EEDE03-1/2 • 04/2003 Prepared in Belgium by Goekint Graphics Zandvoordestraat 300 B - 8400 Ostend Belgium Internet: http://www.daikineurope.com Specifications are subject to change without prior notice. ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product. Daikin units comply with the European regulations that guarantee the safety of the product. Daikin Europe N.V. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products.

TABLE OF CONTENTS

RKS-B 1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Technical specifications Electrical specifications Electrical data 3 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 5 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 6 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 7 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 8 Sound level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Sound level data Sound pressure spectrum 9 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Standard accessories Optional accessories 10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 • Pair Application • R-410A • RKS25-35-50-60-71BVMB 1 • Split - Sky Air • Outdoor Units

Outdoor units for pair application

+ Daikin outdoor units can be mounted easily on a roof or terrace or simply placed against an outside wall. They are fitted with a swing compressor, renowned for its low noise and high energy efficiency. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 1 2 • Split - Sky Air • Outdoor Units

Sound pressure (1) (Cooling)

High/Low dBA 46/43 47/44 47/* 49/* 52/* Sound power (2) (Cooling) High dBA 59 60 63 64 66 FAN Air flow rate (Cooling) High/Low m3/min 25.3/17.0 25.3/17.0 47.7/44.1 47.6/44.1 51.5/41.5 Speed (Cooling) high rpm 670 670 700 730 790 low rpm 450 450 650 680 650 Model Propeller fan Motor output W 19 53 HEAT EXCHANGER Type Waffle fin, J 8 Hi-XA tube Rows x stages x fin pitch mm 2 x 24 x 1.5 1 x 32 x 1.6 2 x 32 x 1.8 REFRIGERANT CIRCUIT Refrigerant type R-410A Refrigerant charge kg 0.96 1.06 1.20 1.70 1.70 Maximum allowable distance between indoor and outdoor m 25 30 Maximum allowable level difference m 15 20 Refrigerant control Motor operated expansion valve - COMPRESSOR Type Hermetically sealed swing type Model 1YC23GXD#A 2YC32HXD 2YC45BXD Motor output 600 600 1,500 1,500 1,900 Oil type FVC50K Oil charge volume ! 0.40 0.40 0.65 0.65 0.75 PIPING CONNECTIONS liquid mm φ6.4 gas mm φ9.5 φ12.7 φ15.9 drain mm φ18.0 INSULATION MATERIAL Heat insulation Both liquid and gas pipes * This information was not available at the time of publication. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 2 3 • Split - Sky Air • Outdoor Units

Nominal running current

cooling A 3.52 5.22 6.82 9.12 10.90 Max. running current cooling A Please refer to electrical data Starting current cooling A 3.7 5.4 7.3 9.3 11.1 OUTDOOR UNITS RKS25BVMB RKS35BVMB RKS50BVMB RKS60BVMB RKS71BVMB POWER SUPPLY VM VM VM VM VM NOMINAL DISTRIBUTION SYSTEM VOLTAGE Phase 1∼ 1∼ 1∼ 1∼ 1∼ Frequency Hz 50 50 50 50 50 Voltage V 230 230 230 230 230 NOTES 1 The sound pressure level is measured in an anechoic room at 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment. For measuring conditions: please refer to item 8 of this chapter. 2 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 2 Specifications 2 4 • Split - Sky Air • Outdoor Units

MAX. 50Hz 253V

MIN. 50Hz 207V 15 15 48 3.21 19 0.35 18 0.20 3D040397 RKS+FTKS35B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FTKS35BVMB RKS35BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 78 4.91 19 0.35 18 0.20 3D040398 RKS+FTKS50B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FTKS50BVMB RKS50BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 18 20 72 6.92 53 0.18 40 0.16 3D040876 RKS+FTKS60B RKS+FTKS71B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FTKS60BVMB RKS60BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 18 20 72 8.86 53 0.24 43 0.16 FTKS71BVMB RKS71BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 16.8 20 80 10.58 53 0.26 43 0.18 3D040877 RKS+FVKS25B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FVKS25BVMB RKS25BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 49 3.25 19 0.35 28 0.16 3D040399 RKS+FVKS35B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FVKS35BVMB RKS35BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 82 5.05 19 0.35 28 0.16 3D040400 SYMBOLS MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RHz : Rated operating frequency (Hz) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps W : Rated motor output (W) NOTES 1. RLA is based on the following conditions: Indoor temp.: 27°CDB/19.0°CWB Outdoor temp. : 35°CDB 2. Maximum allowable voltage unbalance between phases is 2% 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 2 Specifications 2 5 • Split - Sky Air • Outdoor Units

MAX. 50Hz 253V

MIN. 50Hz 207V 18 20 76 7.04 53 0.18 14+14 0.31 3D040876 RKS+FLKS25B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FLKS25BVMB RKS25BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 48 3.17 19 0.35 34 0.34 3D040395 RKS+FLKS35B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FLKS35BVMB RKS35BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 81 5.03 19 0.35 34 0.38 3D040396 RKS+FLKS50B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FLKS50BVMB RKS50BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 18 20 75 7.00 53 0.18 34 0.54 3D040876 RKS+FFQ25B RKS+FFQ35B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FFQ25BV1B RKS25BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 54 3.55 19 0.35 55 0.6 FFQ35BV1B RKS35BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 81 5.08 19 0.35 55 0.6 3D040596 RKS+FFQ50B RKS+FFQ60B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FFQ50BV1B RKS50BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 18 20 72 7.43 53 0.18 55 0.7 FFQ60BV1B RKS60BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 18 20 85 8.45 53 0.24 55 0.7 3D041020 SYMBOLS MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RHz : Rated operating frequency (Hz) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps W : Rated motor output (W) NOTES 1. RLA is based on the following conditions: Indoor temp.: 27°CDB/19.0°CWB Outdoor temp. : 35°CDB 2. Maximum allowable voltage unbalance between phases is 2% 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 2 Specifications 2 6 • Split - Sky Air • Outdoor Units

* This information was not available at the time of publication.

RKS+FHQ35B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FHQ35BUV1B RKS35BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 15 15 78 4.91 19 0.35 62 0.6 3D040596 RKS+FHQ50B RKS+FHQ60B Indoor unit Outdoor unit Power supply Compressor OFM IFM Hz-Volts Voltage range MCA MFA RHz RLA W FLA W FLA FHQ50BUV1B RKS50BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 18 20 79 7.5 53 0.18 62 0.6 FHQ60BUV1B RKS60BVMB 50-230 MAX. 50Hz 253V MIN. 50Hz 207V 18 20 90 8.84 53 0.24 62 0.6 3D040597 RKS+FBQ35B RKS+FBQ50B RKS+FBQ60B * This information was not available at the time of publication. SYMBOLS MCA : Min. Circuit Amps (A) MFA : Max. Fuse Amps (A) RHz : Rated operating frequency (Hz) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor IFM : Indoor Fan Motor FLA : Full Load Amps W : Rated motor output (W) NOTES 1. RLA is based on the following conditions: Indoor temp.: 27°CDB/19.0°CWB Outdoor temp. : 35°CDB 2. Maximum allowable voltage unbalance between phases is 2% 3. Select wire size based on the larger value of MCA. 4. Instead of fuse, use circuit breaker. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 2 Specifications 2 7 • Split - Sky Air • Outdoor Units

Outdoor temperature (°C)

EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 2.33 1.58 0.52 2.25 1.52 0.58 2.17 1.47 0.65 2.14 1.45 0.66 2.08 1.41 0.67 2.00 1.35 0.72 16.0 22 2.51 1.70 0.53 2.43 1.65 0.59 2.35 1.59 0.66 2.31 1.56 0.67 2.25 1.52 0.68 2.16 1.46 0.74 18.0 25 2.70 1.83 0.54 2.61 1.77 0.61 2.52 1.71 0.67 2.48 1.68 0.68 2.42 1.64 0.69 2.32 1.57 0.75 19.0 27 2.80 1.89 0.55 2.70 1.83 0.61 2.61 1.77 0.67 2.57 1.74 0.68 2.50 1.69 0.70 2.40 1.62 0.76 22.0 30 3.09 2.09 0.56 2.99 2.02 0.63 2.88 1.95 0.69 2.84 1.92 0.70 2.76 1.87 0.72 2.65 1.79 0.78 24.0 32 3.28 2.22 0.57 3.18 2.15 0.64 3.07 2.08 0.71 3.02 2.04 0.72 2.94 1.99 0.73 2.81 1.91 0.79 3D040386 RKS+FTKS35B Cooling capacity 230V [50Hz] AFR 7.4 BF 0.16 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 3.26 2.05 0.87 3.15 1.99 0.97 3.04 1.92 1.07 2.99 1.89 1.09 2.92 1.84 1.11 2.79 1.76 1.20 16.0 22 3.52 2.22 0.88 3.40 2.14 0.99 3.29 2.07 1.09 3.23 2.04 1.10 3.15 1.98 1.13 3.02 1.90 1.22 18.0 25 3.78 2.38 0.90 3.66 2.30 1.00 3.53 2.23 1.11 3.47 2.19 1.12 3.38 2.13 1.15 3.24 2.04 1.24 19.0 27 3.91 2.47 0.91 3.78 2.38 1.01 3.65 2.30 1.12 3.59 2.26 1.13 3.50 2.21 1.16 3.35 2.11 1.26 22.0 30 4.32 2.72 0.93 4.18 2.63 1.04 4.04 2.54 1.15 3.97 2.50 1.17 3.87 2.44 1.19 3.71 2.33 1.29 24.0 32 4.60 2.90 0.95 4.45 2.80 1.06 4.29 2.70 1.17 4.22 2.66 1.19 4.11 2.59 1.22 3.94 2.48 1.32 3D040387 RKS+FTKS50B Cooling capacity 230V [50Hz] AFR 11.4 BF 0.22 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 5.06 3.28 1.31 4.91 3.21 1.41 4.76 3.14 1.50 4.70 3.11 1.54 4.61 3.07 1.60 4.46 3.00 1.69 16.0 22 5.22 3.31 1.34 5.07 3.24 1.43 4.92 3.17 1.53 4.86 3.14 1.56 4.77 3.10 1.62 4.62 3.03 1.72 18.0 25 5.37 3.34 1.36 5.22 3.27 1.46 5.07 3.20 1.55 5.01 3.18 1.59 4.92 3.13 1.65 4.77 3.06 1.74 19.0 27 5.45 3.36 1.38 5.30 3.29 1.47 5.15 3.22 1.57 5.09 3.19 1.60 5.00 3.15 1.66 4.85 3.08 1.76 22.0 30 5.68 3.41 1.41 5.53 3.34 1.51 5.38 3.27 1.60 5.32 3.24 1.64 5.23 3.20 1.70 5.08 3.13 1.79 24.0 32 5.84 3.45 1.44 5.69 3.38 1.54 5.54 3.31 1.63 5.48 3.28 1.67 5.39 3.24 1.73 5.24 3.17 1.82 3D040892 RKS+FTKS60B Cooling capacity 230V [50Hz] AFR 16.2 BF 0.29 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 6.06 3.97 1.77 5.91 3.90 1.87 5.76 3.83 1.96 5.70 3.80 2.00 5.61 3.76 2.06 5.46 3.69 2.15 16.0 22 6.22 4.00 1.80 6.07 3.93 1.89 5.92 3.86 1.99 5.86 3.83 2.02 5.77 3.79 2.08 5.62 3.72 2.18 18.0 25 6.37 4.03 1.82 6.22 3.96 1.92 6.07 3.89 2.01 6.01 3.87 2.05 5.92 3.82 2.11 5.77 3.75 2.20 19.0 27 6.45 4.05 1.84 6.30 3.98 1.93 6.15 3.91 2.03 6.09 3.88 2.06 6.00 3.84 2.12 5.85 3.77 2.22 22.0 30 6.68 4.10 1.87 6.53 4.03 1.97 6.38 3.96 2.06 6.32 3.93 2.10 6.23 3.89 2.16 6.08 3.82 2.25 24.0 32 6.84 4.14 1.90 6.69 4.07 2.00 6.54 4.00 2.09 6.48 3.97 2.13 6.39 3.93 2.19 6.24 3.86 2.28 3D040895 SYMBOLS AFR: Air flow rate (m3/min) BF: Bypass factor EWB: Entering wet bulb temp. (°CWB) EDB: Entering dry bulb temp. (°CDB) TC: Total capacity (kW) SHC: Sensible heating capacity (kW) PI: Power input (kW) NOTES 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal cooling capacities and power input 3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB) Add SHC* to SHC. 5. Capacities are based on the following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0 m 6. Air flow rate (AFR) and Bypass factor (BF) are taburated above. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 3 8 • Split - Sky Air • Outdoor Units

Outdoor temperature (°C)

EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 7.16 4.60 2.18 7.01 4.53 2.28 6.86 4.46 2.37 6.80 4.43 2.41 6.71 4.39 2.47 6.56 4.32 2.56 16.0 22 7.32 4.63 2.21 7.17 4.56 2.30 7.02 4.49 2.40 6.96 4.46 2.43 6.87 4.42 2.49 6.72 4.35 2.59 18.0 25 7.47 4.67 2.23 7.32 4.60 2.33 7.17 4.53 2.42 7.11 4.50 2.46 7.02 4.46 2.52 6.87 4.39 2.61 19.0 27 7.55 4.68 2.25 7.40 4.61 2.34 7.25 4.54 2.44 7.19 4.52 2.47 7.10 4.47 2.53 6.95 4.40 2.63 22.0 30 7.78 4.73 2.28 7.63 4.66 2.38 7.48 4.59 2.47 7.42 4.57 2.51 7.33 4.52 2.57 7.18 4.45 2.66 24.0 32 7.94 4.77 2.31 7.79 4.70 2.41 7.64 4.63 2.50 7.58 4.60 2.54 7.49 4.56 2.60 7.34 4.49 2.69 3D040896 RKS+FVKS25B Cooling capacity 230V [50Hz] AFR 8.1 BF 0.29 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 2.33 1.58 0.52 2.25 1.52 0.58 2.17 1.47 0.65 2.14 1.45 0.66 2.08 1.41 0.67 2.00 1.35 0.72 16.0 22 2.51 1.70 0.53 2.43 1.65 0.59 2.35 1.59 0.66 2.31 1.56 0.67 2.25 1.52 0.68 2.16 1.46 0.74 18.0 25 2.70 1.83 0.54 2.61 1.77 0.61 2.52 1.71 0.67 2.48 1.68 0.68 2.42 1.64 0.69 2.32 1.57 0.75 19.0 27 2.80 1.89 0.55 2.70 1.83 0.61 2.61 1.77 0.67 2.57 1.74 0.68 2.50 1.60 0.70 2.40 1.62 0.76 22.0 30 3.09 2.09 0.56 2.99 2.02 0.63 2.88 1.95 0.69 2.84 1.92 0.70 2.76 1.87 0.72 2.65 1.79 0.78 24.0 32 3.28 2.22 0.57 3.18 2.15 0.64 3.07 2.08 0.71 3.02 2.04 0.72 2.94 1.99 0.73 2.81 1.91 0.79 3D040390 RKS+FVKS35B Cooling capacity 230V [50Hz] AFR 8.3 BF 0.13 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 3.26 2.12 0.87 3.15 2.05 0.97 3.04 1.98 1.07 2.99 1.95 1.09 2.92 1.90 1.11 2.79 1.82 1.20 16.0 22 3.52 2.29 0.88 3.40 2.21 0.99 3.29 2.14 1.09 3.23 2.10 1.10 3.15 2.05 1.13 3.02 1.96 1.22 18.0 25 3.78 2.46 0.90 3.66 2.38 1.00 3.53 2.30 1.11 3.47 2.26 1.12 3.38 2.20 1.15 3.24 2.11 1.24 19.0 27 3.91 2.54 0.91 3.78 2.46 1.01 3.65 2.38 1.12 3.59 2.34 1.13 3.50 2.28 1.16 3.35 2.18 1.26 22.0 30 4.32 2.81 0.93 4.18 2.72 1.04 4.04 2.62 1.15 3.97 2.58 1.17 3.87 2.51 1.19 3.71 2.41 1.29 24.0 32 4.60 2.99 0.95 4.45 2.89 1.06 4.29 2.79 1.17 4.22 2.74 1.19 4.11 2.67 1.22 3.94 2.56 1.32 3D040391 RKS+FVKS50B Cooling capacity 230V [50Hz] AFR 10.8 BF 0.23 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 4.86 3.15 1.35 4.71 3.08 1.45 4.56 3.01 1.54 4.50 2.98 1.58 4.41 2.94 1.64 4.26 2.87 1.73 16.0 22 5.02 3.18 1.38 4.87 3.11 1.47 4.72 3.04 1.57 4.66 3.02 1.60 4.57 2.97 1.66 4.42 2.90 1.76 18.0 25 5.17 3.22 1.40 5.02 3.15 1.50 4.87 3.08 1.59 4.81 3.05 1.63 4.72 3.01 1.69 4.57 2.94 1.78 19.0 27 5.25 3.23 1.42 5.10 3.16 1.51 4.95 3.09 1.61 4.89 3.07 1.64 4.80 3.02 1.70 4.65 2.95 1.80 22.0 30 5.48 3.29 1.45 5.33 3.22 1.55 5.18 3.15 1.64 5.12 3.12 1.68 5.03 3.08 1.74 4.88 3.01 1.83 24.0 32 5.64 3.32 1.48 5.49 3.25 1.58 5.34 3.18 1.67 5.28 3.15 1.71 5.19 3.11 1.77 5.04 3.04 1.86 3D040894 SYMBOLS AFR: Air flow rate (m3/min) BF: Bypass factor EWB: Entering wet bulb temp. (°CWB) EDB: Entering dry bulb temp. (°CDB) TC: Total capacity (kW) SHC: Sensible heating capacity (kW) PI: Power input (kW) NOTES 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal cooling capacities and power input 3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB) Add SHC* to SHC. 5. Capacities are based on the following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0 m 6. Air flow rate (AFR) and Bypass factor (BF) are taburated above. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 3 Capacity tables 3 9 • Split - Sky Air • Outdoor Units

Outdoor temperature (°C)

EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 2.33 1.52 0.54 2.25 1.47 0.60 2.17 1.42 0.66 2.14 1.40 0.67 2.08 1.36 0.68 2.00 1.30 0.74 16.0 22 2.51 1.64 0.54 2.43 1.59 0.61 2.35 1.53 0.67 2.31 1.51 0.68 2.25 1.47 0.70 2.16 1.41 0.75 18.0 25 2.70 1.76 0.55 2.61 1.71 0.62 2.52 1.65 0.68 2.48 1.62 0.69 2.42 1.58 0.71 2.32 1.51 0.77 19.0 27 2.80 1.82 0.56 2.70 1.76 0.62 2.61 1.70 0.69 2.57 1.67 0.70 2.50 1.83 0.72 2.40 1.56 0.77 22.0 30 3.09 2.02 0.58 2.99 1.95 0.64 2.88 1.88 0.71 2.84 1.85 0.72 2.76 1.80 0.74 2.65 1.73 0.80 24.0 32 3.28 2.14 0.59 3.18 2.07 0.65 3.07 2.00 0.72 3.02 1.97 0.73 2.94 1.92 0.75 2.81 1.84 0.81 3D040382 RKS+FLKS35B Cooling capacity 230V [50Hz] AFR 8.6 BF 0.35 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 3.26 2.02 0.91 3.15 1.95 1.02 3.04 1.89 1.12 2.99 1.86 1.14 2.92 1.81 1.17 2.79 1.73 1.26 16.0 22 3.52 2.18 0.93 3.40 2.11 1.04 3.29 2.04 1.14 3.23 2.00 1.16 3.15 1.95 1.19 3.02 1.87 1.29 18.0 25 3.78 2.35 0.95 3.66 2.27 1.06 3.53 2.19 1.16 3.47 2.15 1.18 3.38 2.10 1.21 3.24 2.01 1.31 19.0 27 3.91 2.43 0.95 3.78 2.35 1.06 3.65 2.27 1.17 3.59 2.23 1.19 3.50 2.17 1.22 3.35 2.08 1.32 22.0 30 4.32 2.68 0.98 4.18 2.59 1.10 4.04 2.50 1.21 3.97 2.46 1.23 3.87 2.40 1.26 3.71 2.30 1.36 24.0 32 4.60 2.85 1.00 4.45 2.76 1.12 4.29 2.66 1.23 4.22 2.62 1.25 4.11 2.55 1.28 3.94 2.44 1.38 3D040383 RKS+FLKS50B Cooling capacity 230V [50Hz] AFR 11.4 BF 0.18 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 4.96 3.26 1.37 4.81 3.19 1.47 4.66 3.12 1.56 4.60 3.09 1.60 4.51 3.05 1.66 4.36 2.98 1.75 16.0 22 5.12 3.30 1.40 4.97 3.23 1.49 4.82 3.16 1.59 4.76 3.13 1.62 4.67 3.09 1.68 4.52 3.02 1.78 18.0 25 5.27 3.33 1.42 5.12 3.26 1.52 4.97 3.19 1.61 4.91 3.16 1.65 4.82 3.12 1.71 4.67 3.05 1.80 19.0 27 5.35 3.35 1.44 5.20 3.28 1.53 5.05 3.21 1.63 4.99 3.18 1.66 4.90 3.14 1.72 4.75 3.07 1.82 22.0 30 5.58 3.40 1.47 5.43 3.33 1.57 5.28 3.26 1.66 5.22 3.23 1.70 5.13 3.19 1.76 4.98 3.12 1.85 24.0 32 5.74 3.43 1.50 5.59 3.36 1.60 5.44 3.29 1.69 5.38 3.26 1.73 5.29 3.22 1.79 5.14 3.15 1.88 3D040893 RKS+FFQ25B Cooling capacity 230V [50Hz] AFR 9.0 BF 0.24 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 2.33 1.82 0.62 2.25 1.76 0.69 2.17 1.70 0.76 2.14 1.67 0.78 2.08 1.62 0.79 2.00 1.56 0.86 16.0 22 2.51 1.96 0.63 2.43 1.90 0.71 2.35 1.83 0.78 2.31 1.80 0.79 2.25 1.75 0.81 2.16 1.68 0.87 18.0 25 2.70 2.11 0.64 2.61 2.04 0.72 2.52 1.97 0.79 2.48 1.93 0.80 2.42 1.88 0.82 2.32 1.81 0.89 19.0 27 2.80 2.18 0.65 2.70 2.11 0.72 2.61 2.04 0.80 2.57 2.00 0.81 2.50 1.95 0.83 2.40 1.87 0.90 22.0 30 3.09 2.41 0.67 2.99 2.33 0.75 2.88 2.25 0.82 2.84 2.21 0.84 2.76 2.15 0.85 2.65 2.06 0.92 24.0 32 3.28 2.56 0.68 3.18 2.48 0.76 3.07 2.39 0.84 3.02 2.35 0.85 2.94 2.29 0.87 2.81 2.20 0.94 3D040764 SYMBOLS AFR: Air flow rate (m3/min) BF: Bypass factor EWB: Entering wet bulb temp. (°CWB) EDB: Entering dry bulb temp. (°CDB) TC: Total capacity (kW) SHC: Sensible heating capacity (kW) PI: Power input (kW) NOTES 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal cooling capacities and power input 3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB) Add SHC* to SHC. 5. Capacities are based on the following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0 m 6. Air flow rate (AFR) and Bypass factor (BF) are taburated above. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 3 Capacity tables 3 10 • Split - Sky Air • Outdoor Units

Outdoor temperature (°C)

EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 3.17 2.25 0.97 3.06 2.18 1.09 2.96 2.10 1.20 2.91 2.07 1.22 2.83 2.02 1.24 2.71 1.93 1.35 16.0 22 3.42 2.43 0.99 3.31 2.35 1.10 3.19 2.27 1.22 3.14 2.24 1.24 3.06 2.18 1.27 2.93 2.09 1.37 18.0 25 3.67 2.62 1.01 3.55 2.53 1.12 3.43 2.44 1.24 3.37 2.40 1.26 3.29 2.34 1.29 3.15 2.24 1.39 19.0 27 3.80 2.71 1.02 3.68 2.62 1.13 3.55 2.53 1.25 3.49 2.48 1.27 3.40 2.42 1.30 3.26 2.32 1.41 22.0 30 4.20 2.99 1.05 4.06 2.89 1.17 3.92 2.79 1.29 3.86 2.74 1.31 3.76 2.67 1.34 3.60 2.56 1.45 24.0 32 4.47 3.18 1.07 4.32 3.07 1.19 4.17 2.97 1.31 4.10 2.92 1.33 4.00 2.84 1.36 3.83 2.72 1.48 3D040766 RKS+FFQ50B Cooling capacity 230V [50Hz] AFR 12.0 BF 0.16 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 4.76 3.51 1.45 4.61 3.44 1.55 4.46 3.37 1.64 4.40 3.34 1.68 4.31 3.30 1.74 4.16 3.23 1.83 16.0 22 4.92 3.54 1.48 4.77 3.47 1.57 4.62 3.40 1.67 4.56 3.38 1.70 4.47 3.33 1.76 4.32 3.26 1.86 18.0 25 5.07 3.58 1.50 4.92 3.51 1.60 4.77 3.44 1.69 4.71 3.41 1.73 4.62 3.37 1.79 4.47 3.30 1.88 19.0 27 5.15 3.59 1.52 5.00 3.52 1.61 4.85 3.45 1.71 4.79 3.43 1.74 4.70 3.38 1.80 4.55 3.31 1.90 22.0 30 5.38 3.65 1.55 5.23 3.58 1.65 5.08 3.51 1.74 5.02 3.48 1.78 4.93 3.44 1.84 4.78 3.37 1.93 24.0 32 5.54 3.68 1.58 5.39 3.61 1.68 5.24 3.54 1.77 5.18 3.51 1.81 5.09 3.47 1.87 4.94 3.40 1.96 3D041022 RKS+FFQ60B Cooling capacity 230V [50Hz] AFR 15.0 BF 0.11 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 5.86 4.30 1.72 5.71 4.23 1.82 5.56 4.16 1.91 5.50 4.13 1.95 5.41 4.09 2.01 5.26 4.02 2.10 16.0 22 6.02 4.34 1.75 5.87 4.27 1.84 5.72 4.20 1.94 5.66 4.17 1.97 5.57 4.13 2.03 5.42 4.06 2.13 18.0 25 6.17 4.37 1.77 6.02 4.30 1.87 5.87 4.23 1.96 5.81 4.20 2.00 5.72 4.16 2.06 5.57 4.09 2.15 19.0 27 6.25 4.39 1.79 6.10 4.32 1.88 5.95 4.25 1.98 5.89 4.22 2.01 5.80 4.18 2.07 5.65 4.11 2.17 22.0 30 6.48 4.44 1.82 6.33 4.37 1.92 6.18 4.30 2.01 6.12 4.27 2.05 6.03 4.23 2.11 5.88 4.16 2.20 24.0 32 6.64 4.47 1.85 6.49 4.40 1.95 6.34 4.33 2.04 6.28 4.30 2.08 6.19 4.26 2.14 6.04 4.19 2.23 3D041027 SYMBOLS AFR: Air flow rate (m3/min) BF: Bypass factor EWB: Entering wet bulb temp. (°CWB) EDB: Entering dry bulb temp. (°CDB) TC: Total capacity (kW) SHC: Sensible heating capacity (kW) PI: Power input (kW) NOTES 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal cooling capacities and power input 3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB) Add SHC* to SHC. 5. Capacities are based on the following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0 m 6. Air flow rate (AFR) and Bypass factor (BF) are taburated above. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 3 Capacity tables 3 11 • Split - Sky Air • Outdoor Units

Outdoor temperature (°C)

EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 35 14.0 20.0 3.2 2.7 0.91 3.1 2.6 1.01 3.0 2.5 1.12 2.9 2.4 1.13 2.8 2.4 1.16 2.7 2.3 1.25 16.0 22.0 3.4 2.9 0.92 3.3 2.8 1.03 3.2 2.7 1.14 3.1 2.6 1.15 3.1 2.6 1.18 2.9 2.5 1.28 18.0 25.0 3.7 3.1 0.94 3.6 3.0 1.05 3.4 2.9 1.16 3.4 2.8 1.17 3.3 2.8 1.20 3.2 2.6 1.30 19.0 27.0 3.8 3.2 0.95 3.7 3.1 1.06 3.6 3.0 1.17 3.5 2.9 1.18 3.4 2.9 1.21 3.3 2.7 1.31 22.0 30.0 4.2 3.5 0.97 4.1 3.4 1.09 3.9 3.3 1.20 3.9 3.2 1.22 3.8 3.2 1.25 3.6 3.0 1.35 24.0 32.0 4.5 3.8 0.99 4.3 3.6 1.11 4.2 3.5 1.22 4.1 3.4 1.24 4.0 3.4 1.27 3.8 3.2 1.37 50 14.0 20.0 5.1 3.7 1.57 4.9 3.6 1.67 4.8 3.5 1.76 4.7 3.5 1.80 4.6 3.5 1.86 4.5 3.4 1.95 16.0 22.0 5.2 3.7 1.60 5.1 3.6 1.69 4.9 3.6 1.79 4.9 3.5 1.83 4.8 3.5 1.88 4.6 3.4 1.98 18.0 25.0 5.4 3.7 1.62 5.2 3.7 1.72 5.1 3.6 1.81 5.0 3.6 1.85 4.9 3.5 1.91 4.8 3.5 2.00 19.0 27.0 5.5 3.8 1.64 5.3 3.7 1.73 5.2 3.6 1.83 5.1 3.6 1.87 5.0 3.6 1.92 4.9 3.5 2.02 22.0 30.0 5.7 3.8 1.68 5.5 3.7 1.77 5.4 3.7 1.87 5.3 3.6 1.90 5.2 3.6 1.96 5.1 3.5 2.06 24.0 32.0 5.8 3.8 1.70 5.7 3.8 1.80 5.5 3.7 1.89 5.5 3.7 1.93 5.4 3.6 1.99 5.2 3.6 2.08 60 14.0 20.0 5.8 4.5 1.84 5.6 4.4 1.94 5.5 4.3 2.03 5.4 4.3 2.07 5.3 4.3 2.13 5.2 4.2 2.22 16.0 22.0 5.9 4.5 1.87 5.8 4.4 1.96 5.6 4.4 2.06 5.6 4.4 2.10 5.5 4.3 2.15 5.3 4.2 2.25 18.0 25.0 6.1 4.6 1.89 5.9 4.5 1.99 5.8 4.4 2.08 5.7 4.4 2.12 5.6 4.3 2.18 5.5 4.3 2.27 19.0 27.0 6.2 4.6 1.91 6.0 4.5 2.00 5.9 4.4 2.10 5.8 4.4 2.13 5.7 4.4 2.19 5.6 4.3 2.29 22.0 30.0 6.4 4.6 1.95 6.2 4.6 2.04 6.1 4.5 2.14 6.0 4.5 2.17 5.9 4.4 2.23 5.8 4.3 2.33 24.0 32.0 6.5 4.7 1.97 6.4 4.6 2.07 6.2 4.5 2.16 6.2 4.5 2.20 6.1 4.4 2.26 5.9 4.4 2.35 3TW25082-1 SYMBOLS AFR: Air flow rate (m3/min) BF: Bypass factor EWB: Entering wet bulb temp. (°CWB) EDB: Entering dry bulb temp. (°CDB) TC: Total capacity (kW) SHC: Sensible heating capacity (kW) PI: Power input (kW) (comp.+indoor+outdoor fan motor) NOTES 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal cooling capacities and power input 3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB-EDB)/860 Add SHC* to SHC. 5. Capacities are based on the following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0 m 6. Air flow rate and BF are tabulated below. Model FCQ 35 AFR 14 BF 0.16 50 AFR 15 BF 0.16 60 AFR 18 BF 0.10 • Pair Application • R-410A • RKS25-35-50-60-71BVMB 3 Capacity tables 3 12 • Split - Sky Air • Outdoor Units

Outdoor temperature (°C)

EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 3.17 2.47 0.91 3.06 2.39 1.01 2.96 2.30 1.12 2.91 2.27 1.13 2.83 2.21 1.16 2.71 2.11 1.25 16.0 22 3.42 2.67 0.92 3.31 2.58 1.03 3.19 2.49 1.14 3.14 2.45 1.15 3.06 2.38 1.18 2.93 2.28 1.28 18.0 25 3.67 2.86 0.94 3.55 2.77 1.05 3.43 2.67 1.16 3.37 2.63 1.17 3.29 2.56 1.20 3.15 2.45 1.30 19.0 27 3.80 2.96 0.95 3.68 2.86 1.06 3.55 2.77 1.17 3.49 2.72 1.18 3.40 2.65 1.21 3.26 2.54 1.31 22.0 30 4.20 3.27 0.97 4.06 3.17 1.09 3.92 3.06 1.20 3.86 3.01 1.22 3.76 2.93 1.25 3.60 2.81 1.35 24.0 32 4.47 3.48 0.99 4.32 3.37 1.11 4.17 3.25 1.22 4.10 3.20 1.24 4.00 3.11 1.27 3.83 2.98 1.37 3D040599 RKS+FHQ50B Cooling capacity 230V [50Hz] AFR 13 BF 0.1 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 5.06 3.63 1.48 4.91 3.56 1.58 4.76 3.49 1.67 4.70 3.46 1.71 4.61 3.42 1.77 4.46 3.35 1.86 16.0 22 5.22 3.66 1.51 5.07 3.59 1.60 4.92 3.52 1.70 4.86 3.49 1.73 4.77 3.45 1.79 4.62 3.38 1.89 18.0 25 5.37 3.69 1.53 5.22 3.62 1.63 5.07 3.55 1.72 5.01 3.53 1.76 4.92 3.48 1.82 4.77 3.41 1.91 19.0 27 5.45 3.71 1.55 5.30 3.64 1.64 5.15 3.57 1.74 5.09 3.54 1.77 5.00 3.50 1.83 4.85 3.43 1.93 22.0 30 5.68 3.76 1.58 5.53 3.69 1.68 5.38 3.62 1.77 5.32 3.59 1.81 5.23 3.55 1.87 5.08 3.48 1.96 24.0 32 5.84 3.80 1.61 5.69 3.73 1.71 5.54 3.66 1.80 5.48 3.63 1.84 5.39 3.59 1.90 5.24 3.52 1.99 3D040601 RKS+FHQ60B Cooling capacity 230V [50Hz] AFR 17 BF 0.2 Indoor Outdoor temperature (°C) EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14.0 20 5.76 4.17 1.80 5.61 4.10 1.90 5.46 4.03 1.99 5.40 4.00 2.03 5.31 3.96 2.09 5.16 3.89 2.18 16.0 22 5.92 4.21 1.83 5.77 4.14 1.92 5.62 4.07 2.02 5.56 4.04 2.05 5.47 4.00 2.11 5.32 3.93 2.21 18.0 25 6.07 4.24 1.85 5.92 4.17 1.95 5.77 4.10 2.04 5.71 4.07 2.08 5.62 4.03 2.14 5.47 3.96 2.23 19.0 27 6.15 4.26 1.87 6.00 4.19 1.96 5.85 4.12 2.06 5.79 4.09 2.09 5.70 4.05 2.15 5.55 3.98 2.25 22.0 30 6.38 4.31 1.90 6.23 4.24 2.00 6.08 4.17 2.09 6.02 4.14 2.13 5.93 4.10 2.19 5.78 4.03 2.28 24.0 32 6.54 4.34 1.93 6.39 4.27 2.03 6.24 4.20 2.12 6.18 4.17 2.16 6.09 4.13 2.22 5.94 4.06 2.31 3D040604 SYMBOLS AFR: Air flow rate (m3/min) BF: Bypass factor EWB: Entering wet bulb temp. (°CWB) EDB: Entering dry bulb temp. (°CDB) TC: Total capacity (kW) SHC: Sensible heating capacity (kW) PI: Power input (kW) NOTES 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal cooling capacities and power input 3. TC, PI and SHC must be calculated by interpolation using the figures in the above tables. (Figures out of the tables should not be used for calculation.) 4. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB) Add SHC* to SHC. 5. Capacities are based on the following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0 m 6. Air flow rate (AFR) and Bypass factor (BF) are taburated above. • Pair Application • R-410A • RKS25-35-50-60-71BVMB 3 Capacity tables 3 13 • Split - Sky Air • Outdoor Units

Outdoor temperature (°C)

EWB EDB 20 25 30 32 35 40 (°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 35 14.0 20.0 3.2 2.4 0.91 3.1 2.3 1.01 3.0 2.2 1.12 2.9 2.2 1.13 2.8 2.1 1.16 2.7 2.0 1.25 16.0 22.0 3.4 2.6 0.92 3.3 2.5 1.03 3.2 2.4 1.14 3.1 2.4 1.15 3.1 2.3 1.18 2.9 2.2 1.28 18.0 25.0 3.7 2.8 0.94 3.6 2.7 1.05 3.4 2.6 1.16 3.4 2.5 1.17 3.3 2.5 1.20 3.2 2.4 1.30 19.0 27.0 3.8 2.9 0.95 3.7 2.8 1.06 3.6 2.7 1.17 3.5 2.6 1.18 3.4 2.6 1.21 3.3 2.4 1.31 22.0 30.0 4.2 3.2 0.97 4.1 3.0 1.09 3.9 2.9 1.20 3.9 2.9 1.22 3.8 2.8 1.25 3.6 2.7 1.35 24.0 32.0 4.5 3.3 0.99 4.3 3.2 1.11 4.2 3.1 1.22 4.1 3.1 1.24 4.0 3.0 1.27 3.8 2.9 1.37 50 14.0 20.0 5.1 3.6 1.57 4.9 3.5 1.67 4.8 3.4 1.76 4.7 3.4 1.80 4.6 3.4 1.86 4.5 3.3 1.95 16.0 22.0 5.2 3.6 1.60 5.1 3.5 1.69 4.9 3.5 1.79 4.9 3.4 1.83 4.8 3.4 1.88 4.6 3.3 1.98 18.0 25.0 5.4 3.6 1.62 5.2 3.6 1.72 5.1 3.5 1.81 5.0 3.5 1.85 4.9 3.4 1.91 4.8 3.4 2.00 19.0 27.0 5.5 3.7 1.64 5.3 3.6 1.73 5.2 3.5 1.83 5.1 3.5 1.87 5.0 3.5 1.92 4.9 3.4 2.02 22.0 30.0 5.7 3.7 1.68 5.5 3.6 1.77 5.4 3.6 1.87 5.3 3.5 1.90 5.2 3.5 1.96 5.1 3.4 2.06 24.0 32.0 5.8 3.7 1.70 5.7 3.7 1.80 5.5 3.6 1.89 5.5 3.6 1.93 5.4 3.5 1.99 5.2 3.5 2.08 60 14.0 20.0 5.8 4.6 1.84 5.6 4.6 1.94 5.5 4.5 2.03 5.4 4.5 2.07 5.3 4.4 2.13 5.2 4.3 2.22 16.0 22.0 5.9 4.7 1.87 5.8 4.6 1.96 5.6 4.5 2.06 5.6 4.5 2.10 5.5 4.5 2.15 5.3 4.4 2.25 18.0 25.0 6.1 4.7 1.89 5.9 4.6 1.99 5.8 4.6 2.08 5.7 4.5 2.12 5.6 4.5 2.18 5.5 4.4 2.27 19.0 27.0 6.2 4.7 1.91 6.0 4.6 2.00 5.9 4.6 2.10 5.8 4.5 2.13 5.7 4.5 2.19 5.6 4.4 2.29 22.0 30.0 6.4 4.8 1.95 6.2 4.7 2.04 6.1 4.6 2.14 6.0 4;6 2.17 5.9 4.6 2.23 5.8 4.5 2.33 24.0 32.0 6.5 4.8 1.97 6.4 4.7 2.07 6.2 4.7 2.16 6.2 4.6 2.20 6.1 4.6 2.26 5.9 4.5 2.35 3TW25112-1 SYMBOLS AFR: Air flow rate (m3/min) BF: Bypass factor EWB: Entering wet bulb temp. (°CWB) EDB: Entering dry bulb temp. (°CDB) TC: Total capacity (kW) SHC: Sensible heating capacity (kW) PI: Power input (kW) (comp.+indoor+outdoor fan motor) NOTES 1. Ratings shown are net capacities which include a deduction for indoor fan motor heat 2. Shows nominal cooling capacities and power input 3. SHC is based on each EWB and EDB SHC* = SHC correction for other dry bulb SHC* = 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB-EDB)/860 Add SHC* to SHC. 4. Direct interpolation is permissible. Do not extrapolate. 5. Capacities are based on the following conditions: Corresponding refrigerant piping length: 7.5 m Level difference: 0 m 6. Air flow rate and BF are tabulated below. Model FCQ 35 AFR 11.5 BF 0.15 50 AFR 14 BF 0.15 60 AFR 19 BF 0.11 • Pair Application • R-410A • RKS25-35-50-60-71BVMB 3 Capacity tables 3 14 • Split - Sky Air • Outdoor Units

Minimum space for air passage

Wall height on air outlet side = less than 1200 Drain outlet (I.D. J 15.9 hose for connection) 4 x holes for anchor bolts (M8 or M10) Name plate Terminal strip with earth terminal Wiring inlet Gas stop valve (J B CuT) Liquid stop valve (J A CuT) Service port Outdoor air thermistor Brand name label In case of removing stop valve cover RKS50,60,71 unit (mm) 3D034257B Minimum space for air passage Wall height on air outlet side = less than 1200 Drain outlet (I.D. J 15.9 hose for connection) 4 x holes for anchor bolts (M8 or M10) Name plate Terminal strip with earth terminal Wiring inlet Gas stop valve (J B CuT) Liquid stop valve (J A CuT) Service port Outdoor air thermistor Brand name label In case of removing stop valve cover Indication label (refrigerant) Model A B RKS50, RKS60 6.4 12.7 RKS71 6.4 15.9 • Pair Application • R-410A • RKS25-35-50-60-71BVMB 4 15 • Split - Sky Air • Outdoor Units

Outdoor temp. (°CDB)

Pull-down period Indoor temp. (°CWB) Notes: The graph is based on the following conditions: 1. Equivalent piping length 7.5 m 2. Level difference 0 m 3. Air flow rate high • Pair Application • R-410A • RKS25-35-50-60-71BVMB 5 16 • Split - Sky Air • Outdoor Units

Outdoor temperature thermistor

Heat exchanger Propeller fan Capillary tube 1 Liquid stop valve Field piping Field piping Accumulator Compressor Muffler Refrigerant flow Cooling Discharge pipe thermistor Heat exchanger thermistor Capillary tube 2 Muffler Motor operated valve Muffler with filter Outdoor unit Gas stop valve Muffler with filter Muffler with filter 3D039304 RKS35 Outdoor temperature thermistor Heat exchanger Propeller fan Liquid stop valve Field piping Field piping Accumulator Compressor Muffler Refrigerant flow Cooling Discharge pipe thermistor Heat exchanger thermistor Muffler Motor operated valve Muffler with filter Outdoor unit Gas stop valve Muffler with filter Muffler with filter • Pair Application • R-410A • RKS25-35-50-60-71BVMB 6 17 • Split - Sky Air • Outdoor Units

Outdoor temperature thermistor

Heat exchanger Propeller fan Capillary tube 1 Liquid stop valve Field piping Field piping Gas stop valve with service port Accumulator Compressor Capillary tube 3 Refrigerant flow Cooling Discharge pipe thermistor Heat exchanger thermistor Capillary tube 2 Muffler with filter Motor operated valve Muffler with filter Filter Outdoor unit 3D037836A RKS60,71 Outdoor temperature thermistor Heat exchanger Propeller fan Capillary tube 1 Liquid stop valve Field piping Field piping Gas stop valve with service port Accumulator Compressor Capillary tube 3 Refrigerant flow Cooling Discharge pipe thermistor Heat exchanger thermistor Capillary tube 2 Capillary tube 4 Muffler with filter Motor operated valve Muffler with filter Filter Outdoor unit • Pair Application • R-410A • RKS25-35-50-60-71BVMB 6 Piping diagrams 6 18 • Split - Sky Air • Outdoor Units

: Protective earth

C9, C11 C12∼C15 : Capacitor CT1 : Current transformer DB1, DB2 : Diode bridge F1U, F2U : Fuse L : Live L1 : Coil L1R : Reactor M1C : Compressor motor M1F : Fan motor PCB1 : Printed circuit board MRH, MRL, MRM10, MRM20 : Magnetic relay N : Neutral PCB2 : Printed circuit board Q1L : Overload protector R1T, R2T, R3T, R4T : Thermistor S10, S11, S20, S45 S70, S90, S91 HL3, HN3 : Connector SA1 : Surge arrester Z1C : Ferrite core IC3 : Solid state relay TFU : Thermal fuse TRM1 : Transistor module V1, V2, V3 : Varistor Y1E : Electronic expansion valve coil X1M : Terminal strip g Field wiring Indoor Outdoor (outdoor) (Condenser) (discharge) 3D037866D RKS50,60,71 R : Protective earth Z1C, Z2C : Ferrite core X1M : Terminal strip Y2E : Electronic expansion valve coil V2∼V5 : Varistor F1U, F2U, FU201 : Fuse HE1, HE2, HAC1, E, AC1, AC2 H1, H2, HL L1, L2, X11A : Connector MRM10, MRM20, MRC/W : Magnetic relay R1T∼R3T : Thermistor S2∼S102 : Connector LEDA : Pilot lamp PCB1, PCB2 : Printed circuit board L : Live N : Neutral S1W : Forced operation on/off switch (SW1) S4W : Local setting SA1 : Surge arrester DB1 : Diode bridge M1C : Compressor motor M1F : Fan motor L1R : Reactor g Field wiring Indoor Power supply ∼50Hz 220-240V ∼60Hz 220-230V Outdoor (outdoor) (Condenser) (discharge) Q1L : Overload protector CT1 : Current transformer MID : Molded interconnect device SPM : System power module To indoor unit • Pair Application • R-410A • RKS25-35-50-60-71BVMB 7 19 • Split - Sky Air • Outdoor Units

Sound level data

Octave band sound pressure level Octave band sound pressure level Cooling only Model Sound pressure level Sound power level (cooling) 230V, 50Hz Measuring location Cooling H L RKS25B 46 43 59 RKS35B 47 44 60 RKS50B 47 * 63 RKS60B 49 * 64 RKS71B 52 * 66 * This information was not available at the time of publication. Octave band center frequency (Hz) Octave band center frequency (Hz) RKS25B (Cooling) RKS35B (Cooling) 4D013520E 4D013518E Legend 50/60Hz, 220-240/220-230V 8-2 Sound pressure spectrum approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise NOTES 1 Operation sound is measured in an anechoic chamber. 2 Operation sound level differs with operation and ambient conditions. 3 Reference acoustic pressure 0dB = 20µPa • Pair Application • R-410A • RKS25-35-50-60-71BVMB 8 8-1 20 • Split - Sky Air • Outdoor Units

Sound pressure spectrum

Octave band sound pressure level Octave band sound pressure level Octave band center frequency (Hz) Octave band center frequency (Hz) RKS50B RKS60B 4D040949 4D027648B approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise RKS71B Octave band sound pressure level approximate threshold hearing for continuous noise 3D027650B Octave band center frequency (Hz) NOTES 1 Operation sound is measured in an anechoic chamber. 2 Operation sound level differs with operation and ambient conditions. 3 Reference acoustic pressure 0dB = 20µPa Legend 50/60Hz, 220-240/220-230V Cooling only • Pair Application • R-410A • RKS25-35-50-60-71BVMB 8 8-2 21 • Split - Sky Air • Outdoor Units

Accessories supplied with the outdoor unit:

1 9-2 Optional accessories RKS-B RKS25BVMB RKS35BVMB RKS50BVMB RKS60BVMB RKS71BVMB Air direction adjustment grille KPW937A4 KPW945A4 Installation manual • Pair Application • R-410A • RKS25-35-50-60-71BVMB 9 9-1 22 • Split - Sky Air • Outdoor Units

Outdoor unit installation drawings

Wrap the installation pipe with the finishing tape from bottom to top Model 25 / 35 class Max. allowable length Cooling only: 25m Heat pump: 15m Max. allowable height 15m Additional refrigerant required for refrigerant pipe exceeding 10 m in length. 20 g/m Gas pipe O.D. 9.5 mm Liquid pipe O.D. 6.4 mm * Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance. In sites with poor drainage, use block bases for outdoor unit. Adjust foot height until the unit is leveled. Otherwise, water leakage or pooling of water may occur. Where there is a danger of the unit falling, use foot bolts, or wires. Allow space for piping and electrical servicing. Service lid How to remove the service lid. + This service lid is an open/close type. + Slide the lid downward to remove it. How to attach the service lid. + Insert the upper part of the service lid into the outdoor unit to install. + Tighten the screws. Foot bolt-hole centres Foot bolt-hole centres From unit’s side 470 115 288 250 mm from wall RKS25,35B • Pair Application • R-410A • RKS25-35-50-60-71BVMB 10 23 • Split - Sky Air • Outdoor Units

Outdoor unit installation drawings

Wrap the installation pipe with the finishing tape from bottom to top Model 50 class 60 class 71 class Max. allowable length 30m Max. allowable height 20m Additional refrigerant required for refrigerant pipe exceeding 10 m in length. 20 g/m Gas pipe O.D. 12.7 mm O.D. 9.5 mm Liquid pipe O.D. 6.4 mm * Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance. In sites with poor drainage, use block bases for outdoor unit. Adjust foot height until the unit is leveled. Otherwise, water leakage or pooling of water may occur. Where there is a danger of the unit falling, use foot bolts, or wires. Allow space for piping and electrical servicing. Service lid Foot bolt-hole centres Foot bolt-hole centres From unit’s side 250 mm from wall RKS50,60,71B • Pair Application • R-410A • RKS25-35-50-60-71BVMB 10 Installation 10 24 • Split - Sky Air • Outdoor Units