ABB REG670 Applications Manual

Specifications

Brand: ABB
Category: Relays
Model: REG670 (Applications Manual)
File Type: PDF
File Size: —
Pages: 780

Read Online

Read the ABB REG670 Applications Manual online using the built-in PDF viewer.

Text of the manual

Document ID: 1MRK 502 071-UEN

Issued: May 2017 Revision: - Product version: 2.2 © Copyright 2017 ABB. All rights reserved

This document and parts thereof must not be reproduced or copied without written

permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license. This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographic software written/developed by: Eric Young ([email protected]) and Tim Hudson ([email protected]). Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders. Warranty Please inquire about the terms of warranty from your nearest ABB representative.

The data, examples and diagrams in this manual are included solely for the concept or

product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.

This product complies with the directive of the Council of the European Communities

on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive. The product is designed in accordance with the international standards of the IEC 60255 series.

Table of contents

Section 1 Introduction.....................................................................21 This manual......................................................................................21 Intended audience............................................................................21 Product documentation.....................................................................22 Product documentation set..........................................................22 Document revision history........................................................... 23 Related documents......................................................................23 Document symbols and conventions................................................24 Symbols.......................................................................................24 Document conventions................................................................25 IEC 61850 edition 1 / edition 2 mapping...........................................26 Section 2 Application......................................................................35 General IED application....................................................................35 Main protection functions..................................................................44 Back-up protection functions............................................................ 45 Control and monitoring functions......................................................46 Communication.................................................................................52 Basic IED functions.......................................................................... 55 Section 3 Configuration..................................................................57 Description of REG670.....................................................................57 Introduction..................................................................................57 Description of configuration A20 ........................................... 57 Description of configuration B30............................................ 58 Description of configuration C30............................................ 60 Section 4 Analog inputs..................................................................63 Introduction.......................................................................................63 Setting guidelines............................................................................. 63 Setting of the phase reference channel.......................................63 Example................................................................................. 64 Setting of current channels..........................................................64 Example 1.............................................................................. 65 Example 2.............................................................................. 65 Example 3.............................................................................. 66 Examples on how to connect, configure and set CT inputs for most commonly used CT connections.............................. 70 Example on how to connect a star connected three-phase CT set to the IED....................................................................71 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 1 Application manual

Example how to connect delta connected three-phase CT

set to the IED..........................................................................76 Example how to connect single-phase CT to the IED............ 79 Relationships between setting parameter Base Current, CT rated primary current and minimum pickup of a protection IED.. 80 Setting of voltage channels......................................................... 81 Example................................................................................. 81 Examples how to connect, configure and set VT inputs for most commonly used VT connections....................................82 Examples on how to connect a three phase-to-earth connected VT to the IED........................................................ 82 Example on how to connect a phase-to-phase connected VT to the IED..........................................................................84 Example on how to connect an open delta VT to the IED for high impedance earthed or unearthed networks...............86 Example how to connect the open delta VT to the IED for low impedance earthed or solidly earthed power systems.....89 Example on how to connect a neutral point VT to the IED.....90 Section 5 Local HMI....................................................................... 93 Display..............................................................................................94 LEDs.................................................................................................96 Keypad............................................................................................. 97 Local HMI functionality..................................................................... 99 Protection and alarm indication................................................... 99 Parameter management ...........................................................100 Front communication.................................................................101 Section 6 Wide area measurement system..................................103 C37.118 Phasor Measurement Data Streaming Protocol Configuration PMUCONF............................................................... 103 Identification.............................................................................. 103 Application.................................................................................103 Operation principle.................................................................... 103 Short guidance for use of TCP............................................. 104 Short guidance for use of UDP.............................................105 Protocol reporting via IEEE 1344 and C37.118 PMUREPORT......107 Identification.............................................................................. 107 Application.................................................................................107 Operation principle.................................................................... 110 Frequency reporting............................................................. 111 Reporting filters.................................................................... 113 Scaling Factors for ANALOGREPORT channels................. 114 PMU Report Function Blocks Connection Rules in PCM600 Application Configuration Tool (ACT)....................115 Table of contents 2 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Setting guidelines...................................................................... 121

Section 7 Differential protection................................................... 127 Transformer differential protection T2WPDIF and T3WPDIF ........ 127 Identification.............................................................................. 127 Application.................................................................................127 Setting guidelines...................................................................... 128 Restrained and unrestrained differential protection..............128 Elimination of zero sequence currents................................. 131 Inrush restraint methods.......................................................132 Overexcitation restraint method........................................... 132 Cross-blocking between phases.......................................... 133 External/Internal fault discriminator...................................... 133 On-line compensation for on-load tap-changer position.......135 Differential current alarm...................................................... 135 Open CT detection............................................................... 136 Switch onto fault feature.......................................................136 Setting example.........................................................................136 Introduction...........................................................................136 Typical main CT connections for transformer differential protection..............................................................................137 Application Examples...........................................................139 Summary and conclusions................................................... 146 High impedance differential protection, single phase HZPDIF ...... 148 Identification.............................................................................. 148 Application.................................................................................148 The basics of the high impedance principle......................... 150 Connection examples for high impedance differential protection...................................................................................156 Connections for three-phase high impedance differential protection..............................................................................156 Connections for 1Ph High impedance differential protection HZPDIF................................................................157 Setting guidelines...................................................................... 158 Configuration........................................................................158 Settings of protection function..............................................159 T-feeder protection...............................................................159 Tertiary reactor protection.................................................... 162 Restricted earth fault protection........................................... 165 Alarm level operation............................................................166 Generator differential protection GENPDIF ................................... 167 Identification.............................................................................. 167 Application.................................................................................168 Setting guidelines...................................................................... 169 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 3 Application manual

General settings................................................................... 169

Percentage restrained differential operation........................ 170 Negative sequence internal/external fault discriminator feature.................................................................................. 172 Open CT detection............................................................... 173 Other additional options....................................................... 174 Low impedance restricted earth fault protection REFPDIF ........... 175 Identification.............................................................................. 175 Application.................................................................................175 Transformer winding, solidly earthed................................... 176 Transformer winding, earthed through zig-zag earthing transformer...........................................................................177 Autotransformer winding, solidly earthed............................. 178 Reactor winding, solidly earthed.......................................... 178 Multi-breaker applications.................................................... 179 CT earthing direction............................................................180 Setting guidelines...................................................................... 180 Setting and configuration......................................................180 Settings................................................................................ 181 Section 8 Impedance protection...................................................183 Full-scheme distance measuring, Mho characteristic ZMHPDIS .. 183 Identification.............................................................................. 183 Application.................................................................................183 Generator underimpedance protection application.............. 183 Setting guidelines...................................................................... 183 Configuration........................................................................183 Settings................................................................................ 184 High speed distance protection ZMFPDIS..................................... 187 Identification.............................................................................. 187 Application.................................................................................188 System earthing................................................................... 188 Fault infeed from remote end............................................... 191 Load encroachment..............................................................192 Short line application............................................................193 Long transmission line application....................................... 194 Parallel line application with mutual coupling....................... 194 Tapped line application........................................................ 200 Setting guidelines...................................................................... 203 General.................................................................................203 Setting of zone 1.................................................................. 203 Setting of overreaching zone................................................203 Setting of reverse zone........................................................ 204 Setting of zones for parallel line application.........................205 Table of contents 4 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Setting the reach with respect to load.................................. 206

Zone reach setting lower than minimum load impedance.... 207 Zone reach setting higher than minimum load impedance...209 Other settings.......................................................................210 High speed distance protection for series compensated lines ZMFCPDIS .................................................................................... 213 Identification.............................................................................. 213 Application.................................................................................214 System earthing................................................................... 214 Fault infeed from remote end............................................... 216 Load encroachment..............................................................217 Short line application............................................................218 Long transmission line application....................................... 219 Parallel line application with mutual coupling....................... 219 Tapped line application........................................................ 226 Series compensation in power systems.................................... 228 Steady state voltage regulation and increase of voltage collapse limit.........................................................................228 Increase in power transfer....................................................230 Voltage and current inversion...............................................230 Impact of series compensation on protective IED of adjacent lines....................................................................... 239 Distance protection...............................................................240 Underreaching and overreaching schemes..........................241 Setting guidelines...................................................................... 247 General.................................................................................247 Setting of zone 1.................................................................. 248 Setting of overreaching zone................................................248 Setting of reverse zone........................................................ 249 Series compensated and adjacent lines...............................249 Setting of zones for parallel line application.........................254 Setting of reach in resistive direction....................................255 Load impedance limitation, without load encroachment function.................................................................................256 Zone reach setting higher than minimum load impedance...258 Parameter setting guidelines................................................259 Pole slip protection PSPPPAM ......................................................261 Identification.............................................................................. 262 Application.................................................................................262 Setting guidelines...................................................................... 265 Setting example for line application......................................267 Setting example for generator application............................271 Out-of-step protection OOSPPAM .................................................275 Identification.............................................................................. 275 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 5 Application manual

Setting guidelines...................................................................... 278

Loss of excitation LEXPDIS............................................................281 Identification.............................................................................. 281 Application.................................................................................281 Setting guidelines...................................................................... 287 Sensitive rotor earth fault protection, injection based ROTIPHIZ .. 290 Identification.............................................................................. 290 Application.................................................................................290 Rotor earth fault protection function..................................... 291 Setting guidelines...................................................................... 294 Setting injection unit REX060...............................................294 Connecting and setting voltage inputs................................. 295 Settings for sensitive rotor earth fault protection,ROTIPHIZ 297 100% stator earth fault protection, injection based STTIPHIZ .......299 Identification.............................................................................. 299 Application.................................................................................299 100% Stator earth fault protection function.......................... 300 Setting guidelines...................................................................... 305 Setting injection unit REX060...............................................305 Connecting and setting voltage inputs................................. 306 100% stator earth fault protection........................................ 307 Under impedance protection for generators and transformers ZGVPDIS........................................................................................308 Identification.............................................................................. 308 Application.................................................................................308 Operating zones...................................................................310 Zone 1 operation.................................................................. 311 Zone 2 operation.................................................................. 311 Zone 3 operation.................................................................. 312 CT and VT positions.............................................................312 Undervoltage seal-in function...............................................313 Load encroachment for zone 2 and zone 3..........................313 External block signals...........................................................314 Setting Guidelines..................................................................... 314 General.................................................................................314 Load encroachment..............................................................315 Under voltage seal-in........................................................... 316 Rotor earth fault protection using CVGAPC................................... 317 Section 9 Current protection.........................................................319 Instantaneous phase overcurrent protection PHPIOC .................. 319 Identification.............................................................................. 319 Application.................................................................................319 Table of contents 6 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Setting guidelines...................................................................... 320

Meshed network without parallel line................................... 320 Meshed network with parallel line........................................ 322 Directional phase overcurrent protection, four steps OC4PTOC....324 Identification.............................................................................. 324 Application.................................................................................324 Setting guidelines...................................................................... 325 Settings for each step...........................................................327 Setting example....................................................................330 Instantaneous residual overcurrent protection EFPIOC ................ 335 Identification.............................................................................. 335 Application.................................................................................335 Setting guidelines...................................................................... 335 Directional residual overcurrent protection, four steps EF4PTOC .338 Identification.............................................................................. 338 Application.................................................................................338 Setting guidelines...................................................................... 340 Common settings for all steps.............................................. 341 2nd harmonic restrain...........................................................342 Parallel transformer inrush current logic...............................343 Switch onto fault logic...........................................................344 Settings for each step (x = 1, 2, 3 and 4)............................. 344 Transformer application example......................................... 347 Four step directional negative phase sequence overcurrent protection NS4PTOC .....................................................................350 Identification.............................................................................. 350 Application.................................................................................350 Setting guidelines...................................................................... 352 Settings for each step ..........................................................353 Common settings for all steps.............................................. 355 Sensitive directional residual overcurrent and power protection SDEPSDE ..................................................................................... 356 Identification.............................................................................. 357 Application.................................................................................357 Setting guidelines...................................................................... 358 Thermal overload protection, two time constants TRPTTR ...........366 Identification.............................................................................. 367 Application.................................................................................367 Setting guideline........................................................................368 Breaker failure protection CCRBRF............................................... 370 Identification.............................................................................. 370 Application.................................................................................370 Setting guidelines...................................................................... 371 Pole discordance protection CCPDSC........................................... 374 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 7 Application manual

Setting guidelines...................................................................... 375

Directional underpower protection GUPPDUP............................... 376 Identification.............................................................................. 376 Application.................................................................................376 Setting guidelines...................................................................... 378 Directional overpower protection GOPPDOP ................................381 Identification.............................................................................. 381 Application.................................................................................381 Setting guidelines...................................................................... 383 Negativ sequence time overcurrent protection for machines NS2PTOC ......................................................................................387 Identification.............................................................................. 387 Application.................................................................................387 Features............................................................................... 388 Generator continuous unbalance current capability............. 389 Setting guidelines...................................................................... 391 Operate time characteristic.................................................. 391 Start sensitivity..................................................................... 392 Alarm function...................................................................... 392 Accidental energizing protection for synchronous generator AEGPVOC......................................................................................393 Identification.............................................................................. 393 Application.................................................................................393 Setting guidelines...................................................................... 393 Voltage-restrained time overcurrent protection VRPVOC.............. 394 Identification.............................................................................. 394 Application.................................................................................395 Base quantities.....................................................................395 Application possibilities........................................................ 396 Undervoltage seal-in............................................................ 396 Setting guidelines...................................................................... 397 Explanation of the setting parameters..................................397 Voltage-restrained overcurrent protection for generator and step-up transformer.......................................................398 General settings................................................................... 398 Overcurrent protection with undervoltage seal-in.................399 Generator stator overload protection GSPTTR ............................. 399 Identification.............................................................................. 400 Application.................................................................................400 Generator rotor overload protection GRPTTR ...............................400 Identification.............................................................................. 400 Application.................................................................................400 Table of contents 8 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Section 10 Voltage protection........................................................ 403

Two step undervoltage protection UV2PTUV ................................403 Identification.............................................................................. 403 Application.................................................................................403 Setting guidelines...................................................................... 404 Equipment protection, such as for motors and generators...404 Disconnected equipment detection...................................... 404 Power supply quality ........................................................... 404 Voltage instability mitigation.................................................404 Backup protection for power system faults...........................404 Settings for two step undervoltage protection...................... 405 Two step overvoltage protection OV2PTOV ..................................406 Identification.............................................................................. 406 Application.................................................................................406 Setting guidelines...................................................................... 407 Equipment protection, such as for motors, generators, reactors and transformers.................................................... 408 Equipment protection, capacitors......................................... 408 Power supply quality............................................................ 408 High impedance earthed systems........................................ 408 The following settings can be done for the two step overvoltage protection..........................................................408 Two step residual overvoltage protection ROV2PTOV ................. 410 Identification.............................................................................. 410 Application.................................................................................410 Setting guidelines...................................................................... 411 Equipment protection, such as for motors, generators, reactors and transformersEquipment protection for transformers.................................................................... 411 Equipment protection, capacitors......................................... 411 Stator earth-fault protection based on residual voltage measurement....................................................................... 412 Power supply quality............................................................ 415 High impedance earthed systems........................................ 415 Direct earthed system.......................................................... 416 Settings for two step residual overvoltage protection...........417 Overexcitation protection OEXPVPH ............................................ 419 Identification.............................................................................. 419 Application.................................................................................419 Setting guidelines...................................................................... 421 Recommendations for input and output signals................... 421 Settings................................................................................ 422 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 9 Application manual

Service value report............................................................. 423

Setting example....................................................................423 Voltage differential protection VDCPTOV ......................................425 Identification.............................................................................. 425 Application.................................................................................425 Setting guidelines...................................................................... 427 100% Stator earth fault protection, 3rd harmonic based STEFPHIZ429 Identification.............................................................................. 429 Application.................................................................................429 Setting guidelines...................................................................... 433 Section 11 Frequency protection....................................................437 Underfrequency protection SAPTUF ............................................. 437 Identification.............................................................................. 437 Application.................................................................................437 Setting guidelines...................................................................... 437 Overfrequency protection SAPTOF ...............................................438 Identification.............................................................................. 438 Application.................................................................................439 Setting guidelines...................................................................... 439 Rate-of-change of frequency protection SAPFRC .........................440 Identification.............................................................................. 440 Application.................................................................................440 Setting guidelines...................................................................... 440 Frequency time accumulation protection function FTAQFVR........ 441 Identification.............................................................................. 441 Application.................................................................................441 Setting guidelines...................................................................... 443 Section 12 Multipurpose protection................................................445 General current and voltage protection CVGAPC.......................... 445 Identification.............................................................................. 445 Application.................................................................................445 Current and voltage selection for CVGAPC function............446 Base quantities for CVGAPC function..................................448 Application possibilities........................................................ 449 Inadvertent generator energization...................................... 450 Setting guidelines...................................................................... 451 Directional negative sequence overcurrent protection......... 451 Negative sequence overcurrent protection...........................453 Generator stator overload protection in accordance with IEC or ANSI standards.........................................................455 Table of contents 10 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Open phase protection for transformer, lines or

generators and circuit breaker head flashover protection for generators.......................................................................457 Voltage restrained overcurrent protection for generator and step-up transformer.......................................................458 Loss of excitation protection for a generator........................ 458 Inadvertent generator energization...................................... 460 General settings of the instance...........................................462 Settings for OC1...................................................................462 Setting for OC2.....................................................................462 Setting for UC1.....................................................................463 Setting for UC2.....................................................................463 Settings for OV1...................................................................463 Setting for OV2.....................................................................463 Settings for UV1................................................................... 463 Setting for UV2.....................................................................464 Section 13 System protection and control......................................465 Multipurpose filter SMAIHPAC....................................................... 465 Identification.............................................................................. 465 Application.................................................................................465 Setting guidelines...................................................................... 466 Setting example....................................................................466 Section 14 Secondary system supervision.....................................471 Current circuit supervision CCSSPVC............................................471 Identification.............................................................................. 471 Application.................................................................................471 Setting guidelines...................................................................... 471 Fuse failure supervision FUFSPVC................................................472 Identification.............................................................................. 472 Application.................................................................................472 Setting guidelines...................................................................... 473 General.................................................................................473 Setting of common parameters............................................ 473 Negative sequence based....................................................474 Zero sequence based...........................................................475 Delta U and delta I ...............................................................475 Dead line detection...............................................................476 Fuse failure supervision VDSPVC..................................................476 Identification.............................................................................. 476 Application.................................................................................477 Setting guidelines...................................................................... 478 Section 15 Control..........................................................................479 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 11 Application manual

Synchrocheck, energizing check, and synchronizing SESRSYN...479

Identification.............................................................................. 479 Application.................................................................................479 Synchronizing.......................................................................479 Synchrocheck.......................................................................480 Energizing check..................................................................482 Voltage selection..................................................................483 External fuse failure..............................................................484 Application examples.................................................................485 Single circuit breaker with single busbar.............................. 486 Single circuit breaker with double busbar, external voltage selection............................................................................... 486 Single circuit breaker with double busbar, internal voltage selection............................................................................... 487 Double circuit breaker.......................................................... 488 1 1/2 circuit breaker..............................................................488 Setting guidelines...................................................................... 491 Apparatus control APC...................................................................496 Application.................................................................................496 Bay control QCBAY..............................................................500 Switch controller SCSWI...................................................... 501 Switches SXCBR/SXSWI..................................................... 502 Proxy for signals from switching device via GOOSE XLNPROXY..........................................................................503 Reservation function (QCRSV and RESIN)......................... 506 Interaction between modules.....................................................508 Setting guidelines...................................................................... 510 Bay control (QCBAY)........................................................... 511 Switch controller (SCSWI)....................................................511 Switch (SXCBR/SXSWI)...................................................... 512 Proxy for signals from switching device via GOOSE XLNPROXY..........................................................................513 Bay Reserve (QCRSV).........................................................513 Reservation input (RESIN)................................................... 513 Interlocking .................................................................................... 514 Configuration guidelines............................................................515 Interlocking for line bay ABC_LINE .......................................... 515 Application............................................................................515 Signals from bypass busbar.................................................516 Signals from bus-coupler......................................................517 Configuration setting............................................................ 519 Interlocking for bus-coupler bay ABC_BC ................................ 520 Application............................................................................521 Configuration........................................................................521 Table of contents 12 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Signals from all feeders........................................................521

Signals from bus-coupler......................................................523 Configuration setting............................................................ 525 Interlocking for transformer bay AB_TRAFO ............................526 Application............................................................................526 Signals from bus-coupler......................................................527 Configuration setting............................................................ 527 Interlocking for bus-section breaker A1A2_BS..........................528 Application............................................................................528 Signals from all feeders........................................................528 Configuration setting............................................................ 531 Interlocking for bus-section disconnector A1A2_DC ................ 532 Application............................................................................532 Signals in single breaker arrangement.................................532 Signals in double-breaker arrangement............................... 535 Signals in 1 1/2 breaker arrangement.................................. 538 Interlocking for busbar earthing switch BB_ES .........................539 Application............................................................................539 Signals in single breaker arrangement.................................539 Signals in double-breaker arrangement............................... 543 Signals in 1 1/2 breaker arrangement.................................. 544 Interlocking for double CB bay DB ........................................... 545 Application............................................................................545 Configuration setting............................................................ 546 Interlocking for 1 1/2 CB BH .....................................................547 Application............................................................................547 Configuration setting............................................................ 547 Voltage control................................................................................548 Application.................................................................................548 Setting guidelines...................................................................... 580 TR1ATCC or TR8ATCC general settings.............................580 TR1ATCC or TR8ATCC Setting group ................................581 TCMYLTC and TCLYLTC general settings.......................... 589 Logic rotating switch for function selection and LHMI presentation SLGAPC.................................................................... 590 Identification.............................................................................. 590 Application.................................................................................591 Setting guidelines...................................................................... 591 Selector mini switch VSGAPC........................................................591 Identification.............................................................................. 592 Application.................................................................................592 Setting guidelines...................................................................... 592 Generic communication function for Double Point indication DPGAPC........................................................................................ 593 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 13 Application manual

Setting guidelines...................................................................... 594

Single point generic control 8 signals SPC8GAPC........................ 594 Identification.............................................................................. 594 Application.................................................................................594 Setting guidelines...................................................................... 594 AutomationBits, command function for DNP3.0 AUTOBITS.......... 595 Identification.............................................................................. 595 Application.................................................................................595 Setting guidelines...................................................................... 595 Single command, 16 signals SINGLECMD.................................... 595 Identification.............................................................................. 595 Application.................................................................................596 Setting guidelines...................................................................... 597 Section 16 Logic.............................................................................599 Tripping logic SMPPTRC ...............................................................599 Identification.............................................................................. 599 Application.................................................................................599 Three-phase tripping............................................................ 600 Single- and/or three-phase tripping......................................601 Single-, two- or three-phase tripping.................................... 602 Lock-out................................................................................602 Example of directional data..................................................603 Blocking of the function block...............................................605 Setting guidelines...................................................................... 605 Trip matrix logic TMAGAPC........................................................... 605 Identification.............................................................................. 606 Application.................................................................................606 Setting guidelines...................................................................... 606 Logic for group alarm ALMCALH....................................................606 Identification.............................................................................. 606 Application.................................................................................607 Setting guidelines...................................................................... 607 Logic for group alarm WRNCALH.................................................. 607 Identification.............................................................................. 607 Application............................................................................607 Setting guidelines.................................................................607 Logic for group indication INDCALH...............................................607 Identification.............................................................................. 607 Application............................................................................608 Setting guidelines.................................................................608 Configurable logic blocks................................................................608 Table of contents 14 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Setting guidelines...................................................................... 608

Configuration........................................................................608 Fixed signal function block FXDSIGN............................................ 610 Identification.............................................................................. 610 Application.................................................................................610 Boolean 16 to Integer conversion B16I.......................................... 611 Identification.............................................................................. 611 Application.................................................................................611 Boolean to integer conversion with logical node representation, 16 bit BTIGAPC..............................................................................612 Identification.............................................................................. 612 Application.................................................................................612 Integer to Boolean 16 conversion IB16.......................................... 613 Identification.............................................................................. 614 Application.................................................................................614 Integer to Boolean 16 conversion with logic node representation ITBGAPC........................................................................................615 Identification.............................................................................. 615 Application.................................................................................615 Pulse integrator TIGAPC................................................................ 616 Identification.............................................................................. 616 Application.................................................................................616 Setting guidelines...................................................................... 616 Elapsed time integrator with limit transgression and overflow supervision TEIGAPC.....................................................................617 Identification.............................................................................. 617 Application.................................................................................617 Setting guidelines...................................................................... 617 Comparator for integer inputs - INTCOMP..................................... 618 Identification.............................................................................. 618 Application.................................................................................618 Setting guidelines...................................................................... 618 Setting example.........................................................................618 Comparator for real inputs - REALCOMP...................................... 619 Identification.............................................................................. 619 Application.................................................................................619 Setting guidelines...................................................................... 619 Setting example.........................................................................620 Section 17 Monitoring.....................................................................623 Measurement..................................................................................623 Identification.............................................................................. 623 Application.................................................................................623 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 15 Application manual

Setting guidelines...................................................................... 626

Setting examples..................................................................629 Gas medium supervision SSIMG................................................... 635 Identification.............................................................................. 635 Application.................................................................................635 Setting guidelines...................................................................... 635 Liquid medium supervision SSIML................................................. 636 Identification.............................................................................. 636 Application.................................................................................637 Setting guidelines...................................................................... 637 Breaker monitoring SSCBR............................................................638 Identification.............................................................................. 638 Application.................................................................................638 Setting guidelines...................................................................... 640 Setting procedure on the IED...............................................641 Event function EVENT....................................................................642 Identification.............................................................................. 642 Application.................................................................................642 Setting guidelines...................................................................... 642 Disturbance report DRPRDRE....................................................... 643 Identification.............................................................................. 643 Application.................................................................................643 Setting guidelines...................................................................... 644 Recording times................................................................... 647 Binary input signals.............................................................. 647 Analog input signals............................................................. 648 Sub-function parameters......................................................648 Consideration....................................................................... 649 Logical signal status report BINSTATREP..................................... 650 Identification.............................................................................. 650 Application.................................................................................650 Setting guidelines...................................................................... 651 Limit counter L4UFCNT..................................................................651 Identification.............................................................................. 651 Application.................................................................................651 Setting guidelines...................................................................... 651 Running hour-meter TEILGAPC.....................................................652 Identification.............................................................................. 652 Application.................................................................................652 Setting guidelines...................................................................... 652 Estimation of transformer insulation life LOLSPTR ....................... 652 Application.................................................................................652 Table of contents 16 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Setting guidelines...................................................................... 657

Setting example.........................................................................665 Transformer Rated Data.......................................................665 Setting parameters for insulation loss of life calculation function (LOL1).....................................................................666 Section 18 Metering....................................................................... 671 Pulse-counter logic PCFCNT......................................................... 671 Identification.............................................................................. 671 Application.................................................................................671 Setting guidelines...................................................................... 671 Function for energy calculation and demand handling ETPMMTR 672 Identification.............................................................................. 672 Application.................................................................................672 Setting guidelines...................................................................... 673 Section 19 Ethernet-based communication....................................675 Access point................................................................................... 675 Application.................................................................................675 Setting guidelines...................................................................... 675 Redundant communication.............................................................676 Identification.............................................................................. 676 Application.................................................................................677 Setting guidelines...................................................................... 678 Merging unit....................................................................................679 Application.................................................................................679 Setting guidelines...................................................................... 680 Routes............................................................................................ 680 Application.................................................................................680 Setting guidelines...................................................................... 680 Section 20 Station communication.................................................681 Communication protocols...............................................................681 IEC 61850-8-1 communication protocol......................................... 681 Application IEC 61850-8-1.........................................................681 Setting guidelines...................................................................... 683 Horizontal communication via GOOSE..................................... 683 Sending data........................................................................ 683 Receiving data......................................................................684 IEC/UCA 61850-9-2LE communication protocol............................ 685 Introduction................................................................................685 Setting guidelines...................................................................... 687 Specific settings related to the IEC/UCA 61850-9-2LE communication..................................................................... 688 Loss of communication when used with LDCM....................688 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 17 Application manual

Setting examples for IEC/UCA 61850-9-2LE and time

synchronization.................................................................... 692 IEC 61850 quality expander QUALEXP.................................... 697 LON communication protocol......................................................... 698 Application.................................................................................698 MULTICMDRCV and MULTICMDSND..................................... 700 Identification......................................................................... 700 Application............................................................................700 Setting guidelines.................................................................700 SPA communication protocol......................................................... 700 Application.................................................................................700 Setting guidelines...................................................................... 701 IEC 60870-5-103 communication protocol..................................... 703 Application.................................................................................703 Functionality......................................................................... 703 Design.................................................................................. 704 Settings......................................................................................706 Settings for RS485 and optical serial communication.......... 707 Settings from PCM600......................................................... 708 Function and information types................................................. 710 DNP3 Communication protocol...................................................... 711 Application.................................................................................711 Section 21 Remote communication................................................713 Binary signal transfer......................................................................713 Identification.............................................................................. 713 Application.................................................................................713 Communication hardware solutions..................................... 714 Setting guidelines...................................................................... 715 Section 22 Security........................................................................ 719 Authority status ATHSTAT............................................................. 719 Application.................................................................................719 Self supervision with internal event list INTERRSIG...................... 719 Application.................................................................................719 Change lock CHNGLCK.................................................................720 Application.................................................................................720 Denial of service SCHLCCH/RCHLCCH ....................................... 721 Application.................................................................................721 Setting guidelines...................................................................... 721 Section 23 Basic IED functions...................................................... 723 IED identifiers TERMINALID.......................................................... 723 Application.................................................................................723 Table of contents 18 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Product information PRODINF....................................................... 723

Application.................................................................................723 Factory defined settings............................................................ 723 Measured value expander block RANGE_XP................................ 724 Identification.............................................................................. 724 Application.................................................................................725 Setting guidelines...................................................................... 725 Parameter setting groups............................................................... 725 Application.................................................................................725 Setting guidelines...................................................................... 726 Rated system frequency PRIMVAL................................................ 726 Identification.............................................................................. 726 Application.................................................................................726 Setting guidelines...................................................................... 726 Summation block 3 phase 3PHSUM.............................................. 726 Application.................................................................................726 Setting guidelines...................................................................... 727 Global base values GBASVAL....................................................... 727 Identification.............................................................................. 727 Application.................................................................................727 Setting guidelines...................................................................... 727 Signal matrix for binary inputs SMBI.............................................. 728 Application.................................................................................728 Setting guidelines...................................................................... 728 Signal matrix for binary outputs SMBO ......................................... 728 Application.................................................................................728 Setting guidelines...................................................................... 728 Signal matrix for mA inputs SMMI.................................................. 728 Application.................................................................................729 Setting guidelines...................................................................... 729 Signal matrix for analog inputs SMAI............................................. 729 Application.................................................................................729 Frequency values...................................................................... 729 Setting guidelines...................................................................... 730 Test mode functionality TESTMODE..............................................736 Application.................................................................................736 IEC 61850 protocol test mode..............................................736 Setting guidelines...................................................................... 737 Time synchronization TIMESYNCHGEN........................................737 Application.................................................................................737 Setting guidelines...................................................................... 739 System time..........................................................................739 Synchronization....................................................................739 Table of contents Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 19 Application manual

Process bus IEC/UCA 61850-9-2LE synchronization.......... 742

Section 24 Requirements...............................................................743 Current transformer requirements.................................................. 743 Current transformer basic classification and requirements....... 743 Conditions..................................................................................745 Fault current.............................................................................. 746 Secondary wire resistance and additional load......................... 746 General current transformer requirements................................ 746 Rated equivalent secondary e.m.f. requirements......................747 Guide for calculation of CT for generator differential protection..............................................................................747 Transformer differential protection....................................... 753 Breaker failure protection..................................................... 754 Restricted earth fault protection (low impedance differential)754 Current transformer requirements for CTs according to other standards...................................................................................757 Current transformers according to IEC 61869-2, class P, PR757 Current transformers according to IEC 61869-2, class PX, PXR (and old IEC 60044-6, class TPS and old British Standard, class X)........................................ 757 Current transformers according to ANSI/IEEE..................... 758 Voltage transformer requirements.................................................. 758 SNTP server requirements............................................................. 759 PTP requirements...........................................................................759 Sample specification of communication requirements for the protection and control terminals in digital telecommunication networks......................................................................................... 759 IEC/UCA 61850-9-2LE Merging unit requirements ....................... 760 Section 25 Glossary....................................................................... 763 Table of contents 20 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

The application manual contains application descriptions and setting guidelines

sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also provide assistance for calculating settings. 1.2 Intended audience This manual addresses the protection and control engineer responsible for planning, pre-engineering and engineering. The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology, such as protection schemes and communication principles. 1MRK 502 071-UEN - Section 1 Introduction Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 21 Application manual

Product documentation set

IEC07000220-4-en.vsd Planning & purchase Engineering Installing Commissioning Operation Maintenance Decommissioning Deinstalling & disposal Application manual Operation manual Installation manual Engineering manual Communication protocol manual Cyber security deployment guideline Technical manual Commissioning manual IEC07000220 V4 EN Figure 1: The intended use of manuals throughout the product lifecycle The engineering manual contains instructions on how to engineer the IEDs using the various tools available within the PCM600 software. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for the engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 60870-5-103, IEC 61850, DNP3, LON and SPA. The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in the chronological order in which the IED should be installed. The commissioning manual contains instructions on how to commission the IED. The manual can also be used by system engineers and maintenance personnel for assistance during the testing phase. The manual provides procedures for the checking of external circuitry and energizing the IED, parameter setting and configuration as Section 1 1MRK 502 071-UEN - Introduction 22 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

well as verifying settings by secondary injection. The manual describes the process of

testing an IED in a substation which is not in service. The chapters are organized in the chronological order in which the IED should be commissioned. The relevant procedures may be followed also during the service and maintenance activities. The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for the monitoring, controlling and setting of the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also provide assistance for calculating settings. The technical manual contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The communication protocol manual describes the communication protocols supported by the IED. The manual concentrates on the vendor-specific implementations. The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. The cyber security deployment guideline describes the process for handling cyber security when communicating with the IED. Certification, Authorization with role based access control, and product engineering for cyber security related events are described and sorted by function. The guideline can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. 1.3.2 Document revision history Document revision/date History –/May 2017 First release 1.3.3 Related documents Documents related to REG670 Document numbers Application manual 1MRK 502 071-UEN Commissioning manual 1MRK 502 073-UEN Product guide 1MRK 502 074-BEN Technical manual 1MRK 502 072-UEN Type test certificate 1MRK 502 074-TEN 1MRK 502 071-UEN - Section 1 Introduction Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 23 Application manual

670 series manuals

Document numbers Operation manual 1MRK 500 127-UEN Engineering manual 1MRK 511 398-UEN Installation manual 1MRK 514 026-UEN Communication protocol manual, DNP3 1MRK 511 391-UUS Communication protocol manual, IEC 60870-5-103 1MRK 511 394-UEN Communication protocol manual, IEC 61850 Edition 1 1MRK 511 392-UEN Communication protocol manual, IEC 61850 Edition 2 1MRK 511 393-UEN Communication protocol manual, LON 1MRK 511 395-UEN Communication protocol manual, SPA 1MRK 511 396-UEN Point list manual, DNP3 1MRK 511 397-UUS Accessories guide 1MRK 514 012-BEN Cyber security deployment guideline 1MRK 511 399-UEN Connection and Installation components 1MRK 513 003-BEN Test system, COMBITEST 1MRK 512 001-BEN Application guide, Communication set-up 1MRK 505 382-UEN 1.4 Document symbols and conventions 1.4.1 Symbols The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury. The caution hot surface icon indicates important information or warning about the temperature of product surfaces. Class 1 Laser product. Take adequate measures to protect the eyes and do not view directly with optical instruments. The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of Section 1 1MRK 502 071-UEN - Introduction 24 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

a hazard which could result in corruption of software or damage to

equipment or property. The information icon alerts the reader of important facts and conditions. The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. It is important that the user fully complies with all warning and cautionary notices. 1.4.2 Document conventions • Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. • Push button navigation in the LHMI menu structure is presented by using the push button icons. For example, to navigate between the options, use and . • HMI menu paths are presented in bold. For example, select Main menu/Settings. • LHMI messages are shown in Courier font. For example, to save the changes in non-volatile memory, select Yes and press . • Parameter names are shown in italics. For example, the function can be enabled and disabled with the Operation setting. • Each function block symbol shows the available input/output signal. • the character ^ in front of an input/output signal name indicates that the signal name may be customized using the PCM600 software. • the character * after an input signal name indicates that the signal must be connected to another function block in the application configuration to achieve a valid application configuration. • Logic diagrams describe the signal logic inside the function block and are bordered by dashed lines. • Signals in frames with a shaded area on their right hand side represent setting parameter signals that are only settable via the PST, ECT or LHMI. • If an internal signal path cannot be drawn with a continuous line, the suffix -int is added to the signal name to indicate where the signal starts and continues. • Signal paths that extend beyond the logic diagram and continue in another diagram have the suffix ”-cont.” 1MRK 502 071-UEN - Section 1 Introduction Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 25 Application manual

Illustrations are used as an example and might show other products

than the one the manual describes. The example that is illustrated is still valid. 1.5 IEC 61850 edition 1 / edition 2 mapping Function block names are used in ACT and PST to identify functions. Respective function block names of Edition 1 logical nodes and Edition 2 logical nodes are shown in the table below. Table 1: IEC 61850 edition 1 / edition 2 mapping Function block name Edition 1 logical nodes Edition 2 logical nodes AEGPVOC AEGGAPC AEGPVOC AGSAL AGSAL SECLLN0 AGSAL ALMCALH ALMCALH ALMCALH ALTIM - ALTIM ALTMS - ALTMS ALTRK - ALTRK BCZPDIF BCZPDIF BCZPDIF BCZSPDIF BCZSPDIF BCZSPDIF BCZTPDIF BCZTPDIF BCZTPDIF BDCGAPC SWSGGIO BBCSWI BDCGAPC BDZSGAPC BBS6LLN0 BDZSGAPC LLN0 BDZSGAPC BFPTRC_F01 BFPTRC BFPTRC BFPTRC_F02 BFPTRC BFPTRC BFPTRC_F03 BFPTRC BFPTRC BFPTRC_F04 BFPTRC BFPTRC BFPTRC_F05 BFPTRC BFPTRC BFPTRC_F06 BFPTRC BFPTRC BFPTRC_F07 BFPTRC BFPTRC BFPTRC_F08 BFPTRC BFPTRC BFPTRC_F09 BFPTRC BFPTRC BFPTRC_F10 BFPTRC BFPTRC BFPTRC_F11 BFPTRC BFPTRC BFPTRC_F12 BFPTRC BFPTRC BFPTRC_F13 BFPTRC BFPTRC BFPTRC_F14 BFPTRC BFPTRC BFPTRC_F15 BFPTRC BFPTRC Table continues on next page Section 1 1MRK 502 071-UEN - Introduction 26 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes BFPTRC_F16 BFPTRC BFPTRC BFPTRC_F17 BFPTRC BFPTRC BFPTRC_F18 BFPTRC BFPTRC BFPTRC_F19 BFPTRC BFPTRC BFPTRC_F20 BFPTRC BFPTRC BFPTRC_F21 BFPTRC BFPTRC BFPTRC_F22 BFPTRC BFPTRC BFPTRC_F23 BFPTRC BFPTRC BFPTRC_F24 BFPTRC BFPTRC BICPTRC_01 BICPTRC BICPTRC BICPTRC_02 BICPTRC BICPTRC BICPTRC_03 BICPTRC BICPTRC BICPTRC_04 BICPTRC BICPTRC BICPTRC_05 BICPTRC BICPTRC BRCPTOC BRCPTOC BRCPTOC BRPTOC BRPTOC BRPTOC BTIGAPC B16IFCVI BTIGAPC BUSPTRC_B1 BUSPTRC BBSPLLN0 BUSPTRC BUSPTRC_B2 BUSPTRC BUSPTRC BUSPTRC_B3 BUSPTRC BUSPTRC BUSPTRC_B4 BUSPTRC BUSPTRC BUSPTRC_B5 BUSPTRC BUSPTRC BUSPTRC_B6 BUSPTRC BUSPTRC BUSPTRC_B7 BUSPTRC BUSPTRC BUSPTRC_B8 BUSPTRC BUSPTRC BUSPTRC_B9 BUSPTRC BUSPTRC BUSPTRC_B10 BUSPTRC BUSPTRC BUSPTRC_B11 BUSPTRC BUSPTRC BUSPTRC_B12 BUSPTRC BUSPTRC BUSPTRC_B13 BUSPTRC BUSPTRC BUSPTRC_B14 BUSPTRC BUSPTRC BUSPTRC_B15 BUSPTRC BUSPTRC BUSPTRC_B16 BUSPTRC BUSPTRC BUSPTRC_B17 BUSPTRC BUSPTRC BUSPTRC_B18 BUSPTRC BUSPTRC BUSPTRC_B19 BUSPTRC BUSPTRC BUSPTRC_B20 BUSPTRC BUSPTRC BUSPTRC_B21 BUSPTRC BUSPTRC BUSPTRC_B22 BUSPTRC BUSPTRC Table continues on next page 1MRK 502 071-UEN - Section 1 Introduction Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 27 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes BUSPTRC_B23 BUSPTRC BUSPTRC BUSPTRC_B24 BUSPTRC BUSPTRC BUTPTRC_B1 BUTPTRC BBTPLLN0 BUTPTRC BUTPTRC_B2 BUTPTRC BUTPTRC BUTPTRC_B3 BUTPTRC BUTPTRC BUTPTRC_B4 BUTPTRC BUTPTRC BUTPTRC_B5 BUTPTRC BUTPTRC BUTPTRC_B6 BUTPTRC BUTPTRC BUTPTRC_B7 BUTPTRC BUTPTRC BUTPTRC_B8 BUTPTRC BUTPTRC BZISGGIO BZISGGIO BZISGAPC BZITGGIO BZITGGIO BZITGAPC BZNPDIF_Z1 BZNPDIF BZNPDIF BZNPDIF_Z2 BZNPDIF BZNPDIF BZNPDIF_Z3 BZNPDIF BZNPDIF BZNPDIF_Z4 BZNPDIF BZNPDIF BZNPDIF_Z5 BZNPDIF BZNPDIF BZNPDIF_Z6 BZNPDIF BZNPDIF BZNSPDIF_A BZNSPDIF BZASGAPC BZASPDIF BZNSGAPC BZNSPDIF BZNSPDIF_B BZNSPDIF BZBSGAPC BZBSPDIF BZNSGAPC BZNSPDIF BZNTPDIF_A BZNTPDIF BZATGAPC BZATPDIF BZNTGAPC BZNTPDIF BZNTPDIF_B BZNTPDIF BZBTGAPC BZBTPDIF BZNTGAPC BZNTPDIF CBPGAPC CBPLLN0 CBPMMXU CBPPTRC HOLPTOV HPH1PTOV PH3PTUC PH3PTOC RP3PDOP CBPMMXU CBPPTRC HOLPTOV HPH1PTOV PH3PTOC PH3PTUC RP3PDOP CCPDSC CCRPLD CCPDSC CCRBRF CCRBRF CCRBRF CCRWRBRF CCRWRBRF CCRWRBRF CCSRBRF CCSRBRF CCSRBRF Table continues on next page Section 1 1MRK 502 071-UEN - Introduction 28 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes CCSSPVC CCSRDIF CCSSPVC CMMXU CMMXU CMMXU CMSQI CMSQI CMSQI COUVGAPC COUVLLN0 COUVPTOV COUVPTUV COUVPTOV COUVPTUV CVGAPC GF2LLN0 GF2MMXN GF2PHAR GF2PTOV GF2PTUC GF2PTUV GF2PVOC PH1PTRC GF2MMXN GF2PHAR GF2PTOV GF2PTUC GF2PTUV GF2PVOC PH1PTRC CVMMXN CVMMXN CVMMXN D2PTOC D2LLN0 D2PTOC PH1PTRC D2PTOC PH1PTRC DPGAPC DPGGIO DPGAPC DRPRDRE DRPRDRE DRPRDRE ECPSCH ECPSCH ECPSCH ECRWPSCH ECRWPSCH ECRWPSCH EF2PTOC EF2LLN0 EF2PTRC EF2RDIR GEN2PHAR PH1PTOC EF2PTRC EF2RDIR GEN2PHAR PH1PTOC EF4PTOC EF4LLN0 EF4PTRC EF4RDIR GEN4PHAR PH1PTOC EF4PTRC EF4RDIR GEN4PHAR PH1PTOC EFPIOC EFPIOC EFPIOC EFRWPIOC EFRWPIOC EFRWPIOC ETPMMTR ETPMMTR ETPMMTR FDPSPDIS FDPSPDIS FDPSPDIS FMPSPDIS FMPSPDIS FMPSPDIS FRPSPDIS FPSRPDIS FPSRPDIS FTAQFVR FTAQFVR FTAQFVR FUFSPVC SDDRFUF FUFSPVC SDDSPVC GENPDIF GENPDIF GENGAPC GENPDIF GENPHAR GENPTRC GOPPDOP GOPPDOP GOPPDOP PH1PTRC GRPTTR GRPTTR GRPTTR GSPTTR GSPTTR GSPTTR Table continues on next page 1MRK 502 071-UEN - Section 1 Introduction Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 29 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes GUPPDUP GUPPDUP GUPPDUP PH1PTRC HZPDIF HZPDIF HZPDIF INDCALCH INDCALH INDCALH ITBGAPC IB16FCVB ITBGAPC L3CPDIF L3CPDIF L3CGAPC L3CPDIF L3CPHAR L3CPTRC L4CPDIF L4CLLN0 L4CPDIF L4CPTRC LLN0 L4CGAPC L4CPDIF L4CPSCH L4CPTRC L4UFCNT L4UFCNT L4UFCNT L6CPDIF L6CPDIF L6CGAPC L6CPDIF L6CPHAR L6CPTRC LAPPGAPC LAPPLLN0 LAPPPDUP LAPPPUPF LAPPPDUP LAPPPUPF LCCRPTRC LCCRPTRC LCCRPTRC LCNSPTOC LCNSPTOC LCNSPTOC LCNSPTOV LCNSPTOV LCNSPTOV LCP3PTOC LCP3PTOC LCP3PTOC LCP3PTUC LCP3PTUC LCP3PTUC LCPTTR LCPTTR LCPTTR LCZSPTOC LCZSPTOC LCZSPTOC LCZSPTOV LCZSPTOV LCZSPTOV LD0LLN0 LLN0 - LDLPSCH LDLPDIF LDLPSCH LDRGFC STSGGIO LDRGFC LEXPDIS LEXPDIS LEXPDIS LEXPTRC LFPTTR LFPTTR LFPTTR LMBRFLO LMBRFLO LMBRFLO LOLSPTR LOLSPTR LOLSPTR LOVPTUV LOVPTUV LOVPTUV LPHD LPHD LPTTR LPTTR LPTTR LT3CPDIF LT3CPDIF LT3CGAPC LT3CPDIF LT3CPHAR LT3CPTRC Table continues on next page Section 1 1MRK 502 071-UEN - Introduction 30 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes LT6CPDIF LT6CPDIF LT6CGAPC LT6CPDIF LT6CPHAR LT6CPTRC MVGAPC MVGGIO MVGAPC NS2PTOC NS2LLN0 NS2PTOC NS2PTRC NS2PTOC NS2PTRC NS4PTOC EF4LLN0 EF4PTRC EF4RDIR GEN4PHAR PH1PTOC EF4PTRC EF4RDIR PH1PTOC O2RWPTOV GEN2LLN0 O2RWPTOV PH1PTRC O2RWPTOV PH1PTRC OC4PTOC OC4LLN0 GEN4PHAR PH3PTOC PH3PTRC GEN4PHAR PH3PTOC PH3PTRC OEXPVPH OEXPVPH OEXPVPH OOSPPAM OOSPPAM OOSPPAM OOSPTRC OV2PTOV GEN2LLN0 OV2PTOV PH1PTRC OV2PTOV PH1PTRC PAPGAPC PAPGAPC PAPGAPC PCFCNT PCGGIO PCFCNT PH4SPTOC GEN4PHAR OCNDLLN0 PH1BPTOC PH1PTRC GEN4PHAR PH1BPTOC PH1PTRC PHPIOC PHPIOC PHPIOC PSLPSCH ZMRPSL PSLPSCH PSPPPAM PSPPPAM PSPPPAM PSPPTRC QCBAY QCBAY BAY/LLN0 QCRSV QCRSV QCRSV RCHLCCH RCHLCCH RCHLCCH REFPDIF REFPDIF REFPDIF ROTIPHIZ ROTIPHIZ ROTIPHIZ ROTIPTRC ROV2PTOV GEN2LLN0 PH1PTRC ROV2PTOV PH1PTRC ROV2PTOV SAPFRC SAPFRC SAPFRC SAPTOF SAPTOF SAPTOF SAPTUF SAPTUF SAPTUF SCCVPTOC SCCVPTOC SCCVPTOC Table continues on next page 1MRK 502 071-UEN - Section 1 Introduction Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 31 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes SCHLCCH SCHLCCH SCHLCCH SCILO SCILO SCILO SCSWI SCSWI SCSWI SDEPSDE SDEPSDE SDEPSDE SDEPTOC SDEPTOV SDEPTRC SESRSYN RSY1LLN0 AUT1RSYN MAN1RSYN SYNRSYN AUT1RSYN MAN1RSYN SYNRSYN SLGAPC SLGGIO SLGAPC SMBRREC SMBRREC SMBRREC SMPPTRC SMPPTRC SMPPTRC SP16GAPC SP16GGIO SP16GAPC SPC8GAPC SPC8GGIO SPC8GAPC SPGAPC SPGGIO SPGAPC SSCBR SSCBR SSCBR SSIMG SSIMG SSIMG SSIML SSIML SSIML STBPTOC STBPTOC BBPMSS STBPTOC STEFPHIZ STEFPHIZ STEFPHIZ STTIPHIZ STTIPHIZ STTIPHIZ SXCBR SXCBR SXCBR SXSWI SXSWI SXSWI T2WPDIF T2WPDIF T2WGAPC T2WPDIF T2WPHAR T2WPTRC T3WPDIF T3WPDIF T3WGAPC T3WPDIF T3WPHAR T3WPTRC TCLYLTC TCLYLTC TCLYLTC TCSLTC TCMYLTC TCMYLTC TCMYLTC TEIGAPC TEIGGIO TEIGAPC TEIGGIO TEILGAPC TEILGGIO TEILGAPC TMAGAPC TMAGGIO TMAGAPC TPPIOC TPPIOC TPPIOC TR1ATCC TR1ATCC TR1ATCC TR8ATCC TR8ATCC TR8ATCC TRPTTR TRPTTR TRPTTR Table continues on next page Section 1 1MRK 502 071-UEN - Introduction 32 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes U2RWPTUV GEN2LLN0 PH1PTRC U2RWPTUV PH1PTRC U2RWPTUV UV2PTUV GEN2LLN0 PH1PTRC UV2PTUV PH1PTRC UV2PTUV VDCPTOV VDCPTOV VDCPTOV VDSPVC VDRFUF VDSPVC VMMXU VMMXU VMMXU VMSQI VMSQI VMSQI VNMMXU VNMMXU VNMMXU VRPVOC VRLLN0 PH1PTRC PH1PTUV VRPVOC PH1PTRC PH1PTUV VRPVOC VSGAPC VSGGIO VSGAPC WRNCALH WRNCALH WRNCALH ZC1PPSCH ZPCPSCH ZPCPSCH ZC1WPSCH ZPCWPSCH ZPCWPSCH ZCLCPSCH ZCLCPLAL ZCLCPSCH ZCPSCH ZCPSCH ZCPSCH ZCRWPSCH ZCRWPSCH ZCRWPSCH ZCVPSOF ZCVPSOF ZCVPSOF ZGVPDIS ZGVLLN0 PH1PTRC ZGVPDIS ZGVPTUV PH1PTRC ZGVPDIS ZGVPTUV ZMCAPDIS ZMCAPDIS ZMCAPDIS ZMCPDIS ZMCPDIS ZMCPDIS ZMFCPDIS ZMFCLLN0 PSFPDIS ZMFPDIS ZMFPTRC ZMMMXU PSFPDIS ZMFPDIS ZMFPTRC ZMMMXU ZMFPDIS ZMFLLN0 PSFPDIS ZMFPDIS ZMFPTRC ZMMMXU PSFPDIS PSFPDIS ZMFPDIS ZMFPTRC ZMMMXU ZMHPDIS ZMHPDIS ZMHPDIS ZMMAPDIS ZMMAPDIS ZMMAPDIS ZMMPDIS ZMMPDIS ZMMPDIS ZMQAPDIS ZMQAPDIS ZMQAPDIS ZMQPDIS ZMQPDIS ZMQPDIS ZMRAPDIS ZMRAPDIS ZMRAPDIS Table continues on next page 1MRK 502 071-UEN - Section 1 Introduction Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 33 Application manual

Function block name

Edition 1 logical nodes Edition 2 logical nodes ZMRPDIS ZMRPDIS ZMRPDIS ZMRPSB ZMRPSB ZMRPSB ZSMGAPC ZSMGAPC ZSMGAPC Section 1 1MRK 502 071-UEN - Introduction 34 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

General IED application

The REG670 is used for protection, control and monitoring of generators and generator-transformer blocks from relatively small units up to the largest generating units. The IED has a comprehensive function library, covering the requirements for most generator applications. The large number of analog inputs available enables, together with the large functional library, integration of many functions in one IED. In typical applications two IED units can provide total functionality, also providing a high degree of redundancy. REG670 can as well be used for protection and control of shunt reactors. Stator earth fault protection, both traditional 95% as well as 100% injection and 3rd harmonic based are included. When the injection based protection is used, 100% of the machine stator winding, including the star point, is protected under all operating modes. The 3rd harmonic based 100% stator earth fault protection uses 3rd harmonic differential voltage principle. Injection based 100% stator earth fault protection can operate even when machine is at standstill. Well proven algorithms for pole slip, underexcitation, rotor earth fault, negative sequence current protections, and so on, are included in the IED. The generator differential protection in the REG670 adapted to operate correctly for generator applications where factors as long DC time constants and requirement on short trip time have been considered. As many of the protection functions can be used as multiple instances there are possibilities to protect more than one object in one IED. It is possible to have protection for an auxiliary power transformer integrated in the same IED having main protections for the generator. The concept thus enables very cost effective solutions. The REG670 also enables valuable monitoring possibilities as many of the process values can be transferred to an operator HMI. The wide application flexibility makes this product an excellent choice for both new installations and for refurbishment in existing power plants. Forcing of binary inputs and outputs is a convenient way to test wiring in substations as well as testing configuration logic in the IEDs. Basically it means that all binary inputs and outputs on the IED I/O modules (BOM, BIM, IOM & SOM) can be forced to arbitrary values. Central Account Management is an authentication infrastructure that offers a secure solution for enforcing access control to IEDs and other systems within a substation. 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 35 Application manual

This incorporates management of user accounts, roles and certificates and the

distribution of such, a procedure completely transparent to the user. The Flexible Product Naming allows the customer to use an IED-vendor independent IEC 61850 model of the IED. This customer model will be exposed in all IEC 61850 communication, but all other aspects of the IED will remain unchanged (e.g., names on the local HMI and names in the tools). This offers significant flexibility to adapt the IED to the customers' system and standard solution. Communication via optical connections ensures immunity against disturbances. By using patented algorithm REG670 (or any other product from 670 series) can track the power system frequency in quite wide range from 9Hz to 95Hz (for 50Hz power system). In order to do that preferably the three-phase voltage signal from the generator terminals shall be connected to the IED. Then IED can adopt its filtering algorithm in order to properly measure phasors of all current and voltage signals connected to the IED. This feature is essential for proper operation of the protection during generator start-up and shut-down procedure. REG670 can be used in applications with the IEC/UCA 61850-9-2LE process bus with up to eight merging units (MU) depending on the other functionality included in the IED. This adaptive filtering is ensured by proper configuration and settings of all relevant pre-processing blocks, see figure 344 and 345. Note that in all pre-configured REG670 IEDs such configuration and settings are already made and that three-phase voltage at the generator terminals are used for frequency tracking. With such settings REG670 will be able to properly estimate the magnitude and the phase angle of measured current and voltage phasors in this wide frequency range. Note that the following functions will then operate properly in the whole frequency interval: • Generator differential • Transformer differential • Four step overcurrent protection (DFT based measurement) • Four step residual overcurrent protection • Over/under voltage protection (DFT based measurement) • Residual overvoltage protection • Overexcitation protection • General current and voltage protection • Directional over/under power function • Measurement function (that is, MMXU) • and so on Note that during secondary injection testing of this feature, it is absolutely necessary to also inject the voltage signals used for frequency tracking even when a simple overcurrent protection is tested. Section 2 1MRK 502 071-UEN - Application 36 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

If protection for lower frequencies than 9Hz is required (for example, for pump-

storage schemes) four step overcurrent protection with RMS measurement shall be used. This function is able to operate for current signals within frequency range from 1Hz up to 100Hz and it is not at all dependent on any voltage signal. Its pickup for very low frequency is only determined by main CT capability to transfer low frequency current signal to the secondary side. However it shall be noted that during such low frequency conditions this function will react on the measured current peak values instead of usual RMS value and that its operation shall be instantaneous (that is, without any intentional time delay). Function can be used either as normal overcurrent function or even as generator differential function when currents from two generator sides are summed and connected to the four step overcurrent function. Typically for such installations dedicated overcurrent steps are used during such low frequency conditions while some other overcurrent steps with different setting for pickup value and time delay are used during normal machine operation. Such logic can be easily arranged in REG670 application configuration tool. Four step overcurrent protection with RMS measurement shall also be used as machine overcurrent and differential protection during electrical braking. During such operating condition intentional three-phase short-circuit is made at the machine terminal. This will effectively force voltages at the machine terminal to zero and effectively disabled voltage based frequency tracking in REG670. Similar logic as described for pump-storage scheme above can be used. 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 37 Application manual

REG 670 2.0

ZGV PDIS 21 Z< LEX PDIS 40 < GUP PDUP 37 P< GOP PDOP 32 P ROV2 PTOV 59N 3Uo> OC4 PTOC 51/67 3I-> CC RBRF 50BF 3I> BF NS2 PTOC 46 I2> TR PTTR 49 Ith PSP PPAM 78 Ucos + REX060, REX061 AEG PVOC 50AE U/I> CV MMXU Meter. ROV2 PTOV 59N UN> ROTI PHIZ 64R RRE< STTI PHIZ 64S RSE< + REX060 ROV2 PTOV 59N 3Uo> VT Y Y D IEC11000201 V2 EN Figure 2: Generator protection application with generator differential, 100% stator earth fault and back-up protection Section 2 1MRK 502 071-UEN - Application 38 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

REG 670 2.0

ZGV PDIS 21 Z< LEX PDIS 40 < GUP PDUP 37 P< GOP PDOP 32 P ROV2 PTOV 59N 3Uo> OC4 PTOC 51/67 3I-> CC RBRF 50BF 3I> BF NS2 PTOC 46 I2> PSP PPAM 78 Ucos + REX060, REX061 AEG PVOC 50AE U/I> CV MMXU Meter. ROTI PHIZ 64R RRE< STTI PHIZ 64S RSE< + REX060 ROV2 PTOV 59N 3Uo> VT EF4 PTOC 64W IN> Y Y S D IEC11000204 V2 EN Figure 3: Generator protection application for generator with split winding including generator phase differential, 100% stator earth fault and back-up protection 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 39 Application manual

REG 670 2.0

ZGV PDIS 21 Z< LEX PDIS 40 < GUP PDUP 37 P< GOP PDOP 32 P ROV2 PTOV 59N 3Uo> OC4 PTOC 51/67 3I-> CC RBRF 50BF 3I> BF NS2 PTOC 46 I2> PSP PPAM 78 Ucos + REX060, REX061 AEG PVOC 50AE U/I> CV MMXU Meter. ROV2 PTOV 59N UN> ROTI PHIZ 64R RRE< VT EF4 PTOC 64W IN> Y Y STTI PHIZ 64S RSE< + REX060 VT GEN PDIF 87W 3Id/I D S IEC11000206 V2 EN Figure 4: Generator protection application for generator with split winding including generator phase differential, generator split-phase differential, 100% stator earth fault and back-up protection Section 2 1MRK 502 071-UEN - Application 40 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

REG 670 2.0

ZGV PDIS 21 Z< LEX PDIS 40 < GUP PDUP 37 P< GOP PDOP 32 P OC4 PTOC 51/67 3I-> CC RBRF 50BF 3I> BF NS2 PTOC 46 I2> TR PTTR 49 Ith PSP PPAM 78 Ucos AEG PVOC 50AE U/I> STEF PHIZ 59THD U3d/N Auxiliary Bus OC4 PTOC 50/51 3I> OC4 PTOC 50/51 3I> CC RBRF 50BF 3I> BF OC4 PTOC 50/51 3I> ROV2 PTOV 59N 3Uo> T3W PDIF 87T 3Id/I CV MMXU Meter. OEX PVPH 24 U/f> UV2 PTUV 27 3U< OV2 PTOV 59 3U> ROV2 PTOV 59N 3Uo> + REX060, REX061 STTI PHIZ 64S RSE< ROTI PHIZ 64R RRE< + REX060, REX062 Y Y Y Unit Trafo Auxiliary Trafo Excitation Trafo Y Y Grounding Transformer D D D IEC11000202 V2 EN Figure 5: Unit protection application with overall differential, generator differential, 100% stator earth fault and back-up protection. Stator winding grounded via grounding transformer. 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 41 Application manual

REG 670 2.0

T2W PDIF 87T 3Id/I ROV2 PTOV 59N 3Uo> NS2 PTOC 46 I2> TR PTTR 49 Ith FUFSPVC 60FL ZGV PDIS 21 Z< LEX PDIS 40 < GUP PDUP 37 P< GOP PDOP 32 P PSP PPAM 78 Ucos SA PTOF 81 f> OEX PVPH 24 U/f> UV2 PTUV 27 3U< OV2 PTOV 59 3U> OC4 PTOC 50/51 3I> OC4 PTOC 50/51 3I> CC RBRF 50BF 3I> BF GEN PDIF 87G 3Id/I ROV2 PTOV 59N UN> CC RBRF 50BF 3I> BF OC4 PTOC 51/67 3I-> AEG PVOC 50AE U/I> CV MMXU Meter. + REX060, REX061 STTI PHIZ 64S RSE< ROTI PHIZ 64R RRE< + REX060 CV MMXU Meter. Y Y Y Y Y Unit Trafo VT D D D IEC11000203 V2 EN Figure 6: Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator earth fault and back- up protection. Ungrounded stator winding. Section 2 1MRK 502 071-UEN - Application 42 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

REG 670 2.0

T2W PDIF 87T 3Id/I ROV2 PTOV 59N 3Uo> NS2 PTOC 46 I2> TR PTTR 49 Ith FUFSPVC 60FL ZGV PDIS 21 Z< LEX PDIS 40 < GUP PDUP 37 P< GOP PDOP 32 P PSP PPAM 78 Ucos SA PTOF 81 f> OEX PVPH 24 U/f> UV2 PTUV 27 3U< OV2 PTOV 59 3U> OC4 PTOC 50/51 3I> OC4 PTOC 50/51 3I> CC RBRF 50BF 3I> BF GEN PDIF 87G 3Id/I CC RBRF 50BF 3I> BF OC4 PTOC 51/67 3I-> AEG PVOC 50AE U/I> CV MMXU Meter. + REX060, REX061 STTI PHIZ 64S RSE< ROTI PHIZ 64R RRE< + REX060 CV MMXU Meter. Y Y Y Y Y Unit Trafo ROV2 PTOV 59N 3Uo> VT IEC11000207-2-en.vsd D D D IEC11000207 V2 EN Figure 7: Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator earth fault and back- up protection. Stator winding grounded via primary resistor. The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual. 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 43 Application manual

Main protection functions

Table 2: Example of quantities 2 = number of basic instances 0-3 = option quantities 3-A03 = optional function included in packages A03 (refer to ordering details) IEC 61850 or function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) Differential protection T2WPDIF 87T Transformer differential protection, two winding 0-2 1-A31 1-A33 1 T3WPDIF 87T Transformer differential protection, three winding 0-2 1-A33 1 HZPDIF 87 High impedance differential protection, single phase 0-6 3-A02 3 6 GENPDIF 87G Generator differential protection 0-2 1 2 2 REFPDIF 87N Restricted earth fault protection, low impedance 0-3 1-A01 1 Impedance protection ZMHPDIS 21 Full-scheme distance protection, mho characteristic 0-4 3 3 3 ZDMRDIR 21D Directional impedance element for mho characteristic 0-2 1 1 1 ZMFPDIS 21 High speed distance protection, quad and mho characteristic 0-1 ZMFCPDIS 21 High speed distance protection for series comp. lines, quad and mho characteristic 0-1 PSPPPAM 78 Poleslip/out-of-step protection 0-1 1-B22 1-B22 1-B22 OOSPPAM 78 Out-of-step protection 0-1 1-B22 1-B22 1-B22 LEXPDIS 40 Loss of excitation 0-2 1 2 2 ROTIPHIZ 64R Sensitive rotor earth fault protection, injection based 0-1 1-B31 1-B31 1-B31 STTIPHIZ 64S 100% stator earth fault protection, injection based 0-1 1-B32 1-B32 1-B32 ZGVPDIS 21 Underimpedance protection for generators and transformers 0–2 1 1 1 Section 2 1MRK 502 071-UEN - Application 44 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Back-up protection functions

IEC 61850 or function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) Current protection PHPIOC 50 Instantaneous phase overcurrent protection 0-4 1 2 2 OC4PTOC 51_671) Directional phase overcurrent protection, four steps 0-6 4 4 4 EFPIOC 50N Instantaneous residual overcurrent protection 0-2 1 2 2 EF4PTOC 51N 67N2) Directional residual overcurrent protection, four steps 0-6 1 5 5 NS4PTOC 46I2 Four step directional negative phase sequence overcurrent protection 0-2 1-C41 2-C42 2-C42 SDEPSDE 67N Sensitive directional residual overcurrent and power protection 0-2 1-C16 1-C16 1-C16 TRPTTR 49 Thermal overload protection, two time constants 0-3 1 2 3 CCRBRF 50BF Breaker failure protection 0-4 2 4 4 CCPDSC 52PD Pole discordance protection 0-4 2 4 4 GUPPDUP 37 Directional underpower protection 0-4 2 4 4 GOPPDOP 32 Directional overpower protection 0-4 2 4 4 NS2PTOC 46I2 Negative sequence time overcurrent protection for machines 0-2 1 1 1 AEGPVOC 50AE Accidental energizing protection for synchronous generator 0-2 1 1 1 VRPVOC 51V Voltage restrained overcurrent protection 0-3 3-C36 3-C36 3-C36 GSPTTR 49S Stator overload protection 0-1 1 1 1 GRPTTR 49R Rotor overload protection 0-1 1-C38 1-C38 1-C38 Voltage protection UV2PTUV 27 Two step undervoltage protection 0-2 2 2 2 OV2PTOV 59 Two step overvoltage protection 0-2 2 2 2 ROV2PTOV 59N Two step residual overvoltage protection 0-3 3 3 3 OEXPVPH 24 Overexcitation protection 0-2 1 1 2 Table continues on next page 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 45 Application manual

IEC 61850 or

function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) VDCPTOV 60 Voltage differential protection 0-2 2 2 2 STEFPHIZ 59THD 100% stator earth fault protection, 3rd harmonic based 0-1 1-D21 1 1 Frequency protection SAPTUF 81 Underfrequency protection 0-6 3 6 6 SAPTOF 81 Overfrequency protection 0-6 3 6 6 SAPFRC 81 Rate-of-change of frequency protection 0-6 1 3 3 FTAQFVR 81A Frequency time accumulation protection 0-12 12-E03 12-E03 12-E03 Multipurpose protection CVGAPC General current and voltage protection 0-9 6 6 6 General calculation SMAIHPAC Multipurpose filter 0-6 1) 67 requires voltage 2) 67N requires voltage 2.4 Control and monitoring functions IEC 61850 or function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) Control SESRSYN 25 Synchrocheck, energizing check and synchronizing 0-2 1 2 2 APC30 3 Control functionality for up to 6 bays, max 30 objects (6CBs), including interlocking (see Table 4) 0-1 1-H39 1-H39 1-H39 QCBAY Bay control 1+5/APC30 1+5/ APC3 0 1+5/ APC3 0 1+5/ APC3 0 Table continues on next page Section 2 1MRK 502 071-UEN - Application 46 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC 61850 or

function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) LOCREM Handling of LR-switch positions 1+5/APC30 1+5/ APC3 0 1+5/ APC3 0 1+5/ APC3 0 LOCREMCTRL LHMI control of PSTO 1 1 1 1 SXCBR Circuit breaker 18 18 18 18 TCMYLTC 84 Tap changer control and supervision, 6 binary inputs 0-4 1-A31 2-A33 2 TCLYLTC 84 Tap changer control and supervision, 32 binary inputs 0-4 SLGAPC Logic rotating switch for function selection and LHMI presentation 15 15 15 15 VSGAPC Selector mini switch 30 30 30 30 DPGAPC Generic communication function for Double Point indication 16 16 16 16 SPC8GAPC Single point generic control function 8 signals 5 5 5 5 AUTOBITS Automation bits, command function for DNP3.0 3 3 3 3 SINGLECMD Single command, 16 signals 4 4 4 4 I103CMD Function commands for IEC 60870-5-103 1 1 1 1 I103GENCMD Function commands generic for IEC 60870-5-103 50 50 50 50 I103POSCMD IED commands with position and select for IEC 60870-5-103 50 50 50 50 I103POSCMDV IED direct commands with position for IEC 60870-5-103 50 50 50 50 I103IEDCMD IED commands for IEC 60870-5-103 1 1 1 1 I103USRCMD Function commands user defined for IEC 60870-5-103 4 4 4 4 Secondary system supervision CCSSPVC 87 Current circuit supervision 0-5 4 5 5 FUFSPVC Fuse failure supervision 0-3 2 3 3 VDSPVC 60 Fuse failure supervision based on voltage difference 0-2 1-G03 1-G03 1-G03 Logic SMPPTRC 94 Tripping logic 12 12 12 12 SMAGAPC General start matrix block 12 12 12 12 STARTCOMB Start combinator 32 32 32 32 TMAGAPC Trip matrix logic 12 12 12 12 Table continues on next page 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 47 Application manual

IEC 61850 or

function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) ALMCALH Logic for group alarm 5 5 5 5 WRNCALH Logic for group warning 5 5 5 5 INDCALH Logic for group indication 5 5 5 5 AND, GATE, INV, LLD, OR, PULSETIMER, RSMEMORY, SRMEMORY, TIMERSET, XOR Basic configurable logic blocks (see Table 3) 40-420 40-42 0 40-42 0 40-42 0 ANDQT, INDCOMBSPQT, INDEXTSPQT, INVALIDQT, INVERTERQT, ORQT, PULSETIMERQT, RSMEMORYQT, SRMEMORYQT, TIMERSETQT, XORQT Configurable logic blocks Q/T (see Table 5) 0-1 AND, GATE, INV, LLD, OR, PULSETIMER, RSMEMORY, SLGAPC, SRMEMORY, TIMERSET, VSGAPC, XOR Extension logic package (see Table 6) 0-1 FXDSIGN Fixed signal function block 1 1 1 1 B16I Boolean to integer conversion, 16 bit 18 18 18 18 BTIGAPC Boolean to integer conversion with logical node representation, 16 bit 16 16 16 16 IB16 Integer to Boolean 16 conversion 18 18 18 18 ITBGAPC Integer to Boolean 16 conversion with Logic Node representation 16 16 16 16 TIGAPC Delay on timer with input signal integration 30 30 30 30 TEIGAPC Elapsed time integrator with limit transgression and overflow supervision 12 12 12 12 INTCOMP Comparator for integer inputs 30 30 30 30 REALCOMP Comparator for real inputs 30 30 30 30 Section 2 1MRK 502 071-UEN - Application 48 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Total number of instances for basic configurable logic blocks

Basic configurable logic block Total number of instances AND 280 GATE 40 INV 420 LLD 40 OR 298 PULSETIMER 40 RSMEMORY 40 SRMEMORY 40 TIMERSET 60 XOR 40 Table 4: Number of function instances in APC30 Function name Function description Total number of instances SCILO Interlocking 30 BB_ES 6 A1A2_BS 4 A1A2_DC 6 ABC_BC 2 BH_CONN 2 BH_LINE_A 2 BH_LINE_B 2 DB_BUS_A 3 DB_BUS_B 3 DB_LINE 3 ABC_LINE 6 AB_TRAFO 4 SCSWI Switch controller 30 SXSWI Circuit switch 24 QCRSV Apparatus control 6 RESIN1 1 RESIN2 59 POS_EVAL Evaluation of position indication 30 QCBAY Bay control 5 LOCREM Handling of LR-switch positions 5 XLNPROXY Proxy for signals from switching device via GOOSE 42 GOOSEXLNRCV GOOSE function block to receive a switching device 42 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 49 Application manual

Total number of instances for configurable logic blocks Q/T

Configurable logic blocks Q/T Total number of instances ANDQT 120 INDCOMBSPQT 20 INDEXTSPQT 20 INVALIDQT 22 INVERTERQT 120 ORQT 120 PULSETIMERQT 40 RSMEMORYQT 40 SRMEMORYQT 40 TIMERSETQT 40 XORQT 40 Table 6: Total number of instances for extended logic package Extended configurable logic block Total number of instances AND 180 GATE 49 INV 180 LLD 49 OR 180 PULSETIMER 89 RSMEMORY 40 SLGAPC 74 SRMEMORY 130 TIMERSET 109 VSGAPC 120 XOR 89 IEC 61850 or function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) Monitoring CVMMXN Power system measurement 6 6 6 6 CMMXU Current measurement 10 10 10 10 VMMXU Voltage measurement phase-phase 6 6 6 6 CMSQI Current sequence measurement 6 6 6 6 Table continues on next page Section 2 1MRK 502 071-UEN - Application 50 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC 61850 or

function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) VMSQI Voltage sequence measurement 6 6 6 6 VNMMXU Voltage measurement phase-earth 6 6 6 6 AISVBAS General service value presentation of analog inputs 1 1 1 1 EVENT Event function 20 20 20 20 DRPRDRE, A1RADR- A4RADR, B1RBDR- B22RBDR Disturbance report 1 1 1 1 SPGAPC Generic communication function for Single Point indication 64 64 64 64 SP16GAPC Generic communication function for Single Point indication 16 inputs 16 16 16 16 MVGAPC Generic communication function for measured values 24 24 24 24 BINSTATREP Logical signal status report 3 3 3 3 RANGE_XP Measured value expander block 66 66 66 66 SSIMG 63 Insulation supervision for gas medium 21 21 21 21 SSIML 71 Insulation supervision for liquid medium 3 3 3 3 SSCBR Circuit breaker condition monitoring 0-12 6 12 12 LOLSPTR 26/49 HS Transformer insulation loss of life monitoring 0-4 4-M21 4-M21 I103MEAS Measurands for IEC 60870-5-103 1 1 1 1 I103MEASUSR Measurands user defined signals for IEC 60870-5-103 3 3 3 3 I103AR Function status auto-recloser for IEC 60870-5-103 1 1 1 1 I103EF Function status earth-fault for IEC 60870-5-103 1 1 1 1 I103FLTPROT Function status fault protection for IEC 60870-5-103 1 1 1 1 I103IED IED status for IEC 60870-5-103 1 1 1 1 I103SUPERV Supervison status for IEC 60870-5-103 1 1 1 1 I103USRDEF Status for user defined signals for IEC 60870-5-103 20 20 20 20 L4UFCNT Event counter with limit supervision 30 30 30 30 TEILGAPC Running hour meter 6 6 6 6 Table continues on next page 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 51 Application manual

IEC 61850 or

function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) Metering PCFCNT Pulse-counter logic 16 16 16 16 ETPMMTR Function for energy calculation and demand handling 6 6 6 6 2.5 Communication IEC 61850 or function name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) Station communication LONSPA, SPA SPA communication protocol 1 1 1 1 ADE LON communication protocol 1 1 1 1 HORZCOMM Network variables via LON 1 1 1 1 RS485GEN RS485 1 1 1 1 DNPGEN DNP3.0 communication general protocol 1 1 1 1 CHSERRS485 DNP3.0 for EIA-485 communication protocol 1 1 1 1 CH1TCP, CH2TCP, CH3TCP, CH4TCP DNP3.0 for TCP/IP communication protocol 1 1 1 1 CHSEROPT DNP3.0 for TCP/IP and EIA-485 communication protocol 1 1 1 1 MSTSER DNP3.0 serial master 1 1 1 1 MST1TCP, MST2TCP, MST3TCP, MST4TCP DNP3.0 for TCP/IP communication protocol 1 1 1 1 DNPFREC DNP3.0 fault records for TCP/IP and EIA-485 communication protocol 1 1 1 1 IEC 61850-8-1 IEC 61850 1 1 1 1 GOOSEINTLKRCV Horizontal communication via GOOSE for interlocking 59 59 59 59 GOOSEBINRCV GOOSE binary receive 16 16 16 16 GOOSEDPRCV GOOSE function block to receive a double point value 64 64 64 64 Table continues on next page Section 2 1MRK 502 071-UEN - Application 52 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC 61850 or function

name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) GOOSEINTRCV GOOSE function block to receive an integer value 32 32 32 32 GOOSEMVRCV GOOSE function block to receive a measurand value 60 60 60 60 GOOSESPRCV GOOSE function block to receive a single point value 64 64 64 64 MULTICMDRCV, MULTICMDSND Multiple command and transmit 60/10 60/10 60/10 60/10 OPTICAL103 IEC 60870-5-103 Optical serial communication 1 1 1 1 RS485103 IEC 60870-5-103 serial communication for RS485 1 1 1 1 AGSAL Generic security application component 1 1 1 1 LD0LLN0 IEC 61850 LD0 LLN0 1 1 1 1 SYSLLN0 IEC 61850 SYS LLN0 1 1 1 1 LPHD Physical device information 1 1 1 1 PCMACCS IED configuration protocol 1 1 1 1 SECALARM Component for mapping security events on protocols such as DNP3 and IEC103 1 1 1 1 FSTACCS Field service tool access 1 1 1 1 IEC 61850-9-2 Process bus communication, 8 merging units 0-1 1-P30 1-P30 1-P30 ACTIVLOG Activity logging 1 1 1 1 ALTRK Service tracking 1 1 1 1 PRP IEC 62439-3 Parallel redundancy protocol 0-1 1-P23 1-P23 1-P23 HSR IEC 62439-3 High-availability seamless redundancy 0-1 1-P24 1-P24 1-P24 PMUCONF, PMUREPORT, PHASORREPORT1, ANALOGREPORT1 BINARYREPORT1, SMAI1 - SMAI12 3PHSUM PMUSTATUS Synchrophasor report, 16 phasors (see Table 7) 0-1 1-P34 1-P34 1-P34 PTP Precision time protocol 1 1 1 1 FRONTSTATUS Access point diagnostic for front Ethernet port 1 1 1 1 SCHLCCH Access point diagnostic for non- redundant Ethernet port 6 6 6 6 Table continues on next page 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 53 Application manual

IEC 61850 or function

name ANSI Function description Generator REG670 (Customized) REG670 (A20) REG670 (B30) REG670 (C30) RCHLCCH Access point diagnostic for redundant Ethernet ports 3 3 3 3 DHCP DHCP configuration for front access point 1 1 1 1 QUALEXP IEC 61850 quality expander 96 96 96 96 Remote communication BinSignRec1_1 BinSignRec1_2 BinSignReceive2 Binary signal transfer receive 3/3/6 3/3/6 3/3/6 3/3/6 BinSignTrans1_1 BinSignTrans1_2 BinSignTransm2 Binary signal transfer transmit 3/3/6 3/3/6 3/3/6 3/3/6 BinSigRec1_12M BinSigRec1_22M BinSigTran1_12M BinSigTran1_22M Binary signal transfer, 2Mbit receive/ transmit 3 3 3 3 LDCMTRN Transmission of analog data from LDCM 1 1 1 1 LDCMTRN_2M Transmission of analog data from LDCM, 2Mbit 6 6 6 6 LDCMRecBinStat1 LDCMRecBinStat2 LDCMRecBinStat3 Receive binary status from remote LDCM 6/3/3 6/3/3 6/3/3 6/3/3 LDCMRecBinS2_2M Receive binary status from LDCM, 2Mbit 3 3 3 3 LDCMRecBinS3_2M Receive binary status from remote LDCM, 2Mbit 3 3 3 3 Table 7: Number of function instances in Synchrophasor report, 16 phasors Function name Function description Number of instances PMUCONF Configuration parameters for C37.118 2011 and IEEE1344 protocol 1 PMUREPORT Protocol reporting via IEEE 1344 and C37.118 2 PHASORREPORT1 Protocol reporting of phasor data via IEEE 1344 and C37.118, phasors 1-8 2 ANALOGREPORT1 Protocol reporting of analog data via IEEE 1344 and C37.118, analogs 1-8 2 BINARYREPORT1 Protocol reporting of binary data via IEEE 1344 and C37.118, binary 1-8 2 SMAI1–SMAI12 Signal matrix for analog inputs 1 3PHSUM Summation block 3 phase 6 PMUSTATUS Diagnostics for C37.118 2011 and IEEE1344 protocol 1 Section 2 1MRK 502 071-UEN - Application 54 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Basic IED functions

Table 8: Basic IED functions IEC 61850 or function name Description INTERRSIG Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, SYNCHGPS, SYNCHCMPPS, SYNCHLON, SYNCHPPH, SYNCHPPS, SNTP, SYNCHSPA Time synchronization PTP Precision time protocol TIMEZONE Time synchronization IRIG-B Time synchronization SETGRPS Number of setting groups ACTVGRP Parameter setting groups TESTMODE Test mode functionality CHNGLCK Change lock function SMBI Signal matrix for binary inputs SMBO Signal matrix for binary outputs SMMI Signal matrix for mA inputs SMAI1 - SMAI12 Signal matrix for analog inputs 3PHSUM Summation block 3 phase ATHSTAT Authority status ATHCHCK Authority check AUTHMAN Authority management FTPACCS FTP access with password GBASVAL Global base values for settings ALTMS Time master supervision ALTIM Time management COMSTATUS Protocol diagnostic 1MRK 502 071-UEN - Section 2 Application Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 55 Application manual

Local HMI functions

IEC 61850 or function name ANSI Description LHMICTRL Local HMI signals LANGUAGE Local human machine language SCREEN Local HMI Local human machine screen behavior FNKEYTY1–FNKEYTY5 FNKEYMD1– FNKEYMD5 Parameter setting function for HMI in PCM600 LEDGEN General LED indication part for LHMI OPENCLOSE_LED LHMI LEDs for open and close keys GRP1_LED1– GRP1_LED15 GRP2_LED1– GRP2_LED15 GRP3_LED1– GRP3_LED15 Basic part for CP HW LED indication module Section 2 1MRK 502 071-UEN - Application 56 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Description of REG670

3.1.1 Introduction 3.1.1.1 Description of configuration A20 REG670 A20 configuration is used in applications where only generator protection within one IED is required. REG670 A20 is always delivered in 1/2 of 19" case size. Thus only 12 analogue inputs are available. This configuration includes generator low impedance, differential protection and all other typically required generator protection functions. Note that 100% stator earth fault function and Pole Slip protection function are optional. REG670 A20 functional library includes additional functions, which are not configured, such as additional Overcurrent protection, additional Multipurpose protection functions, Synchronizing function, and so on. It is as well possible to order optional two-winding transformer differential or high impedance differential protection functions which than can be used instead of basic low-impedance generator differential protection. Note that REG670 A20 must be re-configured if any additional or optional functions are used. 1MRK 502 071-UEN - Section 3 Configuration Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 57 Application manual

REG670 A20 – Generator differential + backup protection 12AI (7I + 5U)

Y Y ROV2 PTOV 59N 2(U0>) AEG PVOC 50AE U/I> SMP PTRC 94 1→0 ROV2 PTOV 59N 2(U0>) V MMXU MET U GEN_QA1 GEN_TRM_VT GEN_TRM_CT ROT_INJ_VT ROT_INJ_CT GEN_SP_CT GEN_SP_VT OC4 PTOC 51_67 4(3I>) C MSQI MET Isqi C MMXU MET I SES RSYN 25 SC/VC CCS SPVC 87 INd/I ROTI PHIZ 64R R< OOS PPAM 78 Ucos HZ PDIF 87 Id> SDE PSDE 67N IN> T2W PDIF 87T 3Id/I> STEF PHIZ 59THD U3d/N EF4 PTOC 51N_67N 4(IN>) SA PFRC 81 df/dt<> Other Functions available from the function library Optional Functions NS4 PTOC 46I2 4(I2>) PSP PPAM 78 Ucos CC PDSC 52PD PD PH PIOC 50 3I>> EF PIOC 50N IN>> VDC PTOV 60 Ud> Q CBAY 3 Control GR PTTR 49R θ> TCM YLTC 84 ↑↓ VD SPVC 60 Ud> FTA QFVR 81A f<> VR PVOC 51V 2(I>/U<) Q CRSV 3 Control S CILO 3 Control S CSWI 3 Control S SCBR Control ZMH PDIS 21 Z< TR PTTR 49 θ> ZDM RDIR 21D Z<_> IEC11000068-6-en.vsdx S SIML 71 S SIMG 63 S SCBR Control S SCBR Control S XCBR 3 Control PMU REP STTI PHIZ 64S R< S XSWI 3 Control FUF SPVC U>/I< NS2 PTOC 46 I2> IEC11000068 V6 EN Figure 8: Typical generator protection application with generator differential and back-up protection, including 12 analog inputs transformers in half 19" case size. 3.1.1.2 Description of configuration B30 REG670 B30 configuration is used in applications where generator protection and backup protection for surrounding primary equipment within one IED is required. REG670 B30 is always delivered in 1/1 of 19" case size. Thus 24 analogue inputs are available. This configuration includes generator low impedance, differential protection and all other typically required generator protection functions. In figure 9, this configuration is shown. Section 3 1MRK 502 071-UEN - Configuration 58 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

REG670 B30 functional library includes additional functions, which are not

configured, such as additional Multipurpose protection functions, Synchrocheck function, second generator differential protection function, and so on. It is as well possible to order optional two- or three-winding transformer differential protection function, which than can be used as transformer or block (that is overall) differential protection. Note that REG670 B30 must be re-configured if any additional or optional functions are used. 1MRK 502 071-UEN - Section 3 Configuration Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 59 Application manual

Unit Step-up Trafo

Auxiliary Trafo Excitation Trafo CC RBRF 50BF 3I>BF EF4 PTOC 51N_67N 4(IN>) ROV2 PTOV 59N 2(U0>) SA PTUF 81U f< SA PTUF 81 f< SA PTOF 81O f> SA PTOF 81 f> UV2 PTUV 27 2(3U<) OV2 PTOV 59 2(3U>) V MSQI MET Usqi V MMXU MET U CC RBRF 50BF 3I>BF FUF SPVC U>/I< ROV2 PTOV 59N 2(U0>) GOP PDOP 32 P> GUP PDUP 37 P< GS PTTR 49S θ> C MMXU MET I GEN PDIF 87G 3Id/I> ZGV PDIS 21 Z< CV GAPC 64R Re< CV GAPC 2(I>/U<) REG670 B30 – Generator differential + backup protection 24AI (9I+3U, 9I+3U) LEX PDIS 40 Φ < DRP RDRE DFR/SER DR OEX PVPH 24 U/f> ETP MMTR MET W/Varh CV MMXN MET P/Q + RXTTE4 AEG PVOC 50AE U/I> ROV2 PTOV 59N 2(U0>) VN MMXU MET UN STEF PHIZ 59THD U3d/N SMP PTRC 94 1→0 OC4 PTOC 51_67 4(3I>) GEN_QA1 AUX_QA1 HV_QA1 HV_CT LV_VT_3U0 GEN_TRM_VT GEN_TRM_CT GEN_SP_CT GEN_SP_VT OC4 PTOC 51_67 4(3I>) ROT_INJ_VT ROT_INJ_CT AUX_CT EXC_CT HV_NCT Y Y Y G OC4 PTOC 51_67 4(3I>) C MSQI MET Isqi C MMXU MET I C MSQI MET Isqi C MMXU MET I C MSQI MET Isqi C MMXU MET I C MMXU MET I OC4 PTOC 51_67 4(3I>) NS2 PTOC 46 I2> C MSQI MET Isqi =IEC11000071=6=en=Original.vsd SES RSYN 25 SC/VC CCS SPVC 87 INd/I STTI PHIZ 64S R< OOS PPAM 78 Ucos T3W PDIF 87T 3Id/I> REF PDIF 87N IdN/I T2W PDIF 87T 3Id/I> ROTI PHIZ 64R R< HZ PDIF 87 Id> SA PFRC 81 df/dt<> Optional Functions SDE PSDE 67N IN> NS4 PTOC 46I2 4(I2>) PSP PPAM 78 Ucos CC PDSC 52PD PD PH PIOC 50 3I>> EF PIOC 50N IN>> VDC PTOV 60 Ud> Q CBAY 3 Control GR PTTR 49R θ> TCM YLTC 84 ↑↓ VD SPVC 60 Ud> FTA QFVR 81A f<> VR PVOC 51V 2(I>/U<) Q CRSV 3 Control S CILO 3 Control S CSWI 3 Control S XSWI 3 Control ZMH PDIS 21 Z< TR PTTR 49 θ> ZDM RDIR 21D Z<_> Other Functions available from the function library S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SIMG 63 S SIML 71 S XCBR 3 Control PMU REP IEC11000071 V6 EN Figure 9: Enhanced generator protection application with generator differential and back-up protection, including 24 analog inputs in full 19" case size. Optional pole slip protection, 100% stator earth fault protection and overall differential protection can be added. 3.1.1.3 Description of configuration C30 REG670 C30 configuration is used in applications where generator-transformer block protection within one IED is required. REG670 C30 is always delivered in 1/1 of 19" case size. Thus 24 analog inputs are available. This configuration includes generator Section 3 1MRK 502 071-UEN - Configuration 60 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

low impedance, differential protection, transformer differential protection and overall

differential protection functions. Note that Pole Slip protection function is optional. See figure 10, example of one possible application. REG670 C30 functional library includes additional functions, which are not configured, such as additional Multipurpose protection functions, Synchrocheck function, second generator differential protection function, and so on. Note that REG670 C30 must be re-configured if any additional or optional functions are used. 1MRK 502 071-UEN - Section 3 Configuration Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 61 Application manual

Unit Step-up Trafo

Auxiliary Trafo CC RBRF 50BF 3I>BF ROV2 PTOV 59N 2(U0>) SA PTUF 81U f< SA PTUF 81 f< SA PTOF 81O f> SA PTOF 81 f> UV2 PTUV 27 2(3U<) OV2 PTOV 59 2(3U>) V MMXU MET U VN MMXU MET UN V MSQI MET Usqi CC RBRF 50BF I>BF ROV2 PTOV 59G UN> GOP PDOP 32 P> GUP PDUP 37 P< NS2 PTOC 46 I2> C MMXU MET I ZGV PDIS 21 Z< CV GAPC 64R Re< CV GAPC 2(I>/U<) Y Y TR PTTR 49 θ> OV2 PTOV 59 2(3U>) CV MMXN MET P/Q LEX PDIS 40 Φ < ETP MMTR MET W/Varh CV MMXN MET P/Q Grounding Trafo OEX PVPH 24 U/f> DRP RDRE DFR/SER DR + RXTTE4 AEG PVOC 50AE U/I> T2W PDIF 87T 3Id/I> REG670 C30 – Generator and block transformer protection 24AI (9I+3U, 6I+6U) 51N_67N EF4 PTOC 4(IN>) STEF PHIZ 59THD U3d/N OC4 PTOC 51_67 4(3I>) SMP PTRC 94 1→0 HV_QA1 AUX_QA1 GEN_QA1 HV_VT HV_CT LV_VT_3U0 AUX_CT GEN_TRM_VT GEN_TRM_CT ROT_INJ_CT ROT_INJ_VT GEN_SP_CT GEN_SP_VT OC4 PTOC 51_67 4(3I>) OC4 PTOC 51_67 4(3I>) Y Y Y ROV2 PTOV 59N 2(U0>) HV_NCT G C MSQI MET Isqi C MMXU MET I V MMXU MET U V MSQI MET Usqi C MSQI MET Isqi C MMXU MET I T3W PDIF 87T 3Id/I> FUF SPVC U>/I< C MSQI MET Isqi C MMXU MET I GS PTTR 49S θ> SES RSYN 25 SC/VC CCS SPVC 87 INd/I STTI PHIZ 64S R< OOS PPAM 78 Ucos ROTI PHIZ 64R R< HZ PDIF 87 Id> SA PFRC 81 df/dt<> Other Functions available from the function library SDE PSDE 67N IN> NS4 PTOC 46I2 4(I2>) PSP PPAM 78 Ucos CC PDSC 52PD PD PH PIOC 50 3I>> EF PIOC 50N IN>> VDC PTOV 60 Ud> TCM YLTC 84 ↑↓ S SIMG 63 S SIML 71 GR PTTR 49R θ> Q CBAY 3 Control Q CRSV 3 Control S CILO 3 Control S CSWI 3 Control S XSWI 3 Control S XCBR 3 Control VD SPVC 60 Ud> FTA QFVR 81A f<> VR PVOC 51V 2(I>/U<) ZMH PDIS 21 Z< ZDM RDIR 21D Z<_> =IEC11000072=6=en=Original.vsd PMU REP GEN PDIF 87G 3Id/I> S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SCBR Control S SCBR Control REF PDIF 87N IdN/I S SCBR Control S SCBR Control S SCBR Control Optional functions FUF SPVC U>/I< IEC11000072 V6 EN Figure 10: Unit protection including generator and generator transformer protection with 24 analog inputs in full 19" case size. Optional pole slip protection and 100% stator earthfault protection can be added. Section 3 1MRK 502 071-UEN - Configuration 62 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Analog input channels must be configured and set properly in order to get correct

measurement results and correct protection operations. For power measuring, all directional and differential functions, the directions of the input currents must be defined in order to reflect the way the current transformers are installed/connected in the field ( primary and secondary connections ). Measuring and protection algorithms in the IED use primary system quantities. Setting values are in primary quantities as well and it is important to set the data about the connected current and voltage transformers properly. An AISVBAS reference PhaseAngleRef can be defined to facilitate service values reading. This analog channel's phase angle will always be fixed to zero degrees and remaining analog channel's phase angle information will be shown in relation to this analog input. During testing and commissioning of the IED, the reference channel can be changed to facilitate testing and service values reading. The IED has the ability to receive analog values from primary equipment, that are sampled by Merging units (MU) connected to a process bus, via the IEC 61850-9-2 LE protocol. The availability of VT inputs depends on the ordered transformer input module (TRM) type. 4.2 Setting guidelines The available setting parameters related to analog inputs are depending on the actual hardware (TRM) and the logic configuration made in PCM600. 4.2.1 Setting of the phase reference channel All phase angles are calculated in relation to a defined reference. An appropriate analog input channel is selected and used as phase reference. The parameter PhaseAngleRef defines the analog channel that is used as phase angle reference. 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 63 Application manual

Usually the L1 phase-to-earth voltage connected to the first VT channel number of the

transformer input module (TRM) is selected as the phase reference. The first VT channel number depends on the type of transformer input module. For a TRM with 6 current and 6 voltage inputs the first VT channel is 7. The setting PhaseAngleRef=7 shall be used if the phase reference voltage is connected to that channel. 4.2.2 Setting of current channels The direction of a current to the IED is depending on the connection of the CT. Unless indicated otherwise, the main CTs are supposed to be star connected and can be connected with the earthing point to the object or from the object. This information must be set in the IED. The convention of the directionality is defined as follows: A positive value of current, power, and so on means that the quantity has the direction into the object and a negative value means direction out from the object. For directional functions the direction into the object is defined as Forward and the direction out from the object is defined as Reverse. See Figure 11 A positive value of current, power, and so on (forward) means that the quantity flows towards the object. A negative value of current, power, and so on (reverse) means that the quantity flows away from the object. See Figure 11. Protected Object Line, transformer, etc Forward Reverse Definition of direction for directional functions Measured quantity is positive when flowing towards the object e.g. P, Q, I Reverse Forward Definition of direction for directional functions e.g. P, Q, I Measured quantity is positive when flowing towards the object Set parameter CTStarPoint Correct Setting is "ToObject" Set parameter CTStarPoint Correct Setting is "FromObject" en05000456.vsd IEC05000456 V1 EN Figure 11: Internal convention of the directionality in the IED With correct setting of the primary CT direction, CTStarPoint set to FromObject or ToObject, a positive quantities always flowing towards the protected object and a direction defined as Forward always is looking towards the protected object. The following examples show the principle. Section 4 1MRK 502 071-UEN - Analog inputs 64 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Two IEDs used for protection of two objects.

Transformer protection Transformer Line Line Setting of current input: Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" Forward Reverse Definition of direction for directional functions Line protection Setting of current input: Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" Setting of current input: Set parameter CTStarPoint with Line as reference object. Correct setting is "FromObject" IEC05000753=IEC05 000753=1=en=Origin al[1].vsd Is Is Ip Ip Ip IED IED IEC05000753 V2 EN Figure 12: Example how to set CTStarPoint parameters in the IED Figure 12 shows the normal case where the objects have their own CTs. The settings for CT direction shall be done according to the figure. To protect the line, direction of the directional functions of the line protection shall be set to Forward. This means that the protection is looking towards the line. 4.2.2.2 Example 2 Two IEDs used for protection of two objects and sharing a CT. 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 65 Application manual

Setting of current input:

Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" Forward Reverse Definition of direction for directional functions Line protection Setting of current input: Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" Setting of current input: Set parameter CTStarPoint with Line as reference object. Correct setting is "FromObject" IED IED IEC05000460 V2 EN Figure 13: Example how to set CTStarPoint parameters in the IED This example is similar to example 1, but here the transformer is feeding just one line and the line protection uses the same CT as the transformer protection does. The CT direction is set with different reference objects for the two IEDs though it is the same current from the same CT that is feeding the two IEDs. With these settings, the directional functions of the line protection shall be set to Forward to look towards the line. 4.2.2.3 Example 3 One IED used to protect two objects. Section 4 1MRK 502 071-UEN - Analog inputs 66 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Setting of current input:

Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" Reverse Forward Definition of direction for directional line functions Setting of current input: Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" IED IEC05000461 V2 EN Figure 14: Example how to set CTStarPoint parameters in the IED In this example, one IED includes both transformer and line protections and the line protection uses the same CT as the transformer protection does. For both current input channels, the CT direction is set with the transformer as reference object. This means that the direction Forward for the line protection is towards the transformer. To look towards the line, the direction of the directional functions of the line protection must be set to Reverse. The direction Forward/Reverse is related to the reference object that is the transformer in this case. When a function is set to Reverse and shall protect an object in reverse direction, it shall be noted that some directional functions are not symmetrical regarding the reach in forward and reverse direction. It is in first hand the reach of the directional criteria that can differ. Normally it is not any limitation but it is advisable to have it in mind and check if it is acceptable for the application in question. If the IED has sufficient number of analog current inputs, an alternative solution is shown in Figure 15. The same currents are fed to two separate groups of inputs and the line and transformer protection functions are configured to the different inputs. The CT direction for the current channels to the line protection is set with the line as reference object and the directional functions of the line protection shall be set to Forward to protect the line. 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 67 Application manual

Setting of current input

for transformer functions: Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" Forward Reverse Definition of direction for directional line functions Setting of current input for transformer functions: Set parameter CTStarPoint with Transformer as reference object. Correct setting is "ToObject" Setting of current input for line functions: Set parameter CTStarPoint with Line as reference object. Correct setting is "FromObject" IED IEC05000462 V2 EN Figure 15: Example how to set CTStarPoint parameters in the IED Section 4 1MRK 502 071-UEN - Analog inputs 68 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC06000196 V2 EN

Figure 16: Example how to set CTStarPoint parameters in the IED For busbar protection, it is possible to set the CTStarPoint parameters in two ways. The first solution will be to use busbar as a reference object. In that case for all CT inputs marked with 1 in Figure 16, set CTStarPoint = ToObject, and for all CT inputs marked with 2 in Figure 16, set CTStarPoint = FromObject. The second solution will be to use all connected bays as reference objects. In that case for all CT inputs marked with 1 in Figure 16, set CTStarPoint = FromObject, and for all CT inputs marked with 2 in Figure 16, set CTStarPoint = ToObject. Regardless which one of the above two options is selected, busbar differential protection will behave correctly. 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 69 Application manual

The main CT ratios must also be set. This is done by setting the two parameters CTsec

and CTprim for each current channel. For a 1000/1 A CT, the following settings shall be used: • CTprim = 1000 (value in A) • CTsec =1 (value in A). 4.2.2.4 Examples on how to connect, configure and set CT inputs for most commonly used CT connections Figure 17 defines the marking of current transformer terminals commonly used around the world: In the SMAI function block, you have to set if the SMAI block is measuring current or voltage. This is done with the parameter: AnalogInputType: Current/Voltage. The ConnectionType: phase - phase/phase-earth and GlobalBaseSel. ISec IPri S1 (X1) P1 (H1) P2 (H2) S2 (X2) P2 (H2) P1 (H1) x x a) b) c) en06000641.vsd S2 (X2) S1 (X1) IEC06000641 V1 EN Figure 17: Commonly used markings of CT terminals Where: a) is symbol and terminal marking used in this document. Terminals marked with a square indicates the primary and secondary winding terminals with the same (that is, positive) polarity b) and c) are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that for these two cases the CT polarity marking is correct! It shall be noted that depending on national standard and utility practices, the rated secondary current of a CT has typically one of the following values: • 1A • 5A Section 4 1MRK 502 071-UEN - Analog inputs 70 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

However, in some cases, the following rated secondary currents are used as well:

• 2A • 10A The IED fully supports all of these rated secondary values. It is recommended to: • use 1A rated CT input into the IED in order to connect CTs with 1A and 2A secondary rating • use 5A rated CT input into the IED in order to connect CTs with 5A and 10A secondary rating 4.2.2.5 Example on how to connect a star connected three-phase CT set to the IED Figure 18 gives an example about the wiring of a star connected two-phase CT set to the IED. It gives an overview of the actions which are needed to make this measurement available to the built-in protection and control functions within the IED as well. For correct terminal designations, see the connection diagrams valid for the delivered IED. 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 71 Application manual

IEC13000002 V4 EN

Figure 18: Star connected three-phase CT set with star point towards the protected object Where: 1) The drawing shows how to connect three individual phase currents from a star connected three-phase CT set to the three CT inputs of the IED. 2) The current inputs are located in the TRM. It shall be noted that for all these current inputs the following setting values shall be entered for the example shown in Figure 18. • CTprim=600A • CTsec=5A • CTStarPoint=ToObject Ratio of the first two parameters is only used inside the IED. The third parameter (CTStarPoint=ToObject) as set in this example causes no change on the measured currents. In other words, currents are already measured towards the protected object. Table continues on next page Section 4 1MRK 502 071-UEN - Analog inputs 72 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

These three connections are the links between the three current inputs and the three input

channels of the preprocessing function block 4). Depending on the type of functions, which need this current information, more than one preprocessing block might be connected in parallel to the same three physical CT inputs. 4) The preprocessing block that has the task to digitally filter the connected analog inputs and calculate: • fundamental frequency phasors for all three input channels • harmonic content for all three input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors for the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block. For this application most of the preprocessing settings can be left to the default values. If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in power plants), then the setting parameters DFTReference shall be set accordingly. Section SMAI in this manual provides information on adaptive frequency tracking for the signal matrix for analogue inputs (SMAI). 5) AI3P in the SMAI function block is a grouped signal which contains all the data about the phases L1, L2, L3 and neutral quantity; in particular the data about fundamental frequency phasors, harmonic content and positive sequence, negative and zero sequence quantities are available. AI1, AI2, AI3, AI4 are the output signals from the SMAI function block which contain the fundamental frequency phasors and the harmonic content of the corresponding input channels of the preprocessing function block. AIN is the signal which contains the fundamental frequency phasors and the harmonic content of the neutral quantity. In this example, GRP2N is not connected so this data is calculated by the preprocessing function block on the basis of the inputs GRPL1, GRPL2 and GRPL3. If GRP2N is connected, the data reflects the measured value of GRP2N. Another alternative is to have the star point of the three-phase CT set as shown in Figure 19: 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 73 Application manual

IEC11000026 V4 EN

Figure 19: Star connected three-phase CT set with its star point away from the protected object In the example, everything is done in a similar way as in the above described example (Figure 18). The only difference is the setting of the parameter CTStarPoint of the used current inputs on the TRM (item 2 in Figure 19 and 18): • CTprim=600A • CTsec=5A • CTStarPoint=FromObject The ratio of the first two parameters is only used inside the IED. The third parameter as set in this example will negate the measured currents in order to ensure that the currents are measured towards the protected object within the IED. A third alternative is to have the residual/neutral current from the three-phase CT set connected to the IED as shown in Figure 19. Section 4 1MRK 502 071-UEN - Analog inputs 74 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC06000644 V4 EN

Figure 20: Star connected three-phase CT set with its star point away from the protected object and the residual/neutral current connected to the IED Where: 1) Shows how to connect three individual phase currents from a star connected three-phase CT set to the three CT inputs of the IED. 2) Shows how to connect residual/neutral current from the three-phase CT set to the fourth input in the IED. It shall be noted that if this connection is not made, the IED will still calculate this current internally by vectorial summation of the three individual phase currents. 3) Is the TRM where these current inputs are located. It shall be noted that for all these current inputs the following setting values shall be entered. • CTprim=800A • CTsec=1A • CTStarPoint=FromObject • ConnectionType=Ph-N The ratio of the first two parameters is only used inside the IED. The third parameter as set in this example will have no influence on measured currents (that is, currents are already measured towards the protected object). 4) Are three connections made in the Signal Matrix tool (SMT) and Application configuration tool (ACT), which connects these three current inputs to the first three input channels on the preprocessing function block 6). Depending on the type of functions, which need this current information, more than one preprocessing block might be connected in parallel to these three CT inputs. Table continues on next page 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 75 Application manual

Is a connection made in the Signal Matrix tool (SMT) and Application configuration tool

(ACT), which connects the residual/neutral current input to the fourth input channel of the preprocessing function block 6). Note that this connection in SMT shall not be done if the residual/neutral current is not connected to the IED. 6) Is a Preprocessing block that has the task to digitally filter the connected analog inputs and calculate: • fundamental frequency phasors for all input channels • harmonic content for all input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors of the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block in the configuration tool. For this application, most of the preprocessing settings can be left to the default values. If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations), then the setting parameters DFTReference shall be set accordingly. 4.2.2.6 Example how to connect delta connected three-phase CT set to the IED Figure 21 gives an example how to connect a delta connected three-phase CT set to the IED. It gives an overview of the required actions by the user in order to make this measurement available to the built-in protection and control functions in the IED as well. For correct terminal designations, see the connection diagrams valid for the delivered IED. Section 4 1MRK 502 071-UEN - Analog inputs 76 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC11000027 V3 EN

Figure 21: Delta DAB connected three-phase CT set 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 77 Application manual

shows how to connect three individual phase currents from a delta connected three-phase

CT set to three CT inputs of the IED. 2) is the TRM where these current inputs are located. It shall be noted that for all these current inputs the following setting values shall be entered. CTprim=600A CTsec=5A • CTStarPoint=ToObject • ConnectionType=Ph-Ph 3) are three connections made in Signal Matrix Tool (SMT), Application configuration tool (ACT), which connect these three current inputs to first three input channels of the preprocessing function block 4). Depending on the type of functions which need this current information, more then one preprocessing block might be connected in parallel to these three CT inputs. 4) is a Preprocessing block that has the task to digitally filter the connected analog inputs and calculate: • fundamental frequency phasors for all three input channels • harmonic content for all three input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors for the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block. For this application most of the preprocessing settings can be left to the default values. If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations) then the setting parameters DFTReference shall be set accordingly. Another alternative is to have the delta connected CT set as shown in figure 22: Section 4 1MRK 502 071-UEN - Analog inputs 78 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC11000028 V3 EN

Figure 22: Delta DAC connected three-phase CT set In this case, everything is done in a similar way as in the above described example, except that for all used current inputs on the TRM the following setting parameters shall be entered: CTprim=800A CTsec=1A • CTStarPoint=ToObject • ConnectionType=Ph-Ph It is important to notice the references in SMAI. As inputs at Ph-Ph are expected to be L1L2, L2L3 respectively L3L1 we need to tilt 180º by setting ToObject. 4.2.2.7 Example how to connect single-phase CT to the IED Figure 23 gives an example how to connect the single-phase CT to the IED. It gives an overview of the required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED as well. For correct terminal designations, see the connection diagrams valid for the delivered IED. 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 79 Application manual

IEC11000029 V4 EN

Figure 23: Connections for single-phase CT input Where: 1) shows how to connect single-phase CT input in the IED. 2) is TRM where these current inputs are located. It shall be noted that for all these current inputs the following setting values shall be entered. For connection (a) shown in Fgure 23: CTprim= 1000 A CTsec= 1A CTStarPoint=ToObject For connection (b) shown in Figure 23: CTprim= 1000 A CTsec= 1A CTStarPoint=FromObject 3) shows the connection made in SMT tool, which connect this CT input to the fourth input channel of the preprocessing function block 4). 4) is a Preprocessing block that has the task to digitally filter the connected analog inputs and calculate values. The calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block. If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the power plants) then the setting parameters DFTReference shall be set accordingly. 4.2.3 Relationships between setting parameter Base Current, CT rated primary current and minimum pickup of a protection IED Note that for all line protection applications (e.g. distance protection or line differential protection) the parameter Base Current (i.e. IBase setting in the IED) used by the relevant protection function, shall always be set equal to the largest rated CT Section 4 1MRK 502 071-UEN - Analog inputs 80 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

primary current among all CTs involved in the protection scheme. The rated CT

primary current value is set as parameter CTPrim under the IED TRM settings. For all other protection applications (e.g. generator, shunt reactor, shunt capacitor and transformer protection) it is typically desirable to set IBase parameter equal to the rated current of the protected object. However this is only recommended to do if the rated current of the protected object is within the range of 40% to 120% of the selected CT rated primary current. If for any reason (e.g. high maximum short circuit current) the rated current of the protected object is less than 40% of the rated CT primary current, it is strongly recommended to set the parameter IBase in the IED to be equal to the largest rated CT primary current among all CTs involved in the protection scheme and installed on the same voltage level. This will effectively make the protection scheme less sensitive; however, such measures are necessary in order to avoid possible problems with loss of the measurement accuracy in the IED. Regardless of the applied relationship between the IBase parameter and the rated CT primary current, the corresponding minimum pickup of the function on the CT secondary side must always be verified. It is strongly recommended that the minimum pickup of any instantaneous protection function (e.g. differential, restricted earth fault, distance, instantaneous overcurrent, etc.) shall under no circumstances be less than 4% of the used IED CT input rating (i.e. 1A or 5A). This corresponds to 40mA secondary for IED 1A rated inputs and to 200mA secondary for IED 5A rated inputs used by the function. This shall be individually verified for all current inputs involved in the protection scheme. Note that exceptions from the above 4% rule may be acceptable for very special applications (e.g. when Multipurpose filter SMAIHPAC is involved in the protection scheme). 4.2.4 Setting of voltage channels As the IED uses primary system quantities, the main VT ratios must be known to the IED. This is done by setting the two parameters VTsec and VTprim for each voltage channel. The phase-to-phase value can be used even if each channel is connected to a phase-to-earth voltage from the VT. 4.2.4.1 Example Consider a VT with the following data: 132 110 3 3 kV V EQUATION2016 V1 EN (Equation 1) The following setting should be used: VTprim=132 (value in kV) VTsec=110 (value in V) 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 81 Application manual

Examples how to connect, configure and set VT inputs for most

commonly used VT connections Figure 24 defines the marking of voltage transformer terminals commonly used around the world. A (H1) B (H2) b (X2) a (X1) A (H1) N (H2) n (X2) a (X1) b) c) A (H1) N (H2) dn (X2) da (X1) d) UPri + + USec a) en06000591.vsd IEC06000591 V1 EN Figure 24: Commonly used markings of VT terminals Where: a) is the symbol and terminal marking used in this document. Terminals marked with a square indicate the primary and secondary winding terminals with the same (positive) polarity b) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to- earth connected VTs c) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta connected VTs d) is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to- phase connected VTs It shall be noted that depending on national standard and utility practices the rated secondary voltage of a VT has typically one of the following values: • 100 V • 110 V • 115 V • 120 V • 230 V The IED fully supports all of these values and most of them will be shown in the following examples. 4.2.4.3 Examples on how to connect a three phase-to-earth connected VT to the IED Figure 25 gives an example on how to connect a three phase-to-earth connected VT to the IED. It gives an overview of required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED. Section 4 1MRK 502 071-UEN - Analog inputs 82 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

For correct terminal designations, see the connection diagrams valid

for the delivered IED. L1 IED L2 L3 66 3 110 3 kV V 1 3 2 66 3 110 3 kV V 66 3 110 3 kV V . #Not used 5 IEC06000599-4-en.vsdx 4 SMAI2 BLOCK REVROT ^GRP2L1 ^GRP2L2 ^GRP2L3 ^GRP2N AI3P AI1 AI2 AI3 AI4 AIN IEC06000599 V4 EN Figure 25: A Three phase-to-earth connected VT L1 IED L2 132 2 110 2 kV V 1 3 2 132 2 110 2 kV V IEC16000140-1-en.vsdx 4 SMAI2 BLOCK ^GRP2L1 ^GRP2L2 ^GRP2L1L2 ^GRP2N AI2P AI1 AI2 AI3 AI4 AIN 5 IEC16000140 V1 EN Figure 26: A two phase-to-earth connected VT 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 83 Application manual

shows how to connect three secondary phase-to-earth voltages to three VT inputs on the

IED 2) is the TRM where these three voltage inputs are located. For these three voltage inputs, the following setting values shall be entered: VTprim =132 kV VTsec = 110 V Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio of the entered values exactly corresponds to ratio of one individual VT. 66 66 3 110 110 3 = EQUATION1903 V1 EN (Equation 2) 3) are three connections made in Signal Matrix Tool (SMT), which connect these three voltage inputs to first three input channels of the preprocessing function block 5). Depending on the type of functions which need this voltage information, more then one preprocessing block might be connected in parallel to these three VT inputs. 4) shows that in this example the fourth (that is, residual) input channel of the preprocessing block is not connected in SMT tool. Thus the preprocessing block will automatically calculate 3Uo inside by vectorial sum from the three phase to earth voltages connected to the first three input channels of the same preprocessing block. Alternatively, the fourth input channel can be connected to open delta VT input, as shown in Figure 28. 5) is a Preprocessing block that has the task to digitally filter the connected analog inputs and calculate: • fundamental frequency phasors for all input channels • harmonic content for all input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors for the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block in the configuration tool. For this application most of the preprocessing settings can be left to the default values. However the following settings shall be set as shown here: UBase=66 kV (that is, rated Ph-Ph voltage) If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations) then the setting parameters DFTReference shall be set accordingly. 4.2.4.4 Example on how to connect a phase-to-phase connected VT to the IED Figure 27 gives an example how to connect a phase-to-phase connected VT to the IED. It gives an overview of the required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED. It shall be noted that this VT connection is only used on lower voltage levels (that is, rated primary voltage below 40 kV). Section 4 1MRK 502 071-UEN - Analog inputs 84 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC06000600 V5 EN

Figure 27: A Two phase-to-phase connected VT Where: 1) shows how to connect the secondary side of a phase-to-phase VT to the VT inputs on the IED 2) is the TRM where these three voltage inputs are located. It shall be noted that for these three voltage inputs the following setting values shall be entered: VTprim=13.8 kV VTsec=120 V Please note that inside the IED only ratio of these two parameters is used. Table continues on next page 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 85 Application manual

are three connections made in the Signal Matrix tool (SMT), Application configuration tool

(ACT), which connects these three voltage inputs to first three input channels of the preprocessing function block 5). Depending on the type of functions, which need this voltage information, more than one preprocessing block might be connected in parallel to these three VT inputs 4) shows that in this example the fourth (that is, residual) input channel of the preprocessing block is not connected in SMT. Note. If the parameters UL1, UL2, UL3, UN should be used the open delta must be connected here. 5) Preprocessing block has a task to digitally filter the connected analog inputs and calculate: • fundamental frequency phasors for all four input channels • harmonic content for all four input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors for the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block in the configuration tool. For this application most of the preprocessing settings can be left to the default values. However the following settings shall be set as shown here: ConnectionType=Ph-Ph UBase=13.8 kV If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations) then the setting parameters DFTReference shall be set accordingly. 4.2.4.5 Example on how to connect an open delta VT to the IED for high impedance earthed or unearthed networks Figure 28 gives an example about the wiring of an open delta VT to the IED for high impedance earthed or unearthed power systems. It shall be noted that this type of VT connection presents a secondary voltage proportional to 3U0 to the IED. In case of a solid earth fault close to the VT location the primary value of 3Uo will be equal to: 3 0 3 3 Ph Ph Ph N U U U - - = × = × EQUATION1921 V3 EN (Equation 3) The primary rated voltage of an open Delta VT is always equal to UPh-E. Three series connected VT secondary windings gives a secondary voltage equal to three times the individual VT secondary winding rating. Thus the secondary windings of open delta VTs quite often have a secondary rated voltage equal to one third of the rated phase- to-phase VT secondary voltage (110/3V in this particular example). Figure 28 gives overview of required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED as well. Section 4 1MRK 502 071-UEN - Analog inputs 86 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

# Not Used

5 IEC06000601-4-en.vsdx # Not Used # Not Used SMAI2 BLOCK REVROT ^GRP2L1 ^GRP2L2 ^GRP2L3 ^GRP2N AI3P AI1 AI2 AI3 AI4 AIN IEC06000601 V4 EN Figure 28: Open delta connected VT in high impedance earthed power system 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 87 Application manual

shows how to connect the secondary side of the open delta VT to one VT input on the IED.

+3U0 shall be connected to the IED 2) is the TRM where this voltage input is located. It shall be noted that for this voltage input the following setting values shall be entered: 3 6.6 11.43 VTprim kV = × = EQUATION1923 V1 EN (Equation 4) 110 sec 3 110 3 VT V = × = EQUATION1924 V1 EN (Equation 5) Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio of the entered values exactly corresponds to ratio of one individual open delta VT. 6.6 3 6.6 3 110 110 3 × = EQUATION1925 V1 EN (Equation 6) 3) shows that in this example the first three input channel of the preprocessing block is not connected in SMT tool or ACT tool. 4) shows the connection made in Signal Matrix Tool (SMT), Application configuration tool (ACT), which connect this voltage input to the fourth input channel of the preprocessing function block 5). 5) is a Preprocessing block that has the task to digitally filter the connected analog input and calculate: • fundamental frequency phasors for all four input channels • harmonic content for all four input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors for the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block in the configuration tool. For this application most of the preprocessing settings can be left to the default values. If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations ) then the setting parameters DFTReference shall be set accordingly. Section 4 1MRK 502 071-UEN - Analog inputs 88 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

Example how to connect the open delta VT to the IED for low

impedance earthed or solidly earthed power systems Figure 29 gives an example about the connection of an open delta VT to the IED for low impedance earthed or solidly earthed power systems. It shall be noted that this type of VT connection presents secondary voltage proportional to 3U0 to the IED. In case of a solid earth fault close to the VT location the primary value of 3Uo will be equal to: 3 3 Ph Ph Ph E U Uo U - - = = EQUATION1926 V1 EN (Equation 7) The primary rated voltage of such VT is always equal to UPh-E Therefore, three series connected VT secondary windings will give the secondary voltage equal only to one individual VT secondary winding rating. Thus the secondary windings of such open delta VTs quite often has a secondary rated voltage close to rated phase-to-phase VT secondary voltage, that is, 115V or 115/√3V as in this particular example. Figure 29 gives an overview of the actions which are needed to make this measurement available to the built-in protection and control functions within the IED. 1 L1 IED L2 L3 138 3 115 3 kV V +3Uo 138 3 115 3 kV V 138 3 115 3 kV V IEC06000602-4-en.vsdx # Not Used # Not Used # Not Used SMAI2 BLOCK REVROT ^GRP2L1 ^GRP2L2 ^GRP2L3 ^GRP2N AI3P AI1 AI2 AI3 AI4 AIN 2 3 4 5 IEC06000602 V4 EN Figure 29: Open delta connected VT in low impedance or solidly earthed power system 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 89 Application manual

shows how to connect the secondary side of open delta VT to one VT input in the IED.

+3Uo shall be connected to the IED. 2) is TRM where this voltage input is located. It shall be noted that for this voltage input the following setting values shall be entered: 3 138 138 3 VTprim kV = × = EQUATION1928 V1 EN (Equation 8) 115 sec 3 115 3 VT V = × = EQUATION1929 V1 EN (Equation 9) Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio of the entered values exactly corresponds to ratio of one individual open delta VT. 138 138 3 115 115 3 = EQUATION1930 V1 EN (Equation 10) 3) shows that in this example the first three input channel of the preprocessing block is not connected in SMT tool. 4) shows the connection made in Signal Matrix Tool (SMT), which connect this voltage input to the fourth input channel of the preprocessing function block 4). 5) preprocessing block has a task to digitally filter the connected analog inputs and calculate: • fundamental frequency phasors for all four input channels • harmonic content for all four input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors for the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block in the configuration tool. For this application most of the preprocessing settings can be left to the default values. If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations) then the setting parameters DFTReference shall be set accordingly. 4.2.4.7 Example on how to connect a neutral point VT to the IED Figure 30 gives an example on how to connect a neutral point VT to the IED. This type of VT connection presents secondary voltage proportional to U0 to the IED. Section 4 1MRK 502 071-UEN - Analog inputs 90 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

In case of a solid earth fault in high impedance earthed or unearthed systems the

primary value of Uo voltage will be equal to: 0 3 Ph Ph Ph E U U U - - = = EQUATION1931 V2 EN (Equation 11) Figure 30 gives an overview of required actions by the user in order to make this measurement available to the built-in protection and control functions within the IED. L1 L2 L3 IED 6.6 3 100 kV V R Uo IEC06000603-4-en.vsdx # Not Used # Not Used # Not Used Protected Object SMAI2 BLOCK REVROT ^GRP2L1 ^GRP2L2 ^GRP2L3 ^GRP2N AI3P AI1 AI2 AI3 AI4 AIN 1 2 3 4 5 IEC06000603 V4 EN Figure 30: Neutral point connected VT 1MRK 502 071-UEN - Section 4 Analog inputs Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 91 Application manual

shows how to connect the secondary side of neutral point VT to one VT input in the IED.

U0 shall be connected to the IED. 2) is the TRM or AIM where this voltage input is located. For this voltage input the following setting values shall be entered: 6.6 3.81 3 VTprim kV = = EQUATION1933 V1 EN (Equation 12) sec 100 VT V  EQUATION1934 V2 EN (Equation 13) Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio of the entered values exactly corresponds to ratio of the neutral point VT. 3) shows that in this example the first three input channel of the preprocessing block is not connected in SMT tool or ACT tool. 4) shows the connection made in Signal Matrix Tool (SMT), Application configuration tool (ACT), which connects this voltage input to the fourth input channel of the preprocessing function block 5). 5) is a preprocessing block that has the task to digitally filter the connected analog inputs and calculate: • fundamental frequency phasors for all four input channels • harmonic content for all four input channels • positive, negative and zero sequence quantities by using the fundamental frequency phasors for the first three input channels (channel one taken as reference for sequence quantities) These calculated values are then available for all built-in protection and control functions within the IED, which are connected to this preprocessing function block in the configuration tool. For this application, most of the preprocessing settings can be left to the default values. If frequency tracking and compensation is required (this feature is typically required only for IEDs installed in the generating stations) then the setting parameters DFTReference shall be set accordingly. Section 4 1MRK 502 071-UEN - Analog inputs 92 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual

IEC13000239 V3 EN

Figure 31: Local human-machine interface The LHMI of the IED contains the following elements: • Keypad • Display (LCD) • LED indicators • Communication port for PCM600 1MRK 502 071-UEN - Section 5 Local HMI Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 93 Application manual

The LHMI is used for setting, monitoring and controlling.

5.1 Display The LHMI includes a graphical monochrome liquid crystal display (LCD) with a resolution of 320 x 240 pixels. The character size can vary. The amount of characters and rows fitting the view depends on the character size and the view that is shown. The display view is divided into four basic areas. IEC15000270-1-en.vsdx IEC15000270 V1 EN Figure 32: Display layout 1 Path 2 Content 3 Status 4 Scroll bar (appears when needed) The function key button panel shows on request what actions are possible with the function buttons. Each function button has a LED indication that can be used as a Section 5 1MRK 502 071-UEN - Local HMI 94 Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062 Application manual