Daikin EHS157034 Operating Instructions Manual
Read Online
Read the Daikin EHS157034 Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Daikin Controller RoCon HP, EHS157034, EHS157068
Operating instructions
Daikin Controller RoCon HP, EHS157034, EHS157068
English
List of contents
Operating instructions
2
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
1
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1
Observing instructions . . . . . . . . . . . . . . . . . . . . 4
1.2
Warning signs and explanation of symbols . . . . 4
1.2.1
Meaning of the warnings. . . . . . . . . . . . . . . . . . . . .4
1.2.2
Validity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.2.3
Handling instructions. . . . . . . . . . . . . . . . . . . . . . . .5
1.2.4
Display readouts of the RoCon-Controller . . . . . . .5
1.3
Avoiding danger . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4
Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2
Product description. . . . . . . . . . . . . . . . . . . 6
3
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.1
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.2
Display and operating elements. . . . . . . . . . . . . 7
3.2.1
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.2.2
Operating elements. . . . . . . . . . . . . . . . . . . . . . . . .9
3.3
Operating concept . . . . . . . . . . . . . . . . . . . . . . 10
3.4
Basic functions and operating modes . . . . . . . 11
3.4.1
System information (Info) . . . . . . . . . . . . . . . . . . .11
3.4.2
Setting the operating mode. . . . . . . . . . . . . . . . . .13
3.4.3
Temperature setting Daytime room temperature .15
3.4.4
Temperature setting Economy mode . . . . . . . . . .15
3.4.5
Temperature setting hot water generation . . . . . .15
3.4.6
Unscheduled hot water generation . . . . . . . . . . . .15
3.4.7
Switching time program. . . . . . . . . . . . . . . . . . . . .16
3.4.8
System settings. . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.4.9
Terminal function. . . . . . . . . . . . . . . . . . . . . . . . . .18
3.4.10 Quite Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3.4.11 SMART GRID (SG). . . . . . . . . . . . . . . . . . . . . . . .20
3.5
Special functions . . . . . . . . . . . . . . . . . . . . . . . 20
3.5.1
Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . .20
3.5.2
Reference run 3-way diverter valve . . . . . . . . . . .21
3.6
Special system settings . . . . . . . . . . . . . . . . . . 21
3.6.1
Access Rights (Technician password) . . . . . . . . .21
3.6.2
Heat curve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.6.3
Cooling characteristic curve . . . . . . . . . . . . . . . . .23
3.6.4
Weather-controlled flow temperature regulation . .24
3.6.5
Frost protection function . . . . . . . . . . . . . . . . . . . .24
3.6.6
Interlink function . . . . . . . . . . . . . . . . . . . . . . . . . .25
3.6.7
Additional alternative heat generator . . . . . . . . . .25
3.6.8
Heating support. . . . . . . . . . . . . . . . . . . . . . . . . . .26
3.6.9
Special function: Switching contacts. . . . . . . . . . .26
3.6.10 Air Purge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
3.6.11 Legionella protection. . . . . . . . . . . . . . . . . . . . . . .27
3.6.12 Reset to factory settings (Reset). . . . . . . . . . . . . .27
3.6.13 Screed Program . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.6.14 Relay Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
3.6.15 Settings for optional circulation pump . . . . . . . . . .30
3.6.16 Remote control via Internet. . . . . . . . . . . . . . . . . .31
4
Initial start-up. . . . . . . . . . . . . . . . . . . . . . . 32
4.1
Fundamental aspects of the IDs and
authorisations in the RoCon system . . . . . . . . 32
4.2
Operating Support during 1st. Commissioning
and during System Extensions . . . . . . . . . . . . 34
4.3
Starting up the Daikin Altherma EHS(X/H). . . . 34
4.3.1
Allocating the terminal ID on the control unit
RoCon B1 of the Daikin Altherma EHS(X/H) . . . .34
4.4
Commissioning optional RoCon
system components . . . . . . . . . . . . . . . . . . . . . 34
4.4.1
Mixer module EHS157068 . . . . . . . . . . . . . . . . . .34
4.4.2
Room station EHS157034. . . . . . . . . . . . . . . . . . .35
4.4.3
Allocating mixing module EHS157068 to a
heat generator. . . . . . . . . . . . . . . . . . . . . . . . . . . .36
4.4.4
Master-RoCon function . . . . . . . . . . . . . . . . . . . . .36
4.4.5
Caretaker function. . . . . . . . . . . . . . . . . . . . . . . . 36
5
Parameter Overview . . . . . . . . . . . . . . . . . .37
5.1
For first commissioning or resetting to
factory settings . . . . . . . . . . . . . . . . . . . . . . . . 37
5.2
After first commissioning / after successful
basic configuration . . . . . . . . . . . . . . . . . . . . . 38
5.2.1
Rotary switch setting: Configuration . . . . . . . . . . 38
5.2.2
Rotary switch setting: DHW Install . . . . . . . . . . . 39
5.2.3
Rotary switch setting: Operating Mode . . . . . . . 39
5.2.4
Rotary switch setting: Set Temp Day . . . . . . . . . 39
5.2.5
Rotary switch setting: Set Temp Night . . . . . . . . 39
5.2.6
Rotary switch setting: DHW Set Temp . . . . . . . . 39
5.2.7
Rotary switch setting: Time Program . . . . . . . . . 39
5.2.8
Rotary switch setting: Remote Param . . . . . . . . 39
5.2.9
Rotary switch setting: Info . . . . . . . . . . . . . . . . . 39
5.2.10 Exit button: Sonderfunktion . . . . . . . . . . . . . . . . . 39
5.3
Parameter levels for the EHS157068
mixer module. . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3.1
Rotary switch setting: Info . . . . . . . . . . . . . . . . . 39
5.3.2
Rotary switch setting: Operating Mode . . . . . . . 39
5.3.3
Rotary switch setting: Set Temp Day . . . . . . . . . 39
5.3.4
Rotary switch setting: Set Temp Night . . . . . . . . 39
5.3.5
Rotary switch setting: DHW Set Temp . . . . . . . . 39
5.3.6
Rotary switch setting: DHW Install . . . . . . . . . . . 39
5.3.7
Rotary switch setting: Time Program . . . . . . . . . 40
5.3.8
Rotary switch setting: Remote Param . . . . . . . . 40
5.3.9
Rotary switch setting: Configuration . . . . . . . . . . 40
6
Parameter settings . . . . . . . . . . . . . . . . . . .41
6.1
Explanation of the parameter tables . . . . . . . . 41
6.2
Rotary switch setting: Configuration . . . . . . . . 41
6.2.1
Level "Setup". . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.2.2
Level "System " . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2.3
Level "HC Configuration". . . . . . . . . . . . . . . . . . . 46
6.2.4
Level "DHW Configuration" . . . . . . . . . . . . . . . . . 48
6.3
Rotary switch setting: DHW Install . . . . . . . . . 48
6.4
Rotary switch setting: Operating Mode . . . . . 48
6.5
Rotary switch setting: Set Temp Day . . . . . . . 49
6.6
Rotary switch setting: Set Temp Night . . . . . . 49
6.7
Rotary switch setting: DHW Set Temp . . . . . . 49
6.8
Rotary switch setting: Time Program . . . . . . . 50
6.9
Rotary switch setting: Remote Param . . . . . . 50
6.10 Rotary switch setting: Info . . . . . . . . . . . . . . . 51
6.11 Exit button: Sonderfunktion. . . . . . . . . . . . . . . 51
6.12 Parameter level "Basic Configuration" . . . . . . 52
6.13 Parameter levels for the EHS157068
mixer module. . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.13.1 Rotary switch setting: Configuration,
level "Setup" . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.13.2 Rotary switch setting: Configuration,
level "Mixer Config" . . . . . . . . . . . . . . . . . . . . . . . 54
7
Errors, malfunctions and messages . . . . .56
7.1
Recognising errors, correcting malfunctions. . 56
7.1.1
Current fault display . . . . . . . . . . . . . . . . . . . . . . 56
7.1.2
Read Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.1.3
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.2
Emergency operation . . . . . . . . . . . . . . . . . . . 57
7.3
Malfunctions and fault codes. . . . . . . . . . . . . . 57
8
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . .58
List of contents
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
3
9
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
9.1
User-specific settings . . . . . . . . . . . . . . . . . . . .59
9.1.1
Switching timer program . . . . . . . . . . . . . . . . . . . 59
9.1.2
Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
9.1.3
IDs in the RoCon CAN bus system . . . . . . . . . . . 60
9.2
Other items . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
10 List of keywords . . . . . . . . . . . . . . . . . . . . . 63
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
1 x Safety
1
Safety
1.1 Observing instructions
These instructions are a >> translation of the
original version << in your language.
All the activities required for operation and
setting the parameters are described in this in-
struction manual. All parameters needed for
trouble-free operation have been configured at
the factory.
● Please read through this manual carefully
before operating the heating system or before
adjusting the settings for it.
● Make a note of the preset values before you
make any changes to the unit configuration.
Relevant documents
– Daikin Altherma EHS(X/H):
– Installation and maintenance instructions
– Operating instructions for the user/owner
– Commissioning checklist
– External unit for Daikin Altherma EHS(X/H);
the associated installation and operating
instructions.
– When connecting to a solar system; the asso-
ciated installation and operating instructions.
– If a Daikin FWXV(15/20)AVEB is connected;
the associated installation and operating
instructions.
– If a different heater or optional accessories
are connected; the associated installation and
operating instructions.
The guides are included in the scope of supply
for the individual units.
1.2 Warning signs and explanation of
symbols
1.2.1 Meaning of the warnings
Warnings in this manual are classified according
into their severity and probability of occurrence.
DANGER!
Draws attention to imminent danger.
Disregarding this warning can lead to se-
rious injury or death.
WARNING!
Indicates a potentially dangerous situ-
ation.
Disregarding this warning may result in
serious physical injury or death.
CAUTION!
Indicates a situation which may cause
possible damage.
Disregarding this warning may cause
damage to property and the envi-
ronment.
This symbol identifies user tips and par-
ticularly useful information, but not warn-
ings or hazards.
Special warning signs
Some types of danger are represented by
special symbols:
Electric current
Risk of burning or scalding
1 x Safety
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
5
1.2.2 Validity
Some information in this manual has limited va-
lidity. The validity is highlighted by a symbol.
Only valid for Daikin Altherma EHS(X/H)
with cooling function
Valid/available only if a room station
(EHS157034) is connected
Valid/available only if a mixer module
(EHS157068) is connected
1.2.3 Handling instructions
● Handling instructions are shown as a list.
Actions of which the sequential order must be
maintained are numbered.
Results of actions are identified with an
arrow.
1.2.4 Display readouts of the RoCon-
Controller
Entry into a setting procedure
Exit from a setting procedure
Certain screen displays or menu points may
differ from those shown in these instructions due
to country or equipment variations in the Daikin
Altherma EHS(X/H) or the status of the user
logged onto the Controller.
1.3 Avoiding danger
The Daikin Altherma EHS(X/H) is state-of-the-
art and is built to meet all recognised technical
requirements. However, improper use may result
in serious physical injuries or death, as well as
property damage.
To avoid danger, only operate the Daikin
Altherma EHS(X/H):
– as stipulated and in perfect condition,
– with an awareness of safety and the hazards
involved.
This assumes knowledge and use of the con-
tents of this manual, of the relevant accident pre-
vention regulations as well as the recognised
safety-related and occupational health rules.
WARNING!
1.4 Proper use
The RoCon HP may be used only in Daikin
Altherma EHS(X/H) heat pumps that have been
approved for Daikin the regulating system-
RoCon. The Daikin RoCon HP may only op-
erated only according to the indications in this
manual.
Any other use outside the intended use is con-
sidered as improper. The operator alone shall
bear responsibility for any resulting damage.
For any work on the equipment, which extends
above and beyond the operation of the regu-
lating system, you must observe the details pro-
vided in the supplementary documents, particu-
larly with regard to safety instructions.
This equipment must only be used by
children aged 8 and above and by
persons with restricted physical, sensory
or mental capabilities or with a lack of ex-
perience and knowledge, if they are
under supervision or if they have been
instructed in the safe use of the
equipment and understand the dangers
arising therefrom. Children must not
play with the equipment. Cleaning or
user maintenance must not be carried
out by children without supervision.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
2 x Product description
2
Product description
The Controller RoCon HP is part of the Daikin
Altherma EHS(X/H).
It consists of the RoCon BM1 control panel to which
the actuators and sensors, as well as other compo-
nents in the Daikin RoCon regulating system, are con-
nected, and the RoCon B1 operating unit.
In this instruction manual we explain just the functions
and setting possibilities of the Controller. More infor-
mation on the Daikin Altherma EHS(X/H) and other
equipment components can be found in the supple-
mentary documents.
The electronic, digital Controller is able to automatically control all
heating, cooling and hot water functions for a direct heating
circuit, a storage tank charging circuit and optionally connectable
mixer module, depending on the heating unit in question.
It is responsible for all safety management functions of the
Daikin Altherma EHS(X/H). This executes a safety switch-off in
the event of a water shortage or undefined operating states.
A corresponding fault message shows the operator all the infor-
mation for fault causes.
All function settings for the Daikin Altherma EHS(X/H) and the
optional RoCon devices connected via the data bus are carried
out with the operating elements of the integrated RoCon B1
control panel and displayed in clear text display on a coloured
backlit display.
The regulation data bus can be used to connect the Daikin
Altherma EHS(X/H) to the following optional equipment:
–
EHS157034 room station
–
EHS157068 mixer module.
In addition, the RoCon HP control unit has a frost protection
function for the direct heating circuit and the storage tank
charging circuit, as well as an automatic function for heating
support (inclusion of an additional source of heat such as a wood-
burning boiler or solar installation).
The potential-free AUX switching contact can be used to carry out
different control functions in conjunction with external devices
(demand from an external heat generator, switching to bivalent
operating mode, external status display, etc.).
In addition, it also has several inputs for assessing external
control contacts (external operating mode switching or heat
demand, SMART GRID- and low-tariff EVU functions(1.
(1
Energy supply company (EVU) sends signals that are used for controlling the
power mains loading, and which have an influence on the cost of the power and
availability.
The weather-controlled flow temperature regulation can be opti-
mised with the RoCon OT1 optional external temperature probe
which can be installed on the north face of the building.
If the EHS157056 optional gateway is installed and connected to
the Internet, the Daikin Altherma EHS(X/H) can be conveniently
monitored and operated by remote control using a mobile phone
(app).
The Controller RoCon HP contains a timer which can be used to
set:
–
2 individually-adjustable timer programmes(2 for room heat-
ing and room cooling
(direct heating circuit),
–
2 individually-adjustable timer programmes for hot water gen-
eration,
–
1 individually-adjustable timer programme for an optional cir-
culation pump.
(2
Use of the timer programme for room cooling only possible in combination with
a connected room thermostat
Initial commissioning of the heating system is described in the in-
stallation manual for the Daikin Altherma EHS(X/H).
Certain menu items in the Controller RoCon HP are only acces-
sible to the specialist heating technician. This security measure
ensures that no undesirable malfunctions arise during operation
of the system through incorrect settings.
The EHS157034 room station has the same operating panel as
the Daikin Altherma EHS(X/H) B1 operating element integrated
in the RoCon B1.
All settings for the allocated heating circuit can be carried out in
the same way as the operating unit. With activated terminal
function, all operating possibilities that are available on the inte-
grated operating unit are available, with the exception of certain
special functions (e.g. Manual Operation).
An EHS157068 connected mixer module will also be operated,
after appropriate allocation, by the RoCon B1 control unit and/or
the EHS157034 room station.
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
7
3
Operation
3.1
General
DANGER!
If electrical components come into con-
tact with water, this can cause an elec-
tric shock as well as potentially fatal
injuries and burns.
● The displays and the buttons on the
Controller must be protected from
the effects of moisture.
● To clean the Controller use a dry
cotton cloth. Using aggressive
cleaning agents and other liquids
can cause damage to equipment or
lead to an electric shock.
Maximum energy utilisation
The most effective energy utilisation is achieved by the
Daikin Altherma EHS(X/H) at the lowest possible
return flow and hot water temperatures.
If an external heat generator (e.g. the optional Backup
Heater) is used at inflow target temperatures of over
50 °C, the efficiency (COP) of the Daikin
Altherma EHS(X/H) can be affected negatively
(depending on the outside temperature).
3.2
Display and operating elements
1
Clear text display
2
Setting: Configuration
3
Setting: Remote Param
4
Rotary switch
5
Setting: Info
6
Setting: Operating Mode
7
Setting: Set Temp Day
8
Setting: Set Temp Night
9
Setting: DHW Set Temp
10
Rotary button
11
Setting: DHW Install
12
Setting: Time Program
13
Exit button
Fig. 3-1
Arrangement of display and operating elements
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.2.1
Display
All the operating steps are supported by appropriate displays in a
clear text display on a coloured background.
Menu navigation is available in 7 different languages
(see section 3.4.8).
Malfunctions are generally indicated by a fault code and
a clear text fault message on the display.
For troubleshooting instructions refer to chapter 7.
The colour of the backlighting indicates the operational status
and the operational mode:
White:
Standard lighting, normal operational display.
Red:
Fault status, depending on the type of fault, the
Daikin Altherma EHS(X/H) continues to function with
restrictions.
Green:
Operating mode with operator authorisation.
Blue:
Operating mode with expert technician authori-
sation.
1
Date display
2
Status of refrigerant com-
pressor
3
Status display (e.g. Techni-
cian access rights active)
4
Display time
5
Current flow temperature
6
Status heating circuit
7
Current outdoor temperature
8
Active operating mode
9
Status of hot water genera-
tion
10
Current storage tank temper-
ature
Fig. 3-2
Display of the Controller - standard display
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
9
Explanation of symbols
Item
fig. 3-2
Symbol
Explanation
2
Flashing: Heat pump demand active
Permanently on: Refrigerant compressor is
working
2
No connection to the external heat pump
unit
3
Access Rights Expert active
(see section 3.6.1)
2 / 3
Air Purge active (see section 3.6.10)
2 / 3
Terminal function active (see section 3.4.9)
2 / 3
Frost protection function active
(see section 3.6.5)
2 / 3
"Party" temporary timer programme active
(see section 3.4.7)
2 / 3
"Away" temporary timer programme active
(see section 3.4.7)
2 / 3
"Holiday" temporary timer programme
active (see section 3.4.7)
2 / 3
"Vacation" temporary timer programme
active (see section 3.4.7)
2 / 3
Screed Program active (see section 3.6.13)
5
Direct heating circuit
–
Under normal conditions, the current
inflow temperature tV, BH is displayed.
–
In the case of no demand from the heat
pump, the abbreviation "ES" is dis-
played instead of the current flow tem-
perature.
The control system has switched to
energy saving mode (see
section 3.4.2). Superfluous elec-
tronic components are switched off.
5
Mixer circuit
The current inflow temperature of the se-
lected heating circuit is displayed.
5
Room temperature sensor
The current room temperature is displayed.
6
Heating circuit status
–
Heating circuit active (room heating
function)
–
Heating circuit active (room cooling
function)
–
Heating circuit not active (currently no
heat transfer in the heating circuit)
7
Outside temperature sensor
The current outside temperature is dis-
played.
8
Current operating mode (see section 3.4.2)
Standby active.
Reducing active.
Heating active.
Cooling active.
Summer active.
Automatic 1 active.
Automatic 2 active.
9
Domestic hot water generation active
Domestic hot water generation not active
10
Domestic hot water circuit status
The current storage tank temperature
tDHW1 is displayed.
Tab. 3-1
Explanation of display symbols
3.2.2
Operating elements
CAUTION!
Never operate the operating elements
on the controller with a hard, pointed
object. This can cause damage and can
cause the control unit to malfunction.
If special key combinations or extended key pushes are required
for certain function, a separate note is made in each specific
section of this description.
Rotary switch
The rotary switch is used to gain rapid direct access (main
function level) to frequently required functions and setting op-
tions.
Independent of the setting of the rotary switch, the
Daikin Altherma EHS(X/H) operates in accordance with
the operating mode set in the "Operating Mode"
switch position or that has been activated by a
special programme.
Action
Result
Rotating
Direct selection of the main function level allo-
cated to this switch position.
Tab. 3-2
Function of rotary switch
Item
fig. 3-2
Symbol
Explanation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
Rotary switch
The rotary switch can be used to navigate in the individual levels,
setting values can be selected, changed and these changes can
then be accepted by pressing briefly.
Action
Result
Rotating
To the right (+): Increased regulation
To the left (–): Reduced regulation
Pressing
Confirm, accept, selection and execute the
function.
Tab. 3-3
Functions of the rotary switch
Exit button
This button can be used to jump back to the previous display
within a menu display or a function / input can be interrupted.
This button can also be used to call up the special level
(see section 3.5).
Action
Result
Brief pressing.
–
Jump back to the previous display or pre-
vious level or
–
Cancellation of a special function or an
active temporary timer programme.
Pressfor more
than 5 secs.
–
Special level is called up.
Tab. 3-4
Functions of the exit button
3.3
Operating concept
The operating concept for controlling the RoCon HP is structured
in such a way that the frequently required settings options are ac-
cessible quickly and directly at the main function level (selection
using the rotary switch), while the less frequently required set-
tings options are arranged at a lower parameter level.
1
Info (section 3.4.1)
2
Operating Mode (section 3.4.2)
3
Set Temp Day (section 3.4.3)
4
Set Temp Night (section 3.4.4)
5
DHW Set Temp (section 3.4.5)
6
DHW Install (section 3.4.6)
7
Time Program (section 3.4.7)
8
Configuration (section 3.4.8)
9
Remote Param (section 3.4.9)
Fig. 3-3
Illustration of main function level (rotary switch position)
Certain functions and parameters are restricted by access au-
thorisation and can only be adjusted by the heating technician
(see section 3.6.1).
In normal operating mode the rotary switch should be in
position
.
After switching on and successful initialisation, the display auto-
matically shows the standard display with rotary switch
position
.
In the first commissioning, the setting for language selection is
displayed first.
●
Select the language using the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Adaption to the special installation configuration is
carried out in the "Configuration"
rotary switch
position (see section 3.4.8).
When the system is switched on, based on the stipulations set in
the Controller RoCon HP, it fully automatically regulates the
operation of the
–
room heating, room cooling and the
–
sanitary hot water generation.
Independent of the setting of the rotary switch, the
Daikin Altherma EHS(X/H) operates in accordance with
the operating mode set in the "Operating Mode"
switch position or that has been activated by a
special programme.
If the user enters a value manually, this setting remains active
until the user changes it or until the programme clock forces an-
other operating mode.
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
11
The operating mode can be affected by additional functions such
as:
–
Weather-controlled flow temperature regulation
–
Switching time program
–
Setting the temperature target value
–
Setting at the room station
–
Setting on room thermostat
–
Switch status at EXT input (external operating mode switcho-
ver)
–
Switch status at EBA input (external demand request)
–
Quite Mode
–
Interlink fct
–
Switch status at SMART GRID input (EVU function SMART
GRID)
–
Switch ststus at EVU input (EVU function HT/NT (low tariff) or
SMART GRID)
–
Defrosting function
–
Frost protection function
–
Screed function
–
Air Purge
–
Manual Operation
Button block
The operating panel on the RoCon HP can be blocked to prevent
inadvertent actuation (see fig. 3-4).
Unlocking can be carried out in the same way.
The prerequisite for this function is that, in the level "Setup", the
parameter [Keylock Function] is set to "On" (see chapter 6.2.1
tab. 6-1).
Keylock Function
On
Keylock Function
Keylock Function
Off
Fig. 3-4
Activating button lock (1.) and deactivating (4.)
3.4
Basic functions and operating modes
If the storage temperature falls below a certain
minimum value, the safety settings of the Daikin
Altherma EHS(X/H) prevent the operation of the heat
pump in the case of low external temperatures:
–
External temperature < -2 °C, minimum storage
temperature = 30 °C
–
External temperature < 12 °C, minimum storage
temperature = 23 °C.
Without backup heater:
The storage tank water must be heated to the minimum
required storage temperature by an external heater.
With backup heater (EKBUxx):
With an outdoor temperature < 12 °C and a storage
tank temperature < 35 °C, the backup heater (BUH) is
switched on automatically on in order to heat up the
storage tank water to at least 35 °C.
●
In order to accelerate the heating process with
the back-up heater, temporarily
–
Parameter [Function Heating ] = "1" and
–
Set parameter [Power DHW] to the maximum
value of the back-up heater.
–
Set rotary switch to the operating mode
and
parameter [1x Hot Water] to "On".
Automatic defrosting function
At low outdoor temperatures and corresponding humidity values,
the external heat pump unit may ice up. This icing impairs effi-
cient operation. The system detects this condition automatically
and starts the defrosting function.
During the defrosting function, heat is drawn from the hot water
storage tank and the backup heater is turned on if required.
Depending on the heat demand for the defrosting function,
heating of the direct heating circuit may be interrupted tempo-
rarily.
After 8 minutes at most, the system returns to normal mode.
3.4.1
System information (Info)
In this rotary switch position, the rotary switch can be used to call
up all the system temperatures, the type of Daikin
Altherma EHS(X/H), various software information and the oper-
ating statuses of all system components, one after the other.
The number of displayed parameters depends on the connected
components.
No settings can be made to these values.
●
Place the rotary switch in the "Info"
position.
Standard display is shown (see fig. 3-2).
●
Press the rotary switch briefly.
The parameter overview is displayed.
●
Select the desired information level with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
The value is displayed (for example, see fig. 3-6).
●
Select the individual information with the rotary switch.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in tab. 3-5 and in chapter 6.10.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
Display operating data overview
The current operating data for the Daikin Altherma EHS(X/H) are
shown on the RoCon HP Controller in the "Overview" information
level.
The display of the operating data is not divided into several
windows. By adjusting the rotary switch it is toggled between the
windows.
Short
designation
Explanation of the displayed value
Page 1
Mode
Current mode of the heat pump:
- - - : No heating or cooling demand
: Heating
: Cooling
: Domestic hot water generation
: Automatic defrosting function active
Ext
Current energy mode of the heat pump:
LT: EVU function HT/NT active and low tariff.
HT: EVU function HT/NT active and high tariff.
SGN: EVU function SMART GRID active, normal
mode.
SG1: EVU function SMART GRID active, discon-
nection: no heat pump operation, no frost
protection function.
SG2: EVU function SMART GRID active, switch-
on recommendation, mode with higher set
temperatures, cheap power.
SG3: EVU function SMART GRID active, switch-
on command and storage tank charging to 70 °C,
cheap power
- - -: No external mode active, heat pump works
in normal mode.
RT
Parameter [Room thermostat] / [Interlink fct]
= Off: - - -
Parameter [Room thermostat] = On:
–
: Heating or cooling demand
–
: No heating demand
Parameter [Interlink fct] = On (priority):
–
- - -: only frost protection
–
IL1: normal inflow target temperature
–
IL2:
–
increased inflow target temperature in
heating operation
–
decreased inflow target temperature in
cooling operation
Pump
Actual output of the internal heating circulation
pump in %
EHS
Current output of the backup heater in kW
BPV
Current position of the mixing valve 3UVB1
(100% = A, 0% = B)
Page 2
TV
Current inflow temperature after the plate heat
exchanger (tV1)
TVBH
Current heating inflow temperature or temp. after
heating support heat exchanger (tV, BH)
TR
Current heating return flow temperature (tR1)
Tdhw
Current temperature in domestic hot water
storage tank (tDHW1)
TA
Actual outdoor temperature (measured by op-
tional temperature sensor RoCon OT1)
V
Actual volume flow (flow rate) in the heating
system
Page 3
TVBH2
= TVBH
TR2
Current heating return flow temperature, sec-
ondary sensor (tR2)
Tdhw2
Current temperature in domestic hot water
storage tank, secondary sensor (tDHW2)
Tliq2
Current coolant temperature (tL2)
TA2
Actual outdoor temperature (measured by tem-
perature sensor of the external heat pump)
quiet
Shows the status of the whisper mode
Tab. 3-5
Description of the operating data displayed as an overview
Info
Overview
Water Pressure
Off
Fig. 3-5
Display operating data overview
Short
designation
Explanation of the displayed value
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
13
Displaying the water pressure
On the Controller RoCon HP, when it is switched on, you can
display the system pressure (water pressure) in the internal
circuit (direct heating circuit). The water pressure is available as
the first info parameter after the operating data overview
(see fig. 3-6).
The permissible range of water pressure during operation de-
pends on the Daikin Altherma EHS(X/H) and the heating system.
The set values and threshold values must only be changed by the
heating technician. If the water pressure falls below the minimum
value (set parameter value), it must be increased by topping up
the system (see installation instructions of the Daikin
Altherma EHS(X/H), chapter "Inspection and Maintenance").
The pressure limits for the safety switch-off and the set
pressure can be adjusted in the parameter settings in
level "System ".
Info
Overview
Water Pressure
T-HS
Water Pressure
Fig. 3-6
Info values display (e.g. system pressure)
3.4.2
Setting the operating mode
The selection of the operating mode with which the Daikin
Altherma EHS(X/H) is to operate is undertaken on the rotary
switch in the setting "Operating Mode"
.
The selected operating mode is activated by briefly pushing the
rotary switch.
Operating Mode
Standby
Reducing
Operating Mode
Heating
Cooling
Summer
Operating Mode
Summer
Automatic 1
Automatic 2
Operating Mode
Summer
Automatic 1
Automatic 2
Fig. 3-7
Switching the operating mode
(e.g.: from "Standby" to "Automatic 1")
●
Place the rotary switch in the "Operating Mode"
position.
An overview is displayed.
●
Select the desired operating mode with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Daikin Altherma EHS(X/H) operates in accordance with
the set operating mode.
The current operating mode is indicated by an appropriate
symbol in the standard display.
Operating mode Standby (Stand-by)
CAUTION!
A heating system that is not frost-pro-
tected can freeze in cold weather and be
damaged.
● Drain the water out of the heating
system if there is a danger of frost.
● If the heating system is not drained
and there is a risk of frost, the power
supplies must be secured and the
external main switch must remain
switched on.
In this mode, the Daikin Altherma EHS(X/H) is shifted to the
stand-by mode. The frost-protection function
(see section 3.6.5) remains in place. In order to maintain this
function, the system must not be disconnected from the mains!
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
All controllers integrated into the RoCon-system via the CAN bus
are also switched at a higher level to the operating mode
"Standby".
Fig. 3-8
Standard display in "Standby" operating mode
(above the frost-protection limit)
In the "Standby" operating mode, the heat pump and
any optionally connected backup heaters are isolated
from the power supply (Energy saving mode) when
the following conditions are met:
–
The outdoor temperature sensor (RoCon OT1) is
connected and correctly parametrised in the system
configuration (parameter [Outside Config] = On),
–
The outdoor temperature is over 8 °C,
–
There is no heating command,
–
The frost protection function is not active in any of
the connected heating circuits, and
–
Daikin Altherma EHS(X/H) has been switched on
for at least 5 mins.
Operating mode Reducing
Reduced heating mode (lower set room temperature) in ac-
cordance with the target flow temperature set for economy mode
in the parameter [T-Reduced] (see section 3.4.4).
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
Operating modes Heating, Cooling
Heating or cooling operation in accordance with the room tem-
perature set in the parameter [T-Room 1 Setpoint]
(see section 3.4.3).
A connected outdoor temperature sensor (weather-controlled
flow temperature regulation) or a connected room station will also
influence the set flow temperature regulation (requirements:
Parameter [HC Function] = On).
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
Operating mode Summer
Hot water generation according to the set target domestic hot
water temperatures and switching cycles in the hot water time
programme [DHW Program 1] (see section 3.4.5).
All controllers integrated into the RoCon-system via the CAN bus
are also switched at a higher level to the operating mode
"Summer".
Operating mode Automatic 1 (Timer programme)
Automatic heating and economy mode in accordance with the
permanent timer programmes (see section 3.4.7):
–
[HC Program 1]
–
[DHW Program 1]
Operating mode Automatic 2 (Timer programme)
Automatic heating and economy mode in accordance with the
permanent timer programmes (see section 3.4.7):
–
[HC Program 2]
–
[DHW Program 2]
If, in the active operating mode, the hot water gener-
ation is in setback, you can use the rotary switch
to
set temporary "DHW Reheating" without having to
change any other standard settings (see section 3.4.6).
Switching contact for external operating mode
switching
Via a potential-free switching contact connected to con-
nection J8 of the Daikin Altherma EHS(X/H) at ter-
minals "EXT" and switched with a resistance we can
also carry out a changeover of the operating mode from
an external device (e.g. a modem, …) (see tab. 3-6).
Operating mode
Resistance
Tolerance
Standby
< 680 Ω
± 5 %
Heating
1200 Ω
Reducing
1800 Ω
Summer
2700 Ω
Automatic 1
4700 Ω
Automatic 2
8200 Ω
Tab. 3-6
Resistance values for the evaluation of the EXT signal
The resistances specified in tab. 3-6 work at a toler-
ance range of 5 %. Resistances outside of this toler-
ance ranges are interpreted as open input. The heat
generator resets to the previously active operation
mode.
At resistance values higher than the value for
"Automatic 2", the input is not considered.
If several switching contacts are to be connected to the
Daikin Altherma EHS(X/H) (e.g. SMART GRID, Room
thermostat), the associated functions can have a higher
priority than the external operating mode switching.
The operating mode requested by the EXT switching
contact might then not be activated or may be activated
later.
In addition to these operating modes there are various different
temporary heating programmes available (see tab. 3-7), which
run according to priority after they have been activated.
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
15
* only with expert code.
Tab. 3-7
Overview of temporary timer programmes
If a temporary timer programme (DHW Install, Party,
Away, Holiday, Vacation, Screed) is started during the
selected operating mode, the regulation will take place
with preference according to the settings of this timer
programme.
3.4.3
Temperature setting Daytime room temperature
The set room temperatures for room heating during the day are
determined in the rotary switch setting
.
●
Place the rotary switch in the "Set Temp Day"
position.
An overview is displayed.
The end figures of the parameter designations (1 - 3)
within this rotary switch setting designate the associ-
ation with each individual cycle of the timer programme.
●
Select the temperature block to be set with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Settings are displayed.
●
Set the temperature.
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.5.
3.4.4
Temperature setting Economy mode
The set room temperatures for room heating in economy mode
are determined in the rotary switch setting
.
●
Place the rotary switch in the "Set Temp Night"
position.
An overview is displayed.
●
Select the parameter to be set with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
–
[T-Reduced]: Set value for "Reducing" operating mode or
setback by a permanent timer programme.
–
[T-Absence]: Set value for temporary heating / cooling
programmes ("Away" and "Vacation").
Settings are displayed.
●
Set the temperature.
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.6.
3.4.5
Temperature setting hot water generation
The hot water set temperatures for hot water generation for each
individual timer programme are determined in the rotary switch
setting
.
●
Place the rotary switch in the "DHW Set Temp"
position.
The end figures of the parameter designations (1 - 3)
within this rotary switch setting designate the associ-
ation with each individual cycle of the timer programme.
●
Select the temperature block to be set with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Settings are displayed.
●
Set the temperature.
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.7.
3.4.6
Unscheduled hot water generation
You can charge the hot water up manually outside a hot water
timer programme to the preset temperature set in parameter
[T-DHW Setpoint 1] in the rotary switch position
. Heating up
is carried out as a priority and independently of any other heating
programmes.
●
Place the rotary switch in the "DHW Install"
position.
An overview is displayed.
●
Select the parameter to be set with the rotary switch.
–
[1x Hot Water]: Activating one-off hot water generation.
●
Confirm the changes with a brief push of the rotary switch.
●
Setting parameters
●
Confirm the changes with a brief push of the rotary switch.
Begin unscheduled hot water generation.
After this temporary function has expired, the Controller
automatically jumps back to the previously active oper-
ating mode. The rotary switch should therefore be re-
turned to the position "Info"
after activation.
The function is subject to time limits.
It is interrupted at the latest after the maximum charging
time set in the parameter [Max DHW loading ] and
cannot be restarted once more until the blocking time
set in the parameter [DHW Off Time] has expired
(see chapter 6.2.4).
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.3.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.4.7
Switching time program
Various different timer programmes are available, that are set in
the factory, but which can be adjusted to suit, to provide conven-
ient and individual room and hot water temperature control.
The timer programmes regulate the associated heating circuit,
the storage tank charging circuit and an option connected circu-
lation pump in accordance with the stipulated switching times.
Adjustment
In the rotary switch position
we set the time intervals for
the heating circuit, the integrated hot water generation and the
optional circulation pump.
●
Place the rotary switch in the "Time Program"
position.
An overview is displayed.
●
Select the timer programme to be set with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Settings are displayed.
●
Select and change the value to be set with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.8.
Permanent timer programmes
For the connected heating circuits and the storage tank charging
circuit, timer programmes regulate the heating circuit tempera-
tures or the operating times for the circulation pump in ac-
cordance with the stipulated switching cycles. The switching
cycles are saved in time blocks for which various set tempera-
tures apply.
In the switching cycles the heating system is regulated differen-
tiated into day and economy mode.
The target room temperatures for these timer programmes are
set in the rotary switch settings "Set Temp Day"
, "Set Temp
Night"
and "DHW Set Temp 1"
.
The following switching time programmes are available:
–
2 timer programmes for the heating circuit, each with
3 possible time cycles
–
[HC Program 1]
–
[HC Program 2]
A separate input for each individual day of the week is
possible, or in blocks of "Monday to Friday", "Saturday
to Sunday" and "Monday to Sunday".
Programme
Time period
switching cycle
HC Program 1
Single day of the week
(Monday, Tuesday ...)
1st
.
2.
3.
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
Working week
(Monday to Friday)
1st
.
2.
3.
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
Weekend
(Saturday to Sunday)
1st
.
2.
3.
07:00 -> 23:00
--:-- -> --:--
--:-- -> --:--
Entire week
(Monday to Sunday)
1st
.
2.
3.
06:00 -> 22:00
--:-- -> --:--
--:-- -> --:--
HC Program 2
See HC Program 1
1st
.
2.
3.
See
HC Program 1
Tab. 3-8
Menu structure heating circuit timer programme
Time settings for one switching cycle in one weekday or
block programme are also adopted for other time pe-
riods, provided that they affect the same weekdays.
Examples referring to tab. 3-8:
a) For the single working day "Monday" the start time
for the 1st switching cycle changed from 06:00 to
05:00.
In the time period "Working week" and "Entire
week", the 1st. time block switching cycle also
changed from 06:00 to 05:00.
b) For the time period "Weekend", the start time for the
1st switching cycle changed from 07:00 to 08:00.
In the individual weekdays "Saturday" and "Sun-
day", the 1st switching cycle also automatically
changed from 07:00 to 08:00.
c) For the time period "Entire week", the end time in
the 1st. time block switching cycle changed from
22:00 to 21:30.
In all the weekdays the 1st switching cycle is
also changed from 22:00 to 21:30.
–
2 timer programmes for the hot water circuit, each with
3 possible switching cycles
–
[DHW Program 1]
–
[DHW Program 2]
The setting and input structure of the timer programmes
are identical to the ones for the heating circuit timer pro-
gramme (see also tab. 3-8).
–
1 timer programme for one optionally connected circula-
tion pump with 3 individual possible switching cycles
–
[Circulation Time]
The setting and input structure of the timer programmes
are identical to those for the heating circuit timer pro-
gramme (see also tab. 3-8).
For further instructions concerning settings for an op-
tional circulation pump, see section 3.6.15.
Saved switching time programmes can be changed at any time.
To provide a better overview, we recommend making a record of
the programmed switching times and keeping it in a safe place
(see chapter 9.1.1).
The permanent timer programmes are preset as per tab. 3-9.
Switching cycle 1
Switching cycle 2
Switching cycle 3
Time period
On
Off
On
Off
On
Off
Room heating / room cooling
Temperature setting
[T-Room 1 Setpoint]: 20 °C
[T-Room 2 Setpoint]: 20 °C
[T-Room 3 Setpoint]: 20 °C
[T-Reduced]: 10 °C
"HC Program 1"
Monday - Friday
06:00
22:00
- - : - -
- - : - -
- - : - -
- - : - -
Saturday, Sunday
07:00
23:00
- - : - -
- - : - -
- - : - -
- - : - -
"HC Program 2"
Monday - Friday
06:00
08:00
- - : - -
- - : - -
- - : - -
- - : - -
Saturday, Sunday
07:00
23:00
- - : - -
- - : - -
- - : - -
- - : - -
domestic hot water generation
Temperature setting
[T-DHW Setpoint 1]: 48 °C
[T-DHW Setpoint 2]: 48 °C
[T-DHW Setpoint 3]: 48 °C
"DHW Program 1"
Monday - Sunday
00:00
24:00
- - : - -
- - : - -
- - : - -
- - : - -
"DHW Program 2"
Monday - Friday
05:00
21:00
- - : - -
- - : - -
- - : - -
- - : - -
Saturday, Sunday
06:00
22:00
- - : - -
- - : - -
- - : - -
- - : - -
"Circulation Time"
Monday - Friday
05:00
21:00
- - : - -
- - : - -
- - : - -
- - : - -
Saturday, Sunday
06:00
22:00
- - : - -
- - : - -
- - : - -
- - : - -
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
17
Tab. 3-9
Factory setting for the permanent switching time programmes
Temporary timer programmes
For a specific situation there are 4 temporary programmes
available, which deactivate the permanent timer programmes
or the current operating mode for the duration of their validity.
The symbol of the temporary time program is displayed in the
header line of the standard display, as long as the time program
is active.
The following temporary time programmes may be
interrupted at any time by manually changing the oper-
ating mode.
1.
[Party]: Immediate one-off extension of the room
heating
a) If an automatic programme is activated, the last
applicable switching cycle is always extended. In the time
before switching cycle 1, the target room temperature set
in the parameter [T-Room 1 Setpoint] applies.
b) In all other operating modes, the target room temperature
set in the parameter [T-Room 1 Setpoint] applies.
–
The hot water generation is not affected.
–
The time programme runs for the set time period after acti-
vation.
2.
[Away]: Immediate one-off setback up to 6 hours
–
The system operates in economy mode according to the
room temperature set in the rotary switch setting "Set
Temp Night"
in the parameter [T-Absence].
–
The hot water generation is not affected.
–
The time programme runs for the set time period after acti-
vation.
3.
[Holiday]: One-off calendar-controlled presence.
–
The system operates exclusively in accordance with the
"Sunday" settings in the [HC Program 1].
–
The hot water generation operates exclusively in accord-
ance with the "Sunday" settings in the [DHW Program 1].
4.
[Vacation]: One-off calendar-controlled reduction.
–
The system only operates in economy mode according to
the room temperature set in the rotary switch setting "Set
Temp Night"
in the parameter [T-Absence].
–
Hot water generation according to the set temperatures
and switching cycles in the hot water time programme
[DHW Program 1] (see section 3.4.5).
–
The calendar-controlled programme [Vacation] is not
started if the operating mode [Standby] or [Manual Oper-
ation] is active on the set start date.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.4.8
System settings
We undertake the basic settings for the Controller RoCon HP and
the system configurations for the installation environment of the
Daikin Altherma EHS(X/H), the direct heating circuit, the hot
water generation and any optionally connected components in
the rotary switch setting "Configuration"
.
Depending on access authority (user or expert), various different
parameters are available. Certain parameters are only acces-
sible to the heating expert.
LCD Display, Language, Date, Time setting
An internal pre-programmed calendar ensures auto-
matic time reset at the annually recurring
summer/winter time changes.
●
Place the rotary switch in the "Configuration"
position.
An overview is displayed.
●
Select the "Setup" level with the rotary switch.
An overview is displayed.
●
Select the parameter [LCD Brightness] and [LCD Illum Time]
using the rotary switch and change if required.
●
Use the rotary switch to select and confirm the [Language],
[Date] or [Time] parameters.
●
Select and change the value to be changed within the
individual display using the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in section 3.6 and in chapter 6.2.
3.4.9
Terminal function
In the rotary switch setting "Remote Param"
we can also
operate and parametrise other devices integrated via the CAN
bus in the RoCon system (regulating components mixer module
or heat exchanger), provided that the individual component has
the necessary authority (see also chapter 4.3).
After activation of the "Bus -
Scan" a list of the equipment
that was recognised is shown
for selection in the display (ex-
ternal equipment and local
equipment).
After selection and confirming
an external device, the terminal
function for this device is acti-
vated and the associated
standard display for this device
is shown in the display.
The operating component is
then in terminal mode.
Remote Param
Bus - Scan
No selection
Fig. 3-9
Display of the level "Re-
mote Param" at commis-
sioning or temporary
disconnection from the
mains
The local control element acts as the remote control for the ex-
ternal equipment. In this case all the control functions are pro-
vided and saved 1:1 as on the external equipment.
The various different application and parametrisation possibilities
for using the devices and operating components combined in the
RoCon system are described in chapter 4.3.
Remote Param
Bus - Scan
No selection
Remote Param
Bus - Scan
No selection
Remote Param
No selection
Contr BM1/BE1 #X
Mix Valve #X
Remote Param
Contr BM1/BE1 #X
Mix Valve #X
Remote Param
Contr BM1/BE1 #X
Mix Valve #X
B1
Operating component RoCon B1 B1 of the
Altherma EHS(X/H)
Bus
CAN-Bus (connection line between RoCon devices
and operating components)
H1
Direct heating circuit (e.g. radiators)
H2
Mixed heating circuit (e.g. underfloor heating)
M1
Mixer module EHS157068
U1
Room station EHS157034
WE1
Heat generator Altherma EHS(X/H)
Fig. 3-10 Example for "Bus - Scan" on a heating system with 1 heat gen-
erator, 1 mixer, 1 room station and activation of the terminal
function for remote control of the mixer module
During this activated terminal function, the header of the display
carries additional information on the remotely controlled
equipment; the symbol
#X is displayed, where "X" indicates
the bus ID setting for the remotely controlled equipment.
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
19
The displayed values and symbols are always taken over from
the selected equipment (such as the mixer circuit infeed temper-
ature of the mixer module EHS157068 with device ID 1).
Fig. 3-11 Display example for a remotely controlled mixer module
For operation of the local equipment, this must be activated again
in the selection list (parameter [No selection]).
If the message "n. A." is displayed at rotary switch set-
ting
, the control unit has yet to be assigned a valid
terminal address.
If the message "n. A." is still displayed it may be nec-
essary to update the device software before the ter-
minal function can be used. Contact the Daikin Service
Team in such cases.
Activating / deactivating normal operation
Requirement: A valid terminal ID is assigned to the RoCon B1
control element of the Daikin Altherma EHS(X/H) or the
EHS157034 room station.
For setting the terminal address of optional connected
equipment, see chapter 4.4 or the instruction handbook
supplied for the respective equipment.
●
Place the rotary switch in the "Remote Param"
position.
The level "Remote Param" is displayed.
●
Select the parameter [Bus - Scan] with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
The context menu is displayed.
●
Use the rotary switch to select the parameter [Bus - Scan] and
confirm with "Yes".
Bus - Scan is performed.
An overview of all the equipment found is displayed
(example see fig. 3-10).
●
Use the rotary switch to select the equipment for which the
terminal function is to be performed.
●
Confirm the changes with a brief push of the rotary switch.
The local control element acts as the remote control for
the external equipment.
To end terminal mode and restore operation of the assigned
equipment to the control element, at the level "Remote Param"
the parameter [No selection] must be selected and acknowl-
edged.
After interim isolation from the power supply, at the
level "Remote Param", we always show the display as
shown in fig. 3-9.
In order to be able to use the terminal function for con-
nected equipment, a new Bus - Scan must be carried
out.
Communication between the RoCon system compo-
nents continues to function, even without a Bus - Scan,
and previously made settings remain active.
Activation of the terminal function is carried out as
shown in fig. 3-10, but, after confirmation of the display
"Bus - Scan", you must select the parameter [New
scan?] with the rotary button, and confirmed with "Yes".
3.4.10 Quite Mode
Quite Mode means that the exterior heat pump unit is operating
at reduced output. This reduces the operating noise caused by
the exterior heat pump unit.
CAUTION!
Active Quite Mode reduces the perfor-
mance in room heating and room cooling
operation with the result that it may no
longer be possible to reach the preset
target temperatures.
● With outside temperatures below
freezing, there is a risk of material
damage caused by frost.
Quite Mode activation / deactivation
●
Place the rotary switch in the "Configuration"
position.
An overview is displayed.
●
Select the "System " level with the rotary switch.
An overview is displayed.
●
Select the parameter [Quite Mode] with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
The setting for the parameter is displayed.
●
Setting parameters
–
Parameter [Quite Mode] = 0: deactivated
–
Parameter [Quite Mode] = 1: permanently activated
–
Parameter [Quite Mode] = 2: only activated at night
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.2.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.4.11 SMART GRID (SG)
WARNING!
There is a danger of scalding at target
hot water temperatures over 60°C.
This is possible as the electric utilities
company (EVU) is entitled to control the
electricity consumption optimally in
accordance with supply and demand in
the SMART GRID regulations.
Due to the forced charging, the target hot
water temperature in the hot water
storage tank can reach over 60°C.
This storage tank charging even takes
place when the "Standby" operating
mode it set.
● Install scald protection in the hot
water distribution line (e.g. VTA32,
15 60 15 + Screw connection
set 1",
15 60 16).
You will need a special electric meter with an SG receiver for this
function, and the Daikin Altherma EHS(X/H) must be connected
to it.
As soon as the function is activated by the parameter [SMART
GRID] = 1, the heat pump is moved to an operating mode in ac-
cordance with tab. 3-10, depending on the signal from the energy
supply company.
Signal 2)
Cost of
electricity
Effect on
EVU
SG
Hot water
Heating
1
0
- - -
No operating
mode 1)
No operating
mode 1)
0
0
normal
Normal operating
mode
Normal operating
mode
0
1
low
The switch-on rec-
ommendation and
set value storage
tank temperature is
increased, depend-
ing on the parameter
[Mode SG]
The switch-on rec-
ommendation and in-
flow target
temperature are in-
creased depending
on the parameter
[Mode SG]
1
1
very
low
Switch-on command
and set value of stor-
age tank tempera-
ture is set to 70 °C
Switch-on command
for storage tank
charging
1)
No frost-protection function (see section 3.6.5).
2)
Switch contacts at input J8 of the circuit board RoCon BM1 closed (1) or
opened (0).
Tab. 3-10 Utilisation of the SG signal
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.1.
3.5
Special functions
In the "Special Level" we can carry out various different func-
tions that are usually used by the heating expert.
The following special functions are possible:
–
Manual mode (see section 3.5.1).
–
Message display (see section 7)
–
Resetting to factory settings (see section 3.6.12)
More detailed explanations of these functions can be found in chapter 6.11.
The call-up of special functions does not depend on the
setting on the rotary switch.
●
Depress the exit button for at least 5 secs.
Menu "Special Level" is displayed.
●
Select the programme to be started with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
The selected programme starts.
●
Cancellation and jump back by:
–
Pressing the exit button again, or
–
Briefly pressing the rotary switch or
–
selecting a different menu using the rotary switch.
3.5.1
Manual Operation
Manual Operation is used to regulate the Daikin
Altherma EHS(X/H) manually to a specific flow temperature.
The manual mode should only be used for diagnostic purposes.
With hydraulically controlled priority operation for the hot water
generation you must make sure that the inflow target temperature
set in manual mode is adequate to achieve the stored hot water
set temperature (parameter [T-DHW Setpoint 1]).
●
Depress the exit button for at least 5 secs.
Menu "Special Level" is displayed.
●
Select the programme "Manual Operation" with the rotary
switch.
●
Confirm the changes with a brief push of the rotary switch.
"Manual Operation" active.
●
Set the inflow target temperature with the rotary switch.
Do not confirm the setting with the rotary switch,
as this will close the programme.
During active manual mode the hot water is consistently
regulated to the parameter value for the first target hot
water temperature ([T-DHW Setpoint 1]).
The button block (if it was activated from the start of this
function), is activated again within 2 seconds in order to
prevent inadvertent termination of the function by operat-
ing the Controller RoCon HP.
●
Cancellation and jump back by:
–
Pressing the exit button again, or
–
Briefly pressing the rotary switch or
–
selecting a different menu using the rotary switch.
If the manual mode is closed, the Controller RoCon HP
automatically switches to the operating mode "Standby".
Fig. 3-12 Brief symbol-based instructions for manual mode
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
21
3.5.2
Reference run 3-way diverter valve
The positions of the two 3-way diverter valves 3UVB1 and
3UV DHW in the Daikin Altherma EHS(X/H) are regulated be-
tween their two basic settings in a step-less manner for optimised
energy utilisation (e.g. heating support function).
The two 3-way diverter valves are always automatically moved,
on days of the week "Monday", "Wednesday" and "Friday", by
11:00 in each case, to their base position (bypass - way AB-A
open).
This function can take up to 5 minutes. It is rigidly programmed
and cannot be changed.
3.6
Special system settings
The Controller RoCon HP already has the basic configuration for
the Daikin Altherma EHS(X/H). However, it needs to be adapted
to the optionally connected accessories and the installation envi-
ronment during initial commissioning.
Adaption is carried out via the setting of parameters in the rotary
switch setting "Configuration"
.
Navigating with the rotary switch accesses either the next deeper
level or directly to the appropriate parameter.
3.6.1
Access Rights (Technician password)
Certain settings are restricted by Controller access rights.
In order to gain access to these setting values (parameters) you
need to enter the expert "Setup" code in the level.
The fig. 3-13 shows the fundamental procedure for entering the
access code. The expert code will be advised to the expert
company in a separate letter.
Configuration
Setup
System
Access Rights
User
Access Rights
Expert
Setup
Language
Date
Setup
Keylock Function
Access Rights
Outdoor type
Access Rights
Access Rights
Access Rights
Fig. 3-13 Entering the access code
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.6.2
Heat curve
Caution - danger of overheating with
underfloor heating!
In the event of a fault, or in hand mode,
damage may be caused to the screed,
the structure of the floor and the under-
floor heating system by overheating.
● Before initial commissioning of the
underfloor heating system, set the
maximum permissible system
temperature Controller RoCon HP
(parameter [T vbh1 max]) in the
maximum temperature limit in the
Control RoCon HP (parameter [Max
T-Flow]).
● Connect the overheat protection
switch (customer) on the "EXT" plug
connection to the external operating
mode switch so that the Daikin
Altherma EHS(X/H) is in operating
mode "Standby" or "Summer"
(see section 3.4.2).
In parameter [Room thermostat] = On
or parameter [Interlink fct] = On, the
overheat protection switch must be
connected so that the switching con-
tact of the room thermostat is inter-
rupted.
● If the underfloor heating system is
also used for room cooling, the
connection notes from the previous
section are also valid for the
connection of a customer-provided
humidity protection switch.
With the heating characteristic curve, the inflow target temper-
ature is adjusted to building conditions in accordance with the rel-
evant external temperature (weather-controlled flow temperature
regulation, see section 3.6.4). Generally speaking, the steepness
of the heating characteristics describes the ratio of the flow tem-
perature change to the external temperature change.
The heating characteristic curve applies within the minimum and
maximum temperature limits that have been set for the corre-
sponding heating circuit. The room temperature measured in the
living area may differ from the desired room temperature; these
deviations can be kept to a minimum by installing a room station
or a room thermostat.
The Controller is configured in the factory so that the heating
curve does not adjust itself during operation.
The automatic heat curve adaptation can be activated
(parameter [HC Adaption]) if the room station (EHS157034) is
connected (see section 3.6.4).
Starting conditions for the automatic heating curve adaption:
–
Outdoor temperature < 8 °C
–
Operating mode is automatic (I or II)
–
Duration of setback phase at least 6 hours
If an automatic heat curve adaption is not activated, the heat
curve can be set manually by adjusting the parameter [Heat-
Slope]).
Manually adjusting the heating curve
Do not make any corrections to the set values for 1 - 2
days, and then only make them in small increments.
●
Deactivate additional heat sources (e.g. fireplaces,
direct solar radiation, open windows).
●
Fully open any existing radiator thermostat valves
or setting drives.
●
Activate the operating mode "Heating".
Approximate setting values:
–
Radiator: 1.4 to 1.6.
–
Underfloor heating system: 0.5 to 0.9.
T-Outside lim night
Heat-Slope
Room Influence
Heat-Slope
Heat-Slope
Heat-Slope
HC Configuration
Insulation
Heating
Cooling
Fig. 3-14 Manual setting of the heat curve (shown for "User" access
rights)
TA
External temperature
TR
Room temperature set value
TV
Flow temperature
Fig. 3-15 Heat curves
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
23
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.
3.6.3
Cooling characteristic curve
Caution! - risk of condensation!
In the event of a fault or wrong setting of
parameters, damage may be caused to
the screed, the structure of the floor and
the underfloor heating system by con-
densation.
● Before initial commissioning and
activation of cooling operation, set the
maximum permissible system
temperature in the minimum temper-
ature limit in the Controller RoCon HP
(parameter [Min T-Flow Cooling]).
With the cooling characteristic curve, the inflow target temper-
ature is adjusted to suit building conditions in accordance with the
relevant external temperature (weather-controlled flow temper-
ature regulation, see section 3.6.4). Warmer outdoor tempera-
tures result in a colder inflow target temperature and vice versa.
Conditions for cooling operation:
–
Outside temperature > target room temperature setting
–
Outside temperature > [Start T-Out Cooling] parameter set-
ting
–
Operating mode "Cooling" activated.
a) with the rotary switch in the "Operating Mode"
position or
b) via the room thermostat function (cooling
switching
contact closed)
–
No heating demand in the RoCon system of the heating
installation.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
The cooling characteristic curve is specified using the following
four parameters:
1. [Start T-Out Cooling]
2. [Max T-Out Cooling]
3. [T-Flow Cooling start]
4. [T-Flow Cooling max]
During the weather-controlled flow temperature regulation, the
user can adjust the inflow target temperature using the parameter
[Cooling Setpoint adj] by a maximum of 5 K up or down.
The lower temperature limit is limited by the parameter [Min T-
Flow Cooling].
1
Parameter [Start T-Out Cooling]
2
Parameter [Max T-Out Cooling]
3
Parameter [T-Flow Cooling start]
4
Parameter [T-Flow Cooling max]
5
Parameter [Min T-Flow Cooling]
6
Target room temperature
7
Cooling operation possible
TA
External temperature
TV
Flow temperature
―
Cooling characteristic
curve
---
Possible parallel dis-
placement of the cool-
ing characteristic
curve
Fig. 3-16 Parameter-dependency of characteristic cooling curve
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.3.
If the average outdoor temperature, with the activated
operating mode "Cooling", falls below 4 °C, the operat-
ing mode automatically switches to "Heating".
Automatic switching of the operating mode to "Cooling"
again can only take place if:
–
a room thermostat is connected to the plug connec-
tion J16 (cooling
) and
–
the switch contact on the room thermostat is closed
and
–
the average outdoor temperature is over 10 °C
again.
3.6.4
Weather-controlled flow temperature regulation
If the weather-controlled flow temperature regulation is active,
the inflow target temperature (see info parameter [T-HS Set-
point], section 6.10) is determined automatically in accordance
with the set heating/cooling curve depending on the outside tem-
perature.
In delivery status, this function is activated. It can only be deacti-
vated or reactivated with the technician code (set point control).
The weather-controlled flow temperature regulation can be opti-
mised with the RoCon OT1 optional external temperature probe,
which can be installed on the north face of the building. If no
RoCon OT1 is installed, the Controller RoCon HP uses the value
for the outside temperature measured in the exterior heat pump
unit.
If the room station (EHS157034) is additionally connected to the
Daikin Altherma EHS(X/H), the inflow target temperatures will be
controlled dependent on the weather and room temperature
(see tab. 6-3 / tab. 6-16, parameter [Room Influence]). Activation
and deactivation of this function takes place via the parameter
[HC Function] in the rotary switch position "Configuration"
in level "HC Configuration".
–
Parameter [HC Function] = 0: Weather-controlled flow tem-
perature regulation
–
Parameter [HC Function] = 1: Regulation according to fixed
inflow target temperature
–
In heating mode: parameter [T-Flow Day] or parameter
[T-Flow Night]
–
In cooling mode: parameter [T-Flow Cooling]
The weather-controlled flow temperature regulation
has no influence on the set flow temperature in the
event of a demand from the hot water circuit.
If a mixer module
is connected
The setting of the heating/cooling curves and the activation of the
weather-based flow temperature regulation for the assigned
heating circuit is performed in the same way as described above.
There is the option of operating the assigned heating circuit as a
a) Mixer extension
The outside temperature determined by the outside
temperature sensor connected to the Daikin
Altherma EHS(X/H) is transmitted to the mixer module via the
CAN bus.
or as
b) Mixer extension with zone regulation
A separate outside temperature sensor (RoCon OT1) must
be connected to the mixer module. The assigned heating cir-
cuit is regulated based on the relevant outside temperature
for this zone.
When the terminal function is activated, the mixer module is op-
erated via the RoCon B1 control element of the Daikin
Altherma EHS(X/H), and the settings for the assigned heating
circuit are performed.
In conjunction with the EHS157034 room station, the mixer
module can also autonomously control the assigned heating
circuit, fully independently of the Daikin Altherma EHS(X/H).
If the message "n. A." is displayed at the rotary switch
setting
, the control unit has yet to be assigned a
valid terminal address.
If the message "n. A." is still displayed it may be nec-
essary to update the device software before the ter-
minal function can be used. Contact the Daikin Service
Team in such cases.
More detailed explanations and possible setting values for this function can be seen
in sections 6.2.3 and 6.13.2.
3.6.5
Frost protection function
If the outdoor temperature is below the parameter value [T-Frost
Protect], the integrated heating circulation pump is switched on in
order to prevent the heating system from freezing.
In addition, the inflow, storage tank and connected room temper-
ature sensors are continually monitored. If the temperature
measured by any of these sensors drops below 7°C (in the case
of room temperature: 5 °C), the frost protection function is auto-
matically activated.
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
25
When the frost protection function is active, the Controller
RoCon HP standard display shows the
symbol alongside the
time.
If the inflow heating temperature drops below 7 °C, the Daikin
Altherma EHS(X/H) heats up until the temperature reaches at
least 12 °C once more.
The function ceases once the outside temperature has risen to
the set parameter value [T-Frost Protect] + 1 K is reached and
there are no other activation conditions present.
Off-peak tariff activated;
–
parameter [HT/NT Function] = 3
or
–
parameter [SMART GRID] = 1,
the heat pump operation can be completely switched
off by the energy supply company for a limited period of
time. In such cases, no additional heating is carried out
and the internal device heating circulation pump is not
switched on, even in frost-protection conditions.
These situations can arise when the "Overview" infor-
mation level (see section 3.4.1) in the operating data
field "Ext" displays the value "HT" or "SG1".
3.6.6
Interlink function
Caution!
Incorrect flow temperatures can result in
damage to the underfloor heating sys-
tem or the build-up of condensation on
cooling surfaces.
● Limit infeed target temperatures to
suitable ranges.
● Heat distribution areas with different
design temperatures should be
installed as hydraulically separate
heating circuits.
Heating circuits with limited infeed tar-
get temperatures should possibly be
installed as mixing circuits controlled
by mixer modules.
Setting of the parameter [Interlink fct] = On offers the possibility
of the Daikin Altherma EHS(X/H) integrating two different infeed
target temperatures into the control system.
This applies both to a weather-controlled controller and a con-
troller using a fixed inflow target temperature (see section 3.6.4).
A possible use for this might be the additional integration of
aFWXV(15/20)AVEB in a surface heating and cooling system.
Requirement: 2 switching contacts (e.g. room thermostats) need
to be connected to plug connection J16 on the Daikin
Altherma EHS(X/H).
–
Parameter [Interlink fct] = Off: deactivated
–
Parameter [Interlink fct] = On: Evaluation of
and cooling
switching contacts at plug connection J16 on the
RoCon BM1 circuit board.
Activation of cooling mode only possible by changing operat-
ing mode to "Cooling" (see section 3.4.2).
Setting for the parameter [Room thermostat] no longer evalu-
ated.
a) Open switching contacts: only frost protection active.
b) Operating modes "Heating" or "Automatic 1" /
"Automatic 2" active during switching cycles in day mode.
–
Closed switching contact heating
= IL1:
The system operates according to the normal infeed tar-
get temperature according to the parameter settings in
"HC Configuration" > "Heating".
–
Closed switching contact cooling
= IL2:
The system operates according to the increased inflow
target temperature (normal inflow target temperature +
value of parameter [T-Flow CH adj]. Priority if both switch-
ing contacts are closed.
c) "Cooling" operating mode active.
–
Closed switching contact heating
= IL1:
The system operates according to the normal infeed tar-
get temperature according to the parameter settings in
"HC Configuration" > "Cooling".
–
Closed switching contact cooling
= IL2:
The system operates according to the reduced inflow tar-
get temperature (normal inflow target temperature - value
of parameter [T-Flow Cooling adj]. Priority if both switch-
ing contacts are closed.
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.1.
3.6.7
Additional alternative heat generator
The heat supplied by an alternative heat generator must be
added to the unpressurised storage tank water in the Daikin
Altherma EHS(X/H) hot water storage tank.
–
In the case of the optional backup heater EKBUxx, this is
managed by the construction.
–
In the case of using an external heat generator (e.g. gas or oil
boiler) this can be integrated hydraulically
a) unpressurised via connections (solar infeed and solar
return) of the hot water tank
or
b) in device types Daikin Altherma EHS(X/H)B, via the
integrated solar pressure heat exchanger.
Adjustment of the [Function Heating ] sets whether and which ad-
ditional heat generators (WEZ) are available for domestic hot
water generation and heating support.
–
0: No additional WEZ
–
1: Optional backup heater EKBUxx (connected via XBUH1
plug)
–
2: Alternative WEZ takes over the hot water generation and
heating support. To demand from the heat generator, relay
K3 on the RTX-EHS circuit board is switched on.
–
3: Alternative WEZ 1 (optional backup heater EKBUxx) takes
over hot water generation and alternative WEZ 2 takes over
heating support To demand by WEZ 1 and WEZ 2, relay K3
and relay K1 respectively on the RTX-EHS circuit board are
switched on!
The operation of additional heat generators are also influenced
by the setting of the parameter [Equilibrium Func.]
(see chapter 6.2.1) and the parameter [Equilibrium Temp]
(see chapter 6.2.2).
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.1.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.6.8
Heating support
If the heating support function (parameter [HZU] = On) is acti-
vated, the energy in the Daikin Altherma EHS(X/H) integrated
storage tank is used to take over the heating function. At a suffi-
ciently high storage tank temperature, the heat pump (refrigerant
circuit) remains out of use.
The minimum value (THZUmin) is calculated as follows:
THZUmin = Current active target hot water temperature
[T-DHW Setpoint] + parameter [TDiff-DHW CH].
Switch-on condition:
Tdhw > THZUmin + 4 K and Tdhw > info parameter [T-HS Set-
point] + 1 K
If the switch-on condition is fulfilled, heat is taken from the
storage tank for the heating system.
Switch-off condition:
Tdhw < THZUmin or Tdhw < info parameter [T-HS Setpoint]
(see section 3.6.4)
If the switch-off condition is fulfilled, the heating support is
stopped in the domestic hot water storage tank and the heat
pump takes over the heating operation.
Parameter [Power BIV] limits the maximum power which can be
removed. Parameter [T vbh1 max] limits the maximum temper-
ature which the heating system can reach.
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.2.
3.6.9
Special function: Switching contacts
Setting the parameter [AUX Fct] changes the switching condi-
tions for the AUX switching contact (toggle switch output A).
This switching contact can be used, for example, to control an ex-
ternal heat generator.
If one of the switching conditions is fulfilled, the potential-free
switching contact changes over after the time set in the pa-
rameter [AUX time] has passed.
AUX switching contact (toggle switch output A) is not switched
if setting =
0: Function deactivated.
AUX switching contact (toggle switch output A) is switched if
setting =
1: When storage tank temperature (Tdhw) ≥ value of param-
eter [T-DHW 1 min].
2: When there is a cooling or heating demand.
3: When there is a hot water demand to the Backup Heater
(EKBUxx) or the configured Backup Heater is required for
heating support.
4: When there is a malfunction.
5: When sensor value (TVBH) > 60°C.
6: When the outdoor temperature < parameter value [Equilib-
rium Temp].
Heat pump continues to operate = parallel bivalence oper-
ation.
7: When the outdoor temperature < parameter value [Equilib-
rium Temp] + there is a heating or hot water demand.
Heat pump does not continue to operate = alternative
bivalence operation.
8: When there is a hot water demand.
9: When outside temperature < parameter value [Equilibrium
Temp] + heat demand "Room heating" (not for hot water
demand). Heat pump no longer operates in room heating
mode below the value set in parameter [Equilibrium Temp] -
only in hot water mode.
Use: An alternative bivalency operation room heating, if the
boiler is incorporated hydraulically in such a way that it heats
the depressurised storage tank water in the Daikin
Altherma EHS(X/H) directly (connection via solar connec-
tions).
10: "Multi-Oil" - if outside temperature < parameter value
[Equilibrium Temp] + heat demand "Room heating" (not for
hot water demand). Heat pump no longer operates in room
heating mode below the value set in parameter [Equilibrium
Temp] - only in hot water mode.
Use: An alternative bivalency operation room heating, if the
boiler is hydraulically incorporated in the flow of the heat
pump. For this type of application, the frost protection function
must be deactivated on the Daikin Altherma EHS(X/H)
(parameter [T-Frost Protect] = Off).
The frost protection must be provided via the boiler
in this option.
The potential-free AUX switching contact (switching output B)
always closes if the heat pump is in "Cooling" mode.
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.2.
3.6.10 Air Purge
By activating the Air Purge the RoCon HP Controller starts a de-
fined sequence program with Start-Stop operation of the inte-
grated heat circulation pump and various settings for the 3-way
diverter valve integrated into the Daikin Altherma EHS(X/H).
Existing air can leak from the automatic venting valve during the
Air Purge and the heating circuit connected to the Daikin
Altherma EHS(X/H) is evacuated.
The activation of this function does not replace the
correct venting of the heating circuit.
Prior to activating this function, the heating circuit must
be completely filled.
1. Enter the expert code (see section 3.6.1).
The "Setup" level is displayed after entering.
2. Select the [Air Purge] parameter using the rotary switch.
3. Confirm the changes with a brief push of the rotary switch.
The setting for the parameter is displayed.
4. Using the rotary switch, set the parameter for the function to
"On" and confirm by pressing it quickly.
"Air Purge" starts (3-way diverter valves into middle posi-
tion, heating circulation pump modulated - see fig. 3-17).
After the programme is completed (approx. 10 min), the
Daikin Altherma EHS(X/H) switches to "Standby" operat-
ing mode.
Fig. 3-17 Air Purge procedure
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
27
5. Place the rotary switch in the "Operating Mode"
position and set the desired operating mode
(see section 3.4).
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.1.
3.6.11 Legionella protection
WARNING!
There is a danger of scalding at target
hot water temperatures over 60°C.
This is possible when solar energy is
used and when Legionella protection or
SMART GRID is activated or when the
domestic hot water target temperature is
set higher than 60°C.
● Fit a scald-protection in the hot water
distributor line (e.g. VTA32 + Screw
connection set 1").
This function serves to prevent bacterial contamination in the hot
water storage tank. For accurate controllers for drinking water hy-
giene, refer to the national provisions.
The Legionella protection function in the Daikin
Altherma EHS(X/H) is deactivated when leaving the
factory as the possibility of bacterial contamination is
very low:
–
Low volume of heat exchanger (stainless steel)
used for heating drinking water.
–
Frequent complete water replacement "first-in-first-
out".
–
No stagnant water areas in drinking water storage.
An active Legionella protection function (parameter [Anti-Le-
gionella day]) involves heating the connected storage tank to a
disinfection temperature 1 x a day or 1 x a week. The legionella
protection function is active for an hour.
The maximum hot water temperature set by the user or
the heating technician is ignored when hot water is
heated for disinfection purposes.
A connected circulation pump is automatically switched
on during thermal disinfection.
Setting the parameters for legionella protection is carried out in
the rotary switch setting "Configuration"
in level "DHW
Configuration".
Using the factory settings, the storage tank is heated at 03:30
hours if the target hot water temperature is below 65°C at that
time.
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.4.
3.6.12 Reset to factory settings (Reset)
If the Daikin Altherma EHS(X/H) no longer works properly and
any other cause for the malfunction cannot be detected, it may be
helpful to reset all the controller settings to the factory settings.
There are 3 options for this.
Option 1
User access rights allow the switching time program in the
"Special Level" to be reset to the factory setting according to
tab. 3-9.
1. Depress the exit button for at least 5 secs.
Menu "Special Level" is displayed.
2. Select the programme "Timeprog Reset" with the rotary
switch.
3. Execute the programme by briefly pressing on the rotary
switch.
The respective values are reset to the factory setting.
4. Select "Return" with the rotary switch.
5. Confirm the changes with a brief push of the rotary switch.
Possibility 2
Technician access rights permit all customer-specific pa-
rameter settings in the "Special Level" to be reset to the factory
setting according to tab. 6-1 to tab. 6-11.
1. Enter the expert code (see section 3.6.1).
The "Setup" level is displayed after entering.
2. Depress the exit button for at least 5 secs.
Menu "Special Level" is displayed.
3. Select the programme "Reset?" with the rotary switch.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
4. Execute the programme by briefly pressing on the rotary
switch.
The respective values are reset to the factory setting.
5. Select "Return" with the rotary switch.
6. Confirm the changes with a brief push of the rotary switch.
Possibility 3
If fundamental changes to the Daikin Altherma EHS(X/H)
equipment for the function within the RoCon system are nec-
essary, the Basic Configuration can be reset using Technician
access rights to the factory settings or can be redefined.
1. Enter the expert code (see section 3.6.1).
The "Setup" level is displayed after entering.
2. Select the "System Config" level with the rotary switch.
3. Confirm the changes with a brief push of the rotary switch.
An overview is displayed.
4. Select the programme "Delete" with the rotary switch.
5. Confirm the changes with a brief push of the rotary switch.
Restart of the Daikin Altherma EHS(X/H) is performed.
The message "No Basic " is displayed.
6. Place the rotary switch in the "Info"
position.
The message "Basic Configuration " is displayed.
7. There is now the facility either to select manual mode for the
equipment individually (a) or to load the factory settings
automatically (b).
a) Press the rotary switch briefly.
A parameter overview is displayed at the level "Basic
Configuration" and the settings can performed manually
as desired according to tab. 6-14.
b) Turn the Daikin Altherma EHS(X/H) off and restart it.
After the has restarted the question will be Daikin
Altherma EHS(X/H)posed whether the standard configu-
ration should be used. If it is confirmed with "Yes", the
preset basic configuration is loaded. If the answer
given is "No" the settings must be performed manually,
see a).
More detailed explanations and possible setting values for this function can be seen
in chapter 6.12.
After a reset to the factory settings via option 2 or 3, the
system must be configured again by the heating tech-
nician to the installation environment and all the cus-
tomer-specific parameters reset.
3.6.13 Screed Program
The Screed Program is intended exclusively for specified drying
of newly created screed in underfloor heating systems. This op-
erates the heat generator for several days according to a prede-
fined temperature profile (the predefined temperature profile is
based on the recommendations of the Bundesverbandes
Flächenheizungen (Federal Association of Surface Heating
Systems) for heating to cure the floor).
The temperatures and the duration of the Screed Program can be
adjusted as required, after entering the expert code, in the rotary
switch setting "Configuration"
in the level "HC Configu-
ration" in the parameter [Screed Program].
The Screed Program is a special function and is not interrupted
by any other operating mode. It can be activated only by the
heating expert for the direct heating circuit and/or the op-
tionally connected mixed heating circuits. Each heating circuit
must be separately activated.
Prior to start of the Screed Program, the parameters
[Interlink fct] and [Room thermostat] must have been
deactivated.
In the event of a brief power failure the system contin-
ues with a previously activated screed function in place
of shutting down.
After activation of the Screed Program (parameter [Screed] = On)
all the weather-controlled regulating functions of the relevant
heating circuit are switched off. The relevant heating circuit op-
erates independently of the operating mode (switching times) as
a constant temperature regulator.
An already started Screed Program can be deactivated at any
time. At the end of Screed Programs the screed function the pa-
rameter is automatically set to "Off" and the heating circuit once
again operates according to the currently set operating mode.
Function heating
Function heating verifies that the installation is fault-free for the
heating engineer. A pre-prepared heating up protocol for Daikin
underfloor heating can be found in the Daikin Internet portal.
In this case, function heating (identical with "Heating up" in
EN 1264, section 5.2) does not constitute a heating up process
for drying and curing. Normally you need to carry out separate
heating process to cure the floor and/or perform mechanical
drying.
Heating up should be carried out no earlier than after 21 days for
cement screed, and no earlier than after 7 days for anhydrite
screed in accordance with the details provided by the manufac-
turer. The first heating up starts at a feed temperature of 25 °C,
which must be maintained for a period of 3 days. Then heating is
carried out at the maximum flow temperature set for the heating
circuit (limited to max. 55 °C) and this is then held for a further
4 days.
After the heating up process described, there is no guarantee that
the screedhas achieved the moisture content required to cure the
floor.
You must determine the moisture content in the screed by meas-
urement before laying the floor covering.
Procedure in accordance with EN 1264 Part 4:
The heating circuits must be checked for leaks by a
water pressure test once the anhydrite and cement
screeds are completed. The absence of leaks must be
ensured immediately before and during screed laying.
The level of the test pressure is at least 1.3 times the
maximum permissible operating pressure.
If there is a danger of freezing up, you must take suita-
ble measures, e.g. the use of antifreeze or temperature
control in the building. If antifreeze is no longer required
for intended use of the installation, you must remove
the antifreeze by draining it out and flushing the instal-
lation with at least 3 changes of water.
Starting temperature 25 °C
t2
Maximum heating circuit temperature
tV
Flow temperature
Z
Duration of screed function, in days, after function start
Fig. 3-18 Sequence of timings of the Screed Program for function heat-
ing
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
29
Ready-to-apply heating
The drying out procedure for the screed cannot be predicted ex-
actly in advance. At higher humidity levels in the air this can come
to a complete stop under certain circumstances stop under
certain circumstances. The drying out process may be acceler-
atedby running the underfloor heating (curing heating) or by
using measures such as mechanical drying.
Every curing heating process must be commissioned, separately
by the building owner as an extra service in accordance with
VOB. For the flooring contractor to achieve fault-free installation,
the flooring must be properly cured before work is started on the
top flooring layer.
The standard settings can be used to activate the combined
function and curing heating programme in order to achieve a re-
sidual moisture level in the screed required for curing the floor
(see fig. 3-19). The residual moisture level in the screed must,
however, always be checked by measurement before the floor-
covering is laid.
Fig. 3-19 The time sequence of the Screed Program in combined func-
tion and curing heating (for legend see fig. 3-18)
More detailed explanations and possible setting values for this function can be seen
in sections 6.2.3 and 6.13.2.
Screed Program setting and starting
The Screed Program contains factory-set specifications which
can, however, be individually adapted.
Screed Program The day on which the screed function is
activated does not count towards the runtime of the screed
programme. The 1st. The day begins with the change of the day
at 00:00. On the day of activation we heat the remaining time at
the programme of the first day.
●
Enter the expert code (see section 3.6.1).
The "Setup" level is displayed after entering.
●
Using the rotary push button, select and check the param-
eters [Interlink fct] and [Room thermostat] whether they are
deactivated (see tab. 6-1).
Both parameters must be on "Off" before starting the
screed function.
●
Press the Exit key briefly.
An overview is displayed.
●
Select the "HC Configuration" level with the rotary switch.
An overview is displayed.
●
Select the [Screed Program] parameter using the rotary
switch.
●
Check the Screed Program settings and adjust to the stipula-
tions provided for the screed by the manufacturer, if
necessary (see fig. 3-20).
–
The setting range is always between 0.0 and 65 °C.
–
The steps are 1 °C.
Day
Factory setting
Day
Factory setting
1 - 3
25 °C
10 - 19
55 °C
4 - 7
55 °C
20
40 °C
8
25 °C
21
25 °C
9
40 °C
22 - 26
-
Tab. 3-11 Presettings Screed Program
●
Press the Exit key briefly.
An overview is displayed.
●
Select the "Screed" parameter using the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
The setting for the parameter is displayed.
●
Using the rotary switch, set the parameter for the function to
"On" and confirm by pressing it quickly (see fig. 3-20).
Screed Program starts.
The button block (if it was activated from the start of this
function), is activated again within 2 seconds in order to
prevent inadvertent termination of the function by operat-
ing the Controller RoCon HP.
After expiry of the Screed Program the Controller RoCon HP
again operates in the previously set operating mode. Unless con-
figured previously, the following tasks need to be carried out in
conclusion.
a) When connecting without a room station:
●
Set the heating characteristic curve or the inflow target
temperature.
b) When connecting with a room station:
●
Activate the room station.
●
Set the heating characteristic curve or the inflow target
temperature. If required, activate the parameter [Room
Influence] and set the target room temperature.
Tag 2 25 °C
Configuration
System
HC Configuration
DHW Configuration
HC Configuration
HC Function
T-Frost Protect
HC Configuration
Screed
Screed Program
Screed
T-HS
On
Screed
Screed
Screed Program
Tag 2
Tag 2 25 °C
Tag 2
Tag 2 26 °C
Fig. 3-20 Screed Program Setting
Operating instructions
30
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.6.14 Relay Test
In the event of fault signals, heating problems or in the framework
of the annual service, it may be necessary to check the function
of internal switching relays.
●
Enter the expert code (see section 3.6.1).
The "Setup" level is displayed after entering.
●
Press the Exit key briefly.
The level "Configuration" is displayed.
●
Select the "System " level with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
An overview is displayed.
●
Select the parameter [Relay Test] with the rotary switch.
All relays are deactivated.
The selection list of all relays is displayed (for allocation of
relays see chapter 6.2.2).
●
Select the relay to be tested with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
The relay is activated.
●
Cancellation and jump back by:
–
briefly pressing the exit button or the rotary switch
–
selecting a different menu using the rotary switch.
More detailed explanations and possible setting values for this function can be seen
in chapter 6.2.2.
3.6.15 Settings for optional circulation pump
To increase convenience when drawing off hot water we can
switch an optional circulation pump using the Controller
RoCon HP.
There are 2 switching possibilities:
a) Separate timer programme (see section 3.4.7).
The circulation pump operates according to its own timer
programme.
b) Together with a hot water timer programme. The circulation
pump is actuated in parallel with the operating periods of the
hot water timer programme.
Independent of the set timer programme, the energy con-
sumption of the circulation pump van be minimised by operating
it on a cyclic basis. The parameter [Circl-Pump Interval] is used
to set how long the circulation pump is operated within a
15-minute interval.
3 x Operation
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
31
Setting the timer programme for the circulation pump
●
Place the rotary switch in the "Configuration"
position.
An overview is displayed.
●
Select the "DHW Configuration" level with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
An overview is displayed.
●
Select the parameter to be set with the rotary switch.
–
[Circl-Pump DHW]: Setting as to whether the circulation
pump is actuated by the active hot water timer programme
[ON] or from a separate timer programme [OFF].
–
[Circl-Pump Interval]: Setting the interval control for an
optional circulation pump.
●
Confirm the changes with a brief push of the rotary switch.
●
Setting parameters
●
Confirm the changes with a brief push of the rotary switch.
The circulation pump is actuated in accordance with the
settings made by the Controller RoCon HP.
Possible setting values for this rotary switch setting can be seen in chapter 6.2.4.
3.6.16 Remote control via Internet
Using an optional gateway (EHS157056), the Controller
RoCon HP can be connected to the internet. This means that the
Daikin Altherma EHS(X/H) can be controlled remotely via mobile
phone (using an App).
Intuitive operation is possible.
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
4 x Initial start-up
4
Initial start-up
In addition to the commissioning instructions listed in
this chapter, the specific commissioning instructions
listed in the installation instructions for the Daikin
Altherma EHS(X/H) must be complied with.
The RoCon system offers a very wide range of application and
extension possibilities.
The individual RoCon system components communicate via the
CAN data bus. For this reason, the circuit boards RoCon BM1
and the control units RoCon B1 of the Daikin
Altherma EHS(X/H), and possibly the optional system compo-
nents room station EHS157034 and mixer module EHS157068
are connected together via data bus lines.
These system components must be allocated unique functional
IDs, so that the data exchange and the allocation functions
without any problems within the RoCon system.
In many applications, nothing needs to be changed on the basic
settings. The more RoCon system components that are inte-
grated in the RoCon system, the more adjustments that need to
be made during the initial commissioning or when extending the
heating system.
The allocation of the functional IDs is easiest carried out via the
installation menu "Setup Wizard". Most IDs can also be adapted
subsequently to the conditions by means of individual parameter
settings in the specific parameter levels (see chapter 6).
a) If no optional RoCon system components are connected
to the Daikin Altherma EHS(X/H), in the RoCon system, just
the circuit board RoCon BM1 and the integrated control unit
RoCon B1 communicate with each other.
Adaption of the IDs is not necessary.
The question displayed during initial commissioning "Use
standard configuration?" can be confirmed by "Yes".
b) If optional RoCon system components such as
EHS157034 and / or EHS157068 are connected, adaption to
the IDs may be necessary.
4.1
Fundamental aspects of the IDs and authorisations in the RoCon system
In the RoCon system, the following functional IDs exist, which are
relevant for data exchange of the RoCon system components:
ID / function
System components
Parameter
Comments
Heating circuit IDs
Unique numbering of a heating circuit
in the heating system in the RoCon
system. A maximum of 16 heating cir-
cuits can be controlled.
Daikin Altherma EHS(X/H)
(RoCon BM1)
[Unmixed Circ Config]
See tab. 6-14
Factory setting = 0
Should not normally be changed.1)
Room station EHS157034
[HC Assignment]
See tab. 6-1
Factory setting = Off
Adaption necessary because there are dif-
ferent heating circuits in the system and /
or the parameter [Master-RoCon] = On
Mixer module EHS157068
[HC Assignment]
See tab. 6-15
Factory setting = Off
Must always be adapted to the setting of
the address switch (fig. 4-2).
Heat generator ID
Unique numbering of a heat gen-
erator in the RoCon system.1)
Daikin Altherma EHS(X/H)
(RoCon BM1)
[BUS ID HS]
See tab. 6-14
Factory setting = 0
Should not normally be changed.1)
Mixer module EHS157068
[Boiler Assignment]
See tab. 6-15
Factory setting = 0
Should not normally be changed.1)
Defines the heat generator that supplies
the allocated heating circuit with heat.
Terminal ID
Unique numbering of a control unit
RoCon B1 or EHS157034, from
which a heat generator and / or a
mixer module in the RoCon system
can be controlled remotely.
The authorisation for remote control
can be allocated to up to 10 control
units in the RoCon system. If remote
control in the RoCon system is to be
possible, then the control unit must
be allocated the ID "0".
Daikin Altherma EHS(X/H)
(RoCon BM1)
[Terminaladress]
See tab. 6-1
Factory setting = Off
The value should be set to "0" if at least 1
mixer module is connected in the RoCon
system, and the mixer circuit is to be op-
erated from the heat generator.
Room station EHS157034
[Terminaladress]
see tab. 6-1 or
tab. 6-15 - depending
on the set heating cir-
cuit ID and the current
operating mode
Factory setting = Off
The value must be set to a unique nu-
merical value in the RoCon system, if the
room station system components are to be
remotely controlled using a valid device ID.
4 x Initial start-up
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
33
If several control units are incorporated in the RoCon system of a
heating installation, additional parameter settings are relevant for
this, which can be used for setting the individual functions and pa-
rameters using the appropriate authorisations.
On the room station EHS157034
–
Parameter [RoCon U1 assign]:
–
The setting = "Living Room" can be used to influence the
heating circuit defined by the set heating circuit ID.
–
The setting = "Mixing Valve" can be used to carry out all
the settings for the mixer circuit defined by the set heating
circuit ID.
–
Parameter [Master-RoCon]:
If the heating circuit is set for the direct heating circuit of a
Daikin Altherma EHS(X/H), the setting = "On" can be used to
activate the Master-RoCon function. In addition to the heating
circuit functions, the hot water functions of the Daikin
Altherma EHS(X/H) can also be operated with this room sta-
tion.
The activation of the Master-RoCon function can also be used
for heating installations just made up of a Daikin
Altherma EHS(X/H) (without heating circuit extension) and a
room station, and which are to be operated primarily via the
room station (see following information).
If the Master-RoCon function is activated, the oper-
ating mode of the heat generator is set via the room
station, and this is shown in the dispay.
The settings on the room station are transferred to
the heat generator, but not vice versa. The room
station has priority.
For example, if the operating mode [Summer] is set,
and subsequently, on the control unit of the Daikin
Altherma EHS(X/H) the operating mode [Heating] is
set, a heating circuit demand is not generated, be-
cause the direct heating circuit, that is allocated to
the room station by the heating circuit ID, is still in
the operating mode [Summer]. The change in oper-
ating mode must therefore be undertaken at the
room station.
On heating installations with heating circuit extensions, we
recommend not activating the Master-RoCon function
(Setting = "Off") and instead using the terminal function.
With all control units RoCon B1 B1 and EHS157034
–
Parameter [Terminaladress]:
As soon as a control unit is allocated a terminal ID (all settings
with the exception of "Off"), the control unit can be used to
activate the terminal function.
After carrying out the [Bus - Scan], all the system components
incorporated in the RoCon system can be remotely controlled
using a valid device ID (caretaker authorisation).
If you intend to use the terminal function in the heating sys-
tem, you need to allocate the terminal ID = 0 to a control unit.
Device ID
Unique numbering of a heat gen-
erator or mixer module in the RoCon
system.
Up to 16 device numbers can be allo-
cated.
These device numbers are detected
during a [Bus - Scan] and are dis-
played for identification of a remote
controlled device.
Daikin Altherma EHS(X/H)
(RoCon BM1)
[BUS ID HS]
See tab. 6-14
Identical to heat generator detection.
The value must not be the same as the
heating circuit ID of a mixer module in the
RoCon system.
Mixer module EHS157068
[HC Assignment]
See tab. 6-15
Identical to heating circuit ID.
The value must not be the same as the
heat generator ID of a Daikin
Altherma EHS(X/H) in the RoCon system.
The value must be the same as the setting
of the address switch (fig. 4-2).
Tab. 4-1
Functional IDs in the RoCon system
1)
A maximum of 8 heat generators can be connected in the RoCon system via the CAN data bus. Several heat generators incorporated in the heating installation must
be regarded as a special application. If necessary contact Daikin service technician.
ID / function
System components
Parameter
Comments
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
4 x Initial start-up
4.2
Operating Support during 1st.
Commissioning and during System
Extensions
When the Daikin Altherma EHS(X/H) or the room station
EHS157034 are switched on for the first time, you are normally
offered the opportunity of setting the user language.
Then, on the Daikin Altherma EHS(X/H) you will be asked "Use
Standard Config?". This question can normally be answered with
"Yes".
Only with special applications (e.g. several heat generators in the
RoCon system should the answer be "No"). In this case you will
be offered the parameter level "Basic Configuration", in order to
be able to set the necessary adaptions (see tab. 6-14).
With the room station EHS157034, after setting the user lan-
guage, the installation menu "Setup Wizard" appears.
Setup Wizard
Fig. 4-1
Display "Setup Wizard"
The items for definition of the function, the authorisation and the
IDs of the of the room station in the RoCon system are requested
and checked for plausibility.
This prevents setting duplicate device and terminal IDs.
We therefore recommend that, when extending or making
changes to the RoCon system of the heating installation, you use
this installation menu. For this, a room station already incorpo-
rated in the heating installation must first be reset.
1. Enter the technician code (see section 3.6.1).
2. Depress the exit button for at least 5 secs.
Menu "Special Level" is displayed.
3. Select the programme "RoCon B1/U1 Reset" with the rotary
switch.
4. Execute the programme by briefly pressing on the rotary
switch.
The installation menu "Setup Wizard" starts.
4.3
Starting up the Daikin Altherma EHS(X/H)
A precondition for initial commissioning is the completion of all
preparatory installation work in accordance with the installation
and maintenance instructions for the Daikin Altherma EHS(X/H).
●
Turn power supply to Daikin Altherma EHS(X/H) on.
After the start phase, the operating language selector is
displayed.
●
Use the rotary switch to select the desired language.
The operating language can be changed again at any
time.
●
Confirm the changes with a brief push of the rotary switch.
The message "Use Standard Config?" is displayed.
●
Confirm the standard stipulation "Yes" with a brief push on the
rotary switch (see also section 4.2).
The Basic Configuration of the RoCon device is loaded.
The message "Starting Up" is displayed.
The message "Initialization" is displayed.
The standard display for the current rotary switch setting
is displayed.
●
At the RoCon device, adjust the settings to suit the configu-
ration of the heating system (see chapter 3.6).
4.3.1
Allocating the terminal ID on the control unit
RoCon B1 of the Daikin Altherma EHS(X/H)
If several control units are connected in the RoCon
system via the data bus, you must note that the pa-
rameter [Terminaladress] = 0 must be set for a heat
generator.
Make sure not to assign a duplicate value as the setting
of the [Terminaladress] in the RoCon system.
●
Enter the technician code (see section 3.6.1).
The "Setup" level is displayed after entering.
●
Select the parameter [Terminaladress] with the rotary switch.
●
Confirm the changes with a brief push of the rotary switch.
●
Within the display, use the rotary switch to set the unique
terminal address.
For reasons of clarity, this control unit must be allocated the
value = 0.
●
Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 6.2.1.
4.4
Commissioning optional RoCon system
components
4.4.1
Mixer module EHS157068
The EHS157068 mixer module has no control unit of its own.
For configuration and operation it must be connected using a
CAN bus cable to a RoCon-Controller installed in the heat gen-
erator or to an EHS157034 room station.
In conjunction with a room station the mixer module can
also be operated as a free-standing heating circuit con-
troller.
To operate the mixer module directly via the control unit
RoCon B1 of the Daikin Altherma EHS(X/H), it must
have a terminal ID allocated to it and the terminal
function will have to be activated (see chapter 3.4.9).
After selection and confirming an external device, the terminal
function for this device is activated and the associated standard
display for this device is shown in the display.
The operating component is then in terminal mode.
In the rotary switch setting
, the local control unit operates
as a remote control for the external device. In this case all the
control functions are provided and saved 1:1 as on the external
equipment.
For reasons of clarity, this control unit must be allocated the
value = 0.
If the message "n. A." is displayed at rotary switch set-
ting
, the control unit RoCon B1 has yet to be
assigned a valid terminal address.
If the message "n. A." is still displayed it may be nec-
essary to update the device software before the ter-
minal function can be used. Contact the Daikin Service
Team for this.
4 x Initial start-up
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
35
At the address switch (see fig. 4-2) a unique device ID (≥ 1) must
be set for the heating circuit to be controlled by this mixer module,
which must be synchronised with the (parameter [HC As-
signment] of the mixer module (see tab. 4-1]).
Fig. 4-2
Setting device ID for mixer module EHS157068
All settings and operating steps for this heating circuit are per-
formed similarly to those for the direct heating circuit.
The overview of the available parameters and their settings cam
ne found in chapter 6.13.
The current operating status can be determined directly at the
EHS157068 mixer module (see fig. 4-3).
1
LED red
- Flashing: Internal fault
(the fault code is communicated via the CAN bus
to the relevant control unit)
- To: Undervoltage at the internal clock after a pow-
er failure (>10 h)
2
LED green
- To: Display during operation, mixer module
switched on
3
LED green
- To: CAN communication established
4
LED green
- To: Mixer circuit pump switched on
5
LED green
- To: Mixer "OPEN" is activated
6
LED green
- To: Mixer "CLOSED" is activated
Fig. 4-3
Explanation of symbols for status displays EHS157068
4.4.2
Room station EHS157034
The EHS157034 room station can be used as
a) A remotely controlled unit of the Daikin Altherma EHS(X/H),
b) A mixer circuit operating unit (as a mixer circuit extension or
as a free-standing mixer circuit controller),
c) Room thermostat for the Daikin Altherma EHS(X/H),
d) Remotely controlled unit for the entire RoCon-system (with
terminal function activated).
The room station must be connected using a CAN bus line to a
RoCon-Controller installed in the Daikin Altherma EHS(X/H) or to
an EHS157068 mixer module. No separate mains supply is nec-
essary for the room station.
Sequence for initial commissioning
(see also section 4.2)
●
Set the rotary switch on the EHS157034 room station to
position "Info"
.
●
Switch on the power to the Daikin Altherma EHS(X/H).
After the start phase, the operating language selector is
displayed on the EHS157034 room station.
●
Use the rotary switch to select the desired language.
The operating language can be changed again at any
time.
●
Confirm the changes with a brief push of the rotary switch.
The message "Setup Wizard" is displayed.
●
Use the rotary switch to set the desired operating function for
the room station.
–
"Living Room": Operating function see a), c), d)
–
"Mixing Valve": Operating function see b)
Depending on the application selected, the further config-
uration is based either A or B in the following sections.
All the operating steps for the assigned heating circuit
after initial commissioning are performed similarly to
those for the operating element RoCon B1 of the
Daikin Altherma EHS(X/H).
However not all functions (such as manual operation,
resetting of faults) of the Daikin Altherma EHS(X/H) can
be activated by the room station.
A: Configuration for setting "Living Room"
●
Confirm the setting "Living Room" by briefly pressing the
rotary switch.
Setting of the heating circuit ID (parameter [HC Assign-
ment]) is displayed.
●
Use the rotary switch to select the associated heating circuit
in the [HC Assignment] parameter.
●
Confirm the changes with a brief push of the rotary switch.
Setting of the terminal ID (parameter [Terminaladress]) is
displayed.
●
Use the rotary switch to set the [Terminaladress] parameter.
●
Confirm the changes with a brie f push of the rotary switch.
Standard display is shown (see fig. 4-4).
Current room temperature
4
Current outside temperature
5
Operating mode active for
the assigned heating circuit
Fig. 4-4
Standard display EHS157068 - "Living Room"
Operating instructions
36
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
4 x Initial start-up
The settings on the EHS157034 room station are only
valid for the assigned heating circuit (except in the case of
active terminal function).
B: Configuration for setting "Mixing Valve"
●
Confirm the setting "Mixing Valve" by briefly pressing the
rotary switch.
Setting of the heating circuit ID (parameter [HC Assign-
ment]) is displayed.
●
Use the rotary switch to set the[HC Assignment] parameter.
This parameter must be identical to the setting of the address
switch in the mixer module (see fig. 4-2), that is allocated to
the room station EHS157034.
●
Confirm the changes with a brief push of the rotary switch.
Setting of the terminal ID (parameter [Terminaladress]) is
displayed.
●
Use the rotary switch to set the [Terminaladress] parameter.
Standard display is shown (see fig. 4-4).
1
Display date
2
Status display: Screed func-
tion active
3
Status display: Technician
login
4
Display time
5
Current inflow temperature
of the mixer circuit
6
Current outside temperature
7
Operating mode setting for
the assigned heating circuit
Fig. 4-5
Standard display EHS157068 - "Mixing Valve" with example
of the status displays
In the setting "Mixing Valve" the room sensor of the
EHS157068 is deactivated.
4.4.3
Allocating mixing module EHS157068 to a
heat generator
If just 1 heat generator is incorporated in the RoCon system,
adaption of the heat generator ID is not necessary (see tab. 4-1).
If adaptions need to be made, the value of the parameter [Boiler
Assignment] (see chapter 6, tab. 6-15) must be set to the same
value as the heat generator ID of the Daikin Altherma EHS(X/H),
that is intended to supply the mixer circuit of this mixer module.
4.4.4
Master-RoCon function
Each room station EHS157034, whose heating circuit ID is set to
a direct heating circuit, can be allocated the Master-RoCon
function.
●
Enter the technician code (see section 3.6.1).
The "Setup" level is displayed after entering.
●
Select the [Master-RoCon] parameter using the rotary
switch.
●
Confirm the changes with a brief push of the rotary switch.
The setting for the parameter is displayed.
●
Using the rotary switch, set the parameter for the function to
"On" and confirm by pressing it quickly.
All settings on the EHS157034 room station act in the same
way as settings on the RoCon B1 B1 control panel for the as-
signed heat generator.
As a result, the functions for hot water preparation can also be re-
motely operated from the room station.
Since, in this setting, the control unit RoCon B1 has control over
the allocated heating circuit, the settings made on the control unit
of the Daikin Altherma EHS(X/H), only have an effect only on the
heat generator, but not on the heating circuit (see section 4.1).
4.4.5
Caretaker function
The caretaker function equates to the terminal function (see
chapter 3.4.9 and section 4.1 under parameter [Terminala-
dress]).
5 x Parameter Overview
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
37
5
Parameter Overview
5.1
For first commissioning or resetting to factory settings
The parameters listed in this section can be accessed
when the Daikin Altherma EHS(X/H) is commissioned
for the first time or if it is fully reset.
During initial commissioning:
After resetting to factory settings:
●
Rotary switch setting: Info
●
Resetting to factory settings.
(see chapter 3.6.12 - Possibility 3)
●
Rotary switch setting: Info
●
Turn power supply to Daikin Altherma EHS(X/H) on.
Language
Use
Standard Config
Yes
No
Basic Configuration
Boiler Function
Unmixed Circ Config
BUS ID HS
Time Master
System Config
Tab. 5-1
Parameter "Basic Configuration"
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
5 x Parameter Overview
5.2
After first commissioning / after successful basic configuration
5.2.1
Rotary switch setting: Configuration
Setup
LCD Brightness
System
Power DHW
LCD Illum Time
BUH s1 power
Language
BUH s2 power
Date
Power BIV
Time
TDiff-DHW CH
Keylock Function
T vbh1 max
Access Rights
Equilibrium Temp
RoCon U1 assign
Quite Mode
Master-RoCon
AUX Fct
Outdoor type
AUX time
INDOOR UNIT
T-DHW 1 min
HP Version
Delta-T CH
Function Heating
V var
HZU
T-Flow CH adj
Equilibrium Func.
T-Flow Cooling adj
SMART GRID
Min Pressure
Mode SG
Max Pressure
HT/NT Function
Set Point Pressure
HT/NT Contact
Max Pressuredrop
Room thermostat
Relay Test
Interlink fct
MF 1 Config
Air Purge
PWM Config
Max Perform Pump
Min Perform Pump
HC Configuration
HC Function
Sensor Config
Outside Config
T-Frost Protect
Outside Temp Adap
Storage Config
Insulation
Terminaladress
Pressure Config
Screed
System Config
Screed Program
HC Assignment
Heating
T-Outside lim day
Cooling
Start T-Out Cooling
T-Outside lim night
Max T-Out Cooling
Heat-Slope
DHW Configuration
Circl-Pump DHW
T-Flow Cooling start
Room Influence
Circl-Pump Interval
T-Flow Cooling max
T-Room Adj
Anti-Legionella day
Min T-Flow Cooling
T-Flow Day
Anti-Legionella time
T-Flow Cooling
T-Flow Night
Anti-Legionella temp
T_H/C Switch
Max T-Flow
Max DHW loading
Cooling Setpoint adj
Min T-Flow
DHW Off Time
HC Adaption
Tab. 5-2
Parameter in rotary switch setting "Configuration"
Rotary switch setting: DHW Install
1x Hot Water
Hyst HP
Timer BOH
5 x Parameter Overview
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
39
Tab. 5-3
Parameter in rotary switch setting "DHW Install"
5.2.3
Rotary switch setting: Operating Mode
Standby
Reducing
Heating
Cooling
Summer
Automatic 1
Automatic 2
Tab. 5-4
Parameter in rotary switch setting "Operating Mode"
5.2.4
Rotary switch setting: Set Temp Day
T-Room 1 Setpoint
T-Room 2 Setpoint
T-Room 3 Setpoint
Tab. 5-5
Parameter in rotary switch setting "Set Temp Day"
5.2.5
Rotary switch setting: Set Temp Night
T-Reduced
T-Absence
Tab. 5-6
Parameter in rotary switch setting "Set Temp Night"
5.2.6
Rotary switch setting: DHW Set Temp
T-DHW Setpoint 1
T-DHW Setpoint 2
T-DHW Setpoint 3
Tab. 5-7
Parameter in rotary switch setting "DHW Set Temp"
5.2.7
Rotary switch setting: Time Program
Party
Away
HC Program 2
Vacation
DHW Program 1
Holiday
DHW Program 2
HC Program 1
Circulation Time
Tab. 5-8
Parameter in rotary switch setting "Time Program"
5.2.8
Rotary switch setting: Remote Param
Bus - Scan
No selection
Contr BM1/BE1 #X
Mix Valve #X
Tab. 5-9
Parameter in rotary switch setting "Remote Param"
5.2.9
Rotary switch setting: Info
Overview
Mode:
Pump:
Ext:
EHS:
Water Pressure
RT:
BPV:
T-HS
TV:
tDHW:
TVBH:
TA:
T-HS Setpoint
TR:
V:
T-Outside
TVBH2:
Tliq2:
TR2
tA2:
T-DHW
Tdhw2:
quiet:
T-DHW Setpoint
(see also chapter 3,
fig. 3-5)
T-Return
Flow Rate
T-HC
Qsc
T-HC Setpoint
Qch
Status HS pump
QWP
Runtime Compressor
Qdhw
Runtime Pump
HS type
Mixer Position
Sw Nr B1/U1
Qboh
Sw Nr Controller
Qchhp
Sw Nr RTX RT
Tab. 5-10 Parameter in rotary switch setting "Info"
5.2.10 Exit button: Sonderfunktion
Manual Operation
FA failure
Protocol
Delete message
RoCon B1/U1 Reset
Parameter Reset
Timeprog Reset
Return
Tab. 5-11 Parameter in the level "Sonderfunktion"
5.3
Parameter levels for the EHS157068
mixer module
5.3.1
Rotary switch setting: Info
see section 5.2.9
5.3.2
Rotary switch setting: Operating
Mode
see section 5.2.3
5.3.3
Rotary switch setting: Set Temp Day
see section 5.2.4
5.3.4
Rotary switch setting: Set Temp Night
see section 5.2.5
5.3.5
Rotary switch setting: DHW Set Temp
No function
5.3.6
Rotary switch setting: DHW Install
No function
Rotary switch setting: Time Program
see section 5.2.7
5.3.8 Rotary switch setting: Remote Param
see section 5.2.8
5.3.9
Rotary switch setting: Configuration
Setup
LCD Brightness
LCD Illum Time
Language
Date
Time
Keylock Function
Access Rights
RoCon U1 assign
Master-RoCon
PWM Config
Min Perform Pump
Max Perform Pump
Sensor Config
Outside Config
Outside Temp Adap
Terminaladress
Boiler Assignment
HC Assignment
Mixer Config
HC Function
Pump Mode
T-Outside lim day
T-Outside lim night
Heat-Slope
Room Influence
T-Room Adj
T-Flow Day
T-Flow Night
Max T-Flow
Min T-Flow
HC Adaption
Slope Offset
T-Frost Protect
Insulation
Forced Performance
Start T-Out Cooling
Max T-Out Cooling
T-Flow Cooling start
T-Flow Cooling max
Min T-Flow Cooling
T-Flow Cooling
Cooling Setpoint adj
Relay Test
Screed
Screed Program
Operating instructions
40
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
5 x Parameter Overview
Tab. 5-12
Parameter in rotary switch setting "Configuration"
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
41
6
Parameter settings
6.1
Explanation of the parameter tables
The parameter tables listed in the sections 6.2 to 6.11 contain im-
portant information concerning all parameters that are available
in the individual rotary switch setting on the controller (1st. menu
level, 2nd. menu level).
In addition to the parameter designations, the tables contain de-
tails for the setting ranges, factory settings, setting options or
setting step distances and brief function explanations.
In addition, they provide explanation of the access rights for the
operation of the controller. The following abbreviations are
available for appropriate characterisation:
BE
Access right for the operator
HF
Access permission with Technician password
If different settings appear in the BF and HF columns, the
user must log in as a technician so as to be able to
access the parameter level to change the status set in
the HF column (see chapter 3.6.1).
Status:
N
Not visible
E
Visible and configurable
S
Visible
6.2
Rotary switch setting: Configuration
6.2.1
Level "Setup"
Sub-
level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
LCD Brightness
Display brightness
E
E
0 - 100 %
50%
10 %
LCD Illum Time
Duration of display lighting
E
E
5 - 120 s
30 s
1 s
Language
Language of the display text in the operating panel
E
E
Deutsch
English
French
Dutch
Italian
Spanish
Portuguese
Deutsch
-
Date
Current date in format day / month / year. The current day of the week is calculated
automatically from the date.
E
E
Time
Time in format hours / minutes.
E
E
Keylock Function
Release of the keylock function:
Off: Button block cannot be activated.
On: The button block can be activated using the rotary switch (see chapter 3.3).
E
E
Off
On
Off
-
Access Rights
Entering access code. Setting character by character like a combination lock
(see chapter 3.6.1).
E
E
0 - 9
0000
1
RoCon U1 assign
Display only on connected
room station:
Function of the room station EHS157034 in the CAN-data bus system:
Living Room: Control panel for the heating circuit assigned in the parameter [HC As-
signment].
Mixing Valve: Mixer circuit operating unit (as a mixer circuit extension or as a free-
standing mixer circuit controller)
In addition to the aforementioned functions, the room station can be basically used as
a remotely controlled unit of the Daikin Altherma EHS(X/H) and the entire RoCon sys-
tem (with activated terminal function) (see chapter 4.1 and 4.4.2).
N
E
Living Room,
Mixing Valve
Living Room
-
Master-RoCon
Display only on connected
room station:
Setting the Master-RoCon function
Off: Deactivated
On: Function active
On a room station EHS157034, whose heating circuit ID is set to a direct heating cir-
cuit, the Master-RoCon function can be activated (see chapter 4.4.4). Several room
stations with active Master-RoCon function in the system are possible, however only
one room station is possible that is allocated to the same heat generator.
All settings on the room station EHS157034 act, with activated Master-RoCon function,
like settings on the control unit RoCon B1 B1 of the allocated heat generator. As a re-
sult, the functions for hot water preparation can also be remotely operated from the
room station.
N
E
Off
On
Off
-
Outdoor type
Type exterior heat pump unit
0: No Off selection
1: 4 kW
2: 6 kW
3: 8 kW
4: 11 kW
5: 14 kW
6: 16 kW
N
E
0 - 6
0
1
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6 x Parameter settings
INDOOR UNIT
Type of interior heat pump unit
Adaption of the set value important because the device types have different thawing
logic.
0: So far no commissioning has taken place.
1: EHS(X/H)(B)04P30A
2: EHS(X/H)(B)08P30A
3: EHS(X/H)(B)08P50A
4: EHS(X/H)(B)16P50A
N
E
0 - 4
0
1
HP Version
Version of the EHS(X/H) indoor unit
4: Version 4
5: Version 5
N
E
4 - 5
5
-
Function Heating
Setting as to whether there is an additional heat generator (WEZ) for hot water gener-
ation and heating support (see section 3.6.7).
0: No additional WEZ
1: Optional backup heater
2: Alternative WEZ takes over the hot water generation and heating support
3: Alternative WEZ 1 takes over hot water generation and alternative WEZ 2 takes
over heating support
N
E
0 - 3
1
1
HZU
Heating support from domestic hot water storage tanks when the minimum tempera-
ture is exceeded (see section 3.6.8 and parameter [TDiff-DHW CH ]).
Off: No heating support
On: Heating support function active
N
E
Off
On
On
-
Equilibrium Func.
The bivalence function is relevant for operation of the optional ancillary heater based
on a backup demand (room heating operation).
Off: Operation of the backup-heater is always possible.
On: The backup heater is only enabled if the temperature falls below the one set in the
parameter [Equilibrium Temp].
N
E
Off
On
On
-
SMART GRID
Off: Evaluation of the SG signal (see chapter 3.4.11).
0: SMART GRID function not active; SG signal not evaluated.
1: Depending on the signal from the energy supply company, the heat pump is turned
off (no frost-protection function - see section 3.6.5) or run in high-temperature mode.
N
E
0 - 1
0
-
Mode SG
Only if parameter [SMART GRID] = 1:
Used for a possible target temperature increase in the case of a SMART GRID start
command.
0: Comfort (5 K increase in target domestic hot water temperature)
1: Standard (2 K increase in inflow target temperature and 5 K increase in target do-
mestic hot water temperature)
2: Eco (5 K increase in inflow target temperature and 7 K increase in target domestic
hot water temperature)
N
E
0 - 2
1
1
HT/NT Function
Setting which specifies which heat sources are switched off when the standard signal
is received from the energy supply company (EVU) in the case of the customer having
an off-peak tariff network connection.
0: Deactivated (no Off effect)
1: Refrigerant compressor switched off
2: Refrigerant compressor and reserve heating switched off
3: Everything switched off (no frost protection - see section 3.6.5)
N
E
0 - 3
0
1
HT/NT Contact
Specifies whether the HT/NT input is an NC or NO contact.
0: NO contact (switching contact closed = standard tariff)
1: NC contact (switching contact closed = off-peak tariff)
N
E
0 - 1
0
-
Room thermostat
Configuration of a room thermostat connected to the port J16 on the Daikin
Altherma EHS(X/H) using potential-free contacts.
–
Off: Deactivated
–
On: (Only when parameter [Interlink fct] = Off)
Evaluation of
heating and
cooling switching contacts at plug connection
J16 on the RoCon BM1 circuit board (only when none of the operating modes
"Standby", "Economy mode", "Summer", "Vacation", "Holiday" or "Screed" is
active):
a)
Closed switching contact
heating: Operating mode is switched to
"Heating". Priority if both switching contacts are closed.
b)
Closed switching contact
cooling: Operating mode is switched to
"Cooling".
c)
Open contacts: only frost protection active.
N
E
Off
On
Off
-
Sub-
level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
43
Interlink fct
Configuration for systems operating with 2 different inflow target temperatures
(see section 3.6.6).
A possible use for this might be the additional integration of a FWXV(15/20)AVEB in a
surface heating and cooling system.
Requirement: 2 room thermostats need to be connected to plug connection J16 on the
Daikin Altherma EHS(X/H).
–
Off: Deactivated
–
On: Evaluation of
and cooling
switching contacts at plug connection J16
on the RoCon BM1 circuit board.
Activation of cooling mode only possible by changing operating mode to "Cooling"
(see section 3.4.2).
Setting for the parameter [Room thermostat] no longer evaluated.
a)
Open switching contacts: only frost protection active.
b)
Operating modes "Heating" and "Automatic 1" / "Automatic 2" active during
switching cycles in day mode.
–
Closed switching contact heating
= IL1:
→
The system operates according to the normal infeed target temperature
according to the parameter settings in "HC Configuration" > "Heating".
–
Closed switching contact cooling
= IL2:
→
The system operates according to the increased inflow target temperature
(normal inflow target temperature + value of parameter [T-Flow CH adj].
Priority if both switching contacts are closed.
c)
"Cooling" operating mode active.
–
Closed switching contact heating
= IL1:
→
The system operates according to the normal infeed target temperature
according to the parameter settings in "HC Configuration" > "Cooling".
–
Closed switching contact cooling
= IL2:
→
The system operates according to the reduced inflow target temperature
(normal inflow target temperature - value of parameter [T-Flow Cooling adj].
Priority if both switching contacts are closed.
N
E
Off
On
Off
-
MF 1 Config
Configuring the multi-function output (230 V, connection J14):
0: The output has no function.
1: Gathering pump – the output becomes active as soon as a heating circuit of the sys-
tem indicates a heat demand to the heat generator.
2: Circulation pump – the output is activated in accordance with the timer programme
of the circulation pump or in accordance with the timer programme of the hot water
generation, depending on the parametrisation (see chapter 3.4.7).
3: Delivery pump – the output is active as soon as there is a heat demand for the direct
heating circuit of the heat generator.
N
E
0 - 3
2
1
Air Purge
Activation of automatic bleeding of the Daikin Altherma EHS(X/H) and the connected
heating circuit (see section 3.6.10).
Off: Deactivated
On: Start of Air Purge
N
E
Off
On
Off
-
PWM Config
Max Perform Pump
Upper limit for modulation of the pump output
N
E
20 - 100 %
100 %
1 %
Min Perform Pump
Lower limit for modulation of the pump output
N
E
10 - 100 %
50%
1 %
Sensor Config
Outside Config
Configuration of the optional external temperature sensor RoCon OT1:
Off: No sensor evaluation
On: Sensor evaluation activated. This sensor is evaluated for determination of the set
flow temperatures (see chapter 3.6.4) and displayed in the standard display). An error
message is generated if an outdoor temperature sensor is connected.
N
E
Off
On
Off
-
Storage Config
Configuration of water heating:
Inactive: No function for hot water generation.
Sensor: Function for hot water generation is activated. A circulating tank temperature
sensor is evaluated for hot water generation (if no circulating tank temperature sensor
is connected, a fault message is generated).
Thermostat: Function for hot water generation is activated. A thermostatic switch (On
/ Off) is evaluated for hot water generation, and where "open brackets" are evaluated
as "no demand".
N
E
Inactive
Sensor
thermostat
Sensor
-
Pressure Config
Configuring the sensor for assessment of the system water pressure:
Off: No sensor evaluation
On: Sensor evaluation activated (if no pressure sensor is connected, a fault message
is generated.)
N
E
Off
On
On
-
Outside Temp Adap
Individual adapting for the measured value of the outdoor temperature relevant for the
Controller.
N
E
-5.0 to +5.0 kW
0,0 K
0.1 K
Terminaladress
Setting the terminal ID of the control unit for system access. The set value must be ap-
plicable for the entire system. Confirmation of this parameter using the rotary switch
reinitialises the controller.
All settings, except "Off", empower the user of the control unit to activate the terminal
function and thus to operate all RoCon system components with a valid device ID
(see chapter 3.4.9 and 4.1).
N
E
Off, 0 - 9
Off
1
System Config
System configuration of the unit, consisting of the sensor configuration and data bus
configuration. If you answer "yes" to the enquiry about using the standard configuration
when starting the unit for the first time, the basic configuration for the installed heat
generator will be activated automatically.
Confirmation of this parameter setting as "inactive" or "delete" using the rotary switch
reinitialises the controller. A fault message follows. After this the rotary switch must be
set to the position "Info". Use the rotary switch to select the required menu item.
N
E
Inactive
Active
Delete
Active.
-
Sub-
level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6 x Parameter settings
HC Assignment
Display only on connected
room station:
Setting of the heating circuit ID for the room station (see chapter 4.1). This parameter
determines which heating circuit is to be operated with it.
The direct heating circuit of the Daikin Altherma EHS(X/H) is set as standard to heating
circuit "0" (see section 6.12, parameter [Unmixed Circ Config]).
N
E
Off, 0 - 15
Off
1
Tab. 6-1
Parameter in rotary switch setting "Configuration" level "Setup"
Sub-
level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
45
6.2.2
Level "System "
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Power DHW
Heating output of electric auxiliary heater for hot water generation
N
E
1000 -
40000 W
3000 W
1000 W
BUH s1 power
Heat capacity of the ancillary electric heater in Stage 1 heating support
see operating instructions of immersion heater BUxx.
N
E
-
-
-
BUH s2 power
Heat capacity of the ancillary electric heater in Stage 2 heating support
see operating instructions of immersion heater BUxx.
N
E
-
-
-
Power BIV
Setting limits the output of the heating support.
N
E
3000 -
40000 W
15000 W
1000 W
TDiff-DHW CH
Only when parameter [HZU] = On.
Heating support activated when
Tdhw > THZUmin + 4 K and Tdhw > [T-HS Setpoint] + 1 K.
Heating support deactivated when
Tdhw < THZUmin or Tdhw < [T-HS Setpoint].
THZUmin = current active target hot water temperature [T-DHW Setpoint] + set parameter
value [TDiff-DHW CH ].
Tdhw = current hot water storage tank temperature
[T-HS Setpoint] = current active inflow target temperature (see tab. 6-12 and section 3.6.4)
N
E
2 - 15
5
1
T vbh1 max
Setting limits the inflow temperature (measured at tV, BH) with active heating support func-
tion.
N
E
5 - 85°C
60 °C
1 °C
Equilibrium Temp
Setting affects the operation of the potential-free AUX switching contact (toggle switch out-
put A) defined in the parameter [AUX Fct].
Only when parameter [Equilibrium Func.] = On.
Outdoor temperature from which the optional ancillary heating is activated for supporting
the room heating. The bivalent temperature is relevant for operation of the optional ancillary
heater based on a backup demand (room heating operation). The temperature of the sen-
sor integrated into the external unit for heat pump (info value TA2) is used.
The info value TA2 displayed can differ from the value in the standard display depending
on parameter [Outside Config].
E
E
-15 °C to
+35 °C
0 °C
1 °C
Quite Mode
Mode for low-noise operation with reduced output (see section 3.4.10).
0: Deactivated
1: Activated
2: Operated in whisper mode only at night between 22:00 and 6:00 hours.
E
E
0 - 2
0
-
AUX Fct
Setting assigns the switching conditions to the potential-free AUX contact (toggle switch
output A; see section 3.6.9).
0: Function deactivated
AUX switching contact changes;
1: When storage tank temperature (Tdhw) ≥ value of parameter [T-DHW 1 min].
2: When there is a cooling or heating demand.
3: When there is a hot water demand to the Backup Heater (EKBUxx) or the configured
Backup Heater is required for heating support.
4: When there is a malfunction.
5: When sensor value (TVBH) > 60°C.
6: When the outdoor temperature < parameter value [Equilibrium Temp].
→
Heat pump continues to operate = parallel bivalence operation.
7: When the outdoor temperature < parameter value [Equilibrium Temp] + there is a heating
or hot water demand.
→
Heat pump does not continue to operate = alternative bivalence operation.
8: When there is a hot water demand.
9: When outside temperature < parameter value [Equilibrium Temp] + heat demand "Room
heating" (not for hot water demand). Heat pump no longer operates in room heating mode
below the value set in parameter [Equilibrium Temp] - only in hot water mode.
Use: An alternative bivalency operation room heating, if the boiler is incorporated hydrauli-
cally in such a way that it heats the depressurised storage tank water in the Daikin
Altherma EHS(X/H) directly (connection via solar connections).
10: "Multi-Oil" - if outside temperature < parameter value [Equilibrium Temp] + heat demand
"Room heating" (not for hot water demand). Heat pump no longer operates in room heating
mode below the value set in parameter [Equilibrium Temp] - only in hot water mode.
Use: An alternative bivalency operation room heating, if the boiler is hydraulically incorpo-
rated in the flow of the heat pump. For this type of application, the frost protection function
must be deactivated on the Daikin Altherma EHS(X/H) (parameter [T-Frost Protect] = Off).
N
E
0 - 9
0
1
AUX time
AUX switching contact (A) switches with a delay when the switching condition (see param-
eter [AUX Fct]) is pending for longer than the set time.
N
E
0 - 600 s
120 s
5 s
T-DHW 1 min
Switching threshold storage tank temperature (Tdhw) for AUX switching contact (see pa-
rameter [AUX Fct]).
N
E
20 - 85°C
50 °C
1 °C
Delta-T CH
Set outdoor temperature spread The Daikin Altherma EHS(X/H) heating circulation pump
controls the flow rate in order to achieve the set spread between the inflow target tempera-
ture and the return flow temperature (tV, BH - tR1).
N
E
2 - 20 K
7 K
1 K
V var
Current minimum necessary volume flow in the system (calculated value, not configurable)
N
S
INFO VALUE
XXX
-
T-Flow CH adj
Only when parameter [Interlink fct] = On.
With a closed cooling RT switching contact
, the inflow target temperature is increased
by the set value (see tab. 6-1, parameter [Interlink fct]). Demand, e.g. from
FWXV(15/20)AVEB.
N
E
0 - 50 K
5 K
1 K
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6 x Parameter settings
6.2.3
Level "HC Configuration"
T-Flow Cooling adj
Only when parameter [Interlink fct] = On.
With a closed cooling RT switching contact
, the cooling inflow target temperature is re-
duced by the set value (see tab. 6-1, parameter [Interlink fct]). Demand, e.g. from
FWXV(15/20)AVEB.
N
E
0 - 50 K
5 K
1 K
Min Pressure
Defines the minimum water pressure.
Pressure monitor function (only if the pressure sensor is activated, [Pressure Config] = On,
see tab. 6-1): If the measured value falls below the set value, the Daikin Altherma EHS(X/H)
is switched off and an error message is generated.
N
E
0.1 - 5.0 bar
0.5 bar
0.1 bar
Max Pressure
Defines the maximum water pressure.
Pressure monitor function (only if the pressure sensor is activated, [Pressure Config] = On,
see tab. 6-1): If the measured value exceeds the set value, a warning message is generat-
ed.
N
E
0.1 - 5.0 bar
3.0 bar
0.1 bar
Set Point Pressure
Defines the set water pressure.
Pressure monitor function (only if the pressure sensor is activated, [Pressure Config] = On,
see tab. 6-1): If the measured value falls below the value set in the [Max Pressuredrop] pa-
rameter by more than the set amount, a warning message is generated.
N
E
0.1 - 5.0 bar
0.9 bar
0.1 bar
Max Pressuredrop
Defines the maximum acceptable pressure drop in the heating system.
Pressure monitor function (only if the pressure sensor is activated, [Pressure Config] = On,
see tab. 6-1): If the measured value exceeds the value set in the [Set Point Pressure] pa-
rameter by more than the set amount, a warning message is generated.
N
E
0.1 - 5.0 bar
0.5 bar
0.1 bar
Relay Test
Manual actuation of individual relays for test purposes. After confirmation of this parameter
using the rotary switch, the list of the relays 1 - 9 Off is displayed with selection boxes. Off-
For selection and confirmation of a relay using the rotary switch, a tick is set in the selection
box and the respective relay is activated. Off Multiple selections can be made
Relay 1: Off output J1 (internal heating circulation pump),
Off output
Relay 2: Off output J14 (Circulation pump),
Mixer "open"
Relay 3: Contact A to output Off J2 (change-over valve 3UVB1),
mixer "closed"
Relay 4: Contact B to output Off J2 (change-over valve 3UVB1)
Relay 5: Off output J12, change-over valve 3UV DHW, "closed"
Relay 6: Off output J12, change-over valve 3UV DHW, "open"
Relay 7: Port J3 (potential-free relay: NO contact B-B1) - AUX
Relay 8: Port J3 (potential-free relay: Change-over contact A-A1/A-A2) - AUX
Relay 9: Off output J10 (power supply A1P)
N
E
-
Tab. 6-2
Parameter in rotary switch setting "Configuration" level "System "
Depending on the version of the device software certain
information parameters for the device, not described in
tab. 6-2, can be displayed at this level. For this see
tab. 6-12.
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Sub-
level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
HC Function
Setting defines the type of inflow temperature control.
0: Weather-controlled flow temperature regulation
1: Regulating to a fixed set flow value, depending on the heating, cooling or setback
mode
N
E
0 - 1
0
1
T-Frost Protect
Off: No frost protection of the heating circuit
Otherwise: If the outside temperature falls below the programmed value, the system
switches into the frost protection mode (switches the pumps on). The function ceases
once the outside temperature has risen to the set value +1 K.
E
E
Off,
-15 to +5 °C
0 °C
1 °C
Insulation
Setting the insulation standard of the building. This affects the way the heating curve
and the heating times automatically adapt to the outside temperature.
E
E
Off
low
Normal
Good
Very Good
low
-
Screed
Function for screed drying
Off: Deactivated
On: The flow temperature is regulated according to the set screed programme.
The day on which the screed function is activated does not count towards the running
time of the screed programme. The first day starts as the day changes on the first day
at 00:00. On the day of activation we heat for the remaining time at the inflow temper-
ature for the first day’s program (see section 3.6.13).
N
E
Off
On
Off
-
Screed Program
Setting the procedural program for screed heating. An individual inflow temperature
can be set for each day for a maximum period of 28 days. The end of the screed pro-
gramme is defined by the 1st. Day at target value setting "- - - -" (see chapter 3.6.13).
N
E
10 - 70 °C per
heating day
See
tab. 3-11
1 °C
Heating
T-Outside lim day
Setting the automatic summer shutdown of the heating system. If the outside temper-
ature measured and averaged out by the controller exceeds the set value by 1 K, the
heating circuit is switched off. The heating is released again if the outdoor temperature
falls below the set heat curve.
E
E
Off, 10 - 40 °C
19 °C
0,5 °C
T-Outside lim night
Parameter for setting the heating limit for "Switch-off" of the heating circuit during
economy mode (functionality as for parameter [T-Outside lim day]).
E
E
Off, 10 - 40 °C
10 °C
0,5 °C
Heat-Slope
Only if parameter [HC Function] = 0:
Setting the heating curve. The heating curve reflects the dependence of the set inflow
temperature of the heating circuit on the outside temperature (see chapter 3.6.2).
E
E
0,0 - 3,0
0.5
0.1
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
47
Room Influence
Only if the room station
is connected and assigned to the heating circuit.
Setting of the impact the deviation of the room temperature measured by the
EHS157034 from the actual set value (see sections 3.4.3 and 3.4.4) has on the flow
temperature.
Off: Exclusively weather-controlled flow temperature regulation
0: Purely weather-controlled flow temperature regulation, but internal heat recircula-
tion pump continues to run until the next heating cycle following a heat demand during
the setback time.
1-20: Causes a correction of the set flow temperature (parallel shift of the heat curve)
by the set factor.
For example: If the measured temperature is 2 K below the set value, the set flow tem-
perature is raised 2-times the set value.
E
E
Off, 0 - 20
Off
1
T-Room Adj
Only if the room station
is connected and assigned to the heating circuit.
Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature as measured by the
EHS157034 from the actual temperature in the living area of this room be detected,
the measured value can be corrected by the set value.
E
E
-5.0 to +5.0 kW
0.0 K
1 K
T-Flow Day
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the heating time
when in operating mode: "Automatic 1", "Automatic 2", "Heating".
E
E
20 - 90 °C
40 °C
1 °C
T-Flow Night
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the setback time
when in operating mode: "Automatic 1", "Automatic 2", "Reducing".
E
E
10 - 90 °C
10 °C
1 °C
Max T-Flow
The inflow temperature determined for the heating circuit is limited to the maximum
value set here.
If an additionally connected mixed heating circuit demands a higher temperature for
the Daikin Altherma EHS(X/H), this is taken into account. This means that the heat in-
ternal circulation pump for the Daikin Altherma EHS(X/H) runs all the time when this
is switched on. If the connected heating circuit supplies underfloor heating, a mechan-
ical temperature limiter must be fitted to prevent overheating the screed.
N
E
20 - 90 °C
55 °C
1 °C
Min T-Flow
The inflow temperature determined for the heating circuit is limited to the minimum val-
ue set here.
N
E
28 - 90 °C
28 °C
1 °C
HC Adaption
Only if the room station
is connected and assigned to the heating circuit.
Off: Deactivated
On: Activated = Start a one-off automatic adaptation of the heating curve.
Requirements:
- Outside temperature <8 °C
- Setting the operating mode: "Automatic 1" or "Automatic 2"
- Duration of the setback phase must be at least 6 hours
Function: At the start of the setback time the current room temperature is set as the
target value for the following 4 hours. The heating curve is determined by the Control-
ler from the inflow target temperatures that are necessary to maintain this room tem-
perature.
If the automatic adjustment of the heating curve is interrupted, the function pauses un-
til it is performed successfully on the next day or until it is ended by setting the param-
eter to "Off" or by changing the current operating mode.
The hot water generation and the heating-up optimisation are blocked during the au-
tomatic heating curve adapting.
N
E
Off
On
Off
-
Cooling (
Can be used only if the assigned heat generator has a cooling function.)
Start T-Out Cooling
Only if parameter [HC Function] = 0:
Setting from which outside temperature the cooling operation with the highest cooling
infeed target temperature [T-Flow Cooling start] starts (setting condition: operating
mode "Cooling").
E
E
15 - 45 °C
24 °C
1 °C
Max T-Out Cooling
Only if parameter [HC Function] = 0:
Setting to determine from which outdoor temperature the lowest cooling flow temper-
ature [T-Flow Cooling max] is stipulated (setting condition: operating mode "Cooling").
E
E
20 - 45 °C
35 °C
1 °C
T-Flow Cooling start Only if parameter [HC Function] = 0:
Setting the cooling inflow target temperature at the start of cooling mode (outside tem-
perature = parameter [Start T-Out Cooling]).
E
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling max
Only if parameter [HC Function] = 0:
Setting the minimum cooling inflow target temperature. This is kept constant relative
to the outside temperature (parameter [Max T-Out Cooling]).
E
E
5 - 25 °C
8 °C
1 °C
Min T-Flow Cooling
Only if parameter [HC Function] = 0:
Setting the absolute lower limit of the cooling inflow target temperature. The limitation
is effective if a lower cooling inflow target temperature is determined based on other
parameter settings.
N
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling
Only if parameter [HC Function] = 1:
Setting the cooling inflow target temperature (fixed value) when cooling mode is ac-
tive.
E
E
8 - 30 °C
18 °C
1 °C
T_H/C Switch
Automatic activation of the cooling mode.
Off: Deactivated
10 - 40: If the outdoor temperature exceeds the set value, the operating mode
"Cooling" is set. If the outdoor temperature falls below the set value by 2 K, the system
automatically switches back to the previously activated operating mode.
N
E
Off, 10 - 40 °C
Off
1 °C
Cooling Setpoint adj Parallel displacement of the cooling characteristic curve to match the set value.
E
E
-5.0 to +5.0 kW
0.0 K
1 K
Tab. 6-3
Parameter in rotary switch setting "Configuration" level "HC Configuration"
Sub-
level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6 x Parameter settings
6.2.4
Level "DHW Configuration"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Circl-Pump DHW
Setting for activating a circulation pump.
Off: Optional circulation pump operates according to the timer programme [Circulation Time].
On: The optional circulation pump operates synchronously with the switching timer program
activated for generation of hot water.
E
E
Off
On
Off
-
Circl-Pump Interval
Setting the interval control for an optional circulation pump.
Off: Deactivated The circulation pump operates continuously throughout the enabled time of
the assigned switching timer program (parameter [Circl-Pump DHW]).
Otherwise: The circulation pump runs cyclically (duty ratio: pump running time = set value
every 15 min).
E
E
Off,
1 - 15 min
Off
1 min
Anti-Legionella day
Setting the day for the thermal disinfection of the circulating tank.
Off : No thermal disinfection
Monday - Sunday Day for thermal disinfection
Mon - Sun: Daily thermal disinfection
E
E
Off,
Monday
...
Sunday,
Mon - Sun
Off
-
Anti-Legionella time
Setting the start time of the thermal disinfection of the hot water circulating tank (format
hh:mm).
N
E
00:00 - 23:45
03:30
15 min
Anti-Legionella temp Setting the hot water target temperature during thermal disinfection of the hot water circulat-
ing tank (format hh:mm).
N
E
60 - 70 °C
65 °C
1 °C
Max DHW loading
Setting limits the time period for hot water generation to the set target value [T-DHW Set-
point]. After expiry of this time period, the controller automatically returns to the previously
active operating mode. The hot water generation takes place at the actual set value.
N
E
0 - 240 min
60 min
10 min
DHW Off Time
Setting the block time following completion or interruption of a hot water generation cycle.
New demand of hot water generation is satisfied only after expiry of this block time.
N
E
0 - 180 min
30 min
10 min
Tab. 6-4
Parameter in rotary switch setting "Configuration" level "DHW Configuration"
6.3
Rotary switch setting: DHW Install
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
1x Hot Water
Start of the one-off heating up of the hot water and the set value [T-DHW Setpoint 1], inde-
pendent of the heating programmes.
E
E
Off
On
Off
-
Hyst HP
Switching threshold hot water charging
Setting of the temperature difference to which the temperature in the domestic hot water
storage tank compared to the current target hot water temperature [T-DHW Setpoint] can
drop before the heat pump is switched on to provide hot water.
E
E
2 - 20 K
7 K
1 K
Timer BOH
Delay time after which the reserve heating may support the heat pump in hot water charg-
ing (see section 3.6.7).
E
E
20 - 95 min
50 min
1 min
Tab. 6-5
Parameter in rotary switch setting "DHW Install"
6.4
Rotary switch setting: Operating Mode
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Standby
In this operating mode, all internal functions are turned off. Frost protection remains active
and a blocking protection for the pump is guaranteed.
All controllers integrated in the RoCon-system via the CAN bus are also switched at a higher
level to the operating mode when this setting is selected.
Outputs are not free of voltage always.
E
E
-
Reducing
The internal heating circuit provides continuous (24 h per day) regulation to the para-
metrised setback temperature. The hot water generation takes place according to
[DHW Program 1].
E
E
-
Heating
The internal heating circuit provides continuous (24 h per day) regulation to the para-
metrised day set room temperature (heating). The hot water generation takes place accord-
ing to [DHW Program 1].
E
E
-
Cooling
The internal heating circuit provides continuous (24 h per day) regulation to the para-
metrised day room temperature set (cooling). The hot water generation takes place accord-
ing to [DHW Program 1].
Frost protection remains active and a blocking protection for the pump is guaranteed.
E
E
-
Summer
The internal heating circuit is turned off. Frost protection remains active and a blocking pro-
tection for the pump is guaranteed. The hot water generation takes place according to
[DHW Program 1].
All controllers integrated in the RoCon-system via the CAN bus are also switched at a higher
level to the operating mode when this setting is selected.
E
E
-
Automatic 1
The internal heating circuit regulates according to the parametrised timer programme
[HC Program 1] with the individual day room temperatures set. The hot water generation
takes place according to [DHW Program 1].
E
E
-
Automatic 2
The internal heating circuit regulates according to the parametrised timer programme
[HC Program 2] with the individual day room temperatures set. The hot water generation
takes place according to [DHW Program 2].
E
E
-
Tab. 6-6
Parameter in rotary switch setting "Operating Mode"
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
49
6.5
Rotary switch setting: Set Temp Day
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-Room 1 Setpoint
Target room temperature for the 1st switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0,5 °C
T-Room 2 Setpoint
Target room temperature for the 2nd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0,5 °C
T-Room 3 Setpoint
Target room temperature for the 3rd switching cycle of the timer programmes [Automatic 1]
and [Automatic 2].
E
E
5 - 40 °C
20 °C
0,5 °C
Tab. 6-7
Parameter in rotary switch setting "Set Temp Day"
6.6
Rotary switch setting: Set Temp Night
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-Reduced
Target room temperature for the setback times for the permanent timer programmes
[Automatic 1] and [Automatic 2].
E
E
5 - 40°C
15 °C
0,5 °C
T-Absence
Target room temperature for the setback times for the temporary timer programmes [Away]
and [Vacation].
E
E
5 - 40°C
15 °C
0,5 °C
Tab. 6-8
Parameter in rotary switch setting "Set Temp Night"
6.7
Rotary switch setting: DHW Set Temp
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
T-DHW Setpoint 1
Target hot water temperature for the 1st switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
T-DHW Setpoint 2
Target hot water temperature for the 2nd switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
T-DHW Setpoint 3
Target hot water temperature for the 3rd switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E
E
35 - 70 °C
48 °C
1 °C
Tab. 6-9
Parameter in rotary switch setting "DHW Set Temp"
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6 x Parameter settings
6.8
Rotary switch setting: Time Program
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Party
The heating circuit operates at the target room temperature set in the [T-Room 1 Setpoint]
parameter for the set period of time. If the [Automatic 1] or [Automatic 2] timer programmes
are active, the heating cycle is extended or started early. (Target room temperature - see
section 3.4.7).
The hot water generation is not affected.
E
E
00:00 - 06:00
00:00
1 h
Away
The heating circuit operates at the target room temperature set in the [T-Absence] parameter
for the set period of time.
The hot water generation is not affected.
E
E
00:00 - 06:00
00:00
1 h
Vacation
The heating circuit operates at the target room temperature set in the [T-Absence] parameter
permanently (24 h per day).
A calendar function can be used to enter a time period for the absence.
E
E
Date on first
day
-
Date on last
day:
-
1 Day
Holiday
A calendar function can be used to enter a time period for presence.
During this time, the system operates exclusively in accordance with the "Sunday" settings
in [DHW Program 1] and [HC Program 1].
E
E
Date on first
day
-
Date on last
day:
-
1 Day
HC Program 1
In this menu we can parametrise the 1st. timer programme for the heating circuit. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is pos-
sible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
tab. 3-9
15 min
HC Program 2
In this menu we can parametrise the 2nd. timer programme for the heating circuit. 3 switch-
ing cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is
possible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
tab. 3-9
15 min
DHW Program 1
In this menu we can parametrise the 1st. timer programme for hot water generation. 3 switch-
ing cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is
possible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
tab. 3-9
15 min
DHW Program 2
In this menu we can parametrise the 2nd. timer programme for hot water generation.
3 switching cycles with a resolution of 15 minutes can be set. A separate entry for each
weekday is possible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
tab. 3-9
15 min
Circulation Time
In this menu we can parametrise a timer programme for the circulation pump. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is pos-
sible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
tab. 3-9
15 min
Tab. 6-10 Parameter in rotary switch setting "Time Program"
6.9
Rotary switch setting: Remote Param
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Bus - Scan
Off: No function
On: Controller checks which RoCon devices are connected to the system using the CAN bus
lines. Devices that are detected are displayed with their type and device ID (see chapter 4.1,
example: MM#8 = Mixer module with device ID 8).
The selection and confirmation of a device with the rotary switch (brief pressing of the button
places a check mark in the selection box) activates the terminal function.
→
The control unit then operates as a remote control for the selected device
(see chapter 3.4.9).
E
E
Off
On
Off
-
No selection
Activation switches to the local device.
E
E
-
Contr BM1/BE1 #X
Activation switches to the Daikin Altherma EHS(X/H) with the device ID X (see section 6.12,
parameter [BUS ID HS]).
E
E
-
Mix Valve #X
Activation switches to the mixer module with the device ID X (see section 6.13.1, parameter
[HC Assignment]).
E
E
-
Tab. 6-11 Parameter in rotary switch setting "Remote Param"
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
51
6.10 Rotary switch setting: Info
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Overview
Display of different current operating data (see section 3.4.1).
S
S
-
-
-
Water Pressure
The current water pressure is displayed in bar.
S
S
0 - 4 bar
-
0.1 bar
T-HS
The current temperature (TVBH) of the heat generator is displayed in °C.
S
S
0 - 100 °C
-
1 °C
T-HS Setpoint
The current Inflow target temperature of the heat generator is displayed in °C
(see section 3.6.4).
S
S
0 - 90 °C
-
0.1 °C
T-Outside
The average external temperature is displayed °C.
S
S
-39 to +50 °C
0.1 °C
T-DHW
The current temperature of the hot water storage tank is displayed in °C. If there is no hot
water function activated, "- - -" is displayed.
S
S
0 - 100 °C
-
0.1 °C
T-DHW Setpoint
The current target hot water temperature is displayed °C. If there is no hot water function ac-
tivated, "- - -" is displayed. The current set value is here always the maximum value of all
relevant demands for this hot water circuit.
S
S
10 - 70°C
-
0.1 °C
T-Return
The current return flow temperature of the heat generator is displayed in °C. If there is no
relevant sensor connected to the heat generator, "- - -" is displayed.
S
S
0 - 100 °C
-
0.1 °C
Flow Rate
The filtered value of the current volume flow in litres per hour is displayed.
S
S
0 - 5100 l/h
-
l/h
T-HC
The inflow temperature in the direct heating circuit is displayed in °C.
S
S
0 - 100 °C
-
0.1 °C
T-HC Setpoint
The set temperature of the flow in the direct heating circuit is displayed in °C.
S
S
0 - 90 °C
-
0.1 °C
Status HS pump
The current status of the internal heat circulation pump in the Daikin Altherma EHS(X/H) is
displayed.
S
S
Off
On
-
-
Runtime Compres-
sor
The running time of the refrigerant compressor is displayed in h.
S
S
-
-
h
Runtime Pump
The running time of the internal heating circulation pump is displayed in h.
S
S
-
-
h
Mixer Position
The current position of the 3UV DHW 3-way switch valve is displayed.
0%: Position A (room heating)
100%: Position B (domestic hot water generation)
S
S
0 - 100 %
-
1 %
Qboh
The amount of heat in the additional heat generator for hot water generation is displayed in
kWh.
S
S
-
-
kWh
Qchhp
The amount of heat in the additional heat generator for heating mode is displayed in kWh.
S
S
-
-
kWh
Qsc
The quantity of heat in the heat pump for cooling is displayed in kWh.
S
S
-
-
kWh
Qch
The quantity of heat in the heat pump for heating is displayed in kWh.
S
S
-
-
kWh
QWP
The total amount of heat in the heat pump is displayed in kWh.
S
S
-
-
kWh
Qdhw
The quantity of heat for hot water generation is displayed in kWh.
S
S
-
-
kWh
HS type
The heat generator type Daikin Altherma EHS(X/H) detected is displayed.
S
S
-
-
-
Sw Nr B1/U1
The software and version of the control unit RoCon B1 B1 /
of the room station
EHS157034is displayed.
S
S
-
-
-
Sw Nr Controller
The software number and the version of the RoCon BM1 circuit board are displayed.
S
S
-
-
-
Sw Nr RTX RT
The software number and the version of the RTX-AL4 circuit board are displayed.
S
S
-
-
-
Tab. 6-12 Parameter in rotary switch setting "Info"
6.11 Exit button: Sonderfunktion
Depress the exit button for at least 5 secs. for access.
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Manual Operation
The direct heating circuit and the target hot water temperature are controlled according to
the temperature set in this parameter (see section 3.5.1).
E
E
20 - 80 °C
50 °C
1 °C
FA failure
Display of a current heat pump malfunction in the Daikin Altherma EHS(X/H).
If "----" is displayed there is no fault (see chapter 7).
E
E
-
-
-
Protocol
Display of protocol (error and information messages). Here we display the saved messages
of the Daikin Altherma EHS(X/H) and the connected RoCon system components with date
and code as a menu entry in each case. By selecting an entry to using the rotary switch, all
other corresponding information is displayed concerning the selected message:
- Date and time of the message
- Code number (Information for the heating technician)
- Device type from which the message comes
- Device ID for the RoCon unit where the message originates
E
E
-
-
-
Delete message
By setting this parameter to "On" and briefly pressing the rotary switch, all entries in the re-
port, including the faults from connected RoCon system components, are deleted.
E
E
Off
On
Off
-
RoCon B1/U1 Reset Resets all parameter settings to factory setting. Required for software updates or changes
to the RoCon system (see chapter 4.2). Complete reconfiguration subsequently required.
N
E
Off
On
Off
-
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6 x Parameter settings
6.12 Parameter level "Basic Configuration"
This parameter level appears only if:
–
during initial commissioning, during the question "Use Stand-
ard Config?" the answer "No" has been selected or
–
after, in the rotary switch position "Configuration"
, level
"Setup" the parameter [System Config] has been set to "inac-
tive" or "delete".
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Boiler Function
Setting of system functionality of the device in the RoCon system (factory setting not pre-
sent).
The standard value of this parameter is "Single" and thus applies to a Daikin
Altherma EHS(X/H) in self-contained operating mode.
With value settings "Slave 1" to "Slave 8" the Daikin Altherma EHS(X/H) works as a heater
module and waits for the demand for an optional cascade regulator.
These settings are not currently usable.
N
E
Single,
Slave 1
...
Slave 8
Single
-
Unmixed Circ Config Setting the heating circuit ID for the direct heating circuit of the Daikin Altherma EHS(X/H).
The heating circuit ID must be unique in the entire RoCon system. There should be no over-
lap with the heating circuit IDs of optional mixer circuits (parameter [HC Assignment],
see tab. 6-15).
N
E
0 - 15
0
1
BUS ID HS
Settings can only be changed if more than 1 heat generator is incorporated in the RoCon sys-
tem. Several heat generators incorporated in the heating installation must be regarded as a
special application. If necessary contact Daikin service technician.
N
E
0 - 7
0
1
Time Master
Activation of a system-wide time master RoCon. The time master synchronises all controllers
in the Can system with the date and time set at the time master. The input of time and date
can no longer be set at any other control unit in the system. There may be only one time mas-
ter in the entire system. The parameter is not available if the time master parameter is acti-
vated at a different controller in the RoCon system.
N
E
Off
On
On
-
System Config
The system configuration of the unit, consisting of the sensor configuration and data bus con-
figuration, can be deleted, activated and deactivated with this parameter. If you answer "Yes"
to the enquiry about using the standard configuration, when starting the unit for the first time,
the settings required for the basic equipment of the heat generator are activated automatical-
ly (see section 6.2.1, tab. 6-1).
N
E
Inactive,
Active,
Delete
Inactive
-
Tab. 6-14 Parameter in the level "Basic Configuration"
6.13
Parameter levels for the EHS157068 mixer module
The parameter levels, parameter priorities, setting ranges and
associated functions are essentially the same as those described
in the preceding sections.
In some cases there exist at individual levels a restricted scope
of available parameters.
The description below relates only to the sections indicated.
Areas where there are significant differences are described in
greater detail.
Rotary switch setting: Info
see section 6.10
When setting the control unit to "Mix Valve #X" (terminal
function), the displayed values refer to the components con-
nected (pump, mixer valve,...) connected to the EHS157068 of
the mixer circuit allocated using the device ID.
When setting a room station EHS157034 to "Living Room", that
has been allocated to the mixer module via the heating circuit ID,
the parameter [T-Room adj] is available. The rotary switch can be
used to change the room target temperature to the range -5 K to
+5 K. This function is not available if the EHS157034 is used as
a remote control in terminal function.
Rotary switch setting: Operating Mode
see section 6.4
Rotary switch setting: Set Temp Day
see section 6.5
Rotary switch setting: Set Temp Night
see section 6.6
Rotary switch setting: DHW Set Temp
No function
Rotary switch setting: DHW Install
No function
Rotary switch setting: Time Program
see section 6.8
Rotary switch setting: Configuration
(see section 6.13.1 and 6.13.2.
Rotary switch setting: Remote Param
see section 6.9
Parameter Reset
Resets all customer-specific parameter settings to factory setting.
N
E
Off
On
Off
-
Timeprog Reset
Resets all permanent time programmes to factory setting (see tab. 3-9).
E
E
Off
On
Off
-
Return
This parameter is used only to exit the special level.
E
E
Tab. 6-13 Parameter in the level "Sonderfunktion"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
53
6.13.1
Rotary switch setting: Configuration
, level "Setup"
Sub-
level
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
LCD Brightness
Display brightness
E
E
0 - 100 %
50%
10 %
LCD Illum Time
Duration of display lighting
E
E
5 - 120 s
30 s
1 s
Language
Language of the display text in the operating panel
E
E
Deutsch
English
French
Dutch
Italian
Spanish
Portuguese
Deutsch
1
Date
Current date in format day / month / year. The current day of the week is calculated
automatically from the date.
E
E
Time
Time in format hours / minutes.
E
E
Keylock Function
Release of the keylock function:
Off: Button block cannot be activated.
On: The button block can be activated using the rotary switch (see chapter 3.1).
E
E
Off
On
Off
-
Access Rights
Entering access code. Setting character by character like a combination lock
(see chapter 3.6.1).
E
E
0 - 9
0000
1
RoCon U1 assign
Display only on connected
room station:
Function of the room station EHS157034 in the CAN-data bus system:
Living Room: Control unit for the heating circuit assigned in the parameter [HC Assign-
ment] (heating circuit ID).
Mixing Valve: Mixer circuit operating unit (as a mixer circuit extension or as a free-
standing mixer circuit controller)
In addition to the aforementioned functions, the room station can be basically used as
a remotely controlled unit of the Daikin Altherma EHS(X/H) and the entire RoCon sys-
tem (with activated terminal function) (see chapter 4.1 and 4.4.2).
N
E
Living Room,
Mixing Valve
Living Room
-
PWM Config
Min Perform Pump
Lower limit for modulation of the pump output
N
E
0 - 100 %
50%
1 %
Max Perform Pump
Upper limit for modulation of the pump output
N
E
0 - 100 %
100%
1 %
Sensor Config
Outside Config
Configuration of the outside temperature sensor:
Off: Take-over of outdoor temperature of heat generator, to which the mixer module is
allocated by the heat generator ID (Parameter [Boiler Assignment]), or no sensor eval-
uation
On: Sensor evaluation activates (if an outdoor temperature sensor is not connected to
the EHS157068 mixer module, an error message is generated.)
N
E
Off
On
On
-
Outside Temp Adap
Individual adapting for the measured value of the outdoor temperature relevant for the
Controller.
N
E
-5.0 to +5.0 kW
0,0 K
0.1 K
Terminaladress
Setting the terminal ID of the control unit for system access. The set value must be ap-
plicable for the entire system. Confirmation of this parameter using the rotary switch
reinitialises the controller.
All settings, except "Off", empower the user of the control unit to activate the terminal
function and thus to operate all RoCon system components with a valid device ID
(see chapter 3.4.9 and 4.1).
N
E
Off, 0 - 9
Off
1
Boiler Assignment
Setting the heat generator ID. Allocation of the EHS157068 to the heat generator.
The setting must correspond to the value of the parameter [BUS ID HS]
(see section 6.12, tab. 6-14).
N
E
0 - 7
0
1
HC Assignment
Setting the heating circuit ID of the mixer module.
Off: Automatic allocation when there is just one mixer module in the system (system
takes over the value of the address switch as the heating circuit ID, irrespective of the
set value). The setting must always match the heating circuit ID on the address switch
of the mixer module (see section 4.4.1, fig. 4-2).
0 - 9 = 0 - 9
10 = A
11 = B
12 = C
13 = D
14 = E
15 = F
N
E
Off, 0 - 15
Off
1
Tab. 6-15
Parameter in rotary switch setting "Configuration" level "Setup"
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6 x Parameter settings
6.13.2
Rotary switch setting: Configuration
, level "Mixer Config"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
HC Function
Setting defines the type of inflow temperature control.
0: Weather-controlled flow temperature regulation
1: Regulating to a fixed set flow value, depending on the heating, cooling or setback mode
N
E
0 - 1
0
1
Pump Mode
Setting the operating mode of the mixer circuit pump.
0: Standard mixer circuit pump switching according to weather conditions / room tempera-
ture
1: Mixer circuit pump switching according to heating limits (optional room thermostat switch-
off also effective).
2: Mixer circuit pump switching according to heating programme
3: Mixer circuit pump in continuous running mode
N
E
0 - 3
0
1
T-Outside lim day
Only if parameter [Pump Mode] = 1:
Setting the automatic summer shutdown of the heating system. If the outside temperature
measured and averaged out by the controller exceeds the set value by 1 K, the heating cir-
cuit is switched off. The heating is enabled again once the outside temperature falls below
the set heating curve.
E
E
Off, 10 - 40 °C
19 °C
0,5 °C
T-Outside lim night
Only if parameter [Pump Mode] = 1:
Parameter for setting the heating limit for switch-off of the heating circuit during economy
mode (functionality as for parameter [T-Outside lim day]).
E
E
Off, 10 - 40 °C
10 °C
0,5 °C
Heat-Slope
Only if parameter [HC Function] = 0:
Setting the heating curve. The heating curve reflects the dependence of the set inflow tem-
perature of the heating circuit on the outside temperature (see chapter 3.6.2).
E
E
0,0 - 3,0
0.5
0.1
Room Influence
Only if the room station
is connected and assigned to the heating circuit.
Setting of the impact the deviation of the room temperature measured by the EHS157034
from the actual set value (see sections 3.4.3 and 3.4.4) has on the flow temperature.
Off : Exclusively weather-controlled flow temperature regulation
0: Purely weather-controlled flow temperature regulation, but internal heat recirculation
pump continues to run until the next heating cycle following a heat demand during the set-
back time.
1-20: Causes a correction of the set flow temperature (parallel shift of the heat curve) by the
set factor.
For example: If the measured temperature is 2 K below the set value, the set flow temper-
ature is raised 2-times the set value.
E
E
Off, 0 - 20
Off
1
T-Room Adj
Only if the room station
is connected and assigned to the heating circuit.
Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature as measured by the EHS157034
from the actual temperature in the living area of this room be detected, the measured value
can be corrected by the set value.
E
E
-5.0 to +5.0 kW
0.0 K
1 K
T-Flow Day
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the heating time when in
operating mode: "Automatic 1", "Automatic 2", "Heating".
E
E
20 - 90 °C
40 °C
1 °C
T-Flow Night
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the setback time when in
operating mode: "Automatic 1", "Automatic 2", "Reducing".
E
E
10 - 90 °C
10 °C
1 °C
Max T-Flow
The inflow temperature determined for the heating circuit is limited to the maximum value
set here.
N
E
20 - 70 °C
50 °C
1 °C
Min T-Flow
The inflow temperature determined for the heating circuit is limited to the minimum value set
here.
N
E
10 - 70 °C
10 °C
1 °C
HC Adaption
Only if the room station
is connected and assigned to the heating circuit.
Off: Deactivated
On: Activated = Start a one-off automatic adaptation of the heating curve.
Requirements:
- Outside temperature <8 °C
- Setting the operating mode: "Automatic 1" or "Automatic 2"
- Duration of the setback phase must be at least 6 hours
Function: At the start of the setback time the current room temperature is set as the target
value for the following 4 hours. The heating curve is determined by the Controller from the
inflow target temperatures that are necessary to maintain this room temperature.
If the automatic adjustment of the heating curve is interrupted, the function pauses until it is
performed successfully on the next day or until it is ended by setting the parameter to "Off"
or by changing the current operating mode.
Heating-up optimisation is blocked during automatic adaptation of the heating curve.
N
E
Off
On
Off
-
Slope Offset
Setting the increase in the inflow target temperature for the Daikin Altherma EHS(X/H) com-
pared to the set flow temperature determined for the mixer circuit.
N
E
0.0 - 50.0 K
5,0 K
1 K
T-Frost Protect
Off: No frost protection of the heating circuit
Otherwise: If the outside temperature falls below the programmed value, the system switch-
es into the frost protection mode (switches the pumps on). The function ceases once the
outside temperature has risen to the set value +1 K.
E
E
Off,
-15 to +5 °C
0 °C
1 °C
Insulation
Setting the insulation standard of the building. This affects the way the heating curve and
the heating times automatically adapt to the outside temperature.
E
E
Off
low
normal
good
very good
normal
-
Forced Performance Not applicable.
N
E
Off
On
Off
-
6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
55
Start T-Out Cooling
Can be used only if the assigned heat generator has a cooling function
.
Only if parameter [HC Function] = 0:
Setting from which outside temperature the cooling operation with the highest cooling infeed
target temperature [T-Flow Cooling start] starts (setting condition: operating mode "Cool-
ing").
E
E
20 - 45 °C
24 °C
1 °C
Max T-Out Cooling
Can be used only if the assigned heat generator has a cooling function
.
Only if parameter [HC Function] = 0:
Setting to determine from which outdoor temperature the lowest cooling flow temperature
[T-Flow Cooling max] is stipulated (setting condition: operating mode "Cooling").
E
E
20 - 45 °C
35 °C
1 °C
T-Flow Cooling start Can be used only if the assigned heat generator has a cooling function
.
Only if parameter [HC Function] = 0:
Setting the cooling inflow target temperature at the start of cooling mode (outside tempera-
ture = parameter [Start T-Out Cooling]).
E
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling max
Can be used only if the assigned heat generator has a cooling function
.
Only if parameter [HC Function] = 0:
Setting the minimum cooling inflow target temperature. This is kept constant relative to the
outside temperature (parameter [Max T-Out Cooling]).
E
E
5 - 25 °C
18 °C
1 °C
Min T-Flow Cooling
Can be used only if the assigned heat generator has a cooling function
.
Only if parameter [HC Function] = 0:
Setting the absolute lower limit of the cooling inflow target temperature. The limitation is ef-
fective if a lower cooling inflow target temperature is determined based on other parameter
settings.
N
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling
Can be used only if the assigned heat generator has a cooling function
.
Only if parameter [HC Function] = 1:
Setting the cooling inflow target temperature (fixed value) when cooling mode is active.
E
E
8 - 30 °C
18 °C
1 °C
Cooling Setpoint adj Can be used only if the assigned heat generator has a cooling function
.
Parallel displacement of the cooling characteristic curve to match the set value.
N
E
-5.0 to +5.0 kW
0.0 K
1 K
Relay Test
See Section 6.2.2, tab. 6-2.
N
E
-
Screed
Function for screed drying
Off: Deactivated
On: The flow temperature is regulated according to the set screed programme. The day on
which the screed function is activated does not count towards the running time of the screed
programme. The first day starts as the day changes on the first day at 00:00. On the day of
activation we heat for the remaining time at the inflow temperature for the first day’s program
(see section 3.6.13).
N
E
Off
On
Off
-
Screed Program
Setting the procedural program for screed heating. An individual inflow temperature can be
set for each day for a maximum period of 28 days. The end of the screed programme is de-
fined by the 1st. Day at target value setting "- - - -" (see chapter 3.6.13).
N
E
10 - 70 °C per
heating day
See
tab. 3-11
1 °C
Tab. 6-16
Parameter in rotary switch setting "Configuration" level "Mixer Config"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
7 x Errors, malfunctions and messages
7
Errors, malfunctions and messages
CAUTION!
Electrostatic charges can lead to voltage
arcing that can destroy the electronic
components.
● Secure potential equalisation before
touching electronic parts (e.g. by
touching an earthed metallic part).
7.1
Recognising errors, correcting
malfunctions
Electronic control of the Daikin Altherma EHS(X/H):
–
signals an error by means of the background of the display
lighting up red and shows an error code in the display
(see section 7.3).
–
shows information messages regarding the operating status
(not signalled by red background lighting).
An integrated Protocol saves up to 15 error-related or other infor-
mation messages regarding the operating status that last oc-
curred.
Depending on the operating mode, messages are also forwarded
to connected room stations or room thermostats.
7.1.1
Current fault display
1
2
3
E 75
Inside Unit:
Address:
Boiler
0
1
Error message as a code (see section 7.3)
2
Location information (equipment) of the detected fault
3
Device ID for the RoCon unit where the message originates
Fig. 7-1
Displays an active error message (controller fault)
1
2
3
4
Inside Unit:
Address:
Heating Mod-
ule 0
E 9001 / 80
Fault T-return
1
Error message as a code (see section 7.3)
2
Fault message as plain language (see section 7.3)
3
Location information (equipment) of the detected fault
4
Device ID for the RoCon unit where the message originates
Fig. 7-2
Display of a current error message (heat pump fault)
7.1.2
Read Protocol
The Protocol can be read in the "Special Level" (see fig. 7-3).
The last received (latest) message is in the first position. All other
previous messages are then pushed backwards by one place
when a new entry is made. The 15th message will be deleted any
time a new message is received.
E75
E75
E75
Special Level
Manual Operation
FA failure
Protocol
Special Level
FA failure
Protocol
Delete message
Inside Unit:
Address:
Boiler
0
Read Protocol
Fig. 7-3
Reading the protocol
7.1.3
Troubleshooting
Information messages, which are displayed without red back-
lighting, normally result in no permanent limitations on the op-
eration of the Daikin RoCon.
Messages that are displayed with an error code E.... and red
back-lighting required error correction by an authorised and
trained expert heating technician.
For information on warning messages see section 7.3.
●
Detecting and remedying the cause of the malfunction.
–
Contactor triggered:
Nothing shown on the display in the controller. Ascertain
cause of triggering the contactor and remedy fault. Start up
system again.
Once the cause has been remedied, the system will
resume operations as normal.
–
Contactor not triggered:
a) No fault codes are shown but the system is not working
properly. Troubleshooting and eliminating faults
(see section 7.3).
Once the cause has been eliminated, the system contin-
ues to work normally.
b) Fault codes are displayed as long as the fault conditions
are present. Troubleshooting and eliminating faults
(see section 7.3). If the fault message is still displayed
after the cause of the fault has been corrected, the system
must be disconnected fromthe power supply for at least
10 in order to unlock it.
Once the cause has been eliminated, the system contin-
ues to work normally.
In order to ensure that the fault has not been caused by
incorrect setting, set all the parameters back to the
factory settings before possible replacement of compo-
nents (see chapter 3.6.12).
If you are unable to determine the cause of failure
yourself, Daikinplease consult a service technician.
Have the significant equipment data to hand
(see fig. 7-4 for the procedure):
–
Type and manufacturer number of the Daikin
Altherma EHS(X/H)s (see heat pump identifica-
tion plate).
–
Software versions (see fig. 7-4) of:
a: Control unit RoCon B1 [Sw Nr B1/U1]
b: Circuit board RoCon BM1 [Sw Nr Controller]
c: RTX-AL4 circuit board [Sw Nr RTX RT]
–
On optional RoCon system components:
EHS157034 [Sw Nr B1/U1]
EHS157068 [Sw Nr mixing valve]
Info
Overview
Water Pressure
T-HS
Sw Nr B1/U1
Sw Nr RTX RT
Sw Nr Controller
Info
Sw Nr B1/U1
Sw Nr Controller
Sw Nr RTX RT
Info
Sw Nr B1/U1
Sw Nr mixing valve
Sw Nr mixing valve
Fig. 7-4
Software information of the controller components
7 x Errors, malfunctions and messages
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
57
7.2
Emergency operation
In the case of incorrect setting in the electronic control system or
malfunction of the 3-way diverter valves, emergency heating op-
eration can be maintained by activating the special "Manual Op-
eration" function on the control unit (see chapter 3.5.1 and the
supplementary instructions in the installation and mainte-
nance manual of the Daikin Altherma EHS(X/H).
7.3
Malfunctions and fault codes
See Daikin Altherma EHS(X/H) installation and maintenance
manual; section: "Faults, malfunctions, messages".
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
8 x Glossary
8
Glossary
Ancillary heater
An additional heat generator (e.g. backup heater or external heating boiler) which is part of the heating
system and which helps bring the system up to the inflow target temperature in case of an insufficient
or ineffective heat pumping process.
Anti-legionella system
Periodic heating of storage water to >60°C for preventative elimination of pathogenic bacteria
(legionella) in the hot water circuit.
Backup demand
Operating situation in which the desired infeed temperature cannot be reached or cannot be achieved
efficiently through the heat pump process. As a result, an extra heater (e.g. backup heater) is used to
support the Daikin Altherma EHS(X/H) to generate heat.
Backup heater
Optional electric ancillary heater for general support of the Daikin Altherma EHS(X/H) during heat gen-
eration.
Circulation pump
An optional electrical circulation pump which permanently recirculates the hot water in the hot water
pipes (feed from the tap connection back to the domestic hot water storage tank) and thus provides it
at each draw-off point without delay. Circulation is particularly effective in widely branched piping net-
works. In hot water distribution systems without a circulation pipe, at first the water cooled in the outlet
pipe escapes during the tapping process until the outlet pipe is sufficiently heated by the hot water
flowing subsequently.
Control
Device electronics, with which the processes for heat generation and heat distribution for the heating
system are controlled. The Controller consists of many electronic components. The component that is
most important to the operator is the operating element at the front of the heat generator which has
operating elements (rotary switch, rotary button and Exit key) and a display.
Domestic hot water
generation
Operating status of the heat generator, in which heat is generated at increased temperatures and sup-
plied to the hot water circuit, e.g. filling the hot water storage tank.
Flow pipe
Part of the hydraulic circuit that directs the heated water from heat generator to the heating surfaces.
Heat exchanger
A part that transfers thermal energy from one circuit to another. Both circuits are separated from each
other hydraulically by a wall in the heat exchanger.
Heat pumping process
In a closed coolant circuit, the coolant absorbs heat from the surrounding air. Compressing this coolant
results in a higher temperature which can then be transferred to the heating unit (thermodynamic
circuit).
Heating characteristic curve
Mathematical relationship between the external temperature and the target flow temperature (synonym
= heating curve), in order to achieve the desired room temperature at all outside temperatures.
Hot water circuit
Is the water circuit in which the cold water is heated and directed to the hot water discharge point.
Low tariff mains connection
(HT/NT)
A special mains connection to the energy supplier, which offers various cheaper rates during so-called
low-load periods for electrical current (day-, night-, heat pump current, etc.).
Modulation
Automatic and continuous adjustment of the thermal / pump output to the particular heat requirement,
without having to switch various heating / pumping stages or cycles.
Nominal output
Maximum heat output given by the heat generator at certain operating temperatures under test condi-
tions.
Operating mode
User or Controller-demanded function of the heat generator (e.g. room heating, hot water heating,
stand-by, etc.).
Parameter
A value that influences the execution of programs or processes or defines specific states.
Refrigerant
A material which is used for thermal transfer in a heating system. At low temperature and low pressure,
heat is absorbed and at high temperature and a high pressure, heat is emitted.
Return flow
Part of the hydraulic circuit that directs the cooled water from the radiators in the rooms back to the
heat generator via the piping system.
SMART GRID (SG)
Intelligent energy utilisation for economical heating. Using a special electricity meter it is possible to
receive a "SMART GRID signal" from the energy supply company.
Depending on the signal from the energy supply company, the heat pump is turned off, put into
standard mode or run in high-temperature mode.
Switching time programme
Programme for setting dates and times on the Controller to define regular heating, cooling, economy
and hot water cycles.
Water shortage/ overheating
protection
Safety device which switches off the heat generator automatically if there is a water shortage, in order
to avoid over-heating.
Weather-controlled flow tem-
perature regulation
The inflow target temperature for temperature control in the heating unit is calculated from the
measured value for the external temperature and a defined heating curve.
9 x Notes
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
59
9
Notes
9.1
User-specific settings
9.1.1
Switching timer program
The factory settings of the timer programs are stated in
chapter 3.4.7, tab. 3-9.
●
Enter your switching time settings in the table below.
Switching cycle 1
Switching cycle 2
Switching cycle 3
Temperature
setting
[T-Room 1 Setpoint]: ____ °C
[T-Room 2 Setpoint]: ____ °C
[T-Room 3 Setpoint]: ____ °C
Time period
On
Off
On
Off
On
Off
HC Program 1
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
HC Program 2
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Tab. 9-1
Individual settings in the heating timer programmes
Switching cycle 1
Switching cycle 2
Switching cycle 3
Temperature
setting
[T-DHW Setpoint 1]: ____ °C
[T-DHW Setpoint 2]: ____ °C
[T-DHW Setpoint 3]: ____ °C
Time period
On
Off
On
Off
On
Off
DHW Program 1
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
DHW Program 2
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Tab. 9-2
Individual settings in the hot water timer programmes
Switching cycle 1
Switching cycle 2
Switching cycle 3
Time period
On
Off
On
Off
On
Off
Circulation Time
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Tab. 9-3
Individual settings of the circulation-switching time programme
Operating instructions
60
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
9 x Notes
9.1.2
Parameter
●
Enter your parameter changes in the table below.
Rotary switch
setting
Parameter levels /
Parameter
Old value
New value
Date
Comments
Tab. 9-4
Individual parameter modifications
9.1.3
IDs in the RoCon CAN bus system
RoCon-appliance
ID
Comments
Tab. 9-5
IDs in the RoCon CAN bus system
9 x Notes
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
61
9.2
Other items
10 x List of keywords
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
63
10 List of keywords
A
Additional heat generator . . . . . . . . 25
Address switch . . . . . . . . . . . . .35, 36
Anti-legionella system . . . . . . . .27, 58
B
Backup demand . . . . . . . . . . . . . . . 58
Backup heater . . . . . . . . . . . . . . . . . 11
Explanation . . . . . . . . . . . . . . . . . . 58
Parameters . . . . . . . . . . . 42, 45, 48
Basic functions
Automatic defrosting . . . . . . . . . . . 11
Displaying system information . . . 11
Setting the language,
date and time . . . . . . . . . . . . . . . . 18
Switching the system on and off . . 13
Water pressure display . . . . . . . . . 13
Bivalency function . . . . . . . . . . . . . . 42
Bus Scan . . . . . . . . . . . . . . . . .18, 50
Button block . . . . . . . . . . . . . . . . . . 11
C
Caretaker function . . . . . . . . . . . . . 36
Circulation pump . . . . . . . . . . . .16, 30
Cleaning . . . . . . . . . . . . . . . . . . . . . . 7
Cooling operation . . . . . . . . . . .14, 23
D
Data bus . . . . 32, 41, 43, 50, 52, 53
Day mode . . . . . . . . . . . . . . . . . . . . 15
Defrosting function . . . . . . . . . . . . . 11
Device ID . . . . . . . . . . 33, 35, 50, 56
Display . . . . . . . . . . . . . . . . . . . . . . . 8
Domestic hot water generation . . . . 15
Domestic hot water reheating . . . . . 15
E
Economy mode . . . . . . . . . . . . .14, 15
Emergency operation . . . . . . . . . . . 57
Energy saving mode . . . . . . . . . . . . 14
Error messages . . . . . . . . . . . . . . . 51
EVU . . . . . . . . . . . . . . . . . . . . . . . . 11
EVU function . . . . . . . . . . . . . . . . . . 11
EVU function HT/NT . . . . . . . . . . . . 12
EVU function SMART GRID . . . . . . 12
Explanation of symbols . . . . . . . . .4, 9
EXT signal . . . . . . . . . . . . . . . . . . . 12
External operating mode switching . 14
F
Factory setting . . . . . . . . . . . . . . . . 41
Faults and malfunctions
Fault codes . . . . . . . . . . . . . . . . . . 57
Frost protection function . . . . . . .9, 25
G
Glossary . . . . . . . . . . . . . . . . . . . . . 58
H
Heat curve . . . . . . . . . . . . . . . . . . . 22
Heat generator ID . . . . . . . . . . .32, 53
Heating
circuit IDs . . . 32, 33, 35, 36, 52, 53
Heating cycle . . . . . . . . . . . . . . . . . 16
Heating support function . . . . . .26, 42
HT/NT Function . . . . . . . . . . . . . . . 42
I
Inflow target temperature . . . . . . . .14
In cooling mode . . . . . . . . . . . . . . 23
In heating mode . . . . . . . . . . . . . . 22
With weather-dependent
regulation . . . . . . . . . . . . . . . . . . .24
Information messages . . . . . . . 51, 56
L
Language setting . . . . . . . . . . . . . . 18
Low tariff mains connection . . . . . . 58
M
Malfunctions . . . . . . . . . . . . . . . . . .56
Manual operation . . . . . . . . . . . . . . 20
Master-RoCon function . . . 33, 36, 41
Mixer module . . . . . . . . . . 24, 34, 36
N
Normal operation . . . . . . . . . . . . . . 19
O
Operating data overview . . . . . . . . . 12
Operating elements . . . . . . . . 6, 7, 10
Exit button . . . . . . . . . . . . . . . . . . . 10
Rotary push button . . . . . . . . . . . . 10
Rotary switch . . . . . . . . . . . . . . . . . 9
Operating modes
Automatic 1 . . . . . . . . . . . . . . . . . .14
Automatic 2 . . . . . . . . . . . . . . . . . .14
Cooling . . . . . . . . . . . . . . . . . . . . . 14
Heating . . . . . . . . . . . . . . . . . . . . .14
Reduce . . . . . . . . . . . . . . . . . . . . .14
Stand-by . . . . . . . . . . . . . . . . . . . . 13
Summer . . . . . . . . . . . . . . . . . . . . 14
P
Parameters . . . . . . . . . . . . . . . . . . . 58
Pressure monitor function . . . . . . . . 46
Protocol . . . . . . . . . . . . . . . . . . . . . . 20
R
Relay test . . . . . . . . . . . . . . . . . . . . 30
Relevant documents . . . . . . . . . . . . . 4
Remote control via Internet . . . . . . .31
Reports . . . . . . . . . . . . . . . . . . . . . . 56
RESET . . . . . . . . . . . . . . . . . . . . . .27
Room station . . . . . . . . . . . . . . . . . .35
Room thermostat . . . . . . . . . . . . . . 42
Rotary switch position . . . . . . . . . . .10
S
Safety shutdown . . . . . . . . . . . . . . . . 6
Screed programme
Function heating . . . . . . . . . . . . . .28
Heating until sufficiently
cured/ready for installation . . . . . . 29
Setting the date . . . . . . . . . . . . . . . . 18
Setting the time . . . . . . . . . . . . . . . . 18
SMART GRID . . . . . . . . . . 20, 42, 58
Software information . . . . . . . . 11, 57
Special level . . . . . . . . . . . . . . . . . .20
Switching time program . . . . . . . . . 16
Permanent programmes . . . . . . . . 16
Personal settings . . . . . . . . . . . . . 59
Setting . . . . . . . . . . . . . . . . . . . . . . 16
Temporary programmes . . . . . . . . 17
System temperatures . . . . . . . . . . .11
T
Target hot water
temperature . . . . . . . . . . . . 14, 15, 20
Target room temperature . . . . . . . .15
Technician password . . . . . . . 21, 41
Temperature setting
Day mode . . . . . . . . . . . . . . . . . . .15
Domestic hot water mode . . . . . . .15
Economy mode . . . . . . . . . . . . . . .15
Terminal address . . . . . . . . . . . . . .36
Terminal function . . . . . . . . 18, 50, 52
Terminal
ID . . . 24, 32, 33, 34, 35, 36, 43, 53
Timer programme (temporary)
Absent . . . . . . . . . . . . . . . . . . . . . .17
Holiday . . . . . . . . . . . . . . . . . . . . .17
Party . . . . . . . . . . . . . . . . . . . . . . .17
U
Use as intended . . . . . . . . . . . . . . . .5
V
Venting function . . . . . . . . . . . . . . .26
W
Water pressure . . . . . . . . . . . . . . . .13
Whisper mode . . . . . . . . . . . . . 19, 45
Z
Zone regulation . . . . . . . . . . . . . . . .24