Digital Temperature Controller

E5CC-U (48 × 48 mm) Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications. • The white PV display with a height of 15.2 mm improves visibility. • High-speed sampling at 50 ms. • Models are available with up to 2 auxiliary outputs, to cover a wide range of applications. • E5CC: Short body with depth of only 60 mm. • Set up the Controller without wiring the power supply by connecting to the computer with a Communications Conversion Cable (sold separately). Setup is easy with the CX-Thermo (sold separately). Main I/O Functions Refer to Safety Precautions. Refer to your OMRON website for the most recent information on applicable safety standards. 48 × 48 mm E5CC-U Sensor Input Dual displays: PV/SV 4-digit displays E5CC-U Universal input • Thermocouple • Pt • Analog current/voltage Indication Accuracy • Thermocouple input: ±0.3% of PV • Pt input: ±0.2% of PV • Analog input: ±0.2% of FS Sampling Period • 50 ms Event Inputs • None • 2 • 4 Remote SP Input • None • 1 Control Output 1 • Relay output • Voltage output (for driving SSR) • Linear current output Control Output 2 • None • Voltage output (for driving SSR) Transfer Output • None • 1 • PF (shift) Key • Temperature status display • Simple programming • Independent heating and cooling PID control • Changed parameter display • Display brightness setting Auxiliary Outputs • None • 1 • 2 • 3 Serial Communications • None • RS-485 This datasheet is provided as a guideline for selecting products. Be sure to refer to the following manuals for application precautions and other information required for operation before attempting to use the product. E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175) 1

Model Number Legend

●Plug-in Models E5CC-@@ @ @ U @ -@@@ (Example: E5CC-RW0AUM-000) −− −−− − −−− A B C D E F * The control output cannot be used as a transfer output. List of Models Heating and Cooling Control ●Using Heating and Cooling Control A Control Output Assignment An auxiliary output is used as the cooling control output. B Control If PID control is used, you can set PID control separately for heating and cooling. This allows you to handle control systems with different heating and cooling response characteristics. Model A B C D E F Meaning Control outputs 1 and 2 No. of auxiliary outputs Power supply voltage Terminal type Input type Options E5CC 48 × 48 mm Control output 1 Control output 2 RW Relay output (SPDT) None QX Voltage output (for driving SSR) None CX Linear current output* None 0 None 1 1 2 2 (one common) A 100 to 240 VAC D 24 VAC/DC U Plug-in model M Universal input HB alarm and HS alarm Communi- cations Event inputs Remote SP Input Transfer out- put 000 --- --- --- --- --- Control output No. of auxiliary outputs Options Model Model HB alarm and HS alarm No. of event inputs Communications Power supply voltage Power supply voltage 100 to 240 VAC 24 VAC/DC Relay output --- --- --- --- E5CC-RW0AUM-000 E5CC-RW0DUM-000 1 E5CC-RW1AUM-000 E5CC-RW1DUM-000 2 E5CC-RW2AUM-000 E5CC-RW2DUM-000 Voltage output (for driving SSR) --- --- --- --- E5CC-QX0AUM-000 E5CC-QX0DUM-000 1 E5CC-QX1AUM-000 E5CC-QX1DUM-000 2 E5CC-QX2AUM-000 E5CC-QX2DUM-000 Linear current output --- --- --- --- E5CC-CX0AUM-000 E5CC-CX0DUM-000 1 E5CC-CX1AUM-000 E5CC-CX1DUM-000 2 E5CC-CX2AUM-000 E5CC-CX2DUM-000

Optional Products (Order Separately)

USB-Serial Conversion Cable Terminal Covers (for E5CC) Note: The E53-COV10 cannot be used. Refer to page 14 for the mounted dimensions. Waterproof Packing Note: The Waterproof Packing is provided only with E5CC Controllers. The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached. Current Transformers (CTs) Adapter Note: Use this Adapter when the panel has already been prepared for an E5B@ Controller. Waterproof Cover Mounting Adapter Note: This Mounting Adapter is provided with the Digital Temperature Controller. DIN Track Mounting Adapter Sockets (for E5CC-U) Front Covers CX-Thermo Support Software Note: CX-Thermo version 4.5 or higher is required for the E5CC. CX-Thermo version 4.61 or higher is required for the E5CC-U. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com). Model E58-CIFQ2 Model E53-COV17 E53-COV23 Model Y92S-P8 Hole diameter Model 5.8 mm E54-CT1 12.0 mm E54-CT3 Model Y92F-45 Model Y92A-48N Model Y92F-49 Model Y92F-52 Type Model Front-connecting Socket P2CF-11 Front-connecting Socket with Finger Protection P2CF-11-E Back-connecting Socket P3GA-11 Terminal Cover for Back-connecting socket with Finger Protection Y92A-48G Type Model Hard Front Cover Y92A-48H Soft Front Cover Y92A-48D Model EST2-2C-MV4

* You cannot select a relay output or linear current output for control output 2.

Note: There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 4. Power supply voltage A in model number: 100 to 240 VAC, 50/60 Hz D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Power consumption Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or 1.6 W max. at 24 VDC All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC Sensor input Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II Platinum resistance thermometer: Pt100 or JPt100 Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C Analog input Current input: 4 to 20 mA or 0 to 20 mA Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB/THB.) Control method ON/OFF control or 2-PID control (with auto-tuning) Control output Relay output E5CC: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum ap- plicable load: 5 V, 10 mA * E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applica- ble load: 5 V, 10 mA Voltage output (for driving SSR) Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000* Auxiliary output Number of outputs E5CC: 3 E5CC-U: 1 or 2 (depends on model) Output specifications SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V Event input Number of inputs 2 or 4 (depends on model) External contact input specifications Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. Current flow: Approx. 7 mA per contact Transfer output Number of outputs 1 (only on models with a transfer output) Output specifications Contact output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 Linear voltage output: 1 to 5 VDC, load: 1 kΩ max, resolution: Approx. 10,000 Setting method Digital setting using front panel keys Remote SP input Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.) Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) Indication method 11-segment digital display and individual indicators Character height: PV: 15.2 mm, SV: 7.1 mm Multi SP Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or serial communications. Bank switching None Other functions Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, simple calculations, temperature status display, simple programming, moving average of input value, and display brightness setting Ambient operating temperature -10 to 55°C (with no condensation or icing), for 3-year warranty: -10 to 50°C (with no condensation or icing) Ambient operating humidity 25% to 85% Storage temperature -25 to 65°C (with no condensation or icing) Altitude 2,000 m max. Recommended fuse T2A, 250 VAC, time lag, low shut-off capacity Installation environment Installation Category II, Pollution Class 2 (IEC 61010-1 compliant)

●Thermocouple/Platinum Resistance Thermometer (Universal inputs)

Shaded settings are the default settings. The applicable standards for the input types are as follows: K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989 L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751 U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard) W: W5Re/W26Re, ASTM E988-1990 ●Analog input Sensor type Platinum resistance thermometer Thermocouple Infrared temperature sensor Sensor specifica- tion Pt100 JPt100 K J T E L U N R S B W PLII 10 to 70°C 60 to 120°C 115 to 165°C 140 to 260°C 2300 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 -100 -200 2300 1800 1700 1700 1300 1300 1300 850 850 850 600 500.0 500.0 500.0 400.0 400 400.0 400 400.0 260 120 165 100.0 100.0 90 100 0.0 0.0 0 0 0 0 0 0 0 0 -20.0 -100 -20.0 -100 -200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200 Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Input type Current Voltage Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V Setting range Usable in the following ranges by scaling: -1999 to 9999, -199.9 to 999.9, -19.99 to 99.99 or -1.999 to 9.999 Set value 25 26 27 28 29 Temperature range (°C)

Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)

Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed. To use alarm 1, set the output assignment to alarm 1. Set value Alarm type Alarm output operation Description of function When alarm value X is positive When alarm value X is negative 0 Alarm function OFF Output OFF No alarm 1 Upper- and lower-limit *1 *2 Set the upward deviation in the set point for the alarm upper limit (H) and the lower deviation in the set point for the alarm lower limit (L). The alarm is ON when the PV is outside this deviation range. 2 (default) Upper-limit Set the upward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is higher than the SP by the deviation or more. 3 Lower-limit Set the downward deviation in the set point by setting the alarm value (X). The alarm is ON when the PV is lower than the SP by the deviation or more. 4 Upper- and lower-limit range *1 *3 Set the upward deviation in the set point for the alarm upper limit (H) and the lower deviation in the set point for the alarm lower limit (L). The alarm is ON when the PV is inside this de- viation range. 5 Upper- and lower-limit with standby sequence *1 *4 A standby sequence is added to the upper- and lower-limit alarm (1). *6 6 Upper-limit with standby sequence A standby sequence is added to the upper-limit alarm (2). *6 7 Lower-limit with standby sequence A standby sequence is added to the lower-limit alarm (3). *6 8 Absolute-value upper-lim- it The alarm will turn ON if the process value is larger than the alarm value (X) regardless of the set point. 9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller than the alarm value (X) regardless of the set point. 10 Absolute-value upper-lim- it with standby sequence A standby sequence is added to the absolute-value upper- limit alarm (8). *6 11 Absolute-value lower-limit with standby sequence A standby sequence is added to the absolute-value lower- limit alarm (9). *6 12 LBA (alarm 1 type only) - *7 13 PV change rate alarm - *8 14 SP absolute-value upper-limit alarm This alarm type turns ON the alarm when the set point (SP) is higher than the alarm value (X). 15 SP absolute-value lower-limit alarm This alarm type turns ON the alarm when the set point (SP) is lower than the alarm value (X). 16 MV absolute-value upper-limit alarm *9 Standard Control Standard Control This alarm type turns ON the alarm when the manipulated variable (MV) is higher than the alarm value (X). Heating/Cooling Control (Heating MV) Heating/Cooling Control (Heating MV) Always ON 17 MV absolute-value lower-limit alarm *9 Standard Control Standard Control This alarm type turns ON the alarm when the manipulated variable (MV) is lower than the alarm value (X). Heating/Cooling Control (Cooling MV) Heating/Cooling Control (Cooling MV) Always ON 18 RSP absolute-value upper-limit alarm *10 This alarm type turns ON the alarm when the remote SP (RSP) is higher than the alarm value (X). 19 RSP absolute-value lower-limit alarm *10 This alarm type turns ON the alarm when the remote SP (RSP) is lower than the alarm value (X). ON OFF PV SP L H SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV SP L H ON OFF PV SP L H ON OFF PV *5 SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV SP X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF PV 0 X ON OFF SP 0 X ON OFF SP 0 X ON OFF SP 0 X ON OFF SP 0 X ON OFF MV 0 X ON OFF MV 0 X ON OFF MV 0 X ON OFF MV 0 X ON OFF MV 0 X ON OFF MV 0 X ON OFF RSP 0 X ON OFF RSP 0 X ON OFF RSP 0 X ON OFF RSP

With set values 1, 4 and 5, the upper and lower limit values can be set

independently for each alarm type, and are expressed as “L” and “H.” *2 Set value: 1, Upper- and lower-limit alarm *3 Set value: 4, Upper- and lower-limit range *4 Set value: 5, Upper- and lower-limit with standby sequence For Upper- and Lower-Limit Alarm Described Above *2 • Case 1 and 2 Always OFF when the upper-limit and lower-limit hysteresis overlaps. • Case 3: Always OFF *5. Set value: 5, Upper- and lower-limit with standby sequence Always OFF when the upper-limit and lower-limit hysteresis overlaps. *6 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No. H174) for information on the operation of the standby sequence. *7 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.H174) for information on the loop burnout alarm (LBA). *8 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No. H174) for information on the PV change rate alarm. *9 When heating/cooling control is performed, the MV absolute upper limit alarm functions only for the heating operation and the MV absolute lower limit alarm functions only for the cooling operation. *10 This value is displayed only when a remote SP input is used. It functions in both Local SP Mode and Remote SP Mode. Remote SP input is supported only for the E5CC. L H H<0, L>0 |H| < |L| SP Case 1 L H H>0, L<0 |H| > |L| SP Case 2 L H H<0, L<0 SP L H H<0, L>0 |H| ≥ |L| SP L H H>0, L<0 |H| ≤ |L| SP Case 3 (Always ON) L H H<0, L>0 |H| < |L| SP Case 1 L H H>0, L<0 |H| > |L| SP Case 2 L H H<0, L<0 SP L L H H<0, L>0 |H| ≥ |L| SP H H>0, L<0 |H| ≤ |L| SP Case 3 (Always OFF)

*1 The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and U and

L thermocouples at any temperatures is ±2°C ±1 digit max. The indication accuracy of the B thermocouple at a temperature of 400°C max. is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800°C is ±3°C max. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ±3°C ±1 digit max. The indication accuracy of W thermocouples is (±0.3% of PV or ±3°C, whichever is greater) ±1 digit max. The indication accuracy of PL II thermocouples is ±0.3% of PV or ±2°C, whichever is greater, ±1 digit max. *2 Ambient temperature: -10°C to 23°C to 55°C, Voltage range: -15% to 10% of rated voltage *3 K thermocouple at -100°C max.: ±10°C max. *4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time. *6 The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11 is not certified for UL listing. *7 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html *8 Refer to information on maritime standards in Shipping Standards on page 56 for compliance with Lloyd's Standards. The E5CC-U is scheduled to obtain certification in January, 2014. Indication accuracy (at the ambient temperature of 23°C) E5CC Thermocouple: (±0.3% of PV or ±1°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of PV or ±0.8°C, whichever is greater) ±1 digit Analog input: ±0.2% FS ±1 digit max. CT input: ±5% FS ±1 digit max. E5CC-U Thermocouple: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. *1 Platinum resistance thermometer: (±0.2% of PV or ±0.8°C, whichever is greater) ±1 digit Analog input: ±0.2% FS ±1 digit max. Transfer output accuracy ±0.3% FS max. Remote SP Input Type ±0.2% FS ±1 digit max. Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (±1% of PV or ±10°C, whichever is greater) ±1 digit max. Other thermocouple input: (±1% of PV or ±4°C, whichever is greater) ±1 digit max. *3 Platinum resistance thermometer: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. Analog input: ±1%FS ±1 digit max. CT input: ±5% FS ±1 digit max. Remote SP input: ±1% FS ±1 digit max. Influence of voltage *2 Input sampling period 50 ms Hysteresis Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.01% to 99.99% FS (in units of 0.01% FS) Proportional band (P) Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Proportional band (P) for cooling Temperature input: 0.1 to 999.9°C or °F (in units of 0.1°C or °F) Analog input: 0.1% to 999.9% FS (in units of 0.1% FS) Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4 Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s) Manual reset value 0.0 to 100.0% (in units of 0.1%) Alarm setting range -1999 to 9999 (decimal point position depends on input type) Influence of signal source resistance Thermocouple: 0.1°C/Ω max. (100 Ωmax.) Platinum resistance thermometer: 0.1°C/Ω max. (10 Ω max.) Insulation resistance 20 MΩ min. (at 500 VDC) Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge Vibration Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions Shock Malfunction 100 m/s2, 3 times each in X, Y, and Z directions Resistance 300 m/s2, 3 times each in X, Y, and Z directions Weight E5CC: Controller: Approx. 120 g, Mounting Bracket: Approx. 10 g E5CC-U: Controller: Approx. 100 g, Mounting Bracket: Approx. 10 g Degree of protection E5CC: Front panel: IP66, Rear case: IP20, Terminals: IP00 E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00 Memory protection Non-volatile memory (number of writes: 1,000,000 times) Setup Tool E5CC: CX-Thermo version 4.5 or higher E5CC-U: CX-Thermo version 4.61 or higher Setup Tool port E5CC/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on the computer. *5 Standards Approved standards UL 61010-1*6, KOSHA certified (some models) *7, Korean Radio Waves Act (Act 10564) Conformed standards EN 61010-1 (IEC 61010-1): Pollution level 2, overcurrent category II, Lloyd's standards *8 EMC EMI: EN61326 Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A Noise Terminal Voltage: EN 55011 Group 1, class A EMS: EN 61326 ESD Immunity: EN 61000-4-2 Electromagnetic Field Immunity: EN 61000-4-3 Burst Noise Immunity: EN 61000-4-4 Conducted Disturbance Immunity: EN 61000-4-6 Surge Immunity: EN 61000-4-5 Voltage Dip/Interrupting Immunity: EN 61000-4-11

USB-Serial Conversion Cable

Windows is a registered trademark of Microsoft Corporation in the United States and or other countries. * Use a high-power port for the USB port. Note: A driver must be installed on the computer. Refer to the Instruction Manual included with the Cable for the installation procedure. Communications Specifications * The baud rate, data bit length, stop bit length, and vertical parity can be individually set using the Communications Setting Level. Communications Functions MELSEC is a registered trademark of Mitsubishi Electric Corporation. KEYENCE is a registered trademark of Keyence Corporation. *1 A Temperature Controller with version 1.1 or higher is required. A Temperature Controller with version 2.1 or higher is required for the FX Series or the KV Series. *2 Both the programless communications and the component communications support the copying. Current Transformer (Order Separately) Ratings Heater Burnout Alarms and SSR Failure Alarms *1 For heater burnout alarms, the heater current will be measured when the control output is ON, and the output will turn ON if the heater current is lower than the set value (i.e., heater burnout detection current value). *2 For SSR failure alarms, the heater current will be measured when the control output is OFF, and the output will turn ON if the heater current is higher than the set value (i.e., SSR failure detection current value). *3 The value is 30 ms for a control period of 0.1 s or 0.2 s. *4 The value is 35 ms for a control period of 0.1 s or 0.2 s. Electrical Life Expectancy Curve for Relays (Reference Values) Applicable OS Windows XP, Vista, or 7 Applicable software CX-Thermo version 4.5 or higher (Version 4.61 or higher is required for the E5CC-U.) Applicable models E5@C-T Series, E5@C Series, and E5CB Series USB interface standard Conforms to USB Specification 2.0. DTE speed 38400 bps Connector specifications Computer: USB (type A plug) Digital Temperature Controller: Special serial connector Power supply Bus power (Supplied from USB host controller.)* Power supply voltage 5 VDC Current consumption 450 mA max. Output voltage 4.7±0.2 VDC (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.) Output current 250 mA max. (Supplied from USB-Serial Conversion Cable to the Digital Temperature Controller.) Ambient operating temperature 0 to 55°C (with no condensation or icing) Ambient operating humidity 10% to 80% Storage temperature -20 to 60°C (with no condensation or icing) Storage humidity 10% to 80% Altitude 2,000 m max. Weight Approx. 120 g 500 300 100 50 30 10 5 3 1 0 1 2 3 4 5 6 Switching current (A) E5CC 250 VAC, 30 VDC (resistive load) cosφ = 1 Life (× 104 operations) External Connections E5CC-U A B B + − 250 VAC, 3 A (resistive load) Control output 1 • • Auxiliary output 1 Relay output − + V − mA + The E5CC-U is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input type setting does not agree with the temperature sensor. Check the input type. Sensor (temperature/analog) input Auxiliary output 2: Control output (cooling side) Control output 1: Control output 1 100 to 240 VAC 24 VAC/DC (no polarity) RW CX Models with 1 Relay Output QX + − Models with 1 Voltage Output (for Driving SSR) Models with 1 Linear Current Output Output 1 Q Output 1 C Output 1 R E5CC-����UM-000 Control output 1 + − Auxiliary outputs 1 and 2 Voltage output (for driving SSR) 12 VDC, 21 mA Linear current output 4 to 20 mA DC 0 to 20 mA DC Load: 500 Ω max. Relay output (three terminals used) SPDT, 250 VAC, 3 A (resistive load) Input power supply I V TC Pt

Isolation/Insulation Block Diagrams

� ��• E5CC-U Models with 2 Auxiliary Outputs Nomenclature Sensor input Voltage output (for driving SSR) and linear current output Relay output Auxiliary outputs 1 and 2 : Reinforced insulation : Functional isolation Power supply E5CC-U Press O Key once to go to Adjustment Level. Press O Key for at least 3 seconds to go to Initial Setting Level. Use the M Key to change to another parameter. Operation indicators No. 1 display No. 2 display Temperature unit Use S Key to change the digit (default setting). Use the U D Keys to set the parameter. Front panel PV or specified parameter SP or specified parameter value Top View of E5CC Top View of E5CC-U Top-panel Setup Tool port 10 E5CC-U Dimensions (Unit: mm) Controllers 58 76.8 58.6 4 14.2 48 × 48 48 × 48 Mounting Adapter (Accessory) 45+0.6 0 45+0.6 0 45+0.6 0 60 min. (48 × number of units - 2.5)+1.0 0 Panel Cutout Mounted Separately Group Mounted E5CC-U • Recommended panel thickness is 1 to 5 mm. • Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.) • When two or more Controllers are mounted, make sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications. • To attach the USB-Serial Conversion Cable to the control panel, use a panel thickness of 1 to 2.5 mm. The Setup Tool port is on the top of the Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection. Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure. Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

Accessories (Order Separately)

(2,110) (87) 250 1,740 (13) (250) (5) (15) USB connector (type A plug) Serial connector LED (SD) LED (PWR) LED (RD) ● USB-Serial Conversion Cable E58-CIFQ2 48 48.8 22 9.1 10 44.8 2 3.8 Terminal Cover (E53-COV23) ● Terminal Covers E53-COV17 ● Terminal Covers E53-COV23 (Three Covers provided.) Y92A-48G UP P C 34 Twelve, 6.4-dia. 47.7×47.7 48×48 24.6 27.6 16.5 47.4 ● Terminal Cover (for the P3GA-11 Back-connecting Socket) Y92A-48G Note: You can attach the P3GA-11 Back-connecting Socket for finger protection. ● Waterproof Packing Y92S-P8 (for DIN 48 × 48) The Waterproof Packing is provided only with the E5CC. Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment. Therefore, periodic replacement is recommended to ensure the level of waterproofing specified in IP66. The time for periodic replacement depends on the operating environment. Be sure to confirm this point at your site. Consider three years a rough standard.) The Waterproof Packing does not need to be attached if a waterproof structure is not required. The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached. E5CC-U

● DIN Track Mounting Adapter

Fixture (Accessory) 69.6 to 77.6 87 67 × 67 72 × 72 76 4.7 72 × 72 48 × 48 Panel (1 to 8 mm) Mounting Adapter Y92F-30 (Accessory) 62.8 To back of the E5CC 2.2 4.7 Y92F-45 Mounted to E5CC Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel. 50 61 3.5 38 48 80.5 Mounted to E5CC Note: This Adapter cannot be used together with the Terminal Cover. Remove the Terminal Cover to use the Adapter. Y92F-52 This Adapter is used to mount the E5CC to a DIN Track. If you use the Adapter, there is no need for a plate to mount in the panel or to drill mounting holes in the panel. 12 E5CC-U

● E5CC-U Wiring Socket

Front-connecting Socket P2CF-11 Back-connecting Socket P3GA-11 ● Watertight Cover Y92A-48N ● Mounting Adapter Y92F-49 ● Protective Cover ● Protective Cover Y92A-48H 67.6 69 12 21.9 14 (2) 79.2 87.7 The Mounting Adapter is provided with the Temperature Controller. Order this Adapter separately if it becomes lost or damaged. This Protective Cover is soft type. It is able to operate the controller with using this cover. Note: This Protective Cover cannot be used if the Waterproof Packing is installed. Y92A-48D This Protective Cover is hard type. Please use it for the mis-operation prevention etc. 40±0.2 4.5 7 6 5 8 4 3 2 1 9 10 11 70 max. 4 Eleven, M3.5 × 7.5 sems screws 7.8 Two, 4.5-dia. holes 50 max. 3 31.2 max. 35.4 Mounting Holes Terminal Layout/Internal Connections (Top View) Two, 4.5 dia. mounting holes Note: 1. A model with finger protection (P2CF-11-E) is also available. 2. You cannot use the P2CF-11 or P2CF-11-E together with the Y92F-45. Note: Can also be mounted to a DIN track 5 6 7 8 4 3 2 9 11 10 1 25.6 27dia. 45 45 4.5 16.3 6.2 4 7 3 8.7 6 Terminal Layout/Internal Connections (Bottom View) Eleven, M3.5 sems screws Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets. 2. A Protective Cover for finger protection (Y92A-48G) is also available. 3. You cannot use the P3GA-11 together with the Y92F-45. E5CC-U 1�

Setting Levels Diagram

This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level. *1 To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to ON and set the PF Setting parameter to a-m (Auto/Manual). *2 The No. 1 display will flash when the keys are pressed for 1 s or longer. *3 Set the PF Setting parameter to pfdp (monitor/setting items). Operation in progress Stopped Press the O Key once. Communications Setting Level Advanced Function Setting Level Power ON Initial Setting Level Operation Level Adjustment Level Press the O + M Keys for at least 1 s Only when Manual Mode was used just before power OFF Level changes automatically. Press the S Key. Press the S Key.*3 Protect Level Calibration Level Manual Control Level Press the O Key for at least 1 s. Press the O Key for at least 1 s or the S Key for at least 1 s Used to set the MV manually. Used for SP, alarm values, and other basic settings and monitoring. Used to set protection for operations. Used to change adjustment parameters (PID constants, adjustment sensitivity, etc.). Press the O + M Keys for at least 3 s.*2 Release protection and then enter the password (−169) for the amoV (Move to Advanced Setting Level) parameter. Used to set application functions. Enter the password (1201) for the Move to Calibration Level parameter. Used to set the input type and other basic settings. Press the O Key for at least 1 s. Used to set up communications. Press the O Key for at least 3 s*2 Press O Key once (models with communications only). Press the O Key once. Press the O Key once. O Key for at least 3 s while a-m is displayed.*2 S Key for at least 1 s*1 Monitor/Setting Item Level Used to display specified monitor and setting items.

Error Displays (Troubleshooting)

When an error occurs, the No. 1 display or No. 2 display shows the error code. Take necessary measure according to the error code, referring the following table. Display Name Meaning Action Operation s.err Input error The input value exceeded the control range.* The input type is not set correctly. The sensor is disconnected or short- circuited. The sensor is not wired correctly. The sensor is not wired. * Control Range Temperature resistance thermometer or thermocouple input: SP Lower Limit - 20°C to SP Upper Limit + 20°C (SP Lower Limit - 40°F to SP Upper Limit + 40°F) ESIB input: Same as specified input range. Analog input: Scaling range -5% to 105% Check the wiring for input to be sure it is wired correctly, not broken, and not shorted. Also check the input type. If there are no problems in the wiring or input type settings, cycle the power supply. If the display remains the same, replace the Digital Temperature Controller. If the display is restored to normal, then the probable cause is external noise affecting the control system. Check for external noise. Note: For a temperature resistance thermometer, the input is considered disconnected if the A, B, or B’ line is broken. After the error occurs and it is displayed, the alarm output will operate as if the upper limit was exceeded. It will also operate as if transfer output exceeded the upper limit. If an input error is assigned to a control output or auxiliary output, the output will turn ON when the input error occurs. The error message will appear in the display for the PV. Note: 1. The heating and cooling control outputs will turn OFF. 2. When the manual MV, MV at stop, or MV at error is set, the control output is determined by the set value. [[[[ Display range exceeded Below -1,999 This is not an error. It is displayed when the control range is wider than the display range and the PV exceeds the display range. The PV is displayed for the range that is given on the left (the number without the decimal point). - Control continues and operation is normal. The value will appear in the display for the PV. Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the controllable range. ]]]] Above 9,999 e333 A/D converter error There is an error in the internal circuits. First, cycle the power supply. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. The control outputs, auxiliary outputs, and transfer outputs turn OFF. (A current output will be approx. 0 mA and a linear voltage output will be approx. 0V.) e111 Memory error There is an error in the internal memory operation. First, cycle the power supply. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise. The control outputs, auxiliary outputs, and transfer outputs turn OFF. (A current output will be approx. 0 mA and a linear voltage output will be approx. 0V.) ffff Overcurrent This error is displayed when the peak current exceeds 55.0 A. - Control continues and operation is normal. The error message will appear for the following displays. Heater Current Value 1 Monitor Heater Current Value 2 Monitor Leakage Current Value 1 Monitor Leakage Current Value 2 Monitor ct1 ct2 lcr1 lcr2 HB or HS alarm If there is a HB or HS alarm, the No. 1 display will flash in the relevant setting level. - The No. 1 display for the following parameter flashes in Operation Level or Adjustment Level. Heater Current Value 1 Monitor Heater Current Value 2 Monitor Leakage Current Value 1 Monitor Leakage Current Value 2 Monitor However, control continues and operation is normal. ---- Potentiometer Input Error (Position- proportional Models Only) "----" will be displayed for the Valve Opening Monitor parameter if any of the following error occurs. • Motor calibration has not been performed. • The wiring of the potentiometer is incorrect or broken. • The potentiometer input value is incorrect (e.g., the input is out of range or the potentiometer has failed). Check for the above errors. Close control: The control output is OFF or the value that is set for the MV at PV Error parameter is output. Floating control: Operation will be normal.

Starting in Manual Mode.

Starting in Automatic Mode. PID Control only PV/MV Press the O Key less than 1 s. Press the O and M Keys for at least 3 s. Press the O and M Keys for at least 1 s. Press the O Key less than 1 s. Press the O Key for at least 1 s. Press the O Key for less than 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display Press the S Key*2 Press the S Key for at least 1 s. Press the O Key or the S Key for at least 1 s. *1. When the PF Setting parameter is set to A-M. *2. When the PF Setting parameter is set to PFDP. Press the S Key*2 Displayed only for models with communications. Changes are effective after cycling power or after a software reset. *3. Used with component communications. M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M M * Used with programless communications M M M M M M M M M M M M M M M M M M M M M M pmsk on 25 0 C 25 0 l.adj ins 0.0 rss 0.0 inrt 1.000 rsrt 1.000 c-p 8.0 c-i 233 c-d 40 M M M p 8.0 i 233 d 40 c-db 0.0 of-r 50.0 hys 1.0 chys 1.0 soak 1 wt-b off mv-s 0.0 pmov 0 psel cwf u-no 1 bps 9.6 len 7 sbit 2 prty even sdwt 20 maxu 0 area 0 adrh 0 adrl 0 rwat 1000 unit 0 up 1 0 up13 0 dn 1 0 dn13 1000 copy off sps 1.000 spos 0.0 oapt 0 icpt 1 wtpt off pfpt off M M chgp off M prlp 0 mv-e 0.0 sprl same M sprt off w1on w2on w3on w4of w5on w6on w7on w8on w1of w2of w3of w4on w5of w6of w7of w8of plcm 1234 ol-h 100.0 ol-l 0.0 M sqrp 0 M oc-h 0.8 at off cmwt off ct1 0.0 M spmd lsp hb1 0.0 ct2 0.0 hb2 0.0 lcr1 0.0 hs1 50.0 lcr2 0.0 hs2 50.0 sp-0 0 sp-1 0 sp-2 0 sp-3 0 sp-4 0 sp-5 0 sp-6 0 sp-7 0 M sp-3 0 r-s run v-m in-t 5 in-h 100 in-l 0 dp 0 d-u c sl-h 1300 sl-l -200 cntl onof s-hc stnd st on ptrn off cp 20 c-cp 20 orev or-r alt1 2 alh1 0.2 al-1 0 al1h 0 al1l 0 al-2 0 al2h 0 al2l 0 al-4 0 al4h 0 al4l 0 M M M al-3 0 al3h 0 al3l 0 o 0.0 c-o 0.0 0.0 25 0 a-m m-sp 0 sp-m 0 rsp 0.0 ct-1 0.0 ct-2 0.0 lcr1 0.0 lcr2 0.0 prst rset M sktr 0 M orl 0 M db 2.0 Power ON Adjustment Level Press the O Key less than 1 s. Manual Control Level Adjustment Level Display Displayed only once when entering adjustment level. AT Execute/Cancel Communications Writing Heater Current 1 Value Monitor Heater Burnout Detection 1 Heater Current 2 Value Monitor Heater Burnout Detection 2 Leakage Current 1 Monitor Leakage Current 2 Monitor HS Alarm 1 SP Mode SP 4 SP 5 SP 6 SP 7 HS Alarm 2 SP 0 SP 1 SP 2 SP 3 Proportional Band (Cooling) Integral Time (Cooling) Derivative Time (Cooling) Process Value Input Shift Remote SP Input Shift Process Value Slope Coefficient Remote SP Input Slope Coefficient Proportional Band Integral Time PID settings Derivative Time Dead Band SP Ramp Fall Value Manual Reset Value Clear the offset during stabilization of P or PD control. Hysteresis (Heating) Hysteresis (Cooling) Hysteresis settings Soak Time Wait Band MV at Stop MV at PV Error SP Ramp Set Value MV Upper Limit MV Lower Limit MV Change Rate Limit Work Bit 1 ON Delay Work Bit 2 ON Delay Work Bit 3 ON Delay Work Bit 4 OFF Delay Work Bit 5 ON Delay Work Bit 6 ON Delay Work Bit 7 ON Delay Work Bit 8 ON Delay Work Bit 1 OFF Delay Work Bit 2 OFF Delay Work Bit 3 OFF Delay Work Bit 4 ON Delay Work Bit 5 OFF Delay Work Bit 6 OFF Delay Work Bit 7 OFF Delay Work Bit 8 OFF Delay Extraction of Square Root Low-cut Point Press the O Key for at least 3 s. Process Value/ Set Point 1 Process Value/ Set Point 2 Auto/Manual Switch PID control only. Added when auto/manual select addition is ON. Multi-SP Set Point Selection Set Point During SP Ramp Heater Current 1 Value Monitor Heater Current 2 Value Monitor Leakage Current 1 Monitor Leakage Current 2 Monitor Program Start Soak Time Remain RUN/STOP Remote SP Monitor Operation Level Position Proportional Dead Band Open/Close Hysteresis Communications Monitor Initial Setting Level Set either of these parameters. Alarm Value 1 Alarm Value Upper Limit 1 Alarm Value Lower Limit 1 Set either of these parameters. Alarm Value 2 Alarm Value Upper Limit 2 Alarm Value Lower Limit 2 Alarm Value 3 Alarm Value Upper Limit 3 Alarm Value Lower Limit 3 MV Monitor (Heating) MV Monitor (Cooling) Alarm Value Upper Limit 4 Alarm Value Lower Limit 4 Alarm Value 4 Set either of these parameters. Set either of these parameters. Valve Opening Monitor Protect Level Communications Setting Level Move to Protect Level: Displayed only when a password is set. Restricts moving to protect level. Operation/Adjustment Protect: Restricts displaying and modifying menus in operation, adjustment, and manual control levels. Initial Setting/Communications Protect: This protect level restricts movement to the initial setting, communications setting, and advanced function setting levels. Setting Change Protect: Protects changes to setups by operating the front panel keys. Password to Move to Protect Level: Password setting PF Key Protect Parameter Mask Enable: Displayed only when a parameter mask is set. Changed Parameters Only Protocol Setting: Switches between CompoWay/F and Modbus. Communications Unit No. Communications Baud Rate CompoWay/F only Communications Data Length Communications Stop Bits Communications Parity Send Data Wait Time ST (Self-tuning) Input Type Scaling Upper Limit Scaling Lower Limit Decimal Point For input type of analog Temperature Unit °C, °F For input type of temperature SP Upper Limit SP Lower Limit Limit the set point PID ON/OFF Standard or Heating/Cooling For input type of temperature, standard control, or PID Program Pattern When assigning PID or control output to ON/OFF output Control Period (Heating) Control Period (Cooling) Set the ON/OFF output cycle. Direct/Reverse Operation Alarm 1 Type Alarm 1 Hysteresis Highest Communications Unit No. The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. *3 Area First Address Upper Word First Address Lower Word Receive Data Wait Time *3 Communications Node Number Upload Setting 1 Upload Setting 13 Download Setting 1 Download Setting 13 Copy *3 SP Slope *3 SP Offset *3 Parameters The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top parameter in that level. Some parameters may not be displayed depending on the model and other settings.

PV/SP No. 1 Display

Selection PV/SP No. 2 Display Selection Integral/Derivative Time Unit Integrated Alarm Assignment Remote SP Input Remote SP Enable Remote SP Upper Limit Remote SP Lower Limit Moving Average Count Manual Output Method Manual MV Initial Value Heating/Cooling Tuning Method Minimum Output ON/OFF Band SP Tracking Display Brightness Event Input Assignment 5 (E5EC/E5AC only) Control Output 1 Signal Control Output 2 Signal Transfer Output Signal Event Input Assignment 6 (E5EC/E5AC only) RT Monitor/Setting Item Level Monitor/Setting Item Display 1 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). Monitor/Setting Item Display 2 Monitor/Setting Item Display 3 Monitor/Setting Item Display 4 Monitor/Setting Item Display 5 Press the O Key for at least 1 s. Advanced Function Setting Level Alarm 2 Type Alarm 3 Type Alarm 2 Hysteresis Alarm 3 Hysteresis Transfer Output Type Linear output Transfer Output Upper Limit Transfer Output Lower Limit Event Input Assignment 1 Event Input Assignment 2 Extraction of Square Root Enable Move to Advanced Function Setting Level: Displayed when initial setting/communications protect is set to 0. Move by setting password (−169). Parameter Initialization Number of Multi-SP Points SP Ramp Time Unit Standby Sequence Reset Auxiliary Output 1 Open in Alarm Auxiliary Output 2 Open in Alarm Auxiliary Output 3 Open in Alarm HB ON/OFF Heater Burnout Latch Heater Burnout Hysteresis ST Stable Range AT Calculated Gain α AT Hysteresis Limit Cycle MV Amplitude Input Digital Filter MV Display Automatic Display Return Time Alarm 1 Latch Alarm 2 Latch Alarm 3 Latch Move to Protect Level Time Cold Junction Compensation Method Alarm 1 ON Delay Alarm 2 ON Delay Alarm 3 ON Delay Alarm 1 OFF Delay Alarm 2 OFF Delay Alarm 3 OFF Delay MV at Stop and Error Addition Auto/Manual Select Addition HS Alarm Use HS Alarm Latch HS Alarm Hysteresis LBA Detection Time LBA Level LBA Band Control Output 1 Assignment Control Output 2 Assignment Auxiliary Output 4 Assignment (E5EC/E5AC only) Soak Time Unit Alarm SP Selection Manual MV Limit Enable PV Rate of Change Calculation Period LCT Cooling Output Minimum ON Time (E5DC only) PF Setting Monitor/Setting Item 1 Monitor/Setting Item 2 Monitor/Setting Item 3 Monitor/Setting Item 4 Monitor/Setting Item 5 MV Display Selection PV Decimal Point Display PV Status Display Function SV Status Display Function Display Refresh Period Auxiliary Output 4 Open in Alarm (E5EC/E5AC only) Alarm 4 Latch Alarm 4 ON Delay Alarm 4 OFF Delay Auxiliary Output 1 Assignment Auxiliary Output 2 Assignment Auxiliary Output 3 Assignment Alarm 4 Type Alarm 4 Hysteresis Event Input Assignment 3 Event Input Assignment 4 Motor Calibration Close/Floating Travel Time PV Dead Band Direct Setting of Position Proportional MV M cmov 0 Move to Calibration Level

● Be sure to read the precautions for all E5CC/E5EC/E5AC/E5DC models in the website at:

http://www.ia.omron.com/. Warning Indications Meaning of Product Safety Symbols Do not touch the terminals while power is being supplied. Doing so may occasionally result in minor injury due to electric shock. Electric shock may occur. Do not touch any cables or connectors with wet hands. Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors, cuttings from installation work, or moisture to enter the Digital Temperature Controller or the Setup Tool port or ports. Attach the cover to the front-panel Setup Tool port whenever you are not using it to prevent foreign objects from entering the port. Do not use the Digital Temperature Controller where subject to flammable or explosive gas. Otherwise, minor injury from explosion may occasionally occur. Not doing so may occasionally result in fire. Do not allow dirt or other foreign objects to enter the Setup Tool port or ports, or between the pins on the connectors on the Setup Tool cable. Minor electric shock or fire may occasionally occur. Do not use any cables that are damaged. Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric shock, fire, or malfunction may occasionally occur. CAUTION - Risk of Fire and Electric Shock a. This product is UL listed*1 as Open Type Process Control Equipment. It must be mounted in an enclosure that does not allow fire to escape externally. b. More than one disconnect switch may be required to de- energize the equipment before servicing the product. c. Signal inputs are SELV, limited energy. *2 d. Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits. *3 If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always consider the application conditions and use the output relays within their rated load and electrical life expectancy. The life expectancy of output relays varies considerably with the output load and switching conditions. Even if you replace only the Main Unit of the E5DC, check the condition of the Terminal Unit. If corroded terminals are used, contact failure in the terminals may cause the temperature inside the Digital Controller to increase, possibly resulting in fire. If the terminals are corroded, replace the Terminal Unit as well. Tighten the terminal screws to the rated torque of between 0.43 and 0.58 N•m. *4 Loose screws may occasionally result in fire. Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may occasionally result in property damage or accidents. A malfunction in the product may occasionally make control operations impossible or prevent alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the product, take appropriate safety measures, such as installing a monitoring device on a separate line. *1. E5CC, E5EC, E5AC, and E5DC Controllers that were shipped through November 2013 are UL recognized. *2. An SELV (separated extra-low voltage) system is one with a power supply that has double or reinforced insulation between the primary and the secondary circuits and has an output voltage of 30 V r.m.s. max. and 42.4 V peak max. or 60 VDC max. *3. A class 2 circuit is one tested and certified by UL as having the current and voltage of the secondary output restricted to specific levels. *4. The specified torque is 0.5 N·m for the E5CC-U. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or in property damage. Precautions for Safe Use Supplementary comments on what to do or avoid doing, to use the product safely. Precautions for Correct Use Supplementary comments on what to do or avoid doing, to prevent failure to operate, malfunction or undesirable effect on product performance. Used to warn of the risk of electric shock under specific conditions. Used for general prohibitions for which there is no specific symbol. Used to indicate prohibition when there is a risk of minor injury from electrical shock or other source if the product is disassembled. Used for general CAUTION, WARNING, or DANGER precautions for which there is no specified symbol. (This symbol is also used as the alerting symbol, but shall not be used in this meaning on the product.) Used for general mandatory action precautions for which there is no specified symbol. CAUTION

Be sure to observe the following precautions to prevent malfunction

or adverse affects on the performance or functionality of the product. Not doing so may occasionally result in faulty operation. 1. This product is specifically designed for indoor use only. Do not use this product in the following places: • Places directly subject to heat radiated from heating equipment. • Places subject to splashing liquid or oil atmosphere. • Places subject to direct sunlight. • Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas). • Places subject to intense temperature change. • Places subject to icing and condensation. • Places subject to vibration and large shocks. 2. Use and store the product within the rated ambient temperature and humidity. Gang-mounting two or more Digital Temperature Controllers, or mounting Digital Temperature Controllers above each other may cause heat to build up inside the Digital Temperature Controllers, which will shorten their service life. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Digital Temperature Controllers. 3. To allow heat to escape, do not block the area around the Digital Temperature Controller. Do not block the ventilation holes on the Digital Temperature Controller. 4. Be sure to wire properly with correct polarity of terminals. 5. Use the specified size of crimped terminals (M3, width of 5.8 mm or less) to wire the E5CC, E5EC, E5AC, or E5DC. To connect bare wires to the terminal block of the E5CC, E5EC, E5AC, or E5DC, use copper braided or solid wires with a gage of AWG24 to AWG18 (equal to a cross-sectional area of 0.205 to 0.8231 mm2). (The stripping length is 6 to 8 mm.) Up to two wires of the same size and type, or two crimped terminals can be inserted into a single terminal. Use the specified size of crimped terminals (M3.5, width of 7.2 mm or less) to wire the E5CC-U. To connect bare wires to the terminal block of the E5CC-U, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to a cross-sectional area of 0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.) Up to two wires of the same size and type, or two crimped terminals can be inserted into a single terminal. 6. Do not wire the terminals that are not used. 7. Use a commercial power supply for the power supply voltage input to a Digital Temperature Controller with AC input specifications. Do not use the output from an inverter as the power supply. Depending on the output characteristics of the inverter, temperature increases in the Digital Temperature Controller may cause smoke or fire damage even if the inverter has a specified output frequency of 50/60 Hz. 8. To avoid inductive noise, keep the wiring for the product’s terminal block away from power cables carry high voltages or large currents. Also, do not wire power lines together with or parallel to product wiring. Using shielded cables and using separate conduits or ducts is recommended. Attach a surge suppressor or noise filter to peripheral devices that generate noise (in particular, motors, transformers, solenoids, magnetic coils, or other equipment that have an inductance component). When a noise filter is used at the power supply, first check the voltage or current, and attach the noise filter as close as possible to the product. Allow as much space as possible between the product and devices that generate powerful high frequencies (high-frequency welders, high-frequency sewing machines, etc.) or surge. 9. Use this product within the rated load and power supply. 10.Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur. 11.Make sure that the Digital Temperature Controller has 30 minutes or more to warm up after turning ON the power before starting actual control operations to ensure the correct temperature display. 12.When executing self-tuning with E5@C, turn ON power to the load (e.g., heater) at the same time as or before supplying power to the product. If power is turned ON to the product before turning ON power to the load, self-tuning will not be performed properly and optimum control will not be achieved. 13.A switch or circuit breaker must be provided close to the product. The switch or circuit breaker must be within easy reach of the operator, and must be marked as a disconnecting means for this unit. 14.Use a soft and dry cloth to clean the product carefully. Do not use organic solvent, such as paint thinner, benzine or alcohol to clean the product. 15.Design the system (e.g., control panel) considering the 2 seconds of delay that the product's output to be set after power ON. 16.The output may turn OFF when you move to the initial setting level. Take this into consideration when performing control operations. 17.The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when frequently overwriting data during communications or other operations. 18.Use suitable tools when taking the Digital Temperature Temperature Controller apart for disposal. Sharp parts inside the Digital Temperature Controller may cause injury. 19.For compliance with Lloyd’s standards, the E5CC, E5CC-U, E5EC, and E5AC must be installed under the conditions that are specified in Shipping Standards. 20.Do not connect cables to both the front Setup Tool port and the top-panel or bottom-panel Setup Tool port at the same time. The Digital Controller may be damaged or may malfunction. 21.Do not place heavy object on the Conversion Cable, bend the cable past its natural bending radius, or pull on the cable with undue force. 22.Do not disconnect the Communications Conversion Cable or the USB-Serial Conversion Cable while communications are in progress. Damage or malfunction may occur. 23.Do not touch the external power supply terminals or other metal parts on the Digital Temperature Controller. 24.Refer to the E5@C Digital Temperature Controllers User’s Manual (Cat. No. H174) for information on the communications distances and cables for the E5@C. 25.Do not bend the communications cables past their natural bending radius. Do not pull on the communications cables. 26.Do not turn the power supply to the Digital Temperature Controller ON or OFF while the USB-Serial Conversion Cable is connected. The Digital Temperature Controller may malfunction. 27.Make sure that the indicators on the USB-Serial Conversion Cable are operating properly. Depending on the application conditions, deterioration in the connectors and cable may be accelerated, and normal communications may become impossible. Perform periodic inspection and replacement. 28.Connectors may be damaged if they are inserted with excessive force. When connecting a connector, always make sure that it is oriented correctly. Do not force the connector if it does not connect smoothly. 29.Noise may enter on the USB-Serial Conversion Cable, possibly causing equipment malfunctions. Do not leave the USB-Serial Conversion Cable connected constantly to the equipment. 30.For the E5DC, when you attach the Main Unit to the Terminal Unit, make sure that the hooks on the Main Unit are securely inserted into the Terminal Unit. 31.For the E5CC-U, when you attach the Main Unit to the socket, make sure that the hooks on the socket are securely inserted into the Main Unit. 32.Install the DIN Track vertically to the ground. 33.For the E5DC, always turn OFF the power supply before connecting the Main Unit to or disconnecting the Main Unit from the Terminal Unit, and never touch nor apply shock to the terminals or electronic components. When connecting or disconnecting the Main Unit, do not allow the electronic components to touch the case. Precautions for Safe Use

The E5CC, E5CC-U, E5EC, and E5AC comply with Lloyd's

standards. When applying the standards, the following installation requirements must be met in the application. Application Conditions ● Installation Location The E5CC, E5CC-U, E5EC, and E5AC comply with installation category ENV1 and ENV2 of Lloyd's standards. Therefore, they must be installed in a location equipped with air conditioning. They cannot be used on the bridge or decks, or in a location subject to strong vibration. ● Service Life 1. Use the product within the following temperature and humidity ranges: Temperature: -10 to 55°C (with no icing or condensation) Humidity: 25% to 85% If the product is installed inside a control board, the ambient temperature must be kept to under 55°C, including the temperature around the product. 2. The service life of electronic devices like Digital Temperature Controllers is determined not only by the number of times the relay is switched but also by the service life of internal electronic components. Component service life is affected by the ambient temperature: the higher the temperature, the shorter the service life and, the lower the temperature, the longer the service life. Therefore, the service life can be extended by lowering the temperature of the Digital Temperature Controller. 3. When two or more Digital Temperature Controllers are mounted horizontally close to each other or vertically next to one another, the internal temperature will increase due to heat radiated by the Digital Temperature Controllers and the service life will decrease. In such a case, use forced cooling by fans or other means of air ventilation to cool down the Digital Temperature Controllers. When providing forced cooling, however, be careful not to cool down the terminals sections alone to avoid measurement errors. ● Measurement Accuracy 1. When extending or connecting the thermocouple lead wire, be sure to use compensating wires that match the thermocouple types. 2. When extending or connecting the lead wire of the platinum resistance thermometer, be sure to use wires that have low resistance and keep the resistance of the three lead wires the same. 3. Mount the product so that it is horizontally level. 4. If the measurement accuracy is low, check to see if input shift has been set correctly. ● Waterproofing (Not applicable to the E5CC-U/ E5DC.) The degree of protection is as shown below. Sections without any specification on their degree of protection or those with IP@0 are not waterproof. Front panel: IP66, Rear case: IP20, Terminal section: IP00 When waterproofing is required, insert the Waterproof Packing on the backside of the front panel. Keep the Port Cover on the front-panel Setup Tool port of the E5EC/E5AC securely closed. The degree of protection when the Waterproof Packing is used is IP66. To maintain an IP66 degree of protection, the Waterproof Packing and the Port Cover for the front-panel Setup Tool port must be periodically replaced because they may deteriorate, shrink, or harden depending on the operating environment. The replacement period will vary with the operating environment. Check the required period in the actual application. Use 3 years or sooner as a guideline. If the Waterproof Packing and Port Cover are not periodically replaced, waterproof performance may not be maintained. If a waterproof structure is not required, then the Waterproof Packing does not need to be installed. ● Operating Precautions 1. When using self-tuning, turn ON power for the load (e.g., heater) at the same time as or before supplying power to the Digital Controller. If power is turned ON for the Digital Controller before turning ON power for the load, self-tuning will not be performed properly and optimum control will not be achieved. When starting operation after the Digital Temperature Controller has warmed up, turn OFF the power and then turn it ON again at the same time as turning ON power for the load. (Instead of turning the Digital Temperature Controller OFF and ON again, switching from STOP mode to RUN mode can also be used.) 2. Avoid using the Controller in places near a radio, television set, or wireless installing. These devices can cause radio disturbances which adversely affect the performance of the Controller. ● Others 1. Do not Connect or disconnect the Conversion Cable connector repeatedly over a short period of time. The computer may malfunction. 2. After connecting the Conversion Cable to the computer, check the COM port number before starting communications. The computer requires time to recognize the cable connection. This delay does not indicate failure. 3. Do not connect the Conversion Cable through a USB hub. Doing so may damage the Conversion Cable. 4. Do not use an extension cable to extend the Conversion Cable length when connecting to the computer. Doing so may damage the Conversion Cable. ● Mounting Mounting to a Panel E5CC There are two models of Terminal Covers that you can use with the E5CC. E5CC-U For the Wiring Socket for the E5CC-U, purchase the P2CF-11 or PG3A-11 separately. 1. For waterproof mounting, waterproof packing must be installed on the Controller. Waterproofing is not possible when group mounting several Controllers. Waterproof packing is not necessary when there is no need for the waterproofing function. The E5CC-U cannot be waterproofed even if the Waterproof Packing is inserted. 2. Insert the E5CC/E5CC-U into the mounting hole in the panel. 3. Push the adapter from the terminals up to the panel, and temporarily fasten the E5CC. 4. Tighten the two fastening screws on the adapter. Alternately tighten the two screws little by little to maintain a balance. Tighten the screws to a torque of 0.29 to 0.39 N·m. Shipping Standards Precautions for Correct Use Panel Water Proof Packing Terminal Cover (E53-COV17) (Sold separately) Adapter Terminal Cover (E53-COV23)

● Precautions when Wiring

• Separate input leads and power lines in order to prevent external noise. • Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205 to 0.8231 mm2) twisted-pair cable. Use a shielded, AWG24 to AWG14 (cross-sectional area of 0.205 to 2.081 mm2) twisted-pair cable for the E5CC-U. The stripping length is 6 to 8 mm for the E5CC, E5EC, E5AC, or E5DC and 5 to 6 mm for the E5CC-U. • Use crimp terminals when wiring the terminals. • Use the suitable wiring material and crimp tools for crimp terminals. • Tighten the terminal screws to a torque of 0.43 to 0.58 N·m. The specified torque is 0.5 N·m for the E5CC-U. • For the E5CC, E5EC, E5AC, or E5DC, use the following types of crimp terminals for M3 screws. • For the E5CC-U, use the following types of crimp terminals for M3.5 screws. Three-year Guarantee ● Period of Guarantee The guarantee period of the Unit is three years starting from the date the Unit is shipped from the factory. Scope of Guarantee The Unit is guaranteed under the following operating conditions. 1. Average Operating Temperature (see note): −10°C to 50°C 2. Mounting Method: Standard mounting Note: Average Operating Temperature Refer to the process temperature of the Unit mounted to a control panel and connected to peripheral devices on condition that the Unit is in stable operation, sensor input type K is selected for the Unit, the positive and negative thermocouple input terminals of the Unit are short-circuited, and the ambient temperature is stable. Should the Unit malfunction during the guarantee period, OMRON shall repair the Unit or replace any parts of the Unit at the expense of OMRON. 5.8 mm max. 5.8 mm max. 7.2 mm max. 7.2 mm max. Top Bottom

Terms and Conditions of Sale

1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed part of all quotes, agreements, purchase orders, acknowledgments, price lists, catalogs, manuals, brochures and other documents, whether electronic or in writing, relating to the sale of products or services (collectively, the "Products") by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron objects to any terms or conditions proposed in Buyer’s purchase order or other documents which are inconsistent with, or in addition to, these Terms. 2. Prices; Payment Terms. All prices stated are current, subject to change with- out notice by Omron. Omron reserves the right to increase or decrease prices on any unshipped portions of outstanding orders. Payments for Products are due net 30 days unless otherwise stated in the invoice. 3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices sent to Buyer after deducting transportation charges, taxes and duties, and will be allowed only if (i) the invoice is paid according to Omron’s payment terms and (ii) Buyer has no past due amounts. 4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or the maximum legal rate, whichever is less, on any balance not paid within the stated terms. 5. Orders. Omron will accept no order less than $200 net billing. 6. Governmental Approvals. Buyer shall be responsible for, and shall bear all costs involved in, obtaining any government approvals required for the impor- tation or sale of the Products. 7. Taxes. All taxes, duties and other governmental charges (other than general real property and income taxes), including any interest or penalties thereon, imposed directly or indirectly on Omron or required to be collected directly or indirectly by Omron for the manufacture, production, sale, delivery, importa- tion, consumption or use of the Products sold hereunder (including customs duties and sales, excise, use, turnover and license taxes) shall be charged to and remitted by Buyer to Omron. 8. Financial. If the financial position of Buyer at any time becomes unsatisfactory to Omron, Omron reserves the right to stop shipments or require satisfactory security or payment in advance. If Buyer fails to make payment or otherwise comply with these Terms or any related agreement, Omron may (without liabil- ity and in addition to other remedies) cancel any unshipped portion of Prod- ucts sold hereunder and stop any Products in transit until Buyer pays all amounts, including amounts payable hereunder, whether or not then due, which are owing to it by Buyer. Buyer shall in any event remain liable for all unpaid accounts. 9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses. 10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority. 11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron: a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship except in “break down” situations. b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall constitute delivery to Buyer; c. All sales and shipments of Products shall be FOB shipping point (unless oth- erwise stated in writing by Omron), at which point title and risk of loss shall pass from Omron to Buyer; provided that Omron shall retain a security inter- est in the Products until the full purchase price is paid; d. Delivery and shipping dates are estimates only; and e.Omron will package Products as it deems proper for protection against nor- mal handling and extra charges apply to special conditions. 12. Claims. Any claim by Buyer against Omron for shortage or damage to the Products occurring before delivery to the carrier must be presented in writing to Omron within 30 days of receipt of shipment and include the original trans- portation bill signed by the carrier noting that the carrier received the Products from Omron in the condition claimed. 13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied. (b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL- ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or oth- erwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obli- gation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsi- ble for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were prop- erly handled, stored, installed and maintained and not subject to contamina- tion, abuse, misuse or inappropriate modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Compa- nies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environ- ments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty. See http://www.omron247.com or contact your Omron representative for pub- lished information. 14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted. 15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and their employees from and against all liabilities, losses, claims, costs and expenses (including attorney's fees and expenses) related to any claim, inves- tigation, litigation or proceeding (whether or not Omron is a party) which arises or is alleged to arise from Buyer's acts or omissions under these Terms or in any way with respect to the Products. Without limiting the foregoing, Buyer (at its own expense) shall indemnify and hold harmless Omron and defend or set- tle any action brought against such Companies to the extent based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party. 16. Property; Confidentiality. Any intellectual property in the Products is the exclu- sive property of Omron Companies and Buyer shall not attempt to duplicate it in any way without the written permission of Omron. Notwithstanding any charges to Buyer for engineering or tooling, all engineering and tooling shall remain the exclusive property of Omron. All information and materials supplied by Omron to Buyer relating to the Products are confidential and proprietary, and Buyer shall limit distribution thereof to its trusted employees and strictly prevent disclosure to any third party. 17. Export Controls. Buyer shall comply with all applicable laws, regulations and licenses regarding (i) export of products or information; (iii) sale of products to “forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of regulated technology or information. 18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right and no course of dealing between Buyer and Omron shall operate as a waiver of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder without Omron's written consent. (c) Law. These Terms are governed by the law of the jurisdiction of the home office of the Omron company from which Buyer is purchasing the Products (without regard to conflict of law princi- ples). (d) Amendment. These Terms constitute the entire agreement between Buyer and Omron relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. (e) Severability. If any provi- sion hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. (f) Setoff. Buyer shall have no right to set off any amounts against the amount owing in respect of this invoice. (g) Definitions. As used herein, “including” means “including without limitation”; and “Omron Compa- nies” (or similar words) mean Omron Corporation and any direct or indirect subsidiary or affiliate thereof. Certain Precautions on Specifications and Use 1. Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Prod- uct in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases but the following is a non-exhaustive list of applications for which particular attention must be given: (i) Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document. (ii) Use in consumer products or any use in significant quantities. (iii) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equip- ment, and installations subject to separate industry or government regulations. (iv) Systems, machines and equipment that could present a risk to life or prop- erty. Please know and observe all prohibitions of use applicable to this Prod- uct. NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP- ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. 2. Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof. 3. Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitabil- ity and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application require- ments. Actual performance is subject to the Omron’s Warranty and Limitations of Liability. 4. Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our prac- tice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifica- tions of the Product may be changed without any notice. When in doubt, spe- cial part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product. 5. Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.

OMRON CANADA, INC. • HEAD OFFICE

Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com OMRON ELECTRONICS DE MEXICO • HEAD OFFICE México DF • 52.55.59.01.43.00 • 01-800-226-6766 • [email protected] OMRON ELECTRONICS DE MEXICO • SALES OFFICE Apodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • [email protected] OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br OMRON ARGENTINA • SALES OFFICE Cono Sur • 54.11.4783.5300 OMRON CHILE • SALES OFFICE Santiago • 56.9.9917.3920 OTHER OMRON LATIN AMERICA SALES 54.11.4783.5300 Authorized Distributor: Cat. No. H04I-E-01 01/14 Note: Specifications are subject to change. © 2014 Omron Electronics LLC Printed in U.S.A. Printed on recycled paper. Automation Control Systems • Machine Automation Controllers (MAC) • Programmable Controllers (PLC) • Operator interfaces (HMI) • Distributed I/O • Software Drives & Motion Controls • Servo & AC Drives • Motion Controllers & Encoders Temperature & Process Controllers • Single and Multi-loop Controllers Sensors & Vision • Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors • Amplified Photomicrosensors • Measurement Sensors • Ultrasonic Sensors • Vision Sensors Industrial Components • RFID/Code Readers • Relays • Pushbuttons & Indicators • Limit and Basic Switches • Timers • Counters • Metering Devices • Power Supplies Safety • Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety Controllers • Light Curtains • Safety Relays • Safety Interlock Switches OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Hoffman Estates, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu