ABB REG670 Applications Manual
Read Online
Read the ABB REG670 Applications Manual online using the built-in PDF viewer.
Text of the manual
Document ID: 1MRK 502 071-UEN
Issued: May 2017
Revision: -
Product version: 2.2
© Copyright 2017 ABB. All rights reserved
This document and parts thereof must not be reproduced or copied without written
permission from ABB, and the contents thereof must not be imparted to a third party,
nor used for any unauthorized purpose.
The software and hardware described in this document is furnished under a license and
may be used or disclosed only in accordance with the terms of such license.
This product includes software developed by the OpenSSL Project for use in the
OpenSSL Toolkit. (http://www.openssl.org/) This product includes cryptographic
software written/developed by: Eric Young ([email protected]) and Tim Hudson
([email protected]).
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or
product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
The data, examples and diagrams in this manual are included solely for the concept or
product description and are not to be deemed as a statement of guaranteed properties.
All persons responsible for applying the equipment addressed in this manual must
satisfy themselves that each intended application is suitable and acceptable, including
that any applicable safety or other operational requirements are complied with. In
particular, any risks in applications where a system failure and/or product failure
would create a risk for harm to property or persons (including but not limited to
personal injuries or death) shall be the sole responsibility of the person or entity
applying the equipment, and those so responsible are hereby requested to ensure that
all measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be
completely ruled out. In case any errors are detected, the reader is kindly requested to
notify the manufacturer. Other than under explicit contractual commitments, in no
event shall ABB be responsible or liable for any loss or damage resulting from the use
of this manual or the application of the equipment.
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Directive 2004/108/EC) and concerning electrical equipment for
use within specified voltage limits (Low-voltage directive 2006/95/EC). This
conformity is the result of tests conducted by ABB in accordance with the product
standard EN 60255-26 for the EMC directive, and with the product standards EN
60255-1 and EN 60255-27 for the low voltage directive. The product is designed in
accordance with the international standards of the IEC 60255 series.
Table of contents
Section 1
Introduction.....................................................................21
This manual......................................................................................21
Intended audience............................................................................21
Product documentation.....................................................................22
Product documentation set..........................................................22
Document revision history........................................................... 23
Related documents......................................................................23
Document symbols and conventions................................................24
Symbols.......................................................................................24
Document conventions................................................................25
IEC 61850 edition 1 / edition 2 mapping...........................................26
Section 2
Application......................................................................35
General IED application....................................................................35
Main protection functions..................................................................44
Back-up protection functions............................................................ 45
Control and monitoring functions......................................................46
Communication.................................................................................52
Basic IED functions.......................................................................... 55
Section 3
Configuration..................................................................57
Description of REG670.....................................................................57
Introduction..................................................................................57
Description of configuration A20 ........................................... 57
Description of configuration B30............................................ 58
Description of configuration C30............................................ 60
Section 4
Analog inputs..................................................................63
Introduction.......................................................................................63
Setting guidelines............................................................................. 63
Setting of the phase reference channel.......................................63
Example................................................................................. 64
Setting of current channels..........................................................64
Example 1.............................................................................. 65
Example 2.............................................................................. 65
Example 3.............................................................................. 66
Examples on how to connect, configure and set CT inputs
for most commonly used CT connections.............................. 70
Example on how to connect a star connected three-phase
CT set to the IED....................................................................71
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1
Application manual
Example how to connect delta connected three-phase CT
set to the IED..........................................................................76
Example how to connect single-phase CT to the IED............ 79
Relationships between setting parameter Base Current, CT
rated primary current and minimum pickup of a protection IED.. 80
Setting of voltage channels......................................................... 81
Example................................................................................. 81
Examples how to connect, configure and set VT inputs for
most commonly used VT connections....................................82
Examples on how to connect a three phase-to-earth
connected VT to the IED........................................................ 82
Example on how to connect a phase-to-phase connected
VT to the IED..........................................................................84
Example on how to connect an open delta VT to the IED
for high impedance earthed or unearthed networks...............86
Example how to connect the open delta VT to the IED for
low impedance earthed or solidly earthed power systems.....89
Example on how to connect a neutral point VT to the IED.....90
Section 5
Local HMI....................................................................... 93
Display..............................................................................................94
LEDs.................................................................................................96
Keypad............................................................................................. 97
Local HMI functionality..................................................................... 99
Protection and alarm indication................................................... 99
Parameter management ...........................................................100
Front communication.................................................................101
Section 6
Wide area measurement system..................................103
C37.118 Phasor Measurement Data Streaming Protocol
Configuration PMUCONF............................................................... 103
Identification.............................................................................. 103
Application.................................................................................103
Operation principle.................................................................... 103
Short guidance for use of TCP............................................. 104
Short guidance for use of UDP.............................................105
Protocol reporting via IEEE 1344 and C37.118 PMUREPORT......107
Identification.............................................................................. 107
Application.................................................................................107
Operation principle.................................................................... 110
Frequency reporting............................................................. 111
Reporting filters.................................................................... 113
Scaling Factors for ANALOGREPORT channels................. 114
PMU Report Function Blocks Connection Rules in
PCM600 Application Configuration Tool (ACT)....................115
Table of contents
2
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Setting guidelines...................................................................... 121
Section 7
Differential protection................................................... 127
Transformer differential protection T2WPDIF and T3WPDIF ........ 127
Identification.............................................................................. 127
Application.................................................................................127
Setting guidelines...................................................................... 128
Restrained and unrestrained differential protection..............128
Elimination of zero sequence currents................................. 131
Inrush restraint methods.......................................................132
Overexcitation restraint method........................................... 132
Cross-blocking between phases.......................................... 133
External/Internal fault discriminator...................................... 133
On-line compensation for on-load tap-changer position.......135
Differential current alarm...................................................... 135
Open CT detection............................................................... 136
Switch onto fault feature.......................................................136
Setting example.........................................................................136
Introduction...........................................................................136
Typical main CT connections for transformer differential
protection..............................................................................137
Application Examples...........................................................139
Summary and conclusions................................................... 146
High impedance differential protection, single phase HZPDIF ...... 148
Identification.............................................................................. 148
Application.................................................................................148
The basics of the high impedance principle......................... 150
Connection examples for high impedance differential
protection...................................................................................156
Connections for three-phase high impedance differential
protection..............................................................................156
Connections for 1Ph High impedance differential
protection HZPDIF................................................................157
Setting guidelines...................................................................... 158
Configuration........................................................................158
Settings of protection function..............................................159
T-feeder protection...............................................................159
Tertiary reactor protection.................................................... 162
Restricted earth fault protection........................................... 165
Alarm level operation............................................................166
Generator differential protection GENPDIF ................................... 167
Identification.............................................................................. 167
Application.................................................................................168
Setting guidelines...................................................................... 169
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
3
Application manual
General settings................................................................... 169
Percentage restrained differential operation........................ 170
Negative sequence internal/external fault discriminator
feature.................................................................................. 172
Open CT detection............................................................... 173
Other additional options....................................................... 174
Low impedance restricted earth fault protection REFPDIF ........... 175
Identification.............................................................................. 175
Application.................................................................................175
Transformer winding, solidly earthed................................... 176
Transformer winding, earthed through zig-zag earthing
transformer...........................................................................177
Autotransformer winding, solidly earthed............................. 178
Reactor winding, solidly earthed.......................................... 178
Multi-breaker applications.................................................... 179
CT earthing direction............................................................180
Setting guidelines...................................................................... 180
Setting and configuration......................................................180
Settings................................................................................ 181
Section 8
Impedance protection...................................................183
Full-scheme distance measuring, Mho characteristic ZMHPDIS .. 183
Identification.............................................................................. 183
Application.................................................................................183
Generator underimpedance protection application.............. 183
Setting guidelines...................................................................... 183
Configuration........................................................................183
Settings................................................................................ 184
High speed distance protection ZMFPDIS..................................... 187
Identification.............................................................................. 187
Application.................................................................................188
System earthing................................................................... 188
Fault infeed from remote end............................................... 191
Load encroachment..............................................................192
Short line application............................................................193
Long transmission line application....................................... 194
Parallel line application with mutual coupling....................... 194
Tapped line application........................................................ 200
Setting guidelines...................................................................... 203
General.................................................................................203
Setting of zone 1.................................................................. 203
Setting of overreaching zone................................................203
Setting of reverse zone........................................................ 204
Setting of zones for parallel line application.........................205
Table of contents
4
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Setting the reach with respect to load.................................. 206
Zone reach setting lower than minimum load impedance.... 207
Zone reach setting higher than minimum load impedance...209
Other settings.......................................................................210
High speed distance protection for series compensated lines
ZMFCPDIS .................................................................................... 213
Identification.............................................................................. 213
Application.................................................................................214
System earthing................................................................... 214
Fault infeed from remote end............................................... 216
Load encroachment..............................................................217
Short line application............................................................218
Long transmission line application....................................... 219
Parallel line application with mutual coupling....................... 219
Tapped line application........................................................ 226
Series compensation in power systems.................................... 228
Steady state voltage regulation and increase of voltage
collapse limit.........................................................................228
Increase in power transfer....................................................230
Voltage and current inversion...............................................230
Impact of series compensation on protective IED of
adjacent lines....................................................................... 239
Distance protection...............................................................240
Underreaching and overreaching schemes..........................241
Setting guidelines...................................................................... 247
General.................................................................................247
Setting of zone 1.................................................................. 248
Setting of overreaching zone................................................248
Setting of reverse zone........................................................ 249
Series compensated and adjacent lines...............................249
Setting of zones for parallel line application.........................254
Setting of reach in resistive direction....................................255
Load impedance limitation, without load encroachment
function.................................................................................256
Zone reach setting higher than minimum load impedance...258
Parameter setting guidelines................................................259
Pole slip protection PSPPPAM ......................................................261
Identification.............................................................................. 262
Application.................................................................................262
Setting guidelines...................................................................... 265
Setting example for line application......................................267
Setting example for generator application............................271
Out-of-step protection OOSPPAM .................................................275
Identification.............................................................................. 275
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
5
Application manual
Setting guidelines...................................................................... 278
Loss of excitation LEXPDIS............................................................281
Identification.............................................................................. 281
Application.................................................................................281
Setting guidelines...................................................................... 287
Sensitive rotor earth fault protection, injection based ROTIPHIZ .. 290
Identification.............................................................................. 290
Application.................................................................................290
Rotor earth fault protection function..................................... 291
Setting guidelines...................................................................... 294
Setting injection unit REX060...............................................294
Connecting and setting voltage inputs................................. 295
Settings for sensitive rotor earth fault protection,ROTIPHIZ 297
100% stator earth fault protection, injection based STTIPHIZ .......299
Identification.............................................................................. 299
Application.................................................................................299
100% Stator earth fault protection function.......................... 300
Setting guidelines...................................................................... 305
Setting injection unit REX060...............................................305
Connecting and setting voltage inputs................................. 306
100% stator earth fault protection........................................ 307
Under impedance protection for generators and transformers
ZGVPDIS........................................................................................308
Identification.............................................................................. 308
Application.................................................................................308
Operating zones...................................................................310
Zone 1 operation.................................................................. 311
Zone 2 operation.................................................................. 311
Zone 3 operation.................................................................. 312
CT and VT positions.............................................................312
Undervoltage seal-in function...............................................313
Load encroachment for zone 2 and zone 3..........................313
External block signals...........................................................314
Setting Guidelines..................................................................... 314
General.................................................................................314
Load encroachment..............................................................315
Under voltage seal-in........................................................... 316
Rotor earth fault protection using CVGAPC................................... 317
Section 9
Current protection.........................................................319
Instantaneous phase overcurrent protection PHPIOC .................. 319
Identification.............................................................................. 319
Application.................................................................................319
Table of contents
6
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Setting guidelines...................................................................... 320
Meshed network without parallel line................................... 320
Meshed network with parallel line........................................ 322
Directional phase overcurrent protection, four steps OC4PTOC....324
Identification.............................................................................. 324
Application.................................................................................324
Setting guidelines...................................................................... 325
Settings for each step...........................................................327
Setting example....................................................................330
Instantaneous residual overcurrent protection EFPIOC ................ 335
Identification.............................................................................. 335
Application.................................................................................335
Setting guidelines...................................................................... 335
Directional residual overcurrent protection, four steps EF4PTOC .338
Identification.............................................................................. 338
Application.................................................................................338
Setting guidelines...................................................................... 340
Common settings for all steps.............................................. 341
2nd harmonic restrain...........................................................342
Parallel transformer inrush current logic...............................343
Switch onto fault logic...........................................................344
Settings for each step (x = 1, 2, 3 and 4)............................. 344
Transformer application example......................................... 347
Four step directional negative phase sequence overcurrent
protection NS4PTOC .....................................................................350
Identification.............................................................................. 350
Application.................................................................................350
Setting guidelines...................................................................... 352
Settings for each step ..........................................................353
Common settings for all steps.............................................. 355
Sensitive directional residual overcurrent and power protection
SDEPSDE ..................................................................................... 356
Identification.............................................................................. 357
Application.................................................................................357
Setting guidelines...................................................................... 358
Thermal overload protection, two time constants TRPTTR ...........366
Identification.............................................................................. 367
Application.................................................................................367
Setting guideline........................................................................368
Breaker failure protection CCRBRF............................................... 370
Identification.............................................................................. 370
Application.................................................................................370
Setting guidelines...................................................................... 371
Pole discordance protection CCPDSC........................................... 374
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
7
Application manual
Setting guidelines...................................................................... 375
Directional underpower protection GUPPDUP............................... 376
Identification.............................................................................. 376
Application.................................................................................376
Setting guidelines...................................................................... 378
Directional overpower protection GOPPDOP ................................381
Identification.............................................................................. 381
Application.................................................................................381
Setting guidelines...................................................................... 383
Negativ sequence time overcurrent protection for machines
NS2PTOC ......................................................................................387
Identification.............................................................................. 387
Application.................................................................................387
Features............................................................................... 388
Generator continuous unbalance current capability............. 389
Setting guidelines...................................................................... 391
Operate time characteristic.................................................. 391
Start sensitivity..................................................................... 392
Alarm function...................................................................... 392
Accidental energizing protection for synchronous generator
AEGPVOC......................................................................................393
Identification.............................................................................. 393
Application.................................................................................393
Setting guidelines...................................................................... 393
Voltage-restrained time overcurrent protection VRPVOC.............. 394
Identification.............................................................................. 394
Application.................................................................................395
Base quantities.....................................................................395
Application possibilities........................................................ 396
Undervoltage seal-in............................................................ 396
Setting guidelines...................................................................... 397
Explanation of the setting parameters..................................397
Voltage-restrained overcurrent protection for generator
and step-up transformer.......................................................398
General settings................................................................... 398
Overcurrent protection with undervoltage seal-in.................399
Generator stator overload protection GSPTTR ............................. 399
Identification.............................................................................. 400
Application.................................................................................400
Generator rotor overload protection GRPTTR ...............................400
Identification.............................................................................. 400
Application.................................................................................400
Table of contents
8
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Section 10 Voltage protection........................................................ 403
Two step undervoltage protection UV2PTUV ................................403
Identification.............................................................................. 403
Application.................................................................................403
Setting guidelines...................................................................... 404
Equipment protection, such as for motors and generators...404
Disconnected equipment detection...................................... 404
Power supply quality ........................................................... 404
Voltage instability mitigation.................................................404
Backup protection for power system faults...........................404
Settings for two step undervoltage protection...................... 405
Two step overvoltage protection OV2PTOV ..................................406
Identification.............................................................................. 406
Application.................................................................................406
Setting guidelines...................................................................... 407
Equipment protection, such as for motors, generators,
reactors and transformers.................................................... 408
Equipment protection, capacitors......................................... 408
Power supply quality............................................................ 408
High impedance earthed systems........................................ 408
The following settings can be done for the two step
overvoltage protection..........................................................408
Two step residual overvoltage protection ROV2PTOV ................. 410
Identification.............................................................................. 410
Application.................................................................................410
Setting guidelines...................................................................... 411
Equipment protection, such as for motors, generators,
reactors and transformersEquipment protection
for transformers.................................................................... 411
Equipment protection, capacitors......................................... 411
Stator earth-fault protection based on residual voltage
measurement....................................................................... 412
Power supply quality............................................................ 415
High impedance earthed systems........................................ 415
Direct earthed system.......................................................... 416
Settings for two step residual overvoltage protection...........417
Overexcitation protection OEXPVPH ............................................ 419
Identification.............................................................................. 419
Application.................................................................................419
Setting guidelines...................................................................... 421
Recommendations for input and output signals................... 421
Settings................................................................................ 422
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
9
Application manual
Service value report............................................................. 423
Setting example....................................................................423
Voltage differential protection VDCPTOV ......................................425
Identification.............................................................................. 425
Application.................................................................................425
Setting guidelines...................................................................... 427
100% Stator earth fault protection, 3rd harmonic based STEFPHIZ429
Identification.............................................................................. 429
Application.................................................................................429
Setting guidelines...................................................................... 433
Section 11 Frequency protection....................................................437
Underfrequency protection SAPTUF ............................................. 437
Identification.............................................................................. 437
Application.................................................................................437
Setting guidelines...................................................................... 437
Overfrequency protection SAPTOF ...............................................438
Identification.............................................................................. 438
Application.................................................................................439
Setting guidelines...................................................................... 439
Rate-of-change of frequency protection SAPFRC .........................440
Identification.............................................................................. 440
Application.................................................................................440
Setting guidelines...................................................................... 440
Frequency time accumulation protection function FTAQFVR........ 441
Identification.............................................................................. 441
Application.................................................................................441
Setting guidelines...................................................................... 443
Section 12 Multipurpose protection................................................445
General current and voltage protection CVGAPC.......................... 445
Identification.............................................................................. 445
Application.................................................................................445
Current and voltage selection for CVGAPC function............446
Base quantities for CVGAPC function..................................448
Application possibilities........................................................ 449
Inadvertent generator energization...................................... 450
Setting guidelines...................................................................... 451
Directional negative sequence overcurrent protection......... 451
Negative sequence overcurrent protection...........................453
Generator stator overload protection in accordance with
IEC or ANSI standards.........................................................455
Table of contents
10
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Open phase protection for transformer, lines or
generators and circuit breaker head flashover protection
for generators.......................................................................457
Voltage restrained overcurrent protection for generator
and step-up transformer.......................................................458
Loss of excitation protection for a generator........................ 458
Inadvertent generator energization...................................... 460
General settings of the instance...........................................462
Settings for OC1...................................................................462
Setting for OC2.....................................................................462
Setting for UC1.....................................................................463
Setting for UC2.....................................................................463
Settings for OV1...................................................................463
Setting for OV2.....................................................................463
Settings for UV1................................................................... 463
Setting for UV2.....................................................................464
Section 13 System protection and control......................................465
Multipurpose filter SMAIHPAC....................................................... 465
Identification.............................................................................. 465
Application.................................................................................465
Setting guidelines...................................................................... 466
Setting example....................................................................466
Section 14 Secondary system supervision.....................................471
Current circuit supervision CCSSPVC............................................471
Identification.............................................................................. 471
Application.................................................................................471
Setting guidelines...................................................................... 471
Fuse failure supervision FUFSPVC................................................472
Identification.............................................................................. 472
Application.................................................................................472
Setting guidelines...................................................................... 473
General.................................................................................473
Setting of common parameters............................................ 473
Negative sequence based....................................................474
Zero sequence based...........................................................475
Delta U and delta I ...............................................................475
Dead line detection...............................................................476
Fuse failure supervision VDSPVC..................................................476
Identification.............................................................................. 476
Application.................................................................................477
Setting guidelines...................................................................... 478
Section 15 Control..........................................................................479
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
11
Application manual
Synchrocheck, energizing check, and synchronizing SESRSYN...479
Identification.............................................................................. 479
Application.................................................................................479
Synchronizing.......................................................................479
Synchrocheck.......................................................................480
Energizing check..................................................................482
Voltage selection..................................................................483
External fuse failure..............................................................484
Application examples.................................................................485
Single circuit breaker with single busbar.............................. 486
Single circuit breaker with double busbar, external voltage
selection............................................................................... 486
Single circuit breaker with double busbar, internal voltage
selection............................................................................... 487
Double circuit breaker.......................................................... 488
1 1/2 circuit breaker..............................................................488
Setting guidelines...................................................................... 491
Apparatus control APC...................................................................496
Application.................................................................................496
Bay control QCBAY..............................................................500
Switch controller SCSWI...................................................... 501
Switches SXCBR/SXSWI..................................................... 502
Proxy for signals from switching device via GOOSE
XLNPROXY..........................................................................503
Reservation function (QCRSV and RESIN)......................... 506
Interaction between modules.....................................................508
Setting guidelines...................................................................... 510
Bay control (QCBAY)........................................................... 511
Switch controller (SCSWI)....................................................511
Switch (SXCBR/SXSWI)...................................................... 512
Proxy for signals from switching device via GOOSE
XLNPROXY..........................................................................513
Bay Reserve (QCRSV).........................................................513
Reservation input (RESIN)................................................... 513
Interlocking .................................................................................... 514
Configuration guidelines............................................................515
Interlocking for line bay ABC_LINE .......................................... 515
Application............................................................................515
Signals from bypass busbar.................................................516
Signals from bus-coupler......................................................517
Configuration setting............................................................ 519
Interlocking for bus-coupler bay ABC_BC ................................ 520
Application............................................................................521
Configuration........................................................................521
Table of contents
12
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Signals from all feeders........................................................521
Signals from bus-coupler......................................................523
Configuration setting............................................................ 525
Interlocking for transformer bay AB_TRAFO ............................526
Application............................................................................526
Signals from bus-coupler......................................................527
Configuration setting............................................................ 527
Interlocking for bus-section breaker A1A2_BS..........................528
Application............................................................................528
Signals from all feeders........................................................528
Configuration setting............................................................ 531
Interlocking for bus-section disconnector A1A2_DC ................ 532
Application............................................................................532
Signals in single breaker arrangement.................................532
Signals in double-breaker arrangement............................... 535
Signals in 1 1/2 breaker arrangement.................................. 538
Interlocking for busbar earthing switch BB_ES .........................539
Application............................................................................539
Signals in single breaker arrangement.................................539
Signals in double-breaker arrangement............................... 543
Signals in 1 1/2 breaker arrangement.................................. 544
Interlocking for double CB bay DB ........................................... 545
Application............................................................................545
Configuration setting............................................................ 546
Interlocking for 1 1/2 CB BH .....................................................547
Application............................................................................547
Configuration setting............................................................ 547
Voltage control................................................................................548
Application.................................................................................548
Setting guidelines...................................................................... 580
TR1ATCC or TR8ATCC general settings.............................580
TR1ATCC or TR8ATCC Setting group ................................581
TCMYLTC and TCLYLTC general settings.......................... 589
Logic rotating switch for function selection and LHMI
presentation SLGAPC.................................................................... 590
Identification.............................................................................. 590
Application.................................................................................591
Setting guidelines...................................................................... 591
Selector mini switch VSGAPC........................................................591
Identification.............................................................................. 592
Application.................................................................................592
Setting guidelines...................................................................... 592
Generic communication function for Double Point indication
DPGAPC........................................................................................ 593
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
13
Application manual
Setting guidelines...................................................................... 594
Single point generic control 8 signals SPC8GAPC........................ 594
Identification.............................................................................. 594
Application.................................................................................594
Setting guidelines...................................................................... 594
AutomationBits, command function for DNP3.0 AUTOBITS.......... 595
Identification.............................................................................. 595
Application.................................................................................595
Setting guidelines...................................................................... 595
Single command, 16 signals SINGLECMD.................................... 595
Identification.............................................................................. 595
Application.................................................................................596
Setting guidelines...................................................................... 597
Section 16 Logic.............................................................................599
Tripping logic SMPPTRC ...............................................................599
Identification.............................................................................. 599
Application.................................................................................599
Three-phase tripping............................................................ 600
Single- and/or three-phase tripping......................................601
Single-, two- or three-phase tripping.................................... 602
Lock-out................................................................................602
Example of directional data..................................................603
Blocking of the function block...............................................605
Setting guidelines...................................................................... 605
Trip matrix logic TMAGAPC........................................................... 605
Identification.............................................................................. 606
Application.................................................................................606
Setting guidelines...................................................................... 606
Logic for group alarm ALMCALH....................................................606
Identification.............................................................................. 606
Application.................................................................................607
Setting guidelines...................................................................... 607
Logic for group alarm WRNCALH.................................................. 607
Identification.............................................................................. 607
Application............................................................................607
Setting guidelines.................................................................607
Logic for group indication INDCALH...............................................607
Identification.............................................................................. 607
Application............................................................................608
Setting guidelines.................................................................608
Configurable logic blocks................................................................608
Table of contents
14
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Setting guidelines...................................................................... 608
Configuration........................................................................608
Fixed signal function block FXDSIGN............................................ 610
Identification.............................................................................. 610
Application.................................................................................610
Boolean 16 to Integer conversion B16I.......................................... 611
Identification.............................................................................. 611
Application.................................................................................611
Boolean to integer conversion with logical node representation,
16 bit BTIGAPC..............................................................................612
Identification.............................................................................. 612
Application.................................................................................612
Integer to Boolean 16 conversion IB16.......................................... 613
Identification.............................................................................. 614
Application.................................................................................614
Integer to Boolean 16 conversion with logic node representation
ITBGAPC........................................................................................615
Identification.............................................................................. 615
Application.................................................................................615
Pulse integrator TIGAPC................................................................ 616
Identification.............................................................................. 616
Application.................................................................................616
Setting guidelines...................................................................... 616
Elapsed time integrator with limit transgression and overflow
supervision TEIGAPC.....................................................................617
Identification.............................................................................. 617
Application.................................................................................617
Setting guidelines...................................................................... 617
Comparator for integer inputs - INTCOMP..................................... 618
Identification.............................................................................. 618
Application.................................................................................618
Setting guidelines...................................................................... 618
Setting example.........................................................................618
Comparator for real inputs - REALCOMP...................................... 619
Identification.............................................................................. 619
Application.................................................................................619
Setting guidelines...................................................................... 619
Setting example.........................................................................620
Section 17 Monitoring.....................................................................623
Measurement..................................................................................623
Identification.............................................................................. 623
Application.................................................................................623
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
15
Application manual
Setting guidelines...................................................................... 626
Setting examples..................................................................629
Gas medium supervision SSIMG................................................... 635
Identification.............................................................................. 635
Application.................................................................................635
Setting guidelines...................................................................... 635
Liquid medium supervision SSIML................................................. 636
Identification.............................................................................. 636
Application.................................................................................637
Setting guidelines...................................................................... 637
Breaker monitoring SSCBR............................................................638
Identification.............................................................................. 638
Application.................................................................................638
Setting guidelines...................................................................... 640
Setting procedure on the IED...............................................641
Event function EVENT....................................................................642
Identification.............................................................................. 642
Application.................................................................................642
Setting guidelines...................................................................... 642
Disturbance report DRPRDRE....................................................... 643
Identification.............................................................................. 643
Application.................................................................................643
Setting guidelines...................................................................... 644
Recording times................................................................... 647
Binary input signals.............................................................. 647
Analog input signals............................................................. 648
Sub-function parameters......................................................648
Consideration....................................................................... 649
Logical signal status report BINSTATREP..................................... 650
Identification.............................................................................. 650
Application.................................................................................650
Setting guidelines...................................................................... 651
Limit counter L4UFCNT..................................................................651
Identification.............................................................................. 651
Application.................................................................................651
Setting guidelines...................................................................... 651
Running hour-meter TEILGAPC.....................................................652
Identification.............................................................................. 652
Application.................................................................................652
Setting guidelines...................................................................... 652
Estimation of transformer insulation life LOLSPTR ....................... 652
Application.................................................................................652
Table of contents
16
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Setting guidelines...................................................................... 657
Setting example.........................................................................665
Transformer Rated Data.......................................................665
Setting parameters for insulation loss of life calculation
function (LOL1).....................................................................666
Section 18 Metering....................................................................... 671
Pulse-counter logic PCFCNT......................................................... 671
Identification.............................................................................. 671
Application.................................................................................671
Setting guidelines...................................................................... 671
Function for energy calculation and demand handling ETPMMTR 672
Identification.............................................................................. 672
Application.................................................................................672
Setting guidelines...................................................................... 673
Section 19 Ethernet-based communication....................................675
Access point................................................................................... 675
Application.................................................................................675
Setting guidelines...................................................................... 675
Redundant communication.............................................................676
Identification.............................................................................. 676
Application.................................................................................677
Setting guidelines...................................................................... 678
Merging unit....................................................................................679
Application.................................................................................679
Setting guidelines...................................................................... 680
Routes............................................................................................ 680
Application.................................................................................680
Setting guidelines...................................................................... 680
Section 20 Station communication.................................................681
Communication protocols...............................................................681
IEC 61850-8-1 communication protocol......................................... 681
Application IEC 61850-8-1.........................................................681
Setting guidelines...................................................................... 683
Horizontal communication via GOOSE..................................... 683
Sending data........................................................................ 683
Receiving data......................................................................684
IEC/UCA 61850-9-2LE communication protocol............................ 685
Introduction................................................................................685
Setting guidelines...................................................................... 687
Specific settings related to the IEC/UCA 61850-9-2LE
communication..................................................................... 688
Loss of communication when used with LDCM....................688
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
17
Application manual
Setting examples for IEC/UCA 61850-9-2LE and time
synchronization.................................................................... 692
IEC 61850 quality expander QUALEXP.................................... 697
LON communication protocol......................................................... 698
Application.................................................................................698
MULTICMDRCV and MULTICMDSND..................................... 700
Identification......................................................................... 700
Application............................................................................700
Setting guidelines.................................................................700
SPA communication protocol......................................................... 700
Application.................................................................................700
Setting guidelines...................................................................... 701
IEC 60870-5-103 communication protocol..................................... 703
Application.................................................................................703
Functionality......................................................................... 703
Design.................................................................................. 704
Settings......................................................................................706
Settings for RS485 and optical serial communication.......... 707
Settings from PCM600......................................................... 708
Function and information types................................................. 710
DNP3 Communication protocol...................................................... 711
Application.................................................................................711
Section 21 Remote communication................................................713
Binary signal transfer......................................................................713
Identification.............................................................................. 713
Application.................................................................................713
Communication hardware solutions..................................... 714
Setting guidelines...................................................................... 715
Section 22 Security........................................................................ 719
Authority status ATHSTAT............................................................. 719
Application.................................................................................719
Self supervision with internal event list INTERRSIG...................... 719
Application.................................................................................719
Change lock CHNGLCK.................................................................720
Application.................................................................................720
Denial of service SCHLCCH/RCHLCCH ....................................... 721
Application.................................................................................721
Setting guidelines...................................................................... 721
Section 23 Basic IED functions...................................................... 723
IED identifiers TERMINALID.......................................................... 723
Application.................................................................................723
Table of contents
18
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Product information PRODINF....................................................... 723
Application.................................................................................723
Factory defined settings............................................................ 723
Measured value expander block RANGE_XP................................ 724
Identification.............................................................................. 724
Application.................................................................................725
Setting guidelines...................................................................... 725
Parameter setting groups............................................................... 725
Application.................................................................................725
Setting guidelines...................................................................... 726
Rated system frequency PRIMVAL................................................ 726
Identification.............................................................................. 726
Application.................................................................................726
Setting guidelines...................................................................... 726
Summation block 3 phase 3PHSUM.............................................. 726
Application.................................................................................726
Setting guidelines...................................................................... 727
Global base values GBASVAL....................................................... 727
Identification.............................................................................. 727
Application.................................................................................727
Setting guidelines...................................................................... 727
Signal matrix for binary inputs SMBI.............................................. 728
Application.................................................................................728
Setting guidelines...................................................................... 728
Signal matrix for binary outputs SMBO ......................................... 728
Application.................................................................................728
Setting guidelines...................................................................... 728
Signal matrix for mA inputs SMMI.................................................. 728
Application.................................................................................729
Setting guidelines...................................................................... 729
Signal matrix for analog inputs SMAI............................................. 729
Application.................................................................................729
Frequency values...................................................................... 729
Setting guidelines...................................................................... 730
Test mode functionality TESTMODE..............................................736
Application.................................................................................736
IEC 61850 protocol test mode..............................................736
Setting guidelines...................................................................... 737
Time synchronization TIMESYNCHGEN........................................737
Application.................................................................................737
Setting guidelines...................................................................... 739
System time..........................................................................739
Synchronization....................................................................739
Table of contents
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
19
Application manual
Process bus IEC/UCA 61850-9-2LE synchronization.......... 742
Section 24 Requirements...............................................................743
Current transformer requirements.................................................. 743
Current transformer basic classification and requirements....... 743
Conditions..................................................................................745
Fault current.............................................................................. 746
Secondary wire resistance and additional load......................... 746
General current transformer requirements................................ 746
Rated equivalent secondary e.m.f. requirements......................747
Guide for calculation of CT for generator differential
protection..............................................................................747
Transformer differential protection....................................... 753
Breaker failure protection..................................................... 754
Restricted earth fault protection (low impedance differential)754
Current transformer requirements for CTs according to other
standards...................................................................................757
Current transformers according to IEC 61869-2, class P, PR757
Current transformers according to IEC 61869-2, class PX,
PXR (and old IEC 60044-6, class TPS
and old British Standard, class X)........................................ 757
Current transformers according to ANSI/IEEE..................... 758
Voltage transformer requirements.................................................. 758
SNTP server requirements............................................................. 759
PTP requirements...........................................................................759
Sample specification of communication requirements for the
protection and control terminals in digital telecommunication
networks......................................................................................... 759
IEC/UCA 61850-9-2LE Merging unit requirements ....................... 760
Section 25 Glossary....................................................................... 763
Table of contents
20
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose a
typical protection function can be used. The manual can also provide assistance for
calculating settings.
1.2
Intended audience
This manual addresses the protection and control engineer responsible for planning,
pre-engineering and engineering.
The protection and control engineer must be experienced in electrical power
engineering and have knowledge of related technology, such as protection schemes
and communication principles.
1MRK 502 071-UEN -
Section 1
Introduction
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
21
Application manual
Product documentation set
IEC07000220-4-en.vsd
Planning & purchase
Engineering
Installing
Commissioning
Operation
Maintenance
Decommissioning
Deinstalling & disposal
Application manual
Operation manual
Installation manual
Engineering manual
Communication
protocol manual
Cyber security
deployment guideline
Technical manual
Commissioning manual
IEC07000220 V4 EN
Figure 1:
The intended use of manuals throughout the product lifecycle
The engineering manual contains instructions on how to engineer the IEDs using the
various tools available within the PCM600 software. The manual provides
instructions on how to set up a PCM600 project and insert IEDs to the project
structure. The manual also recommends a sequence for the engineering of protection
and control functions, LHMI functions as well as communication engineering for IEC
60870-5-103, IEC 61850, DNP3, LON and SPA.
The installation manual contains instructions on how to install the IED. The manual
provides procedures for mechanical and electrical installation. The chapters are
organized in the chronological order in which the IED should be installed.
The commissioning manual contains instructions on how to commission the IED. The
manual can also be used by system engineers and maintenance personnel for
assistance during the testing phase. The manual provides procedures for the checking
of external circuitry and energizing the IED, parameter setting and configuration as
Section 1
1MRK 502 071-UEN -
Introduction
22
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
well as verifying settings by secondary injection. The manual describes the process of
testing an IED in a substation which is not in service. The chapters are organized in the
chronological order in which the IED should be commissioned. The relevant
procedures may be followed also during the service and maintenance activities.
The operation manual contains instructions on how to operate the IED once it has been
commissioned. The manual provides instructions for the monitoring, controlling and
setting of the IED. The manual also describes how to identify disturbances and how to
view calculated and measured power grid data to determine the cause of a fault.
The application manual contains application descriptions and setting guidelines
sorted per function. The manual can be used to find out when and for what purpose a
typical protection function can be used. The manual can also provide assistance for
calculating settings.
The technical manual contains operation principle descriptions, and lists function
blocks, logic diagrams, input and output signals, setting parameters and technical
data, sorted per function. The manual can be used as a technical reference during the
engineering phase, installation and commissioning phase, and during normal service.
The communication protocol manual describes the communication protocols
supported by the IED. The manual concentrates on the vendor-specific
implementations.
The point list manual describes the outlook and properties of the data points specific
to the IED. The manual should be used in conjunction with the corresponding
communication protocol manual.
The cyber security deployment guideline describes the process for handling cyber
security when communicating with the IED. Certification, Authorization with role
based access control, and product engineering for cyber security related events are
described and sorted by function. The guideline can be used as a technical reference
during the engineering phase, installation and commissioning phase, and during
normal service.
1.3.2
Document revision history
Document revision/date
History
–/May 2017
First release
1.3.3
Related documents
Documents related to REG670
Document numbers
Application manual
1MRK 502 071-UEN
Commissioning manual
1MRK 502 073-UEN
Product guide
1MRK 502 074-BEN
Technical manual
1MRK 502 072-UEN
Type test certificate
1MRK 502 074-TEN
1MRK 502 071-UEN -
Section 1
Introduction
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
23
Application manual
670 series manuals
Document numbers
Operation manual
1MRK 500 127-UEN
Engineering manual
1MRK 511 398-UEN
Installation manual
1MRK 514 026-UEN
Communication protocol manual, DNP3
1MRK 511 391-UUS
Communication protocol manual, IEC
60870-5-103
1MRK 511 394-UEN
Communication protocol manual, IEC 61850
Edition 1
1MRK 511 392-UEN
Communication protocol manual, IEC 61850
Edition 2
1MRK 511 393-UEN
Communication protocol manual, LON
1MRK 511 395-UEN
Communication protocol manual, SPA
1MRK 511 396-UEN
Point list manual, DNP3
1MRK 511 397-UUS
Accessories guide
1MRK 514 012-BEN
Cyber security deployment guideline
1MRK 511 399-UEN
Connection and Installation components
1MRK 513 003-BEN
Test system, COMBITEST
1MRK 512 001-BEN
Application guide, Communication set-up
1MRK 505 382-UEN
1.4
Document symbols and conventions
1.4.1
Symbols
The electrical warning icon indicates the presence of a hazard which
could result in electrical shock.
The warning icon indicates the presence of a hazard which could
result in personal injury.
The caution hot surface icon indicates important information or
warning about the temperature of product surfaces.
Class 1 Laser product. Take adequate measures to protect the eyes and
do not view directly with optical instruments.
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence of
Section 1
1MRK 502 071-UEN -
Introduction
24
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
a hazard which could result in corruption of software or damage to
equipment or property.
The information icon alerts the reader of important facts and
conditions.
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, it is necessary to understand
that under certain operational conditions, operation of damaged equipment may result
in degraded process performance leading to personal injury or death. It is important
that the user fully complies with all warning and cautionary notices.
1.4.2
Document conventions
•
Abbreviations and acronyms in this manual are spelled out in the glossary. The
glossary also contains definitions of important terms.
•
Push button navigation in the LHMI menu structure is presented by using the
push button icons.
For example, to navigate between the options, use
and
.
•
HMI menu paths are presented in bold.
For example, select Main menu/Settings.
•
LHMI messages are shown in Courier font.
For example, to save the changes in non-volatile memory, select Yes and press
.
•
Parameter names are shown in italics.
For example, the function can be enabled and disabled with the Operation setting.
•
Each function block symbol shows the available input/output signal.
•
the character ^ in front of an input/output signal name indicates that the
signal name may be customized using the PCM600 software.
•
the character * after an input signal name indicates that the signal must be
connected to another function block in the application configuration to
achieve a valid application configuration.
•
Logic diagrams describe the signal logic inside the function block and are
bordered by dashed lines.
•
Signals in frames with a shaded area on their right hand side represent
setting parameter signals that are only settable via the PST, ECT or LHMI.
•
If an internal signal path cannot be drawn with a continuous line, the suffix
-int is added to the signal name to indicate where the signal starts and
continues.
•
Signal paths that extend beyond the logic diagram and continue in another
diagram have the suffix ”-cont.”
1MRK 502 071-UEN -
Section 1
Introduction
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
25
Application manual
Illustrations are used as an example and might show other products
than the one the manual describes. The example that is illustrated is
still valid.
1.5
IEC 61850 edition 1 / edition 2 mapping
Function block names are used in ACT and PST to identify functions. Respective
function block names of Edition 1 logical nodes and Edition 2 logical nodes are shown
in the table below.
Table 1:
IEC 61850 edition 1 / edition 2 mapping
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
AEGPVOC
AEGGAPC
AEGPVOC
AGSAL
AGSAL
SECLLN0
AGSAL
ALMCALH
ALMCALH
ALMCALH
ALTIM
-
ALTIM
ALTMS
-
ALTMS
ALTRK
-
ALTRK
BCZPDIF
BCZPDIF
BCZPDIF
BCZSPDIF
BCZSPDIF
BCZSPDIF
BCZTPDIF
BCZTPDIF
BCZTPDIF
BDCGAPC
SWSGGIO
BBCSWI
BDCGAPC
BDZSGAPC
BBS6LLN0
BDZSGAPC
LLN0
BDZSGAPC
BFPTRC_F01
BFPTRC
BFPTRC
BFPTRC_F02
BFPTRC
BFPTRC
BFPTRC_F03
BFPTRC
BFPTRC
BFPTRC_F04
BFPTRC
BFPTRC
BFPTRC_F05
BFPTRC
BFPTRC
BFPTRC_F06
BFPTRC
BFPTRC
BFPTRC_F07
BFPTRC
BFPTRC
BFPTRC_F08
BFPTRC
BFPTRC
BFPTRC_F09
BFPTRC
BFPTRC
BFPTRC_F10
BFPTRC
BFPTRC
BFPTRC_F11
BFPTRC
BFPTRC
BFPTRC_F12
BFPTRC
BFPTRC
BFPTRC_F13
BFPTRC
BFPTRC
BFPTRC_F14
BFPTRC
BFPTRC
BFPTRC_F15
BFPTRC
BFPTRC
Table continues on next page
Section 1
1MRK 502 071-UEN -
Introduction
26
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
BFPTRC_F16
BFPTRC
BFPTRC
BFPTRC_F17
BFPTRC
BFPTRC
BFPTRC_F18
BFPTRC
BFPTRC
BFPTRC_F19
BFPTRC
BFPTRC
BFPTRC_F20
BFPTRC
BFPTRC
BFPTRC_F21
BFPTRC
BFPTRC
BFPTRC_F22
BFPTRC
BFPTRC
BFPTRC_F23
BFPTRC
BFPTRC
BFPTRC_F24
BFPTRC
BFPTRC
BICPTRC_01
BICPTRC
BICPTRC
BICPTRC_02
BICPTRC
BICPTRC
BICPTRC_03
BICPTRC
BICPTRC
BICPTRC_04
BICPTRC
BICPTRC
BICPTRC_05
BICPTRC
BICPTRC
BRCPTOC
BRCPTOC
BRCPTOC
BRPTOC
BRPTOC
BRPTOC
BTIGAPC
B16IFCVI
BTIGAPC
BUSPTRC_B1
BUSPTRC
BBSPLLN0
BUSPTRC
BUSPTRC_B2
BUSPTRC
BUSPTRC
BUSPTRC_B3
BUSPTRC
BUSPTRC
BUSPTRC_B4
BUSPTRC
BUSPTRC
BUSPTRC_B5
BUSPTRC
BUSPTRC
BUSPTRC_B6
BUSPTRC
BUSPTRC
BUSPTRC_B7
BUSPTRC
BUSPTRC
BUSPTRC_B8
BUSPTRC
BUSPTRC
BUSPTRC_B9
BUSPTRC
BUSPTRC
BUSPTRC_B10
BUSPTRC
BUSPTRC
BUSPTRC_B11
BUSPTRC
BUSPTRC
BUSPTRC_B12
BUSPTRC
BUSPTRC
BUSPTRC_B13
BUSPTRC
BUSPTRC
BUSPTRC_B14
BUSPTRC
BUSPTRC
BUSPTRC_B15
BUSPTRC
BUSPTRC
BUSPTRC_B16
BUSPTRC
BUSPTRC
BUSPTRC_B17
BUSPTRC
BUSPTRC
BUSPTRC_B18
BUSPTRC
BUSPTRC
BUSPTRC_B19
BUSPTRC
BUSPTRC
BUSPTRC_B20
BUSPTRC
BUSPTRC
BUSPTRC_B21
BUSPTRC
BUSPTRC
BUSPTRC_B22
BUSPTRC
BUSPTRC
Table continues on next page
1MRK 502 071-UEN -
Section 1
Introduction
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
27
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
BUSPTRC_B23
BUSPTRC
BUSPTRC
BUSPTRC_B24
BUSPTRC
BUSPTRC
BUTPTRC_B1
BUTPTRC
BBTPLLN0
BUTPTRC
BUTPTRC_B2
BUTPTRC
BUTPTRC
BUTPTRC_B3
BUTPTRC
BUTPTRC
BUTPTRC_B4
BUTPTRC
BUTPTRC
BUTPTRC_B5
BUTPTRC
BUTPTRC
BUTPTRC_B6
BUTPTRC
BUTPTRC
BUTPTRC_B7
BUTPTRC
BUTPTRC
BUTPTRC_B8
BUTPTRC
BUTPTRC
BZISGGIO
BZISGGIO
BZISGAPC
BZITGGIO
BZITGGIO
BZITGAPC
BZNPDIF_Z1
BZNPDIF
BZNPDIF
BZNPDIF_Z2
BZNPDIF
BZNPDIF
BZNPDIF_Z3
BZNPDIF
BZNPDIF
BZNPDIF_Z4
BZNPDIF
BZNPDIF
BZNPDIF_Z5
BZNPDIF
BZNPDIF
BZNPDIF_Z6
BZNPDIF
BZNPDIF
BZNSPDIF_A
BZNSPDIF
BZASGAPC
BZASPDIF
BZNSGAPC
BZNSPDIF
BZNSPDIF_B
BZNSPDIF
BZBSGAPC
BZBSPDIF
BZNSGAPC
BZNSPDIF
BZNTPDIF_A
BZNTPDIF
BZATGAPC
BZATPDIF
BZNTGAPC
BZNTPDIF
BZNTPDIF_B
BZNTPDIF
BZBTGAPC
BZBTPDIF
BZNTGAPC
BZNTPDIF
CBPGAPC
CBPLLN0
CBPMMXU
CBPPTRC
HOLPTOV
HPH1PTOV
PH3PTUC
PH3PTOC
RP3PDOP
CBPMMXU
CBPPTRC
HOLPTOV
HPH1PTOV
PH3PTOC
PH3PTUC
RP3PDOP
CCPDSC
CCRPLD
CCPDSC
CCRBRF
CCRBRF
CCRBRF
CCRWRBRF
CCRWRBRF
CCRWRBRF
CCSRBRF
CCSRBRF
CCSRBRF
Table continues on next page
Section 1
1MRK 502 071-UEN -
Introduction
28
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
CCSSPVC
CCSRDIF
CCSSPVC
CMMXU
CMMXU
CMMXU
CMSQI
CMSQI
CMSQI
COUVGAPC
COUVLLN0
COUVPTOV
COUVPTUV
COUVPTOV
COUVPTUV
CVGAPC
GF2LLN0
GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC
GF2MMXN
GF2PHAR
GF2PTOV
GF2PTUC
GF2PTUV
GF2PVOC
PH1PTRC
CVMMXN
CVMMXN
CVMMXN
D2PTOC
D2LLN0
D2PTOC
PH1PTRC
D2PTOC
PH1PTRC
DPGAPC
DPGGIO
DPGAPC
DRPRDRE
DRPRDRE
DRPRDRE
ECPSCH
ECPSCH
ECPSCH
ECRWPSCH
ECRWPSCH
ECRWPSCH
EF2PTOC
EF2LLN0
EF2PTRC
EF2RDIR
GEN2PHAR
PH1PTOC
EF2PTRC
EF2RDIR
GEN2PHAR
PH1PTOC
EF4PTOC
EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC
EFPIOC
EFPIOC
EFPIOC
EFRWPIOC
EFRWPIOC
EFRWPIOC
ETPMMTR
ETPMMTR
ETPMMTR
FDPSPDIS
FDPSPDIS
FDPSPDIS
FMPSPDIS
FMPSPDIS
FMPSPDIS
FRPSPDIS
FPSRPDIS
FPSRPDIS
FTAQFVR
FTAQFVR
FTAQFVR
FUFSPVC
SDDRFUF
FUFSPVC
SDDSPVC
GENPDIF
GENPDIF
GENGAPC
GENPDIF
GENPHAR
GENPTRC
GOPPDOP
GOPPDOP
GOPPDOP
PH1PTRC
GRPTTR
GRPTTR
GRPTTR
GSPTTR
GSPTTR
GSPTTR
Table continues on next page
1MRK 502 071-UEN -
Section 1
Introduction
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
29
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
GUPPDUP
GUPPDUP
GUPPDUP
PH1PTRC
HZPDIF
HZPDIF
HZPDIF
INDCALCH
INDCALH
INDCALH
ITBGAPC
IB16FCVB
ITBGAPC
L3CPDIF
L3CPDIF
L3CGAPC
L3CPDIF
L3CPHAR
L3CPTRC
L4CPDIF
L4CLLN0
L4CPDIF
L4CPTRC
LLN0
L4CGAPC
L4CPDIF
L4CPSCH
L4CPTRC
L4UFCNT
L4UFCNT
L4UFCNT
L6CPDIF
L6CPDIF
L6CGAPC
L6CPDIF
L6CPHAR
L6CPTRC
LAPPGAPC
LAPPLLN0
LAPPPDUP
LAPPPUPF
LAPPPDUP
LAPPPUPF
LCCRPTRC
LCCRPTRC
LCCRPTRC
LCNSPTOC
LCNSPTOC
LCNSPTOC
LCNSPTOV
LCNSPTOV
LCNSPTOV
LCP3PTOC
LCP3PTOC
LCP3PTOC
LCP3PTUC
LCP3PTUC
LCP3PTUC
LCPTTR
LCPTTR
LCPTTR
LCZSPTOC
LCZSPTOC
LCZSPTOC
LCZSPTOV
LCZSPTOV
LCZSPTOV
LD0LLN0
LLN0
-
LDLPSCH
LDLPDIF
LDLPSCH
LDRGFC
STSGGIO
LDRGFC
LEXPDIS
LEXPDIS
LEXPDIS
LEXPTRC
LFPTTR
LFPTTR
LFPTTR
LMBRFLO
LMBRFLO
LMBRFLO
LOLSPTR
LOLSPTR
LOLSPTR
LOVPTUV
LOVPTUV
LOVPTUV
LPHD
LPHD
LPTTR
LPTTR
LPTTR
LT3CPDIF
LT3CPDIF
LT3CGAPC
LT3CPDIF
LT3CPHAR
LT3CPTRC
Table continues on next page
Section 1
1MRK 502 071-UEN -
Introduction
30
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
LT6CPDIF
LT6CPDIF
LT6CGAPC
LT6CPDIF
LT6CPHAR
LT6CPTRC
MVGAPC
MVGGIO
MVGAPC
NS2PTOC
NS2LLN0
NS2PTOC
NS2PTRC
NS2PTOC
NS2PTRC
NS4PTOC
EF4LLN0
EF4PTRC
EF4RDIR
GEN4PHAR
PH1PTOC
EF4PTRC
EF4RDIR
PH1PTOC
O2RWPTOV
GEN2LLN0
O2RWPTOV
PH1PTRC
O2RWPTOV
PH1PTRC
OC4PTOC
OC4LLN0
GEN4PHAR
PH3PTOC
PH3PTRC
GEN4PHAR
PH3PTOC
PH3PTRC
OEXPVPH
OEXPVPH
OEXPVPH
OOSPPAM
OOSPPAM
OOSPPAM
OOSPTRC
OV2PTOV
GEN2LLN0
OV2PTOV
PH1PTRC
OV2PTOV
PH1PTRC
PAPGAPC
PAPGAPC
PAPGAPC
PCFCNT
PCGGIO
PCFCNT
PH4SPTOC
GEN4PHAR
OCNDLLN0
PH1BPTOC
PH1PTRC
GEN4PHAR
PH1BPTOC
PH1PTRC
PHPIOC
PHPIOC
PHPIOC
PSLPSCH
ZMRPSL
PSLPSCH
PSPPPAM
PSPPPAM
PSPPPAM
PSPPTRC
QCBAY
QCBAY
BAY/LLN0
QCRSV
QCRSV
QCRSV
RCHLCCH
RCHLCCH
RCHLCCH
REFPDIF
REFPDIF
REFPDIF
ROTIPHIZ
ROTIPHIZ
ROTIPHIZ
ROTIPTRC
ROV2PTOV
GEN2LLN0
PH1PTRC
ROV2PTOV
PH1PTRC
ROV2PTOV
SAPFRC
SAPFRC
SAPFRC
SAPTOF
SAPTOF
SAPTOF
SAPTUF
SAPTUF
SAPTUF
SCCVPTOC
SCCVPTOC
SCCVPTOC
Table continues on next page
1MRK 502 071-UEN -
Section 1
Introduction
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
31
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
SCHLCCH
SCHLCCH
SCHLCCH
SCILO
SCILO
SCILO
SCSWI
SCSWI
SCSWI
SDEPSDE
SDEPSDE
SDEPSDE
SDEPTOC
SDEPTOV
SDEPTRC
SESRSYN
RSY1LLN0
AUT1RSYN
MAN1RSYN
SYNRSYN
AUT1RSYN
MAN1RSYN
SYNRSYN
SLGAPC
SLGGIO
SLGAPC
SMBRREC
SMBRREC
SMBRREC
SMPPTRC
SMPPTRC
SMPPTRC
SP16GAPC
SP16GGIO
SP16GAPC
SPC8GAPC
SPC8GGIO
SPC8GAPC
SPGAPC
SPGGIO
SPGAPC
SSCBR
SSCBR
SSCBR
SSIMG
SSIMG
SSIMG
SSIML
SSIML
SSIML
STBPTOC
STBPTOC
BBPMSS
STBPTOC
STEFPHIZ
STEFPHIZ
STEFPHIZ
STTIPHIZ
STTIPHIZ
STTIPHIZ
SXCBR
SXCBR
SXCBR
SXSWI
SXSWI
SXSWI
T2WPDIF
T2WPDIF
T2WGAPC
T2WPDIF
T2WPHAR
T2WPTRC
T3WPDIF
T3WPDIF
T3WGAPC
T3WPDIF
T3WPHAR
T3WPTRC
TCLYLTC
TCLYLTC
TCLYLTC
TCSLTC
TCMYLTC
TCMYLTC
TCMYLTC
TEIGAPC
TEIGGIO
TEIGAPC
TEIGGIO
TEILGAPC
TEILGGIO
TEILGAPC
TMAGAPC
TMAGGIO
TMAGAPC
TPPIOC
TPPIOC
TPPIOC
TR1ATCC
TR1ATCC
TR1ATCC
TR8ATCC
TR8ATCC
TR8ATCC
TRPTTR
TRPTTR
TRPTTR
Table continues on next page
Section 1
1MRK 502 071-UEN -
Introduction
32
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
U2RWPTUV
GEN2LLN0
PH1PTRC
U2RWPTUV
PH1PTRC
U2RWPTUV
UV2PTUV
GEN2LLN0
PH1PTRC
UV2PTUV
PH1PTRC
UV2PTUV
VDCPTOV
VDCPTOV
VDCPTOV
VDSPVC
VDRFUF
VDSPVC
VMMXU
VMMXU
VMMXU
VMSQI
VMSQI
VMSQI
VNMMXU
VNMMXU
VNMMXU
VRPVOC
VRLLN0
PH1PTRC
PH1PTUV
VRPVOC
PH1PTRC
PH1PTUV
VRPVOC
VSGAPC
VSGGIO
VSGAPC
WRNCALH
WRNCALH
WRNCALH
ZC1PPSCH
ZPCPSCH
ZPCPSCH
ZC1WPSCH
ZPCWPSCH
ZPCWPSCH
ZCLCPSCH
ZCLCPLAL
ZCLCPSCH
ZCPSCH
ZCPSCH
ZCPSCH
ZCRWPSCH
ZCRWPSCH
ZCRWPSCH
ZCVPSOF
ZCVPSOF
ZCVPSOF
ZGVPDIS
ZGVLLN0
PH1PTRC
ZGVPDIS
ZGVPTUV
PH1PTRC
ZGVPDIS
ZGVPTUV
ZMCAPDIS
ZMCAPDIS
ZMCAPDIS
ZMCPDIS
ZMCPDIS
ZMCPDIS
ZMFCPDIS
ZMFCLLN0
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU
ZMFPDIS
ZMFLLN0
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU
PSFPDIS
PSFPDIS
ZMFPDIS
ZMFPTRC
ZMMMXU
ZMHPDIS
ZMHPDIS
ZMHPDIS
ZMMAPDIS
ZMMAPDIS
ZMMAPDIS
ZMMPDIS
ZMMPDIS
ZMMPDIS
ZMQAPDIS
ZMQAPDIS
ZMQAPDIS
ZMQPDIS
ZMQPDIS
ZMQPDIS
ZMRAPDIS
ZMRAPDIS
ZMRAPDIS
Table continues on next page
1MRK 502 071-UEN -
Section 1
Introduction
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
33
Application manual
Function block name
Edition 1 logical nodes
Edition 2 logical nodes
ZMRPDIS
ZMRPDIS
ZMRPDIS
ZMRPSB
ZMRPSB
ZMRPSB
ZSMGAPC
ZSMGAPC
ZSMGAPC
Section 1
1MRK 502 071-UEN -
Introduction
34
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
General IED application
The REG670 is used for protection, control and monitoring of generators and
generator-transformer blocks from relatively small units up to the largest generating
units. The IED has a comprehensive function library, covering the requirements for
most generator applications. The large number of analog inputs available enables,
together with the large functional library, integration of many functions in one IED. In
typical applications two IED units can provide total functionality, also providing a
high degree of redundancy. REG670 can as well be used for protection and control of
shunt reactors.
Stator earth fault protection, both traditional 95% as well as 100% injection and 3rd
harmonic based are included. When the injection based protection is used, 100% of the
machine stator winding, including the star point, is protected under all operating
modes. The 3rd harmonic based 100% stator earth fault protection uses 3rd harmonic
differential voltage principle. Injection based 100% stator earth fault protection can
operate even when machine is at standstill. Well proven algorithms for pole slip,
underexcitation, rotor earth fault, negative sequence current protections, and so on,
are included in the IED.
The generator differential protection in the REG670 adapted to operate correctly for
generator applications where factors as long DC time constants and requirement on
short trip time have been considered.
As many of the protection functions can be used as multiple instances there are
possibilities to protect more than one object in one IED. It is possible to have
protection for an auxiliary power transformer integrated in the same IED having main
protections for the generator. The concept thus enables very cost effective solutions.
The REG670 also enables valuable monitoring possibilities as many of the process
values can be transferred to an operator HMI.
The wide application flexibility makes this product an excellent choice for both new
installations and for refurbishment in existing power plants.
Forcing of binary inputs and outputs is a convenient way to test wiring in substations
as well as testing configuration logic in the IEDs. Basically it means that all binary
inputs and outputs on the IED I/O modules (BOM, BIM, IOM & SOM) can be forced
to arbitrary values.
Central Account Management is an authentication infrastructure that offers a secure
solution for enforcing access control to IEDs and other systems within a substation.
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
35
Application manual
This incorporates management of user accounts, roles and certificates and the
distribution of such, a procedure completely transparent to the user.
The Flexible Product Naming allows the customer to use an IED-vendor independent
IEC 61850 model of the IED. This customer model will be exposed in all IEC 61850
communication, but all other aspects of the IED will remain unchanged (e.g., names
on the local HMI and names in the tools). This offers significant flexibility to adapt the
IED to the customers' system and standard solution.
Communication via optical connections ensures immunity against disturbances.
By using patented algorithm REG670 (or any other product from 670 series) can track
the power system frequency in quite wide range from 9Hz to 95Hz (for 50Hz power
system). In order to do that preferably the three-phase voltage signal from the
generator terminals shall be connected to the IED. Then IED can adopt its filtering
algorithm in order to properly measure phasors of all current and voltage signals
connected to the IED. This feature is essential for proper operation of the protection
during generator start-up and shut-down procedure.
REG670 can be used in applications with the IEC/UCA 61850-9-2LE process bus
with up to eight merging units (MU) depending on the other functionality included in
the IED.
This adaptive filtering is ensured by proper configuration and settings of all relevant
pre-processing blocks, see figure 344 and 345. Note that in all pre-configured
REG670 IEDs such configuration and settings are already made and that three-phase
voltage at the generator terminals are used for frequency tracking. With such settings
REG670 will be able to properly estimate the magnitude and the phase angle of
measured current and voltage phasors in this wide frequency range.
Note that the following functions will then operate properly in the whole frequency
interval:
•
Generator differential
•
Transformer differential
•
Four step overcurrent protection (DFT based measurement)
•
Four step residual overcurrent protection
•
Over/under voltage protection (DFT based measurement)
•
Residual overvoltage protection
•
Overexcitation protection
•
General current and voltage protection
•
Directional over/under power function
•
Measurement function (that is, MMXU)
•
and so on
Note that during secondary injection testing of this feature, it is absolutely necessary
to also inject the voltage signals used for frequency tracking even when a simple
overcurrent protection is tested.
Section 2
1MRK 502 071-UEN -
Application
36
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
If protection for lower frequencies than 9Hz is required (for example, for pump-
storage schemes) four step overcurrent protection with RMS measurement shall be
used. This function is able to operate for current signals within frequency range from
1Hz up to 100Hz and it is not at all dependent on any voltage signal. Its pickup for very
low frequency is only determined by main CT capability to transfer low frequency
current signal to the secondary side. However it shall be noted that during such low
frequency conditions this function will react on the measured current peak values
instead of usual RMS value and that its operation shall be instantaneous (that is,
without any intentional time delay). Function can be used either as normal overcurrent
function or even as generator differential function when currents from two generator
sides are summed and connected to the four step overcurrent function. Typically for
such installations dedicated overcurrent steps are used during such low frequency
conditions while some other overcurrent steps with different setting for pickup value
and time delay are used during normal machine operation. Such logic can be easily
arranged in REG670 application configuration tool.
Four step overcurrent protection with RMS measurement shall also be used as
machine overcurrent and differential protection during electrical braking. During
such operating condition intentional three-phase short-circuit is made at the machine
terminal. This will effectively force voltages at the machine terminal to zero and
effectively disabled voltage based frequency tracking in REG670. Similar logic as
described for pump-storage scheme above can be used.
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
37
Application manual
REG 670 2.0
ZGV PDIS
21
Z<
LEX PDIS
40
<
GUP PDUP
37
P<
GOP PDOP
32
P
ROV2 PTOV
59N
3Uo>
OC4 PTOC
51/67
3I->
CC RBRF
50BF 3I> BF
NS2 PTOC
46
I2>
TR PTTR
49
Ith
PSP PPAM
78
Ucos
+ REX060, REX061
AEG PVOC
50AE
U/I>
CV MMXU
Meter.
ROV2 PTOV
59N
UN>
ROTI PHIZ
64R
RRE<
STTI PHIZ
64S
RSE<
+ REX060
ROV2 PTOV
59N
3Uo>
VT
Y
Y
D
IEC11000201 V2 EN
Figure 2:
Generator protection application with generator differential, 100%
stator earth fault and back-up protection
Section 2
1MRK 502 071-UEN -
Application
38
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
REG 670 2.0
ZGV PDIS
21
Z<
LEX PDIS
40
<
GUP PDUP
37
P<
GOP PDOP
32
P
ROV2 PTOV
59N
3Uo>
OC4 PTOC
51/67
3I->
CC RBRF
50BF 3I> BF
NS2 PTOC
46
I2>
PSP PPAM
78
Ucos
+ REX060, REX061
AEG PVOC
50AE
U/I>
CV MMXU
Meter.
ROTI PHIZ
64R
RRE<
STTI PHIZ
64S
RSE<
+ REX060
ROV2 PTOV
59N
3Uo>
VT
EF4 PTOC
64W
IN>
Y
Y
S
D
IEC11000204 V2 EN
Figure 3:
Generator protection application for generator with split winding
including generator phase differential, 100% stator earth fault and
back-up protection
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
39
Application manual
REG 670 2.0
ZGV PDIS
21
Z<
LEX PDIS
40
<
GUP PDUP
37
P<
GOP PDOP
32
P
ROV2 PTOV
59N
3Uo>
OC4 PTOC
51/67
3I->
CC RBRF
50BF 3I> BF
NS2 PTOC
46
I2>
PSP PPAM
78
Ucos
+ REX060, REX061
AEG PVOC
50AE
U/I>
CV MMXU
Meter.
ROV2 PTOV
59N
UN>
ROTI PHIZ
64R
RRE<
VT
EF4 PTOC
64W
IN>
Y
Y
STTI PHIZ
64S
RSE<
+ REX060
VT
GEN PDIF
87W
3Id/I
D
S
IEC11000206 V2 EN
Figure 4:
Generator protection application for generator with split winding
including generator phase differential, generator split-phase
differential, 100% stator earth fault and back-up protection
Section 2
1MRK 502 071-UEN -
Application
40
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
REG 670 2.0
ZGV PDIS
21
Z<
LEX PDIS
40
<
GUP PDUP
37
P<
GOP PDOP
32
P
OC4 PTOC
51/67
3I->
CC RBRF
50BF 3I> BF
NS2 PTOC
46
I2>
TR PTTR
49
Ith
PSP PPAM
78
Ucos
AEG PVOC
50AE
U/I>
STEF PHIZ
59THD U3d/N
Auxiliary Bus
OC4 PTOC
50/51
3I>
OC4 PTOC
50/51
3I>
CC RBRF
50BF 3I> BF
OC4 PTOC
50/51
3I>
ROV2 PTOV
59N
3Uo>
T3W PDIF
87T
3Id/I
CV MMXU
Meter.
OEX PVPH
24
U/f>
UV2 PTUV
27
3U<
OV2 PTOV
59
3U>
ROV2 PTOV
59N
3Uo>
+ REX060, REX061
STTI PHIZ
64S
RSE<
ROTI PHIZ
64R
RRE<
+ REX060, REX062
Y
Y
Y
Unit Trafo
Auxiliary Trafo
Excitation Trafo
Y
Y
Grounding
Transformer
D
D
D
IEC11000202 V2 EN
Figure 5:
Unit protection application with overall differential, generator
differential, 100% stator earth fault and back-up protection. Stator
winding grounded via grounding transformer.
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
41
Application manual
REG 670 2.0
T2W PDIF
87T
3Id/I
ROV2 PTOV
59N
3Uo>
NS2 PTOC
46
I2>
TR PTTR
49
Ith
FUFSPVC
60FL
ZGV PDIS
21
Z<
LEX PDIS
40
<
GUP PDUP
37
P<
GOP PDOP
32
P
PSP PPAM
78
Ucos
SA PTOF
81
f>
OEX PVPH
24
U/f>
UV2 PTUV
27
3U<
OV2 PTOV
59
3U>
OC4 PTOC
50/51
3I>
OC4 PTOC
50/51
3I>
CC RBRF
50BF 3I> BF
GEN PDIF
87G
3Id/I
ROV2 PTOV
59N
UN>
CC RBRF
50BF 3I> BF
OC4 PTOC
51/67
3I->
AEG PVOC
50AE
U/I>
CV MMXU
Meter.
+ REX060, REX061
STTI PHIZ
64S
RSE<
ROTI PHIZ
64R
RRE<
+ REX060
CV MMXU
Meter.
Y
Y
Y
Y
Y
Unit Trafo
VT
D
D
D
IEC11000203 V2 EN
Figure 6:
Unit protection application with overall differential, unit transformer
differential, generator differential, 100% stator earth fault and back-
up protection. Ungrounded stator winding.
Section 2
1MRK 502 071-UEN -
Application
42
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
REG 670 2.0
T2W PDIF
87T
3Id/I
ROV2 PTOV
59N
3Uo>
NS2 PTOC
46
I2>
TR PTTR
49
Ith
FUFSPVC
60FL
ZGV PDIS
21
Z<
LEX PDIS
40
<
GUP PDUP
37
P<
GOP PDOP
32
P
PSP PPAM
78
Ucos
SA PTOF
81
f>
OEX PVPH
24
U/f>
UV2 PTUV
27
3U<
OV2 PTOV
59
3U>
OC4 PTOC
50/51
3I>
OC4 PTOC
50/51
3I>
CC RBRF
50BF 3I> BF
GEN PDIF
87G
3Id/I
CC RBRF
50BF 3I> BF
OC4 PTOC
51/67
3I->
AEG PVOC
50AE
U/I>
CV MMXU
Meter.
+ REX060, REX061
STTI PHIZ
64S
RSE<
ROTI PHIZ
64R
RRE<
+ REX060
CV MMXU
Meter.
Y
Y
Y
Y
Y
Unit Trafo
ROV2 PTOV
59N
3Uo>
VT
IEC11000207-2-en.vsd
D
D
D
IEC11000207 V2 EN
Figure 7:
Unit protection application with overall differential, unit transformer
differential, generator differential, 100% stator earth fault and back-
up protection. Stator winding grounded via primary resistor.
The following tables list all the functions available in the IED. Those
functions that are not exposed to the user or do not need to be
configured are not described in this manual.
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
43
Application manual
Main protection functions
Table 2:
Example of quantities
2
= number of basic instances
0-3
= option quantities
3-A03
= optional function included in packages A03 (refer to ordering details)
IEC 61850 or
function name
ANSI
Function description
Generator
REG670 (Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
Differential protection
T2WPDIF
87T
Transformer differential protection,
two winding
0-2
1-A31
1-A33
1
T3WPDIF
87T
Transformer differential protection,
three winding
0-2
1-A33
1
HZPDIF
87
High impedance differential
protection, single phase
0-6
3-A02
3
6
GENPDIF
87G
Generator differential protection
0-2
1
2
2
REFPDIF
87N
Restricted earth fault protection, low
impedance
0-3
1-A01
1
Impedance protection
ZMHPDIS
21
Full-scheme distance protection,
mho characteristic
0-4
3
3
3
ZDMRDIR
21D
Directional impedance element for
mho characteristic
0-2
1
1
1
ZMFPDIS
21
High speed distance protection,
quad and mho characteristic
0-1
ZMFCPDIS
21
High speed distance protection for
series comp. lines, quad and mho
characteristic
0-1
PSPPPAM
78
Poleslip/out-of-step protection
0-1
1-B22
1-B22
1-B22
OOSPPAM
78
Out-of-step protection
0-1
1-B22
1-B22
1-B22
LEXPDIS
40
Loss of excitation
0-2
1
2
2
ROTIPHIZ
64R
Sensitive rotor earth fault protection,
injection based
0-1
1-B31
1-B31
1-B31
STTIPHIZ
64S
100% stator earth fault protection,
injection based
0-1
1-B32
1-B32
1-B32
ZGVPDIS
21
Underimpedance protection for
generators and transformers
0–2
1
1
1
Section 2
1MRK 502 071-UEN -
Application
44
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Back-up protection functions
IEC 61850 or
function name
ANSI
Function description
Generator
REG670 (Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
Current protection
PHPIOC
50
Instantaneous phase overcurrent
protection
0-4
1
2
2
OC4PTOC
51_671)
Directional phase overcurrent
protection, four steps
0-6
4
4
4
EFPIOC
50N
Instantaneous residual overcurrent
protection
0-2
1
2
2
EF4PTOC
51N
67N2)
Directional residual overcurrent
protection, four steps
0-6
1
5
5
NS4PTOC
46I2
Four step directional negative
phase sequence overcurrent
protection
0-2
1-C41
2-C42
2-C42
SDEPSDE
67N
Sensitive directional residual
overcurrent and power protection
0-2
1-C16
1-C16
1-C16
TRPTTR
49
Thermal overload protection, two
time constants
0-3
1
2
3
CCRBRF
50BF
Breaker failure protection
0-4
2
4
4
CCPDSC
52PD
Pole discordance protection
0-4
2
4
4
GUPPDUP
37
Directional underpower protection
0-4
2
4
4
GOPPDOP
32
Directional overpower protection
0-4
2
4
4
NS2PTOC
46I2
Negative sequence time
overcurrent protection for
machines
0-2
1
1
1
AEGPVOC
50AE
Accidental energizing protection
for synchronous generator
0-2
1
1
1
VRPVOC
51V
Voltage restrained overcurrent
protection
0-3
3-C36
3-C36
3-C36
GSPTTR
49S
Stator overload protection
0-1
1
1
1
GRPTTR
49R
Rotor overload protection
0-1
1-C38
1-C38
1-C38
Voltage protection
UV2PTUV
27
Two step undervoltage protection
0-2
2
2
2
OV2PTOV
59
Two step overvoltage protection
0-2
2
2
2
ROV2PTOV
59N
Two step residual overvoltage
protection
0-3
3
3
3
OEXPVPH
24
Overexcitation protection
0-2
1
1
2
Table continues on next page
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
45
Application manual
IEC 61850 or
function name
ANSI
Function description
Generator
REG670 (Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
VDCPTOV
60
Voltage differential protection
0-2
2
2
2
STEFPHIZ
59THD
100% stator earth fault protection,
3rd harmonic based
0-1
1-D21
1
1
Frequency protection
SAPTUF
81
Underfrequency protection
0-6
3
6
6
SAPTOF
81
Overfrequency protection
0-6
3
6
6
SAPFRC
81
Rate-of-change of frequency
protection
0-6
1
3
3
FTAQFVR
81A
Frequency time accumulation
protection
0-12
12-E03
12-E03
12-E03
Multipurpose protection
CVGAPC
General current and voltage
protection
0-9
6
6
6
General calculation
SMAIHPAC
Multipurpose filter
0-6
1)
67 requires voltage
2)
67N requires voltage
2.4
Control and monitoring functions
IEC 61850 or
function name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
Control
SESRSYN
25
Synchrocheck, energizing check and
synchronizing
0-2
1
2
2
APC30
3
Control functionality for up to 6 bays,
max 30 objects (6CBs), including
interlocking (see Table 4)
0-1
1-H39
1-H39
1-H39
QCBAY
Bay control
1+5/APC30
1+5/
APC3
0
1+5/
APC3
0
1+5/
APC3
0
Table continues on next page
Section 2
1MRK 502 071-UEN -
Application
46
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC 61850 or
function name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
LOCREM
Handling of LR-switch positions
1+5/APC30
1+5/
APC3
0
1+5/
APC3
0
1+5/
APC3
0
LOCREMCTRL
LHMI control of PSTO
1
1
1
1
SXCBR
Circuit breaker
18
18
18
18
TCMYLTC
84
Tap changer control and supervision,
6 binary inputs
0-4
1-A31
2-A33
2
TCLYLTC
84
Tap changer control and supervision,
32 binary inputs
0-4
SLGAPC
Logic rotating switch for function
selection and LHMI presentation
15
15
15
15
VSGAPC
Selector mini switch
30
30
30
30
DPGAPC
Generic communication function for
Double Point indication
16
16
16
16
SPC8GAPC
Single point generic control function 8
signals
5
5
5
5
AUTOBITS
Automation bits, command function for
DNP3.0
3
3
3
3
SINGLECMD
Single command, 16 signals
4
4
4
4
I103CMD
Function commands for IEC
60870-5-103
1
1
1
1
I103GENCMD
Function commands generic for IEC
60870-5-103
50
50
50
50
I103POSCMD
IED commands with position and
select for IEC 60870-5-103
50
50
50
50
I103POSCMDV
IED direct commands with position for
IEC 60870-5-103
50
50
50
50
I103IEDCMD
IED commands for IEC 60870-5-103
1
1
1
1
I103USRCMD
Function commands user defined for
IEC 60870-5-103
4
4
4
4
Secondary system
supervision
CCSSPVC
87
Current circuit supervision
0-5
4
5
5
FUFSPVC
Fuse failure supervision
0-3
2
3
3
VDSPVC
60
Fuse failure supervision based on
voltage difference
0-2
1-G03
1-G03
1-G03
Logic
SMPPTRC
94
Tripping logic
12
12
12
12
SMAGAPC
General start matrix block
12
12
12
12
STARTCOMB
Start combinator
32
32
32
32
TMAGAPC
Trip matrix logic
12
12
12
12
Table continues on next page
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
47
Application manual
IEC 61850 or
function name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
ALMCALH
Logic for group alarm
5
5
5
5
WRNCALH
Logic for group warning
5
5
5
5
INDCALH
Logic for group indication
5
5
5
5
AND, GATE, INV,
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
Basic configurable logic blocks (see
Table 3)
40-420
40-42
0
40-42
0
40-42
0
ANDQT,
INDCOMBSPQT,
INDEXTSPQT,
INVALIDQT,
INVERTERQT,
ORQT,
PULSETIMERQT,
RSMEMORYQT,
SRMEMORYQT,
TIMERSETQT,
XORQT
Configurable logic blocks Q/T (see
Table 5)
0-1
AND, GATE, INV,
LLD, OR,
PULSETIMER,
RSMEMORY,
SLGAPC,
SRMEMORY,
TIMERSET,
VSGAPC, XOR
Extension logic package (see Table 6)
0-1
FXDSIGN
Fixed signal function block
1
1
1
1
B16I
Boolean to integer conversion, 16 bit
18
18
18
18
BTIGAPC
Boolean to integer conversion with
logical node representation, 16 bit
16
16
16
16
IB16
Integer to Boolean 16 conversion
18
18
18
18
ITBGAPC
Integer to Boolean 16 conversion with
Logic Node representation
16
16
16
16
TIGAPC
Delay on timer with input signal
integration
30
30
30
30
TEIGAPC
Elapsed time integrator with limit
transgression and overflow
supervision
12
12
12
12
INTCOMP
Comparator for integer inputs
30
30
30
30
REALCOMP
Comparator for real inputs
30
30
30
30
Section 2
1MRK 502 071-UEN -
Application
48
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Total number of instances for basic configurable logic blocks
Basic configurable logic block
Total number of instances
AND
280
GATE
40
INV
420
LLD
40
OR
298
PULSETIMER
40
RSMEMORY
40
SRMEMORY
40
TIMERSET
60
XOR
40
Table 4:
Number of function instances in APC30
Function name
Function description
Total number of instances
SCILO
Interlocking
30
BB_ES
6
A1A2_BS
4
A1A2_DC
6
ABC_BC
2
BH_CONN
2
BH_LINE_A
2
BH_LINE_B
2
DB_BUS_A
3
DB_BUS_B
3
DB_LINE
3
ABC_LINE
6
AB_TRAFO
4
SCSWI
Switch controller
30
SXSWI
Circuit switch
24
QCRSV
Apparatus control
6
RESIN1
1
RESIN2
59
POS_EVAL
Evaluation of position indication
30
QCBAY
Bay control
5
LOCREM
Handling of LR-switch positions
5
XLNPROXY
Proxy for signals from switching
device via GOOSE
42
GOOSEXLNRCV
GOOSE function block to
receive a switching device
42
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
49
Application manual
Total number of instances for configurable logic blocks Q/T
Configurable logic blocks Q/T
Total number of instances
ANDQT
120
INDCOMBSPQT
20
INDEXTSPQT
20
INVALIDQT
22
INVERTERQT
120
ORQT
120
PULSETIMERQT
40
RSMEMORYQT
40
SRMEMORYQT
40
TIMERSETQT
40
XORQT
40
Table 6:
Total number of instances for extended logic package
Extended configurable logic block
Total number of instances
AND
180
GATE
49
INV
180
LLD
49
OR
180
PULSETIMER
89
RSMEMORY
40
SLGAPC
74
SRMEMORY
130
TIMERSET
109
VSGAPC
120
XOR
89
IEC 61850 or
function name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
Monitoring
CVMMXN
Power system measurement
6
6
6
6
CMMXU
Current measurement
10
10
10
10
VMMXU
Voltage measurement phase-phase
6
6
6
6
CMSQI
Current sequence measurement
6
6
6
6
Table continues on next page
Section 2
1MRK 502 071-UEN -
Application
50
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC 61850 or
function name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
VMSQI
Voltage sequence measurement
6
6
6
6
VNMMXU
Voltage measurement phase-earth
6
6
6
6
AISVBAS
General service value presentation of
analog inputs
1
1
1
1
EVENT
Event function
20
20
20
20
DRPRDRE,
A1RADR-
A4RADR,
B1RBDR-
B22RBDR
Disturbance report
1
1
1
1
SPGAPC
Generic communication function for
Single Point indication
64
64
64
64
SP16GAPC
Generic communication function for
Single Point indication 16 inputs
16
16
16
16
MVGAPC
Generic communication function for
measured values
24
24
24
24
BINSTATREP
Logical signal status report
3
3
3
3
RANGE_XP
Measured value expander block
66
66
66
66
SSIMG
63
Insulation supervision for gas medium
21
21
21
21
SSIML
71
Insulation supervision for liquid
medium
3
3
3
3
SSCBR
Circuit breaker condition monitoring
0-12
6
12
12
LOLSPTR
26/49
HS
Transformer insulation loss of life
monitoring
0-4
4-M21
4-M21
I103MEAS
Measurands for IEC 60870-5-103
1
1
1
1
I103MEASUSR
Measurands user defined signals for
IEC 60870-5-103
3
3
3
3
I103AR
Function status auto-recloser for IEC
60870-5-103
1
1
1
1
I103EF
Function status earth-fault for IEC
60870-5-103
1
1
1
1
I103FLTPROT
Function status fault protection for IEC
60870-5-103
1
1
1
1
I103IED
IED status for IEC 60870-5-103
1
1
1
1
I103SUPERV
Supervison status for IEC
60870-5-103
1
1
1
1
I103USRDEF
Status for user defined signals for IEC
60870-5-103
20
20
20
20
L4UFCNT
Event counter with limit supervision
30
30
30
30
TEILGAPC
Running hour meter
6
6
6
6
Table continues on next page
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
51
Application manual
IEC 61850 or
function name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
Metering
PCFCNT
Pulse-counter logic
16
16
16
16
ETPMMTR
Function for energy calculation and
demand handling
6
6
6
6
2.5
Communication
IEC 61850 or function
name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
Station communication
LONSPA, SPA
SPA communication protocol
1
1
1
1
ADE
LON communication protocol
1
1
1
1
HORZCOMM
Network variables via LON
1
1
1
1
RS485GEN
RS485
1
1
1
1
DNPGEN
DNP3.0 communication general
protocol
1
1
1
1
CHSERRS485
DNP3.0 for EIA-485 communication
protocol
1
1
1
1
CH1TCP, CH2TCP,
CH3TCP, CH4TCP
DNP3.0 for TCP/IP communication
protocol
1
1
1
1
CHSEROPT
DNP3.0 for TCP/IP and EIA-485
communication protocol
1
1
1
1
MSTSER
DNP3.0 serial master
1
1
1
1
MST1TCP,
MST2TCP,
MST3TCP,
MST4TCP
DNP3.0 for TCP/IP communication
protocol
1
1
1
1
DNPFREC
DNP3.0 fault records for TCP/IP and
EIA-485 communication protocol
1
1
1
1
IEC 61850-8-1
IEC 61850
1
1
1
1
GOOSEINTLKRCV
Horizontal communication via
GOOSE for interlocking
59
59
59
59
GOOSEBINRCV
GOOSE binary receive
16
16
16
16
GOOSEDPRCV
GOOSE function block to receive a
double point value
64
64
64
64
Table continues on next page
Section 2
1MRK 502 071-UEN -
Application
52
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC 61850 or function
name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
GOOSEINTRCV
GOOSE function block to receive an
integer value
32
32
32
32
GOOSEMVRCV
GOOSE function block to receive a
measurand value
60
60
60
60
GOOSESPRCV
GOOSE function block to receive a
single point value
64
64
64
64
MULTICMDRCV,
MULTICMDSND
Multiple command and transmit
60/10
60/10
60/10
60/10
OPTICAL103
IEC 60870-5-103 Optical serial
communication
1
1
1
1
RS485103
IEC 60870-5-103 serial
communication for RS485
1
1
1
1
AGSAL
Generic security application
component
1
1
1
1
LD0LLN0
IEC 61850 LD0 LLN0
1
1
1
1
SYSLLN0
IEC 61850 SYS LLN0
1
1
1
1
LPHD
Physical device information
1
1
1
1
PCMACCS
IED configuration protocol
1
1
1
1
SECALARM
Component for mapping security
events on protocols such as DNP3
and IEC103
1
1
1
1
FSTACCS
Field service tool access
1
1
1
1
IEC 61850-9-2 Process bus
communication, 8 merging units
0-1
1-P30
1-P30
1-P30
ACTIVLOG
Activity logging
1
1
1
1
ALTRK
Service tracking
1
1
1
1
PRP
IEC 62439-3 Parallel redundancy
protocol
0-1
1-P23
1-P23
1-P23
HSR
IEC 62439-3 High-availability
seamless redundancy
0-1
1-P24
1-P24
1-P24
PMUCONF,
PMUREPORT,
PHASORREPORT1,
ANALOGREPORT1
BINARYREPORT1,
SMAI1 - SMAI12
3PHSUM
PMUSTATUS
Synchrophasor report, 16 phasors
(see Table 7)
0-1
1-P34
1-P34
1-P34
PTP
Precision time protocol
1
1
1
1
FRONTSTATUS
Access point diagnostic for front
Ethernet port
1
1
1
1
SCHLCCH
Access point diagnostic for non-
redundant Ethernet port
6
6
6
6
Table continues on next page
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
53
Application manual
IEC 61850 or function
name
ANSI
Function description
Generator
REG670
(Customized)
REG670 (A20)
REG670 (B30)
REG670 (C30)
RCHLCCH
Access point diagnostic for
redundant Ethernet ports
3
3
3
3
DHCP
DHCP configuration for front access
point
1
1
1
1
QUALEXP
IEC 61850 quality expander
96
96
96
96
Remote communication
BinSignRec1_1
BinSignRec1_2
BinSignReceive2
Binary signal transfer receive
3/3/6
3/3/6
3/3/6
3/3/6
BinSignTrans1_1
BinSignTrans1_2
BinSignTransm2
Binary signal transfer transmit
3/3/6
3/3/6
3/3/6
3/3/6
BinSigRec1_12M
BinSigRec1_22M
BinSigTran1_12M
BinSigTran1_22M
Binary signal transfer, 2Mbit receive/
transmit
3
3
3
3
LDCMTRN
Transmission of analog data from
LDCM
1
1
1
1
LDCMTRN_2M
Transmission of analog data from
LDCM, 2Mbit
6
6
6
6
LDCMRecBinStat1
LDCMRecBinStat2
LDCMRecBinStat3
Receive binary status from remote
LDCM
6/3/3
6/3/3
6/3/3
6/3/3
LDCMRecBinS2_2M
Receive binary status from LDCM,
2Mbit
3
3
3
3
LDCMRecBinS3_2M
Receive binary status from remote
LDCM, 2Mbit
3
3
3
3
Table 7:
Number of function instances in Synchrophasor report, 16 phasors
Function name
Function description
Number of instances
PMUCONF
Configuration parameters for C37.118 2011 and IEEE1344 protocol
1
PMUREPORT
Protocol reporting via IEEE 1344 and C37.118
2
PHASORREPORT1
Protocol reporting of phasor data via IEEE 1344 and C37.118, phasors 1-8
2
ANALOGREPORT1
Protocol reporting of analog data via IEEE 1344 and C37.118, analogs 1-8
2
BINARYREPORT1
Protocol reporting of binary data via IEEE 1344 and C37.118, binary 1-8
2
SMAI1–SMAI12
Signal matrix for analog inputs
1
3PHSUM
Summation block 3 phase
6
PMUSTATUS
Diagnostics for C37.118 2011 and IEEE1344 protocol
1
Section 2
1MRK 502 071-UEN -
Application
54
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Basic IED functions
Table 8:
Basic IED functions
IEC 61850 or function
name
Description
INTERRSIG
Self supervision with internal event list
TIMESYNCHGEN
Time synchronization module
BININPUT,
SYNCHCAN,
SYNCHGPS,
SYNCHCMPPS,
SYNCHLON,
SYNCHPPH,
SYNCHPPS, SNTP,
SYNCHSPA
Time synchronization
PTP
Precision time protocol
TIMEZONE
Time synchronization
IRIG-B
Time synchronization
SETGRPS
Number of setting groups
ACTVGRP
Parameter setting groups
TESTMODE
Test mode functionality
CHNGLCK
Change lock function
SMBI
Signal matrix for binary inputs
SMBO
Signal matrix for binary outputs
SMMI
Signal matrix for mA inputs
SMAI1 - SMAI12
Signal matrix for analog inputs
3PHSUM
Summation block 3 phase
ATHSTAT
Authority status
ATHCHCK
Authority check
AUTHMAN
Authority management
FTPACCS
FTP access with password
GBASVAL
Global base values for settings
ALTMS
Time master supervision
ALTIM
Time management
COMSTATUS
Protocol diagnostic
1MRK 502 071-UEN -
Section 2
Application
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
55
Application manual
Local HMI functions
IEC 61850 or function
name
ANSI
Description
LHMICTRL
Local HMI signals
LANGUAGE
Local human machine language
SCREEN
Local HMI Local human machine screen behavior
FNKEYTY1–FNKEYTY5
FNKEYMD1–
FNKEYMD5
Parameter setting function for HMI in PCM600
LEDGEN
General LED indication part for LHMI
OPENCLOSE_LED
LHMI LEDs for open and close keys
GRP1_LED1–
GRP1_LED15
GRP2_LED1–
GRP2_LED15
GRP3_LED1–
GRP3_LED15
Basic part for CP HW LED indication module
Section 2
1MRK 502 071-UEN -
Application
56
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Description of REG670
3.1.1
Introduction
3.1.1.1
Description of configuration A20
REG670 A20 configuration is used in applications where only generator protection
within one IED is required. REG670 A20 is always delivered in 1/2 of 19" case size.
Thus only 12 analogue inputs are available. This configuration includes generator low
impedance, differential protection and all other typically required generator
protection functions. Note that 100% stator earth fault function and Pole Slip
protection function are optional.
REG670 A20 functional library includes additional functions, which are not
configured, such as additional Overcurrent protection, additional Multipurpose
protection functions, Synchronizing function, and so on. It is as well possible to order
optional two-winding transformer differential or high impedance differential
protection functions which than can be used instead of basic low-impedance generator
differential protection. Note that REG670 A20 must be re-configured if any additional
or optional functions are used.
1MRK 502 071-UEN -
Section 3
Configuration
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
57
Application manual
REG670 A20 – Generator differential + backup protection 12AI (7I + 5U)
Y
Y
ROV2 PTOV
59N
2(U0>)
AEG PVOC
50AE
U/I>
SMP PTRC
94
1→0
ROV2 PTOV
59N
2(U0>)
V MMXU
MET
U
GEN_QA1
GEN_TRM_VT
GEN_TRM_CT
ROT_INJ_VT
ROT_INJ_CT
GEN_SP_CT
GEN_SP_VT
OC4 PTOC
51_67
4(3I>)
C MSQI
MET
Isqi
C MMXU
MET
I
SES RSYN
25
SC/VC
CCS SPVC
87
INd/I
ROTI PHIZ
64R
R<
OOS PPAM
78
Ucos
HZ PDIF
87
Id>
SDE PSDE
67N
IN>
T2W PDIF
87T
3Id/I>
STEF PHIZ
59THD U3d/N
EF4 PTOC
51N_67N 4(IN>)
SA PFRC
81
df/dt<>
Other Functions available from the function library
Optional Functions
NS4 PTOC
46I2
4(I2>)
PSP PPAM
78
Ucos
CC PDSC
52PD
PD
PH PIOC
50
3I>>
EF PIOC
50N
IN>>
VDC PTOV
60
Ud>
Q CBAY
3
Control
GR PTTR
49R
θ>
TCM YLTC
84
↑↓
VD SPVC
60
Ud>
FTA QFVR
81A
f<>
VR PVOC
51V
2(I>/U<)
Q CRSV
3
Control
S CILO
3
Control
S CSWI
3
Control
S SCBR
Control
ZMH PDIS
21
Z<
TR PTTR
49
θ>
ZDM RDIR
21D
Z<_>
IEC11000068-6-en.vsdx
S SIML
71
S SIMG
63
S SCBR
Control
S SCBR
Control
S XCBR
3
Control
PMU REP
STTI PHIZ
64S
R<
S XSWI
3
Control
FUF SPVC
U>/I<
NS2 PTOC
46
I2>
IEC11000068 V6 EN
Figure 8:
Typical generator protection application with generator differential
and back-up protection, including 12 analog inputs transformers in
half 19" case size.
3.1.1.2
Description of configuration B30
REG670 B30 configuration is used in applications where generator protection and
backup protection for surrounding primary equipment within one IED is required.
REG670 B30 is always delivered in 1/1 of 19" case size. Thus 24 analogue inputs are
available. This configuration includes generator low impedance, differential
protection and all other typically required generator protection functions. In figure 9,
this configuration is shown.
Section 3
1MRK 502 071-UEN -
Configuration
58
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
REG670 B30 functional library includes additional functions, which are not
configured, such as additional Multipurpose protection functions, Synchrocheck
function, second generator differential protection function, and so on. It is as well
possible to order optional two- or three-winding transformer differential protection
function, which than can be used as transformer or block (that is overall) differential
protection. Note that REG670 B30 must be re-configured if any additional or optional
functions are used.
1MRK 502 071-UEN -
Section 3
Configuration
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
59
Application manual
Unit Step-up Trafo
Auxiliary Trafo
Excitation Trafo
CC RBRF
50BF
3I>BF
EF4 PTOC
51N_67N
4(IN>)
ROV2 PTOV
59N
2(U0>)
SA PTUF
81U
f<
SA PTUF
81
f<
SA PTOF
81O
f>
SA PTOF
81
f>
UV2 PTUV
27
2(3U<)
OV2 PTOV
59
2(3U>)
V MSQI
MET
Usqi
V MMXU
MET
U
CC RBRF
50BF
3I>BF
FUF SPVC
U>/I<
ROV2 PTOV
59N
2(U0>)
GOP PDOP
32
P>
GUP PDUP
37
P<
GS PTTR
49S
θ>
C MMXU
MET
I
GEN PDIF
87G
3Id/I>
ZGV PDIS
21
Z<
CV GAPC
64R
Re<
CV GAPC
2(I>/U<)
REG670 B30 – Generator differential + backup protection
24AI (9I+3U, 9I+3U)
LEX PDIS
40
Φ <
DRP RDRE
DFR/SER
DR
OEX PVPH
24
U/f>
ETP MMTR
MET
W/Varh
CV MMXN
MET
P/Q
+
RXTTE4
AEG PVOC
50AE
U/I>
ROV2 PTOV
59N
2(U0>)
VN MMXU
MET
UN
STEF PHIZ
59THD U3d/N
SMP PTRC
94
1→0
OC4 PTOC
51_67
4(3I>)
GEN_QA1
AUX_QA1
HV_QA1
HV_CT
LV_VT_3U0
GEN_TRM_VT
GEN_TRM_CT
GEN_SP_CT
GEN_SP_VT
OC4 PTOC
51_67
4(3I>)
ROT_INJ_VT
ROT_INJ_CT
AUX_CT
EXC_CT
HV_NCT
Y
Y
Y
G
OC4 PTOC
51_67
4(3I>)
C MSQI
MET
Isqi
C MMXU
MET
I
C MSQI
MET
Isqi
C MMXU
MET
I
C MSQI
MET
Isqi
C MMXU
MET
I
C MMXU
MET
I
OC4 PTOC
51_67
4(3I>)
NS2 PTOC
46
I2>
C MSQI
MET
Isqi
=IEC11000071=6=en=Original.vsd
SES RSYN
25
SC/VC
CCS SPVC
87
INd/I
STTI PHIZ
64S
R<
OOS PPAM
78
Ucos
T3W PDIF
87T
3Id/I>
REF PDIF
87N
IdN/I
T2W PDIF
87T
3Id/I>
ROTI PHIZ
64R
R<
HZ PDIF
87
Id>
SA PFRC
81
df/dt<>
Optional Functions
SDE PSDE
67N
IN>
NS4 PTOC
46I2
4(I2>)
PSP PPAM
78
Ucos
CC PDSC
52PD
PD
PH PIOC
50
3I>>
EF PIOC
50N
IN>>
VDC PTOV
60
Ud>
Q CBAY
3
Control
GR PTTR
49R
θ>
TCM YLTC
84
↑↓
VD SPVC
60
Ud>
FTA QFVR
81A
f<>
VR PVOC
51V
2(I>/U<)
Q CRSV
3
Control
S CILO
3
Control
S CSWI
3
Control
S XSWI
3
Control
ZMH PDIS
21
Z<
TR PTTR
49
θ>
ZDM RDIR
21D
Z<_>
Other Functions available from the function library
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SIMG
63
S SIML
71
S XCBR
3
Control
PMU REP
IEC11000071 V6 EN
Figure 9:
Enhanced generator protection application with generator differential
and back-up protection, including 24 analog inputs in full 19" case
size. Optional pole slip protection, 100% stator earth fault protection
and overall differential protection can be added.
3.1.1.3
Description of configuration C30
REG670 C30 configuration is used in applications where generator-transformer block
protection within one IED is required. REG670 C30 is always delivered in 1/1 of 19"
case size. Thus 24 analog inputs are available. This configuration includes generator
Section 3
1MRK 502 071-UEN -
Configuration
60
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
low impedance, differential protection, transformer differential protection and overall
differential protection functions. Note that Pole Slip protection function is optional.
See figure 10, example of one possible application.
REG670 C30 functional library includes additional functions, which are not
configured, such as additional Multipurpose protection functions, Synchrocheck
function, second generator differential protection function, and so on. Note that
REG670 C30 must be re-configured if any additional or optional functions are used.
1MRK 502 071-UEN -
Section 3
Configuration
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
61
Application manual
Unit Step-up Trafo
Auxiliary Trafo
CC RBRF
50BF
3I>BF
ROV2 PTOV
59N
2(U0>)
SA PTUF
81U
f<
SA PTUF
81
f<
SA PTOF
81O
f>
SA PTOF
81
f>
UV2 PTUV
27
2(3U<)
OV2 PTOV
59
2(3U>)
V MMXU
MET
U
VN MMXU
MET
UN
V MSQI
MET
Usqi
CC RBRF
50BF
I>BF
ROV2 PTOV
59G
UN>
GOP PDOP
32
P>
GUP PDUP
37
P<
NS2 PTOC
46
I2>
C MMXU
MET
I
ZGV PDIS
21
Z<
CV GAPC
64R
Re<
CV GAPC
2(I>/U<)
Y
Y
TR PTTR
49
θ>
OV2 PTOV
59
2(3U>)
CV MMXN
MET
P/Q
LEX PDIS
40
Φ <
ETP MMTR
MET
W/Varh
CV MMXN
MET
P/Q
Grounding
Trafo
OEX PVPH
24
U/f>
DRP RDRE
DFR/SER
DR
+
RXTTE4
AEG PVOC
50AE
U/I>
T2W PDIF
87T
3Id/I>
REG670 C30 – Generator and block transformer protection
24AI (9I+3U, 6I+6U)
51N_67N
EF4 PTOC
4(IN>)
STEF PHIZ
59THD U3d/N
OC4 PTOC
51_67
4(3I>)
SMP PTRC
94
1→0
HV_QA1
AUX_QA1
GEN_QA1
HV_VT
HV_CT
LV_VT_3U0
AUX_CT
GEN_TRM_VT
GEN_TRM_CT
ROT_INJ_CT
ROT_INJ_VT
GEN_SP_CT
GEN_SP_VT
OC4 PTOC
51_67
4(3I>)
OC4 PTOC
51_67
4(3I>)
Y
Y
Y
ROV2 PTOV
59N
2(U0>)
HV_NCT
G
C MSQI
MET
Isqi
C MMXU
MET
I
V MMXU
MET
U
V MSQI
MET
Usqi
C MSQI
MET
Isqi
C MMXU
MET
I
T3W PDIF
87T
3Id/I>
FUF SPVC
U>/I<
C MSQI
MET
Isqi
C MMXU
MET
I
GS PTTR
49S
θ>
SES RSYN
25
SC/VC
CCS SPVC
87
INd/I
STTI PHIZ
64S
R<
OOS PPAM
78
Ucos
ROTI PHIZ
64R
R<
HZ PDIF
87
Id>
SA PFRC
81
df/dt<>
Other Functions available from the function library
SDE PSDE
67N
IN>
NS4 PTOC
46I2
4(I2>)
PSP PPAM
78
Ucos
CC PDSC
52PD
PD
PH PIOC
50
3I>>
EF PIOC
50N
IN>>
VDC PTOV
60
Ud>
TCM YLTC
84
↑↓
S SIMG
63
S SIML
71
GR PTTR
49R
θ>
Q CBAY
3
Control
Q CRSV
3
Control
S CILO
3
Control
S CSWI
3
Control
S XSWI
3
Control
S XCBR
3
Control
VD SPVC
60
Ud>
FTA QFVR
81A
f<>
VR PVOC
51V
2(I>/U<)
ZMH PDIS
21
Z<
ZDM RDIR
21D
Z<_>
=IEC11000072=6=en=Original.vsd
PMU REP
GEN PDIF
87G
3Id/I>
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
S SCBR
Control
REF PDIF
87N
IdN/I
S SCBR
Control
S SCBR
Control
S SCBR
Control
Optional functions
FUF SPVC
U>/I<
IEC11000072 V6 EN
Figure 10:
Unit protection including generator and generator transformer
protection with 24 analog inputs in full 19" case size. Optional pole
slip protection and 100% stator earthfault protection can be added.
Section 3
1MRK 502 071-UEN -
Configuration
62
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Analog input channels must be configured and set properly in order to get correct
measurement results and correct protection operations. For power measuring, all
directional and differential functions, the directions of the input currents must be
defined in order to reflect the way the current transformers are installed/connected in
the field ( primary and secondary connections ). Measuring and protection algorithms
in the IED use primary system quantities. Setting values are in primary quantities as
well and it is important to set the data about the connected current and voltage
transformers properly.
An AISVBAS reference PhaseAngleRef can be defined to facilitate service values
reading. This analog channel's phase angle will always be fixed to zero degrees and
remaining analog channel's phase angle information will be shown in relation to this
analog input. During testing and commissioning of the IED, the reference channel can
be changed to facilitate testing and service values reading.
The IED has the ability to receive analog values from primary
equipment, that are sampled by Merging units (MU) connected to a
process bus, via the IEC 61850-9-2 LE protocol.
The availability of VT inputs depends on the ordered transformer
input module (TRM) type.
4.2
Setting guidelines
The available setting parameters related to analog inputs are
depending on the actual hardware (TRM) and the logic configuration
made in PCM600.
4.2.1
Setting of the phase reference channel
All phase angles are calculated in relation to a defined reference. An appropriate
analog input channel is selected and used as phase reference. The parameter
PhaseAngleRef defines the analog channel that is used as phase angle reference.
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
63
Application manual
Usually the L1 phase-to-earth voltage connected to the first VT channel number of the
transformer input module (TRM) is selected as the phase reference. The first VT
channel number depends on the type of transformer input module.
For a TRM with 6 current and 6 voltage inputs the first VT channel is 7. The setting
PhaseAngleRef=7 shall be used if the phase reference voltage is connected to that
channel.
4.2.2
Setting of current channels
The direction of a current to the IED is depending on the connection of the CT. Unless
indicated otherwise, the main CTs are supposed to be star connected and can be
connected with the earthing point to the object or from the object. This information
must be set in the IED. The convention of the directionality is defined as follows: A
positive value of current, power, and so on means that the quantity has the direction
into the object and a negative value means direction out from the object. For
directional functions the direction into the object is defined as Forward and the
direction out from the object is defined as Reverse. See Figure 11
A positive value of current, power, and so on (forward) means that the quantity flows
towards the object. A negative value of current, power, and so on (reverse) means that
the quantity flows away from the object. See Figure 11.
Protected Object
Line, transformer, etc
Forward
Reverse
Definition of direction
for directional functions
Measured quantity is
positive when flowing
towards the object
e.g. P, Q, I
Reverse
Forward
Definition of direction
for directional functions
e.g. P, Q, I
Measured quantity is
positive when flowing
towards the object
Set parameter
CTStarPoint
Correct Setting is
"ToObject"
Set parameter
CTStarPoint
Correct Setting is
"FromObject"
en05000456.vsd
IEC05000456 V1 EN
Figure 11:
Internal convention of the directionality in the IED
With correct setting of the primary CT direction, CTStarPoint set to FromObject or
ToObject, a positive quantities always flowing towards the protected object and a
direction defined as Forward always is looking towards the protected object. The
following examples show the principle.
Section 4
1MRK 502 071-UEN -
Analog inputs
64
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Two IEDs used for protection of two objects.
Transformer
protection
Transformer
Line
Line
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IEC05000753=IEC05
000753=1=en=Origin
al[1].vsd
Is
Is
Ip
Ip
Ip
IED
IED
IEC05000753 V2 EN
Figure 12:
Example how to set CTStarPoint parameters in the IED
Figure 12 shows the normal case where the objects have their own CTs. The settings
for CT direction shall be done according to the figure. To protect the line, direction of
the directional functions of the line protection shall be set to Forward. This means that
the protection is looking towards the line.
4.2.2.2
Example 2
Two IEDs used for protection of two objects and sharing a CT.
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
65
Application manual
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction
for directional functions
Line protection
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IED
IED
IEC05000460 V2 EN
Figure 13:
Example how to set CTStarPoint parameters in the IED
This example is similar to example 1, but here the transformer is feeding just one line
and the line protection uses the same CT as the transformer protection does. The CT
direction is set with different reference objects for the two IEDs though it is the same
current from the same CT that is feeding the two IEDs. With these settings, the
directional functions of the line protection shall be set to Forward to look towards the
line.
4.2.2.3
Example 3
One IED used to protect two objects.
Section 4
1MRK 502 071-UEN -
Analog inputs
66
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Reverse
Forward
Definition of direction
for directional
line functions
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
IED
IEC05000461 V2 EN
Figure 14:
Example how to set CTStarPoint parameters in the IED
In this example, one IED includes both transformer and line protections and the line
protection uses the same CT as the transformer protection does. For both current input
channels, the CT direction is set with the transformer as reference object. This means
that the direction Forward for the line protection is towards the transformer. To look
towards the line, the direction of the directional functions of the line protection must
be set to Reverse. The direction Forward/Reverse is related to the reference object that
is the transformer in this case.
When a function is set to Reverse and shall protect an object in reverse direction, it
shall be noted that some directional functions are not symmetrical regarding the reach
in forward and reverse direction. It is in first hand the reach of the directional criteria
that can differ. Normally it is not any limitation but it is advisable to have it in mind
and check if it is acceptable for the application in question.
If the IED has sufficient number of analog current inputs, an alternative solution is
shown in Figure 15. The same currents are fed to two separate groups of inputs and the
line and transformer protection functions are configured to the different inputs. The
CT direction for the current channels to the line protection is set with the line as
reference object and the directional functions of the line protection shall be set to
Forward to protect the line.
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
67
Application manual
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction
for directional
line functions
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input
for line functions:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IED
IEC05000462 V2 EN
Figure 15:
Example how to set CTStarPoint parameters in the IED
Section 4
1MRK 502 071-UEN -
Analog inputs
68
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC06000196 V2 EN
Figure 16:
Example how to set CTStarPoint parameters in the IED
For busbar protection, it is possible to set the CTStarPoint parameters in two ways.
The first solution will be to use busbar as a reference object. In that case for all CT
inputs marked with 1 in Figure 16, set CTStarPoint = ToObject, and for all CT inputs
marked with 2 in Figure 16, set CTStarPoint = FromObject.
The second solution will be to use all connected bays as reference objects. In that case
for all CT inputs marked with 1 in Figure 16, set CTStarPoint = FromObject, and for
all CT inputs marked with 2 in Figure 16, set CTStarPoint = ToObject.
Regardless which one of the above two options is selected, busbar differential
protection will behave correctly.
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
69
Application manual
The main CT ratios must also be set. This is done by setting the two parameters CTsec
and CTprim for each current channel. For a 1000/1 A CT, the following settings shall
be used:
•
CTprim = 1000 (value in A)
•
CTsec =1 (value in A).
4.2.2.4
Examples on how to connect, configure and set CT inputs for most
commonly used CT connections
Figure 17 defines the marking of current transformer terminals commonly used
around the world:
In the SMAI function block, you have to set if the SMAI block is
measuring current or voltage. This is done with the parameter:
AnalogInputType: Current/Voltage. The ConnectionType: phase -
phase/phase-earth and GlobalBaseSel.
ISec
IPri
S1 (X1)
P1
(H1)
P2
(H2)
S2 (X2)
P2
(H2)
P1
(H1)
x
x
a)
b)
c)
en06000641.vsd
S2 (X2)
S1 (X1)
IEC06000641 V1 EN
Figure 17:
Commonly used markings of CT terminals
Where:
a)
is symbol and terminal marking used in this document. Terminals marked with a square
indicates the primary and secondary winding terminals with the same (that is, positive) polarity
b) and c)
are equivalent symbols and terminal marking used by IEC (ANSI) standard for CTs. Note that for
these two cases the CT polarity marking is correct!
It shall be noted that depending on national standard and utility practices, the rated
secondary current of a CT has typically one of the following values:
•
1A
•
5A
Section 4
1MRK 502 071-UEN -
Analog inputs
70
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
However, in some cases, the following rated secondary currents are used as well:
•
2A
•
10A
The IED fully supports all of these rated secondary values.
It is recommended to:
•
use 1A rated CT input into the IED in order to connect CTs with
1A and 2A secondary rating
•
use 5A rated CT input into the IED in order to connect CTs with
5A and 10A secondary rating
4.2.2.5
Example on how to connect a star connected three-phase CT set to the
IED
Figure 18 gives an example about the wiring of a star connected two-phase CT set to
the IED. It gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the IED
as well.
For correct terminal designations, see the connection diagrams valid
for the delivered IED.
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
71
Application manual
IEC13000002 V4 EN
Figure 18:
Star connected three-phase CT set with star point towards the protected object
Where:
1)
The drawing shows how to connect three individual phase currents from a star connected
three-phase CT set to the three CT inputs of the IED.
2)
The current inputs are located in the TRM. It shall be noted that for all these current inputs the
following setting values shall be entered for the example shown in Figure 18.
•
CTprim=600A
•
CTsec=5A
•
CTStarPoint=ToObject
Ratio of the first two parameters is only used inside the IED. The third parameter
(CTStarPoint=ToObject) as set in this example causes no change on the measured currents.
In other words, currents are already measured towards the protected object.
Table continues on next page
Section 4
1MRK 502 071-UEN -
Analog inputs
72
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
These three connections are the links between the three current inputs and the three input
channels of the preprocessing function block 4). Depending on the type of functions, which
need this current information, more than one preprocessing block might be connected in
parallel to the same three physical CT inputs.
4)
The preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all three input channels
•
harmonic content for all three input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block. For this application
most of the preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in power plants), then the setting parameters DFTReference shall be set
accordingly.
Section SMAI in this manual provides information on adaptive frequency tracking for the
signal matrix for analogue inputs (SMAI).
5)
AI3P in the SMAI function block is a grouped signal which contains all the data about the
phases L1, L2, L3 and neutral quantity; in particular the data about fundamental frequency
phasors, harmonic content and positive sequence, negative and zero sequence quantities
are available.
AI1, AI2, AI3, AI4 are the output signals from the SMAI function block which contain the
fundamental frequency phasors and the harmonic content of the corresponding input
channels of the preprocessing function block.
AIN is the signal which contains the fundamental frequency phasors and the harmonic
content of the neutral quantity. In this example, GRP2N is not connected so this data is
calculated by the preprocessing function block on the basis of the inputs GRPL1, GRPL2 and
GRPL3. If GRP2N is connected, the data reflects the measured value of GRP2N.
Another alternative is to have the star point of the three-phase CT set as shown in
Figure 19:
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
73
Application manual
IEC11000026 V4 EN
Figure 19:
Star connected three-phase CT set with its star point away from the protected object
In the example, everything is done in a similar way as in the above described example
(Figure 18). The only difference is the setting of the parameter CTStarPoint of the
used current inputs on the TRM (item 2 in Figure 19 and 18):
•
CTprim=600A
•
CTsec=5A
•
CTStarPoint=FromObject
The ratio of the first two parameters is only used inside the IED. The third parameter
as set in this example will negate the measured currents in order to ensure that the
currents are measured towards the protected object within the IED.
A third alternative is to have the residual/neutral current from the three-phase CT set
connected to the IED as shown in Figure 19.
Section 4
1MRK 502 071-UEN -
Analog inputs
74
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC06000644 V4 EN
Figure 20:
Star connected three-phase CT set with its star point away from the protected object and the
residual/neutral current connected to the IED
Where:
1)
Shows how to connect three individual phase currents from a star connected three-phase CT
set to the three CT inputs of the IED.
2)
Shows how to connect residual/neutral current from the three-phase CT set to the fourth input
in the IED. It shall be noted that if this connection is not made, the IED will still calculate this
current internally by vectorial summation of the three individual phase currents.
3)
Is the TRM where these current inputs are located. It shall be noted that for all these current
inputs the following setting values shall be entered.
•
CTprim=800A
•
CTsec=1A
•
CTStarPoint=FromObject
•
ConnectionType=Ph-N
The ratio of the first two parameters is only used inside the IED. The third parameter as set in
this example will have no influence on measured currents (that is, currents are already
measured towards the protected object).
4)
Are three connections made in the Signal Matrix tool (SMT) and Application configuration tool
(ACT), which connects these three current inputs to the first three input channels on the
preprocessing function block 6). Depending on the type of functions, which need this current
information, more than one preprocessing block might be connected in parallel to these three
CT inputs.
Table continues on next page
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
75
Application manual
Is a connection made in the Signal Matrix tool (SMT) and Application configuration tool
(ACT), which connects the residual/neutral current input to the fourth input channel of the
preprocessing function block 6). Note that this connection in SMT shall not be done if the
residual/neutral current is not connected to the IED.
6)
Is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all input channels
•
harmonic content for all input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors of the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the configuration
tool. For this application, most of the preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations), then the setting parameters DFTReference shall be
set accordingly.
4.2.2.6
Example how to connect delta connected three-phase CT set to the IED
Figure 21 gives an example how to connect a delta connected three-phase CT set to the
IED. It gives an overview of the required actions by the user in order to make this
measurement available to the built-in protection and control functions in the IED as
well.
For correct terminal designations, see the connection diagrams valid
for the delivered IED.
Section 4
1MRK 502 071-UEN -
Analog inputs
76
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC11000027 V3 EN
Figure 21:
Delta DAB connected three-phase CT set
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
77
Application manual
shows how to connect three individual phase currents from a delta connected three-phase
CT set to three CT inputs of the IED.
2)
is the TRM where these current inputs are located. It shall be noted that for all these current
inputs the following setting values shall be entered.
CTprim=600A
CTsec=5A
•
CTStarPoint=ToObject
•
ConnectionType=Ph-Ph
3)
are three connections made in Signal Matrix Tool (SMT), Application configuration tool
(ACT), which connect these three current inputs to first three input channels of the
preprocessing function block 4). Depending on the type of functions which need this current
information, more then one preprocessing block might be connected in parallel to these three
CT inputs.
4)
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all three input channels
•
harmonic content for all three input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block. For this application
most of the preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations) then the setting parameters DFTReference shall be
set accordingly.
Another alternative is to have the delta connected CT set as shown in figure 22:
Section 4
1MRK 502 071-UEN -
Analog inputs
78
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC11000028 V3 EN
Figure 22:
Delta DAC connected three-phase CT set
In this case, everything is done in a similar way as in the above described example,
except that for all used current inputs on the TRM the following setting parameters
shall be entered:
CTprim=800A
CTsec=1A
•
CTStarPoint=ToObject
•
ConnectionType=Ph-Ph
It is important to notice the references in SMAI. As inputs at Ph-Ph are expected to be
L1L2, L2L3 respectively L3L1 we need to tilt 180º by setting ToObject.
4.2.2.7
Example how to connect single-phase CT to the IED
Figure 23 gives an example how to connect the single-phase CT to the IED. It gives
an overview of the required actions by the user in order to make this measurement
available to the built-in protection and control functions within the IED as well.
For correct terminal designations, see the connection diagrams valid
for the delivered IED.
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
79
Application manual
IEC11000029 V4 EN
Figure 23:
Connections for single-phase CT input
Where:
1)
shows how to connect single-phase CT input in the IED.
2)
is TRM where these current inputs are located. It shall be noted that for all these current
inputs the following setting values shall be entered.
For connection (a) shown in Fgure 23:
CTprim= 1000 A
CTsec= 1A
CTStarPoint=ToObject
For connection (b) shown in Figure 23:
CTprim= 1000 A
CTsec= 1A
CTStarPoint=FromObject
3)
shows the connection made in SMT tool, which connect this CT input to the fourth input
channel of the preprocessing function block 4).
4)
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate values. The calculated values are then available for all built-in protection and
control functions within the IED, which are connected to this preprocessing function block.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the power plants) then the setting parameters DFTReference shall be
set accordingly.
4.2.3
Relationships between setting parameter Base Current, CT
rated primary current and minimum pickup of a protection
IED
Note that for all line protection applications (e.g. distance protection or line
differential protection) the parameter Base Current (i.e. IBase setting in the IED) used
by the relevant protection function, shall always be set equal to the largest rated CT
Section 4
1MRK 502 071-UEN -
Analog inputs
80
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
primary current among all CTs involved in the protection scheme. The rated CT
primary current value is set as parameter CTPrim under the IED TRM settings.
For all other protection applications (e.g. generator, shunt reactor, shunt capacitor and
transformer protection) it is typically desirable to set IBase parameter equal to the
rated current of the protected object. However this is only recommended to do if the
rated current of the protected object is within the range of 40% to 120% of the selected
CT rated primary current. If for any reason (e.g. high maximum short circuit current)
the rated current of the protected object is less than 40% of the rated CT primary
current, it is strongly recommended to set the parameter IBase in the IED to be equal
to the largest rated CT primary current among all CTs involved in the protection
scheme and installed on the same voltage level. This will effectively make the
protection scheme less sensitive; however, such measures are necessary in order to
avoid possible problems with loss of the measurement accuracy in the IED.
Regardless of the applied relationship between the IBase parameter and the rated CT
primary current, the corresponding minimum pickup of the function on the CT
secondary side must always be verified. It is strongly recommended that the minimum
pickup of any instantaneous protection function (e.g. differential, restricted earth
fault, distance, instantaneous overcurrent, etc.) shall under no circumstances be less
than 4% of the used IED CT input rating (i.e. 1A or 5A). This corresponds to 40mA
secondary for IED 1A rated inputs and to 200mA secondary for IED 5A rated inputs
used by the function. This shall be individually verified for all current inputs involved
in the protection scheme.
Note that exceptions from the above 4% rule may be acceptable for very special
applications (e.g. when Multipurpose filter SMAIHPAC is involved in the protection
scheme).
4.2.4
Setting of voltage channels
As the IED uses primary system quantities, the main VT ratios must be known to the
IED. This is done by setting the two parameters VTsec and VTprim for each voltage
channel. The phase-to-phase value can be used even if each channel is connected to a
phase-to-earth voltage from the VT.
4.2.4.1
Example
Consider a VT with the following data:
132
110
3
3
kV
V
EQUATION2016 V1 EN
(Equation 1)
The following setting should be used: VTprim=132 (value in kV) VTsec=110 (value
in V)
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
81
Application manual
Examples how to connect, configure and set VT inputs for most
commonly used VT connections
Figure 24 defines the marking of voltage transformer terminals commonly used
around the world.
A
(H1)
B
(H2)
b
(X2)
a
(X1)
A
(H1)
N
(H2)
n
(X2)
a
(X1)
b)
c)
A
(H1)
N
(H2)
dn
(X2)
da
(X1)
d)
UPri
+
+
USec
a)
en06000591.vsd
IEC06000591 V1 EN
Figure 24:
Commonly used markings of VT terminals
Where:
a)
is the symbol and terminal marking used in this document. Terminals marked with a square
indicate the primary and secondary winding terminals with the same (positive) polarity
b)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
earth connected VTs
c)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for open delta
connected VTs
d)
is the equivalent symbol and terminal marking used by IEC (ANSI) standard for phase-to-
phase connected VTs
It shall be noted that depending on national standard and utility practices the rated
secondary voltage of a VT has typically one of the following values:
•
100 V
•
110 V
•
115 V
•
120 V
•
230 V
The IED fully supports all of these values and most of them will be shown in the
following examples.
4.2.4.3
Examples on how to connect a three phase-to-earth connected VT to
the IED
Figure 25 gives an example on how to connect a three phase-to-earth connected VT to
the IED. It gives an overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
Section 4
1MRK 502 071-UEN -
Analog inputs
82
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
For correct terminal designations, see the connection diagrams valid
for the delivered IED.
L1
IED
L2
L3
66
3
110
3
kV
V
1
3
2
66
3
110
3
kV
V
66
3
110
3
kV
V
.
#Not used
5
IEC06000599-4-en.vsdx
4
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
IEC06000599 V4 EN
Figure 25:
A Three phase-to-earth connected VT
L1
IED
L2
132
2
110
2
kV
V
1
3
2
132
2
110
2
kV
V
IEC16000140-1-en.vsdx
4
SMAI2
BLOCK
^GRP2L1
^GRP2L2
^GRP2L1L2
^GRP2N
AI2P
AI1
AI2
AI3
AI4
AIN
5
IEC16000140 V1 EN
Figure 26:
A two phase-to-earth connected VT
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
83
Application manual
shows how to connect three secondary phase-to-earth voltages to three VT inputs on the
IED
2)
is the TRM where these three voltage inputs are located. For these three voltage inputs,
the following setting values shall be entered:
VTprim =132 kV
VTsec = 110 V
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio
of the entered values exactly corresponds to ratio of one individual VT.
66
66
3
110
110
3
=
EQUATION1903 V1 EN
(Equation 2)
3)
are three connections made in Signal Matrix Tool (SMT), which connect these three
voltage inputs to first three input channels of the preprocessing function block 5).
Depending on the type of functions which need this voltage information, more then one
preprocessing block might be connected in parallel to these three VT inputs.
4)
shows that in this example the fourth (that is, residual) input channel of the preprocessing
block is not connected in SMT tool. Thus the preprocessing block will automatically
calculate 3Uo inside by vectorial sum from the three phase to earth voltages connected to
the first three input channels of the same preprocessing block. Alternatively, the fourth
input channel can be connected to open delta VT input, as shown in Figure 28.
5)
is a Preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all input channels
•
harmonic content for all input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values. However the following settings shall be set as shown here:
UBase=66 kV (that is, rated Ph-Ph voltage)
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
4.2.4.4
Example on how to connect a phase-to-phase connected VT to the IED
Figure 27 gives an example how to connect a phase-to-phase connected VT to the
IED. It gives an overview of the required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
It shall be noted that this VT connection is only used on lower voltage levels (that is,
rated primary voltage below 40 kV).
Section 4
1MRK 502 071-UEN -
Analog inputs
84
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC06000600 V5 EN
Figure 27:
A Two phase-to-phase connected VT
Where:
1)
shows how to connect the secondary side of a phase-to-phase VT to the VT inputs on the IED
2)
is the TRM where these three voltage inputs are located. It shall be noted that for these three
voltage inputs the following setting values shall be entered:
VTprim=13.8 kV
VTsec=120 V
Please note that inside the IED only ratio of these two parameters is used.
Table continues on next page
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
85
Application manual
are three connections made in the Signal Matrix tool (SMT), Application configuration tool
(ACT), which connects these three voltage inputs to first three input channels of the
preprocessing function block 5). Depending on the type of functions, which need this voltage
information, more than one preprocessing block might be connected in parallel to these three
VT inputs
4)
shows that in this example the fourth (that is, residual) input channel of the preprocessing
block is not connected in SMT. Note. If the parameters UL1, UL2, UL3, UN should be used the
open delta must be connected here.
5)
Preprocessing block has a task to digitally filter the connected analog inputs and calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the configuration
tool. For this application most of the preprocessing settings can be left to the default values.
However the following settings shall be set as shown here:
ConnectionType=Ph-Ph
UBase=13.8 kV
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations) then the setting parameters DFTReference shall be
set accordingly.
4.2.4.5
Example on how to connect an open delta VT to the IED for high
impedance earthed or unearthed networks
Figure 28 gives an example about the wiring of an open delta VT to the IED for high
impedance earthed or unearthed power systems. It shall be noted that this type of VT
connection presents a secondary voltage proportional to 3U0 to the IED.
In case of a solid earth fault close to the VT location the primary value of 3Uo will be
equal to:
3 0
3
3
Ph Ph
Ph N
U
U
U
-
-
=
×
= ×
EQUATION1921 V3 EN
(Equation 3)
The primary rated voltage of an open Delta VT is always equal to UPh-E. Three series
connected VT secondary windings gives a secondary voltage equal to three times the
individual VT secondary winding rating. Thus the secondary windings of open delta
VTs quite often have a secondary rated voltage equal to one third of the rated phase-
to-phase VT secondary voltage (110/3V in this particular example).
Figure 28 gives overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED
as well.
Section 4
1MRK 502 071-UEN -
Analog inputs
86
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
# Not Used
5
IEC06000601-4-en.vsdx
# Not Used
# Not Used
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
IEC06000601 V4 EN
Figure 28:
Open delta connected VT in high impedance earthed power system
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
87
Application manual
shows how to connect the secondary side of the open delta VT to one VT input on the IED.
+3U0 shall be connected to the IED
2)
is the TRM where this voltage input is located. It shall be noted that for this voltage input the
following setting values shall be entered:
3 6.6
11.43
VTprim
kV
=
×
=
EQUATION1923 V1 EN
(Equation 4)
110
sec
3
110
3
VT
V
=
×
=
EQUATION1924 V1 EN
(Equation 5)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio
of the entered values exactly corresponds to ratio of one individual open delta VT.
6.6
3 6.6
3
110
110
3
×
=
EQUATION1925 V1 EN
(Equation 6)
3)
shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool or ACT tool.
4)
shows the connection made in Signal Matrix Tool (SMT), Application configuration tool
(ACT), which connect this voltage input to the fourth input channel of the preprocessing
function block 5).
5)
is a Preprocessing block that has the task to digitally filter the connected analog input and
calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for
sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to the
default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations ) then the setting parameters DFTReference
shall be set accordingly.
Section 4
1MRK 502 071-UEN -
Analog inputs
88
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Example how to connect the open delta VT to the IED for low
impedance earthed or solidly earthed power systems
Figure 29 gives an example about the connection of an open delta VT to the IED for
low impedance earthed or solidly earthed power systems. It shall be noted that this
type of VT connection presents secondary voltage proportional to 3U0 to the IED.
In case of a solid earth fault close to the VT location the primary value of 3Uo will be
equal to:
3
3
Ph
Ph
Ph
E
U
Uo
U
-
-
=
=
EQUATION1926 V1 EN
(Equation 7)
The primary rated voltage of such VT is always equal to UPh-E Therefore, three series
connected VT secondary windings will give the secondary voltage equal only to one
individual VT secondary winding rating. Thus the secondary windings of such open
delta VTs quite often has a secondary rated voltage close to rated phase-to-phase VT
secondary voltage, that is, 115V or 115/√3V as in this particular example. Figure 29
gives an overview of the actions which are needed to make this measurement available
to the built-in protection and control functions within the IED.
1
L1
IED
L2
L3
138
3
115
3
kV
V
+3Uo
138
3
115
3
kV
V
138
3
115
3
kV
V
IEC06000602-4-en.vsdx
# Not Used
# Not Used
# Not Used
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
2
3
4
5
IEC06000602 V4 EN
Figure 29:
Open delta connected VT in low impedance or solidly earthed power system
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
89
Application manual
shows how to connect the secondary side of open delta VT to one VT input in the IED.
+3Uo shall be connected to the IED.
2)
is TRM where this voltage input is located. It shall be noted that for this voltage input the
following setting values shall be entered:
3 138
138
3
VTprim
kV
=
×
=
EQUATION1928 V1 EN
(Equation 8)
115
sec
3
115
3
VT
V
=
×
=
EQUATION1929 V1 EN
(Equation 9)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the
ratio of the entered values exactly corresponds to ratio of one individual open delta VT.
138
138
3
115
115
3
=
EQUATION1930 V1 EN
(Equation 10)
3)
shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool.
4)
shows the connection made in Signal Matrix Tool (SMT), which connect this voltage
input to the fourth input channel of the preprocessing function block 4).
5)
preprocessing block has a task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental
frequency phasors for the first three input channels (channel one taken as
reference for sequence quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the
configuration tool. For this application most of the preprocessing settings can be left to
the default values.
If frequency tracking and compensation is required (this feature is typically required only
for IEDs installed in the generating stations) then the setting parameters DFTReference
shall be set accordingly.
4.2.4.7
Example on how to connect a neutral point VT to the IED
Figure 30 gives an example on how to connect a neutral point VT to the IED. This type
of VT connection presents secondary voltage proportional to U0 to the IED.
Section 4
1MRK 502 071-UEN -
Analog inputs
90
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
In case of a solid earth fault in high impedance earthed or unearthed systems the
primary value of Uo voltage will be equal to:
0
3
Ph
Ph
Ph
E
U
U
U
-
-
=
=
EQUATION1931 V2 EN
(Equation 11)
Figure 30 gives an overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
L1
L2
L3
IED
6.6
3
100
kV
V
R
Uo
IEC06000603-4-en.vsdx
# Not Used
# Not Used
# Not Used
Protected Object
SMAI2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
1
2
3
4
5
IEC06000603 V4 EN
Figure 30:
Neutral point connected VT
1MRK 502 071-UEN -
Section 4
Analog inputs
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
91
Application manual
shows how to connect the secondary side of neutral point VT to one VT input in the IED.
U0 shall be connected to the IED.
2)
is the TRM or AIM where this voltage input is located. For this voltage input the following
setting values shall be entered:
6.6
3.81
3
VTprim
kV
=
=
EQUATION1933 V1 EN
(Equation 12)
sec
100
VT
V
EQUATION1934 V2 EN
(Equation 13)
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the ratio
of the entered values exactly corresponds to ratio of the neutral point VT.
3)
shows that in this example the first three input channel of the preprocessing block is not
connected in SMT tool or ACT tool.
4)
shows the connection made in Signal Matrix Tool (SMT), Application configuration tool
(ACT), which connects this voltage input to the fourth input channel of the preprocessing
function block 5).
5)
is a preprocessing block that has the task to digitally filter the connected analog inputs and
calculate:
•
fundamental frequency phasors for all four input channels
•
harmonic content for all four input channels
•
positive, negative and zero sequence quantities by using the fundamental frequency
phasors for the first three input channels (channel one taken as reference for sequence
quantities)
These calculated values are then available for all built-in protection and control functions
within the IED, which are connected to this preprocessing function block in the configuration
tool. For this application, most of the preprocessing settings can be left to the default values.
If frequency tracking and compensation is required (this feature is typically required only for
IEDs installed in the generating stations) then the setting parameters DFTReference shall be
set accordingly.
Section 4
1MRK 502 071-UEN -
Analog inputs
92
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC13000239 V3 EN
Figure 31:
Local human-machine interface
The LHMI of the IED contains the following elements:
•
Keypad
•
Display (LCD)
•
LED indicators
•
Communication port for PCM600
1MRK 502 071-UEN -
Section 5
Local HMI
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
93
Application manual
The LHMI is used for setting, monitoring and controlling.
5.1
Display
The LHMI includes a graphical monochrome liquid crystal display (LCD) with a
resolution of 320 x 240 pixels. The character size can vary. The amount of characters
and rows fitting the view depends on the character size and the view that is shown.
The display view is divided into four basic areas.
IEC15000270-1-en.vsdx
IEC15000270 V1 EN
Figure 32:
Display layout
1
Path
2
Content
3
Status
4
Scroll bar (appears when needed)
The function key button panel shows on request what actions are possible with the
function buttons. Each function button has a LED indication that can be used as a
Section 5
1MRK 502 071-UEN -
Local HMI
94
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual