limiting, thermal fuse & reverse polarity
Input Isolation:
500 Vdc input to output& input to chassis for <60Vdc input
1400 Vdc input to output& input to chassis for ³60Vdc input
500Vdc output to chassis – all inverters
OUTPUT
Output Voltage / Current:
115 VAC / 60 Hz / 8.7 Amp continuous (1000VA)
Wave Form:
Sinusoidal
Total Harmonic Distortion:
Better than 5% at full load
Line Regulation:
Maximum 0.5%
Load Regulation:
Maximum ±6% from 10% load to full load
Output Noise:
High frequency ripple is better than 500 mVrms (20 MHz BW)
GENERAL
Temperature Drift:
0.05% per º C over operating temperature range
Operating Temp. Range:
0 º C to +50 º C for full specification with internal fan
Humidity:
5 - 95 % non-condensing
Output Protection:
Current limiting with short-circuit protection. Thermal shutdown with
automatic recovery in case of continuous overload or insufficient airflow
Output Overload Protec-
tion:
Hiccup at 1200 W
Output Over-voltage
Protection:
By internal supply voltage limiting at 120% V out, nominal level
Load Crest Factor:
Maximum 2.5 at 90% load
RFI Suppression:
Meets requirements of FCC 20780 Class B and EN55022 Class B conducted
emissions as a minimum
Efficiency:
Minimum 80% at full load
Cooling:
By internal fan
Input Connection:
Screw-type terminal block
Output Connection:
Standard AC Receptacle (North American Type)
Package Size / Weight:
5.3 x 7.5 x 15.5 Enclosed case, 13 pounds ( 6 kg )
The equipment manufactured for Analytic Systems Ware (1993) Ltd. (the “Warrantor”) is warranted to
be free from defects in workmanship and materials under normal use and service.
2.
This warranty is in effect for: 2 Years from date of Purchase.
3.
In case any part of the equipment proves to be defective, the Purchaser should do the following:
a. Prepare a written statement of the nature of the defect to the best of the Purchasers knowledge,
and include the date of purchase, the place of purchase, and the Purchasers name, address and
telephone number.
b. Call Analytic Systems at 800-668-3884 or 604-946-9981 and request a return material authori-
zation number (RMA).
c.
Return the defective part or unit along with the statement at the Purchasers expense to the
Warrantor; Analytic Systems Ware (1993) Ltd., 8128 River Way, Delta, B.C., V4G 1K5, Canada.
4.
If upon the Warrantor’s examination the defect proves to be the result of defective material or work-
manship, the equipment will be repaired or replaced at the Warrantor’s option without charge, and
returned to the Purchaser at the Warrantor’s expense by the most economical means. Requests for a
different method of return or special handling will incur additional charges and are the responsibility of
the Purchaser.
5.
Analytic Systems reserves the right to void the warranty if:
a.
Identification marks or serial numbers are removed or altered in any way.
b.
Our invoice is unpaid.
c.
The defect is the result of misuse, neglect, improper installation, environmental conditions,
non-authorized repair, alteration or accident.
6.
No refund of the purchase price will be granted to the Purchaser, unless the Warrantor is unable to
remedy the defect after having a reasonable number of opportunities to do so.
7.
Only the Warrantor shall perform warranty service. Any attempt to remedy the defect by anyone else
shall render this warranty void.
8.
There shall be no warranty for defects or damages caused by faulty installation or hook-up, abuse or
misuse of the equipment including exposure to excessive heat, salt or fresh water spray, or water im-
mersion except for equipment specifically stated to be waterproof.
9.
No other express warranty is hereby given and there are no warranties that extend beyond those de-
scribed herein. This warranty is expressly in lieu of any other expressed or implied warranties, includ-
ing any implied warranty of merchantability, fitness for the ordinary purposes for which such goods
are used, or fitness for a particular purpose, or any other obligations on the part of the Warrantor or its
employees and representatives.
Limited Warranty
There shall be no responsibility or liability whatsoever on the part of the Warrantor or its employees
and representatives for injury to any person or persons, or damage to property, or loss of income or
profit, or any other consequential or resulting damage which may be claimed to have been incurred
through the use or sale of the equipment, including any possible failure of malfunction of the equip-
ment, or part thereof.
11.
The Warrantor assumes no liability for incidental or consequential damages of any kind.