Alpha Alpha CD25C Instructions
Text of the manual
Supplementary LPG Boiler
Instructions
Alpha CD25C/28C/35C
Wall Mounted, Fan Assisted, Room Sealed, Gas Fired
High Efficiency Condensing Boilers
Alpha CD25C
British Gas G.C. No. 47 532 32
Alpha CD28C
British Gas G.C. No. 47 532 34
Alpha CD35C
British Gas G.C. No. 47 532 36
British Gas
Service Listed
For use with LPG (Propane) only
Leave these instructions with the User
0051
Nepicar House, London Road,
Wrotham Heath, Sevenoaks,
Kent TN15 7RS
For Technical help or for Service call ...
ALPHA HELPLINE Tel: 0870 3001964
website:www.alpha-innovation.co.uk
CD25C/28C/35C LPG Supplement
37.0
14.8
11.4
2.5
13.3
2.9
37.0
14.8
37.0
14.8
9.6
2.2
11.2
2.5
1
INTRODUCTION
This supplement is for the LPG model of the boiler; it must be read in conjunction with the 'Installation and Servicing
Instructions' supplied with the boiler and provides the extra information which is particular to LPG.
The Alpha CD25C, CD28C and CD35C are combination boilers providing both central heating and domestic hot water at
mains pressure.
The boilers are designed for use with a fully pumped, sealed and pressurised heating system using only PROPANE gas.
2
TECHNICAL DATA
PERFORMANCE - PROPANE GAS (CAT I3P 3P - G31 - 37 mbar)
Alpha CD28C
Alpha CD28C
MAX.
27.1
92 400
24.4
83 250
25.9
88 400
24.0
81 900
7.27
2.9
1.04
36.7
MIN.
7.3
24 900
6.6
22 500
6.9
23 500
6.3
21 500
0.64
0.26
0.28
9.8
Room sealed
chamber panel
fitted
Central Heating
Heat Input (Hs)
kW
(Gross)
Btu/h
Heat Input (Hi)
kW
(Net)
Btu/h
Heat Output (Hs condensing)
kW
(50°C/30°C)
Btu/h
Heat Output (Hi non-condensing) kW
(80°C/60°C)
Btu/h
Differential Burner
mbar
Pressure
in wg
Gas Supply Pressure (LPG)
mbar
in wg
Gas Rate (LPG)
m³/h
ft³/h
MAX.
31.6
107 900
28.5
97 200
28.7
97 900
9.06
3.62
1.21
42.7
MIN.
7.3
24 900
6.6
22 500
6.3
21 500
0.64
0.26
0.28
9.8
Domestic Hot Water
Heat Input (Hs)
kW
(Gross)
Btu/h
Heat Input (Hi)
kW
(Net)
Btu/h
Output to Water (Hs)
kW
(modulating)
Btu/h
Differential Burner
mbar
Pressure
in wg
Gas Supply Pressure (LPG)
mbar
in wg
Gas Rate (LPG)
m³/h
ft³/h
Flow Rate at 35°C Rise
L/min
gal/min
Specific Flow Rate (D) at 30°C Rise L/min
(Flow rate @ 30K to EN625)
gal/min
Room sealed
chamber panel
fitted
37.0
14.8
Alpah CD25C
MAX.
20.4
69 600
18.4
62 780
19.5
66 550
18.0
61 420
3.15
1.26
0.78
27.6
MIN.
6.4
21 800
5.8
19 780
6.1
20 820
5.5
18 780
0.4
0.16
0.24
8.5
Room sealed
chamber panel
fitted
Central Heating
Heat Input (Hs)
kW
(Gross)
Btu/h
Heat Input (Hi)
kW
(Net)
Btu/h
Heat Output (Hs condensing)
kW
(50°C/30°C)
Btu/h
Heat Output (Hi non-condensing) kW
(80°C/60°C)
Btu/h
Differential Burner
mbar
Pressure
in wg
Gas Supply Pressure (LPG)
mbar
in wg
Gas Rate (LPG)
m³/h
ft³/h
Alpha CD25C
MAX.
26.7
91 100
24.1
82 200
24.3
84 800
6.10
2.44
1.02
36
MIN.
6.4
21 960
5.8
19 780
5.5
18 780
0.40
0.16
0.24
8.5
Domestic Hot Water
Heat Input (Hs)
kW
(Gross)
Btu/h
Heat Input (Hi)
kW
(Net)
Btu/h
Output to Water (Hs)
kW
(modulating)
Btu/h
Differential Burner
mbar
Pressure
in wg
Gas Supply Pressure (LPG)
mbar
in wg
Gas Rate (LPG)
m³/h
ft³/h
Flow Rate at 35°C Rise
L/min
gal/min
Specific Flow Rate (D) at 30°C Rise L/min
(Flow rate @ 30K to EN625)
gal/min
Room sealed
chamber panel
fitted
CD25C/28C/35C LPG Supplement
37.0
14.8
3
BOILER LOCATION
Installation pipes, cylinders and pressure regulators should be fitted in accordance with BS 5482:1. Bulk tank installation must
comply with the requirements of the Home Office code of practice for the storage of liquefied petroleum gas at fixed installations.
The boiler must not be installed in a room or internal space below ground level, e.g. in a basement or cellar, except where at
least one side is open to ground level.
4
INSTALLATION
In addition to the regulations and requirements stated in the Installation and Servicing instructions, the boiler must be installed
in accordance with BS 5482:1 - The Installation of Propane Burning Appliances in Permanent Dwellings.
2.3
GAS SUPPLY
The Alpha CD25C boiler requires a gas rate of 1.87 kg/h (4.0 lb/h) or 3.6 litres/h of liquid gas.
The Alpha CD28C boiler requires a gas rate of 2.22 kg/h (4.8 lb/h) or 4.2 litres/h of liquid gas.
The Alpha CD35C boiler requires a gas rate of 2.67 kg/h (5.7 lb/h) or 5.0 litres/h of liquid gas.
The supply pipes must be capable of delivering this quantity of gas in addition to the demand from any other appliances in the
house. The boilers require at least a 22 mm gas supply pipe.
The complete installation must be tested for gas soundness against leakage.
The local Propane gas supplier should be consulted, at the installation planning stage, in order to establish the availability of an
adequate supply of gas.
37.0
14.8
14.2
3.13
15.6
3.44
Alpha CD35C
MAX.
38.0
129 600
34.3
117 000
34.6
118 100
3.43
1.37
1.46
51.5
MIN.
8.9
30 600
8.1
27 600
8.0
27 300
0.23
0.09
0.34
12.0
Domestic Hot Water
Heat Input (Hs)
kW
(Gross)
Btu/h
Heat Input (Hi)
kW
(Net)
Btu/h
Output to Water (Hs)
kW
(modulating)
Btu/h
Differential Burner
mbar
Pressure
in wg
Gas Supply Pressure (LPG)
mbar
in wg
Gas Rate (LPG)
m³/h
ft³/h
Flow Rate at 35°C Rise
L/min
gal/min
Specific Flow Rate (D) at 30°C Rise L/min
(Flow rate @ 30K to EN625)
gal/min
Room sealed
chamber
panel fitted
Alpha CD35C
MAX.
31.6
107 800
28.5
97 200
30.3
103 400
28.0
95 550
2.49
1.0
1.21
42.7
MIN.
8.9
30 600
8.1
27 600
8.5
29 000
7.8
26 600
0.23
0.09
0.34
12.0
Room sealed
chamber panel
fitted
Central Heating
Heat Input (Hs)
kW
(Gross)
Btu/h
Heat Input (Hi)
kW
(Net)
Btu/h
Heat Output (Hs condensing)
kW
(50°C/30°C)
Btu/h
Heat Output (Hi non-condensing) kW
(80°C/60°C)
Btu/h
Differential Burner
mbar
Pressure
in wg
Gas Supply Pressure (LPG)
mbar
in wg
Gas Rate (LPG)
m³/h
ft³/h
%CO2 content (± 0.2%)
Sedbuk rating
LPG (propane)
Efficiency
band
A
A
A
SAP efficiency
(%)
91.9
91.6
92.4
Min
10.0
10.1
9.1
CH Max
10.7
10.6
10.7
DHW max
10.6
10.6
10.8
NOx class
5
5
5
Boiler model
CD25C
CD28C
CD35C
DETAILS OF BOILER INSTALLATION
Date of Installation: ......................................................................
Name of Installer: ........................................................................
Address: ......................................................................................
....................................................................................................
....................................................................................................
....................................................................................................
Postcode: ....................................................................................
Telephone No: .............................................................................
Boiler Serial Number: (LPG) ........................................................
(see inside controls panel hinged cover)
Leaflet compiled and designed by Publications 2000 - Tel: (01670) 356211
11/08/D232
Part No. 1.024987
These instructions have been carefully prepared but we reserve the right to
alter the specification at any time in the interest of product improvement.
© Alpha Therm Limited 2008.
6
PARTS LIST
Only the main burner injectors are special to Propane boilers. For other 'Short List Spare Parts', refer to the Installation and
Servicing instructions supplied with the boiler.
Propane components
Main burner injector - CD25C and 28C
Main burner injector - CD35C
Qty.
1
1
Type
4.0 mm
5.4 mm
Alpha Part No.
1.022509
1.024388
7
SERVICING
When servicing or replacing boiler components follow the procedures as described in the main Installation and Servicing
instructions supplied with the boiler.
Remembering the parts special for Propane boilers and the burner pressures special to Propane boilers given in this leaflet.
Alpha Therm Limited.
Nepicar House, London Road, Wrotham Heath,
Sevenoaks, Kent TN15 7RS
Tel: 0870 3001964
email: [email protected]
website: www.alpha-innovation.co.uk
5
COMMISSIONING
The boiler has been tested and factory set for use with Propane gas and it should only be necessary to ensure the correct gas
supply pressure of 37 mbar is available.