PR 5725 Operation & User’s Manual
Read Online
Read the PR 5725 Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
5 7 2 5
S I G N A L S T H E B E S T
P r o g r a m m a b l e
f r e q u e n c y i n d i c a t o r
N o . 5 7 2 5 V 1 0 0 - U K
F r o m s e r . n o . 1 0 0 6 8 7 0 0 1
PR electronics A/S tilbyder et bredt program af analoge og digitale
signalbehandlingsmoduler til industriel automation. Programmet
består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere,
Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv
barske miljøer med elektrisk støj, vibrationer og temperaturudsving,
og alle produkter opfylder de strengeste internationale standarder.
Vores motto »Signals the Best« er indbegrebet af denne filosofi –
og din garanti for kvalitet.
PR electronics A/S offers a wide range of analogue and digital
signal conditioning devices for industrial automation. The product
range includes Isolators, Displays, Ex Interfaces, Temperature
Transmitters, and Universal Devices. You can trust our products
in the most extreme environments with electrical noise, vibrations
and temperature fluctuations, and all products comply with the
most exacting international standards. »Signals the Best« is the
epitome of our philosophy – and your guarantee for quality.
PR electronics A/S offre une large gamme de produits pour le
traitement des signaux analogiques et numériques dans tous
les domaines industriels. La gamme de produits s’étend des
transmetteurs de température aux afficheurs, des isolateurs aux
interfaces SI, jusqu’aux modules universels. Vous pouvez compter
sur nos produits même dans les conditions d’utilisation sévères,
p.ex. bruit électrique, vibrations et fluctuations de température.
Tous nos produits sont conformes aux normes internationales les
plus strictes. Notre devise »SIGNALS the BEST« c’est notre ligne
de conduite - et pour vous l’assurance de la meilleure qualité.
PR electronics A/S verfügt über ein breites Produktprogramm
an analogen und digitalen Signalverarbeitungsmodule für die in
dustrielle Automatisierung. Dieses Programm umfasst Displays,
Temperaturtransmitter, Ex- und galvanische Signaltrenner, und
Universalgeräte. Sie können unsere Geräte auch unter extremen
Einsatzbedingungen wie elektrisches Rauschen, Erschütterungen
und Temperaturschwingungen vertrauen, und alle Produkte von
PR electronics werden in Übereinstimmung mit den strengsten
internationalen Normen produziert. »Signals the Best« ist Ihre
Garantie für Qualität!
DK
UK
FR
DE
Programmable Frequency indicator
5725
contents
Warning...............................................................................
4
Safety instructions...............................................................
5
EC declaration of conformity..............................................
7
Front and back layout.........................................................
8
Application..........................................................................
9
Technical characteristics.....................................................
9
Mounting / installation.........................................................
9
Applications......................................................................... 10
Electrical specifications....................................................... 11
Order: 5725......................................................................... 11
Sensor error indication, inside and outside range.............. 15
Connections........................................................................ 16
Block diagram..................................................................... 17
Routing diagram for 5725A................................................. 19
Routing diagram for 5725D................................................. 21
Scrolling help texts.............................................................. 22
Configuration / operating the function keys....................... 24
Graphic depiction of the relay function setpoint ............... 26
Triangle with an exclamation mark: Warning / demand. Potentially
lethal situations.
The CE mark proves the compliance of the device with the essential
requirements of the directives.
Warning
This device is designed for connection to hazardous electric
voltages. Ignoring this warning can result in severe personal
injury or mechanical damage. To avoid the risk of electric shock
and fire, the safety instructions of this manual must be observed
and the guidelines followed. The specifications must not be
exceeded, and the device must only be applied as described
in the following. Prior to the commissioning of the device, this
manual must be examined carefully. Only qualified personnel
(technicians) should install this device.
If the equipment is used in a manner not specified by the
manufacturer, the protection provided by the equipment may be
impaired.
WARNING
Until the device is fixed, do not connect hazardous voltages to
the device.
The following operations should only be carried out on a
disconnected device and under ESD safe conditions:
Troubleshooting the device.
Repair of the device must be done by PR electronics A/S
only.
GENERAL
HAZARD-
OUS
VOLTAGE
Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and
50 to 1000 Volt AC.
Technicians are qualified persons educated or trained to mount, operate, and
also troubleshoot technically correct and in accordance with safety regulations.
Operators, being familiar with the contents of this manual, adjust and operate
the knobs or potentiometers during normal operation.
Receipt and unpacking
Unpack the device without damaging it. The packing should always follow the
device until this has been permanently mounted. Check at the receipt of the
device whether the type corresponds to the one ordered.
Environment
Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,
as well as rain and heavy moisture. If necessary, heating in excess of the stated
limits for ambient temperatures should be avoided by way of ventilation.
All devices fall under Installation Category II, Pollution Degree 1, and Insulation
Class II.
Mounting
Only technicians who are familiar with the technical terms, warnings, and
instructions in the manual and who are able to follow these should connect the
device.
Should there be any doubt as to the correct handling of the device, please
contact your local distributor or, alternatively,
PR electronics A/S
www.prelectronics.com
Mounting and connection of the device should comply with national legislation
for mounting of electric materials, i.e. wire cross section, protective fuse, and
location. Descriptions of Input / Output and supply connections are shown in
the block diagram and side label.
The following apply to fixed hazardous voltages-connected devices:
The max. size of the protective fuse is 10 A and, together with a power
switch, it shall be easily accessible and close to the device. The power
switch shall be marked as the disconnecting unit for the device.
UL installation requirements
For use on a flat surface of a type 1 enclosure.
Use 60/75°C copper conducters only.
Enclosure rating (face only)..................... Type 4X, UL50E
Max. ambient temperature...................... 60°C
Max. wire size, pins 41...46..................... AWG 30-16
Max. wire size, others............................. AWG 30-12
UL file number......................................... E248256
Calibration and Adjustment
During calibration and adjustment, the measuring and connection of external
voltages must be carried out according to the specifications of this manual. The
technician must use tools and instruments that are safe to use.
Normal operation
Operators are only allowed to adjust and operate devices that are safely fixed
in panels, etc., thus avoiding the danger of personal injury and damage. This
means there is no electrical shock hazard, and the device is easily accessible.
Cleaning
When disconnected, the device may be cleaned with a cloth moistened with
distilled water.
Liability
To the extent the instructions in this manual are not strictly observed, the
customer cannot advance a demand against PR electronics A/S that would
otherwise exist according to the concluded sales agreement.
EC declaration of conformity
As manufacturer
PR electronics A/S
Lerbakken 10
DK-8410 Rønde
hereby declares that the following product:
Type: 5725
Name: LED frequency / pulse converter
is in conformity with the following directives and standards:
The EMC Directive 2004/108/EC and later amendments
EN 61326-1 : 2006
For specification of the acceptable EMC performance level, refer to the
electrical specifications for the device.
The Low Voltage Directive 2006/95/EC and later amendments
EN 61010-1 : 2001
Rønde, 17 February 2011
Kim Rasmussen
Manufacturer’s signature
Programmable Frequency indicator
5725
• Frequencies from 0.001 Hz to 50 kHz
• Input for various sensors; NPN, PNP, Contact,
Namur, S0, Tacho and TTL
• 2 SPDT relays and analogue output
• 4-digit, 14-segment easily readable LED display
• Universal supply voltage
Application
• 5725 is a digital indicator for readout of frequency signals and pulse signals.
• Typical applications are indication and conversion of process speed
measurements and flow rate.
• The indicator can also be used for measuring the passing time on e.g. a
conveyor line, as the 5725 can handle period time measurements.
• Process control is possible as the type 5725D contains 2 pairs of potential-
free change-over relays and an analogue output.
• The display offers IP65 protection from the front and the splash-proof cover -
PR type 8335 - can be used against atmospheres and liquids.
Technical characteristics
• 4-digit LED indication with 13.8 mm 14-segment characters for a
-1999...9999 display readout with programmable decimal point.
• Relay ON / OFF indication via front LED’s.
• Various input sensor types and custom current and voltage trig levels can be
selected via the programming menu.
• Input and supply of NPN and PNP proximity switches is possible from the
input terminals.
• A menu item allows the user to minimise the installation test time for the relay
outputs by activating or deactivating each relay independently of the input
signal.
Mounting / installation
• Panel mounted indicator, 48x96mm which obtains IP65 (type 4X) when using
the rubber gasket provided.
• All standard operational parameters can be adjusted to any application by
way of the front function keys.
• Help texts in eight different languages are available and can be selected via a
menu item.
Analogue, 0/4...20 mA
Special trig
current & voltage
Namur
Tacho
Supply:
21.6...253 VAC
or
19.2...300 VDC
S0
PNP
NPN
Contact
(NPN)
+ Sup
+ Sup
TTL
Input signals:
+ Sup 5...17 V
+ Input
Input gnd
tacho
Relay 2
Specifications range..................................... -20°C to +60°C
Storage temperature.................................... -40°C to +85°C
Calibration temperature............................... 20...28°C
Relative humidity.......................................... < 95% RH (non-cond.)
Protection degree......................................... IP20
Installation in pollution degree 2 & overvoltage category II.
Mechanical specifications:
Dimensions (H x W x D)............................... 48 x 96 x 120 mm
Cutout dimensions....................................... 44.5 x 91.5 mm
Protection degree (mounted in panel).......... IP65 / Type 4X, UL50E
Weight.......................................................... 230 g
Wire size, pin 11-12 & 41-44, max............... 1 x 1.5 mm2/
AWG 30...16 stranded wire
Wire size, others, max.................................. 1 x 2.5 mm2/
AWG 30...12 stranded wire
Terminal connection..................................... Spring-cage
Common electrical specifications:
Supply voltage, universal............................. 21.6...253 VAC, 50...60 Hz
or 19.2...300 VDC
Max consumption, 5725A / 5725D.............. 2.8 W / 3.6 W
Isolation voltage, test / operation................ 2.3 kVAC / 250 VAC
Signal / noise ratio....................................... > 60 dB
Order: 5725
Type
Version
5725
Standard . . . . . . . . . . . . . . . . . . :
A
Analogue output and 2 relays . . :
D
8335 = Splash proof front
Accessories:
Frequency range, F/I conversion function...... 0.001 Hz to 50 kHz
Time range, Period time function................. 999.9 sec to 20 µsec
Response time (0...90%, 100...10%)............ < 1 period + 100 msec
Low cut off frequency.................................. 0.0009 Hz
Low cut off period time................................ 1111 sec
Max. frequency, with input filter ON............ 50 Hz
NAMUR input - acc. to EN 60947-5-6:
Trig-level LOW.............................................. ≤ 1.2 mA
Trig-level HIGH............................................. ≥ 2.1 mA
Input impedance.......................................... 1 kΩ / < 1.5 nF
Breakage detection...................................... ≤ 0.1 mA
Short-circuit detection................................. ≥ 6.9 mA
Sensor supply - pin 44, fixed....................... 8.3 V
Tacho input:
Trig-level LOW.............................................. ≤ - 50 mV
Trig-level HIGH............................................. ≥ + 50 mV
Input impedance.......................................... ≥ 100 kΩ / < 1.5 nF
Max. input voltage........................................ 80 VAC pp
Sensor supply - pin 44, programmable ...... 5 -17 V / 20 mA
NPN / PNP input:
Trig-level LOW.............................................. ≤ 4.0 V
Trig-level HIGH............................................. ≥ 7.0 V
Input impedance.......................................... 3.48 kΩ / < 1.5 nF
Sensor supply - pin 44, programmable ...... 5 -17 V / 20 mA
Accuracy values
Specification
Absolute
accuracy
Temperature
coefficient
Input to Display & Relays
≤ ±0.05%
≤ ±0.01% / °C
Input to Analogue Output
≤ ±0.1%
EMC immunity influence................................... < ±0.5% of span
Extended EMC immunity:
NAMUR NE 21, A criterion, burst..................... < ±1% of span
Trig-level LOW.............................................. ≤ 0.8 VDC
Trig-level HIGH............................................. ≥ 2.0 VDC
Input impedance.......................................... ≥ 100 kΩ / < 1.5 nF
Sensor supply - pin 44, programmable ...... 5 -17 V / 20 mA
S0 input acc. to DIN 43864:
Trig-level LOW.............................................. ≤ 2.2 mA
Trig-level HIGH............................................. ≥ 9.0 mA
Input impedance.......................................... 758 Ω / < 1.5 nF
Sensor supply - pin 44, fixed....................... 17 V
Special voltage input:
User programmable trig-levels..................... -0.05...6.50 V
Hysteresis, min............................................. 50 mV
Input impedance, selectable:
High Z..................................................... ≥100 kΩ / < 1.5 nF
Pull up and pull down............................ 3.48 kΩ / < 1.5 nF
Sensor supply - pin 44, programmable....... 5 -17 V / 20 mA
Special current input:
User programmable trig-levels..................... 0.0...10.0 mA
Hysteresis, min............................................. 0.2 mA
Input impedance.......................................... 1 kΩ / < 1.5 nF
Sensor supply - pin 44, programmable ...... 5 -17 V / 20 mA
Output:
Display:
Display readout............................................ -1999...9999 (4 digits)
Decimal point............................................... Programmable
Digit height................................................... 13.8 mm
Display updating.......................................... 2.2 times / sec.
Input frequency outside range &
Namur input sensor error is indicated by....... Explanatory text
Current output (5725D):
Programmable signal ranges....................... 0...20, 4...20 &
20...0, 20...4 mA
Load (max.)................................................... 20 mA / 800 Ω / 16 VDC
Current limit.................................................. ≤ 28 mA
Load stability................................................ ≤ 0.01% of span / 100 Ω
Programmable response time...................... 1.0...60.0 sec
Sensor error indication, at Namur input:
selectable............................................... 0 / 3.5 / 23 mA / none
Output limitation at outside range:
on 4...20 and 20...4 mA signals............. 3.8...20.5 mA
on 0...20 and 20...0 mA signals............. 0...20.5 mA
Relay outputs (5725D):
Relay function.............................................. Setpoint
Hysteresis, in % / display counts................ 0.1...100% / 1...9999
On and Off delay.......................................... 0...3600 sec
Power On delay............................................ 1.0...60.0 sec
Sensor error action....................................... Make / Break / Hold
Max. voltage................................................. 250 VRMS
Max. current................................................. 2 A / AC
Max. AC power............................................ 500 VA
Max. current at 24 VDC............................... 1 A
Approvals:
EMC 2004/108/EC....................................... EN 61326-1
LVD 2006/95/EC........................................... EN 61010-1
UL, Standard for Safety............................... UL 61010-1
GOST R
Marine:
Det Norske Veritas, Ships & Offshore.......... Stand. f. Certific. No. 2.4
Sensor error indication, inside and outside range
Input ”out of range” indication
Valid measurement range:
Out of range limit
Display readout
F to I function:
0.001 Hz to 50 kHz
< 0.0009 Hz
- equals ”Low cut off time”
”0” or ”IN.LO” if 0% input
value is set different from ”0”
> 50.5 kHz
”IN.HI”
Period time function:
20 µs to 999.9 s
>1111 s (18 min. 31 sec.)
- equals ”Low cut off time”
”IN.LO”
< 19.8 µs
”IN.HI”
! Error indications in the display blink once a second. The help text explains the error.
Sensor error indication in 5725, only available for NAMUR input:
Condition
Out of range
limit
Relay
behaviour
Analogue
output value
Display
redaout
Sensor input
type = NAMUR
and sensor error
detection = ON
> 6.9 mA
Set to user
defined value:
HOLD. ACTIVE.
DEACTIVE or NONE
Set to user-
defined value
(23, 0, 3.5 mA
or NONE)
”SE.SH”
< 0.1 mA
”SE.BR”
Display out of range Indication
Valid display value range:
Out of range limit
Display readout
-1999 to 9999
< -1999
”-1.9.9.9.” - flashing
> 9999
”9.9.9.9.” - flashing
Hardware error indication
Error explanation
Error cause
Display readout
Error in internal communication
(SPI etc.)
Permanent error in inter-
communication between
microcontrollers
”HW.ER”
Error in checksum test of the
configuration in RAM
Error in RAM
”RA.ER”
Error in checksum test of the
configuration in EEPROM
Error in EEPROM
”EE.ER”
Error in OK check or checksum
test of the calibration data in
FLASH
Error in FLASH or
Calibration has not been per-
formed or Calibration data in
FLASH are corrupt
”NO.CA”
41 42 43 44
45
46
41 42 43 44
45
46
41 42 43 44
45
46
41 42 43 44
45
46
41 42 43 44
45
46
41 42 43 44
45
46
41 42 43 44
45
46
41 42 43 44
45
46
mA
11 12
R2
R1
21 22 23 24 25 26
S0
-
+
+ Sup
+ Sup
+ Sup 5-17V
+ Sup 5-17V
∼
41 42 43 44
45
46
TTL
TTL
+ Sup 8.3V
+ Sup 17V
+
+ Sup 5-17V
+ Sup 5-17V
+
+
Special current
Special voltage
Tacho
S0
Namur
PNP
NPN
Contact (NPN)
Current
Inputs:
Output:
Supply:
Relays
Connections
5725A & D
1
2
3
4
44
46
45
43
42
41
R1
R2
mA
VREG
5...17 V
Block diagram
I
Output
Common
Relay 1 N.O.
Relay 1 N.C.
Common
Relay 2 N.O.
Relay 2 N.C.
Supply
Supply
21.6...253 VAC
or
19.2...300 VDC
Option D
Gnd.
Option D
fin
Freq.
detector
Only visible if password is enabled
(E.PAS = YES)
*1
*2
*3
Password 5000...9999:
FastSet and Relay Test features disabled.
(FastSet menus show the actual setpoints).
”Start”
”Monitor”
Hold
(∼3sec.)
Power up
”Start”
Routing diagram for 5725A
If no key is activated for 2 minutes, the display returns to default state
”Monitor” without saving configuration changes.
1 Increase value / choose next parameter
2 Decrease value / choose previous parameter
3 Accept the chosen parameter and go to the next menu
Hold 3 Back to previous menu / return to default state ”Monitor” without
saving.
Minimum IN.HI value is automatically
limited to 1 display count above IN.LO.
”Start”
”Start”
Displays either Hz/kHz or s/ms for 1 sec.
before actual value is displayed.
When value hits digit-limit while scrolling,
either Hz/kHz or s/ms is displayed again for
1 sec. to show the user that the new range
is active.
*4
Only visible if password is enabled
(E.PAS = YES)
*1
*2
*3
Password 5000...9999:
FastSet and Relay Test features disabled.
(FastSet menus show the actual setpoints).
*5
*6
*7
Only visible if max. (IN.LO,IN.HI) value
is ≤ 50 Hz (F/I) or ≥ 20 ms (Period time)
Default if visible = YES, else deactivated.
Range depends on selected display scaling.
Fast setpoint adjustment and relay test
1 Increase setpoint
2 Decrease setpoint
3 Save and exit the menu
1 and 2 simultaneously =
relay changes state
Same procedure
for REL2!
”Start”
”Monitor”
Hold
(∼3sec.)
Power up
”Start”
”Start”
”Start”
Routing diagram for 5725D
If no key is activated for 2 minutes, the display returns to default state ”Monitor”
without saving configuration changes.
1 Increase value / choose next parameter
2 Decrease value / choose previous parameter
3 Accept the chosen parameter and go to the next menu
Hold 3 Back to previous menu / return to default state ”Monitor” without saving.
Only visible if max. (IN.LO,IN.HI) value
is ≤ 50 Hz (F/I) or ≥ 20 ms (Period time)
Default if visible = YES, else deactivated.
Range depends on selected display scaling.
Only visible for NAMUR input.
0mA only visible for A.OUT = 0-20 or 20-0
3.5mA only visible for A.OUT = 4-20 or 20-4
Not visible if both relay functions are OFF.
Minimum IN.HI value is automatically
limited to 1 display count above IN.L0.
”Start”
”Start”
Scrolling help texts
Top line
Scrolling text
TEXT NR
Language menu
UK
UK - SELECT ENGLISH HELP TEXT
0
DK
DK - VAELG DANSK HJAELPETEKST
1
DE
DE - WAEHLE DEUTSCHEN HILFETEXT
2
FR
FR - SELECTION TEXTE D’AIDE EN
FRANCAIS
3
SE
SE - VALJ SVENSK HJALPTEXT
4
IT
IT - SELEZIONARE TESTI DI AIUTO
ITALIANI
5
ES
ES - SELECCIONAR TEXTO DE AYUDA
EN ESPANOL
6
CZ
CZ - VYBER CESKOU NAPOVEDU
7
Error indication
(when active, labels are flashing @ app. 1 Hz)
SE.BR
SENSOR WIRE BREAKAGE
8
IN.HI
INPUT OVERRANGE
9
SE.SH
SENSOR SHORT CIRCUIT
10
IN.LO
INPUT UNDERRANGE
11
9.9.9.9.
DISPLAY OVERRANGE
12
-1.9.9.9.
DISPLAY UNDERRANGE
13
HW.ER
HARDWARE ERROR
14
EE.ER
EEPROM ERROR - CHECK
CONFIGURATION
15
RA.ER
RAM MEMORY ERROR
16
NO.CA
DEVICE NOT CALIBRATED
17
Fastset Menu
F.SET
REL1
FAST SET MENU - SELECT RELAY
18
REL2
FAST SET MENU - SELECT RELAY
18
SETP
(if fastset is enabled)
xxxx
RELAY SETPOINT - PRESS OK TO SAVE
19
SETP
(if fastset is disabled)
xxxx
RELAY SETPOINT - READ ONLY
20
Configuration setup
PASS
xxxx
SET CORRECT PASSWORD
21
IN
PNP
PNP SENSOR INPUT
22
NPN
NPN SENSOR INPUT
23
TTL
TTL SENSOR INPUT
24
NAMU
NAMUR SENSOR INPUT
25
S0
S0 SENSOR INPUT
26
TACH
TACHO SENSOR INPUT
27
XmA
SPECIAL CURRENT SENSOR INPUT
28
XV
SPECIAL VOLTAGE SENSOR INPUT
29
TR.LO
(when special voltage input is selected)
xxxx
SET LOW TRIGGER LEVEL IN VOLT
30
TR.LO
(when special current input is selected)
xxxx
SET LOW TRIGGER LEVEL IN mA
31
TR.HI
(when special voltage input is selected)
xxxx
SET HIGH TRIGGER LEVEL IN VOLT
32
TR.HI
(when special current input is selected)
xxxx
SET HIGH TRIGGER LEVEL IN mA
33
Z.IN
(when special voltage input is selected)
HI.Z
SET INPUT RESISTANCE HIGH
34
PL.UP
SET INPUT PULL UP
35
PL.DN
SET INPUT PULL DOWN
36
S.SUP
(not when NAMUR or S0 input is selected)
xxxx
SET SENSOR SUPPLY VOLTAGE
37
IN.UN
HZ
SET INPUT UNIT FOR FREQUENCY
38
S
SET INPUT UNIT FOR PERIOD TIME
39
IN.LO
xxxx
SET INPUT RANGE LOW IN HZ
40
xxxx
SET INPUT RANGE LOW IN KHZ
41
xxxx
SET INPUT RANGE LOW IN S
42
xxxx
SET INPUT RANGE LOW IN mS
43
IN.HI
xxxx
SET INPUT RANGE HIGH IN HZ
44
xxxx
SET INPUT RANGE HIGH IN KHZ
45
xxxx
SET INPUT RANGE HIGH IN S
46
xxxx
SET INPUT RANGE HIGH IN mS
47
FILT
NO
ENABLE INPUT FILTER
48
YES
ENABLE INPUT FILTER
48
DEC.P
1111
DECIMAL POINT POSITION
49
111.1
DECIMAL POINT POSITION
49
11.11
DECIMAL POINT POSITION
49
1.111
DECIMAL POINT POSITION
49
DI.LO
xxxx
DISPLAY READOUT LOW
50
DI.HI
xxxx
DISPLAY READOUT HIGH
51
SET RELAY IN PERCENTAGE
52
DISP
SET RELAY IN DISPLAY UNITS
53
REL1
OFF
RELAY 1 DISABLED
54
SETP
ENTER RELAY 1 SETUP
55
SKIP
SKIP RELAY 1 SETUP
56
SETP
xxxx
RELAY SETPOINT
57
ACT1
INCR
ACTIVATE AT INCREASING SIGNAL
58
DECR
ACTIVATE AT DECREASING SIGNAL
59
HYS1
xxxx
RELAY HYSTERESIS
60
ERR1
HOLD
HOLD RELAY AT ERROR
61
ACTI
ACTIVATE RELAY AT ERROR
62
DEAC
DEACTIVATE RELAY AT ERROR
63
NONE
UNDEFINED STATUS AT ERROR
64
ON.DE
xxxx
RELAY ON-DELAY IN SECONDS
65
OF.DE
xxxx
RELAY OFF-DELAY IN SECONDS
66
REL2
OFF
RELAY 2 DISABLED
67
SETP
ENTER RELAY 2 SETUP
68
SKIP
SKIP RELAY 2 SETUP
69
SETP
xxxx
RELAY SETPOINT
57
ACT2
INCR
ACTIVATE AT INCREASING SIGNAL
58
DECR
ACTIVATE AT DECREASING SIGNAL
59
HYS2
xxxx
RELAY HYSTERESIS
60
ERR2
HOLD
HOLD RELAY AT ERROR
61
ACTI
ACTIVATE RELAY AT ERROR
62
DEAC
DEACTIVATE RELAY AT ERROR
63
NONE
UNDEFINED STATUS AT ERROR
64
ON.DE
xxxx
RELAY ON-DELAY IN SECONDS
65
OF.DE
xxxx
RELAY OFF-DELAY IN SECONDS
66
PO.DE
xxxx
RELAY POWER ON DELAY IN SECONDS
70
A.OUT
20-4
OUTPUT RANGE IN mA
71
20-0
OUTPUT RANGE IN mA
71
4-20
OUTPUT RANGE IN mA
71
0-20
OUTPUT RANGE IN mA
71
O.ERR
23mA
NAMUR NE43 UPSCALE AT ERROR
72
3.5mA
NAMUR NE43 DOWNSCALE AT ERROR
73
0mA
DOWNSCALE AT ERROR
74
NONE
UNDEFINED OUTPUT AT ERROR
75
RESP
xxxx
ANALOG OUTPUT RESPONSE TIME IN
SECONDS
76
E.PAS
NO
ENABLE PASSWORD PROTECTION
77
YES
ENABLE PASSWORD PROTECTION
77
N.PAS
(when password enabled)
xxxx
SELECT NEW PASSWORD
78
Configuration / operating
the function keys
Documentation for the routing diagram
In general:
When configuring the display you are guided through all parameters, allowing
you to choose the settings which fit the application. For each menu there is
a scrolling help text which is automatically shown in the display if no key has
been activated for appr. 5 seconds.
Configuration is carried out by way of the 3 function keys 1 2 and 3.
1 will increase the numerical value or choose the next parameter. 2 will
decrease the numerical value or choose the previous parameter. 3 will
accept the chosen value and go to the next menu. If a function does not exist
in the hardware, all parametres belonging to that function will be skipped in
order to make configuration as simple as possible. The configuration will not
be saved until the end of the menu structure when the display shows - - - -.
Pressing and holding 3 will return to the previous menu or go back to the
default state (”Monitor”) without saving the changed values or parameters.
If no key is activated for 2 minutes, the display will return to the default state
(”Monitor”) without saving the changed values or parameters.
Furhter explanations:
Fast setpoint adjustment and relay test: These menus are interactive and
allow you to adjust the setpoints while the display is measuring the input
signal. The diodes will then indicate when the relays change state, thus
easing the setpoint adjustment in many situations. By activating 1 and 2
simultaneously, a relay test will be initiated and the relay will change state.
The setpoint adjustment will be saved by a quick press of 3 . Holding
down 3 for more that 0.5 seconds wil return the display to the default state
(”Monitor”) without changing the setpoint.
Password protection: Using a password will block access to the menu and
parameters. There are two levels of password protection. Passwords between
0000 and 4999 allow access to the fast setpoint adjustment and relay test
menus (using this password blocks access to all other parts of the menu).
Passwords between 5000 and 9999 block access to all parts of the menu,
fast setpoint and relay test (current setpoint is still shown). Default password
2008 allows access to all configuration menus.
Graphic depiction of the relay function setpoint
Relay units
Relay units
Setpoint = 50
Hysteresis = 10
Setpoint = 50
Relay action: Increasing
Relay action: Decreasing
Hysteresis = 10
Programmable displays with a wide
selection of inputs and outputs for display of temperature,
volume and weight, etc. Feature linearisation, scaling,
and difference measurement functions for programming
via PReset software.
Displays
A wide selection of transmitters for DIN
form B mounting and DIN rail modules with analogue
and digital bus communication ranging from application-
specific to universal transmitters.
Temperature
Galvanic isolators for analogue and digital
signals as well as HART® signals. A wide product range
with both loop-powered and universal isolators featuring
linearisation, inversion, and scaling of output signals.
Isolation
Interfaces for analogue and digital signals
as well as HART® signals between sensors / I/P converters /
frequency signals and control systems in Ex zone 0, 1 & 2
and for some modules in zone 20, 21 & 22.
Ex interfaces
PC or front programmable modules with
universal options for input, output and supply. This range
offers a number of advanced features such as process
calibration, linearisation and auto-diagnosis.
Universal
PR electronics A/S
[email protected]
Lerbakken 10
tel. +45 86 37 26 77
DK-8410 Rønde
fax +45 86 37 30 85