ABB REG650 ANSI Technical Manual
Read Online
Read the ABB REG650 ANSI Technical Manual online using the built-in PDF viewer.
Text of the manual
Document ID: 1MRK 502 048-UEN
Issued: October 2016
Revision: A
Product version: 1.3
© Copyright 2013 ABB. All rights reserved
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the
OpenSSL Toolkit. (http://www.openssl.org/)
This product includes cryptographic software written/developed by: Eric Young
([email protected]) and Tim Hudson ([email protected]).
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB AB
Grid Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 32 50 00
Facsimile: +46 (0) 21 14 69 18
http://www.abb.com/protection-control
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure
would create a risk for harm to property or persons (including but not limited to
personal injuries or death) shall be the sole responsibility of the person or entity
applying the equipment, and those so responsible are hereby requested to ensure that
all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standards EN 50263 and EN 60255-26 for the EMC directive, and with the product
standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is
designed in accordance with the international standards of the IEC 60255 series.
Table of contents
Section 1
Introduction.....................................................................31
This manual......................................................................................31
Intended audience............................................................................31
Product documentation.....................................................................32
Product documentation set..........................................................32
Document revision history........................................................... 33
Related documents......................................................................33
Symbols and conventions.................................................................34
Symbols.......................................................................................34
Document conventions................................................................35
Section 2
Available functions......................................................... 37
Main protection functions..................................................................37
Back-up protection functions............................................................ 37
Control and monitoring functions......................................................38
Station communication..................................................................... 42
Basic IED functions.......................................................................... 43
Section 3
Analog inputs..................................................................45
Introduction.......................................................................................45
Operation principle........................................................................... 45
Presumptions for technical data....................................................... 46
Settings.............................................................................................47
Section 4
Binary input and output modules....................................53
Binary input.......................................................................................53
Binary input debounce filter.........................................................53
Oscillation filter............................................................................ 53
Settings........................................................................................54
Setting parameters for binary input modules..........................54
Setting parameters for communication module......................55
Section 5
Local Human-Machine-Interface LHMI...........................59
Local HMI screen behaviour.............................................................59
Identification................................................................................ 59
Settings........................................................................................59
Local HMI signals............................................................................. 59
Identification................................................................................ 59
Function block............................................................................. 59
Signals.........................................................................................60
Table of contents
1
Technical manual
Basic part for LED indication module............................................... 60
Identification................................................................................ 60
Function block............................................................................. 60
Signals.........................................................................................61
Settings........................................................................................62
LCD part for HMI function keys control module................................62
Identification................................................................................ 62
Function block............................................................................. 62
Signals.........................................................................................63
Settings........................................................................................63
Operation principle........................................................................... 64
Local HMI.................................................................................... 64
Display....................................................................................64
LEDs.......................................................................................67
Keypad................................................................................... 67
LED..............................................................................................68
Functionality........................................................................... 68
Status LEDs........................................................................... 69
Indication LEDs...................................................................... 69
Function keys.............................................................................. 77
Functionality........................................................................... 77
Operation principle................................................................. 77
Section 6
Differential protection..................................................... 81
Transformer differential protection....................................................81
Functionality ............................................................................... 81
Transformer differential protection, three winding T3WPDIF ..... 82
Identification........................................................................... 82
Function block........................................................................ 82
Signals....................................................................................82
Settings.................................................................................. 83
Monitored data....................................................................... 85
Operation principle...................................................................... 85
Function calculation principles............................................... 86
Fundamental frequency differential currents.......................... 87
Differential current alarm........................................................ 92
Bias current............................................................................ 92
Elimination of zero sequence currents................................... 92
Restrained and unrestrained limits of the differential
protection................................................................................93
Fundamental frequency negative sequence differential
currents.................................................................................. 95
Internal/external fault discriminator........................................ 97
Unrestrained, and sensitive negative sequence protections 100
Table of contents
2
Technical manual
Instantaneous differential currents....................................... 102
Harmonic and waveform block criteria................................. 102
Switch onto fault feature.......................................................103
Logic diagram.......................................................................104
Technical data........................................................................... 109
Restricted earth-fault protection, low impedance REFPDIF .......... 109
Identification.............................................................................. 109
Functionality.............................................................................. 110
Function block........................................................................... 110
Signals.......................................................................................110
Settings......................................................................................111
Monitored data...........................................................................111
Operation principle.................................................................... 112
Fundamental principles of the restricted earth-fault
protection..............................................................................112
Operate and restrain characteristic...................................... 114
Calculation of differential current and bias current............... 115
Detection of external earth faults..........................................116
Algorithm of the restricted earth-fault protection.................. 117
Technical data........................................................................... 118
1Ph High impedance differential protection HZPDIF .....................118
Identification.............................................................................. 118
Introduction................................................................................119
Function block........................................................................... 119
Signals.......................................................................................119
Settings......................................................................................120
Monitored data...........................................................................120
Operation principle.................................................................... 120
Logic diagram.......................................................................120
Technical data........................................................................... 121
Generator differential protection GENPDIF ................................... 121
Identification.............................................................................. 121
Functionality.............................................................................. 122
Function block........................................................................... 123
Signals.......................................................................................123
Settings......................................................................................124
Operation principle.................................................................... 125
Function calculation principles............................................. 126
Fundamental frequency differential currents........................ 126
Supplementary criteria......................................................... 131
Harmonic restrain................................................................. 134
Cross-block logic scheme.................................................... 134
Simplified block diagrams.....................................................134
Table of contents
3
Technical manual
Technical data........................................................................... 137
Section 7
Impedance protection...................................................139
Power swing detection ZMRPSB ...................................................139
Identification.............................................................................. 139
Functionality.............................................................................. 139
Function block........................................................................... 139
Signals.......................................................................................140
Settings......................................................................................140
Operation principle.................................................................... 141
Resistive reach in forward direction..................................... 142
Resistive reach in reverse direction..................................... 143
Reactive reach in forward and reverse direction.................. 144
Basic detection logic.............................................................144
Operating and inhibit conditions...........................................146
Technical data........................................................................... 146
Underimpedance protection for generators and transformers
ZGCPDIS........................................................................................146
Identification.............................................................................. 146
Functionality.............................................................................. 147
Function block........................................................................... 147
Signals.......................................................................................148
Settings......................................................................................148
Operation principle.................................................................... 149
Full scheme measurement................................................... 149
Impedance characteristic..................................................... 149
Basic operation characteristics.............................................150
Theory of operation.............................................................. 151
Technical data........................................................................... 153
Loss of excitation LEXPDIS............................................................153
Identification.............................................................................. 153
Functionality.............................................................................. 153
Function block........................................................................... 154
Signals.......................................................................................154
Settings......................................................................................155
Monitored data...........................................................................156
Operation principle.................................................................... 156
Technical data........................................................................... 160
Out-of-step protection OOSPPAM..................................................160
Identification.............................................................................. 160
Functionality.............................................................................. 160
Function block........................................................................... 161
Signals.......................................................................................161
Settings......................................................................................162
Table of contents
4
Technical manual
Operation principle.................................................................... 163
Lens characteristic............................................................... 166
Detecting an out-of-step condition........................................168
Maximum slip frequency.......................................................169
Taking care of the circuit breaker soundness.......................170
Design.................................................................................. 172
Technical data........................................................................... 172
Load encroachment LEPDIS .........................................................173
Identification.............................................................................. 173
Functionality.............................................................................. 173
Function block........................................................................... 173
Signals.......................................................................................173
Settings......................................................................................174
Operation principle.................................................................... 174
Load encroachment..............................................................174
Simplified logic diagrams......................................................175
Technical data........................................................................... 176
Section 8
Current protection.........................................................177
Four step phase overcurrent protection 3-phase output
OC4PTOC ..................................................................................... 177
Identification ............................................................................. 177
Functionality.............................................................................. 177
Function block........................................................................... 178
Signals.......................................................................................178
Settings......................................................................................179
Monitored data...........................................................................181
Operation principle.................................................................... 181
Second harmonic blocking element...........................................185
Technical data........................................................................... 186
Four step residual overcurrent protection, zero, negative
sequence direction EF4PTOC .......................................................186
Identification ............................................................................. 186
Functionality.............................................................................. 187
Function block........................................................................... 187
Signals.......................................................................................188
Settings......................................................................................189
Monitored data...........................................................................191
Operation principle.................................................................... 191
Operating quantity within the function.................................. 192
Internal polarizing.................................................................193
External polarizing for earth-fault function............................195
Base quantities within the protection....................................196
Table of contents
5
Technical manual
Internal earth-fault protection structure................................ 196
Four residual overcurrent steps............................................196
Directional supervision element with integrated
directional comparison function............................................197
Second harmonic blocking element...........................................201
Technical data........................................................................... 202
Sensitive directional residual overcurrent and power protection
SDEPSDE ..................................................................................... 203
Identification.............................................................................. 203
Functionality.............................................................................. 203
Function block........................................................................... 204
Signals.......................................................................................204
Settings......................................................................................205
Monitored data...........................................................................206
Operation principle ................................................................... 206
Function inputs.....................................................................206
Directional residual current protection measuring 3I0·cos φ.207
Directional residual power protection measuring 3I0 · 3U0
· cos φ...................................................................................209
Directional residual current protection measuring 3I0 and φ 210
Directional functions.............................................................211
Non-directional earth fault current protection....................... 211
Residual overvoltage release and protection....................... 211
Technical data........................................................................... 213
Thermal overload protection, two time constants TRPTTR ...........214
Identification ............................................................................. 214
Functionality.............................................................................. 214
Function block........................................................................... 215
Signals.......................................................................................215
Settings......................................................................................216
Monitored data...........................................................................217
Operation principle.................................................................... 217
Technical data........................................................................... 221
Breaker failure protection 3-phase activation and output CCRBRF 221
Identification.............................................................................. 221
Functionality.............................................................................. 221
Function block........................................................................... 222
Signals.......................................................................................222
Settings......................................................................................223
Monitored data...........................................................................223
Operation principle.................................................................... 224
Technical data........................................................................... 226
Pole discordance protection CCRPLD .......................................... 227
Table of contents
6
Technical manual
Identification ............................................................................. 227
Functionality.............................................................................. 227
Function block........................................................................... 227
Signals.......................................................................................228
Settings......................................................................................228
Monitored data...........................................................................229
Operation principle.................................................................... 229
Pole discordance signaling from circuit breaker...................230
Unsymmetrical current detection..........................................230
Technical data........................................................................... 231
Directional over-/under-power protection GOPPDOP/GUPPDUP. 231
Functionality.............................................................................. 231
Directional overpower protection GOPPDOP ...........................232
Identification......................................................................... 232
Function block...................................................................... 232
Signals..................................................................................232
Settings................................................................................ 233
Monitored data..................................................................... 234
Directional underpower protection GUPPDUP..........................234
Identification......................................................................... 234
Function block...................................................................... 234
Signals..................................................................................235
Settings................................................................................ 235
Monitored data..................................................................... 236
Operation principle.................................................................... 236
Low pass filtering..................................................................238
Technical data........................................................................... 239
Accidental energizing protection for synchronous generator
AEGGAPC......................................................................................239
Identification.............................................................................. 239
Functionality ............................................................................. 239
Function block........................................................................... 240
Signals.......................................................................................240
Settings......................................................................................241
Monitored data...........................................................................241
Operation principle.................................................................... 241
Technical data........................................................................... 242
Negative-sequence time overcurrent protection for machines
NS2PTOC ......................................................................................243
Identification.............................................................................. 243
Functionality.............................................................................. 243
Function block........................................................................... 244
Signals.......................................................................................244
Settings......................................................................................245
Table of contents
7
Technical manual
Operation principle.................................................................... 246
Start sensitivity..................................................................... 248
Alarm function...................................................................... 248
Logic diagram.......................................................................248
Technical data........................................................................... 249
Voltage-restrained time overcurrent protection VRPVOC.............. 249
Identification.............................................................................. 249
Functionality.............................................................................. 249
Function block........................................................................... 250
Signals.......................................................................................250
Settings......................................................................................251
Monitored data...........................................................................252
Operation principle.................................................................... 252
Measured quantities.............................................................252
Base quantities.....................................................................252
Overcurrent protection..........................................................252
Logic diagram.......................................................................254
Undervoltage protection....................................................... 254
Technical data........................................................................... 255
Section 9
Voltage protection........................................................ 257
Two step undervoltage protection UV2PTUV ................................257
Identification.............................................................................. 257
Functionality.............................................................................. 257
Function block........................................................................... 257
Signals.......................................................................................258
Settings......................................................................................258
Monitored data...........................................................................259
Operation principle.................................................................... 259
Measurement principle.........................................................260
Time delay............................................................................260
Blocking................................................................................261
Design.................................................................................. 261
Technical data........................................................................... 262
Two step overvoltage protection OV2PTOV ..................................263
Identification.............................................................................. 263
Functionality.............................................................................. 263
Function block........................................................................... 264
Signals.......................................................................................264
Settings......................................................................................265
Monitored data...........................................................................265
Operation principle.................................................................... 266
Measurement principle.........................................................266
Table of contents
8
Technical manual
Technical data........................................................................... 270
Two step residual overvoltage protection ROV2PTOV ................. 270
Identification.............................................................................. 270
Functionality.............................................................................. 270
Function block........................................................................... 271
Signals.......................................................................................271
Settings......................................................................................271
Monitored data...........................................................................272
Operation principle.................................................................... 272
Measurement principle.........................................................273
Time delay............................................................................273
Blocking................................................................................273
Design.................................................................................. 273
Technical data........................................................................... 275
Overexcitation protection OEXPVPH ............................................ 275
Identification.............................................................................. 275
Functionality.............................................................................. 275
Function block........................................................................... 276
Signals.......................................................................................276
Settings......................................................................................276
Monitored data...........................................................................277
Operation principle.................................................................... 277
Measured voltage.................................................................279
Operate time of the overexcitation protection.......................280
Cooling................................................................................. 282
Overexcitation protection function measurands................... 283
Overexcitation alarm............................................................ 283
Logic diagram.......................................................................284
Technical data........................................................................... 284
100% Stator earth fault protection, 3rd harmonic based STEFPHIZ285
Identification.............................................................................. 285
Functionality.............................................................................. 285
Function block........................................................................... 286
Signals.......................................................................................286
Settings......................................................................................287
Monitored data...........................................................................288
Operation principle.................................................................... 288
Technical data........................................................................... 293
Section 10 Frequency protection....................................................295
Underfrequency protection SAPTUF ............................................. 295
Table of contents
9
Technical manual
Function block........................................................................... 295
Signals.......................................................................................296
Settings......................................................................................296
Monitored data...........................................................................296
Operation principle.................................................................... 296
Measurement principle.........................................................297
Time delay............................................................................297
Blocking................................................................................298
Design.................................................................................. 298
Technical data........................................................................... 298
Overfrequency protection SAPTOF ...............................................298
Identification.............................................................................. 299
Functionality.............................................................................. 299
Function block........................................................................... 299
Signals.......................................................................................299
Settings......................................................................................300
Monitored data...........................................................................300
Operation principle.................................................................... 300
Measurement principle.........................................................300
Time delay............................................................................301
Blocking................................................................................301
Design.................................................................................. 301
Technical data........................................................................... 302
Rate-of-change frequency protection SAPFRC .............................302
Identification.............................................................................. 303
Functionality.............................................................................. 303
Function block........................................................................... 303
Signals.......................................................................................303
Settings......................................................................................304
Operation principle.................................................................... 304
Measurement principle.........................................................304
Time delay............................................................................304
Design.................................................................................. 305
Technical data........................................................................... 306
Section 11 Secondary system supervision.....................................307
Fuse failure supervision SDDRFUF............................................... 307
Identification.............................................................................. 307
Functionality.............................................................................. 307
Function block........................................................................... 308
Signals.......................................................................................308
Settings......................................................................................309
Table of contents
10
Technical manual
Operation principle.................................................................... 310
Zero and negative sequence detection................................ 310
Delta current and delta voltage detection.............................311
Dead line detection...............................................................314
Main logic............................................................................. 314
Technical data........................................................................... 318
Breaker close/trip circuit monitoring TCSSCBR............................. 318
Identification.............................................................................. 318
Functionality.............................................................................. 318
Function block........................................................................... 318
Signals.......................................................................................319
Settings......................................................................................319
Operation principle.................................................................... 319
Technical data........................................................................... 320
Section 12 Control..........................................................................321
Synchrocheck, energizing check, and synchronizing SESRSYN...321
Identification.............................................................................. 321
Functionality.............................................................................. 321
Function block........................................................................... 322
Signals.......................................................................................322
Settings......................................................................................324
Monitored data...........................................................................326
Operation principle.................................................................... 327
Basic functionality.................................................................327
Synchrocheck.......................................................................327
Synchronizing.......................................................................329
Energizing check..................................................................330
Fuse failure supervision....................................................... 331
Voltage selection..................................................................331
Voltage selection for a single circuit breaker with double
busbars.................................................................................332
Voltage selection for a 1 1/2 circuit breaker arrangement....333
Technical data........................................................................... 337
Apparatus control........................................................................... 338
Functionality.............................................................................. 338
Switch controller SCSWI........................................................... 338
Identification ........................................................................ 338
Functionality......................................................................... 338
Function block...................................................................... 339
Signals..................................................................................339
Settings................................................................................ 340
Circuit breaker SXCBR..............................................................340
Table of contents
11
Technical manual
Circuit switch SXSWI.................................................................341
Signals..................................................................................341
Settings................................................................................ 342
Bay control QCBAY...................................................................343
Identification ........................................................................ 343
Functionality......................................................................... 343
Function block...................................................................... 343
Signals..................................................................................343
Settings................................................................................ 344
Local remote LOCREM............................................................. 344
Identification ........................................................................ 344
Functionality......................................................................... 344
Function block...................................................................... 344
Signals..................................................................................344
Settings................................................................................ 345
Local remote control LOCREMCTRL........................................ 345
Identification ........................................................................ 345
Functionality......................................................................... 345
Function block...................................................................... 346
Signals..................................................................................346
Settings................................................................................ 347
Select release SELGGIO...........................................................347
Identification......................................................................... 347
Function block...................................................................... 347
Signals..................................................................................347
Settings................................................................................ 348
Operation principle.................................................................... 348
Switch controller SCSWI...................................................... 348
Bay control QCBAY..............................................................352
Local remote/Local remote control LOCREM/
LOCREMCTRL.....................................................................354
Interlocking..................................................................................... 355
Functionality.............................................................................. 355
Logical node for interlocking SCILO .........................................355
Identification......................................................................... 355
Functionality......................................................................... 355
Function block...................................................................... 355
Logic diagram.......................................................................356
Signals..................................................................................356
Settings................................................................................ 357
Interlocking for busbar earthing switch BB_ES .........................357
Table of contents
12
Technical manual
Function block...................................................................... 357
Logic diagram.......................................................................357
Signals..................................................................................358
Settings................................................................................ 358
Interlocking for bus-section breaker A1A2_BS..........................358
Identification......................................................................... 358
Functionality......................................................................... 358
Function block...................................................................... 359
Logic diagram.......................................................................360
Signals..................................................................................361
Settings................................................................................ 363
Interlocking for bus-section disconnector A1A2_DC ................ 363
Identification......................................................................... 363
Functionality......................................................................... 363
Function block...................................................................... 364
Logic diagram.......................................................................364
Signals..................................................................................364
Settings................................................................................ 365
Interlocking for bus-coupler bay ABC_BC ................................ 365
Identification......................................................................... 366
Functionality......................................................................... 366
Function block...................................................................... 367
Logic diagram.......................................................................367
Signals..................................................................................370
Settings................................................................................ 372
Interlocking for 1 1/2 CB BH .....................................................372
Identification......................................................................... 372
Functionality......................................................................... 373
Function block...................................................................... 374
Logic diagrams.....................................................................376
Signals..................................................................................381
Settings................................................................................ 385
Interlocking for double CB bay DB ........................................... 385
Identification......................................................................... 385
Functionality......................................................................... 386
Function block...................................................................... 387
Logic diagrams.....................................................................388
Signals..................................................................................391
Settings................................................................................ 394
Interlocking for line bay ABC_LINE .......................................... 394
Identification......................................................................... 394
Table of contents
13
Technical manual
Function block...................................................................... 396
Logic diagram.......................................................................397
Signals..................................................................................402
Settings................................................................................ 404
Interlocking for transformer bay AB_TRAFO ............................404
Identification......................................................................... 405
Functionality......................................................................... 405
Function block...................................................................... 406
Logic diagram.......................................................................406
Signals..................................................................................408
Settings................................................................................ 409
Position evaluation POS_EVAL.................................................410
Identification......................................................................... 410
Functionality......................................................................... 410
Function block...................................................................... 410
Logic diagram.......................................................................410
Signals..................................................................................411
Settings................................................................................ 411
Operation principle.................................................................... 411
Logic rotating switch for function selection and LHMI
presentation SLGGIO.....................................................................414
Identification.............................................................................. 414
Functionality.............................................................................. 414
Function block........................................................................... 415
Signals.......................................................................................415
Settings......................................................................................416
Monitored data...........................................................................417
Operation principle.................................................................... 417
Selector mini switch VSGGIO.........................................................417
Identification.............................................................................. 417
Functionality.............................................................................. 418
Function block........................................................................... 418
Signals.......................................................................................418
Settings......................................................................................419
Operation principle.................................................................... 419
IEC 61850 generic communication I/O functions DPGGIO............ 420
Identification.............................................................................. 420
Functionality.............................................................................. 420
Function block........................................................................... 420
Signals.......................................................................................420
Settings......................................................................................421
Operation principle.................................................................... 421
Table of contents
14
Technical manual
Single point generic control 8 signals SPC8GGIO......................... 421
Identification.............................................................................. 421
Functionality.............................................................................. 421
Function block........................................................................... 421
Signals.......................................................................................422
Settings......................................................................................422
Operation principle.................................................................... 423
Automation bits AUTOBITS............................................................423
Identification.............................................................................. 423
Functionality.............................................................................. 423
Function block........................................................................... 424
Signals.......................................................................................424
Settings......................................................................................425
Operation principle.................................................................... 425
Function commands for IEC 60870-5-103 I103CMD..................... 426
Functionality.............................................................................. 426
Function block........................................................................... 426
Signals.......................................................................................426
Settings......................................................................................427
IED commands for IEC 60870-5-103 I103IEDCMD....................... 427
Functionality.............................................................................. 427
Function block........................................................................... 427
Signals.......................................................................................427
Settings......................................................................................428
Function commands user defined for IEC 60870-5-103
I103USRCMD.................................................................................428
Functionality.............................................................................. 428
Function block........................................................................... 428
Signals.......................................................................................428
Settings......................................................................................429
Function commands generic for IEC 60870-5-103 I103GENCMD.429
Functionality.............................................................................. 429
Function block........................................................................... 430
Signals.......................................................................................430
Settings......................................................................................430
IED commands with position and select for IEC 60870-5-103
I103POSCMD.................................................................................430
Functionality.............................................................................. 430
Function block........................................................................... 431
Signals.......................................................................................431
Settings......................................................................................431
Section 13 Logic.............................................................................433
Tripping logic common 3-phase output SMPPTRC........................433
Table of contents
15
Technical manual
Function block........................................................................... 433
Signals.......................................................................................434
Settings......................................................................................434
Operation principle.................................................................... 434
Technical data........................................................................... 435
Trip matrix logic TMAGGIO............................................................ 435
Identification.............................................................................. 435
Functionality.............................................................................. 435
Function block........................................................................... 436
Signals.......................................................................................436
Settings......................................................................................437
Operation principle.................................................................... 438
Configurable logic blocks................................................................439
Standard configurable logic blocks............................................439
Functionality......................................................................... 439
OR function block.................................................................441
Inverter function block INVERTER....................................... 442
PULSETIMER function block .............................................. 443
Controllable gate function block GATE................................ 444
Exclusive OR function block XOR........................................ 445
Loop delay function block LOOPDELAY.............................. 446
Timer function block TIMERSET.......................................... 447
AND function block ..............................................................448
Set-reset memory function block SRMEMORY....................449
Reset-set with memory function block RSMEMORY........... 450
Technical data........................................................................... 452
Fixed signals FXDSIGN..................................................................453
Identification.............................................................................. 453
Functionality.............................................................................. 453
Function block........................................................................... 453
Signals.......................................................................................453
Settings......................................................................................454
Operation principle.................................................................... 454
Boolean 16 to integer conversion B16I...........................................454
Identification.............................................................................. 454
Functionality.............................................................................. 454
Function block........................................................................... 455
Signals.......................................................................................455
Settings......................................................................................456
Monitored data...........................................................................456
Operation principle.................................................................... 456
Table of contents
16
Technical manual
Boolean 16 to integer conversion with logic node representation
B16IFCVI........................................................................................457
Identification.............................................................................. 457
Functionality.............................................................................. 457
Function block........................................................................... 458
Signals.......................................................................................458
Settings......................................................................................459
Monitored data...........................................................................459
Operation principle.................................................................... 459
Integer to boolean 16 conversion IB16A........................................ 460
Identification.............................................................................. 460
Functionality.............................................................................. 460
Function block........................................................................... 460
Signals.......................................................................................461
Settings......................................................................................461
Operation principle.................................................................... 461
Integer to boolean 16 conversion with logic node representation
IB16FCVB.......................................................................................463
Identification.............................................................................. 463
Functionality.............................................................................. 463
Function block........................................................................... 463
Signals.......................................................................................463
Settings......................................................................................464
Operation principle.................................................................... 464
Elapsed time integrator with limit transgression and overflow
supervision TEIGGIO..................................................................... 465
Identification.............................................................................. 465
Functionality.............................................................................. 466
Function block........................................................................... 466
Signals.......................................................................................466
Settings......................................................................................467
Operation principle.................................................................... 467
Operation Accuracy..............................................................468
Memory storage................................................................... 468
Technical data........................................................................... 469
Section 14 Monitoring.....................................................................471
Measurements................................................................................471
Functionality.............................................................................. 471
Measurements CVMMXN..........................................................472
Identification ........................................................................ 472
Function block...................................................................... 473
Signals..................................................................................473
Settings................................................................................ 474
Table of contents
17
Technical manual
Monitored data..................................................................... 477
Phase current measurement CMMXU.......................................477
Identification ........................................................................ 477
Function block...................................................................... 478
Signals..................................................................................478
Settings................................................................................ 478
Monitored data..................................................................... 479
Phase-phase voltage measurement VMMXU........................... 480
Identification ........................................................................ 480
Function block...................................................................... 480
Signals..................................................................................480
Settings................................................................................ 481
Monitored data..................................................................... 481
Current sequence component measurement CMSQI............... 482
Identification ........................................................................ 482
Function block...................................................................... 482
Signals..................................................................................482
Settings................................................................................ 483
Monitored data..................................................................... 484
Voltage sequence measurement VMSQI.................................. 484
Identification ........................................................................ 484
Function block...................................................................... 485
Signals..................................................................................485
Settings................................................................................ 486
Monitored data..................................................................... 487
Phase-neutral voltage measurement VNMMXU........................487
Identification ........................................................................ 487
Function block...................................................................... 487
Signals..................................................................................488
Settings................................................................................ 488
Monitored data..................................................................... 489
Operation principle.................................................................... 489
Measurement supervision.................................................... 489
Measurements CVMMXN.....................................................494
Phase current measurement CMMXU................................. 499
Phase-phase and phase-neutral voltage measurements
VMMXU, VNMMXU.............................................................. 500
Voltage and current sequence measurements VMSQI,
CMSQI..................................................................................500
Technical data........................................................................... 500
Event Counter CNTGGIO...............................................................501
Identification.............................................................................. 501
Functionality.............................................................................. 501
Function block........................................................................... 501
Table of contents
18
Technical manual
Operation principle.................................................................... 502
Reporting..............................................................................503
Technical data........................................................................... 503
Function description....................................................................... 503
Limit counter L4UFCNT.............................................................503
Introduction................................................................................503
Principle of operation.................................................................504
Design.................................................................................. 504
Reporting..............................................................................505
Function block........................................................................... 505
Signals.......................................................................................506
Settings......................................................................................506
Monitored data...........................................................................507
Technical data........................................................................... 507
Disturbance report..........................................................................507
Functionality.............................................................................. 507
Disturbance report DRPRDRE.................................................. 508
Identification......................................................................... 508
Function block...................................................................... 508
Signals..................................................................................508
Settings................................................................................ 508
Monitored data..................................................................... 509
Analog input signals AxRADR...................................................512
Identification......................................................................... 512
Function block...................................................................... 513
Signals..................................................................................513
Settings................................................................................ 514
Analog input signals A4RADR...................................................517
Identification......................................................................... 517
Function block...................................................................... 517
Signals..................................................................................518
Settings................................................................................ 518
Binary input signals BxRBDR....................................................522
Identification......................................................................... 522
Function block...................................................................... 522
Signals..................................................................................522
Settings................................................................................ 523
Operation principle.................................................................... 528
Disturbance information....................................................... 530
Indications ........................................................................... 530
Table of contents
19
Technical manual
Event recorder .....................................................................530
Event list ..............................................................................530
Trip value recorder .............................................................. 530
Disturbance recorder ...........................................................530
Time tagging.........................................................................530
Recording times................................................................... 530
Analog signals......................................................................531
Binary signals.......................................................................533
Trigger signals......................................................................533
Post Retrigger...................................................................... 534
Technical data........................................................................... 535
Indications...................................................................................... 535
Functionality.............................................................................. 535
Function block........................................................................... 536
Signals.......................................................................................536
Input signals......................................................................... 536
Operation principle.................................................................... 536
Technical data........................................................................... 537
Event recorder ...............................................................................537
Functionality.............................................................................. 537
Function block........................................................................... 537
Signals.......................................................................................537
Input signals......................................................................... 537
Operation principle.................................................................... 537
Technical data........................................................................... 538
Event list.........................................................................................538
Functionality.............................................................................. 538
Function block........................................................................... 538
Signals.......................................................................................539
Input signals......................................................................... 539
Operation principle.................................................................... 539
Technical data........................................................................... 539
Trip value recorder......................................................................... 539
Functionality.............................................................................. 539
Function block........................................................................... 540
Signals.......................................................................................540
Input signals......................................................................... 540
Operation principle.................................................................... 540
Technical data........................................................................... 541
Disturbance recorder......................................................................541
Functionality.............................................................................. 541
Function block........................................................................... 541
Signals.......................................................................................541
Table of contents
20
Technical manual
Operation principle.................................................................... 542
Memory and storage............................................................ 542
Technical data........................................................................... 544
IEC 61850 generic communication I/O functions SPGGIO............ 544
Identification.............................................................................. 544
Functionality.............................................................................. 544
Function block........................................................................... 544
Signals.......................................................................................544
Settings......................................................................................545
Operation principle.................................................................... 545
IEC 61850 generic communication I/O functions 16 inputs
SP16GGIO..................................................................................... 545
Identification.............................................................................. 545
Functionality.............................................................................. 545
Function block........................................................................... 545
Signals.......................................................................................546
Settings......................................................................................546
MonitoredData...........................................................................546
Operation principle.................................................................... 547
IEC 61850 generic communication I/O functions MVGGIO............547
Identification.............................................................................. 547
Functionality.............................................................................. 548
Function block........................................................................... 548
Signals.......................................................................................548
Settings......................................................................................548
Monitored data...........................................................................549
Operation principle.................................................................... 549
Measured value expander block MVEXP....................................... 549
Identification.............................................................................. 549
Functionality.............................................................................. 550
Function block........................................................................... 550
Signals.......................................................................................550
Settings......................................................................................550
Operation principle.................................................................... 551
Station battery supervision SPVNZBAT......................................... 551
Identification.............................................................................. 551
Function block........................................................................... 551
Functionality.............................................................................. 551
Signals.......................................................................................552
Settings......................................................................................552
Measured values....................................................................... 553
Monitored Data..........................................................................553
Table of contents
21
Technical manual
Operation principle ................................................................... 553
Technical data........................................................................... 554
Insulation gas monitoring function SSIMG..................................... 554
Identification.............................................................................. 554
Functionality.............................................................................. 555
Function block........................................................................... 555
Signals.......................................................................................555
Settings......................................................................................556
Operation principle.................................................................... 556
Technical data........................................................................... 557
Insulation liquid monitoring function SSIML....................................557
Identification.............................................................................. 557
Functionality.............................................................................. 557
Function block........................................................................... 557
Signals.......................................................................................558
Settings......................................................................................558
Operation principle.................................................................... 559
Technical data........................................................................... 559
Circuit breaker condition monitoring SSCBR..................................559
Identification.............................................................................. 559
Functionality.............................................................................. 560
Function block........................................................................... 560
Signals.......................................................................................560
Settings......................................................................................561
Monitored data...........................................................................562
Operation principle.................................................................... 563
Circuit breaker status........................................................... 564
Circuit breaker operation monitoring.................................... 565
Breaker contact travel time...................................................566
Operation counter.................................................................567
Accumulation of Iyt................................................................568
Remaining life of the circuit breaker..................................... 570
Circuit breaker spring charged indication............................. 571
Gas pressure supervision.....................................................572
Technical data........................................................................... 573
Measurands for IEC 60870-5-103 I103MEAS................................ 573
Functionality.............................................................................. 573
Function block........................................................................... 574
Signals.......................................................................................575
Settings......................................................................................575
Measurands user defined signals for IEC 60870-5-103
I103MEASUSR...............................................................................576
Functionality.............................................................................. 576
Table of contents
22
Technical manual
Function block........................................................................... 576
Signals.......................................................................................576
Settings......................................................................................577
Function status auto-recloser for IEC 60870-5-103 I103AR...........577
Functionality.............................................................................. 577
Function block........................................................................... 577
Signals.......................................................................................578
Settings......................................................................................578
Function status earth-fault for IEC 60870-5-103 I103EF................578
Functionality.............................................................................. 578
Function block........................................................................... 578
Signals.......................................................................................578
Settings......................................................................................579
Function status fault protection for IEC 60870-5-103
I103FLTPROT................................................................................ 579
Functionality.............................................................................. 579
Function block........................................................................... 580
Signals.......................................................................................580
Settings......................................................................................581
IED status for IEC 60870-5-103 I103IED....................................... 581
Functionality.............................................................................. 581
Function block........................................................................... 582
Signals.......................................................................................582
Settings......................................................................................582
Supervison status for IEC 60870-5-103 I103SUPERV...................582
Functionality.............................................................................. 582
Function block........................................................................... 583
Signals.......................................................................................583
Settings......................................................................................583
Status for user defined signals for IEC 60870-5-103 I103USRDEF583
Functionality.............................................................................. 583
Function block........................................................................... 584
Signals.......................................................................................584
Settings......................................................................................585
Section 15 Metering....................................................................... 587
Pulse counter PCGGIO.................................................................. 587
Identification.............................................................................. 587
Functionality.............................................................................. 587
Function block........................................................................... 587
Signals.......................................................................................587
Settings......................................................................................588
Monitored data...........................................................................588
Operation principle.................................................................... 588
Table of contents
23
Technical manual
Technical data........................................................................... 590
Energy calculation and demand handling ETPMMTR....................590
Identification.............................................................................. 590
Functionality.............................................................................. 590
Function block........................................................................... 591
Signals.......................................................................................591
Settings......................................................................................592
Monitored data...........................................................................593
Operation principle.................................................................... 593
Technical data........................................................................... 594
Section 16 Station communication.................................................595
DNP3 protocol................................................................................ 595
IEC 61850-8-1 communication protocol ........................................ 595
Identification.............................................................................. 595
Functionality.............................................................................. 595
Communication interfaces and protocols.................................. 596
Settings......................................................................................596
Technical data........................................................................... 597
Horizontal communication via GOOSE for interlocking.................. 597
Identification.............................................................................. 597
Function block........................................................................... 598
Signals.......................................................................................598
Settings......................................................................................600
Goose binary receive GOOSEBINRCV..........................................600
Identification.............................................................................. 600
Function block........................................................................... 601
Signals.......................................................................................601
Settings......................................................................................602
Operation principle.................................................................... 602
GOOSE function block to receive a double point value
GOOSEDPRCV..............................................................................603
Identification.............................................................................. 603
Functionality.............................................................................. 603
Function block........................................................................... 603
Signals.......................................................................................603
Settings......................................................................................604
Operation principle ................................................................... 604
GOOSE function block to receive an integer value
GOOSEINTRCV............................................................................. 604
Identification.............................................................................. 604
Functionality.............................................................................. 605
Function block........................................................................... 605
Signals.......................................................................................605
Table of contents
24
Technical manual
Operation principle ................................................................... 605
GOOSE function block to receive a measurand value
GOOSEMVRCV............................................................................. 606
Identification.............................................................................. 606
Functionality.............................................................................. 606
Function block........................................................................... 606
Signals.......................................................................................606
Settings......................................................................................607
Operation principle ................................................................... 607
GOOSE function block to receive a single point value
GOOSESPRCV..............................................................................607
Identification.............................................................................. 607
Functionality.............................................................................. 608
Function block........................................................................... 608
Signals.......................................................................................608
Settings......................................................................................608
Operation principle ................................................................... 608
IEC 60870-5-103 communication protocol..................................... 609
Functionality.............................................................................. 609
Settings......................................................................................610
IEC 61850-8-1 redundant station bus communication................... 610
Functionality ............................................................................. 611
Principle of operation.................................................................611
Function block........................................................................... 612
Setting parameters.................................................................... 613
Activity logging parameters ACTIVLOG......................................... 613
Activity logging ACTIVLOG....................................................... 613
Settings......................................................................................613
Generic security application component AGSAL............................614
Generic security application AGSAL......................................... 614
Security events on protocols SECALARM......................................614
Security alarm SECALARM.......................................................614
Signals.......................................................................................614
Settings......................................................................................614
Section 17 Basic IED functions...................................................... 615
Self supervision with internal event list ..........................................615
Functionality.............................................................................. 615
Internal error signals INTERRSIG............................................. 615
Identification......................................................................... 615
Function block...................................................................... 615
Signals..................................................................................615
Settings................................................................................ 616
Table of contents
25
Technical manual
Internal event list SELFSUPEVLST...........................................616
Identification......................................................................... 616
Settings................................................................................ 616
Operation principle.................................................................... 616
Internal signals..................................................................... 618
Run-time model....................................................................620
Technical data........................................................................... 621
Time synchronization......................................................................622
Functionality.............................................................................. 622
Time synchronization TIMESYNCHGEN...................................622
Identification......................................................................... 622
Settings................................................................................ 622
Time synchronization via SNTP................................................ 622
Identification......................................................................... 622
Settings................................................................................ 623
Time system, summer time begin DSTBEGIN.......................... 623
Identification......................................................................... 623
Settings................................................................................ 623
Time system, summer time ends DSTEND...............................624
Identification......................................................................... 624
Settings................................................................................ 624
Time zone from UTC TIMEZONE..............................................624
Identification......................................................................... 624
Settings................................................................................ 625
Time synchronization via IRIG-B...............................................625
Identification......................................................................... 625
Settings................................................................................ 625
Operation principle.................................................................... 625
General concepts................................................................. 625
Real-time clock (RTC) operation.......................................... 627
Synchronization alternatives................................................ 627
Technical data........................................................................... 629
Parameter setting group handling.................................................. 629
Functionality.............................................................................. 629
Setting group handling SETGRPS............................................ 629
Identification......................................................................... 629
Settings................................................................................ 629
Parameter setting groups ACTVGRP........................................630
Identification......................................................................... 630
Function block...................................................................... 630
Signals..................................................................................630
Settings................................................................................ 630
Operation principle.................................................................... 631
Table of contents
26
Technical manual
Test mode functionality TESTMODE..............................................632
Identification.............................................................................. 632
Functionality.............................................................................. 632
Function block........................................................................... 632
Signals.......................................................................................632
Settings......................................................................................633
Operation principle.................................................................... 633
Change lock function CHNGLCK .................................................. 634
Identification.............................................................................. 634
Functionality.............................................................................. 634
Function block........................................................................... 635
Signals.......................................................................................635
Settings......................................................................................635
Operation principle.................................................................... 635
IED identifiers TERMINALID.......................................................... 636
Identification.............................................................................. 636
Functionality.............................................................................. 636
Settings......................................................................................636
Product information ....................................................................... 637
Identification.............................................................................. 637
Functionality.............................................................................. 637
Settings......................................................................................637
Primary system values PRIMVAL...................................................637
Identification.............................................................................. 637
Functionality.............................................................................. 638
Settings......................................................................................638
Signal matrix for analog inputs SMAI............................................. 638
Functionality.............................................................................. 638
Identification.............................................................................. 638
Function block........................................................................... 639
Signals.......................................................................................639
Settings......................................................................................641
Operation principle ................................................................... 642
Summation block 3 phase 3PHSUM.............................................. 646
Identification.............................................................................. 646
Functionality.............................................................................. 646
Function block........................................................................... 646
Signals.......................................................................................646
Settings......................................................................................647
Operation principle.................................................................... 647
Global base values GBASVAL....................................................... 647
Identification.............................................................................. 648
Functionality.............................................................................. 648
Table of contents
27
Technical manual
Authority check ATHCHCK.............................................................648
Identification.............................................................................. 648
Functionality.............................................................................. 648
Settings......................................................................................649
Operation principle.................................................................... 649
Authorization handling in the IED.........................................650
Authority management AUTHMAN.................................................651
Identification.............................................................................. 651
AUTHMAN.................................................................................651
Settings......................................................................................651
FTP access with password FTPACCS........................................... 652
Identification.............................................................................. 652
FTP access with SSL FTPACCS...............................................652
Settings......................................................................................652
Authority status ATHSTAT............................................................. 653
Identification.............................................................................. 653
Functionality.............................................................................. 653
Function block........................................................................... 653
Signals.......................................................................................653
Settings......................................................................................653
Operation principle.................................................................... 653
Denial of service.............................................................................654
Functionality.............................................................................. 654
Denial of service, frame rate control for front port DOSFRNT...654
Identification......................................................................... 654
Function block...................................................................... 654
Signals..................................................................................654
Settings................................................................................ 655
Monitored data..................................................................... 655
Denial of service, frame rate control for LAN1 port DOSLAN1..655
Identification......................................................................... 655
Function block...................................................................... 656
Signals..................................................................................656
Settings................................................................................ 656
Monitored data..................................................................... 656
Operation principle.................................................................... 657
Section 18 IED physical connections............................................. 659
Protective earth connections.......................................................... 659
Inputs..............................................................................................659
Measuring inputs....................................................................... 659
Auxiliary supply voltage input.................................................... 660
Binary inputs..............................................................................661
Table of contents
28
Technical manual
Outputs for tripping, controlling and signalling...........................664
Outputs for signalling.................................................................666
IRF.............................................................................................669
Communication connections.......................................................... 669
Ethernet RJ-45 front connection................................................669
Station communication rear connection.................................... 670
Optical serial rear connection....................................................670
EIA-485 serial rear connection.................................................. 670
Communication interfaces and protocols.................................. 671
Recommended industrial Ethernet switches............................. 671
Connection diagrams......................................................................671
Section 19 Technical data..............................................................673
Dimensions.....................................................................................673
Power supply..................................................................................673
Energizing inputs............................................................................674
Binary inputs...................................................................................674
Signal outputs.................................................................................675
Power outputs.................................................................................675
Data communication interfaces...................................................... 676
Enclosure class.............................................................................. 677
Ingress protection...........................................................................677
Environmental conditions and tests................................................678
Section 20 IED and functionality tests............................................679
Electromagnetic compatibility tests................................................ 679
Insulation tests................................................................................681
Mechanical tests.............................................................................681
Product safety.................................................................................681
EMC compliance............................................................................ 682
Section 21 Time inverse characteristics.........................................683
Application......................................................................................683
Operation principle......................................................................... 686
Mode of operation......................................................................686
Inverse time characteristics............................................................ 689
Section 22 Glossary....................................................................... 713
Table of contents
29
Technical manual
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data, sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
1.2
Intended audience
This manual addresses system engineers and installation and commissioning
personnel, who use technical data during engineering, installation and
commissioning, and in normal service.
The system engineer must have a thorough knowledge of protection systems,
protection equipment, protection functions and the configured functional logic in the
IEDs. The installation and commissioning personnel must have a basic knowledge in
handling electronic equipment.
1MRK 502 048-UEN A
Section 1
Introduction
31
Technical manual
Product documentation set
IEC07000220-3-en.vsd
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
Deinstalling & disposal
Application manual
Operation manual
Installation manual
Engineering manual
Communication
protocol manual
Technical manual
Commissioning manual
IEC07000220 V3 EN
Figure 1:
The intended use of manuals throughout the product lifecycle
The engineering manual contains instructions on how to engineer the IEDs using the
various tools available within the PCM600 software. The manual provides
instructions on how to set up a PCM600 project and insert IEDs to the project
structure. The manual also recommends a sequence for the engineering of protection
and control functions, LHMI functions as well as communication engineering for IEC
60870-5-103, IEC 61850 and DNP 3.0.
The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in the chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The
manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for the checking
of external circuitry and energizing the IED, parameter setting and configuration as
well as verifying settings by secondary injection. The manual describes the process of
testing an IED in a substation which is not in service. The chapters are organized in the
Section 1
1MRK 502 048-UEN A
Introduction
32
Technical manual
chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and
setting of the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose a
typical protection function can be used. The manual can also provides assistance for
calculating settings.
The technical manual contains application and functionality descriptions and lists
function blocks, logic diagrams, input and output signals, setting parameters and
technical data, sorted per function. The manual can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
The communication protocol manual describes the communication protocols
supported by the IED. The manual concentrates on the vendor-specific
implementations.
The point list manual describes the outlook and properties of the data points specific
to the IED. The manual should be used in conjunction with the corresponding
communication protocol manual.
1.3.2
Document revision history
Document revision/date
History
-/March 2013
First release
A/October 2016
Minor corrections made
1.3.3
Related documents
Documents related to REG650
Identity number
Application manual
1MRK 502 047-UEN
Technical manual
1MRK 502 048-UEN
Commissioning manual
1MRK 502 049-UEN
Product Guide
1MRK 502 050-BEN
Type test certificate
1MRK 502 050-TEN
Rotor Earth Fault Protection with Injection Unit RXTTE4 and REG670
1MRG001910
Application notes for Circuit Breaker Control
1MRG006806
1MRK 502 048-UEN A
Section 1
Introduction
33
Technical manual
650 series manuals
Identity number
Communication protocol manual, DNP 3.0
1MRK 511 280-UEN
Communication protocol manual, IEC 61850–8–1
1MRK 511 281-UEN
Communication protocol manual, IEC 60870-5-103
1MRK 511 282-UEN
Cyber Security deployment guidelines
1MRK 511 285-UEN
Point list manual, DNP 3.0
1MRK 511 283-UEN
Engineering manual
1MRK 511 284-UEN
Operation manual
1MRK 500 096-UEN
Installation manual
1MRK 514 016-UEN
Accessories, 650 series
1MRK 513 023-BEN
MICS
1MRG 010 656
PICS
1MRG 010 660
PIXIT
1MRG 010 658
1.4
Symbols and conventions
1.4.1
Symbols
The electrical warning icon indicates the presence of a hazard which
could result in electrical shock.
The warning icon indicates the presence of a hazard which could
result in personal injury.
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence of
a hazard which could result in corruption of software or damage to
equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand
that under certain operational conditions, operation of damaged equipment may result
Section 1
1MRK 502 048-UEN A
Introduction
34
Technical manual
in degraded process performance leading to personal injury or death. It is important
that the user fully complies with all warning and cautionary notices.
1.4.2
Document conventions
•
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the
push button icons.
For example, to navigate between the options, use
and
.
•
HMI menu paths are presented in bold.
For example, select Main menu/Settings.
•
LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press
.
•
Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
•
Each function block symbol shows the available input/output signal.
•
the character ^ in front of an input/output signal name indicates that the
signal name may be customized using the PCM600 software.
•
the character * after an input/output signal name indicates that the signal
must be connected to another function block in the application
configuration to achieve a valid application configuration.
1MRK 502 048-UEN A
Section 1
Introduction
35
Technical manual
Main protection functions
IEC 61850 or
Function name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
Differential protection
T3WPDIF
87T
Transformer differential protection, three winding
0–1
1
REFPDIF
87N
Restricted earth fault protection, low impedance
0–1
HZPDIF
87
1Ph High impedance differential protection
0–1
1
1
GENPDIF
87G
Generator differential protection
0–1
1
Impedance protection
ZMRPSB
68
Power swing detection
0–1
ZGCPDIS
21G
Underimpedance protection for generators and transformers
0–1
1
1
LEXPDIS
40
Loss of excitation
0–1
1
1
LEPDIS
Load encroachment
0–1
1
1
2.2
Back-up protection functions
IEC 61850 or
Function name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
Current protection
OC4PTOC
51/67
Four step phase overcurrent protection, 3-phase output
0–2
2
2
EF4PTOC
51N/67N
Four step residual overcurrent protection, zero/negative
sequence direction
0–2
2
2
SDEPSDE
67N
Sensitive directional residual overcurrent and power
protection
0–1
1
1
TRPTTR
49
Thermal overload protection, two time constants
0–2
2
2
CCRBRF
50BF
Breaker failure protection, 3–phase activation and output
0–1
1
1
CCRPLD
52PD
Pole discordance protection
0–1
1
1
Table continues on next page
1MRK 502 048-UEN A
Section 2
Available functions
37
Technical manual
IEC 61850 or
Function name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
GUPPDUP
37
Directional underpower protection
0–1
1
1
GOPPDOP
32
Directional overpower protection
0–2
2
2
AEGGAPC
50AE
Accidental energizing protection for synchronous generator
1
1
1
NS2PTOC
46I2
Negative-sequence time overcurrent protection for
machines
1
1
1
VRPVOC
51V
Voltage-restrained time overcurrent protection
1
1
1
Voltage protection
UV2PTUV
27
Two step undervoltage protection
0–1
1
1
OV2PTOV
59
Two step overvoltage protection
0–1
1
1
ROV2PTOV
59N
Two step residual overvoltage protection
0–2
2
2
OEXPVPH
24
Overexcitation protection
0–1
1
1
STEFPHIZ
59THD
100% Stator earth fault protection, 3rd harmonic based
0–1
1
1
Frequency protection
SAPTUF
81
Underfrequency function
0–4
4
4
SAPTOF
81
Overfrequency function
0–4
4
4
SAPFRC
81
Rate-of-change frequency protection
0–2
2
2
2.3
Control and monitoring functions
IEC 61850 or Function
name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
Control
SESRSYN
25
Synchrocheck, energizing check, and synchronizing
0–1
1
1
SLGGIO
Logic Rotating Switch for function selection and LHMI
presentation
15
15
15
VSGGIO
Selector mini switch
20
20
20
DPGGIO
IEC 61850 generic communication I/O functions double
point
16
16
16
SPC8GGIO
Single point generic control 8 signals
5
5
5
AUTOBITS
AutomationBits, command function for DNP3.0
3
3
3
I103CMD
Function commands for IEC60870-5-103
1
1
1
I103IEDCMD
IED commands for IEC60870-5-103
1
1
1
Table continues on next page
Section 2
1MRK 502 048-UEN A
Available functions
38
Technical manual
IEC 61850 or Function
name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
I103USRCMD
Function commands user defined for IEC60870-5-103
4
4
4
I103GENCMD
Function commands generic for IEC60870-5-103
50
50
50
I103POSCMD
IED commands with position and select for
IEC60870-5-103
50
50
50
Apparatus control and Interlocking
APC8
Apparatus control for single bay, max 8 app. (1CB) incl.
interlocking
0–1
SCILO
3
Logical node for interlocking
BB_ES
3
Interlocking for busbar earthing switch
A1A2_BS
3
Interlocking for bus-section breaker
A1A2_DC
3
Interlocking for bus-section disconnector
ABC_BC
3
Interlocking for bus-coupler bay
BH_CONN
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_A
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_B
3
Interlocking for 1 1/2 breaker diameter
DB_BUS_A
3
Interlocking for double CB bay
DB_BUS_B
3
Interlocking for double CB bay
DB_LINE
3
Interlocking for double CB bay
ABC_LINE
3
Interlocking for line bay
AB_TRAFO
3
Interlocking for transformer bay
SCSWI
Switch controller
QCBAY
Bay control
1
1
1
LOCREM
Handling of LR-switch positions
1
1
1
LOCREMCTRL
LHMI control of Permitted Source To Operate (PSTO)
1
1
1
CBC1
Circuit breaker control for 1CB
0–1
1
CBC2
Circuit breaker control for 2CB
0–1
1
Secondary system supervision
SDDRFUF
Fuse failure supervision
0–1
1
1
TCSSCBR
Breaker close/trip circuit monitoring
3
3
3
Logic
SMPPTRC
94
Tripping logic, common 3–phase output
1–6
6
6
TMAGGIO
Trip matrix logic
12
12
12
OR
Configurable logic blocks
283
283
283
INVERTER
Configurable logic blocks
140
140
140
PULSETIMER
Configurable logic blocks
40
40
40
GATE
Configurable logic blocks
40
40
40
Table continues on next page
1MRK 502 048-UEN A
Section 2
Available functions
39
Technical manual
IEC 61850 or Function
name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
XOR
Configurable logic blocks
40
40
40
LOOPDELAY
Configurable logic blocks
40
40
40
TIMERSET
Configurable logic blocks
40
40
40
AND
Configurable logic blocks
280
280
280
SRMEMORY
Configurable logic blocks
40
40
40
RSMEMORY
Configurable logic blocks
40
40
40
Q/T
Configurable logic blocks Q/T
0–1
ANDQT
Configurable logic blocks Q/T
0–120
ORQT
Configurable logic blocks Q/T
0–120
INVERTERQT
Configurable logic blocks Q/T
0–120
XORQT
Configurable logic blocks Q/T
0–40
SRMEMORYQT
Configurable logic blocks Q/T
0–40
RSMEMORYQT
Configurable logic blocks Q/T
0–40
TIMERSETQT
Configurable logic blocks Q/T
0–40
PULSETIMERQT
Configurable logic blocks Q/T
0–40
INVALIDQT
Configurable logic blocks Q/T
0–12
INDCOMBSPQT
Configurable logic blocks Q/T
0–20
INDEXTSPQT
Configurable logic blocks Q/T
0–20
FXDSIGN
Fixed signal function block
1
1
1
B16I
Boolean 16 to Integer conversion
16
16
16
B16IFCVI
Boolean 16 to Integer conversion with logic node
representation
16
16
16
IB16A
Integer to Boolean 16 conversion
16
16
16
IB16FCVB
Integer to Boolean 16 conversion with logic node
representation
16
16
16
TEIGGIO
Elapsed time integrator with limit transgression and
overflow supervision
12
12
12
Monitoring
CVMMXN
Measurements
6
6
6
CMMXU
Phase current measurement
10
10
10
VMMXU
Phase-phase voltage measurement
6
6
6
CMSQI
Current sequence component measurement
6
6
6
VMSQI
Voltage sequence measurement
6
6
6
VNMMXU
Phase-neutral voltage measurement
6
6
6
AISVBAS
Function block for service values presentation of the
analog inputs
1
1
1
Table continues on next page
Section 2
1MRK 502 048-UEN A
Available functions
40
Technical manual
IEC 61850 or Function
name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
TM_P_P2
Function block for service values presentation of primary
analog inputs 600TRM
1
1
1
AM_P_P4
Function block for service values presentation of primary
analog inputs 600AIM
1
1
1
TM_S_P2
Function block for service values presentation of
secondary analog inputs 600TRM
1
1
1
AM_S_P4
Function block for service values presentation of
secondary analog inputs 600AIM
1
1
1
CNTGGIO
Event counter
5
5
5
L4UFCNT
Event counter with limit supervision
12
12
12
DRPRDRE
Disturbance report
1
1
1
AnRADR
Analog input signals
4
4
4
BnRBDR
Binary input signals
6
6
6
SPGGIO
IEC 61850 generic communication I/O functions
64
64
64
SP16GGIO
IEC 61850 generic communication I/O functions 16
inputs
16
16
16
MVGGIO
IEC 61850 generic communication I/O functions
16
16
16
MVEXP
Measured value expander block
66
66
66
SPVNZBAT
Station battery supervision
0–1
1
1
SSIMG
63
Insulation gas monitoring function
0–2
2
2
SSIML
71
Insulation liquid monitoring function
0–2
2
2
SSCBR
Circuit breaker condition monitoring
0–1
1
1
I103MEAS
Measurands for IEC60870-5-103
1
1
1
I103MEASUSR
Measurands user defined signals for IEC60870-5-103
3
3
3
I103AR
Function status auto-recloser for IEC60870-5-103
1
1
1
I103EF
Function status earth-fault for IEC60870-5-103
1
1
1
I103FLTPROT
Function status fault protection for IEC60870-5-103
1
1
1
I103IED
IED status for IEC60870-5-103
1
1
1
I103SUPERV
Supervison status for IEC60870-5-103
1
1
1
I103USRDEF
Status for user defined signals for IEC60870-5-103
20
20
20
Metering
PCGGIO
Pulse counter
16
16
16
ETPMMTR
Function for energy calculation and demand handling
3
3
3
1MRK 502 048-UEN A
Section 2
Available functions
41
Technical manual
IEC 61850 or Function
name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
Station communication
IEC61850-8-1
IEC 61850 communication protocol
1
1
1
DNPGEN
DNP3.0 communication general protocol
1
1
1
RS485DNP
DNP3.0 for RS-485 communication protocol
1
1
1
CH1TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
CH2TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
CH3TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
CH4TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
OPTICALDNP
DNP3.0 for optical RS-232 communication protocol
1
1
1
MSTSERIAL
DNP3.0 for serial communication protocol
1
1
1
MST1TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
MST2TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
MST3TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
MST4TCP
DNP3.0 for TCP/IP communication protocol
1
1
1
RS485GEN
RS485
1
1
1
OPTICALPROT
Operation selection for optical serial
1
1
1
RS485PROT
Operation selection for RS485
1
1
1
DNPFREC
DNP3.0 fault records for TCP/IP communication
protocol
1
1
1
OPTICAL103
IEC60870-5-103 Optical serial communication
1
1
1
RS485103
IEC60870-5-103 serial communication for RS485
1
1
1
GOOSEINTLKRCV
Horizontal communication via GOOSE for
interlocking
59
59
59
GOOSEBINRCV
GOOSE binary receive
4
4
4
ETHFRNT
ETHLAN1
GATEWAY
Ethernet configuration of front port, LAN1 port and
gateway
1
1
1
ETHLAN1_AB
Ethernet configuration of LAN1 port
1
PRPSTATUS
System component for parallell redundancy protocol
1
CONFPROT
IED Configuration Protocol
1
1
1
ACTIVLOG
Activity logging parameters
1
1
1
SECALARM
Component for mapping security events on protocols
such as DNP3 and IEC103
1
1
1
AGSAL
Generic security application component
1
1
1
GOOSEDPRCV
GOOSE function block to receive a double point value
32
32
32
Table continues on next page
Section 2
1MRK 502 048-UEN A
Available functions
42
Technical manual
IEC 61850 or Function
name
ANSI
Function description
Generator
REG650
REG650 (B01)
Gen diff
REG650 (B05)
Gen+Trafo diff
GOOSEINTRCV
GOOSE function block to receive an integer value
32
32
32
GOOSEMVRCV
GOOSE function block to receive a measurand value
16
16
16
GOOSESPRCV
GOOSE function block to receive a single point value
64
64
64
2.5
Basic IED functions
IEC 61850/Function
block name
Function description
Basic functions included in all products
INTERRSIG
Self supervision with internal event list
1
SELFSUPEVLST
Self supervision with internal event list
1
TIMESYNCHGEN
Time synchronization
1
SNTP
Time synchronization
1
DTSBEGIN, DTSEND,
TIMEZONE
Time synchronization, daylight saving
1
IRIG-B
Time synchronization
1
SETGRPS
Setting group handling
1
ACTVGRP
Parameter setting groups
1
TESTMODE
Test mode functionality
1
CHNGLCK
Change lock function
1
PRIMVAL
Primary system values
1
SMAI_20_1 -
SMAI_20_12
Signal matrix for analog inputs
2
3PHSUM
Summation block 3 phase
12
GBASVAL
Global base values for settings
6
ATHSTAT
Authority status
1
ATHCHCK
Authority check
1
AUTHMAN
Authority management
1
FTPACCS
FTPS access with password
1
DOSFRNT
Denial of service, frame rate control for front port
1
DOSLAN1
Denial of service, frame rate control for LAN1A and LAN1B ports
1
DOSSCKT
Denial of service, socket flow control
1
1MRK 502 048-UEN A
Section 2
Available functions
43
Technical manual
Analog input channels in the IED must be set properly in order to get correct
measurement results and correct protection operations. For power measuring and all
directional and differential functions the directions of the input currents must be
defined in order to reflect the way the current transformers are installed/connected in
the field ( primary and secondary connections ). Measuring and protection algorithms
in the IED use primary system quantities. Consequently the setting values are
expressed in primary quantities as well and therefore it is important to set the
transformation ratio of the connected current and voltage transformers properly.
The availability of CT and VT inputs, as well as setting parameters depends on the
ordered IED.
A reference PhaseAngleRef must be defined to facilitate service values reading. This
analog channels phase angle will always be fixed to zero degrees and all other angle
information will be shown in relation to this analog input. During testing and
commissioning of the IED the reference channel can be changed to facilitate testing
and service values reading.
3.2
Operation principle
The direction of a current depends on the connection of the CT. The main CTs are
typically star connected and can be connected with the star point towards the object or
away from the object. This information must be set in the IED.
The convention of the directionality is defined as follows:
•
Positive value of current or power means that the quantity has the direction into
the object.
•
Negative value of current or power means that the quantity has the direction out
from the object.
For directional functions the directional conventions are defined as follows (see figure
2)
•
Forward means the direction is into the object.
•
Reverse means the direction is out from the object.
1MRK 502 048-UEN A
Section 3
Analog inputs
45
Technical manual
Line, transformer, etc
Forward
Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse
Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
IEC05000456 V1 EN
Figure 2:
Internal convention of the directionality in the IED
If the settings of the primary CT is correct, that is CTStarPoint set as FromObject or
ToObject according to the plant condition, then a positive quantity always flows
towards the protected object, and a Forward direction always looks towards the
protected object.
The settings of the IED is performed in primary values. The ratios of the main CTs and
VTs are therefore basic data for the IED. The user has to set the rated secondary and
primary currents and voltages of the CTs and VTs to provide the IED with their rated
ratios.
The CT and VT ratio and the name on respective channel is done under Main menu/
Hardware/Analog modules in the Parameter Settings tool or on the HMI.
3.3
Presumptions for technical data
The technical data stated in this document are only valid under the following
circumstances:
•
CT and VT ratios in the IED are set in accordance with the associated main
instrument transformers. Note that for functions which measure an analogue
signal which do not have corresponding primary quantity, the 1:1 ratio shall be set
for the used analogue inputs on the IED, For example, HZPDIF.
•
Parameter IBase used by the tested function is set equal to the rated CT primary
current.
•
Parameter UBase used by the tested function is set equal to the rated primary
phase-to-phase voltage.
•
Parameter SBase used by the tested function is set equal to sqrt(3)* IBase* UBase
for three-phase power system.
Section 3
1MRK 502 048-UEN A
Analog inputs
46
Technical manual
Dependent on ordered IED type.
Table 1:
AISVBAS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
PhaseAngleRef
TRM - Channel 1
TRM - Channel 2
TRM - Channel 3
TRM - Channel 4
TRM - Channel 5
TRM - Channel 6
TRM - Channel 7
TRM - Channel 8
TRM - Channel 9
TRM - Channel 10
AIM - Channel 1
AIM - Channel 2
AIM - Channel 3
AIM - Channel 4
AIM - Channel 5
AIM - Channel 6
AIM - Channel 7
AIM - Channel 8
AIM - Channel 9
AIM - Channel 10
-
-
TRM - Channel 1
Reference channel for phase angle
presentation
Table 2:
TRM_6I_4U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
Table continues on next page
1MRK 502 048-UEN A
Section 3
Analog inputs
47
Technical manual
ToObject= towards protected object,
FromObject= the opposite
CTsec6
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim6
1 - 99999
A
1
1000
Rated CT primary current
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 3:
TRM_8I_2U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim6
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint7
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec7
0.1 - 10.0
A
0.1
1
Rated CT secondary current
Table continues on next page
Section 3
1MRK 502 048-UEN A
Analog inputs
48
Technical manual
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint8
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec8
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim8
1 - 99999
A
1
1000
Rated CT primary current
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 4:
TRM_4I_1I_5U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
VTsec6
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim6
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
1MRK 502 048-UEN A
Section 3
Analog inputs
49
Technical manual
TRM_4I_6U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
VTsec5
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim5
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec6
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim6
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 6:
AIM_6I_4U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
Table continues on next page
Section 3
1MRK 502 048-UEN A
Analog inputs
50
Technical manual
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim4
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim6
1 - 99999
A
1
1000
Rated CT primary current
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
Table 7:
AIM_4I_1I_5U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim1
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim2
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim3
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
Table continues on next page
1MRK 502 048-UEN A
Section 3
Analog inputs
51
Technical manual
1 - 99999
A
1
1000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
0.1 - 10.0
A
0.1
1.0
Rated CT secondary current
CTprim5
1 - 99999
A
1
1000
Rated CT primary current
VTsec6
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim6
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec7
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim7
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec8
0.001 - 999.999
V
0.001
110
Rated VT secondary voltage
VTprim8
0.001 - 9999.999
kV
0.001
132
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim10
0.001 - 9999.999
kV
0.001
132.000
Rated VT primary voltage
Section 3
1MRK 502 048-UEN A
Analog inputs
52
Technical manual
Binary input and output modules
4.1
Binary input
4.1.1
Binary input debounce filter
The debounce filter eliminates bounces and short disturbances on a binary input.
A time counter is used for filtering. The time counter is increased once in a millisecond
when a binary input is high, or decreased when a binary input is low. A new debounced
binary input signal is forwarded when the time counter reaches the set DebounceTime
value and the debounced input value is high or when the time counter reaches 0 and
the debounced input value is low. The default setting of DebounceTime is 5 ms.
The binary input ON-event gets the time stamp of the first rising edge, after which the
counter does not reach 0 again. The same happens when the signal goes down to 0
again.
Each binary input has a filter time parameter DebounceTimex, where x is the number
of the binary input of the module in question (for example DebounceTime1).
The debounce time should be set to the same value for all channels on
the board.
4.1.2
Oscillation filter
Binary input wiring can be very long in substations and there are electromagnetic
fields from for example nearby breakers. Floating input lines can result in
disturbances to binary inputs. These disturbances are unwanted in the system. An
oscillation filter is used to reduce the disturbance from the system when a binary input
starts oscillating.
Each debounced input signal change increments of an oscillation counter. Every time
the oscillation time counter reaches the set OscillationTime, the oscillation counter is
checked and both the time counter and the oscillation counter are reset. If the counter
value is above the set OscillationCount value the signal is declared as oscillating and
not valid. If the value is below the set OscillationCount value, the signal is declared as
valid again. During counting of the oscillation time the status of the signal remains
unchanged, leading to a fixed delay in the status update, even if the signal has attained
normal status again.
1MRK 502 048-UEN A
Section 4
Binary input and output modules
53
Technical manual
Each binary input has an oscillation count parameter OscillationCountx and an
oscillation time parameter OscillationTimex, where x is the number of the binary input
of the module in question.
4.1.3
Settings
4.1.3.1
Setting parameters for binary input modules
Table 8:
BIO_9BI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
BatteryVoltage
24 - 250
V
1
110
Station battery voltage
Table 9:
BIO_9BI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Threshold1
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 1
DebounceTime1
0.000 - 0.100
s
0.001
0.005
Debounce time for input 1
OscillationCount1
0 - 255
-
1
0
Oscillation count for input 1
OscillationTime1
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 1
Threshold2
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 2
DebounceTime2
0.000 - 0.100
s
0.001
0.005
Debounce time for input 2
OscillationCount2
0 - 255
-
1
0
Oscillation count for input 2
OscillationTime2
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 2
Threshold3
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 3
DebounceTime3
0.000 - 0.100
s
0.001
0.005
Debounce time for input 3
OscillationCount3
0 - 255
-
1
0
Oscillation count for input 3
OscillationTime3
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 3
Threshold4
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 4
DebounceTime4
0.000 - 0.100
s
0.001
0.005
Debounce time for input 4
OscillationCount4
0 - 255
-
1
0
Oscillation count for input 4
OscillationTime4
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 4
Threshold5
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 5
DebounceTime5
0.000 - 0.100
s
0.001
0.005
Debounce time for input 5
OscillationCount5
0 - 255
-
1
0
Oscillation count for input 5
OscillationTime5
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 5
Threshold6
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 6
DebounceTime6
0.000 - 0.100
s
0.001
0.005
Debounce time for input 6
OscillationCount6
0 - 255
-
1
0
Oscillation count for input 6
Table continues on next page
Section 4
1MRK 502 048-UEN A
Binary input and output modules
54
Technical manual
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 6
Threshold7
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 7
DebounceTime7
0.000 - 0.100
s
0.001
0.005
Debounce time for input 7
OscillationCount7
0 - 255
-
1
0
Oscillation count for input 7
OscillationTime7
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 7
Threshold8
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 8
DebounceTime8
0.000 - 0.100
s
0.001
0.005
Debounce time for input 8
OscillationCount8
0 - 255
-
1
0
Oscillation count for input 8
OscillationTime8
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 8
Threshold9
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 9
DebounceTime9
0.000 - 0.100
s
0.001
0.005
Debounce time for input 9
OscillationCount9
0 - 255
-
1
0
Oscillation count for input 9
OscillationTime9
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 9
4.1.3.2
Setting parameters for communication module
Table 10:
COM05_12BI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
BatteryVoltage
24 - 250
V
1
110
Station battery voltage
Table 11:
COM05_12BI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Threshold1
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 1
DebounceTime1
0.000 - 0.100
s
0.001
0.005
Debounce time for input 1
OscillationCount1
0 - 255
-
1
0
Oscillation count for input 1
OscillationTime1
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 1
Threshold2
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 2
DebounceTime2
0.000 - 0.100
s
0.001
0.005
Debounce time for input 2
OscillationCount2
0 - 255
-
1
0
Oscillation count for input 2
OscillationTime2
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 2
Threshold3
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 3
DebounceTime3
0.000 - 0.100
s
0.001
0.005
Debounce time for input 3
OscillationCount3
0 - 255
-
1
0
Oscillation count for input 3
OscillationTime3
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 3
Table continues on next page
1MRK 502 048-UEN A
Section 4
Binary input and output modules
55
Technical manual
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 4
DebounceTime4
0.000 - 0.100
s
0.001
0.005
Debounce time for input 4
OscillationCount4
0 - 255
-
1
0
Oscillation count for input 4
OscillationTime4
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 4
Threshold5
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 5
DebounceTime5
0.000 - 0.100
s
0.001
0.005
Debounce time for input 5
OscillationCount5
0 - 255
-
1
0
Oscillation count for input 5
OscillationTime5
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 5
Threshold6
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 6
DebounceTime6
0.000 - 0.100
s
0.001
0.005
Debounce time for input 6
OscillationCount6
0 - 255
-
1
0
Oscillation count for input 6
OscillationTime6
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 6
Threshold7
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 7
DebounceTime7
0.000 - 0.100
s
0.001
0.005
Debounce time for input 7
OscillationCount7
0 - 255
-
1
0
Oscillation count for input 7
OscillationTime7
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 7
Threshold8
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 8
DebounceTime8
0.000 - 0.100
s
0.001
0.005
Debounce time for input 8
OscillationCount8
0 - 255
-
1
0
Oscillation count for input 8
OscillationTime8
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 8
Threshold9
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 9
DebounceTime9
0.000 - 0.100
s
0.001
0.005
Debounce time for input 9
OscillationCount9
0 - 255
-
1
0
Oscillation count for input 9
OscillationTime9
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 9
Threshold10
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 10
DebounceTime10
0.000 - 0.100
s
0.001
0.005
Debounce time for input 10
OscillationCount10
0 - 255
-
1
0
Oscillation count for input 10
OscillationTime10
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 10
Threshold11
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 11
DebounceTime11
0.000 - 0.100
s
0.001
0.005
Debounce time for input 11
OscillationCount11
0 - 255
-
1
0
Oscillation count for input 11
OscillationTime11
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 11
Threshold12
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 12
Table continues on next page
Section 4
1MRK 502 048-UEN A
Binary input and output modules
56
Technical manual
0.000 - 0.100
s
0.001
0.005
Debounce time for input 12
OscillationCount12
0 - 255
-
1
0
Oscillation count for input 12
OscillationTime12
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 12
1MRK 502 048-UEN A
Section 4
Binary input and output modules
57
Technical manual
Local Human-Machine-Interface LHMI
5.1
Local HMI screen behaviour
5.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local HMI screen behaviour
SCREEN
-
-
5.1.2
Settings
Table 12:
SCREEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
DisplayTimeout
10 - 120
Min
10
60
Local HMI display timeout
ContrastLevel
-100 - 100
%
10
0
Contrast level for display
DefaultScreen
0 - 0
-
1
0
Default screen
EvListSrtOrder
Latest on top
Oldest on top
-
-
Latest on top
Sort order of event list
AutoIndicationDRP
Off
On
-
-
Off
Automatic indication of disturbance report
SubstIndSLD
No
Yes
-
-
No
Substitute indication on single line
diagram
InterlockIndSLD
No
Yes
-
-
No
Interlock indication on single line diagram
BypassCommands
No
Yes
-
-
No
Enable bypass of commands
5.2
Local HMI signals
5.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local HMI signals
LHMICTRL
-
-
5.2.2
Function block
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
59
Technical manual
IEC09000320 V1 EN
Figure 3:
LHMICTRL function block
5.2.3
Signals
Table 13:
LHMICTRL Input signals
Name
Type
Default
Description
CLRLEDS
BOOLEAN
0
Input to clear the LCD-HMI LEDs
Table 14:
LHMICTRL Output signals
Name
Type
Description
HMI-ON
BOOLEAN
Backlight of the LCD display is active
RED-S
BOOLEAN
Red LED on the LCD-HMI is steady
YELLOW-S
BOOLEAN
Yellow LED on the LCD-HMI is steady
YELLOW-F
BOOLEAN
Yellow LED on the LCD-HMI is flashing
CLRPULSE
BOOLEAN
A pulse is provided when the LEDs on the LCD-HMI
are cleared
LEDSCLRD
BOOLEAN
Active when the LEDs on the LCD-HMI are not
active
5.3
Basic part for LED indication module
5.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Basic part for LED indication module
LEDGEN
-
-
Basic part for LED indication module
GRP1_LED1 -
GRP1_LED15
GRP2_LED1 -
GRP2_LED15
GRP3_LED1 -
GRP3_LED15
-
-
5.3.2
Function block
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
60
Technical manual
IEC09000321 V1 EN
Figure 4:
LEDGEN function block
GRP1_LED1
^HM1L01R
^HM1L01Y
^HM1L01G
IEC09000322 V1 EN
Figure 5:
GRP1_LED1 function block
The GRP1_LED1 function block is an example, all 15 LED in each of group 1 - 3 has
a similar function block.
5.3.3
Signals
Table 15:
LEDGEN Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Input to block the operation of the LEDs
RESET
BOOLEAN
0
Input to acknowledge/reset the indication LEDs
Table 16:
GRP1_LED1 Input signals
Name
Type
Default
Description
HM1L01R
BOOLEAN
0
Red indication of LED1, local HMI alarm group 1
HM1L01Y
BOOLEAN
0
Yellow indication of LED1, local HMI alarm group 1
HM1L01G
BOOLEAN
0
Green indication of LED1, local HMI alarm group 1
Table 17:
LEDGEN Output signals
Name
Type
Description
NEWIND
BOOLEAN
New indication signal if any LED indication input is
set
ACK
BOOLEAN
A pulse is provided when the LEDs are
acknowledged
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
61
Technical manual
LEDGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
tRestart
0.0 - 100.0
s
0.1
0.0
Defines the disturbance length
tMax
0.0 - 100.0
s
0.1
0.0
Maximum time for the definition of a
disturbance
Table 19:
GRP1_LED1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SequenceType
Follow-S
Follow-F
LatchedAck-F-S
LatchedAck-S-F
LatchedColl-S
LatchedReset-S
-
-
Follow-S
Sequence type for LED 1, local HMI alarm
group 1
LabelOff
0 - 18
-
1
G1L01_OFF
Label string shown when LED 1, alarm
group 1 is off
LabelRed
0 - 18
-
1
G1L01_RED
Label string shown when LED 1, alarm
group 1 is red
LabelYellow
0 - 18
-
1
G1L01_YELLOW
Label string shown when LED 1, alarm
group 1 is yellow
LabelGreen
0 - 18
-
1
G1L01_GREEN
Label string shown when LED 1, alarm
group 1 is green
5.4
LCD part for HMI function keys control module
5.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
LCD part for HMI Function Keys Control
module
FNKEYMD1 -
FNKEYMD5
-
-
5.4.2
Function block
FNKEYMD1
^LEDCTL1
^FKEYOUT1
IEC09000327 V1 EN
Figure 6:
FNKEYMD1 function block
Only the function block for the first button is shown above. There is a similar block for
every function button.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
62
Technical manual
FNKEYMD1 Input signals
Name
Type
Default
Description
LEDCTL1
BOOLEAN
0
LED control input for function key
Table 21:
FNKEYMD1 Output signals
Name
Type
Description
FKEYOUT1
BOOLEAN
Output controlled by function key
5.4.4
Settings
Table 22:
FNKEYMD1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Mode
Off
Toggle
Pulsed
-
-
Off
Output operation mode
PulseTime
0.001 - 60.000
s
0.001
0.200
Pulse time for output controlled by
LCDFn1
LabelOn
0 - 18
-
1
LCD_FN1_ON
Label for LED on state
LabelOff
0 - 18
-
1
LCD_FN1_OFF
Label for LED off state
Table 23:
FNKEYTY1 Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Type
Off
Menu shortcut
Control
-
-
Off
Function key type
MenuShortcut
Menu shortcut for
function key
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
63
Technical manual
IEC12000175 V1 EN
Figure 7:
Local human-machine interface
The LHMI of the IED contains the following elements:
•
Display (LCD)
•
Buttons
•
LED indicators
•
Communication port for PCM600
The LHMI is used for setting, monitoring and controlling.
5.5.1.1
Display
The LHMI includes a graphical monochrome display with a resolution of 320 x 240
pixels. The character size can vary. The amount of characters and rows fitting the view
depends on the character size and the view that is shown.
The display view is divided into four basic areas.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
64
Technical manual
IEC13000063 V1 EN
Figure 8:
Display layout
1
Path
2
Content
3
Status
4
Scroll bar (appears when needed)
•
The path shows the current location in the menu structure. If the path is too long
to be shown, it is truncated from the beginning, and the truncation is indicated
with three dots.
•
The content area shows the menu content.
•
The status area shows the current IED time, the user that is currently logged in and
the object identification string which is settable via the LHMI or with PCM600.
•
If text, pictures or other items do not fit in the display, a vertical scroll bar appears
on the right. The text in content area is truncated from the beginning if it does not
fit in the display horizontally. Truncation is indicated with three dots.
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
65
Technical manual
IEC13000045 V1 EN
Figure 9:
Truncated path
The number before the function instance, for example ETHFRNT:1, indicates the
instance number.
The function button panel shows on request what actions are possible with the
function buttons. Each function button has a LED indication that can be used as a
feedback signal for the function button control action. The LED is connected to the
required signal with PCM600.
IEC12000025-2-en.vsd
IEC12000025 V2 EN
Figure 10:
Function button panel
The alarm LED panel shows on request the alarm text labels for the alarm LEDs. Three
alarm LED pages are available.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
66
Technical manual
GUID-D20BB1F1-FDF7-49AD-9980-F91A38B2107D V1 EN
Figure 11:
Alarm LED panel
The function button and alarm LED panels are not visible at the same time. Each panel
is shown by pressing one of the function buttons or the Multipage button. Pressing the
ESC button clears the panel from the display. Both the panels have dynamic width that
depends on the label string length that the panel contains.
5.5.1.2
LEDs
The LHMI includes three protection status LEDs above the display: Ready, Start and
Trip.
There are 15 programmable alarm LEDs on the front of the LHMI. Each LED can
indicate three states with the colors: green, yellow and red. The alarm texts related to
each three-color LED are divided into three pages.
There are 3 separate pages of LEDs available. The 15 physical three-color LEDs in
one LED group can indicate 45 different signals. Altogether, 135 signals can be
indicated since there are three LED groups. The LEDs can be configured with
PCM600 and the operation mode can be selected with the LHMI or PCM600.
5.5.1.3
Keypad
The LHMI keypad contains push-buttons which are used to navigate in different
views or menus. The push-buttons are also used to acknowledge alarms, reset
indications, provide help and switch between local and remote control mode.
The keypad also contains programmable push-buttons that can be configured either as
menu shortcut or control buttons.
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
67
Technical manual
IEC11000247 V2 EN
Figure 12:
LHMI keypad with object control, navigation and command push-
buttons and RJ-45 communication port
1...5
Function button
6
Close
7
Open
8
Escape
9
Left
10
Down
11
Up
12
Right
13
User Log on
14
Enter
15
Remote/Local
16
Uplink LED
17
Ethernet communication port (RJ-45)
18
Multipage
19
Menu
20
Clear
21
Help
22
Programmable alarm LEDs
23
Protection status LEDs
5.5.2
LED
5.5.2.1
Functionality
The function blocks LEDGEN and GRP1_LEDx, GRP2_LEDx and GRP3_LEDx
(x=1-15) controls and supplies information about the status of the indication LEDs.
The input and output signals of the function blocks are configured with PCM600. The
input signal for each LED is selected individually using SMT or ACT. Each LED is
controlled by a GRP1_LEDx function block, that controls the color and the operating
mode.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
68
Technical manual
Each indication LED on local HMI can be set individually to operate in 6 different
sequences; two as follow type and four as latch type. Two of the latching sequence
types are intended to be used as a protection indication system, either in collecting or
restarting mode, with reset functionality. The other two are intended to be used as
signalling system in collecting mode with acknowledgment functionality.
5.5.2.2
Status LEDs
There are three status LEDs above the LCD in the front of the IED, green, yellow and
red.
The green LED has a fixed function that present the healthy status of the IED. The
yellow and red LEDs are user configured. The yellow LED can be used to indicate that
a disturbance report is triggered (steady) or that the IED is in test mode (flashing). The
red LED can be used to indicate a trip command.
The yellow and red status LEDs are configured in the disturbance recorder function,
DRPRDRE, by connecting a start or trip signal from the actual function to a BxRBDR
binary input function block using the PCM600 and configure the setting to Off, Start
or Trip for that particular signal.
5.5.2.3
Indication LEDs
Operating modes
Collecting mode
•
LEDs, which are used in collecting mode of operation, are accumulated
continuously until the unit is acknowledged manually. This mode is suitable
when the LEDs are used as a simplified alarm system.
Re-starting mode
•
In the re-starting mode of operation each new start resets all previous active LEDs
and activates only those, which appear during one disturbance. Only LEDs
defined for re-starting mode with the latched sequence type 6 (LatchedReset-S)
will initiate a reset and a restart at a new disturbance. A disturbance is defined to
end a settable time after the reset of the activated input signals or when the
maximum time limit has elapsed.
Acknowledgment/reset
•
From local HMI
•
The active indications can be acknowledged/reset manually. Manual
acknowledgment and manual reset have the same meaning and is a
common signal for all the operating sequences and LEDs. The function is
positive edge triggered, not level triggered. The acknowledgment/reset is
performed via the
button and menus on the LHMI.
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
69
Technical manual
From function input
•
The active indications can also be acknowledged/reset from an input,
ACK_RST, to the function. This input can for example be configured to a
binary input operated from an external push button. The function is positive
edge triggered, not level triggered. This means that even if the button is
continuously pressed, the acknowledgment/reset only affects indications
active at the moment when the button is first pressed.
•
Automatic reset
•
The automatic reset can only be performed for indications defined for re-
starting mode with the latched sequence type 6 (LatchedReset-S). When the
automatic reset of the LEDs has been performed, still persisting indications
will be indicated with a steady light.
Operating sequence
The sequences can be of type Follow or Latched. For the Follow type the LED follow
the input signal completely. For the Latched type each LED latches to the
corresponding input signal until it is reset.
The figures below show the function of available sequences selectable for each LED
separately. For sequence 1 and 2 Follow type, the acknowledgment/reset function is
not applicable. Sequence 3 and 4 Latched type with acknowledgement are only
working in collecting mode. Sequence 5 is working according to Latched type and
collecting mode while Sequence 6 is working according to Latched type and re-
starting mode. The letters S and F in the sequence names have the meaning S = Steady
and F = Flash.
At the activation of the input signal, the indication obtains corresponding color
corresponding to the activated input and operates according to the selected sequence
diagrams below.
In the sequence diagrams the LEDs have the following characteristics:
= No indication
= Steady light
= Flash
G= Green
Y= Yellow
R= Red
IEC09000311.vsd
IEC09000311 V1 EN
Figure 13:
Symbols used in the sequence diagrams
Sequence 1 (Follow-S)
This sequence follows all the time, with a steady light, the corresponding input
signals. It does not react on acknowledgment or reset. Every LED is independent of
the other LEDs in its operation.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
70
Technical manual
IEC01000228 V2 EN
Figure 14:
Operating Sequence 1 (Follow-S)
If inputs for two or more colors are active at the same time to one LED the priority is
as described above. An example of the operation when two colors are activated in
parallel is shown in Figure 15.
Activating
signal GREEN
LED
IEC09000312_1_en.vsd
G
R
G
G
Activating
signal RED
IEC09000312 V1 EN
Figure 15:
Operating sequence 1, two colors
Sequence 2 (Follow-F)
This sequence is the same as Sequence 1, Follow-S, but the LEDs are flashing instead
of showing steady light.
Sequence 3 LatchedAck-F-S
This sequence has a latched function and works in collecting mode. Every LED is
independent of the other LEDs in its operation. At the activation of the input signal,
the indication starts flashing. After acknowledgment the indication disappears if the
signal is not present any more. If the signal is still present after acknowledgment it gets
a steady light.
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
71
Technical manual
IEC01000231 V1 EN
Figure 16:
Operating Sequence 3 LatchedAck-F-S
When an acknowledgment is performed, all indications that appear before the
indication with higher priority has been reset, will be acknowledged, independent of
if the low priority indication appeared before or after acknowledgment. In Figure 17 it
is shown the sequence when a signal of lower priority becomes activated after
acknowledgment has been performed on a higher priority signal. The low priority
signal will be shown as acknowledged when the high priority signal resets.
Activating
signal RED
LED
Acknow
IEC09000313_1_en.vsd
Activating
signal GREEN
R
R
G
IEC09000313 V1 EN
Figure 17:
Operating Sequence 3 (LatchedAck-F-S), 2 colors involved
If all three signals are activated the order of priority is still maintained.
Acknowledgment of indications with higher priority will acknowledge also low
priority indications, which are not visible according to Figure 18.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
72
Technical manual
IEC09000314 V1 EN
Figure 18:
Operating sequence 3, three colors involved, alternative 1
If an indication with higher priority appears after acknowledgment of a lower priority
indication the high priority indication will be shown as not acknowledged according
to Figure 19.
Activating
signal RED
LED
Acknow.
IEC09000315-1-en.vsd
Activating
signal YELLOW
G
G
R
R
Y
Activating
signal GREEN
IEC09000315 V1 EN
Figure 19:
Operating sequence 3, three colors involved, alternative 2
Sequence 4 (LatchedAck-S-F)
This sequence has the same functionality as sequence 3, but steady and flashing light
have been alternated.
Sequence 5 LatchedColl-S
This sequence has a latched function and works in collecting mode. At the activation
of the input signal, the indication will light up with a steady light. The difference to
sequence 3 and 4 is that indications that are still activated will not be affected by the
reset that is, immediately after the positive edge of the reset has been executed a new
reading and storing of active signals is performed. Every LED is independent of the
other LEDs in its operation.
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
73
Technical manual
IEC01000235 V2 EN
Figure 20:
Operating Sequence 5 LatchedColl-S
That means if an indication with higher priority has reset while an indication with
lower priority still is active at the time of reset, the LED will change color according to
Figure 21.
Activating
signal RED
LED
Reset
IEC09000316_1_en.vsd
Activating
signal GREEN
R
G
IEC09000316 V1 EN
Figure 21:
Operating sequence 5, two colors
Sequence 6 LatchedReset-S
In this mode all activated LEDs, which are set to Sequence 6 (LatchedReset-S), are
automatically reset at a new disturbance when activating any input signal for other
LEDs set to Sequence 6 LatchedReset-S. Also in this case indications that are still
activated will not be affected by manual reset, that is, immediately after the positive
edge of that the manual reset has been executed a new reading and storing of active
signals is performed. LEDs set for sequence 6 are completely independent in its
operation of LEDs set for other sequences.
Timing diagram for sequence 6
Figure 22 shows the timing diagram for two indications within one disturbance.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
74
Technical manual
IEC01000239 V2 EN
Figure 22:
Operating sequence 6 (LatchedReset-S), two indications within
same disturbance
Figure 23 shows the timing diagram for a new indication after tRestart time has
elapsed.
IEC01000240_2_en.vsd
Activating
signal 2
LED 2
Manual
reset
Activating
signal 1
Automatic
reset
LED 1
Disturbance
tRestart
Disturbance
tRestart
IEC01000240 V2 EN
Figure 23:
Operating sequence 6 (LatchedReset-S), two different disturbances
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
75
Technical manual
Figure 24 shows the timing diagram when a new indication appears after the first one
has reset but before tRestart has elapsed.
IEC01000241_2_en.vsd
Activating
signal 2
LED 2
Manual
reset
Activating
signal 1
Automatic
reset
LED 1
Disturbance
tRestart
IEC01000241 V2 EN
Figure 24:
Operating sequence 6 (LatchedReset-S), two indications within
same disturbance but with reset of activating signal between
Figure 25 shows the timing diagram for manual reset.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
76
Technical manual
IEC01000242 V2 EN
Figure 25:
Operating sequence 6 (LatchedReset-S), manual reset
5.5.3
Function keys
5.5.3.1
Functionality
Local Human-Machine-Interface (LHMI) has five function buttons, directly to the left
of the LCD, that can be configured either as menu shortcut or control buttons. Each
button has an indication LED that can be configured in the application configuration.
When used as a menu shortcut, a function button provides a fast way to navigate
between default nodes in the menu tree. When used as a control, the button can control
a binary signal.
5.5.3.2
Operation principle
Each output on the FNKEYMD1 - FNKEYMD5 function blocks can be controlled
from the LHMI function keys. By pressing a function button on the LHMI, the output
status of the actual function block will change. These binary outputs can in turn be
used to control other function blocks, for example, switch control blocks, binary I/O
outputs etc.
FNKEYMD1 - FNKEYMD5 function block also has a number of settings and
parameters that control the behavior of the function block. These settings and
parameters are normally set using the PST.
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
77
Technical manual
The operation mode is set individually for each output, either OFF, TOGGLE or
PULSED.
Setting OFF
This mode always gives the output the value. A change of the input value does not
affect the output value.
Input value
Output value
IEC09000330-1-en.vsd
IEC09000330 V1 EN
Figure 26:
Sequence diagram for setting OFF
Setting TOGGLE
In this mode the output toggles each time the function block detects that the input has
been written (the input has completed a pulse). Note that the input attribute is reset
each time the function block executes. The function block execution is marked with
a dotted line below.
Input value
Output value
IEC09000331_1_en.vsd
IEC09000331 V1 EN
Figure 27:
Sequence diagram for setting TOGGLE
Setting PULSED
In this mode the output will be high for as long as the setting pulse time. After this time
the output will go back to 0. The input attribute is reset when the function block detects
it being high and there is no output pulse.
Note that the third positive edge on the input attribute does not cause a pulse, since the
edge was applied during pulse output. A new pulse can only begin when the output is
zero; else the trigger edge is lost.
Section 5
1MRK 502 048-UEN A
Local Human-Machine-Interface LHMI
78
Technical manual
IEC09000332 V1 EN
Figure 28:
Sequence diagram for setting PULSED
Input function
All inputs work the same way: When the LHMI is configured so that a certain function
button is of type CONTROL, then the corresponding input on this function block
becomes active, and will light the yellow function button LED when high. This
functionality is active even if the function block operation setting is set to off.
There is an exception for the optional extension EXT1 function keys 7 and 8, since
they are tri-color (they can be red, yellow or green). Each of these LEDs are controlled
by three inputs, which are prioritized in the following order: Red - Yellow - Green
INPUT
OUTPUT
RED
YELLOW
GREEN
Function key LED color
1
0/1
0/1
red
-
1
0/1
yellow
-
-
1
green
0
0
0
off
1MRK 502 048-UEN A
Section 5
Local Human-Machine-Interface LHMI
79
Technical manual
Transformer differential protection
6.1.1
Functionality
Transformer differential protection, three-winding T3WPDIF is provided with
internal CT ratio matching and vector group compensation and settable zero sequence
current elimination.
The function can be provided with -phase sets of current inputs. All current inputs are
provided with percentage bias restraint features, making the IED suitable for two- or
three-winding transformer arrangements.
Three-winding applications
xx05000052.vsd
IEC05000052 V1 EN
three-winding power
transformer with all
three windings
connected
xx05000049.vsd
IEC05000049 V1 EN
three-winding power
transformer with
unconnected delta
tertiary winding
Figure 29:
CT group arrangement
for differential
protection and other
protections
The setting facilities cover the application of the differential protection to all types of
power transformers and auto-transformers with or without load tap changer as well as
shunt reactors and local feeders within the station. An adaptive stabilizing feature is
included for heavy through-faults.
Stabilization is included for inrush and overexcitation currents respectively, cross-
blocking is also available. Adaptive stabilization is also included for system recovery
inrush and CT saturation during external faults. A high set unrestrained differential
current protection element is included for a very high speed tripping at a high internal
fault currents.
1MRK 502 048-UEN A
Section 6
Differential protection
81
Technical manual
Included is an innovative sensitive differential protection element based on the theory
of symmetrical components. This element offers the best possible coverage of power
transformer windings turn to turn faults.
6.1.2
Transformer differential protection, three winding T3WPDIF
6.1.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Transformer differential protection,
three-winding
T3WPDIF
3Id/I
SYMBOL-BB V1 EN
87T
6.1.2.2
Function block
T3WPDIF
I3PW1CT1*
I3PW2CT1*
I3PW3CT1*
BLOCK
TRIP
TRIPRES
TRIPUNRE
TRNSUNR
TRNSSENS
START
STL1
STL2
STL3
BLK2H
BLK5H
BLKWAV
IDALARM
IDL1MAG
IDL2MAG
IDL3MAG
IBIAS
IDNSMAG
IEC09000269_1_en.vsd
IEC09000269 V1 EN
Figure 30:
T3WPDIF function block
6.1.2.3
Signals
Table 24:
T3WPDIF Input signals
Name
Type
Default
Description
I3PW1CT1
GROUP
SIGNAL
-
Three phase current connection winding 1 (W1)
CT1
I3PW2CT1
GROUP
SIGNAL
-
Three phase current connection winding 2 (W2)
CT1
I3PW3CT1
GROUP
SIGNAL
-
Three phase current connection winding 3 (W3)
CT1
BLOCK
BOOLEAN
0
Block of function
Section 6
1MRK 502 048-UEN A
Differential protection
82
Technical manual
T3WPDIF Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TRIPRES
BOOLEAN
Start signal from restrained differential protection
TRIPUNRE
BOOLEAN
Start signal from unrestrained differential
protection
TRNSUNR
BOOLEAN
Start signal from unrestrained negative sequence
differential protection
TRNSSENS
BOOLEAN
Start signal from sensitive negative sequence
differential protection
START
BOOLEAN
General start signal
STL1
BOOLEAN
Start signal from phase L1
STL2
BOOLEAN
Start signal from phase L2
STL3
BOOLEAN
Start signal from phase L3
BLK2H
BOOLEAN
General second harmonic block signal
BLK5H
BOOLEAN
General fifth harmonic block signal
BLKWAV
BOOLEAN
General block signal from waveform criteria
IDALARM
BOOLEAN
General alarm for sustained differential currents
IDL1MAG
REAL
Magnitude of fundamental frequency differential
current, phase L1
IDL2MAG
REAL
Magnitude of fundamental frequency differential
current, phase L2
IDL3MAG
REAL
Magnitude of fundamental frequency differential
current, phase L3
IBIAS
REAL
Magnitude of the bias current, which is common to
all phases
IDNSMAG
REAL
Magnitude of the negative sequence differential
current
6.1.2.4
Settings
Table 26:
T3WPDIF Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IdMin
0.10 - 0.60
IB
0.01
0.30
Section 1 sensitivity current, usually W1
current
EndSection1
0.20 - 1.50
IB
0.01
1.25
End of section 1, multiple of W1 rated
current
EndSection2
1.00 - 10.00
IB
0.01
3.00
End of section 2, multiple of W1 rated
current
SlopeSection2
10.0 - 50.0
%
0.1
40.0
Slope in section 2 of operate-restrain
characteristics
SlopeSection3
30.0 - 100.0
%
0.1
80.0
Slope in section 3 of operate-restrain
characteristics
Table continues on next page
1MRK 502 048-UEN A
Section 6
Differential protection
83
Technical manual
1.00 - 50.00
IB
0.01
10.00
Unrestrained protection limit, multiple of
W1 rated current
I2/I1Ratio
5.0 - 100.0
%
0.1
15.0
Maximum ratio of 2nd harmonic to
fundamental harmonic differential current
I5/I1Ratio
5.0 - 100.0
%
0.1
25.0
Maximum ratio of 5th harmonic to
fundamental harmonic differential current
CrossBlockEn
Off
On
-
-
On
Operation Off/On for cross-block logic
between phases
NegSeqDiffEn
Off
On
-
-
On
Operation Off/On for negative sequence
differential function
IMinNegSeq
0.02 - 0.20
IB
0.01
0.04
Minimum negative sequence current
NegSeqROA
30.0 - 90.0
Deg
0.1
60.0
Operate angle for internal/external
negative sequence fault discriminator
SOTFMode
Off
On
-
-
On
Operation mode for switch onto fault
function
IDiffAlarm
0.05 - 1.00
IB
0.01
0.20
Differential current alarm, multiple of base
current, usually W1 current
tAlarmDelay
0.000 - 60.000
s
0.001
10.000
Time delay for differential current alarm
Table 27:
T3WPDIF Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSelW1
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, winding 1
GlobalBaseSelW2
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, winding 2
GlobalBaseSelW3
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, winding 3
ConnectTypeW1
WYE (Y)
Delta (D)
-
-
WYE (Y)
Connection type of winding 1: Y-wye or D-
delta
ConnectTypeW2
WYE (Y)
Delta (D)
-
-
WYE (Y)
Connection type of winding 2: Y-wye or D-
delta
ConnectTypeW3
WYE (Y)
Delta (D)
-
-
Delta (D)
Connection type of winding 3: Y-wye or D-
delta
ClockNumberW2
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
-
-
0 [0 deg]
Phase displacement between W2 &
W1=HV winding, hour notation
Table continues on next page
Section 6
1MRK 502 048-UEN A
Differential protection
84
Technical manual
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
-
-
5 [150 deg lag]
Phase displacement between W3 &
W1=HV winding, hour notation
ZSCurrSubtrW1
Off
On
-
-
On
Enable zero sequence subtraction for W1
side, Off/On
ZSCurrSubtrW2
Off
On
-
-
On
Enable zero sequence subtraction for W2
side, Off/On
ZSCurrSubtrW3
Off
On
-
-
On
Enable zero sequence subtraction for W3
side, Off/On
6.1.2.5
Monitored data
Table 28:
T3WPDIF Monitored data
Name
Type
Values (Range)
Unit
Description
IDL1MAG
REAL
-
A
Magnitude of
fundamental frequency
differential current, phase
L1
IDL2MAG
REAL
-
A
Magnitude of
fundamental frequency
differential current, phase
L2
IDL3MAG
REAL
-
A
Magnitude of
fundamental frequency
differential current, phase
L3
IBIAS
REAL
-
A
Magnitude of the bias
current, which is common
to all phases
IDNSMAG
REAL
-
A
Magnitude of the
negative sequence
differential current
6.1.3
Operation principle
The task of the power transformer differential protection is to determine whether a
fault is within the protected zone, or outside of the protected zone. The protected zone
is limited by the position of current transformers (see figure 31), and in principle can
include more objects than just a transformer. If the fault is found to be internal, the
faulty power transformer must be quickly disconnected from the system.
1MRK 502 048-UEN A
Section 6
Differential protection
85
Technical manual
The main CTs are normally supposed to be star connected and can be earthed in any
direction (that is, either "ToObject" or "FromObject"). Internally the IED will always
measure the currents on all sides of the power transformer with the same reference
direction towards the power transformer windings as shown in figure 31.
en05000186.vsd
IED
IW1
IW2
IW1
IW2
E1S1
Z1S1
E1S2
Z1S2
IEC05000186 V1 EN
Figure 31:
Typical CT location and definition of positive current direction
Due to the ratio of the number of turns of the windings and the connection group of the
protected transformer, the current between two windings can not be directly compared
to each other. Therefore the differential protection must first correlate all currents to
each other before any calculation can be performed.
In numerical differential protections this correlation and comparison is performed
mathematically. First, compensation for the protected transformer transformation
ratio and connection group is made, and only then the currents are compared phase-
wise. This makes external auxiliary (interposing) current transformers unnecessary.
Conversion of all currents to the common reference side of the power transformer is
performed by pre-programmed coefficient matrices, which depends on the protected
power transformer transformation ratio and connection group. Once the power
transformer vector group, rated currents and voltages have been entered by the user,
the differential protection is capable to calculate the matrix coefficients required in
order to perform the on-line current comparison by means of a fixed equation.
6.1.3.1
Function calculation principles
To make a differential IED as sensitive and stable as possible, restrained differential
characteristics have been developed and is now adopted as the general practice in the
protection of power transformers. The protection should be provided with a
proportional bias, which makes the protection operate for a certain percentage
differential current related to the current through the transformer. This stabilizes the
protection under through fault conditions while still permitting the system to have
good basic sensitivity. The following chapters explain how these quantities are
derived.
Section 6
1MRK 502 048-UEN A
Differential protection
86
Technical manual
Fundamental frequency differential currents
The fundamental frequency differential current is a vectorial sum (sum of
fundamental frequency phasors) of the individual phase currents from the different
sides of the protected power transformer.
Before any differential current can be calculated, the power transformer phase shift,
and its transformation ratio, must be accounted for. Conversion of all currents to a
common reference is performed in two steps:
•
all current phasors are phase-shifted to (referred to) the phase-reference side,
(whenever possible the first winding with star connection)
•
all currents magnitudes are always referred to the first winding of the power
transformer (typically transformer high-voltage side)
The two steps of conversion are made simultaneously on-line by the pre-programmed
coefficient matrices, as shown in equation 1 for a two-winding power transformer, and
in equation 2 for a three-winding power transformer.
These are the internal compensation algorithms within the differential
function. The protected power transformer data is always entered per
its nameplate. The Differential function will adapt nameplate data and
select proper reference windings.
1
1_
1
1_
2
_
2
2
2 _
1
2 _
2
_
1
3
3_
1
3_
2
IDL
IL
W
IL
W
Un W
IDL
A
IL
W
B
IL
W
Un W
IDL
IL
W
IL
W
é
ù
é
ù
é
ù
ê
ú
ê
ú
ê
ú
=
×
+
×
×
ê
ú
ê
ú
ê
ú
ê
ú
ê
ú
ê
ú
ë
û
ë
û
ë
û
1
2
3
EQUATION1880 V1 EN
(Equation 1)
where:
1.
is the resulting Differential Currents
2.
is the current contribution from the W1 side
3.
is the current contribution from the W2 side
1MRK 502 048-UEN A
Section 6
Differential protection
87
Technical manual
EQUATION1556 V2 EN
(Equation 2)
where:
1.
is the resulting Differential Currents
2.
is the current contribution from the W1 side
3.
is the current contribution from the W2 side
4.
is the current contribution from the W3 side
and where, for equation 1 and equation 2:
IDL1
is the fundamental frequency differential current in phase L1 (in W1 side primary amperes)
IDL2
is the fundamental frequency differential current in phase L2 (in W1 side primary amperes)
IDL3
is the fundamental frequency differential current in phase L3 (in W1 side primary amperes)
IL1_W1
is the fundamental frequency phase current in phase L1 on the W1 side
IL2_W1
is the fundamental frequency phase current in phase L2 on the W1 side
IL3_W1
is the fundamental frequency phase current in phase L3 on the W1 side
IL1_W2
is the fundamental frequency phase current in phase L1 on the W2 side
IL2_W2
is the fundamental frequency phase current in phase L2 on the W2 side
IL3_W2
is the fundamental frequency phase current in phase L3 on the W2 side
IL1_W3
is the fundamental frequency phase current in phase L1 on the W3 side
IL2_W3
is the fundamental frequency phase current in phase L2 on the W3 side
IL3_W3
is the fundamental frequency phase current in phase L3 on the W3 side
Ur_W1
is transformer rated phase-to-phase voltage on the W1 side (setting parameter)
Ur_W2
is transformer rated phase-to-phase voltage on the W2 side (setting parameter)
Ur_W3
is transformer rated phase-to-phase voltage on the W3 side (setting parameter)
A, B and C
are three by three matrices with numerical coefficients
Values of the matrix A, B and C coefficients depend on:
1.
The Power transformer winding connection type, such as star (Y/y) or delta (D/
d)
2.
The Transformer vector group such as Yd1, Dy11, YNautod5, Yy0d5 and so on,
which introduce phase displacement between individual windings currents in
multiples of 30°.
3.
The Settings for elimination of zero sequence currents for the individual
windings.
Section 6
1MRK 502 048-UEN A
Differential protection
88
Technical manual
When the end user enters all these parameters, transformer differential function
automatically determines the matrix coefficients based on the following rules:
For the phase reference, the highest voltage star (Y) connected winding is used. For
example, if the power transformer is a Yd1 power transformer, the HV winding (Y) is
taken as the phase reference winding. If the power transformer is a Yy0 power
transformer the HV winding (Y) is taken as the phase reference winding. If the power
transformer is a Dy1, then the LV winding (y) is taken for the phase reference. If there
is no star connected winding, such as in Dd0 type of power transformers, then the HV
delta winding (D) is automatically chosen as the phase reference winding.
The fundamental frequency differential currents are in general composed of currents
of all sequences, that is, the positive-, the negative-, and the zero-sequence currents.
If the zero-sequence currents are eliminated (see section "Elimination of zero
sequence currents"), then the differential currents can consist only of the positive-, and
the negative-sequence currents. When the zero-sequence current is subtracted on one
side of the power transformer , then it is subtracted from each individual phase current.
Table 29 summarizes the values of the matrices for all standard phase shifts between
windings.
Table 29:
Matrices for differential current calculation
Matrix with Zero Sequence
Reduction set to On
Matrix with Zero Sequence
Reduction set to Off
Matrix for Reference Winding
2
1
1
1
1
2
1
3
1
1
2
-
-
× -
-
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1227 V1 EN
(Equation 3)
1
0
0
0
1
0
0
0
1
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1228 V1 EN
(Equation 4)
Matrix for winding with 30°
lagging
1
-1
0
1
0
1
1
3
1
0
1
×
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1229 V1 EN
(Equation 5)
Not applicable. Matrix on the
left used.
Matrix for winding with 60°
lagging
1
2
1
1
1
1
2
3
2
1
1
-
×
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1230 V1 EN
(Equation 6)
0
1
0
0
0
1
1
0
0
-
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1231 V1 EN
(Equation 7)
Matrix for winding with 90°
lagging
0
-1
1
1
1
0
1
3
1
1
0
×
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1232 V1 EN
(Equation 8)
Not applicable. Matrix on the
left used.
Table continues on next page
1MRK 502 048-UEN A
Section 6
Differential protection
89
Technical manual
Matrix with Zero Sequence
Reduction set to On
Matrix with Zero Sequence
Reduction set to Off
Matrix for winding with 120°
lagging
1
1
2
1
2
1
1
3
1
2
1
-
-
×
-
-
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1233 V1 EN
(Equation 9)
0
0
1
1
0
0
0
1
0
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1234 V1 EN
(Equation 10)
Matrix for winding with 150°
lagging
-1
0
1
1
1
1
0
3
0
1
1
×
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1235 V1 EN
(Equation 11)
Not applicable. Matrix on the
left used.
Matrix for winding which is in
opposite phase
2
1
1
1
1
2
1
3
1
1
2
-
×
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1236 V1 EN
(Equation 12)
1
0
0
0
1
0
0
0
1
-
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1237 V1 EN
(Equation 13)
Matrix for winding with 150°
leading
-1
1
0
1
0
1
1
3
1
0
1
×
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1238 V1 EN
(Equation 14)
Not applicable. Matrix on the
left used.
Matrix for winding with 120°
leading
1
2
1
1
1
1
2
3
2
1
1
-
-
× -
-
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1239 V1 EN
(Equation 15)
0
1
0
0
0
1
1
0
0
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1240 V1 EN
(Equation 16)
Matrix for winding with 90°
leading
0
1
-1
1
-1
0
1
3
1
1
0
×
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1241 V1 EN
(Equation 17)
Not applicable. Matrix on the
left used.
Matrix for winding with 60°
leading
1
1
2
1
2
1
1
3
1
2
1
-
× -
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1242 V1 EN
(Equation 18)
0
0
1
1
0
0
0
1
0
-
-
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1243 V1 EN
(Equation 19)
Matrix for winding with 30°
leading
1
0
-1
1
-1
1
0
3
0
1
1
×
-
é
ù
ê
ú
ê
ú
ê
ú
ë
û
EQUATION1244 V1 EN
(Equation 20)
Not applicable. Matrix on the
left used.
By using this table we can derive a complete calculation for all common transformer
configuration. For example when considering a YNd5 power transformer the
following can be concluded:
Section 6
1MRK 502 048-UEN A
Differential protection
90
Technical manual
HV star (Y) connected winding will be used as reference winding and zero
sequence currents shall be subtracted on that side
2.
The LV winding is lagging for 150°
With the help of table 29, the following matrix equation can be written for this power
transformer:
1
2
1
1
1_
1
1
0
1
1_
2
1
_
2
1
2
1
2
1
2_
1
1
1
0
2_
2
3
_
1
3
3
1
1
2
3_
1
0
1
1
3_
2
IDL
IL
W
IL
W
Ur W
IDL
IL
W
IL
W
Ur W
IDL
IL
W
IL
W
-
-
-
é
ù
é
ù é
ù
é
ù é
ù
ê
ú
ê
ú ê
ú
ê
ú ê
ú
=
× -
-
×
+
×
×
-
×
ê
ú
ê
ú ê
ú
ê
ú ê
ú
ê
ú
ê
ú ê
ú
ê
ú ê
ú
-
-
-
ë
û
ë
û ë
û
ë
û ë
û
EQUATION2015 V1 EN
(Equation 21)
where:
IDL1
is the fundamental frequency differential current in phase L1 (in W1 side primary amperes)
IDL2
is the fundamental frequency differential current in phase L2 (in W1 side primary amperes)
IDL3
is the fundamental frequency differential current in phase L3 (in W1 side primary amperes)
IL1_W1
is the fundamental frequency phase current in phase L1 on the W1 side
IL2_W1
is the fundamental frequency phase current in phase L2 on the W1 side
IL3_W1
is the fundamental frequency phase current in phase L3 on the W1 side
IL1_W2
is the fundamental frequency phase current in phase L1 on the W2 side
IL2_W2
is the fundamental frequency phase current in phase L2 on the W2 side
IL3_W2
is the fundamental frequency phase current in phase L3 on the W2 side
Ur_W1
is transformer rated phase-to-phase voltage on the W1 side (setting parameter)
Ur_W2
is transformer rated phase-to-phase voltage on the W2 side (setting parameter)
As marked in equation 1 and equation 2, the first term on the right hand side of the
equation, represents the total contribution from the individual phase currents from the
W1 side to the fundamental frequency differential currents, compensated for eventual
power transformer phase shift. The second term on the right hand side of the equation,
represents the total contribution from the individual phase currents from the W2 side
to the fundamental frequency differential currents, compensated for eventual power
transformer phase shift and transferred to the power transformer reference side. The
third term on the right hand side of the equation, represents the total contribution from
the individual phase currents from the W3 side to the fundamental frequency
differential currents, compensated for eventual power transformer phase shift and
transferred to the power transformer reference side. .
The fundamental frequency differential currents are the magnitudes which are applied
in a phase segregated manner to the operate - restrain characteristic of the differential
protection. The magnitudes of the differential currents can be read as service values
from the function and they are available as outputs IDL1MAG, IDL2MAG,
IDL3MAG from the differential protection function block. Thus they can be
connected to the disturbance recorder and automatically recorded during any external
or internal fault condition.
1MRK 502 048-UEN A
Section 6
Differential protection
91
Technical manual
Differential current alarm
The fundamental frequency differential current level is monitored at all times within
the differential function. As soon as all three fundamental frequency differential
currents are set above the set alarm level (IDiffAlarm), the pickup timer is started.
When the pre-set time, defined by setting parameter tAlarmDelay, has expired a
differential current alarm is generated and the output signal IDALARM is set to
logical value one.
6.1.3.4
Bias current
The bias current is calculated as the highest current amongst all individual winding
current contributions, compensated for eventual power transformer phase shift and
transferred to the power transformer reference side. All individual winding current
contributions are already referred to the power transformer winding one side (power
transformer HV winding) and therefore they can be compared regarding their
magnitudes. There are six (or nine in the case of a three-winding transformer)
contributions to the total fundamental differential currents, which are the candidates
for the common bias current. The highest individual current contribution is taken as a
common bias (restrain) current for all three phases. This "maximum principle" makes
the differential protection more secure, with less risk to operate for external faults and
in the same time brings more meaning to the breakpoint settings of the operate -
restrain characteristic.
The magnitudes of the common bias (restrain) current expressed in reference side
amperes can be read as service value from the function. At the same time it is available
as an output IBIAS from the differential protection function block. It can be connected
to the disturbance recorder and automatically recorded during any external or internal
fault condition.
6.1.3.5
Elimination of zero sequence currents
The zero sequence currents can be eliminated from the differential bias current on a
per winding basis via a parameter.
Elimination of the zero sequence current component is necessary whenever:
•
the protected power transformer cannot transform the zero sequence currents to
the other side.
•
the zero sequence currents can only flow on one side of the protected power
transformer.
In most cases, power transformers do not properly transform the zero sequence current
to the other side. A typical example is a power transformer of the star-delta type, for
example YNd1. Transformers of this type do not transform the zero sequence
quantities, but zero sequence currents can flow in the earthed star- connected winding.
In such cases, an external earth-fault on the star-side causes zero sequence current to
flow on the star-side of the power transformer, but not on the delta side. This results
Section 6
1MRK 502 048-UEN A
Differential protection
92
Technical manual
in false differential currents - consisting exclusively of the zero sequence currents. If
high enough, these false differential currents can cause an unwanted disconnection of
the healthy power transformer. They must therefore be subtracted from the
fundamental frequency differential currents if an unwanted trip is to be avoided.
For delta windings this feature shall be enabled only if an earthing transformer exist
within the differential zone on the delta side of the protected power transformer.
Removing the zero sequence current from the differential currents decreases to some
extent the sensitivity of the differential protection for internal earth-faults. In order to
counteract this effect to some degree, the zero sequence current is subtracted not only
from the three fundamental frequency differential currents, but from the bias current
as well.
6.1.3.6
Restrained and unrestrained limits of the differential protection
The power transformer differential protection function uses two limits, to which
actual magnitudes of the three fundamental frequency differential currents are
compared at each execution of the function.
The unrestrained (that is, non-stabilized, "instantaneous") part of the differential
protection is used for very high differential currents, where it should be beyond any
doubt, that the fault is internal. This settable limit is constant and not proportional to
the bias current. Neither harmonic, nor any other restrain is applied to this limit, which
is therefore capable to trip the power transformer instantaneously.
The restrained (stabilized) part of the differential protection compares the calculated
fundamental differential (operating) currents and the bias (restrain) current, by
applying them to the operate - restrain characteristic. The operate - restrain
characteristic is represented by a double-slope, double-breakpoint diagram, where the
operating current is set against the bias current, as shown in figure 32 The
characteristic is determined by the following 5 settings:
1.
IdMin (Sensitivity in section 1, multiple of trans. Reference side rated current set
under the parameter IBase in GlobalbaseSelW1)
2.
EndSection1 (End of section 1, as multiple of transformer reference side rated
current set under the parameter IBase in GlobalbaseSelW1)
3.
EndSection2 (End of section 2, as multiple of transformer reference side rated
current set under the parameter IBase in GlobalbaseSelW1)
4.
SlopeSection2 (Slope in section 2, as multiple of transformer reference side rated
current set under the parameter IBase in GlobalbaseSelW1)
5.
SlopeSection3 (Slope in section 2, as multiple of transformer reference side rated
current set under the parameter IBase in GlobalbaseSelW1)
1MRK 502 048-UEN A
Section 6
Differential protection
93
Technical manual
[ times IBase ]
operate current
[ times IBase ]
SlopeSection2
SlopeSection3
en05000187-2.vsd
IEC05000187 V2 EN
Figure 32:
Description of the restrained, and the unrestrained operate
characteristics
where:
Ioperate 100%
slope
Irestrain
D
= D
×
EQUATION1246 V1 EN
The operate - restrain characteristic is tailor-made and can be designed freely by the
user after his needs. The default characteristic is recommended to be used. It gives
good results in a majority of applications. The reset ratio is in all parts of the
characteristic equal to 0.95.
Section 1: This is the most sensitive part on the characteristic. In section 1, normal
currents flow through the protected object and its current transformers, and risk for
higher false differential currents is relatively low. An un-compensated on-load tap-
changer is a typical reason for existence of the false differential currents in this
section. The slope in section 1 is always zero percent.
Section 6
1MRK 502 048-UEN A
Differential protection
94
Technical manual