Daikin RKS25BVMB Techical Data
Text of the manual
Split - Sky Air
EEDE03-1/2 • 04/2003
Prepared in Belgium by Goekint Graphics
Zandvoordestraat 300
B - 8400 Ostend Belgium
Internet: http://www.daikineurope.com
Specifications are subject to change without prior notice.
ISO14001 assures an effective environmental
management system in order to help protect
human health and the environment from the potential
impact of our activities, products and services and to
assist in maintaining and improving the quality of
the environment
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001
standard. ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as to services
related to the product.
Daikin units comply with the European
regulations that guarantee the safety of
the product.
Daikin Europe N.V. is participating
in the EUROVENT Certification Programme.
Products are as listed in the EUROVENT
Directory of Certified Products.
TABLE OF CONTENTS
RKS-B
1
Features
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
2
Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Technical specifications
Electrical specifications
Electrical data
3
Capacity tables
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
4
Dimensional drawings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
5
Operation range
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
6
Piping diagrams
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
17
7
Wiring diagrams
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
8
Sound level
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
Sound level data
Sound pressure spectrum
9
Accessories
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
22
Standard accessories
Optional accessories
10
Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
1
• Split - Sky Air • Outdoor Units
Outdoor units for pair application
+ Daikin outdoor units can be mounted easily on a roof or terrace or simply placed against an outside wall.
They are fitted with a swing compressor, renowned for its low noise and high energy efficiency.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
1
2
• Split - Sky Air • Outdoor Units
Sound pressure (1) (Cooling)
High/Low
dBA
46/43
47/44
47/*
49/*
52/*
Sound power (2) (Cooling)
High
dBA
59
60
63
64
66
FAN
Air flow rate (Cooling)
High/Low
m3/min
25.3/17.0
25.3/17.0
47.7/44.1
47.6/44.1
51.5/41.5
Speed (Cooling)
high
rpm
670
670
700
730
790
low
rpm
450
450
650
680
650
Model
Propeller fan
Motor output
W
19
53
HEAT EXCHANGER
Type
Waffle fin, J 8 Hi-XA tube
Rows x stages x fin pitch
mm
2 x 24 x 1.5
1 x 32 x 1.6
2 x 32 x 1.8
REFRIGERANT CIRCUIT
Refrigerant type
R-410A
Refrigerant charge
kg
0.96
1.06
1.20
1.70
1.70
Maximum allowable distance between indoor
and outdoor
m
25
30
Maximum allowable level difference
m
15
20
Refrigerant control
Motor operated expansion valve
-
COMPRESSOR
Type
Hermetically sealed swing type
Model
1YC23GXD#A
2YC32HXD
2YC45BXD
Motor output
600
600
1,500
1,500
1,900
Oil type
FVC50K
Oil charge volume
!
0.40
0.40
0.65
0.65
0.75
PIPING CONNECTIONS
liquid
mm
φ6.4
gas
mm
φ9.5
φ12.7
φ15.9
drain
mm
φ18.0
INSULATION MATERIAL
Heat insulation
Both liquid and gas pipes
* This information was not available at the time of publication.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
2
3
• Split - Sky Air • Outdoor Units
Nominal running current
cooling
A
3.52
5.22
6.82
9.12
10.90
Max. running current
cooling
A
Please refer to electrical data
Starting current
cooling
A
3.7
5.4
7.3
9.3
11.1
OUTDOOR UNITS
RKS25BVMB
RKS35BVMB
RKS50BVMB
RKS60BVMB
RKS71BVMB
POWER SUPPLY
VM
VM
VM
VM
VM
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase
1∼
1∼
1∼
1∼
1∼
Frequency
Hz
50
50
50
50
50
Voltage
V
230
230
230
230
230
NOTES
1
The sound pressure level is measured in an anechoic room at 1m distance from the unit. It is a relative value, depending on the distance and
acoustic environment. For measuring conditions: please refer to item 8 of this chapter.
2
The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
2
Specifications
2
4
• Split - Sky Air • Outdoor Units
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
48
3.21
19
0.35
18
0.20
3D040397
RKS+FTKS35B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTKS35BVMB
RKS35BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
78
4.91
19
0.35
18
0.20
3D040398
RKS+FTKS50B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTKS50BVMB
RKS50BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
6.92
53
0.18
40
0.16
3D040876
RKS+FTKS60B
RKS+FTKS71B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTKS60BVMB
RKS60BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
8.86
53
0.24
43
0.16
FTKS71BVMB
RKS71BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
16.8
20
80
10.58
53
0.26
43
0.18
3D040877
RKS+FVKS25B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FVKS25BVMB
RKS25BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
49
3.25
19
0.35
28
0.16
3D040399
RKS+FVKS35B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FVKS35BVMB
RKS35BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
82
5.05
19
0.35
28
0.16
3D040400
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
2
Specifications
2
5
• Split - Sky Air • Outdoor Units
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
76
7.04
53
0.18
14+14
0.31
3D040876
RKS+FLKS25B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FLKS25BVMB
RKS25BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
48
3.17
19
0.35
34
0.34
3D040395
RKS+FLKS35B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FLKS35BVMB
RKS35BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
81
5.03
19
0.35
34
0.38
3D040396
RKS+FLKS50B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FLKS50BVMB
RKS50BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
75
7.00
53
0.18
34
0.54
3D040876
RKS+FFQ25B
RKS+FFQ35B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FFQ25BV1B
RKS25BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
54
3.55
19
0.35
55
0.6
FFQ35BV1B
RKS35BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
81
5.08
19
0.35
55
0.6
3D040596
RKS+FFQ50B
RKS+FFQ60B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FFQ50BV1B
RKS50BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
72
7.43
53
0.18
55
0.7
FFQ60BV1B
RKS60BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
85
8.45
53
0.24
55
0.7
3D041020
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
2
Specifications
2
6
• Split - Sky Air • Outdoor Units
* This information was not available at the time of publication.
RKS+FHQ35B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FHQ35BUV1B
RKS35BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
15
15
78
4.91
19
0.35
62
0.6
3D040596
RKS+FHQ50B
RKS+FHQ60B
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FHQ50BUV1B
RKS50BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
79
7.5
53
0.18
62
0.6
FHQ60BUV1B
RKS60BVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
18
20
90
8.84
53
0.24
62
0.6
3D040597
RKS+FBQ35B
RKS+FBQ50B
RKS+FBQ60B
* This information was not available at the time of publication.
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
2
Specifications
2
7
• Split - Sky Air • Outdoor Units
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
2.33
1.58
0.52
2.25
1.52
0.58
2.17
1.47
0.65
2.14
1.45
0.66
2.08
1.41
0.67
2.00
1.35
0.72
16.0
22
2.51
1.70
0.53
2.43
1.65
0.59
2.35
1.59
0.66
2.31
1.56
0.67
2.25
1.52
0.68
2.16
1.46
0.74
18.0
25
2.70
1.83
0.54
2.61
1.77
0.61
2.52
1.71
0.67
2.48
1.68
0.68
2.42
1.64
0.69
2.32
1.57
0.75
19.0
27
2.80
1.89
0.55
2.70
1.83
0.61
2.61
1.77
0.67
2.57
1.74
0.68
2.50
1.69
0.70
2.40
1.62
0.76
22.0
30
3.09
2.09
0.56
2.99
2.02
0.63
2.88
1.95
0.69
2.84
1.92
0.70
2.76
1.87
0.72
2.65
1.79
0.78
24.0
32
3.28
2.22
0.57
3.18
2.15
0.64
3.07
2.08
0.71
3.02
2.04
0.72
2.94
1.99
0.73
2.81
1.91
0.79
3D040386
RKS+FTKS35B
Cooling capacity
230V [50Hz]
AFR
7.4
BF
0.16
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
3.26
2.05
0.87
3.15
1.99
0.97
3.04
1.92
1.07
2.99
1.89
1.09
2.92
1.84
1.11
2.79
1.76
1.20
16.0
22
3.52
2.22
0.88
3.40
2.14
0.99
3.29
2.07
1.09
3.23
2.04
1.10
3.15
1.98
1.13
3.02
1.90
1.22
18.0
25
3.78
2.38
0.90
3.66
2.30
1.00
3.53
2.23
1.11
3.47
2.19
1.12
3.38
2.13
1.15
3.24
2.04
1.24
19.0
27
3.91
2.47
0.91
3.78
2.38
1.01
3.65
2.30
1.12
3.59
2.26
1.13
3.50
2.21
1.16
3.35
2.11
1.26
22.0
30
4.32
2.72
0.93
4.18
2.63
1.04
4.04
2.54
1.15
3.97
2.50
1.17
3.87
2.44
1.19
3.71
2.33
1.29
24.0
32
4.60
2.90
0.95
4.45
2.80
1.06
4.29
2.70
1.17
4.22
2.66
1.19
4.11
2.59
1.22
3.94
2.48
1.32
3D040387
RKS+FTKS50B
Cooling capacity
230V [50Hz]
AFR
11.4
BF
0.22
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.06
3.28
1.31
4.91
3.21
1.41
4.76
3.14
1.50
4.70
3.11
1.54
4.61
3.07
1.60
4.46
3.00
1.69
16.0
22
5.22
3.31
1.34
5.07
3.24
1.43
4.92
3.17
1.53
4.86
3.14
1.56
4.77
3.10
1.62
4.62
3.03
1.72
18.0
25
5.37
3.34
1.36
5.22
3.27
1.46
5.07
3.20
1.55
5.01
3.18
1.59
4.92
3.13
1.65
4.77
3.06
1.74
19.0
27
5.45
3.36
1.38
5.30
3.29
1.47
5.15
3.22
1.57
5.09
3.19
1.60
5.00
3.15
1.66
4.85
3.08
1.76
22.0
30
5.68
3.41
1.41
5.53
3.34
1.51
5.38
3.27
1.60
5.32
3.24
1.64
5.23
3.20
1.70
5.08
3.13
1.79
24.0
32
5.84
3.45
1.44
5.69
3.38
1.54
5.54
3.31
1.63
5.48
3.28
1.67
5.39
3.24
1.73
5.24
3.17
1.82
3D040892
RKS+FTKS60B
Cooling capacity
230V [50Hz]
AFR
16.2
BF
0.29
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
6.06
3.97
1.77
5.91
3.90
1.87
5.76
3.83
1.96
5.70
3.80
2.00
5.61
3.76
2.06
5.46
3.69
2.15
16.0
22
6.22
4.00
1.80
6.07
3.93
1.89
5.92
3.86
1.99
5.86
3.83
2.02
5.77
3.79
2.08
5.62
3.72
2.18
18.0
25
6.37
4.03
1.82
6.22
3.96
1.92
6.07
3.89
2.01
6.01
3.87
2.05
5.92
3.82
2.11
5.77
3.75
2.20
19.0
27
6.45
4.05
1.84
6.30
3.98
1.93
6.15
3.91
2.03
6.09
3.88
2.06
6.00
3.84
2.12
5.85
3.77
2.22
22.0
30
6.68
4.10
1.87
6.53
4.03
1.97
6.38
3.96
2.06
6.32
3.93
2.10
6.23
3.89
2.16
6.08
3.82
2.25
24.0
32
6.84
4.14
1.90
6.69
4.07
2.00
6.54
4.00
2.09
6.48
3.97
2.13
6.39
3.93
2.19
6.24
3.86
2.28
3D040895
SYMBOLS
AFR:
Air flow rate
(m3/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
3
8
• Split - Sky Air • Outdoor Units
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
7.16
4.60
2.18
7.01
4.53
2.28
6.86
4.46
2.37
6.80
4.43
2.41
6.71
4.39
2.47
6.56
4.32
2.56
16.0
22
7.32
4.63
2.21
7.17
4.56
2.30
7.02
4.49
2.40
6.96
4.46
2.43
6.87
4.42
2.49
6.72
4.35
2.59
18.0
25
7.47
4.67
2.23
7.32
4.60
2.33
7.17
4.53
2.42
7.11
4.50
2.46
7.02
4.46
2.52
6.87
4.39
2.61
19.0
27
7.55
4.68
2.25
7.40
4.61
2.34
7.25
4.54
2.44
7.19
4.52
2.47
7.10
4.47
2.53
6.95
4.40
2.63
22.0
30
7.78
4.73
2.28
7.63
4.66
2.38
7.48
4.59
2.47
7.42
4.57
2.51
7.33
4.52
2.57
7.18
4.45
2.66
24.0
32
7.94
4.77
2.31
7.79
4.70
2.41
7.64
4.63
2.50
7.58
4.60
2.54
7.49
4.56
2.60
7.34
4.49
2.69
3D040896
RKS+FVKS25B
Cooling capacity
230V [50Hz]
AFR
8.1
BF
0.29
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
2.33
1.58
0.52
2.25
1.52
0.58
2.17
1.47
0.65
2.14
1.45
0.66
2.08
1.41
0.67
2.00
1.35
0.72
16.0
22
2.51
1.70
0.53
2.43
1.65
0.59
2.35
1.59
0.66
2.31
1.56
0.67
2.25
1.52
0.68
2.16
1.46
0.74
18.0
25
2.70
1.83
0.54
2.61
1.77
0.61
2.52
1.71
0.67
2.48
1.68
0.68
2.42
1.64
0.69
2.32
1.57
0.75
19.0
27
2.80
1.89
0.55
2.70
1.83
0.61
2.61
1.77
0.67
2.57
1.74
0.68
2.50
1.60
0.70
2.40
1.62
0.76
22.0
30
3.09
2.09
0.56
2.99
2.02
0.63
2.88
1.95
0.69
2.84
1.92
0.70
2.76
1.87
0.72
2.65
1.79
0.78
24.0
32
3.28
2.22
0.57
3.18
2.15
0.64
3.07
2.08
0.71
3.02
2.04
0.72
2.94
1.99
0.73
2.81
1.91
0.79
3D040390
RKS+FVKS35B
Cooling capacity
230V [50Hz]
AFR
8.3
BF
0.13
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
3.26
2.12
0.87
3.15
2.05
0.97
3.04
1.98
1.07
2.99
1.95
1.09
2.92
1.90
1.11
2.79
1.82
1.20
16.0
22
3.52
2.29
0.88
3.40
2.21
0.99
3.29
2.14
1.09
3.23
2.10
1.10
3.15
2.05
1.13
3.02
1.96
1.22
18.0
25
3.78
2.46
0.90
3.66
2.38
1.00
3.53
2.30
1.11
3.47
2.26
1.12
3.38
2.20
1.15
3.24
2.11
1.24
19.0
27
3.91
2.54
0.91
3.78
2.46
1.01
3.65
2.38
1.12
3.59
2.34
1.13
3.50
2.28
1.16
3.35
2.18
1.26
22.0
30
4.32
2.81
0.93
4.18
2.72
1.04
4.04
2.62
1.15
3.97
2.58
1.17
3.87
2.51
1.19
3.71
2.41
1.29
24.0
32
4.60
2.99
0.95
4.45
2.89
1.06
4.29
2.79
1.17
4.22
2.74
1.19
4.11
2.67
1.22
3.94
2.56
1.32
3D040391
RKS+FVKS50B
Cooling capacity
230V [50Hz]
AFR
10.8
BF
0.23
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
4.86
3.15
1.35
4.71
3.08
1.45
4.56
3.01
1.54
4.50
2.98
1.58
4.41
2.94
1.64
4.26
2.87
1.73
16.0
22
5.02
3.18
1.38
4.87
3.11
1.47
4.72
3.04
1.57
4.66
3.02
1.60
4.57
2.97
1.66
4.42
2.90
1.76
18.0
25
5.17
3.22
1.40
5.02
3.15
1.50
4.87
3.08
1.59
4.81
3.05
1.63
4.72
3.01
1.69
4.57
2.94
1.78
19.0
27
5.25
3.23
1.42
5.10
3.16
1.51
4.95
3.09
1.61
4.89
3.07
1.64
4.80
3.02
1.70
4.65
2.95
1.80
22.0
30
5.48
3.29
1.45
5.33
3.22
1.55
5.18
3.15
1.64
5.12
3.12
1.68
5.03
3.08
1.74
4.88
3.01
1.83
24.0
32
5.64
3.32
1.48
5.49
3.25
1.58
5.34
3.18
1.67
5.28
3.15
1.71
5.19
3.11
1.77
5.04
3.04
1.86
3D040894
SYMBOLS
AFR:
Air flow rate
(m3/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
3
Capacity tables
3
9
• Split - Sky Air • Outdoor Units
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
2.33
1.52
0.54
2.25
1.47
0.60
2.17
1.42
0.66
2.14
1.40
0.67
2.08
1.36
0.68
2.00
1.30
0.74
16.0
22
2.51
1.64
0.54
2.43
1.59
0.61
2.35
1.53
0.67
2.31
1.51
0.68
2.25
1.47
0.70
2.16
1.41
0.75
18.0
25
2.70
1.76
0.55
2.61
1.71
0.62
2.52
1.65
0.68
2.48
1.62
0.69
2.42
1.58
0.71
2.32
1.51
0.77
19.0
27
2.80
1.82
0.56
2.70
1.76
0.62
2.61
1.70
0.69
2.57
1.67
0.70
2.50
1.83
0.72
2.40
1.56
0.77
22.0
30
3.09
2.02
0.58
2.99
1.95
0.64
2.88
1.88
0.71
2.84
1.85
0.72
2.76
1.80
0.74
2.65
1.73
0.80
24.0
32
3.28
2.14
0.59
3.18
2.07
0.65
3.07
2.00
0.72
3.02
1.97
0.73
2.94
1.92
0.75
2.81
1.84
0.81
3D040382
RKS+FLKS35B
Cooling capacity
230V [50Hz]
AFR
8.6
BF
0.35
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
3.26
2.02
0.91
3.15
1.95
1.02
3.04
1.89
1.12
2.99
1.86
1.14
2.92
1.81
1.17
2.79
1.73
1.26
16.0
22
3.52
2.18
0.93
3.40
2.11
1.04
3.29
2.04
1.14
3.23
2.00
1.16
3.15
1.95
1.19
3.02
1.87
1.29
18.0
25
3.78
2.35
0.95
3.66
2.27
1.06
3.53
2.19
1.16
3.47
2.15
1.18
3.38
2.10
1.21
3.24
2.01
1.31
19.0
27
3.91
2.43
0.95
3.78
2.35
1.06
3.65
2.27
1.17
3.59
2.23
1.19
3.50
2.17
1.22
3.35
2.08
1.32
22.0
30
4.32
2.68
0.98
4.18
2.59
1.10
4.04
2.50
1.21
3.97
2.46
1.23
3.87
2.40
1.26
3.71
2.30
1.36
24.0
32
4.60
2.85
1.00
4.45
2.76
1.12
4.29
2.66
1.23
4.22
2.62
1.25
4.11
2.55
1.28
3.94
2.44
1.38
3D040383
RKS+FLKS50B
Cooling capacity
230V [50Hz]
AFR
11.4
BF
0.18
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
4.96
3.26
1.37
4.81
3.19
1.47
4.66
3.12
1.56
4.60
3.09
1.60
4.51
3.05
1.66
4.36
2.98
1.75
16.0
22
5.12
3.30
1.40
4.97
3.23
1.49
4.82
3.16
1.59
4.76
3.13
1.62
4.67
3.09
1.68
4.52
3.02
1.78
18.0
25
5.27
3.33
1.42
5.12
3.26
1.52
4.97
3.19
1.61
4.91
3.16
1.65
4.82
3.12
1.71
4.67
3.05
1.80
19.0
27
5.35
3.35
1.44
5.20
3.28
1.53
5.05
3.21
1.63
4.99
3.18
1.66
4.90
3.14
1.72
4.75
3.07
1.82
22.0
30
5.58
3.40
1.47
5.43
3.33
1.57
5.28
3.26
1.66
5.22
3.23
1.70
5.13
3.19
1.76
4.98
3.12
1.85
24.0
32
5.74
3.43
1.50
5.59
3.36
1.60
5.44
3.29
1.69
5.38
3.26
1.73
5.29
3.22
1.79
5.14
3.15
1.88
3D040893
RKS+FFQ25B
Cooling capacity
230V [50Hz]
AFR
9.0
BF
0.24
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
2.33
1.82
0.62
2.25
1.76
0.69
2.17
1.70
0.76
2.14
1.67
0.78
2.08
1.62
0.79
2.00
1.56
0.86
16.0
22
2.51
1.96
0.63
2.43
1.90
0.71
2.35
1.83
0.78
2.31
1.80
0.79
2.25
1.75
0.81
2.16
1.68
0.87
18.0
25
2.70
2.11
0.64
2.61
2.04
0.72
2.52
1.97
0.79
2.48
1.93
0.80
2.42
1.88
0.82
2.32
1.81
0.89
19.0
27
2.80
2.18
0.65
2.70
2.11
0.72
2.61
2.04
0.80
2.57
2.00
0.81
2.50
1.95
0.83
2.40
1.87
0.90
22.0
30
3.09
2.41
0.67
2.99
2.33
0.75
2.88
2.25
0.82
2.84
2.21
0.84
2.76
2.15
0.85
2.65
2.06
0.92
24.0
32
3.28
2.56
0.68
3.18
2.48
0.76
3.07
2.39
0.84
3.02
2.35
0.85
2.94
2.29
0.87
2.81
2.20
0.94
3D040764
SYMBOLS
AFR:
Air flow rate
(m3/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
3
Capacity tables
3
10
• Split - Sky Air • Outdoor Units
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
3.17
2.25
0.97
3.06
2.18
1.09
2.96
2.10
1.20
2.91
2.07
1.22
2.83
2.02
1.24
2.71
1.93
1.35
16.0
22
3.42
2.43
0.99
3.31
2.35
1.10
3.19
2.27
1.22
3.14
2.24
1.24
3.06
2.18
1.27
2.93
2.09
1.37
18.0
25
3.67
2.62
1.01
3.55
2.53
1.12
3.43
2.44
1.24
3.37
2.40
1.26
3.29
2.34
1.29
3.15
2.24
1.39
19.0
27
3.80
2.71
1.02
3.68
2.62
1.13
3.55
2.53
1.25
3.49
2.48
1.27
3.40
2.42
1.30
3.26
2.32
1.41
22.0
30
4.20
2.99
1.05
4.06
2.89
1.17
3.92
2.79
1.29
3.86
2.74
1.31
3.76
2.67
1.34
3.60
2.56
1.45
24.0
32
4.47
3.18
1.07
4.32
3.07
1.19
4.17
2.97
1.31
4.10
2.92
1.33
4.00
2.84
1.36
3.83
2.72
1.48
3D040766
RKS+FFQ50B
Cooling capacity
230V [50Hz]
AFR
12.0
BF
0.16
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
4.76
3.51
1.45
4.61
3.44
1.55
4.46
3.37
1.64
4.40
3.34
1.68
4.31
3.30
1.74
4.16
3.23
1.83
16.0
22
4.92
3.54
1.48
4.77
3.47
1.57
4.62
3.40
1.67
4.56
3.38
1.70
4.47
3.33
1.76
4.32
3.26
1.86
18.0
25
5.07
3.58
1.50
4.92
3.51
1.60
4.77
3.44
1.69
4.71
3.41
1.73
4.62
3.37
1.79
4.47
3.30
1.88
19.0
27
5.15
3.59
1.52
5.00
3.52
1.61
4.85
3.45
1.71
4.79
3.43
1.74
4.70
3.38
1.80
4.55
3.31
1.90
22.0
30
5.38
3.65
1.55
5.23
3.58
1.65
5.08
3.51
1.74
5.02
3.48
1.78
4.93
3.44
1.84
4.78
3.37
1.93
24.0
32
5.54
3.68
1.58
5.39
3.61
1.68
5.24
3.54
1.77
5.18
3.51
1.81
5.09
3.47
1.87
4.94
3.40
1.96
3D041022
RKS+FFQ60B
Cooling capacity
230V [50Hz]
AFR
15.0
BF
0.11
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.86
4.30
1.72
5.71
4.23
1.82
5.56
4.16
1.91
5.50
4.13
1.95
5.41
4.09
2.01
5.26
4.02
2.10
16.0
22
6.02
4.34
1.75
5.87
4.27
1.84
5.72
4.20
1.94
5.66
4.17
1.97
5.57
4.13
2.03
5.42
4.06
2.13
18.0
25
6.17
4.37
1.77
6.02
4.30
1.87
5.87
4.23
1.96
5.81
4.20
2.00
5.72
4.16
2.06
5.57
4.09
2.15
19.0
27
6.25
4.39
1.79
6.10
4.32
1.88
5.95
4.25
1.98
5.89
4.22
2.01
5.80
4.18
2.07
5.65
4.11
2.17
22.0
30
6.48
4.44
1.82
6.33
4.37
1.92
6.18
4.30
2.01
6.12
4.27
2.05
6.03
4.23
2.11
5.88
4.16
2.20
24.0
32
6.64
4.47
1.85
6.49
4.40
1.95
6.34
4.33
2.04
6.28
4.30
2.08
6.19
4.26
2.14
6.04
4.19
2.23
3D041027
SYMBOLS
AFR:
Air flow rate
(m3/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
3
Capacity tables
3
11
• Split - Sky Air • Outdoor Units
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
35
14.0
20.0
3.2
2.7
0.91
3.1
2.6
1.01
3.0
2.5
1.12
2.9
2.4
1.13
2.8
2.4
1.16
2.7
2.3
1.25
16.0
22.0
3.4
2.9
0.92
3.3
2.8
1.03
3.2
2.7
1.14
3.1
2.6
1.15
3.1
2.6
1.18
2.9
2.5
1.28
18.0
25.0
3.7
3.1
0.94
3.6
3.0
1.05
3.4
2.9
1.16
3.4
2.8
1.17
3.3
2.8
1.20
3.2
2.6
1.30
19.0
27.0
3.8
3.2
0.95
3.7
3.1
1.06
3.6
3.0
1.17
3.5
2.9
1.18
3.4
2.9
1.21
3.3
2.7
1.31
22.0
30.0
4.2
3.5
0.97
4.1
3.4
1.09
3.9
3.3
1.20
3.9
3.2
1.22
3.8
3.2
1.25
3.6
3.0
1.35
24.0
32.0
4.5
3.8
0.99
4.3
3.6
1.11
4.2
3.5
1.22
4.1
3.4
1.24
4.0
3.4
1.27
3.8
3.2
1.37
50
14.0
20.0
5.1
3.7
1.57
4.9
3.6
1.67
4.8
3.5
1.76
4.7
3.5
1.80
4.6
3.5
1.86
4.5
3.4
1.95
16.0
22.0
5.2
3.7
1.60
5.1
3.6
1.69
4.9
3.6
1.79
4.9
3.5
1.83
4.8
3.5
1.88
4.6
3.4
1.98
18.0
25.0
5.4
3.7
1.62
5.2
3.7
1.72
5.1
3.6
1.81
5.0
3.6
1.85
4.9
3.5
1.91
4.8
3.5
2.00
19.0
27.0
5.5
3.8
1.64
5.3
3.7
1.73
5.2
3.6
1.83
5.1
3.6
1.87
5.0
3.6
1.92
4.9
3.5
2.02
22.0
30.0
5.7
3.8
1.68
5.5
3.7
1.77
5.4
3.7
1.87
5.3
3.6
1.90
5.2
3.6
1.96
5.1
3.5
2.06
24.0
32.0
5.8
3.8
1.70
5.7
3.8
1.80
5.5
3.7
1.89
5.5
3.7
1.93
5.4
3.6
1.99
5.2
3.6
2.08
60
14.0
20.0
5.8
4.5
1.84
5.6
4.4
1.94
5.5
4.3
2.03
5.4
4.3
2.07
5.3
4.3
2.13
5.2
4.2
2.22
16.0
22.0
5.9
4.5
1.87
5.8
4.4
1.96
5.6
4.4
2.06
5.6
4.4
2.10
5.5
4.3
2.15
5.3
4.2
2.25
18.0
25.0
6.1
4.6
1.89
5.9
4.5
1.99
5.8
4.4
2.08
5.7
4.4
2.12
5.6
4.3
2.18
5.5
4.3
2.27
19.0
27.0
6.2
4.6
1.91
6.0
4.5
2.00
5.9
4.4
2.10
5.8
4.4
2.13
5.7
4.4
2.19
5.6
4.3
2.29
22.0
30.0
6.4
4.6
1.95
6.2
4.6
2.04
6.1
4.5
2.14
6.0
4.5
2.17
5.9
4.4
2.23
5.8
4.3
2.33
24.0
32.0
6.5
4.7
1.97
6.4
4.6
2.07
6.2
4.5
2.16
6.2
4.5
2.20
6.1
4.4
2.26
5.9
4.4
2.35
3TW25082-1
SYMBOLS
AFR:
Air flow rate
(m3/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
(comp.+indoor+outdoor fan motor)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB-EDB)/860
Add SHC* to SHC.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate and BF are tabulated below.
Model
FCQ
35
AFR
14
BF
0.16
50
AFR
15
BF
0.16
60
AFR
18
BF
0.10
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
3
Capacity tables
3
12
• Split - Sky Air • Outdoor Units
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
3.17
2.47
0.91
3.06
2.39
1.01
2.96
2.30
1.12
2.91
2.27
1.13
2.83
2.21
1.16
2.71
2.11
1.25
16.0
22
3.42
2.67
0.92
3.31
2.58
1.03
3.19
2.49
1.14
3.14
2.45
1.15
3.06
2.38
1.18
2.93
2.28
1.28
18.0
25
3.67
2.86
0.94
3.55
2.77
1.05
3.43
2.67
1.16
3.37
2.63
1.17
3.29
2.56
1.20
3.15
2.45
1.30
19.0
27
3.80
2.96
0.95
3.68
2.86
1.06
3.55
2.77
1.17
3.49
2.72
1.18
3.40
2.65
1.21
3.26
2.54
1.31
22.0
30
4.20
3.27
0.97
4.06
3.17
1.09
3.92
3.06
1.20
3.86
3.01
1.22
3.76
2.93
1.25
3.60
2.81
1.35
24.0
32
4.47
3.48
0.99
4.32
3.37
1.11
4.17
3.25
1.22
4.10
3.20
1.24
4.00
3.11
1.27
3.83
2.98
1.37
3D040599
RKS+FHQ50B
Cooling capacity
230V [50Hz]
AFR
13
BF
0.1
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.06
3.63
1.48
4.91
3.56
1.58
4.76
3.49
1.67
4.70
3.46
1.71
4.61
3.42
1.77
4.46
3.35
1.86
16.0
22
5.22
3.66
1.51
5.07
3.59
1.60
4.92
3.52
1.70
4.86
3.49
1.73
4.77
3.45
1.79
4.62
3.38
1.89
18.0
25
5.37
3.69
1.53
5.22
3.62
1.63
5.07
3.55
1.72
5.01
3.53
1.76
4.92
3.48
1.82
4.77
3.41
1.91
19.0
27
5.45
3.71
1.55
5.30
3.64
1.64
5.15
3.57
1.74
5.09
3.54
1.77
5.00
3.50
1.83
4.85
3.43
1.93
22.0
30
5.68
3.76
1.58
5.53
3.69
1.68
5.38
3.62
1.77
5.32
3.59
1.81
5.23
3.55
1.87
5.08
3.48
1.96
24.0
32
5.84
3.80
1.61
5.69
3.73
1.71
5.54
3.66
1.80
5.48
3.63
1.84
5.39
3.59
1.90
5.24
3.52
1.99
3D040601
RKS+FHQ60B
Cooling capacity
230V [50Hz]
AFR
17
BF
0.2
Indoor
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
14.0
20
5.76
4.17
1.80
5.61
4.10
1.90
5.46
4.03
1.99
5.40
4.00
2.03
5.31
3.96
2.09
5.16
3.89
2.18
16.0
22
5.92
4.21
1.83
5.77
4.14
1.92
5.62
4.07
2.02
5.56
4.04
2.05
5.47
4.00
2.11
5.32
3.93
2.21
18.0
25
6.07
4.24
1.85
5.92
4.17
1.95
5.77
4.10
2.04
5.71
4.07
2.08
5.62
4.03
2.14
5.47
3.96
2.23
19.0
27
6.15
4.26
1.87
6.00
4.19
1.96
5.85
4.12
2.06
5.79
4.09
2.09
5.70
4.05
2.15
5.55
3.98
2.25
22.0
30
6.38
4.31
1.90
6.23
4.24
2.00
6.08
4.17
2.09
6.02
4.14
2.13
5.93
4.10
2.19
5.78
4.03
2.28
24.0
32
6.54
4.34
1.93
6.39
4.27
2.03
6.24
4.20
2.12
6.18
4.17
2.16
6.09
4.13
2.22
5.94
4.06
2.31
3D040604
SYMBOLS
AFR:
Air flow rate
(m3/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m3/min) x (1-BF) x (DB-EDB)
Add SHC* to SHC.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate (AFR) and Bypass factor (BF) are taburated above.
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
3
Capacity tables
3
13
• Split - Sky Air • Outdoor Units
Outdoor temperature (°C)
EWB
EDB
20
25
30
32
35
40
(°C)
(°C)
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
35
14.0
20.0
3.2
2.4
0.91
3.1
2.3
1.01
3.0
2.2
1.12
2.9
2.2
1.13
2.8
2.1
1.16
2.7
2.0
1.25
16.0
22.0
3.4
2.6
0.92
3.3
2.5
1.03
3.2
2.4
1.14
3.1
2.4
1.15
3.1
2.3
1.18
2.9
2.2
1.28
18.0
25.0
3.7
2.8
0.94
3.6
2.7
1.05
3.4
2.6
1.16
3.4
2.5
1.17
3.3
2.5
1.20
3.2
2.4
1.30
19.0
27.0
3.8
2.9
0.95
3.7
2.8
1.06
3.6
2.7
1.17
3.5
2.6
1.18
3.4
2.6
1.21
3.3
2.4
1.31
22.0
30.0
4.2
3.2
0.97
4.1
3.0
1.09
3.9
2.9
1.20
3.9
2.9
1.22
3.8
2.8
1.25
3.6
2.7
1.35
24.0
32.0
4.5
3.3
0.99
4.3
3.2
1.11
4.2
3.1
1.22
4.1
3.1
1.24
4.0
3.0
1.27
3.8
2.9
1.37
50
14.0
20.0
5.1
3.6
1.57
4.9
3.5
1.67
4.8
3.4
1.76
4.7
3.4
1.80
4.6
3.4
1.86
4.5
3.3
1.95
16.0
22.0
5.2
3.6
1.60
5.1
3.5
1.69
4.9
3.5
1.79
4.9
3.4
1.83
4.8
3.4
1.88
4.6
3.3
1.98
18.0
25.0
5.4
3.6
1.62
5.2
3.6
1.72
5.1
3.5
1.81
5.0
3.5
1.85
4.9
3.4
1.91
4.8
3.4
2.00
19.0
27.0
5.5
3.7
1.64
5.3
3.6
1.73
5.2
3.5
1.83
5.1
3.5
1.87
5.0
3.5
1.92
4.9
3.4
2.02
22.0
30.0
5.7
3.7
1.68
5.5
3.6
1.77
5.4
3.6
1.87
5.3
3.5
1.90
5.2
3.5
1.96
5.1
3.4
2.06
24.0
32.0
5.8
3.7
1.70
5.7
3.7
1.80
5.5
3.6
1.89
5.5
3.6
1.93
5.4
3.5
1.99
5.2
3.5
2.08
60
14.0
20.0
5.8
4.6
1.84
5.6
4.6
1.94
5.5
4.5
2.03
5.4
4.5
2.07
5.3
4.4
2.13
5.2
4.3
2.22
16.0
22.0
5.9
4.7
1.87
5.8
4.6
1.96
5.6
4.5
2.06
5.6
4.5
2.10
5.5
4.5
2.15
5.3
4.4
2.25
18.0
25.0
6.1
4.7
1.89
5.9
4.6
1.99
5.8
4.6
2.08
5.7
4.5
2.12
5.6
4.5
2.18
5.5
4.4
2.27
19.0
27.0
6.2
4.7
1.91
6.0
4.6
2.00
5.9
4.6
2.10
5.8
4.5
2.13
5.7
4.5
2.19
5.6
4.4
2.29
22.0
30.0
6.4
4.8
1.95
6.2
4.7
2.04
6.1
4.6
2.14
6.0
4;6
2.17
5.9
4.6
2.23
5.8
4.5
2.33
24.0
32.0
6.5
4.8
1.97
6.4
4.7
2.07
6.2
4.7
2.16
6.2
4.6
2.20
6.1
4.6
2.26
5.9
4.5
2.35
3TW25112-1
SYMBOLS
AFR:
Air flow rate
(m3/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
(comp.+indoor+outdoor fan motor)
NOTES
1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat
2.
Shows nominal cooling capacities and power input
3. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB-EDB)/860
Add SHC* to SHC.
4. Direct interpolation is permissible.
Do not extrapolate.
5. Capacities are based on the following conditions:
Corresponding refrigerant piping length:
7.5 m
Level difference:
0 m
6. Air flow rate and BF are tabulated below.
Model
FCQ
35
AFR
11.5
BF
0.15
50
AFR
14
BF
0.15
60
AFR
19
BF
0.11
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
3
Capacity tables
3
14
• Split - Sky Air • Outdoor Units
Minimum space for air passage
Wall height on air outlet side = less
than 1200
Drain outlet
(I.D. J 15.9 hose for connection)
4 x holes for anchor bolts (M8 or M10)
Name plate
Terminal strip with earth
terminal
Wiring inlet
Gas stop valve
(J B CuT)
Liquid stop valve
(J A CuT)
Service port
Outdoor air thermistor
Brand name label
In case of removing
stop valve cover
RKS50,60,71
unit (mm)
3D034257B
Minimum space for air passage
Wall height on air outlet side = less
than 1200
Drain outlet
(I.D. J 15.9 hose for connection)
4 x holes for anchor bolts (M8 or M10)
Name plate
Terminal strip with earth
terminal
Wiring inlet
Gas stop valve
(J B CuT)
Liquid stop valve
(J A CuT)
Service port
Outdoor air thermistor
Brand name label
In case of removing stop
valve cover
Indication label (refrigerant)
Model
A
B
RKS50, RKS60
6.4
12.7
RKS71
6.4
15.9
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
4
15
• Split - Sky Air • Outdoor Units
Outdoor temp. (°CDB)
Pull-down period
Indoor temp. (°CWB)
Notes:
The graph is based on the following conditions:
1. Equivalent piping length
7.5 m
2. Level difference
0 m
3. Air flow rate
high
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
5
16
• Split - Sky Air • Outdoor Units
Outdoor temperature thermistor
Heat exchanger
Propeller fan
Capillary tube 1
Liquid stop
valve
Field piping
Field piping
Accumulator
Compressor
Muffler
Refrigerant flow
Cooling
Discharge pipe
thermistor
Heat exchanger thermistor
Capillary tube 2
Muffler
Motor operated valve
Muffler with filter
Outdoor unit
Gas stop
valve
Muffler with filter
Muffler with
filter
3D039304
RKS35
Outdoor temperature thermistor
Heat exchanger
Propeller fan
Liquid stop
valve
Field piping
Field piping
Accumulator
Compressor
Muffler
Refrigerant flow
Cooling
Discharge pipe
thermistor
Heat exchanger thermistor
Muffler
Motor operated valve
Muffler with filter
Outdoor unit
Gas stop
valve
Muffler with filter
Muffler with
filter
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
6
17
• Split - Sky Air • Outdoor Units
Outdoor temperature thermistor
Heat exchanger
Propeller fan
Capillary tube 1
Liquid stop valve
Field piping
Field piping
Gas stop valve with service port
Accumulator
Compressor
Capillary tube 3
Refrigerant flow
Cooling
Discharge pipe
thermistor
Heat exchanger thermistor
Capillary tube 2
Muffler with
filter
Motor operated valve
Muffler with
filter
Filter
Outdoor unit
3D037836A
RKS60,71
Outdoor temperature thermistor
Heat exchanger
Propeller fan
Capillary tube 1
Liquid stop valve
Field piping
Field piping
Gas stop valve with service port
Accumulator
Compressor
Capillary tube 3
Refrigerant flow
Cooling
Discharge pipe
thermistor
Heat exchanger thermistor
Capillary tube 2
Capillary tube 4
Muffler with
filter
Motor operated valve
Muffler with filter
Filter
Outdoor unit
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
6
Piping diagrams
6
18
• Split - Sky Air • Outdoor Units
: Protective earth
C9, C11
C12∼C15
: Capacitor
CT1
: Current transformer
DB1, DB2
: Diode bridge
F1U, F2U
: Fuse
L
: Live
L1
: Coil
L1R
: Reactor
M1C
: Compressor motor
M1F
: Fan motor
PCB1
: Printed circuit board
MRH, MRL,
MRM10, MRM20 : Magnetic relay
N
: Neutral
PCB2
: Printed circuit board
Q1L
: Overload protector
R1T, R2T, R3T, R4T
: Thermistor
S10, S11, S20, S45
S70, S90, S91
HL3, HN3
: Connector
SA1
: Surge arrester
Z1C
: Ferrite core
IC3
: Solid state relay
TFU
: Thermal fuse
TRM1
: Transistor module
V1, V2, V3
: Varistor
Y1E
: Electronic expansion valve coil
X1M
: Terminal strip
g
Field wiring
Indoor
Outdoor
(outdoor)
(Condenser)
(discharge)
3D037866D
RKS50,60,71
R
: Protective earth
Z1C, Z2C
: Ferrite core
X1M
: Terminal strip
Y2E
: Electronic expansion valve coil
V2∼V5
: Varistor
F1U, F2U, FU201
: Fuse
HE1, HE2, HAC1,
E, AC1, AC2
H1, H2, HL
L1, L2, X11A
: Connector
MRM10, MRM20,
MRC/W
: Magnetic relay
R1T∼R3T
: Thermistor
S2∼S102
: Connector
LEDA
: Pilot lamp
PCB1, PCB2
: Printed circuit board
L
: Live
N
: Neutral
S1W
: Forced operation on/off switch (SW1)
S4W
: Local setting
SA1
: Surge arrester
DB1
: Diode bridge
M1C
: Compressor motor
M1F
: Fan motor
L1R
: Reactor
g
Field wiring
Indoor
Power supply
∼50Hz 220-240V
∼60Hz 220-230V
Outdoor
(outdoor)
(Condenser)
(discharge)
Q1L
: Overload protector
CT1
: Current transformer
MID
: Molded interconnect device
SPM
: System power module
To indoor unit
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
7
19
• Split - Sky Air • Outdoor Units
Sound level data
Octave band sound pressure level
Octave band sound pressure level
Cooling only
Model
Sound pressure level
Sound power level
(cooling)
230V, 50Hz
Measuring location
Cooling
H
L
RKS25B
46
43
59
RKS35B
47
44
60
RKS50B
47
*
63
RKS60B
49
*
64
RKS71B
52
*
66
* This information was not available at the time of publication.
Octave band center frequency (Hz)
Octave band center frequency (Hz)
RKS25B (Cooling)
RKS35B (Cooling)
4D013520E
4D013518E
Legend
50/60Hz, 220-240/220-230V
8-2
Sound pressure spectrum
approximate
threshold hearing
for continuous
noise
approximate
threshold hearing
for continuous
noise
NOTES
1
Operation sound is measured in an anechoic chamber.
2
Operation sound level differs with operation and ambient conditions.
3
Reference acoustic pressure 0dB = 20µPa
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
8
8-1
20
• Split - Sky Air • Outdoor Units
Sound pressure spectrum
Octave band sound pressure level
Octave band sound pressure level
Octave band center frequency (Hz)
Octave band center frequency (Hz)
RKS50B
RKS60B
4D040949
4D027648B
approximate
threshold hearing
for continuous noise
approximate
threshold hearing for
continuous noise
RKS71B
Octave band sound pressure level
approximate
threshold hearing
for continuous noise
3D027650B
Octave band center frequency (Hz)
NOTES
1
Operation sound is measured in an anechoic chamber.
2
Operation sound level differs with operation and ambient conditions.
3
Reference acoustic pressure 0dB = 20µPa
Legend
50/60Hz, 220-240/220-230V
Cooling only
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
8
8-2
21
• Split - Sky Air • Outdoor Units
Accessories supplied with the outdoor unit:
1
9-2
Optional accessories
RKS-B
RKS25BVMB
RKS35BVMB
RKS50BVMB
RKS60BVMB
RKS71BVMB
Air direction adjustment grille
KPW937A4
KPW945A4
Installation manual
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
9
9-1
22
• Split - Sky Air • Outdoor Units
Outdoor unit installation drawings
Wrap the installation pipe with the finishing
tape from bottom to top
Model
25 / 35 class
Max. allowable length
Cooling only: 25m
Heat pump: 15m
Max. allowable height
15m
Additional refrigerant required
for refrigerant pipe exceeding
10 m in length.
20 g/m
Gas pipe
O.D. 9.5 mm
Liquid pipe
O.D. 6.4 mm
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
In sites with poor drainage, use block bases for outdoor
unit. Adjust foot height until the unit is leveled. Otherwise,
water leakage or pooling of water may occur.
Where there is a danger of the unit falling, use foot bolts, or
wires.
Allow space for piping and electrical servicing.
Service lid
How to remove the service lid.
+ This service lid is an open/close type.
+ Slide the lid downward to remove it.
How to attach the service lid.
+ Insert the upper part of the service lid into the
outdoor unit to install.
+ Tighten the screws.
Foot bolt-hole
centres
Foot bolt-hole
centres
From unit’s side
470
115
288
250 mm from wall
RKS25,35B
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
10
23
• Split - Sky Air • Outdoor Units
Outdoor unit installation drawings
Wrap the installation pipe with the
finishing tape from bottom to top
Model
50 class
60 class
71 class
Max. allowable length
30m
Max. allowable height
20m
Additional refrigerant required
for refrigerant pipe exceeding
10 m in length.
20 g/m
Gas pipe
O.D. 12.7 mm
O.D. 9.5 mm
Liquid pipe
O.D. 6.4 mm
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
In sites with poor drainage, use block bases for
outdoor unit. Adjust foot height until the unit is
leveled. Otherwise, water leakage or pooling of
water may occur.
Where there is a danger of the unit falling, use foot bolts, or
wires.
Allow space for piping and electrical
servicing.
Service lid
Foot bolt-hole
centres
Foot bolt-hole centres
From unit’s side
250 mm from wall
RKS50,60,71B
• Pair Application • R-410A • RKS25-35-50-60-71BVMB
10
Installation
10
24
• Split - Sky Air • Outdoor Units