ABB relion REF615 Applications Manual
Read Online
Read the ABB relion REF615 Applications Manual online using the built-in PDF viewer.
Text of the manual
Document ID: 1MRS756378
Issued: 04.03.2009
Revision: D
Product version: 2.0
© Copyright 2009 ABB. All rights reserved
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, Finland
Telephone: +358 10 2211
Facsimile: +358 10 22 41094
http://www.abb.com/substationautomation
The data, examples and diagrams in this manual are included solely for the concept
or product description and are not to be deemed as a statement of guaranteed
properties. All persons responsible for applying the equipment addressed in this
manual must satisfy themselves that each intended application is suitable and
acceptable, including that any applicable safety or other operational requirements are
complied with. In particular, any risks in applications where a system failure and/or
product failure would create a risk for harm to property or persons (including but not
limited to personal injuries or death) shall be the sole responsibility of the person or
entity applying the equipment, and those so responsible are hereby requested to ensure
that all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested
to notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the
use of this manual or the application of the equipment.
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Council Directive 2004/108/EC) and concerning electrical
equipment for use within specified voltage limits (Low-voltage directive 2006/95/
EC). This conformity is the result of a test conducted by ABB in accordance with
Article 10 of the directive in agreement with the product standards EN 50263 and EN
60255-26 for the EMC directive, and with the product standards EN 60255-6 and EN
60255-27 for the low voltage directive. The IED is designed in accordance with the
international standards of the IEC 60255 series.
Table of contents
Section 1
Introduction.......................................................................7
This manual........................................................................................7
Intended audience..............................................................................7
Product documentation.......................................................................8
Product documentation set............................................................8
Document revision history.............................................................9
Related documentation................................................................10
Document symbols and conventions................................................10
Safety indication symbols............................................................10
Document conventions................................................................11
Functions, codes and symbols....................................................11
Section 2
REF615 overview...........................................................15
Overview...........................................................................................15
Product version history................................................................16
PCM600 and IED connectivity package version..........................16
Operation functionality......................................................................16
Standard configurations...............................................................16
Optional functions........................................................................18
Physical hardware............................................................................19
LHMI.................................................................................................21
LCD.............................................................................................21
LEDs............................................................................................22
Keypad........................................................................................22
WHMI................................................................................................23
Authorization.....................................................................................24
Communication.................................................................................25
Section 3
REF615 variants.............................................................27
REF615 variant list...........................................................................27
Presentation of standard configurations...........................................27
Standard configurations...............................................................28
Connection diagrams...................................................................31
Standard configuration A including directional earth-fault
protection..........................................................................................34
Applications.................................................................................34
Functions.....................................................................................35
Default I/O connections..........................................................36
Functional diagrams....................................................................36
Functional diagrams for protection.........................................37
Table of contents
REF615
1
Application Manual
Functional diagrams for disturbance recorder and trip
circuit supervision...................................................................42
Functional diagrams for control and interlocking....................43
Standard configuration B including directional earth-fault
protection and CB condition monitoring............................................45
Applications.................................................................................45
Functions.....................................................................................45
Default I/O connections..........................................................46
Functional diagrams....................................................................47
Functional diagrams for protection.........................................47
Functional diagram for disturbance recorder and trip
circuit supervision...................................................................53
Functional diagrams for control and interlocking....................54
Standard configuration C including non-directional earth-fault
protection..........................................................................................58
Applications.................................................................................58
Functions.....................................................................................58
Default I/O connections..........................................................59
Functional diagrams....................................................................60
Functional diagrams for protection.........................................60
Functional diagram for disturbance recorder and trip
circuit supervision...................................................................65
Functional diagrams for control and interlocking....................66
Standard configuration D including non-directional earth-fault
protection and CB condition monitoring............................................68
Applications.................................................................................68
Functions.....................................................................................68
Default I/O connections..........................................................69
Functional diagrams....................................................................70
Functional diagrams for protection.........................................70
Functional diagram for disturbance recorder and trip
circuit supervision...................................................................75
Functional diagrams for control and interlocking....................76
Standard configuration E including directional earth-fault
protection with phase-voltage measurement....................................80
Applications.................................................................................80
Functions.....................................................................................80
Default I/O connections..........................................................81
Functional diagrams....................................................................82
Functional diagrams for protection.........................................82
Functional diagram for disturbance recorder and trip
circuit supervision...................................................................88
Functional diagrams for control and interlocking....................89
Standard configuration F including directional overcurrent
protection with voltage protection.....................................................93
Table of contents
2
REF615
Application Manual
Default I/O connections..........................................................95
Functional diagrams....................................................................96
Functional diagrams for protection.........................................96
Functional diagram for disturbance recorder and trip
circuit supervision.................................................................102
Functional diagrams for control and interlocking..................104
Section 4
Basic functions.............................................................111
General parameters........................................................................111
Self-supervision..............................................................................126
Internal faults.............................................................................127
Warnings...................................................................................128
Time synchronization......................................................................129
Parameter setting groups...............................................................130
Section 5
Protection functions......................................................133
Three-phase current protection......................................................133
Three-phase non-directional overcurrent protection
PHxPTOC..................................................................................133
Identification.........................................................................133
Functionality.........................................................................133
Application............................................................................133
Three-phase directional overcurrent protection
DPHxPDOC...............................................................................140
Identification.........................................................................140
Functionality.........................................................................140
Application............................................................................140
Three-phase thermal overload protection for overhead lines
and cables T1PTTR...................................................................143
Identification.........................................................................143
Functionality.........................................................................143
Application............................................................................144
Earth-fault protection......................................................................145
Non-directional earth-fault protection EFxPTOC.......................145
Identification.........................................................................145
Functionality.........................................................................145
Application............................................................................145
Directional earth-fault protection DEFxPDEF............................146
Identification.........................................................................146
Functionality.........................................................................146
Directional earth-fault principles...........................................146
Application............................................................................152
Table of contents
REF615
3
Application Manual
Transient/intermittent earth-fault protection INTRPTEF............154
Identification.........................................................................154
Functionality.........................................................................155
Application............................................................................155
Unbalance protection......................................................................158
Negative phase-sequence current protection NSPTOC............158
Identification.........................................................................158
Functionality.........................................................................159
Application............................................................................159
Phase discontinuity PDNSPTOC...............................................159
Identification.........................................................................159
Functionality.........................................................................160
Application............................................................................160
Arc protection ARCSARC...............................................................162
Identification..............................................................................162
Functionality..............................................................................162
Application.................................................................................162
Voltage protection...........................................................................166
Overvoltage protection PHPTOV...............................................166
Identification.........................................................................166
Functionality.........................................................................167
Application............................................................................167
Undervoltage protection PHPTUV.............................................167
Identification.........................................................................167
Functionality.........................................................................168
Application............................................................................168
Residual overvoltage protection ROVPTOV..............................169
Identification.........................................................................169
Functionality.........................................................................169
Application............................................................................169
Negative sequence overvoltage protection NSPTOV................170
Identification.........................................................................170
Functionality.........................................................................170
Application............................................................................170
Positive sequence undervoltage protection PSPTUV...............171
Identification.........................................................................171
Functionality.........................................................................171
Application............................................................................171
Section 6
Protection related functions..........................................181
Three-phase inrush detector INRPHAR.........................................181
Identification..............................................................................181
Functionality..............................................................................181
Application.................................................................................181
Table of contents
4
REF615
Application Manual
Circuit breaker failure protection CCBRBRF..................................182
Identification..............................................................................182
Functionality..............................................................................182
Application.................................................................................183
Protection trip conditioning TRPPTRC...........................................184
Identification..............................................................................184
Functionality..............................................................................184
Application.................................................................................185
Section 7
Supervision functions...................................................187
Trip circuit supervision TCSSCBR..................................................187
Identification..............................................................................187
Functionality..............................................................................187
Application.................................................................................187
Current circuit supervision CCRDIF...............................................194
Identification..............................................................................194
Functionality..............................................................................194
Application.................................................................................195
Fuse failure supervision SEQRFUF...............................................199
Identification..............................................................................199
Functionality..............................................................................199
Application.................................................................................200
Section 8
Condition monitoring functions.....................................201
Circuit breaker condition monitoring SSCBR..................................201
Identification..............................................................................201
Functionality..............................................................................201
Application.................................................................................201
Section 9
Measurement functions................................................205
Basic measurements......................................................................205
Three-phase current CMMXU...................................................205
Identification.........................................................................205
Three-phase voltage VMMXU...................................................205
Identification.........................................................................205
Neutral current RESCMMXU.....................................................205
Identification.........................................................................205
Residual voltage RESVMMXU..................................................205
Identification.........................................................................205
Sequence current CSMSQI.......................................................206
Identification.........................................................................206
Phase sequence voltage VSMSQI............................................206
Identification.........................................................................206
Three-phase power and energy PEMMXU................................206
Table of contents
REF615
5
Application Manual
Measurement function applications...........................................207
Disturbance recorder......................................................................208
Functionality..............................................................................208
Application.................................................................................208
Section 10 Control functions..........................................................211
Circuit breaker control CBXCBR....................................................211
Identification..............................................................................211
Functionality..............................................................................211
Application.................................................................................211
Disconnector DCSXSWI and earthing switch ESSXSWI...............212
Identification..............................................................................212
Functionality..............................................................................212
Application.................................................................................213
Interaction between control modules..............................................213
Auto recloser DARREC..................................................................214
Identification..............................................................................214
Functionality..............................................................................214
Application.................................................................................214
Shot initiation........................................................................215
Sequence.............................................................................217
Configuration examples........................................................218
Delayed initiation lines..........................................................221
Shot initiation from protection start signal............................223
Fast trip in Switch on to fault................................................223
Section 11 Requirements for measurement transformers..............225
Current transformers......................................................................225
Current transformer requirements for non-directional
overcurrent protection................................................................225
Current transformer accuracy class and accuracy limit
factor....................................................................................225
Non-directional overcurrent protection.................................226
Example for non-directional overcurrent protection..............227
Section 12 Glossary.......................................................................229
Table of contents
6
REF615
Application Manual
Application Manual contains application descriptions and setting guidelines sorted
per function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating
settings.
1.2
Intended audience
This manual addresses the protection and control engineer responsible for planning,
pre-engineering and engineering.
The protection and control engineer must be experienced in electrical power
engineering and have knowledge of related technology, such as communication and
protocols.
1MRS756378 D
Section 1
Introduction
REF615
7
Application Manual
Product documentation set
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Application manual
Operation manual
Installation manual
Service manual
Engineering manual
Commissioning manual
Communication protocol
manual
Technical manual
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
deinstalling & disposal
Application manual
Application manual
Operation manual
Operation manual
Installation manual
Installation manual
Service manual
Service manual
Engineering manual
Engineering manual
Commissioning manual
Commissioning manual
Communication protocol
manual
Communication protocol
manual
Technical manual
Technical manual
en07000220.vsd
IEC07000220 V1 EN
Engineering Manual contains instructions on how to engineer the IEDs. The manual
provides instructions on how to use the different tools for IED engineering. It also
includes instructions on how to handle the tool component available to read
disturbance files from the IEDs on the basis of the IEC 61850 definitions. It further
introduces the diagnostic tool components available for IEDs and the PCM600 tool.
Installation Manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in chronological order in which the IED should be installed.
Commissioning Manual contains instructions on how to commission the IED. The
manual can also be used as a reference during periodic testing. The manual provides
procedures for energizing and checking of external circuitry, setting and
configuration as well as verifying settings and performing directional tests. The
chapters are organized in chronological order in which the IED should be
commissioned.
Section 1
1MRS756378 D
Introduction
8
REF615
Application Manual
Operation Manual contains instructions on how to operate the IED during normal
service once it has been commissioned. The manual can be used to find out how to
handle disturbances or how to view calculated and measured network data to
determine the cause of a fault.
Service Manual contains instructions on how to service and maintain the IED. The
manual also provides procedures for de-energizing, de-commissioning and disposal
of the IED.
Application Manual contains application descriptions and setting guidelines sorted
per function. The manual can be used to find out when and for what purpose a typical
protection function can be used. The manual can also be used when calculating
settings.
Technical Manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
Communication Protocol Manual describes a communication protocol supported by
the IED. The manual concentrates on vendor-specific implementations.
Point List Manual describes the outlook and properties of the data points specific to
the IED. The manual should be used in conjunction with the corresponding
Communication Protocol Manual.
All manuals are not available yet.
1.3.2
Document revision history
Document revision/date
Product version
History
A/20.12.2007
1.0
First release
B/08.02.2008
1.0
Content updated
C/02.07.2008
1.1
Content updated to correspond
to the product version
D/04.03.2009
2.0
Content updated to correspond
to the product version
Download the latest revision of the document from the ABB web site
http://www.abb.com/substationautomation.
1MRS756378 D
Section 1
Introduction
REF615
9
Application Manual
Name of the document
Document ID
Modbus Communication Protocol Manual
1MRS756468
DNP 3.0 Communication Protocol Manual
1MRS756709
IEC 60870-5-103 Communication Protocol
Manual
1MRS756710
Installation Manual
1MRS756375
Operation Manual
1MRS756708
Technical Manual
1MRS756377
1.4
Document symbols and conventions
1.4.1
Safety indication symbols
This publication includes icons that point out safety-related conditions or other
important information.
The electrical warning icon indicates the presence of a hazard which
could result in electrical shock.
The warning icon indicates the presence of a hazard which could
result in personal injury.
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence of
a hazard which could result in corruption of software or damage to
equipment or property.
The information icon alerts the reader to relevant facts and conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
Section 1
1MRS756378 D
Introduction
10
REF615
Application Manual
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all warning and caution notices.
1.4.2
Document conventions
•
Abbreviations and acronyms in this manual are spelled out in Glossary. Glossary
also contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the
push button icons, for example:
To navigate between the options, use
and
.
•
HMI menu paths are presented in bold, for example:
Select Main menu/Configuration/HMI.
•
Menu names are shown in bold in WHMI, for example:
Click Information in the WHMI menu structure.
•
LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press
.
•
Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
•
Parameter values are indicated with quotation marks, for example:
The corresponding parameter values are "On" and "Off".
•
IED input/output messages and monitored data names are shown in Courier font,
for example:
When the function starts, the START output is set to TRUE.
1.4.3
Functions, codes and symbols
All available functions are listed in the table. All of these may not be applicable to
all products.
Table 1:
Functions included in standard configurations
Function
IEC 61850
IEC 60617
IEC-ANSI
Three-phase non-directional
overcurrent protection
PHLPTOC1
3I>
51P-1
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
PHIPTOC1
3I>>>
50P/51P
Three-phase directional overcurrent,
low stage
DPHLPDOC1
3I> → (1)
67-1 (1)
DPHLPDOC2
3I> → (2)
67-1 (2)
Three-phase directional overcurrent,
high stage
DPHHPDOC1
3I>> →
67-2
Arc protection
ARCSARC1
ARC (1)
50L/50NL (1)
ARCSARC2
ARC (2)
50L/50NL (2)
ARCSARC3
ARC (3)
50L/50NL (3)
Table continues on next page
1MRS756378 D
Section 1
Introduction
REF615
11
Application Manual
Non-directional earth-fault protection
EFLPTOC1
I0> (1)
51N-1 (1)
EFLPTOC2
I0> (2)
51N-1 (2)
EFHPTOC1
I0>>
51N-2
EFIPTOC1
I0>>>
50N/51N
Directional earth-fault protection
DEFLPDEF1
I0> → (1)
67N-1 (1)
DEFLPDEF2
I0> → (2)
67N-1 (2)
DEFHPDEF1
I0>> →
67N-2
Transient/Intermittent earth-fault
protection
INTRPTEF1
I0> → IEF
67NIEF
Non-directional (cross-country) earth
fault, using calculated I0
EFHPTOC1
I0>>
51N-2
Negative-sequence overcurrent
protection
NSPTOC1
I2> (1)
46 (1)
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity
PDNSPTOC1
I2/I1>
46PD
Residual overvoltage protection
ROVPTOV1
U0> (1)
59G (1)
ROVPTOV2
U0> (2)
59G (2)
ROVPTOV3
U0> (3)
59G (3)
Three-phase undervoltage protection
PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
PHPTUV3
3U< (3)
27 (3)
Three-phase overvoltage protection
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
PHPTOV3
3U> (3)
59 (3)
Positive-sequence undervoltage
PSPTUV1
U1<
47U+
Negative-sequence overvoltage
NSPTOV1
U2>
47O-
Three-phase inrush detector
INRPHAR1
3I2f>
68
Three-phase thermal protection for
feeders, cables and distribution
transformers
T1PTTR1
3Ith>F
49F
Autoreclosure
DARREC1
O → I
79
Circuit breaker failure protection
CCBRBRF1
3I>/I0>BF
51BF/51NBF
Master Trip
TRPPTRC1
Master Trip (1)
94/86 (1)
TRPPTRC2
Master Trip (2)
94/86 (2)
Trip circuit supervision
TCSSCBR1
TCS (1)
TCM (1)
TCSSCBR2
TCS (2)
TCM (2)
Fuse failure supervision
SEQRFUF1
FUSEF
60
Disturbance recorder
RDRE1
-
-
Circuit breaker condition monitoring
SSCBR1
CBCM
CBCM
Three-phase current measurement
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Table continues on next page
Section 1
1MRS756378 D
Introduction
12
REF615
Application Manual
Residual current measurement
RESCMMXU1
I0
In
Residual voltage measurement
RESVMMXU1
U0
Vn
Three-phase voltage measurement
VMMXU1
3U
3U
Sequence voltage measurement
VSMSQI1
U1, U2, U0
U1, U2, U0
Three-phase power and energy
measurement
PEMMXU1
P, E
P, E
1MRS756378 D
Section 1
Introduction
REF615
13
Application Manual
REF615 is a native IEC 61850 feeder protection IED for selective short-circuit,
overcurrent and earth-fault protection. It is applicable to all types of radial isolated
neutral networks, resistant earthed networks and compensated networks. REF615 is
part of a product family that will cover many protection applications for utility and
industry customers.
The IED features draw-out-type design, compact size and ease of use. Depending on
the IED variant, the protection functions may include:
•
Three-phase non-directional overcurrent protection, 4 stages
•
Three-phase directional overcurrent, 3 stages
•
Directional earth-fault protection, 3 stages
•
Non-directional (cross-country) earth fault, using calculated I0
•
Non-directional earth fault, 3 stages
•
Transient/intermittent earth-fault protection
•
Non-directional sensitive earth fault
•
Negative-sequence overcurrent protection, 2 stages
•
Phase discontinuity
•
Three-phase overvoltage protection, 3 stages
•
Positive-sequence undervoltage protection
•
Negative-sequence overvoltage protection
•
Residual overvoltage protection, 3 stages
•
Three-phase undervoltage protection, 3 stages
•
Three-phase transformer inrush detector
•
Three-phase thermal overload, lines and cables
•
Circuit-breaker failure protection
•
Electrically latched lockout relay
Depending on the IED variant, the optional functions may include:
•
Auto-reclose
•
Arc protection, three lens sensors for arc detection
1MRS756378 D
Section 2
REF615 overview
REF615
15
Application Manual
Product version history
IED version
Release date
Product history
1.0
20.12.2007
Product released
1.1
02.07.2008
•
IRIG-B
•
Support for parallel protocols added: IEC 61850
and Modbus
•
X130 BIO added: optional for variants B and D
•
CB interlocking functionality enhanced
•
TCS functionality in HW enhanced
•
Non-volatile memory added
2.0
04.03.2009
•
Support for DNP 3.0 serial or TCP/IP
•
Support for IEC 60870-5-103
•
Voltage measurement and protection
•
Power and energy measurement
•
New standard configurations E and F
•
Disturbance recorder upload via WHMI
•
Fuse failure supervision
2.1.2
PCM600 and IED connectivity package version
Supported tools:
•
Protection and Control IED Manager PCM600 Ver. 2.0 SP2 or later
•
REF615 Connectivity Package Ver. 2.0
•
Parameter Setting Tool
•
Disturbance Handling Tool
•
Signal Monitoring Tool
•
Signal Matrix Tool
•
Communication Management Tool
•
Firmware Update Tool
•
IED Configuration Migration Tool (ICM)
•
Lifecycle Traceability Tool
Download connectivity packages from the ABB web site http://
www.abb.com/substationautomation
2.2
Operation functionality
2.2.1
Standard configurations
The IED is available with six alternative standard configurations. The table indicates
the functions supported by the different IED configurations.
Section 2
1MRS756378 D
REF615 overview
16
REF615
Application Manual
Non-directional overcurrent and directional earth-fault protection
A and B
Non-directional overcurrent and non-directional earth-fault protection
C and D
Non-directional overcurrent and directional earth-fault protection with phase-voltage based measurements
E
Directional overcurrent and earth-fault protection with phase-voltage based measurements, undervoltage and overvoltage
protection
F
Table 3:
Supported functions
Functionality
A
B
C
D
E
F
Protection
Three-phase non-directional overcurrent, low-set stage
●
●
●
●
●
-
Three-phase non-directional overcurrent, high-set stage, instance 1
●
●
●
●
●
-
Three-phase non-directional overcurrent, high-set stage, instance 2
●
●
●
●
●
-
Three-phase non-directional overcurrent, instantaneous stage
●
●
●
●
●
●
Three-phase directional overcurrent, low-set stage, instance 1
-
-
-
-
-
●
Three-phase directional overcurrent, low-set stage, instance 2
-
-
-
-
-
●
Three-phase directional overcurrent, high-set stage
-
-
-
-
-
●
Directional earth-fault, low-set stage, instance 1
●
●
-
-
●
●
Directional earth-fault, low-set stage, instance 2
●
●
-
-
●
●
Directional earth-fault, high-set stage
●
●
-
-
●
●
Non-directional (cross country) earth fault, using calculated Io
●
●
-
-
●
●
Transient/intermittent earth fault
●
●
-
-
●
●
Non-directional earth fault, low-set stage
-
-
●
●
-
-
Non-directional earth fault, high-set stage
-
-
●
●
-
-
Non-directional earth fault, instantaneous stage
-
-
●
●
-
-
Non-directional sensitive earth fault
-
-
●
●
-
-
Negative-sequence overcurrent, instance 1
●
●
●
●
●
●
Negative-sequence overcurrent, instance 2
●
●
●
●
●
●
Phase discontinuity
●
●
●
●
●
●
Thermal overload
●
●
●
●
●
●
Circuit-breaker failure
●
●
●
●
●
●
Three-phase overvoltage, instance 1
-
-
-
-
-
●
Three-phase overvoltage, instance 2
-
-
-
-
-
●
Three-phase overvoltage, instance 3
-
-
-
-
-
●
Positive-sequence undervoltage
-
-
-
-
-
●
Negative-sequence overvoltage
-
-
-
-
-
●
Residual overvoltage, instance 1
-
-
-
-
-
●
Residual overvoltage, instance 2
-
-
-
-
-
●
Residual overvoltage, instance 3
-
-
-
-
-
●
Table continues on next page
1MRS756378 D
Section 2
REF615 overview
REF615
17
Application Manual
Three-phase undervoltage, instance 1
-
-
-
-
-
●
Three-phase undervoltage, instance 2
-
-
-
-
-
●
Three-phase undervoltage, instance 3
-
-
-
-
-
●
Three-phase inrush current detection
●
●
●
●
●
●
Arc protection with three sensors
○
○
○
○
○
○
Control
Circuit breaker control with basic interlocking1)
●
●
●
●
●
●
Circuit breaker control with extended interlocking2)
-
●
-
●
●
●
Auto-reclosing of one circuit breaker
○
○
○
○
○
○
Supervision and monitoring
Fuse failure supervision
-
-
-
-
●
●
Current circuit supervision
-
-
-
-
●
●
Circuit breaker condition monitoring
-
●
-
●
●
●
Trip-circuit supervision of two trip circuits
●
●
●
●
●
●
Disconnector position indication
-
●
-
●
●
●
Earthing switch position indication
-
●
-
●
●
●
Measurement
Transient disturbance recorder
●
●
●
●
●
●
Three-phase current
●
●
●
●
●
●
Current sequence components
●
●
●
●
●
●
Three-phase voltage
-
-
-
-
●
●
Voltage sequence components
-
-
-
-
●
●
Residual current
●
●
●
●
●
●
Residual voltage
●
●
-
-
●
●
Power, including power factor
-
-
-
-
●
●
Energy
-
-
-
-
●
●
● = Included,○ = Optional at the time of the order
1)
Basic interlocking functionality: Closing of the circuit breaker can be enabled by a binary input signal. The actual interlocking scheme is
implemented outside the IED. The binary input serves as a “master interlocking input” and when energized it will enable circuit breaker
closing.
2)
Extended interlocking functionality: The circuit breaker interlocking scheme is implemented in the IED configuration, based on primary
equipment position information (via binary inputs) and the logical functions available. The signal matrix tool of PCM600 can be used for
modifying the interlocking scheme to suit your application.
2.2.2
Optional functions
The optional functions available in the IED are:
Section 2
1MRS756378 D
REF615 overview
18
REF615
Application Manual
Modbus TCP/IP or RTU/ASCII
•
IEC 60870-5-103
•
DNP 3.0 TCP/IP or serial
2.3
Physical hardware
The IED consists of two main parts: plug-in unit and case. The plug-in unit content
depends on the ordered functionality.
Table 4:
Plug-in unit and case
Main unit
Slot ID
Content options
Plug-in
unit
-
HMI
Small (4 lines, 16 characters)
Large (8 lines, 16 characters)
X100
Auxiliary power/BO
module
48-250 V DC/100-240 V AC; or 24-60 V DC
2 normally-open PO contacts
1 change-over SO contacts
1 normally open SO contact
2 double-pole PO contacts with TCS
1 dedicated internal fault output contact
X110
BI/O module
Only with configurations B, D, E and F:
8 BIs
4 SO contacts
X120
AI/BI module
Only with configurations A and B:
3 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A)1)
1 residual voltage input (100, 110, 115 or 120 V)
3 BIs
Only with configurations C, D, E and F:
3 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A)1)
4 BIs
Case
X130
AI/BI module
Only with configurations E and F:
3 phase voltage inputs (100, 110, 115 or 120 V)
1 residual voltage input (100, 110, 115 or 120 V)
4 BIs
Optional BI/O
module
Only with configurations B and D:
6 BIs
3 SO contacts
X90
Optional
communication
module
See technical manual for details about different type of
communication modules.
1)
The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring
core-balance current transformers.
The rated input levels are selected in the IED software for phase current, residual
current and residual voltage. The binary input thresholds 18...176 V DC are selected
by adjusting the IED's parameter settings.
1MRS756378 D
Section 2
REF615 overview
REF615
19
Application Manual
The connection diagrams of different hardware modules are presented in this manual.
See the Installation Manual for more information about the case and
the plug-in unit.
Table 5:
Number of physical connections in standard configurations
Conf.
Analog channels
Binary channels
CT
VT
BI
BO
A
4
1
3
6
B
4
1
11 (17)1)
10 (13)1)
C
4
-
4
6
D
4
-
12 (18)1)
10 (13)1)
E
4
52)
16
10
F
4
52)
16
10
1)
With optional BIO module
2)
One of the five channels reserved for future applications
Section 2
1MRS756378 D
REF615 overview
20
REF615
Application Manual
A070704 V2 EN
Figure 1:
LHMI
The LHMI of the IED contains the following elements:
•
Display
•
Buttons
•
LED indicators
•
Communication port
The LHMI is used for setting, monitoring and controlling.
2.4.1
LCD
The LHMI includes a graphical LCD that supports two character sizes. The character
size depends on the selected language.
The amount of characters and rows fitting the view depends on the character size:
1MRS756378 D
Section 2
REF615 overview
REF615
21
Application Manual
Rows in view
Characters on row
Small, mono-spaced (6x12
pixels)
5 rows
10 rows with large screen
20
Large, variable width (13x14
pixels)
4 rows
8 rows with large screen
min 8
The display view is divided into four basic areas:
1
2
3
4
A070705 V2 EN
Figure 2:
Display layout
1
Header
2
Icon
3
Content
4
Scroll bar (displayed when needed)
2.4.2
LEDs
The LHMI includes three protection indicators above the display: Ready, Start and
Trip.
There are also 11 matrix programmable alarm LEDs on front of the LHMI. The LEDs
can be configured with PCM600 and the operation mode can be selected with the
LHMI and PST.
2.4.3
Keypad
The LHMI keypad consists of push-buttons which are used to navigate in different
views or menus. With push-buttons you can give open or close commands to one
primary object, for example, a circuit breaker, disconnector or switch. The push-
buttons are also used to acknowledge alarms, reset indications, provide help and
switch between local and remote control mode.
Section 2
1MRS756378 D
REF615 overview
22
REF615
Application Manual
A071176 V1 EN
Figure 3:
LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
2.5
WHMI
The WHMI enables the user to access the IED via a web browser. The supported web
browser version is Internet Explorer 7.0 or later.
WHMI is disabled by default.
WHMI offers the following functions:
•
Alarm indications and event lists
•
System supervision
•
Parameter settings
•
Measurement display
•
Disturbance records
•
Phasor diagram
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
1MRS756378 D
Section 2
REF615 overview
REF615
23
Application Manual
A070754 V3 EN
Figure 4:
Example view of the WHMI
The WHMI can be accessed:
•
Locally by connecting your laptop to the IED via the front communication port.
•
Remotely over LAN/WAN.
2.6
Authorization
The user categories have been predefined for the LHMI and the WHMI, each with
different rights and default passwords.
The default passwords can be changed with Administrator user rights.
User authorization is disabled by default but WHMI always uses
authorization.
Section 2
1MRS756378 D
REF615 overview
24
REF615
Application Manual
Predefined user categories
Username
User rights
VIEWER
Read only access
OPERATOR
•
Selecting remote or local state with
(only locally)
•
Changing setting groups
•
Controlling
•
Clearing alarm and indication LEDs and textual indications
ENGINEER
•
Changing settings
•
Clearing event list
•
Clearing disturbance records
•
Changing system settings such as IP address, serial baud rate or
disturbance recorder settings
•
Setting the IED to test mode
•
Selecting language
ADMINISTRATOR
•
All listed above
•
Changing password
For user authorization for PCM600, see PCM600 documentation.
2.7
Communication
The IED supports different communication protocols: IEC 61850-8-1, DNP 3.0, IEC
60870-5-103 and Modbus®. Operational information and controls are available
through these protocols. However, some communication functionality, for example,
horizontal communication between the IEDs and parameters setting, is only enabled
by the IEC 61850 communication protocol.
The IEC 61850 communication implementation supports all monitoring and control
functions. Additionally, parameter setting and disturbance file records can be
accessed using the IEC 61850-8-1 protocol. Further, the IED can send and receive
binary signals from other IEDs (so called horizontal communication) using the
IEC61850-8-1 GOOSE profile, where the highest performance class with a total
transmission time of 3 ms is supported. The IED can simultaneously report to five
different IEC 61850-8-1 clients.
The IED can support five simultaneous clients. If PCM600 reserves one client
connection, only four client connections are left, for example, for IEC 61850 and
Modbus.
All communication connectors, except for the front port connector, are placed on
integrated optional communication modules. The IED can be connected to Ethernet-
based communication systems via the RJ-45 connector (100BASE-TX) or the fibre-
1MRS756378 D
Section 2
REF615 overview
REF615
25
Application Manual
optic LC connector (100BASE-FX). An optional serial interface is available for
RS-232/RS-485 communication.
Section 2
1MRS756378 D
REF615 overview
26
REF615
Application Manual
REF615 variant list
REF615 is intended for protection and control mainly in MV feeder applications. The
product has a number of standard configurations covering a wide range of primary
circuit configurations in distribution networks based on different system earthing
methods.
Some of the functions included in the IED's standard configurations are optional at
the time of placing the order. The description of standard configurations covers the
full functionality including options, presenting the functionality, flexibility and
external connections of REF615 with a specific configuration as delivered from the
factory.
3.2
Presentation of standard configurations
Functional diagrams
The functional diagrams describe the IED's functionality from the protection,
measuring, condition monitoring, disturbance recording, control and interlocking
perspective. Diagrams show the default functionality with simple symbol logics
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers. The positive
measuring direction of directional protection functions is towards the outgoing feeder.
The functional diagrams are divided into sections which each constitute one
functional entity. The external connections are also divided into sections. Only the
relevant connections for a particular functional entity are presented in each section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used several
times in the configuration. To separate the blocks from each other, the IEC 61850
name, IEC symbol and ANSI function number are appended with a running number,
that is an instance number, from one upwards. If the block has no suffix after the IEC
or ANSI symbol, the function block has been used, that is, instantiated, only once.
The IED’s internal functionality and the external connections are separated with a
dashed line presenting the IED’s physical casing.
1MRS756378 D
Section 3
REF615 variants
REF615
27
Application Manual
Signal Matrix Tool
With SMT the user can modify the standard configuration according to the actual
needs. The IED is delivered from the factory with default connections described in
the functional diagrams for BI's, BO's, function to function connections and alarm
LEDs. SMT has a number of different page views, designated as follows:
•
Binary input
•
Binary output
•
Functions
The functions in different page views are identified by the IEC 61850 names with
analogy to the functional diagrams.
3.2.1
Standard configurations
The IED is available with six alternative standard configurations. The table indicates
the functions supported by the different IED configurations.
Table 7:
Standard configurations
Description
Std. conf.
Non-directional overcurrent and directional earth-fault protection
A and B
Non-directional overcurrent and non-directional earth-fault protection
C and D
Non-directional overcurrent and directional earth-fault protection with phase-voltage based measurements
E
Directional overcurrent and earth-fault protection with phase-voltage based measurements, undervoltage and overvoltage
protection
F
Table 8:
Supported functions
Functionality
A
B
C
D
E
F
Protection
Three-phase non-directional overcurrent, low-set stage
●
●
●
●
●
-
Three-phase non-directional overcurrent, high-set stage, instance 1
●
●
●
●
●
-
Three-phase non-directional overcurrent, high-set stage, instance 2
●
●
●
●
●
-
Three-phase non-directional overcurrent, instantaneous stage
●
●
●
●
●
●
Three-phase directional overcurrent, low-set stage, instance 1
-
-
-
-
-
●
Three-phase directional overcurrent, low-set stage, instance 2
-
-
-
-
-
●
Three-phase directional overcurrent, high-set stage
-
-
-
-
-
●
Directional earth-fault, low-set stage, instance 1
●
●
-
-
●
●
Directional earth-fault, low-set stage, instance 2
●
●
-
-
●
●
Directional earth-fault, high-set stage
●
●
-
-
●
●
Non-directional (cross country) earth fault, using calculated Io
●
●
-
-
●
●
Transient/intermittent earth fault
●
●
-
-
●
●
Non-directional earth fault, low-set stage
-
-
●
●
-
-
Table continues on next page
Section 3
1MRS756378 D
REF615 variants
28
REF615
Application Manual
Non-directional earth fault, high-set stage
-
-
●
●
-
-
Non-directional earth fault, instantaneous stage
-
-
●
●
-
-
Non-directional sensitive earth fault
-
-
●
●
-
-
Negative-sequence overcurrent, instance 1
●
●
●
●
●
●
Negative-sequence overcurrent, instance 2
●
●
●
●
●
●
Phase discontinuity
●
●
●
●
●
●
Thermal overload
●
●
●
●
●
●
Circuit-breaker failure
●
●
●
●
●
●
Three-phase overvoltage, instance 1
-
-
-
-
-
●
Three-phase overvoltage, instance 2
-
-
-
-
-
●
Three-phase overvoltage, instance 3
-
-
-
-
-
●
Positive-sequence undervoltage
-
-
-
-
-
●
Negative-sequence overvoltage
-
-
-
-
-
●
Residual overvoltage, instance 1
-
-
-
-
-
●
Residual overvoltage, instance 2
-
-
-
-
-
●
Residual overvoltage, instance 3
-
-
-
-
-
●
Three-phase undervoltage, instance 1
-
-
-
-
-
●
Three-phase undervoltage, instance 2
-
-
-
-
-
●
Three-phase undervoltage, instance 3
-
-
-
-
-
●
Three-phase inrush current detection
●
●
●
●
●
●
Arc protection with three sensors
○
○
○
○
○
○
Control
Circuit breaker control with basic interlocking1)
●
●
●
●
●
●
Circuit breaker control with extended interlocking2)
-
●
-
●
●
●
Auto-reclosing of one circuit breaker
○
○
○
○
○
○
Supervision and monitoring
Fuse failure supervision
-
-
-
-
●
●
Current circuit supervision
-
-
-
-
●
●
Circuit breaker condition monitoring
-
●
-
●
●
●
Trip-circuit supervision of two trip circuits
●
●
●
●
●
●
Disconnector position indication
-
●
-
●
●
●
Earthing switch position indication
-
●
-
●
●
●
Measurement
Transient disturbance recorder
●
●
●
●
●
●
Three-phase current
●
●
●
●
●
●
Current sequence components
●
●
●
●
●
●
Three-phase voltage
-
-
-
-
●
●
Voltage sequence components
-
-
-
-
●
●
Residual current
●
●
●
●
●
●
Table continues on next page
1MRS756378 D
Section 3
REF615 variants
REF615
29
Application Manual
Power, including power factor
-
-
-
-
●
●
Energy
-
-
-
-
●
●
● = Included,○ = Optional at the time of the order
1)
Basic interlocking functionality: Closing of the circuit breaker can be enabled by a binary input signal. The actual interlocking scheme is
implemented outside the IED. The binary input serves as a “master interlocking input” and when energized it will enable circuit breaker
closing.
2)
Extended interlocking functionality: The circuit breaker interlocking scheme is implemented in the IED configuration, based on primary
equipment position information (via binary inputs) and the logical functions available. The signal matrix tool of PCM600 can be used for
modifying the interlocking scheme to suit your application.
Section 3
1MRS756378 D
REF615 variants
30
REF615
Application Manual
A071288 V4 EN
Figure 5:
Connection diagram for configurations A and B (overcurrent and
directional earth-fault protection) [1]
[1] Additional BIO-module (X110 in the diagram) is included in the IED variant B
1MRS756378 D
Section 3
REF615 variants
REF615
31
Application Manual
A071290 V3 EN
Figure 6:
Connection diagram for configurations C and D (overcurrent and
non-directional earth-fault protection) [2]
[2] Additional BIO-module (X110 in the diagram) is included in the IED variant D
Section 3
1MRS756378 D
REF615 variants
32
REF615
Application Manual
GUID-F7601942-ACF2-47E2-8F21-CD9C1D2BC1F0 V2 EN
Figure 7:
Connection diagram for configurations E and F (directional
overcurrent and earth-fault protection with phase-to-phase voltage
measurement)
1MRS756378 D
Section 3
REF615 variants
REF615
33
Application Manual
GUID-5D0135B3-3890-497A-8AAA-0362730C8682 V1 EN
Figure 8:
Connection diagram for configurations E and F (directional
overcurrent and earth-fault protection with phase-to-earth voltage
measurement)
3.3
Standard configuration A including directional earth-
fault protection
3.3.1
Applications
The standard configuration for directional earth-fault protection is mainly intended
for cable and overhead line feeder applications in isolated and resonant-earthed
distribution networks. The IED with this standard configuration is delivered from the
factory with default settings and parameters. The end-user flexibility for incoming,
outgoing and internal signal designation within the IED enables this configuration to
be further adapted to different primary circuit layouts and the related functionality
needs by modifying the internal functionality using PCM600.
Section 3
1MRS756378 D
REF615 variants
34
REF615
Application Manual
Functions included in the REF615 standard configuration with directional earth-fault
protection
Function
IEC 61850
IEC
ANSI
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1
3I>
51P-1
Three-phase non-directional overcurrent
protection, high stage, instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional overcurrent
protection, high stage, instance 2
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1
3I>>>
50P/51P
Arc protection
ARCSARC1
ARCSARC2
ARCSARC3
ARC (1)
ARC (2)
ARC (3)
50L/50NL (1)
50L/50NL (2)
50L/50NL (3)
Directional earth-fault protection, low stage,
instance 1
DEFLPDEF1
I0> → (1)
67N-1 (1)
Directional earth-fault protection, low stage,
instance 2
DEFLPDEF2
I0> → (2)
67N-1 (2)
Directional earth-fault protection, high stage
DEFHPDEF1
I0>> →
67N-2
Transient/intermittent earth-fault protection
INTRPTEF1
I0> → IEF
67NIEF
Non-directional earth-fault protection, high
stage, calculated I0 current (Double earth-fault
protection)
EFHPTOC1
I0>>
51N-2
Negative-sequence overcurrent protection,
instance 1
NSPTOC1
I2> (1)
46 (1)
Negative-sequence overcurrent protection,
instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity
PDNSPTOC1
I2/I1>
46PD
Three-phase inrush detector
INRPHAR1
3I2f>
68
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1
3Ith>
49F
Autoreclosure
DARREC1
O → I
79
Circuit breaker failure protection
CCBRBRF1
3I>/I0>BF
51BF/51NBF
Master Trip
TRPPTRC1
TRPPTRC2
Master Trip (1)
Master Trip (2)
94/86 (1)
94/86 (2)
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Disturbance recorder
RDRE1
-
-
Three-phase current measurement
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Residual current measurement
RESCMMXU1
I0
In
Residual voltage measurement
RESVMMXU1
U0
Vn
1MRS756378 D
Section 3
REF615 variants
REF615
35
Application Manual
Default I/O connections
Binary Input
Default usage
Connector-Pins
X120-BI1
Blocking of Overcurrent Instantaneous Stage
X120-1,2
X120-BI2
Circuit Breaker Closed position indication
X120-3,2
X120-BI3
Circuit Breaker Open position indication
X120-4,2
Binary Output
Default usage
Connector-Pins
X100-PO1
Close Circuit Breaker
X100-6,7
X100-PO2
Circuit Breaker Failure protection trip to upstream
breaker
X100-8,9
X100-PO3
Open Circuit Breaker / trip coil 1
X100-16,17,18,19
X100-PO4
Open Circuit Breaker / trip coil 2
X100-20,21,22,23
X100-SO1
General Start Indication
X100-10,11,12
X100-SO2
General Operate Indication
X100-13,14,15
LED
Default usage
1
Non-Directional Overcurrent Operate
2
Directional/Intermittent Earth fault Operate
3
Double (Cross country) Earth fault Operate
4
Negative Seq. Overcurrent/Phase Discontinuity Operate
5
Thermal Overload Alarm
6
Breaker Failure Operate
7
Disturbance Recorder Triggered
8
Not connected
9
Trip Circuit Supervision Alarm
10
ARC Protection Operate
11
Auto Reclose in Progress
3.3.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function
to function connections. The default connections can be viewed with SMT and
changed according to the application requirements, if necessary.
The analog channels, measurements from CTs and VTs, have fixed connections
towards the different function blocks inside the IED’s standard configuration.
Exceptions from this rule are the 12 analog channels available for the disturbance
recorder function. These channels are freely selectable and a part of the disturbance
recorder’s parameter settings, thus not included in the SMT functionality.
Section 3
1MRS756378 D
REF615 variants
36
REF615
Application Manual
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a core balance
CT. The signal marked with U0 represents the measured residual voltage via open
delta connected VTs.
The EFHPTOC protection function block for double (cross-country) earth-faults uses
the calculated residual current originating from the measured phase currents.
3.3.3.1
Functional diagrams for protection
The following functional diagrams describe the IED’s protection functionality in
detail and according to the factory set default connections in SMT.
A071316 V3 EN
Figure 9:
Overcurrent protection
1MRS756378 D
Section 3
REF615 variants
REF615
37
Application Manual
Four overcurrent stages are offered for overcurrent and short-circuit protection. The
instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1
(X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 and NSPTOC2)
are offered for phase unbalance protection. The inrush detection block’s
(INRPHAR1) output BLK2H caters the possibility to either block the function or
multiply the active settings for any of the shown protection function blocks.
All operate signals are connected to the Master Trip and also to the alarm LEDs. LED
1 is used for overcurrent and LED 4 for negative sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
There are four IED variant specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The change of an
active setting group can also be made via a binary input if the binary input is enabled
for this. To enable the change of the active setting group via a binary input, connect
a free binary input with SMT to the ActSG input of the SGCB-block.
Table 10:
Binary input states and corresponding active setting groups
BI State
Active setting group
OFF
1
ON
2
The active setting group defined by a parameter is overridden when a binary input is
enabled for changing the active setting group.
Section 3
1MRS756378 D
REF615 variants
38
REF615
Application Manual
A071318 V4 EN
Figure 10:
Directional earth-fault protection
Three stages are offered for directional earth-fault protection. In addition, there is a
dedicated protection stage (INTRPTEF) either for transient based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for
protection against double earth-fault situations in isolated or compensated networks.
This protection function uses the calculated residual current originating from the
phase currents.
All operate signals are connected to the Master Trip and also to the alarm LEDs. LED
2 is used for directional earth-fault and LED 3 for double earth-fault protection operate
indication.
1MRS756378 D
Section 3
REF615 variants
REF615
39
Application Manual
A071320 V4 EN
Figure 11:
Phase discontinuity, thermal overload and circuit breaker failure
protection
The phase discontinuity protection (PDNPSTOC1) provides protection for
interruptions in the normal three-phase load supply, for example, in downed
conductor situations. The thermal overload protection (T1PTTR1) provides
indication on overload situations. The operate signal of the phase discontinuity
protection is connected to the Master Trip and also to an alarm LED. LED 4 is used
for the phase discontinuity protection operate indication, the same as for negative
sequence overcurrent protection operate indication, and LED 5 is used for the thermal
overload protection alarm indication.
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker position
and the measured phase and residual currents. The breaker failure protection has two
operating outputs: TRRET and TRBU. The TRRET operate output is used for re-
tripping its own breaker through the Master Trip 2. The TRBU output is used to give
a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate
output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up
(TRBU) operate indication.
Section 3
1MRS756378 D
REF615 variants
40
REF615
Application Manual
A071322 V4 EN
Figure 12:
Arc protection
ARC protection (ARCSARC1-3) and autoreclosing (DARREC1) are included as
optional functions.
The ARC protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each ARC protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the ARC protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
The autorecloser is configured to be initiated by operate signals from a number of
protection stages through the INIT1-5 inputs. It is possible to create individual
autoreclose sequences for each input.
The autoreclose function can be blocked with the INHIBIT_RECL input. As a default,
the operation of selected protection functions are connected to this input. A control
1MRS756378 D
Section 3
REF615 variants
REF615
41
Application Manual
command to the circuit breaker, either local or remote, also blocks the autoreclose
function via the CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the
CB_RDY input in DARREC1. In the configuration, this signal is not connected to
any of the binary inputs. As a result, the function assumes that the breaker is available
all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.3.3.2
Functional diagrams for disturbance recorder and trip circuit
supervision
PHLPTOC1-start
PHHPTOC1-start
PHHPTOC2-start
PHIPTOC1-start
NSPTOC1-start
NSPTOC2-start
DEFLPDEF1-start
DEFLPDEF2-start
DEFHPDEF1-start
INTRPTEF1-start
EFHPTOC1-start
PDNSPTOC1-start
T1PTTR1-start
CCRBRF1-trret
CCRBRF1-trbu
OR
PHLPTOC1-operate
PHHPTOC1-operate
PHHPTOC2-operate
PHIPTOC1-operate
LED7 (DR TRIGGERED)
OR
OR
INTRPTEF1-operate
EFHPTOC1-operate
PDNSPTOC1-operate
INRPHAR1-blk2h
T1PTTR1-operate
OR
ARCSARC1-operate
ARCSARC2-operate
ARCSARC3-operate
DARREC1-inpro
OR
NSPTOC1-operate
NSPTOC2-operate
ARCSARC1-fault_arc_det
ARCSARC2-fault_arc_det
ARCSARC3-fault_arc_det
DEFLPDEF1-operate
DEFLPDEF2-operate
DEFHPDEF1-operate
DARREC1-close cb
DARREC1-unsuc_recl
BI 1 (Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
DISTURBANCE RECORDER
TCSSCBR1
ALARM
BLOCK
TCSSCBR2
ALARM
BLOCK
OR
OR
TRPPTRC1- trip
TRPPTRC2- trip
LED9 (TCS ALARM)
TRIP CIRCUIT SUPERVISION
RDRE1
TRIGGERED
BI#1
BI#2
BI#3
BI#4
BI#5
BI#6
BI#7
BI#8
BI#9
BI#10
BI#11
BI#12
BI#13
BI#14
BI#15
BI#16
BI#17
BI#18
BI#19
BI#20
BI#21
BI#22
BI#23
BI#24
BI#25
BI#26
BI#27
BI#28
BI#29
BI#30
BI#31
BI#32
A071324 V4 EN
Figure 13:
Disturbance recorder
The disturbance recorder has 64 digital inputs, of which 32 are connected as default.
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected autorecloser, the ARC
protection signals and the three binary inputs from X120 are also connected.
Section 3
1MRS756378 D
REF615 variants
42
REF615
Application Manual
Two separate TCS functions have been included: TCSSCBR1 for PO3 (X100:16-19)
and TCSSCBR2 for PO4 (X100:20-23). Both functions are blocked by the Master
Trip and the circuit breaker open position signal. The TCS alarm indication is
connected to LED 9.
3.3.3.3
Functional diagrams for control and interlocking
A071326 V4 EN
Figure 14:
Master trip
The operate signals from the protections described above are connected to the two
trip output contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding
Master Trips TRPPTRC1 and TRPPTRC2. The open control commands to the circuit
breaker from local or remote CBXCBR1-exe_op or from the auto-recloser
DARREC1-open_cb are connected directly to the output PO3 (X100:16-19).
The TRPPTRC1 and 2 blocks provide the lockout/latching function, event generation
and the trip signal duration setting. If the lockout operation mode is selected, one
binary input can be re-assigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
1MRS756378 D
Section 3
REF615 variants
REF615
43
Application Manual
A071328 V3 EN
Figure 15:
Circuit breaker control
The ENA_CLOSE input, that is, enable the closing of the circuit breaker, in the
breaker control function block CBXCBR is a combination of the status of the Master
Trip. The open operation is always enabled.
If the ENA_CLOSE signal is completely removed from the breaker
control function block CBXCBR with SMT, the function assumes
that the breaker close commands are allowed continuously.
A071330 V3 EN
Figure 16:
Alarm indication
The signal outputs from the IED are connected to give dedicated information on:
•
start of any protection function SO1 (X100:10-12)
•
operation (trip) of any protection function SO2 (X100:13-15).
Section 3
1MRS756378 D
REF615 variants
44
REF615
Application Manual
The TPGAPC1 is a timer and used for setting the minimum pulse length for the
outputs. There are four generic timers (TPGAPC1..4) available in the IED. The
remaining ones not described in the functional diagram are available in SMT for
connection where applicable.
3.4
Standard configuration B including directional earth-
fault protection and CB condition monitoring
3.4.1
Applications
The standard configuration for directional earth-fault protection is mainly intended
for cable and overhead line feeder applications in isolated and resonant-earthed
distribution networks. The IED with this standard configuration is delivered from the
factory with default settings and parameters. The end-user flexibility for incoming,
outgoing and internal signal designation within the IED enables this configuration to
be further adapted to different primary circuit layouts and the related functionality
needs by modifying the internal functionality using PCM600.
3.4.2
Functions
Table 11:
Functions included in the REF615 standard configuration with directional earth-fault
protection
Function
IEC 61850
IEC
ANSI
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1
3I>
51P-1
Three-phase non-directional overcurrent
protection, high stage, instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional overcurrent
protection, high stage, instance 2
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1
3I>>>
50P/51P
Arc protection
ARCSARC1
ARCSARC2
ARCSARC3
ARC (1)
ARC (2)
ARC (3)
50L/50NL (1)
50L/50NL (2)
50L/50NL (3)
Directional earth-fault protection, low stage,
instance 1
DEFLPDEF1
I0> → (1)
67N-1 (1)
Directional earth-fault protection, low stage,
instance 2
DEFLPDEF2
I0> → (2)
67N-1 (2)
Directional earth-fault protection, high stage
DEFHPDEF1
I0>> →
67N-2
Transient/intermittent earth-fault protection
INTRPTEF1
I0> → IEF
67NIEF
Non-directional earth-fault protection, high
stage, calculated I0 current (Double earth-fault
protection)
EFHPTOC1
I0>>
51N-2
Negative-sequence overcurrent protection,
instance 1
NSPTOC1
I2> (1)
46 (1)
Table continues on next page
1MRS756378 D
Section 3
REF615 variants
REF615
45
Application Manual
Negative-sequence overcurrent protection,
instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity
PDNSPTOC1
I2/I1>
46PD
Three-phase inrush detector
INRPHAR1
3I2f>
68
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1
3Ith>
49F
Autoreclosure
DARREC1
O → I
79
Circuit breaker failure protection
CCBRBRF1
3I>/I0>BF
51BF/51NBF
Master Trip
TRPPTRC1
TRPPTRC2
Master trip (1)
Master trip (2)
94/86 (1)
94/86 (2)
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Disturbance recorder
RDRE1
-
-
Circuit breaker condition monitoring
SSCBR1
CBCM
CBCM
Three-phase current measurement
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Residual current measurement
RESCMMXU1
I0
In
Residual voltage measurement
RESVMMXU1
U0
Vn
3.4.2.1
Default I/O connections
Binary Input
Default usage
Connector-Pins
X110-BI2
Directional Earth Fault Protection's Basic Angle Control
X110-3,4
X110-BI3
Circuit Breaker low Gas Pressure indication
X110-5,6
X110-BI4
Circuit Breaker Spring Charged indication
X110-6,7
X110-BI5
CB Truck in (Service position) indication
X110-8,9
X110-BI6
CB Truck out (Test position) indication
X110-10,9
X110-BI7
Earthing Switch Closed indication
X110-11,12
X110-BI8
Earthing Switch Open indication
X110-13,12
X120-BI1
Blocking of Overcurrent Instantaneous Stage
X120-1,2
X120-BI2
Circuit Breaker Closed indication
X120-3,2
X120-BI3
Circuit Breaker Open indication
X120-4,2
Binary Output
Default usage
Connector-Pins
X100-PO1
Close Circuit Breaker
X100-6,7
X100-PO2
Circuit Breaker Failure protection trip to upstream breaker
X100-8,9
X100-PO3
Open Circuit Breaker / trip coil 1
X100-16,17,18,19
X100-PO4
Open Circuit Breaker / trip coil 2
X100-20,21,22,23
X100-SO1
General Start Indication
X100-10,11,12
X100-SO2
General Operate Indication
X100-13,14,15
Table continues on next page
Section 3
1MRS756378 D
REF615 variants
46
REF615
Application Manual
Upstream Overcurrent Blocking
X110-14,15,16
X110-SO2
Overcurrent Operate Alarm
X110-17,18,19
X110-SO3
Earth fault Operate Alarm
X110-20,21,22
LED
Default usage
1
Non-Directional Overcurrent Operate
2
Directional/Intermittent Earth fault Operate
3
Double (Cross country) Earth fault Operate
4
Negative Seq. Overcurrent/Phase Discontinuity Operate
5
Thermal Overload Alarm
6
Breaker Failure Operate
7
Disturbance Recorder Triggered
8
Circuit Breaker Condition Monitoring Alarm
9
Trip Circuit Supervision Alarm
10
ARC Protection Operate
11
Auto Reclose in Progress
3.4.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed with SMT and
changed according to the application requirements, if necessary.
The analog channels, measurements from CTs and VTs, have fixed connections
towards the different function blocks inside the IED’s standard configuration.
Exceptions from this rule are the 12 analog channels available for the disturbance
recorder function. These channels are freely selectable and a part of the disturbance
recorder’s parameter settings, thus not included in the SMT functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a core balance
CT. The signal marked with U0 represents the measured residual voltage via open
delta connected VTs.
The EFHPTOC protection function block for double (cross-country) earth-faults uses
the calculated residual current originating from the measured phase currents.
3.4.3.1
Functional diagrams for protection
The following functional diagrams describe the IED’s protection functionality in
detail and according to the factory set default connections in SMT.
1MRS756378 D
Section 3
REF615 variants
REF615
47
Application Manual
A071332 V4 EN
Figure 17:
Overcurrent protection
Four overcurrent stages are offered for overcurrent and short-circuit protection. The
instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1
(X120:1-2). Two negative sequence overcurrent stages (NPSTOC1 and NPSTOC2)
are offered for phase unbalance protection. The inrush detection block’s
(INRPHAR1) output BLK2H caters the possibility to either block the function or
multiply the active settings for any of the shown protection function blocks.
All operate signals are connected to the Master Trip and also to the alarm LEDs. LED
1 is used for overcurrent and LED 4 for negative sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for
sending a blocking signal to the relevant overcurrent protection stage of the IED at
the infeeding bay.
Section 3
1MRS756378 D
REF615 variants
48
REF615
Application Manual
There are four IED variant specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The change of an
active setting group can also be made via a binary input if the binary input is enabled
for this. To enable the change of an active setting group via a binary input, connect
a free binary input with SMT to the ActSG input of the SGCB-block.
Table 12:
Binary input states and corresponding active setting groups
BI State
Active setting group
OFF
1
ON
2
The active setting group defined by a parameter is overridden when a binary input is
enabled for changing the active setting group.
I > (1)
DEFLPDEF1
START
OPERATE
I0
U0
ENA_MULT
67N-1 (1)
0
RCA_CTL
BLOCK
I > (2)
DEFLPDEF2
START
OPERATE
I0
U0
ENA_MULT
67N-1 (2)
0
RCA_CTL
BLOCK
I >>
DEFHPDEF
START
OPERATE
I0
U0
ENA_MULT
67N-2
0
RCA_CTL
BLOCK
LED2 (DEF OPERATE)
OR
DIRECTIONAL OR INTERMITTENT EARTH FAULT PROTECTION
DOUBLE (CROSS COUNTRY) EARTH FAULT PROTECTION
LED3 (NEF OPERATE)
I >>
EFHPTOC1
START
OPERATE
I0
BLOCK
ENA_MULTI
51N-2
0
Calculated Io
X110
3
4
BI 2 (BACTRL)
INTRPTEF1
START
OPERATE
U0
BLOCK
BLK_EF
67NIEF
I >
0
I0
A071334 V4 EN
Figure 18:
Directional earth-fault protection
1MRS756378 D
Section 3
REF615 variants
REF615
49
Application Manual
Three stages are offered for directional earth-fault protection. In addition, there is a
dedicated protection stage (INTRPTEF) either for transient based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for
protection against double earth-fault situations in isolated or compensated networks.
This protection function uses the calculated residual current originating from the
phase currents.
The binary input 2 (X110:3-4) is intended for directional earth-fault protection
blocks’ Relay Characteristic Angle (RCA: 0°/-90°) or operation mode (I0Sinφ/
I0Cosφ) change. All operate signals are connected to the Master Trip and also to the
alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for double earth-
fault protection operate indication.
A071320 V4 EN
Figure 19:
Phase discontinuity, thermal overload and circuit breaker failure
protection
The phase discontinuity protection (PDNSPTOC1) provides protection for
interruptions in the normal three-phase load supply, for example, in downed
conductor situations. The thermal overload protection (T1PTTR1) provides
indication on overload situations. The operate signal of the phase discontinuity
protection is connected to the Master Trip and also to an alarm LED. LED 4 is used
for the phase discontinuity protection operate indication, the same as for negative
sequence overcurrent protection operate indication, and LED 5 is used for the thermal
overload protection alarm indication.
Section 3
1MRS756378 D
REF615 variants
50
REF615
Application Manual
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker position
and the measured phase and residual currents. The breaker failure protection has two
operating outputs: TRRET and TRBU. The TRRET operate output is used for re-
tripping its own breaker through the Master Trip 2. The TRBU output is used to give
a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate
output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up
(TRBU) operate indication.
A071338 V5 EN
Figure 20:
Arc protection
ARC protection (ARCSARC1-3) and autoreclosing (DARREC1) are included as
optional functions.
1MRS756378 D
Section 3
REF615 variants
REF615
51
Application Manual
The ARC protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each ARC protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the ARC protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
The autorecloser is configured to be initiated by operate signals from a number of
protection stages through the INIT1-5 inputs. It is possible to create individual
autoreclose sequences for each input.
The autoreclose function can be blocked with the INHIBIT_RECL input. As a default,
the operation of some selected protection functions are connected to this input. A
control command to the circuit breaker, either local or remote, also blocks the
autoreclose function via the CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the
binary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. In
case this signal is completely removed from the autoreclose function block with SMT,
the function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
Section 3
1MRS756378 D
REF615 variants
52
REF615
Application Manual
Functional diagram for disturbance recorder and trip circuit supervision
PHLPTOC1-start
PHHPTOC1-start
PHHPTOC2-start
PHIPTOC1-start
NSPTOC1-start
NSPTOC2-start
DEFLPDEF1-start
DEFLPDEF2-start
DEFHPDEF1-start
INTRPTEF1-start
EFHPTOC1-start
PDNSPTOC1-start
T1PTTR1-start
CCRBRF1-trret
CCRBRF1-trbu
OR
PHLPTOC1-operate
PHHPTOC1-operate
PHHPTOC2-operate
PHIPTOC1-operate
LED7 (DR TRIGGERED)
OR
OR
INTRPTEF1-operate
EFHPTOC1-operate
PDNSPTOC1-operate
INRPHAR1-blk2h
T1PTTR1-operate
OR
ARCSARC1-operate
ARCSARC2-operate
ARCSARC3-operate
DARREC1-inpro
OR
NSPTOC1-operate
NSPTOC2-operate
ARCSARC1-fault_arc_det
ARCSARC2-fault_arc_det
ARCSARC3-fault_arc_det
DEFLPDEF1-operate
DEFLPDEF2-operate
DEFHPDEF1-operate
DARREC1-close cb
DARREC1-unsuc_recl
BI 1 (Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
DISTURBANCE RECORDER
TCSSCBR1
ALARM
BLOCK
TCSSCBR2
ALARM
BLOCK
OR
OR
TRPPTRC1- trip
TRPPTRC2- trip
LED9 (TCS ALARM)
TRIP CIRCUIT SUPERVISION
RDRE1
TRIGGERED
BI#1
BI#2
BI#3
BI#4
BI#5
BI#6
BI#7
BI#8
BI#9
BI#10
BI#11
BI#12
BI#13
BI#14
BI#15
BI#16
BI#17
BI#18
BI#19
BI#20
BI#21
BI#22
BI#23
BI#24
BI#25
BI#26
BI#27
BI#28
BI#29
BI#30
BI#31
BI#32
A071324 V4 EN
Figure 21:
Disturbance recorder
The disturbance recorder has 64 digital inputs, of which 32 are connected as default.
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected autorecloser, the ARC
protection signals and the three binary inputs from X120 are also connected.
Two separate TCS functions have been included: TCSSCBR1 for PO3 (X100:16-19)
and TCSSCBR2 for PO4 (X100:20-23). Both functions are blocked by the Master
Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open position signal. The
TCS alarm indication is connected to LED 9.
1MRS756378 D
Section 3
REF615 variants
REF615
53
Application Manual
Functional diagrams for control and interlocking
A071326 V4 EN
Figure 22:
Master trip
The operate signals from the protections described above are connected to the two
trip output contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding
Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit
breaker from local or remote CBXCBR1-exe_op or from the auto-recloser
DARREC1-open_cb are connected directly to the output PO3 (X100:16-19).
The TRPPTRC1 and 2 blocks provide the lockout/latching function, event generation
and the trip signal duration setting. If the lockout operation mode is selected, one
binary input can be re-assigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
Section 3
1MRS756378 D
REF615 variants
54
REF615
Application Manual
A071344 V4 EN
Figure 23:
Circuit breaker control
There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
The remaining two not described in the functional diagram are available in SMT for
connection where applicable.
The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector
(DCSXSWI1) or circuit breaker truck position indication.
Primary device position
Input to be energized
Input 5 (X110:8-9)
Input 6 (X110:10-9)
Busbar disconnector closed
X
Busbar disconnector open
X
CB truck in service position
X
CB truck in test position
X
The binary inputs 7 and 8 (X110:11-13) are for the position indication of the line side
earthing switch.
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. This
can be done by the configuration logic, which is a combination of the disconnector
or breaker truck and earthing switch position statuses and the statuses of the master
1MRS756378 D
Section 3
REF615 variants
REF615
55
Application Manual
trip logics and gas pressure alarm and circuit breaker spring charging. The OKPOS
output from the DCSXSWI block defines if the disconnector or breaker truck is
definitely either open/in test position or close/in service position. This, together with
the open earthing switch and non-active trip signals, activates the close-enable signal
to the circuit breaker control function block. The open operation is always enabled.
The auto-recloser close command signals are directly connected to the output contact
PO1 (X100:6-7).
If the ENA_CLOSE signal is completely removed from the breaker
control function block CBXCBR with SMT, the function assumes
that the breaker close commands are allowed continuously.
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is out in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured current
levels. The function introduces various supervision methods. The corresponding
supervision alarm signals are routed to LED 8.
Section 3
1MRS756378 D
REF615 variants
56
REF615
Application Manual
A071346 V4 EN
Figure 24:
Alarm indication
The signal outputs from the IED are connected to give dedicated information on:
•
start of any protection function SO1 (X100:10-12)
•
operation (trip) of any protection function SO2 (X100:13-15)
•
operation (trip) of any stage of the overcurrent protection function SO2
(X110:17-19)
•
operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-22).
The two TPGAPC blocks 1 and 2 are timers and used for setting the minimum pulse
length for the outputs. There are four generic timers (TPGAPC1..4) available in the
IED. The remaining ones not described in the functional diagram are available in
SMT for connection where applicable.
1MRS756378 D
Section 3
REF615 variants
REF615
57
Application Manual
Standard configuration C including non-directional
earth-fault protection
3.5.1
Applications
The standard configuration for non-directional earth-fault protection is mainly
intended for cable and overhead line feeder applications in directly or resistance
earthed distribution networks. The IED with this standard configuration is delivered
from the factory with default settings and parameters. The end-user flexibility for
incoming, outgoing and internal signal designation within the IED enables this
configuration to be further adapted to different primary circuit layouts and the related
functionality needs by modifying the internal functionality with SMT and PST.
3.5.2
Functions
Table 13:
Functions included in the REF615 standard configuration with non-directional earth-
fault protection
Function
IEC 61850
IEC
ANSI
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1
3I>
51P-1
Three-phase non-directional overcurrent
protection, high stage, instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional overcurrent
protection, high stage, instance 2
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1
3I>>>
50P/51P
Arc protection
ARCSARC1
ARCSARC2
ARCSARC3
ARC (1)
ARC (2)
ARC (3)
50L/50NL (1)
50L/50NL (2)
50L/50NL (3)
Non-directional earth-fault protection, low stage
EFLPTOC1
I0> (1)
51N-1 (1)
Non-directional earth-fault protection, low stage
(Non-directional sensitive earth-fault)
EFLPTOC2
I0> (2)
51N-1 (2)
Non-directional earth-fault protection, high stage
EFHPTOC1
I0>>
51N-2
Non-directional earth-fault protection,
instantaneous stage
EFIPTOC1
I0>>>
50N/51N
Negative-sequence overcurrent protection,
instance 1
NSPTOC1
I2> (1)
46 (1)
Negative-sequence overcurrent protection,
instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity
PDNSPTOC1
I2/I1>
46PD
Three-phase inrush detector
INRPHAR1
3I2f>
68
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1
3Ith>
49F
Autoreclosure
DARREC1
O → I
79
Circuit breaker failure protection
CCBRBRF1
3I>/I0>BF
51BF/51NBF
Table continues on next page
Section 3
1MRS756378 D
REF615 variants
58
REF615
Application Manual
Master Trip (1)
Master Trip (2)
94/86 (1)
94/86 (2)
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Disturbance recorder
RDRE1
-
-
Three-phase current measurement
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Residual current measurement
RESCMMXU1
I0
In
3.5.2.1
Default I/O connections
Binary Input
Default usage
Connector-Pins
X120-BI1
Blocking of Overcurrent Instantaneous Stage
X120-1,2
X120-BI2
Circuit Breaker Closed indication
X120-3,2
X120-BI3
Circuit Breaker Open indication
X120-4,2
X120-BI4
Reset of Master Trip Lockout
X120-5,6
Binary Output
Default usage
Connector-Pins
X100-PO1
Close Circuit Breaker
X100-6,7
X100-PO2
Circuit Breaker Failure protection trip to upstream breaker
X100-8,9
X100-PO3
Open Circuit Breaker / trip coil 1
X100-16,17,18,19
X100-PO4
Open Circuit Breaker / trip coil 2
X100-20,21,22,23
X100-SO1
General Start Indication
X100-10,11,12
X100-SO2
General Operate Indication
X100-13,14,15
LED
Default usage
1
Non-Directional Overcurrent Operate
2
Non-Directional Earth fault Operate
3
Sensitive Earth fault Operate
4
Negative Seq. Overcurrent/Phase Discontinuity Operate
5
Thermal Overload Alarm
6
Breaker Failure Operate
7
Disturbance Recorder Triggered
8
Not connected
9
Trip Circuit Supervision Alarm
10
ARC Protection Operate
11
Auto Reclose in Progress
1MRS756378 D
Section 3
REF615 variants
REF615
59
Application Manual
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed with SMT and
changed according to the application requirements, if necessary.
The analog channels, measurements from CTs and VTs, have fixed connections
towards the different function blocks inside the IED’s standard configuration.
Exceptions from this rule are the 12 analog channels available for the disturbance
recorder function. These channels are freely selectable and a part of the disturbance
recorder’s parameter settings, thus not included in the SMT functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a summation
connection of the phase current transformers.
3.5.3.1
Functional diagrams for protection
The following functional diagrams describe the IED’s protection functionality in
detail and according to the factory set default connections in SMT.
Section 3
1MRS756378 D
REF615 variants
60
REF615
Application Manual
A071348 V3 EN
Figure 25:
Overcurrent protection
Four overcurrent stages are offered for overcurrent and short-circuit protection. The
instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1
(X120:1-2). Two negative sequence overcurrent stages (NPSTOC1 and NPSTOC2)
are offered for phase unbalance protection. The inrush detection block’s
(INRPHAR1) output BLK2H caters the possibility to either block the function or
multiply the active settings for any of the shown protection function blocks.
All operate signals are connected to the Master Trip and also to the alarm LEDs. LED
1 is used for overcurrent and LED 4 for negative sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
There are four IED variant specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter. The change of an
active setting group can also be made via a binary input if the binary input is enabled
1MRS756378 D
Section 3
REF615 variants
REF615
61
Application Manual
for this. To enable the change of an active setting group via a binary input, connect
a free binary input with SMT to the ActSG input of the SGCB-block.
Table 14:
Binary input states and corresponding active setting groups
BI State
Active setting group
OFF
1
ON
2
The active setting group defined by a parameter is overridden when a binary input is
enabled for changing the active setting group.
LED2 (EF OPERATE)
OR
EARTH FAULT PROTECTION
SENSITIVE EARTH FAULT PROTECTION
LED3 (SEF OPERATE)
I >
EFLPTOC1
START
OPERATE
I0
BLOCK
ENA_MULT
51N-1
0
I >
EFLPTOC2
START
OPERATE
I0
BLOCK
ENA_MULT
51N-1
0
I >>
EFHPTOC1
START
OPERATE
I0
BLOCK
ENA_MULT
51N-2
0
I >>>
EFIPTOC1
START
OPERATE
I0
BLOCK
ENA_MULT
50N
0
A071350 V4 EN
Figure 26:
Non-directional earth-fault protection
Four stages are offered for non-directional earth-fault protection. One stage is
dedicated to sensitive earth-fault protection.
All operate signals are connected to the Master Trip and also to the alarm LEDs. LED
2 is used for directional earth-fault and LED 3 for the sensitive earth-fault protection
operate indication.
Section 3
1MRS756378 D
REF615 variants
62
REF615
Application Manual
A071352 V4 EN
Figure 27:
Phase discontinuity, thermal overload and circuit breaker failure
protection
The phase discontinuity protection (PDNSPTOC1) provides protection for
interruptions in the normal three-phase load supply, for example, in downed
conductor situations. The thermal overload protection (T1PTTR1) provides
indication on overload situations. The operate signal of the phase discontinuity
protection is connected to the Master Trip and also to an alarm LED. LED 4 is used
for the phase discontinuity protection operate indication, the same as for negative
sequence overcurrent protection operate indication, and LED 5 is used for the thermal
overload protection alarm indication.
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker position
and the measured phase and residual currents. The breaker failure protection has two
operating outputs: TRRET and TRBU. The TRRET operate output is used for re-
tripping its own breaker through the Master Trip 2. The TRBU output is used to give
a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate
output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up
(TRBU) operate indication.
1MRS756378 D
Section 3
REF615 variants
REF615
63
Application Manual
A071354 V4 EN
Figure 28:
Arc protection
ARC protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as
optional functions.
The ARC protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each ARC protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the ARC protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
The autorecloser is configured to be initiated by operate signals from a number of
protection stages through the INIT1-5 inputs. It is possible to create individual
autoreclosing sequences for each input.
The autoreclosing function can be blocked with the INHIBIT_RECL input. As a
default, the operation of some selected protection functions are connected to this
Section 3
1MRS756378 D
REF615 variants
64
REF615
Application Manual
input. A control command to the circuit breaker, either local or remote, also blocks
the autoreclose function via the CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the
CB_RDY input in DARREC1. In the configuration, this signal is not connected to
any of the binary inputs. As a result, the function assumes that the breaker is available
all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.5.3.2
Functional diagram for disturbance recorder and trip circuit supervision
PHLPTOC1-start
PHHPTOC1-start
PHHPTOC2-start
PHIPTOC1-start
NSPTOC1-start
NSPTOC2-start
EFLPTOC1-start
EFHPTOC1-start
EFIPTOC1-start
EFLPTOC2-start
PDNSPTOC1-start
T1PTTR1-start
CCRBRF1-trret
CCRBRF1-trbu
OR
PHLPTOC1-operate
PHHPTOC1-operate
PHHPTOC2-operate
PHIPTOC1-operate
LED7 (DR TRIGGERED)
OR
OR
EFLPTOC2-operate
PDNSPTOC1-operate
INRPHAR1-blk2h
T1PTTR1-operate
OR
ARCSARC1-operate
ARCSARC2-operate
ARCSARC3-operate
DARREC1-inpro
OR
NSPTOC1-operate
NSPTOC2-operate
ARCSARC1-fault_arc_det
ARCSARC2-fault_arc_det
ARCSARC3-fault_arc_det
EFLPTOC11-operate
EFHPTOC1-operate
EFIPTOC1-operate
DARREC1-close cb
DARREC1-unsuc_recl
BI 1(Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
DISTURBANCE RECORDER
TCSSCBR1
ALARM
BLOCK
TCSSCBR2
ALARM
BLOCK
OR
OR
TRPPTRC1- trip
TRPPTRC2- trip
LED9 (TCS ALARM)
TRIP CIRCUIT SUPERVISION
RDRE1
TRIGGERED
BI#1
BI#2
BI#3
BI#4
BI#5
BI#6
BI#7
BI#8
BI#9
BI#10
BI#11
BI#12
BI#13
BI#14
BI#15
BI#16
BI#17
BI#18
BI#19
BI#20
BI#21
BI#22
BI#23
BI#24
BI#25
BI#26
BI#27
BI#28
BI#29
BI#30
BI#31
BI#32
A071356 V3 EN
Figure 29:
Disturbance recorder
The disturbance recorder has 64 digital inputs, of which 32 are connected as default.
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected autorecloser, the ARC
protection signals and the three binary inputs from X120 are also connected.
Two separate TCS functions are included: TCSSCBR1 for PO3 (X100:16-19) and
TCSSCBR2 for PO4 (X100:20-23). Both functions are blocked by the Master Trip
1MRS756378 D
Section 3
REF615 variants
REF615
65
Application Manual
(TRPPTRC1 and TRPPTRC2) and the circuit breaker open position signal. The TCS
alarm indication is connected to LED 9.
3.5.3.3
Functional diagrams for control and interlocking
A071358 V4 EN
Figure 30:
Master trip
The operate signals from the protections described above are connected to both of
the two trip output contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the
corresponding Master Trips TRPPTRC1 and TRPPTRC2. The open control
commands to the circuit breaker from local or remote CBXCBR1-exe_op or from the
auto-recloser DARREC1-open_cb are connected directly to the output PO3
(X100:16-19).
The TRPPTRC1 and 2 blocks provide the lockout/latching function, event generation
and the trip signal duration setting. In case the lockout operation mode is selected,
the binary input 4 (X120:5-6) is assigned to the RST_LKOUT input of the Master
Trip to enable external reset with a push button.
Section 3
1MRS756378 D
REF615 variants
66
REF615
Application Manual
A071360 V3 EN
Figure 31:
Circuit breaker control
The ENA_CLOSE input, that is, enable the closing of the circuit breaker, in the
breaker control function block CBXCBR is a combination of the status of the Master
Trip. The open operation is always enabled.
If the ENA_CLOSE signal is completely removed from the breaker
control function block CBXCBR with SMT, the function assumes
that the breaker close commands are allowed continuously.
A071362 V3 EN
Figure 32:
Alarm indication
The signal outputs from the IED have been connected to give dedicated information
on:
•
start of any protection function SO1 (X100:10-12)
•
operation (trip) of any protection function SO2 (X100:13-14).
1MRS756378 D
Section 3
REF615 variants
REF615
67
Application Manual
The two TPGAPC blocks 1 and 2 are timers and used for setting the minimum pulse
length for the outputs. There are four generic timers (TPGAPC1..4) available in the
IED. The remaining ones not described in the functional diagram are available in
SMT for connection where applicable.
3.6
Standard configuration D including non-directional
earth-fault protection and CB condition monitoring
3.6.1
Applications
The standard configuration for non-directional earth-fault protection is mainly
intended for cable and overhead line feeder applications in directly or resistance
earthed distribution networks. The IED with this standard configuration is delivered
from the factory with default settings and parameters. The end-user flexibility for
incoming, outgoing and internal signal designation within the IED enables this
configuration to be further adapted to different primary circuit layouts and the related
functionality needs by modifying the internal functionality with SMT and PST.
3.6.2
Functions
Table 15:
Functions included in the REF615 standard configuration with non-directional earth-
fault protection
Function
IEC 61850
IEC
ANSI
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1
3I>
51P-1
Three-phase non-directional overcurrent
protection, high stage, instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional overcurrent
protection, high stage, instance 2
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1
3I>>>
50P/51P
Arc protection
ARCSARC1
ARCSARC2
ARCSARC3
ARC (1)
ARC (2)
ARC (3)
50L/50NL (1)
50L/50NL (2)
50L/50NL (3)
Non-directional earth-fault protection, low stage
EFLPTOC1
I0> (1)
51N-1 (1)
Non-directional earth-fault protection, low stage
(Non-directional sensitive earth-fault)
EFLPTOC2
I0> (2)
51N-1 (2)
Non-directional earth-fault protection, high stage
EFHPTOC1
I0>>
51N-2
Non-directional earth-fault protection,
instantaneous stage
EFIPTOC1
I0>>>
50N/51N
Negative-sequence overcurrent protection,
instance 1
NSPTOC1
I2> (1)
46 (1)
Negative-sequence overcurrent protection,
instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity
PDNSPTOC1
I2/I1>
46PD
Table continues on next page
Section 3
1MRS756378 D
REF615 variants
68
REF615
Application Manual
Three-phase inrush detector
INRPHAR1
3I2f>
68
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1
3Ith>
49F
Autoreclosure
DARREC1
O → I
79
Circuit breaker failure protection
CCBRBRF1
3I>/I0>BF
51BF/51NBF
Master trip
TRPPTRC1
TRPPTRC2
Master Trip (1)
Master Trip (2)
94/86 (1)
94/86 (2)
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Disturbance recorder
RDRE1
-
-
Circuit breaker condition monitoring
SSCBR1
CBCM
CBCM
Three-phase current measurement
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Residual current measurement
RESCMMXU1
I0
In
3.6.2.1
Default I/O connections
Binary Input
Default usage
Connector-Pins
X110-BI2
Auto Reclose External Start Command
X110-3,4
X110-BI3
Circuit Breaker low Gas Pressure indication
X110-5,6
X110-BI4
Circuit Breaker Spring Charged indication
X110-6,7
X110-BI5
CB Truck in (Service position) indication
X110-8,9
X110-BI6
CB Truck out (Test position) indication
X110-10,9
X110-BI7
Earthing Switch Closed indication
X110-11,12
X110-BI8
Earthing Switch Open indication
X110-13,12
X120-BI1
Blocking of Overcurrent Instantaneous Stage
X120-1,2
X120-BI2
Circuit Breaker Closed indication
X120-3,2
X120-BI3
Circuit Breaker Open indication
X120-4,2
X120-BI4
Reset of Master Trip Lockout
X120-5,6
Binary Output
Default usage
Connector-Pins
X100-PO1
Close Circuit Breaker
X100-6,7
X100-PO2
Circuit Breaker Failure protection trip to upstream breaker
X100-8,9
X100-PO3
Open Circuit Breaker / trip coil 1
X100-16,17,18,19
X100-PO4
Open Circuit Breaker / trip coil 2
X100-20,21,22,23
X100-SO1
General Start Indication
X100-10,11,12
X100-SO2
General Operate Indication
X100-13,14,15
X110-SO1
Upstream Overcurrent Blocking
X110-14,15,16
X110-SO2
Overcurrent Operate Alarm
X110-17,18,19
X110-SO3
Earth fault Operate Alarm
X110-20,21,22
1MRS756378 D
Section 3
REF615 variants
REF615
69
Application Manual
Non-Directional Overcurrent Operate
2
Non-Directional Earth fault Operate
3
Sensitive Earth fault Operate
4
Negative Seq. Overcurrent/Phase Discontinuity Operate
5
Thermal Overload Alarm
6
Breaker Failure Operate
7
Disturbance Recorder Triggered
8
Circuit Breaker Condition Monitoring Alarm
9
Trip Circuit Supervision Alarm
10
ARC Protection Operate
11
Auto Reclose in Progress
3.6.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed with SMT and
changed according to the application requirements, if necessary.
The analog channels, measurements from CTs and VTs, have fixed connections
towards the different function blocks inside the IED’s standard configuration.
Exceptions from this rule are the 12 analog channels available for the disturbance
recorder function. These channels are freely selectable and a part of the disturbance
recorder’s parameter settings, thus not included in the SMT functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current, via a summation
connection of the phase current transformers.
3.6.3.1
Functional diagrams for protection
The following functional diagrams describe the IED’s protection functionality in
detail and according to the factory set default connections in SMT.
Section 3
1MRS756378 D
REF615 variants
70
REF615
Application Manual
A071364 V4 EN
Figure 33:
Overcurrent protection
Four overcurrent stages are offered for overcurrent and short-circuit protection. The
instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1
(X120:1-2). Two negative sequence overcurrent stages (NPSTOC1 and NPSTOC2)
are offered for phase unbalance protection. The inrush detection block’s
(INRPHAR1) output BLK2H caters the possibility to either block the function or
multiply the active settings for any of the shown protection function blocks.
All operate signals are connected to the Master Trip and also to the alarm LEDs. LED
1 is used for overcurrent and LED 4 for negative sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for
sending a blocking signal to the relevant overcurrent protection stage of the IED at
the infeeding bay.
There are four IED variant specific setting groups. Parameters can be set
independently for each setting group.
1MRS756378 D
Section 3
REF615 variants
REF615
71
Application Manual
The active setting group (1...4) can be changed with a parameter. The change of an
active setting group can also be made via a binary input if the binary input is enabled
for this. To enable the change of an active setting group via a binary input, connect
a free binary input with SMT to the ActSG input of the SGCB-block.
Table 16:
Binary input states and corresponding active setting groups
BI State
Active setting group
OFF
1
ON
2
The active setting group defined by a parameter is overridden when a binary input is
enabled for changing the active setting group.
LED2 (EF OPERATE)
OR
EARTH FAULT PROTECTION
SENSITIVE EARTH FAULT PROTECTION
LED3 (SEF OPERATE)
I >
EFLPTOC1
START
OPERATE
I0
BLOCK
ENA_MULT
51N-1
0
I >
EFLPTOC2
START
OPERATE
I0
BLOCK
ENA_MULT
51N-1
0
I >>
EFHPTOC1
START
OPERATE
I0
BLOCK
ENA_MULT
51N-2
0
I >>>
EFIPTOC1
START
OPERATE
I0
BLOCK
ENA_MULT
50N
0
A071350 V4 EN
Figure 34:
Non-directional earth-fault protection
Four stages are offered for non-directional earth-fault protection. One stage is
dedicated to sensitive earth-fault protection.
All operate signals are connected to the Master Trip and also to the alarm LEDs. LED
2 is used for directional earth-fault and LED 3 for the sensitive earth-fault protection
operate indication.
Section 3
1MRS756378 D
REF615 variants
72
REF615
Application Manual
A071352 V4 EN
Figure 35:
Phase discontinuity, thermal overload and circuit breaker failure
protection
The phase discontinuity protection (PDNSPTOC1) provides protection for
interruptions in the normal three-phase load supply, for example, in downed
conductor situations. The thermal overload protection (T1PTTR1) provides
indication on overload situations. The operate signal of the phase discontinuity
protection is connected to the Master Trip and also to the alarm LEDs. LED 4 is used
for the phase discontinuity protection operate indication, the same as for negative
sequence overcurrent protection operate indication, and LED 5 is used for the thermal
overload protection alarm indication.
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker position
and the measured phase and residual currents. The breaker failure protection has two
operating outputs: TRRET and TRBU. The TRRET operate output is used for re-
tripping its own breaker through the Master Trip 2. The TRBU output is used to give
a back-up trip to the breaker feeding upstream. For this purpose, the TRBU operate
output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for back-up
(TRBU) operate indication.
1MRS756378 D
Section 3
REF615 variants
REF615
73
Application Manual
A071370 V4 EN
Figure 36:
Arc protection
ARC protection (ARCSARC1-3) and autoreclosing (DARREC1) are included as
optional functions.
The ARC protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each ARC protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the ARC protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
The autorecloser is configured to be initiated by operate signals from a number of
protection stages through the INIT1-5 inputs. The INIT6 input in the autorecloser
function block is controlled by a binary input 2 (X110:3-4) enabling the use of the
Section 3
1MRS756378 D
REF615 variants
74
REF615
Application Manual
external start command. It is possible to create individual autoreclose sequences for
each input.
The autoreclose function can be blocked with the INHIBIT_RECL input. As a default,
the operation of some selected protection functions are connected to this input. A
control command to the circuit breaker, either local or remote, also blocks the
autoreclose function via the CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the
binary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. In
case this signal is completely removed from the autoreclose function block with SMT,
the function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.6.3.2
Functional diagram for disturbance recorder and trip circuit supervision
PHLPTOC1-start
PHHPTOC1-start
PHHPTOC2-start
PHIPTOC1-start
NSPTOC1-start
NSPTOC2-start
EFLPTOC1-start
EFHPTOC1-start
EFIPTOC1-start
EFLPTOC2-start
PDNSPTOC1-start
T1PTTR1-start
CCRBRF1-trret
CCRBRF1-trbu
OR
PHLPTOC1-operate
PHHPTOC1-operate
PHHPTOC2-operate
PHIPTOC1-operate
LED7 (DR TRIGGERED)
OR
OR
EFLPTOC2-operate
PDNSPTOC1-operate
INRPHAR1-blk2h
T1PTTR1-operate
OR
ARCSARC1-operate
ARCSARC2-operate
ARCSARC3-operate
DARREC1-inpro
OR
NSPTOC1-operate
NSPTOC2-operate
ARCSARC1-fault_arc_det
ARCSARC2-fault_arc_det
ARCSARC3-fault_arc_det
EFLPTOC11-operate
EFHPTOC1-operate
EFIPTOC1-operate
DARREC1-close cb
DARREC1-unsuc_recl
BI 1(Blocking)
BI 2 (CB Closed)
BI 3 (CB Open)
DISTURBANCE RECORDER
TCSSCBR1
ALARM
BLOCK
TCSSCBR2
ALARM
BLOCK
OR
OR
TRPPTRC1- trip
TRPPTRC2- trip
LED9 (TCS ALARM)
TRIP CIRCUIT SUPERVISION
RDRE1
TRIGGERED
BI#1
BI#2
BI#3
BI#4
BI#5
BI#6
BI#7
BI#8
BI#9
BI#10
BI#11
BI#12
BI#13
BI#14
BI#15
BI#16
BI#17
BI#18
BI#19
BI#20
BI#21
BI#22
BI#23
BI#24
BI#25
BI#26
BI#27
BI#28
BI#29
BI#30
BI#31
BI#32
X110
3
4
BI 2 (AR ext. start)
A071372 V4 EN
Figure 37:
Disturbance recorder
The disturbance recorder has 64 digital inputs, of which 32 are connected as default.
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected autorecloser, the ARC
1MRS756378 D
Section 3
REF615 variants
REF615
75
Application Manual
protection signals and the three binary inputs from X120 are also connected, as well
as the autorecloser external start command from the binary input 2 (X110:3-4).
Two separate TCS functions are included: TCSSCBR1 for PO3 (X100:16-19) and
TCSSCBR2 for PO4 (X100:20-23). Both functions are blocked by the Master Trip
(TRPPTRC1 and TRPPTRC2) and the circuit breaker open position signal. The TCS
alarm indication is connected to LED 9.
3.6.3.3
Functional diagrams for control and interlocking
A071358 V4 EN
Figure 38:
Master trip
The operate signals from the protections described above are connected to the two
trip output contacts PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding
Master Trips TRPPTRC1 and TRPPTRC2. The open control commands to the circuit
breaker from local or remote CBXCBR1-exe_op or from the auto-recloser
DARREC1-open_cb are connected directly to the output PO3 (X100:16-19).
The TRPPTRC1 and 2 blocks provide the lockout/latching function, event generation
and the trip signal duration setting. If the lockout operation mode is selected, the
binary input 4 (X120:5-6) is assigned to the RST_LKOUT input of the Master Trip
to enable external reset with a push button.
Section 3
1MRS756378 D
REF615 variants
76
REF615
Application Manual
A071376 V4 EN
Figure 39:
Circuit breaker control
There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
The remaining two not described in the functional diagram are available in SMT for
connection where applicable.
The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector
(DCSXSWI1) or circuit breaker truck position indication.
Primary device position
Input to be energized
Input 5 (X110:8-9)
Input 6 (X110:10-9)
Busbar disconnector closed
X
Busbar disconnector open
X
CB truck in service position
X
CB truck in test position
X
The binary inputs 7 and 8 (X110:11-13) are for the position indication of the line side
earthing switch.
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. This
can be done by the configuration logic, which is a combination of the disconnector
or breaker truck and earthing switch position statuses and the statuses of the master
1MRS756378 D
Section 3
REF615 variants
REF615
77
Application Manual
trip logics and gas pressure alarm and circuit breaker spring charging. The OKPOS
output from the DCSXSWI block defines if the disconnector or breaker truck is
definitely either open/in test position or close/in service position. This, together with
the open earthing switch and non-active trip signals, activates the close-enable signal
to the circuit breaker control function block. The open operation is always enabled.
The auto-recloser close command signals are directly connected to the output contact
PO1 (X100:6-7).
If the ENA_CLOSE signal is completely removed from the breaker
control function block CBXCBR with SMT, the function assumes
that the breaker close commands are allowed continuously.
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is out in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured current
levels. The function introduces various supervision methods. The corresponding
supervision alarm signals are routed to LED 8.
Section 3
1MRS756378 D
REF615 variants
78
REF615
Application Manual
A071378 V4 EN
Figure 40:
Alarm indication
The signal outputs from the IED are connected to give dedicated information on:
•
start of any protection function SO1 (X100:10-12)
•
operation (trip) of any protection function SO2 (X100:13-14)
•
operation (trip) of any stage of the overcurrent protection function SO2
(X110:17-19)
•
operation (trip) of any stage of the earth fault protection function SO3
(X110:20-22).
The two TPGAPC blocks 1 and 2 are timers and used for setting the minimum pulse
length for the outputs. There are four generic timers (TPGAPC1..4) available in the
IED. The remaining ones not described in the functional diagram are available in
SMT for connection where applicable.
1MRS756378 D
Section 3
REF615 variants
REF615
79
Application Manual
Standard configuration E including directional earth-
fault protection with phase-voltage measurement
3.7.1
Applications
The standard configuration for directional earth-fault protection is mainly intended
for cable and overhead line feeder applications in isolated and resonant-earthed
distribution networks. The IED with this standard configuration is delivered from the
factory with default settings and parameters. The end-user flexibility for incoming,
outgoing and internal signal designation within the IED enables this configuration to
be further adapted to different primary circuit layouts and the related functionality
needs by modifying the internal functionality using PCM600.
3.7.2
Functions
Table 17:
Functions included in the REF615 standard configuration including directional earth-
fault protection with phase voltage measurement
Function
IEC 61850
IEC
ANSI
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1
3I>
51P-1
Three-phase non-directional overcurrent
protection, high stage, instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional overcurrent
protection, high stage, instance 2
PHHPTOC2
3I>> (2)
51P-2 (2)
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1
3I>>>
50P/51P
Arc protection
ARCSARC1
ARCSARC2
ARCSARC3
ARC (1)
ARC (2)
ARC (3)
50L/50NL (1)
50L/50NL (2)
50L/50NL (3)
Directional earth-fault protection, low stage,
instance 1
DEFLPDEF1
I0> → (1)
67N-1 (1)
Directional earth-fault protection, low stage,
instance 2
DEFLPDEF2
I0> → (2)
67N-1 (2)
Directional earth-fault protection, high stage
DEFHPDEF1
I0>> →
67N-2
Transient/intermittent earth-fault protection
INTRPTEF1
I0> → IEF
67NIEF
Non-directional earth-fault protection, high
stage, calculated I0 current (Double earth-fault
protection)
EFHPTOC1
I0>>
51N-2
Negative-sequence overcurrent protection,
instance 1
NSPTOC1
I2> (1)
46 (1)
Negative-sequence overcurrent protection,
instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity
PDNSPTOC1
I2/I1>
46PD
Three-phase inrush detector
INRPHAR1
3I2f>
68
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1
3Ith>
49F
Table continues on next page
Section 3
1MRS756378 D
REF615 variants
80
REF615
Application Manual
O → I
79
Circuit breaker failure protection
CCBRBRF1
3I>/I0>BF
51BF/51NBF
Master Trip
TRPPTRC1
TRPPTRC2
Master trip (1)
Master trip (2)
94/86 (1)
94/86 (2)
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Disturbance recorder
RDRE1
-
-
Circuit breaker condition monitoring
SSCBR1
CBCM
CBCM
Three-phase current measurement
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Residual current measurement
RESCMMXU1
I0
In
Residual voltage measurement
RESVMMXU1
U0
Vn
Three-phase voltage measurement
VMMXU1
3U
3U
Voltage sequence components measurement
VSMSQI1
U1, U2, U0
U1, U2, U0
Power and energy measurement
PEMMXU1
P, E
P, E
3.7.2.1
Default I/O connections
Binary input
Default usage
Connector pins
X110-BI1
MCB open
X110-1,2
X110-BI2
Directional Earth Fault Protection's Basic Angle
Control
X110-3,4
X110-BI3
Circuit breaker low gas pressure alarm
X110-5,6
X110-BI4
CB spring charged indication
X110-7,6
X110-BI5
CB Truck in (Service position) indication
X110-8,9
X110-BI6
CB Truck out (Test position) indication
X110-10,9
X110-BI7
Earthing switch closed indication
X110-11,12
X110-BI8
Earthing switch open indication
X110-13,12
X120-BI1
Blocking of overcurrent instantaneous stage
X120-1,2
X120-BI2
Circuit Breaker Closed indication
X120-3,2
X120-BI3
Circuit Breaker Open indication
X120-4,2
X120-BI4
Lock-out reset
X120-5,6
Binary output
Default usage
Connector pins
X100-PO1
Close circuit breaker
X100-6,7
X100-PO2
Breaker failure backup trip to upstream breaker
X100-8,9
X100-SO1
General Start indication
X100-10,11,(12)
X100-SO2
General Operate indication
X100-13,14
X100-PO3
Open Circuit Breaker/trip coil 1
X100-15-19
Table continues on next page
1MRS756378 D
Section 3
REF615 variants
REF615
81
Application Manual
Open Circuit Breaker/trip coil 2
X100-20-24
X110-SO1
Upstream Overcurrent Blocking
X110-14,15
X110-SO2
Over current operate Alarm
X110-17,18
X110-SO3
Earth fault operate Alarm
X110-20,21
LED
Default usage
1
Non-directional overcurrent protection operated
2
Directional earth-fault protection operated
3
Non-directional earth-fault protection operated
4
Negative-sequence overcurrent or phase discontinuity protection operated
5
Thermal overload protection operated
6
Circuit-breaker failure protection backup protection operated
7
Disturbance recorder triggered
8
Circuit-breaker condition monitoring alarm
9
Supervision alarm
10
Arc fault detected
11
Autoreclose in progress
3.7.3
Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function-
to-function connections. The default connections can be viewed with SMT and
changed according to the application requirements, if necessary.
The analog channels, measurements from CTs and VTs, have fixed connections
towards the different function blocks inside the IED’s standard configuration.
Exceptions from this rule are the 12 analog channels available for the disturbance
recorder function. These channels are freely selectable and a part of the disturbance
recorder’s parameter settings, thus not included in the SMT functionality.
The analog channels are assigned to different functions as shown in the functional
diagrams. The common signal marked with 3I represents the three phase currents.
The signal marked with I0 represents the measured residual current via a core balance
CT. The signal marked with U0 represents the measured residual voltage via open
delta connected VTs.
The EFHPTOC protection function block for double (cross-country) earth-faults uses
the calculated residual current originating from the measured phase currents.
3.7.3.1
Functional diagrams for protection
The following functional diagrams describe the IED’s protection functionality in
detail and according to the factory set default connections in SMT.
Section 3
1MRS756378 D
REF615 variants
82
REF615
Application Manual
Four overcurrent stages are available for overcurrent and short-circuit protection. The
instantaneous stage (PHIPTOC1) can be blocked by energizing the binary input 1
(X120:1-2). Two negative-sequence overcurrent stages (NSPTOC1 and NSPTOC2)
are available for phase unbalance protection. The inrush detection block’s
(INRPHAR1) output BLK2H enables either blocking the function or multiplying the
active settings for any of the shown protection function blocks.
GUID-37D627C4-6097-4322-BACC-161CC6039EC5 V1 EN
Figure 41:
Overcurrent protection and inrush indication
All operate signals are connected to the Master Trip and also to the alarm LEDs.
LED1 is used for overcurrent and LED 4 for negative sequence overcurrent protection
operate indication. LED 4 is also used for phase discontinuity protection operate
indication.
The upstream blocking from the start of the overcurrent second high stage
(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is used for
sending a blocking signal to the relevant overcurrent protection stage of the IED at
the infeeding bay.
There are four IED variant specific setting groups. Parameters can be set
independently for each setting group.
The active setting group (1...4) can be changed with a parameter or via a binary input
if the binary input is enabled for this. To enable the change of an active setting group
1MRS756378 D
Section 3
REF615 variants
REF615
83
Application Manual
via a binary input, connect a free binary input with SMT to the ActSG input of the
SGCB-block.
Table 18:
Binary input states and corresponding active setting groups
BI state
Active setting group
OFF
1
ON
2
The active setting group defined by a parameter is overridden when a binary input is
enabled for changing the active setting group.
Three stages are offered for directional earth-fault protection. In addition, there is a
dedicated protection stage (INTRPTEF) either for transient based earth-fault
protection or for cable intermittent earth-fault protection in compensated networks.
A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for
protection against double earth-fault situations in isolated or compensated networks.
This protection function uses the calculated residual current originating from the
phase currents.
The binary input 2 (X110:3-4) is intended for directional earth-fault protection
blocks’ Relay Characteristic Angle (RCA: 0°/-90°) or operation mode (I0Sinφ/
I0Cosφ) change. All operate signals are connected to the Master Trip and also to the
alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for double earthfault
protection operate indication.
Section 3
1MRS756378 D
REF615 variants
84
REF615
Application Manual
GUID-1F3C1F26-6F11-4250-9476-82C47C3AC570 V1 EN
Figure 42:
Earth-fault protection
The phase discontinuity protection (PDNSPTOC1) provides protection for
interruptions in the normal three-phase load supply, for example, in downed
conductor situations. The thermal overload protection (T1PTTR1) provides
indication on overload situations. The operate signal of the phase discontinuity
protection is connected to the Master Trip and also to an alarm LED. LED 4 is used
for the phase discontinuity protection operate indication, the same as for negative
sequence overcurrent protection operate indication, and LED 5 is used for the thermal
overload protection alarm indication.
The breaker failure protection (CCBRBRF1) is initiated via the start input by a
number of different protection stages in the IED. The breaker failure protection
function offers different operating modes associated with the circuit breaker position
and the measured phase and residual currents. The breaker failure protection has two
operating outputs: TRRET and TRBU. The TRRET operate output is used for
retripping its own breaker through the Master Trip 2. The TRBU output is used to
give a back-up trip to the breaker feeding upstream. For this purpose, the TRBU
operate output signal is connected to the output PO2 (X100: 8-9). LED 6 is used for
back-up (TRBU) operate indication.
1MRS756378 D
Section 3
REF615 variants
REF615
85
Application Manual
GUID-8BD4614B-2C4D-475E-ADC3-A376E213BF3C V1 EN
Figure 43:
Phase discontinuity, thermal overload and circuit breaker failure
protection
ARC protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as
optional functions.
The ARC protection offers individual function blocks for three ARC sensors that can
be connected to the IED. Each ARC protection function block has two different
operation modes, with or without the phase and residual current check. Operate
signals from the ARC protection function blocks are connected to the Master Trip
and also to the alarm LED 10 as a common operate indication.
Section 3
1MRS756378 D
REF615 variants
86
REF615
Application Manual
GUID-86A27183-AE21-4420-AA8D-B53A43C77BBE V1 EN
Figure 44:
Arc protection
The autorecloser is configured to be initiated by operate signals from a number of
protection stages through the INIT1-5 inputs. It is possible to create individual
autoreclose sequences for each input.
The autoreclose function can be blocked with the INHIBIT_RECL input. As a default,
the operation of some selected protection functions are connected to this input. A
control command to the circuit breaker, either local or remote, also blocks the
autoreclose function via the CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the
binary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. In
case this signal is completely removed from the autoreclose function block with SMT,
the function assumes that the breaker is available all the time.
1MRS756378 D
Section 3
REF615 variants
REF615
87
Application Manual
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.7.3.2
Functional diagram for disturbance recorder and trip circuit supervision
GUID-4BE45287-D708-41F3-851A-084A9AC3265E V1 EN
Figure 45:
Disturbance recorder
The disturbance recorder has 64 digital inputs, of which 35 are connected as default.
All start and operate signals from the protection stages are routed either to trigger the
disturbance recorder or to be recorded by the disturbance recorder, depending on the
parameter settings. Additionally, the selected autorecloser, the ARC protection
signals and the three binary inputs from X120 are also connected.
Two separate TCS functions are included: TCSSCBR1 for PO3 (X100:16-19) and
TCSSCBR2 for PO4 (X100:20-23). Both functions are blocked by the Master Trip
(TRPPTRC1 and TRPPTRC2) and the circuit breaker open position signal. The TCS
alarm indication is connected to LED 9.
Section 3
1MRS756378 D
REF615 variants
88
REF615
Application Manual
The fuse failure supervision provides functionality for detecting failures in voltage
measurement circuits. Failures, such as open miniature circuit breaker, are detected
and the alarm is connected to the supervision alarm LED 9.
Failures in current measuring circuits are detected by the current measuring circuit
supervision function CCRDIF. When a failure is detected, the blocking signal is
activated in current protection functions measuring calculated sequence component
currents, and unnecessary operation can be avoided. The alarm signal is connected
to supervision alarm LED 9.
GUID-48DD2A49-CF29-4088-914B-7AE1629E18CA V1 EN
Figure 46:
Trip circuit supervision
3.7.3.3
Functional diagrams for control and interlocking
The operate signals from the protections are connected to the two trip output contacts
PO3 (X100:16-19) and PO4 (X100:20-23) via the corresponding Master Trips
TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breaker from
local or remote CBXCBR1-exe_op or from the autorecloser DARREC1-open_cb are
connected directly to the output PO3 (X100:16-19).
1MRS756378 D
Section 3
REF615 variants
REF615
89
Application Manual
GUID-4963C315-60C2-4C60-BE7F-B18D87A8D35E V1 EN
Figure 47:
Master trip
The TRPPTRC1 and 2 blocks provide the lockout/latching function, event generation
and the trip signal duration setting. If the lockout operation mode is selected, one
binary input can be re-assigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
There are three disconnector status blocks (DCSXSWI1…3) available in the IED.
The remaining two not described in the functional diagram are available in SMT for
connection where applicable.
Section 3
1MRS756378 D
REF615 variants
90
REF615
Application Manual
GUID-4DED2926-A92A-4F6A-BCAA-7D9CD24ACFC8 V1 EN
Figure 48:
Circuit breaker control
The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector
(DCSXSWI1) or circuit breaker truck position indication.
Table 19:
Device positions indicated by binary inputs 5 and 6
Primary device position
Input to be energized
Input 5 (X110:8-9)
Input 6 (X110:10-9)
Busbar disconnector closed
X
Busbar disconnector open
X
CB truck in service position
X
CB truck in test position
X
The binary inputs 7 and 8 (X110:11-13) are for the position indication of the line side
earthing switch.
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The
input can be activated by the configuration logic, which is a combination of the
disconnector or breaker truck and earthing switch position statuses and the statuses
of the master trip logics and gas pressure alarm and circuit breaker spring charging.
The OKPOS output from the DCSXSWI block defines if the disconnector or breaker
truck is definitely either open/in test position or close/in service position. This,
1MRS756378 D
Section 3
REF615 variants
REF615
91
Application Manual
together with the open earthing switch and non-active trip signals, activates the close-
enable signal to the circuit breaker control function block. The open operation is
always enabled. The autorecloser close command signals are directly connected to
the output contact PO1 (X100:6-7).
If the ENA_CLOSE signal is completely removed from the breaker
control function block CBXCBR with SMT, the function assumes
that the breaker close commands are allowed continuously.
The ITL_BYPASS input can be used, for example, to always enable the closing of
the circuit breaker when the circuit breaker truck is out in the test position, despite of
the interlocking conditions being active when the circuit breaker truck is closed in
service position.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit
breaker status based on the binary input information connected and measured current
levels. The function introduces various supervision methods. The corresponding
supervision alarm signals are routed to LED 8.
GUID-572DA8CC-7A7D-4F9F-87C5-272A4283FB3E V1 EN
Figure 49:
Alarm indication
The signal outputs from the IED are connected to give dedicated information on:
Section 3
1MRS756378 D
REF615 variants
92
REF615
Application Manual
Start of any protection function SO1 (X100:10-12)
•
Operation (trip) of any protection function SO2 (X100:13-14)
•
Operation (trip) of any stage of the overcurrent protection function SO2
(X110:17-19)
•
Operation (trip) of any stage of the earth-fault protection function SO3
(X110:20-22)
The two TPGAPC blocks 1 and 2 are timers and used for setting the minimum pulse
length for the outputs. There are four generic timers (TPGAPC1..4) available in the
IED. The remaining ones not described in the functional diagram are available in
SMT for connection where applicable.
3.8
Standard configuration F including directional
overcurrent protection with voltage protection
3.8.1
Applications
The standard configuration for directional overcurrent protection is mainly intended
for cable and overhead line feeder applications in isolated and resonant-earthed
distribution networks, where directional protections are necessary to improve the
selectivity of the fault detection. The standard configuration includes phase voltage
and residual voltage protection and measurement and also power and energy
measurement.
The IED with this standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and internal
signal designation within the IED enables this configuration to be further adapted to
different primary circuit layouts and the related functionality needs by modifying the
internal functionality with SMT and PST.
3.8.2
Functions
Table 20:
Functions included in the REF615 standard configuration including directional
overcurrent protection with voltage protection
Function
IEC 61850
IEC
ANSI
Three-phase directional overcurrent protection,
low stage, instance 1
DPHLPDOC1
3I> → (1)
67-1 (1)
Three-phase directional overcurrent protection,
low stage, instance 2
DPHLPDOC2
3I> → (2)
67-1 (2)
Three-phase directional overcurrent protection,
high stage
DPHHPDOC1
3I>> →
67-2
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1
3I>>>
50P/51P
Arc protection
ARCSARC1
ARCSARC2
ARCSARC3
ARC (1)
ARC (2)
ARC (3)
50L/50NL (1)
50L/50NL (2)
50L/50NL (3)
Table continues on next page
1MRS756378 D
Section 3
REF615 variants
REF615
93
Application Manual
Directional earth-fault protection, low stage,
instance 1
DEFLPDEF1
I0> → (1)
67N-1 (1)
Directional earth-fault protection, low stage,
instance 2
DEFLPDEF2
I0> → (2)
67N-1 (2)
Directional earth-fault protection, high stage
DEFHPDEF1
I0>> →
67N-2
Transient/intermittent earth-fault protection
INTRPTEF1
I0> → IEF
67NIEF
Non-directional earth-fault protection, high
stage, calculated I0 current (Double earth-fault
protection)
EFHPTOC1
I0>>
51N-2
Negative-sequence overcurrent protection,
instance 1
NSPTOC1
I2> (1)
46 (1)
Negative-sequence overcurrent protection,
instance 2
NSPTOC2
I2> (2)
46 (2)
Phase discontinuity
PDNSPTOC1
I2/I1>
46PD
Three-phase inrush detector
INRPHAR1
3I2f>
68
Three-phase undervoltage protection
PHTUV1
PHTUV2
PHTUV3
3U< (1)
3U< (2)
3U< (3)
27 (1)
27 (2)
27 (3)
Three-phase overvoltage protection
PHTOV1
PHTOV2
PHTOV3
3U> (1)
3U> (2)
3U> (3)
59 (1)
59 (2)
59 (3)
Residual overvoltage protection
ROVPTOV1
ROVPTOV2
ROVPTOV3
U0> (1)
U0> (2)
U0> (3)
59G (1)
59G (2)
59G (3)
Positive-sequence undervoltage protection
PSPTUV
U1<
47U+
Negative-sequence overvoltage protection
NSPTOV
U2>
47O-
Three-phase thermal protection for feeders,
cables and distribution transformers
T1PTTR1
3Ith>
49F
Autoreclosure
DARREC1
O → I
79
Circuit breaker failure protection
CCBRBRF1
3I>/I0>BF
51BF/51NBF
Master Trip
TRPPTRC1
TRPPTRC2
Master trip (1)
Master trip (2)
94/86 (1)
94/86 (2)
Trip circuit supervision, instance 1
TCSSCBR1
TCS (1)
TCM (1)
Trip circuit supervision, instance 2
TCSSCBR2
TCS (2)
TCM (2)
Disturbance recorder
RDRE1
-
-
Circuit breaker condition monitoring
SSCBR1
CBCM
CBCM
Three-phase current measurement
CMMXU1
3I
3I
Sequence current measurement
CSMSQI1
I1, I2, I0
I1, I2, I0
Residual current measurement
RESCMMXU1
I0
In
Residual voltage measurement
RESVMMXU1
U0
Vn
Three-phase voltage measurement
VMMXU1
3U
3U
Voltage sequence components measurement
VSMSQI1
U1, U2, U0
U1, U2, U0
Power and energy measurement
PEMMXU1
P, E
P, E
Section 3
1MRS756378 D
REF615 variants
94
REF615
Application Manual