Installation manual for wired remote controller (RC-E3)
Installation manual for wired remote controller
Installation and wiring of remote controller
Wiring of remote controller should use 0.3m
Maximum prolongation of remote controlle
100 - 200m.........................0.5mm2 × 2 cor
Under 300m .......................0.75mm2 × 2 co
Under 400m .......................1.25mm2 × 2 co
Under 600m .......................2.0mm2 × 2 cor
Master/ slave setting when more than one re
A maximum of two remote controllers can be co
Remote controller cord (no pola
Remote controller
SW1 "Master"
Switc
SW1
The indication when power source is supplie
When power source is turned on, the following i
communication between the remote controller a
Master remote controller : "
Slave remote controller : "
At the same time, a mark or a number will be dis
This is the software's administration number of t
When remote controller cannot communicate wit
appear.
Check wiring of the indoor unit and the outdoor
Read together with indoor unit's installation manual.
Accessories
Remote controller, wood screw
2 pieces
Prepare on site
Remote controller cord (2 cores)
[In case of embedding cord] Erectrical box, M4 screw (2 pieces)
[In case of exposing cord] Cord clamp (if needed)
Screw
Installation procedure
Open the cover of remote controller , and remove the screw under the
buttons without fail.
Remove the upper case of remote controller.
Insert a flat-blade screwdriver into the dented part of the upper part
of the remote controller, and wrench slightly.
[In case of embedding cord]
Embed the erectrical box and remote controller cord beforehand.
Prepare two M4 screws (recommended length is 12-16mm) on site, and install the lower case to erectrical box.
Choose either of the following two positions in fixing it with screws.
Connect the remote controller cord to the terminal block.
Connect the terminal of remote controller (X,Y) with the terminal of
indoor unit (X,Y). (X and Y are no polarity)
Install the upper case as before so as not to catch up the remote controller cord,
and tighten with the screws.
[In case of exposing cord]
You can pull out the remote controller cord from left upper part or center upper part.
Cut off the upper thin part of remote controller lower case with a nipper or knife,
and grind burrs with a file etc.
Install the lower case to the flat wall with attached two wooden screws.
Connect the remote controller cord to the
terminal block.
Connect the terminal of remote controller (X
with the terminal of indoor unit (X,Y).
(X and Y are no polarity)
Wiring route is as shown in the right diagram
depending on the pulling out direction.
The wiring inside the remote controller case
The sheath should be peeled off inside the
The peeling-off length of each wire is as be
Pulling out from upper left Pulling out from
X wiring : 215mm
Y wiring : 195mm
X wiring :
Y wiring :
Install the upper case as before so as not to
the screws.
In case of exposing cord, fix the cord on the
WARNING
CAUTION
Fasten the wiring to the terminal securely and hold the cable securely so as not to apply unexpected stress on the
terminal.
Loose connection or hold will cause abnormal heat generation or fire.
Make sure the power supply is turned off when electric wiring work.
Otherwise, electric shock, malfunction and improper running may occur.
DO NOT install the remote controller at the following places in order to avoid malfunction.
DO NOT leave the remote controller without the upper case.
(1) Places exposed to direct sunlight
(2) Places near heat devices
(3) High humidity places
In case the upper cace needs to be detached, protect the remote controller with a packaging box or bag in
order to keep it away from water and dust.
(4) Hot surface or cold surface enough to generate condensation
(5) Places exposed to oil mist or steam directly
(6) Uneven surface
Tighten the screws after
cutting off the thin part of
screw mounting part.
Controller cord
Erectrical box
(Prepare on site)
Lower part
Lower part
Upper part
Lower case
Lower case
Wiring oulet
Wiring oulet
M4 screw 2 (Prepare on site)
The thin part
If the prolongation is over 100m, change to
But, wiring in the remote controller case sh
of the case according to wire connecting. W
connecting section. Be careful about conta
Remote controller
SW1 "Slave"
The left mark
example. Oth
appear.
Upper part
Lower
Lower case
Upper
Lower
Lower case
Upper
Indoor units
Set SW1 to "Slave" for the slave remote co
Note: The setting "Remote controller thermistor
controller in the position where you want t
The air conditioner operation follows the la
master/ slave setting of it.
C
PJA012D728A
- 2 -
ired remote controller
Installation and wiring of remote controller
Wiring of remote controller should use 0.3mm2 × 2 core wires or cables. (on-site configuration)
Maximum prolongation of remote controller wiring is 600 m.
100 - 200m.........................0.5mm2 × 2 cores
Under 300m .......................0.75mm2 × 2 cores
Under 400m .......................1.25mm2 × 2 cores
Under 600m .......................2.0mm2 × 2 cores
Master/ slave setting when more than one remote controllers are used
A maximum of two remote controllers can be connected to one indoor unit (or one group of indoor units.)
Remote controller cord (no polarity)
Remote controller
SW1 "Master"
Switch
Setting
Contents
M
Master remote controller
SW1
S
Slave remote controller
The indication when power source is supplied
When power source is turned on, the following is displayed on the remote controller until the
communication between the remote controller and indoor unit settled.
Master remote controller : " "
Slave remote controller : " "
At the same time, a mark or a number will be displayed for two seconds first.
This is the software's administration number of the remote controller, not an error cord.
The range of temperature setting
When shipped, the range of set temperature differs de
Heating : 16~30oC (55~86oF)
Except heating (cooling, fan, dry, automatic) : 18
Upper limit and lower limit of set tempe
Upper limit setting: valid during heating operation.
Lower limit setting: valid except heating (automatic
79oF).
When you set upper and lower limit by this function
1. When TEMP RANGE SET, remote controller
During heating, you cannot set the value excee
During operation mode except heating, you can
2. When TEMP RANGE SET, remote controller
During heating, even if the value exceeding the
But, the indication is the same as the temperatu
During except heating, even if the value lower th
But, the indication is the same as the temperatu
How to set upper and lower limit value
1. Stop the air-conditioner, and press (SE
seconds .
The indication changes to "FUNCTION SET
2. Press button once, and change to the "TE
3. Press (SET) button, and enter the temp
4. Select "UPPER LIMIT " or "LOWER LIMIT
5. Press (SET) button to fix.
6. When "UPPER LIMIT " is selected (valid du
Press (SET) button to fix. Indication
After the fixed upper limit value displayed fo
7. When "LOWER LIMIT " is selected (valid du
Indication: " SET UP" "LOWER
8. Press ON/OFF button to finish.
When remote controller cannot communicate with the indoor unit for half an hour, the below indication will
appear.
Check wiring of the indoor unit and the outdoor unit etc.
2 pieces
Erectrical box, M4 screw (2 pieces)
ord clamp (if needed)
Screw
screw under the
he upper part
beforehand.
mm) on site, and install the lower case to erectrical box.
with screws.
ck.
he terminal of
the remote controller cord,
pper part or center upper part.
ase with a nipper or knife,
wooden screws.
Connect the remote controller cord to the
terminal block.
Connect the terminal of remote controller (X,Y)
with the terminal of indoor unit (X,Y).
(X and Y are no polarity)
Wiring route is as shown in the right diagram
depending on the pulling out direction.
The wiring inside the remote controller case should be within 0.3mm2 (recommended) to 0.5mm2.
The sheath should be peeled off inside the remote controller case.
The peeling-off length of each wire is as below.
Pulling out from upper left Pulling out from upper center
X wiring : 215mm
Y wiring : 195mm
X wiring : 170mm
Y wiring : 190mm
Install the upper case as before so as not to catch up the remote controller cord, and tighten with
the screws.
In case of exposing cord, fix the cord on the wall with cord clamp so as not to slack.
In case of pulling out from
upper left
In case of pulling out from
upper center
The peeling-off length
of sheath
ING
ON
securely so as not to apply unexpected stress on the
n or fire.
work.
may occur.
n order to avoid malfunction.
ote controller with a packaging box or bag in
ace or cold surface enough to generate condensation
xposed to oil mist or steam directly
surface
Tighten the screws after
cutting off the thin part of
screw mounting part.
Controller cord
Erectrical box
(Prepare on site)
Lower part
Lower case
iring oulet
M4 screw 2 (Prepare on site)
The thin part
Wiring
Wiring
Upper
Upper
Sheath
Upper case
Upper case
Board
Board
Lower
Lower
If the prolongation is over 100m, change to the size below.
But, wiring in the remote controller case should be under 0.5mm2 . Change the wire size outside
of the case according to wire connecting. Waterproof treatment is necessary at the wire
connecting section. Be careful about contact failure.
Remote controller
SW1 "Slave"
Lower
Master
Slave
Upper
Board
The left mark is only an
example. Other marks may
appear.
Upper part
Lower
Lower case
Upper
Lower
Lower case
Upper
Sheath
If upper limit value is set
If upper limit value is set
If lower limit value is set
If lower limit value is set
Indication: " SET UP" "UPPER
Select the upper limit value with temperatu
(blinking)
Select the lower limit value with temperatur
(blinking)
Press (SET) button to fix. Indication
After the fixed lower limit value displayed fo
It is possible to finish by pressing
ON/OFF button on the way, but
unfinished change of setting is
unavailable.
During setting, if you press
(RESET) button, you return to the
previous screen.
Indoor units
Set SW1 to "Slave" for the slave remote controller. It was factory set to "Master" for shipment.
Note: The setting "Remote controller thermistor enabled" is only selectable with the master remote
controller in the position where you want to check room temperature.
The air conditioner operation follows the last operation of the remote controller regardless of the
master/ slave setting of it.
- 3 -
C
e wires or cables. (on-site configuration)
00 m.
ollers are used
one indoor unit (or one group of indoor units.)
g
Contents
Master remote controller
Slave remote controller
on the remote controller until the
nit settled.
wo seconds first.
controller, not an error cord.
The range of temperature setting
When shipped, the range of set temperature differs depending on the operation mode as below.
Heating : 16~30oC (55~86oF)
Except heating (cooling, fan, dry, automatic) : 18~30oC (62~86oF)
Upper limit and lower limit of set temperature can be changed with remote controller.
Upper limit setting: valid during heating operation. Possible to set in the range of 20 to 30oC (68 to 86oF).
Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26oC (62 to
79oF).
When you set upper and lower limit by this function, control as below.
1. When TEMP RANGE SET, remote controller function of function setting mode is "INDN CHANGE" (factory setting),
During heating, you cannot set the value exceeding the upper limit.
During operation mode except heating, you cannot set the value below the lower limit.
2. When TEMP RANGE SET, remote controller function of function setting mode is "NO INDN CHANGE"
During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
How to set upper and lower limit value
1. Stop the air-conditioner, and press (SET) and (MODE) button at the same time for over three
seconds .
The indication changes to "FUNCTION SET ".
2. Press button once, and change to the "TEMP RANGE " indication.
3. Press (SET) button, and enter the temperature range setting mode.
4. Select "UPPER LIMIT " or "LOWER LIMIT " by using button.
5. Press (SET) button to fix.
6. When "UPPER LIMIT " is selected (valid during heating)
Press (SET) button to fix. Indication example: "UPPER 26OC" (Displayed for two seconds)
After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT ".
7. When "LOWER LIMIT " is selected (valid during cooling, dry, fan, automatic)
Indication: " SET UP" "LOWER 18OC "
8. Press ON/OFF button to finish.
PJA012D728A
unit for half an hour, the below indication will
within 0.3mm2 (recommended) to 0.5mm2.
roller case.
e remote controller cord, and tighten with
ord clamp so as not to slack.
pulling out from
pper left
In case of pulling out from
upper center
The peeling-off length
of sheath
Wiring
Wiring
Upper
Upper
Sheath
Upper case
Upper case
oard
Board
ower
Lower
low.
er 0.5mm2 . Change the wire size outside
reatment is necessary at the wire
Lower
Master
Slave
Upper
Board
Previous button
Sheath
If upper limit value is set
If upper limit value is set
If lower limit value is set
If lower limit value is set
Indication: " SET UP" "UPPER 30OC "
Select the upper limit value with temperature setting button . Indication example: "UPPER 26OC "
(blinking)
Select the lower limit value with temperature setting button . Indication example: "LOWER 24OC "
(blinking)
Press (SET) button to fix. Indication for example: "LOWER 24OC" (Displayed for two seconds)
After the fixed lower limit value displayed for two seconds, the indication will return to "LOWER LIMIT ".
It is possible to finish by pressing
ON/OFF button on the way, but
unfinished change of setting is
unavailable.
During setting, if you press
(RESET) button, you return to the
previous screen.
was factory set to "Master" for shipment.
only selectable with the master remote
m temperature.
n of the remote controller regardless of the
- 4 -
r unit, and is automatically defined as following table.
h only one of air flow setting
it
ing unit
mode selectable indoor unit.
hout "Auto-RUN" mode
h two or three step of air flow setting
h only one of air flow setting
h automatically swing louver
hout automatically swing louver
h three step of air flow setting
h two step of air flow setting
oor unit.
nction “05 EXTERNAL INPUT” and “06 PERMISSION /
PEED"
Indoor unit air flow setting
HI-MID-LO
HI-LO
HI- MID
UHI- HI- MID
UHI- MID
UHI- HI
ndoor unit is "HIGH SPEED".
operation will be valid.
nning for 180 hours.
nning for 600 hours.
nning for 1000 hours.
nning for 1000 hours, then the indoor unit will be stopped by
"04 ",
roller function "14 " accordingly.
sition in the four.
n.
stop all indoor units connected with the same outdoor unit immediately.
remote on-off terminal "CNT-6", all indoor units are stopped immediately.
ncrease in temperature during heating.
ncrease in temperature during heating.
ncrease in temperature during heating.
ease in return air temperature of indoor unit.
ease in return air temperature of indoor unit.
ease in return air temperature of indoor unit.
ease in return air temperature of indoor unit.
ease in return air temperature of indoor unit.
ease in return air temperature of indoor unit.
fan speed is low speed.
fan speed is set speed.
fan speed is operated intermittently.
the fan is stopped.
rking, "FAN OFF" is set automatically.
ndoor unit's thermistor is working.
and dry.
dry and heating.
dry, heating and fan.
dry and fan.
thermostat is OFF, the fan does not perform extra operation.
thermostat is OFF, the fan perform extra operation for half an hour.
thermostat is OFF, the fan perform extra operation for an hour.
thermostat is OFF, the fan perform extra operation for six hours.
g thermostat is OFF, the fan does not perform extra operation.
g thermostat is OFF,the fan perform extra operation for half an hour.
g thermostat is OFF,the fan perform extra operation for two hours.
g thermostat is OFF, the fan perform extra operation for six hours.
ng thermostat is OFF, the fan perform intermittent operation for five minutes
nutes' OFF.
ng thermostat is OFF, the fan perform intermittent operation for five minutes
tes' OFF.
series.
door fan tap is raised.
temperature to start frost prevention control.
Press or button.
Make sure which do you want to set, " FUNCTION "
(remote controller function) or "I/U FUNCTION " (indoor
unit function).
How to set function
2.
1.
3.
4.
5.
It is possible to finish by pressing ON/OFF button on the way, but unfinished change of setting is
unavailable.
During setting, if you press (RESET) button, you return to the previous screen.
Setting is memorized in the controller and it is saved independently of power failure.
How to check the current setting
When you select from "No. and funcion" and press set button by the previous operation, the "Setting" displayed first is the current
setting.
(But, if you select "ALL UNIT ", the setting of the lowest number indoor unit is displayed.)
Stop air-conditioner and press (SET) (MODE)
buttons at the same time for over three seconds, and the
"FUNCTION SET " will be displayed.
Press (SET) button.
Selecct " FUNCTION " (remote controller function) or "I/U
FUNCTION " (indoor unit function).
Operation message
Function description: ,
setting description:
Function No.
Fixing button
Finishing button
7
2
1
6
Starting button
Previous screen button
Indoor unit selection button
Press (SET) button.
6.
"DATA LOADING" (Indication with blinking)
Display is changed to "01 GRILLE SET".
7.
"DATA LOADING" (Blinking for 2 to 23 seconds to read the data)
(1)
(2)
(3)
Press (SET) button.
On the occasion of remote controller function selection
On the occasion of indoor unit function selection
Press or button.
"No. and function"are indicated by turns on the remote
controller function table, then you can select from them.
(For example)
Press or button.
Select the setting.
Press or button.
Select the setting.
The current setting of selected function is indicated.
(for example) "AUTO RUN ON" If "02 AUTO RUN SET" is
selected
Press (SET) button.
Press (SET) button.
Press or button.
Press or button.
Select the number of the indoor unit you are to set
If you select "ALL UNIT ", you can set the same setting with
all unites.
Press (SET)
"SET COMPLETE" will be indicated, and the setting will be
completed.
Then after "No. and function" indication returns, Set as the
same procedure if you want to set continuously ,and if to
finish, go to 7.
Press ON/OFF button.
Setting is finished.
Indication is changed to "01 AUTO FILTER CLEANING".
Go to .
[Note]
If plural indoor units are connected to a remote controller,
the indication is "I/U 000" (blinking) The lowest number of
the indoor unit connected is indicated.
"No. and function" are indicated by turns on the indoor unit function
table, then you can select from them.
(For example)
The current setting of selected function is indicated.
(For example) "STANDARD" If "02 FAN SPEED SET" is
selected.
Press (SET) button.
"SET COMPLETE" will be indicated, and the setting will be
completed.
Then after "No. and function" indication returns, set as the same
procedure if you want to set continuously , and if to finish, go to 7.
Setting
Function No.
Function
When plural indoor units are connected to a remote controller,
press the AIRCON NO. button, which allows you to go back to
the indoor unit selection screen. (example "I/U 000 ")
Function No.
Function
Setting
The functional setting
Refer to page 256
C