Amana PACKAGE TERMINAL Installation Instructions & Owner's Manual

File Specifications

Brand: Amana
Category: Air Conditioner
Model: PACKAGE TERMINAL (Installation Instructions & Owner's Manual), prwW779BnTg8.
File Info: Adobe Acrobat PDF (DjVu)
File Size: 0.9 Mb
Pages: 20 pages

Download PDF

Download Amana PACKAGE TERMINAL Manual (20 pages)

Read Online:

Read the Amana PACKAGE TERMINAL Installation Instructions & Owner's Manual online using the built-in PDF viewer. This document explains how to operate the device, adjust settings and perform regular maintenance.

Key Pages of Document

Once the unit is properly wired, measure the unit supply voltage.

Voltage must fall within the voltage utilization range given in Table 2. Unit Voltage Rating Minimum Maximum 230/208 197 253 265 238 292 115 103.5 126.5 Operating Voltage Voltage Utilization Range Table 2 - Operating Voltage OPERATING INSTRUCTIONS USERS CONTROLS A 7 button touch key pad, located behind the control door, controls both temperature and operation mode. The key pads can be used alone or in combination. THERMOSTAT SETTING 7 BUTTON TOUCH PAD WITH DISPLAY Pressing the COOL thermostat control and t ...

• Automatic freeze protection - Whenever power is sup-

plied to the unit and the master switch is in the ON posi- tion, automatic freeze protection is active. If the unit senses temperature below 40°F, the fan motor and elec- tric strip heat are turned on. Freeze protection can be turned off, if required. • Random restart delay - To help eliminate power surges after a power outage, the unit is equipped with a two to four minute random restart delay feature. Whenever the unit is plugged in with the master switch turned on and the mode switch set in the cool or heat mode, a random resta ...

REMOTE CONTROL INPUTS

The C, R, GL, W2, Y/W1, B/O, and GH terminals provide control inputs for a “manufacturer-approved” remote wall mounted thermostat. The “B” terminal can be configured to become “O” if needed see Configuration Settings For remote control thermo- stat operation, refer to the Remote Thermostat Operation section. FRONT DESK CONTROL (FD1, FD2, EH, IN) The FD1, FD2, EH and IN terminals provide control inputs for a front desk switch. Shorting across the FD1 and FD2 terminals will disable unit operation. The only control function which will remain active when thes ...

Vent - (Left Side Unit)

Cabinet Front The cabinet front and discharge air grille can be cleaned with a water dampened cloth. Under no circumstances should hydro- carbon-based cleaners (e.g. acetone, benzene, naphtha gaso- line, etc.) or ammonia based cleaners be used to clean the front or air grilles. Use care when cleaning the control area. YEARLY MAINTENANCE AND CLEANING NOTE: Use a mild biodegradable detergent such as Simple Green™ when cleaning the unit. Special care must be taken to protect the unit’s control board and other electrical components from getting any water on them w ...

REMOTE CONTROL INPUTS

The C, R, GL, W2, Y/W1, B/O, and GH terminals provide control inputs for a “manufacturer-approved” remote wall mounted thermostat. The “B” terminal can be configured to become “O” if needed see Configuration Settings For remote control thermo- stat operation, refer to the Remote Thermostat Operation section. FRONT DESK CONTROL (FD1, FD2, EH, IN) The FD1, FD2, EH and IN terminals provide control inputs for a front desk switch. Shorting across the FD1 and FD2 terminals will disable unit operation. The only control function which will remain active when thes ...

To ensure that the unit operates safely and efficiently, it must

be installed, operated and maintained according to these instal- lation and operating instructions and all local codes and ordi- nances or, in their absence, with the latest edition of the National Electric Code. The proper installation of this unit is described in the following sections. Following the steps in the order presented should ensure proper installation. SLEEVE STIFFENER AND REAR CLOSURE PANEL REMOVAL Before the chassis can be installed in the wall sleeve, the sleeve stiffener and the rear c ...

Amana PACKAGE TERMINAL user guide recommended for: C-Model, AAC081SRB Service, AVH09, PGA**C, PTH MODELS.

⚠️ Download Safety

The Air Conditioner Installation instructions & owner's manual (20 pages) is completely safe to download (last scan date: 05/01/2026).

Related PDF Instructions for Amana PACKAGE TERMINAL:

Air Conditioner Equipment: Frequently Requested

Have some Questions about Amana PACKAGE TERMINAL Device?

Get valuable and actionable advices from other Amana PACKAGE TERMINAL device users. Describe your problem or question, regarding the using of PACKAGE TERMINAL, in as much detail as possible, and other users will be able to answer you.