Desoutter CVI3 Function Operation & User’s Manual
Read Online
Read the Desoutter CVI3 Function Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
Part no 6159930320
Issue no 06
Date
02/2017
Model
Part number
CVI3 Function
6159326900
CVI3 Function eSTOP
6159326930
Table of contents_02/2017
- 3 -
TABLE OF CONTENTS
1 - SAFETY INSTRUCTIONS .....................7
1.1 - General instructions .......................................... 7
1.2 - Personal safety.................................................. 7
1.3 - Tool use hazards ............................................... 7
1.4 - Tool care and service ........................................ 7
2 - GETTING STARTED ..............................7
2.1 - Front panel ........................................................ 7
2.2 - LEDs color code ................................................ 7
2.3 - Bottom panel ..................................................... 8
2.4 - Installation ......................................................... 8
2.5 - Changing the controller language ..................... 8
3 - TREE VIEW ............................................9
4 - CONTROLLER SETTINGS .................10
4.1 - Using icons and keyboards ............................. 10
4.2 - Secondary controller in a workgroup ............... 10
4.3 - Network ........................................................... 10
4.4 - Ping ..................................................................11
4.5 - Fieldbus ............................................................11
4.6 - Customized protocol.........................................11
4.7 - Date & time.......................................................11
4.8 - Beep ................................................................ 12
4.9 - Zoom in Control mode ..................................... 12
4.10 - Input/Output (reading only)............................ 12
4.11 - Access manager ............................................ 13
5 - MONITORING ......................................13
5.1 - Pset/Assembly Process selection ................... 13
5.1.1 - First selection ........................................ 13
5.1.2 - Control mode .......................................... 13
5.2 - Last result ........................................................ 13
5.3 - Report details .................................................. 14
5.4 - Monitoring symbols ......................................... 14
5.5 - Trend symbols ................................................. 14
6 - RESULTS .............................................15
6.1 - Display of the last result .................................. 15
6.2 - Display of other results .................................... 15
6.3 - Display of run reverse results .......................... 15
7 - MAINTENANCE ...................................16
7.1 - Controller ......................................................... 16
7.1.1 - USB key - Firmware upgrade ................. 16
7.1.2 - USB key - Save logs .............................. 16
7.1.3 - USB key - Save config ........................... 16
7.1.4 - USB key - Save results .......................... 16
7.1.5 - USB key - Advanced diagnostic ............. 16
7.1.6 - CVILOGIX .............................................. 17
7.1.7 - Memory .................................................. 17
7.2 - ePOD............................................................... 18
7.2.1 - Backup/Restore ...................................... 18
7.2.2 - Eject ....................................................... 18
7.2.3 - Repair ..................................................... 18
7.2.4 - Erase results .......................................... 18
7.3 - User information .............................................. 19
7.4 - Firmware version ............................................. 19
Table of contents_02/2017
- 4 -
8 - APPENDIX - I/O AND EVENTS ...........20
8.1 - Logical outputs ................................................ 20
8.2 - Logical inputs .................................................. 25
9 - APPENDIX - USER INFO CODES ......29
10 - APPENDIX - CONNECTIONS ...........37
10.1 - Tool connector ............................................... 37
10.2 - RS232 - SubD 9pt ......................................... 37
10.3 - Digital inputs (0 – 24V) .................................. 38
10.4 - Digital outputs (0 – 24V) ................................ 38
10.5 - Tightening flow chart and timing chart ........... 39
10.6 - Synchronizing single-channel controllers ...... 41
10.7 - Synchronizing TWINCVI3 controllers ............ 41
10.8 - eBUS (for accessories) ................................. 42
10.9 - Workgroup ..................................................... 42
11 - APPENDIX - EPOD ............................43
- 6 -
Original instructions.
© Copyright 2017, Ets Georges Renault 44818 St
Herblain, FR
All rights reserved. Any unauthorized use or copying of
the contents or part thereof is prohibited. This applies in
particular to trademarks, model denominations, part numbers
and drawings. Use only authorized parts. Any damage or
malfunction caused by the use of unauthorised parts is not
covered by Warranty or Product Liability.
1 - SAFETY INSTRUCTIONS
1.1 - General instructions
To reduce risk of injury, everyone using,
installing, repairing, maintaining, changing
accessories on, or working near this tool must
read and understand the safety instructions
before performing any such task.
Failure to follow all instructions listed below
may result in electric shock, fire and / or serious
personal injury.
• Refer to the following booklets:
- General safety instructions
- Quick-start user manual
at http://resource-center.desouttertools.com.
SAVE THESE INSTRUCTIONS CAREFULLY.
1.2 - Personal safety
WARNING: This power tool must be earthed.
If the power tool is not earthed, the system will
disable the power stage and the tool will not start.
The error message "Bad tool ground" will be
displayed.
1.3 - Tool use hazards
The selection of the tool takes account of the operating
conditions as stated by the user.
When selected, they must not exceed the operating limits as
specified by the manufacturer.
Any excessive internal temperature of the tool electric motor
is detected and stops the tool. The motor can start again only
after the temperature has decreased.
Motor temperature limits are different for handheld tools and
for fixed tools:
- 60°C for handheld tools.
- 100°C for fixed tools.
1.4 - Tool care and service
Only experienced and qualified personnel (authorized
electricians) are entitled to open and have access to the
inside of the controller.
• If in doubt, return the tool to a Desoutter-authorized service
centre. Contact your Desoutter representative for support.
• Disconnect from power supply and wait 10 minutes before
starting service operations.
Failure to wait 10 minutes may result in electric
shock from not yet unloaded capacitors.
2 - GETTING STARTED
2.1 - Front panel
1
2
3
4
5
Legend
1
Report LEDs
2
122 x 32 full graphic display
3
Keypad
4
On / Off switch
5
Dedicated PC software port + USB port
2.2 - LEDs color code
LED
color
Designation
Action
Green
Accept report
-
Yellow
Incomplete rundown
Tighten again
Orange
Reject report
Loosen and tighten again
Red
Above High Angle
Remove and replace
fastener.
- 7 -
2.3 - Bottom panel
2
8
9
10
12
3
5
7
11
1
4
6
Legend
1
Ethernet port dedicated only to PC software
2
USB port for data transfer / firmware updating / access
control management
3
ePOD port for controller backup, memory extension,
customer features activation, workgroup configuration.
4
2 USB ports to connect barcode readers
5
Auto-sensing input voltage mains connector
6
2x8 I/O connector dedicated to customer use + 2 quick
stops.
7
Ground Fault Interruptor: earth fault and overcurrent
protection
8
Fieldbus port for plug & play Fieldbus modules
9
eBUS to daisy-chain up to 15 accessories (e.g. socket
tray)
10
RS232 port (2 serial ports) to connect:
Barcode reader / Delta measuring unit
11
8-pin tool connector
12
4 Ethernet ports for 1 or 2 networks:
1 network
• Plug the Ethernet cable
into any port.
2 networks
Ethernet network 1
Ethernet network 2
• Refer to "Appendix - CVI3 connections" to get
more information.
• For more information about installing Fieldbus
modules, refer to the " Quick start user manual"
part no. 6159931440 at http://resource-center.
desouttertools.com.
2.4 - Installation
• To install and power the controller, follow the instructions
listed in the Quick-start user manual supplied in the
controller box.
The controller should be installed in such a way
that it should be easily switched off.
When the controller is powered on, the Desoutter logo is
displayed and the LEDs are blinking.
• Wait for a few seconds while the firmware is being
initialized.
The monitoring screen is displayed:
2.5 - Changing the controller language
• Keep pressing this key up to
the following screen.
• Keep pressing this key up to
the following screen.
• Press any key. The name of
the language is blinking.
• Select the language.
• Validate
- 8 -
3 - TREE VIEW
The controller is waiting for the
selection of a Pset or Assembly
Process.
The tool is locked.
- to display the last result.
- to select the next Assembly
Process and/or Pset.
- to display the results.
- to display the user info codes.
- to save the results, the
configurations and the logs
on a USB key.
- to upgrade the firmware.
- to backup/restore/erase the
results from the ePOD..
- to eject the ePOD
- to repair the ePOD
- to erase the results, the user
info codes and the Pset/
AP configuration from the
controller.
- to launch a CVILOGIX
program.
- to set up the network.
- to customize the controller.
- to set up the role of the
controller in the workgroup.
- to display the status of the
Input/Output.
- to enable/disable the data
protection of the controller.
- to display the controller
firmware version.
- 9 -
4 - CONTROLLER SETTINGS
• Use CVI CONFIG software to create Psets and
Assembly Processes.
4.1 - Using icons and keyboards
to quit without changing
to validate
to navigate
to change
Pset symbol
Assembly Process symbol
?
• Select a Pset or an Assembly Process.
The tool is locked.
• Select a Pset or an Assembly Process
The screen is
locked.
• Refer to chapter "Access
manager".
The screen is
unlocked.
4.2 - Secondary controller in a workgroup
A workgroup is a system designed to drive from 2 to 14
fixtured tools with cable connection.
The controller can be selected as one of the secondary
controllers of the workgroup.
The controller is stand-alone.
• Select the value to change
The controller is selected
as one of the secondary
controllers of the workgroup.
• Validate
• Select the tool ID (position of
the tool in the workgroup).
The monitoring screen will be as follows:
When changing from "Secondary" to "None", the
network configuration previously set for the stand-
alone controller will be restored.
• Refer to "Appendix - CVI3 connections" to get
more information.
4.3 - Network
1 network
• Plug the Ethernet cable into
any port.
2 networks
Ethernet network 1
Ethernet network 2
• Enter the controller IP address, Subnet mask and Gateway
parameters.
• Select the
value to
change
• Change the
value
• Validate
- 10 -
4.4 - Ping
This function is used to check the network connection with
any device connected on the network.
• Select the IP address to ping.
There are 4 attempts.
• Select the
value to
change
• Change the
value
• Validate
4.5 - Fieldbus
• For more information about how to setup Fieldbus,
refer to the CVI CONFIG user manual at http://
resource-center.desouttertools.com.
4.6 - Customized protocol
• Plug the "ePOD customer" into the bottom panel of the
controller.
Depending on the protocol used, the following icons are
displayed in the monitoring screen.
XML protocol
PFCS protocol
IPM protocol
The controller is connected to
the server.
The controller is not
connected to the server.
"Customized protocol status" events are available.
• Refer to "Appendix - CVI3 I/O and events" to get
more information.
• For further information, contact your Desoutter
representative for support.
4.7 - Date & time
This function is used to synchronize the controller date and
time to ensure that the tightening results are stored with the
correct date and time.
• Change the current date if
necessary.
• Change the current time if
necessary.
• Use CVI CONFIG software to select the date
format and the synchronization source.
- 11 -
4.8 - Beep
If enabled, this function enables a "Beep" sound each time a
button is pressed.
The beep is disabled.
The beep is enabled.
4.9 - Zoom in Control mode
The "Zoom" mode can be used to display:
- the torque value
- the angle value
- the report
When the "Zoom" mode is activated, the last result and the
selected Pset are alternatively displayed full screen.
If any key is pressed, the zoom is removed and the default
configuration is displayed.
• Validate your
selection.
4.10 - Input/Output (reading only)
This part shows the status of the physical I/O of the controller.
6
6
OFF
ON
• Refer to "Appendix - CVI3 I/O and events" to get
more information.
• Refer to "Appendix - CVI3 connections" to get
more information.
- 12 -
4.11 - Access manager
It is recommended to protect the controller parameters
against hazardous changes.
When the controller is delivered, the access manager is not
activated and any modification can be done.
To activate the access manager on the controller,
you need to have a USB stick with the right profile
(configured with the Desoutter CVIKEY software).
• If not, contact your CVIKEY manager for support.
• Connect your USB stick to the front panel of the controller.
The padlock will open to let you have access to the menu.
The padlock is not locked
anymore.
By default, the protection of the
data is not activated.
• Select to activate or not the
protection of the data.
• Validate your selection.
• Remove the USB key from the controller.
The padlock is locked.
The controller protection is
activated.
5 - MONITORING
5.1 - Pset/Assembly Process selection
5.1.1 - First selection
Upon delivery, the controller is
waiting for the selection of a
Pset or Assembly Process.
The tool is locked.
• Select the value to change.
The question mark is blinking.
• Change the value
• Validate
5.1.2 - Control mode
• Select the
value to
change
• Change the
value
• Validate
5.2 - Last result
The report status is displayed:
OK or NOK.
The torque and angle values
are displayed.
The trend is displayed
The report details are available.
• Press this key to
display the report
details.
- 13 -
5.3 - Report details
- Result number
- Report status
- Date
- Time
- Pset number
- Step number
- Stop source
to display the
message when
too long.
The last step is done.
The Pset has stopped before the last step.
OK
The report is successful.
NOK
The operation has failed.
5.4 - Monitoring symbols
Monitorings OK
Torque
Time
Overall time
Current
Torque rate
Angle
Overall angle
Second part angle 1
Second part angle 2
Rundown angle
5.5 - Trend symbols
The torque is below the minimum torque.
The torque is above the maximum torque.
The angle is below the minimum angle.
The angle is above the maximum angle.
The torque is in the tolerance of the target torque.
The angle is in the tolerance of the target angle.
The torque is above the assembly torque limit.
The angle is above the assembly angle limit.
- 14 -
6 - RESULTS
6.1 - Display of the last result
6.2 - Display of other results
• Press one of these keys to select another
result.
• Keep pressing the key to display the
results by 10.
6.3 - Display of run reverse results
This icon indicates a run reverse operation.
- 15 -
7 - MAINTENANCE
7.1 - Controller
7.1.1 - USB key - Firmware upgrade
• Plug the USB key into the front panel port.
• Check you have 1 ".cvi3" image and
1 ".cvi3.md5" file only on your USB key.
The controller beeps during 2 seconds and starts the process.
• Do not switch off the controller.
• Wait for the automatic reboot. The update lasts a few
minutes.
When the upgrade is successful, the green LED is on.
7.1.2 - USB key - Save logs
• Plug any USB key into the front panel port.
7.1.3 - USB key - Save config
• Plug any USB key into the front panel port.
7.1.4 - USB key - Save results
• Plug any USB key into the front panel port.
7.1.5 - USB key - Advanced diagnostic
• Plug any USB key into the front panel port.
• Select how often the logs are saved on the USB key.
Period
1/2/6/12/24 hour(s)
The period is blinking.
• Change the period.
• Do not unplug the USB key from the front panel.
- 16 -
7.1.6 - CVILOGIX
Pre-requisite:
- ePOD including the CVILOGIX function
- USB key including your own CVILOGIX program.
• Plug in the ePOD into the bottom panel.
• Plug in the USB key into the front panel.
The CVILOGIX program is
running.
In the control mode, the CVILOGIX logo is activated and
displayed on the top left of the monitoring screen.
The program is running.
The program is stopped.
Other functions:
to save the program on any
USB stick connected to the
controller front panel.
Mandatory
• Use the "Eject" command to unplug the ePOD
from the controller.
• Contact your local Desoutter representative for
more information.
7.1.7 - Memory
• Select which type of information to erase from the controller
memory:
- results
- user information
- Psets and Assembly Processes configurations
For example:
- 17 -
7.2 - ePOD
• Plug in the ePOD into the controller.
• For more information about installing the
ePOD, refer to the installation manual" part
no. 6159931050 at http://resource-center.
desouttertools.com.
7.2.1 - Backup/Restore
• Select first the backup mode: manual or automatic.
The ePOD is a snapshot of the
controller.
Each modification is saved in
real-time in the ePOD. The
ePOD acts as the controller
mirror.
In both modes:
• Select "Backup" to start the
process.
• Select "Restore" to transfer
the data from the ePOD to
the controller.
7.2.2 - Eject
Mandatory
• Use the "Eject" command to unplug the ePOD
from the controller.
• Unplug the ePOD.
7.2.3 - Repair
• Use this function to start a recovery attempt of the data and
results from the ePOD.
7.2.4 - Erase results
• Use this function to erase all results stored in the ePOD.
- 18 -
7.3 - User information
to display the description.
to display the next code.
This icon indicates that the user information can be
acknowledged.
• Press this key to clear the screen.
• Refer to "Appendix - User info codes" to get more
information.
7.4 - Firmware version
This information is useful to exchange information with
Desoutter Servicing.
• Refer to chapter "7.1.1 - USB key - Firmware
upgrade" to update the controller.
Appendix - I/O and events_02/2017
- 19 -
APPENDIX - I/O AND EVENTS
1 - LOGICAL OUTPUTS
Name
Description
Raising condition
Falling condition
General status
Ready
The system is free of any internal issue that could prevent it
from being fully operative.
Communication between controller and tool is OK.
No error in controller
nor in tool
- Quick stop activated
- Error coming from
the system
Identifier OK
Identifier received (e.g. barcode) matches masks (stays during
0.5 s at active level).
Identifier received and
identified
0.5 s after rising
Identifier NOK
Identifier received (e.g. barcode) does not match masks (stays
during 0.5 s at active level).
Identifier received but
not identified
0.5 s after rising
User info
present
User info (Info, Warning or Error) is present.
User info present on
screen
No user info on
screen
Keep alive ack
This output is the copy of the "Keep alive" input.
It can be used by the PLC to check the controller is still
running.
When "Keep alive"
input raises.
When "Keep alive"
input falls.
Fieldbus fault
No Fieldbus.
The "Fieldbus fault" is on as long as the Fieldbus
communication is not established.
It switches off automatically when the communication works
again.
Communication lost
and/or keep alive
missing.
Fieldbus
communication
established and keep
alive present
Reporting Alarm
When working with ToolsNet or CVINet: FIFO Threshold Alarm
reached.
Results are stored in the controller memory and are erased
when sent to ToolsNet or CVINet. This way the controller
memory will never be full. A full controller memory induces
result losses and traceability error. To detect communication
issues with ToolsNet or CVINet, the software measures the
fill in rate (%) of the memory. When the rate overpasses
the target threshold, the Reporting alarm will switch on;
maintenance operators are then able to solve the issue before
loosing results.
FIFO Threshold Alarm
reached
FIFO under threshold
alarm.
Open Protocol
activated
Open Protocol is activated in configuration
Protocol is enabled
Protocol is disabled
Open Protocol
connected
Open Protocol is connected to the Tightening Unit
At least 1 peer
connected
No peer is connected
Time synchro
done
Time synchronisation completed successfully using Fieldbus
data (Q_SYN in VWXML)
-
-
Emergency stop
Emergency stop is activated
Emergency stop
activated
Emergency stop
deactivated
TU running
This indicates that the fastening operation has actually started:
at least one involved tool is running. The signal switches off as
soon as the fastening operation is finished (all reports sent).
Pset is started.
The fastening
operation is finished
(all reports sent)
Tool status
Tool ready
The tool is ready:
- communication between controller and tool is ok
- a valid Pset has to be selected
- the tightening strategy must cope with the tool"
Tool connected AND
valid Pset.
Tool disconnection,
Pset selection.
Tool not locked
forward
There is no tool lock in forward direction.
Tool unlocked in
forward direction
New lock in forward
direction
Tool not locked
reverse
There is no tool lock in reverse direction.
Tool unlocked in
reverse direction
New lock in reverse
direction
Tool running
The tool is running (CW or CCW, tightening or loosening).
Tool starts to run.
Turns off when the
tool stops.
Tool direction
Indicates if the tool is in tightening mode.
Active: tightening mode
Inactive: run reverse mode
Note: independent if tool is running or not.
Entering tightening
mode.
Entering run reverse
mode.
Tool tightening
Tool is running in tightening mode.
Pset threshold is not taken into account.
Tool start in tightening
mode.
Tool stops.
Tool middle
course trigger
Reflects the raw state of tool middle course start trigger,
independently from Tightening Unit state.
Middle course of main
trigger is reached
Main trigger is
completely released.
Appendix - I/O and events_02/2017
- 20 -
Name
Description
Raising condition
Falling condition
Tool main start
trigger
Reflects the raw state of tool main course start trigger,
independently from the Tightening Unit state.
Trigger is pushed.
Trigger is released
Tool push start
or front start
trigger
Reflects the raw state of tool push start or front start trigger,
independently from the Tightening Unit state.
Trigger is pushed.
Trigger is released
Manual reverse
in progress
The operator has selected the reverse direction on the tool and
is running the tool.
Manual runreverse
selected and trigger
pushed.
Stays on as long
as the operator is
running the tool
Fastener
loosened
There is a fixed minimum torque value to declare that the
fastener was "loosened".
Run reverse
Result generation.
New start (tool trigger
or external start)
Tube nut open
Indicates that the tube nut is open.
The tool can be removed from the assembly.
-
Tool running
Tool
maintenance
alarm
Reflects the different tool maintenance alarm state with or
condition.
Tool maintenance
alarm 1 or 2 is active.
No tool maintenance
alarm is active.
Invalid spindle
settings
Tool characteristics does not match Pset parameters (e.g.
negative jog times or contradictions, torque over the maximum
tool torque range, speed over the maximum tool speed,
maximum tool torque range, etc…)
Pset selection or tool
connection.
Tool disconnection or
new Pset selected.
Span failure
When starting a tightening, before running the tool, the
controller checks the torque span.
"Span failure" indicates that the span drifts by ±3% or more,
causing a tool lockout.
This fault can be due to the torque transducer or the tool
electronics.
The only solution is to replace the tool.
Span failure detection.
Disconnecting tool
or new check without
fault.
Offset failure
Indicates the offset (0 point) drifts by 50 % of full scale or
more.
This error exists when, at the beginning of the Pset, the torque
transducer is seen to have 50 % or more of full-scale torque
prior to even starting the motor. With an "Offset failure", the
controller cannot adequately compensate for this transducer
error and, therefore, will not allow a tightening operation to
occur.
The only solution is to replace the tool.
Offset failures can come from a severely damaged torque
transducer, a bad field cable or a bad controller.
Offset failure detection
Disconnecting tool
or new check without
fault.
Motor over
temperature
Indicates that the temperature of the tool motor windings has
exceeded the temperature threshold.
An error message remains.
Temperature
threshold:
- 100°C for fixed tools
- 60°C for portable
tools
The signal turns
off as soon as the
temperature returns
below the threshold
(minus hysteresis =
10°C).
Angle
measurement
fault
Drive detected angle sensor fault.
It can be an angle sensor fault, a tool electronic fault or a
combination of both.
The communication is tested permanently.
As soon as the fault disappears, the signal turns off.
Angle fault detection.
Disconnecting tool
Angle
measurement
fault
Drive detected angle sensor fault.
It can be an angle sensor fault, a tool electronic fault or a
combination of both.
The communication is tested permanently.
As soon as the fault disappears, the signal turns off.
Angle fault detection.
Disconnecting tool
No tool
connected
Indicates that the controller is not detecting the tool.
Controllers are designed to work with a range of fastening
tools. The tools have an Intelligent Tool Interface (ITI) board
which is continuously sending status information to the
controller. If the controller requests status information from the
tool and gets no response, the controller software turns on the
"No tool connected" output.
This output resets immediately upon successful
communication with a tool.
No tool connected or
tool not recognized
Tool connected and
recognized.
Redundancy
error
Redundancy error in case of operational control transducer
and faulty monitoring transducer.
Result generation
Use of "reset of
redundancy error"
input, change of tool
free of this error
Appendix - I/O and events_02/2017
- 21 -
Name
Description
Raising condition
Falling condition
Pset status
Pset selected
bits (0..7)
Echoes the binary "Pset select bit 0 to 7" input if the
corresponding Pset exists, echoes 0 if the Pset does not exist
or there is no Pset selected.
New Pset selected
New Pset selected
Tightening
running (old
cycle declared)
This indicates that the fastening operation has actually started:
the tool is running and the torque is over the Pset start torque
threshold.
The signal switches off as soon as the fastening operation is
finished (all reports sent).
Torque reach the cycle
start threshold.
The fastening
operation is finished
(all reports sent)
Tightening
finished
Indicates that a Pset report is available.
Result generation.
New start (tool trigger
or external start) or
reset input
Tightening OK
Indicates that the fastening operation (for a specific Tightening
Unit) ends correctly and that all controlled and monitored
tightening parameters are within tolerances.
Result generation.
New start (tool trigger
or external start) or
reset input
Tightening NOK
Indicates that the fastening operation (for a specific Tightening
Unit) has failed.
Result generation.
New start (tool trigger
or external start) or
reset input
Spindle OK
Indicates that the fastening operation (for a specific tool) ends
correctly and that all controlled and monitored tightening
parameters are within tolerances.
Result generation.
New start (tool trigger
or external start) or
reset input
Spindle NOK
Indicates that the fastening operation (for a specific tool has
failed.
Result generation.
New start (tool trigger
or external start) or
reset input
Angle low
Indicates a low angle reject.
The angle must meet or exceed this value for a correct Pset.
When the angle stays below this value, it becomes a "Low
angle reject" and this output is turned on.
Stays on until a new fastening operation starts.
Result generation.
New start (tool trigger
or external start) or
reset input
Angle OK
Indicates a correct angle.
The angle is inside the limits declared in the step.
Result generation.
New start (tool trigger
or external start) or
reset input
Angle high
Indicates a high angle reject.
The angle must stay below this value to be a correct Pset.
When the angle meets or exceeds this value, it becomes a
"High angle reject". The tool will stop when this limit is reached
and this output is turned on.
Stays on until a new fastening operation starts.
Result generation.
New start (tool trigger
or external start) or
reset input
Torque low
Indicates the peak torque low reject.
If the torque stays below the "Peak torque low limit" and
results in a “Reject” Pset. This can happen when a Pset is
prematurely finished, a thread strips out or when the Pset is
automatically finished due to other error conditions, such as
a High angle fault or when a Pset Time Monitor expires and
causes the Pset to be terminated.
Stays on until a new fastening operation starts.
Result generation.
New start (tool trigger
or external start) or
reset input
Torque OK
Indicates a correct torque.
Torque is in inside the limits declared in the step.
Result generation.
New start (tool trigger
or external start) or
reset input
Torque high
Indicates the peak torque high reject.
When the torque meets or exceeds this value, this output is
turned on and the results is NOK. If a Peak Torque High error
persists, it may be advisable to slow down the tool speed
or replace the tool with one of lesser capacity. A second
variable that can cause Peak Torque High errors is a badly
chattering joint. Chatter is the squawking noise you hear
on some fasteners at the end of the fastening operation.
Chatter is induced by slip-stick and actually causes the
fastener to momentarily stop rotating, then crack loose and
re-start turning. This condition can cause a Peak Torque High
condition. A potential solution for this is to view Psets, General
Tab, and set the frequency response slide bar to Better
Noise Immunity, Chattering Joint). This causes the software
to average many torque readings together to minimize the
possibility of using a single high frequency torque value that
could trigger a peak torque high fault.
Stays on as long as a new fastening operation starts.
Result generation.
New start (tool trigger
or external start) or
reset input
Appendix - I/O and events_02/2017
- 22 -
Name
Description
Raising condition
Falling condition
Yellow report
on tightening
controller
This output reflects the state of the controller yellow light.
Controller yellow light
is on
New fastening
operation starts
Green report
on tightening
controller
This output reflects the state of the controller green light.
Controller green light
is on
New fastening
operation starts
Red report
on tightening
controller
This output reflects the state of the controller red light.
Controller red light is
on
New fastening
operation starts
Lock on reject
Indicates that a tool is locked out because of an incorrect
tightening operation.
The controller will not continue to run the tool depending on
“lock on reject option:
- until the "Error Acknowledge" input is activated.
- until a run reverse operation
- until a loosening operation"
Tightening finished
with bad result and
option “Lock on reject”
activated.
Input “Error
acknowledge”
activated or
runreverse operation
or loosening
operation
Remove
fastener
Indicates that the fastening operation resulted in a torque that
exceeded the “Remove Fastener” setpoint.
When correctly set, this means that the torque for any reason
becomes very high. There is a risk that the fastening operation
is not reliable: disassemble the joint and check parts.
Result generation.
New start (tool trigger
or external start) or
reset input
Tightening
finished without
timeout
Indicates that a Pset report is available and the source stop is
not overall timeout.
Result generation.
New start (tool trigger
or external start) or
reset input
Overall time
reached
Max overall time has been reached during tightening
Result generation.
New start (tool trigger
or external start) or
reset input
Synchro out
Synchro output: set to 1 when running step starts, reset to 0
when a synchro step is reached.
Start of running step.
Synchro step
reached
Invalid
parameter set
selected
Indicates the Pset is disabled (has not been set).
For example, if 3 Psets are used, Psets 1, 2 and 3 are
enabled. If, however, any Pset other than 1, 2 or 3 is selected,
the Pset is invalid and this output is turned on.
It is possible for an Assembly Process to select invalid Psets.
Pset unselection
Pset selection
Assembly Process status
Assembly
Process
selected bits
(0..7)
Indicates the Assembly Operation per Tightening Unit currently
selected (Bit 0..7)
New AP selected.
AP aborted
New AP selected.
AP aborted
Assembly
Process running
Indicates the assembly operation is being processed.
The signal is on as long as the assembly operation is running.
The signal falls down when the assembly operation is finished.
Assembly Process
start.
Assembly Process
finished or aborted.
Assembly
Process finished
Indicates when an assembly operation is completed.
Assembly Process
finished.
A new Assembly
Process start or reset
input
Assembly
Process OK
Indicates when an assembly operation is completed with no
rejects.
The signal stays on as long as a new Assembly Process starts.
Assembly Process
finished and OK.
A new Assembly
Process start or reset
input
Assembly
Process NOK
Indicates when an Assembly Process reject occurs.
Stays on as long as a new Assembly Process starts.
Assembly Process
finished and NOK or
aborted.
A new Assembly
Process start or reset
input
Assembly
Process aborted
When an Assembly Process has been aborted, "Assembly
Process aborted" is activated.
Stays on as long as a new Assembly Process starts.
Assembly Process
aborted.
A new Assembly
Process start or reset
input
Current batch
count bit (0..6)
Bit indicator of current batch count
Batch count increment
when batch is
finished, new start
(tool trigger or
external start) or
reset input or new AP
selection
Remaining batch
count bit (0-6)
Bit indicator of the number of remaining bolts in the batch
Batch count increment
When batch is
finished, new start
(tool trigger or
external start) or
reset input or new AP
selection
Appendix - I/O and events_02/2017
- 23 -
Name
Description
Raising condition
Falling condition
Batch running
A batch process is underway.
The output is set to 1 before the first tightening operation.
A batch operation is
enabled
Batch is finished or
reset input
Batch finished
Indicates when the batch count equals the batch size and the
batch is declared completed.
It is used together with "Batch OK" to indicate the status of a
batch.
Batch is finished.
New start (tool trigger
or external start) or
reset input
Batch OK
Indicates the status of the batch together with the "Batch
finished" output (managed by Assembly Process).
Batch is finished and
OK.
New start (tool trigger
or external start) or
reset input
Batch NOK
Such as when the batch gets aborted…or in the case rejects
are included as part of the batch count (managed by Assembly
Process).
Batch is finished and
NOK.
A new AP has been
selected.
New start (tool trigger
or external start) or
reset input
Max retries
reached
Indicates when max number of retries is reached.
Max number of retries
is reached.
Max number of
retries is reset.
External outputs AP
External Out
AP bit
Outputs that can be set or reset within an Assembly Process
Depending of AP
behavior
Depending of AP
behavior
External outputs PLC
External Out
PLC bit (0..9)
Indicates this output is controlled by a PLC via Fieldbus (like a
remote I/O).
On PLC side, it is an output.
Depending on PLC
behavior
Depending on PLC
behavior
External outputs OP
External Out OP
bit (0..9)
Outputs dedicated to Open Protocol.
Depending on OP
behavior
Depending on OP
behavior
Socket tray
Socket
selectable (0..4)
24 V socket trays (BSD).
Informs which socket can be taken by the operator.
A new socket has to
be taken by the user.
No socket to be taken
by the user.
Customized protocol Status
Customer
protocol
activated
A customer protocol has been activated in configuration
Protocol is enabled
Protocol is disabled
Customer
protocol
connected
The activated customer protocol is connected
Protocol is connected
Protocol is
disconnected
Customer
protocol
reporting alarm
The activated customer protocol has declared an alarm about
result reporting of this Tightening Unit.
Alarm is raised
Alarm is cleared
Q_SAS
ACK start tightening job
-
-
RDY
Controller ready
-
-
Q_LSN
Reverse disabled
-
-
WGZ
Tool disabled
-
-
Q_EDZ
Result and reports reset
-
-
Q_XMS
XML data transfer completed
-
-
EIO
Result OK
-
-
ENO
Result NOK
-
-
FSCIO
Group status OK
-
-
FSCNIO
Group status NOK
-
-
CVILOGIX
External Out
CVILogix bit
(0..100)
Indicates that this output can be used by an internal CVILOGIX
application.
-
-
Miscellaneous
ON
On state, used to set level "1" to physical outputs.
At controller startup.
Never falls
OFF
Off state, used to set level "0" to physical outputs.
At controller startup.
Never falls
Appendix - I/O and events_02/2017
- 24 -
2 - LOGICAL INPUTS
Name
Description
Status
General commands
Start stop Tightening
on state
Initiates a fastening cycle if:
- the "Spindle validation forward" is active and required by the Tightening Unit,
- a Pset is selected.
A rising edge must be detected to initiate a tightening, that is the change in the state of the
tool from off to on as the trigger is released, then pressed again must be detected. For the
tightening to proceed, this input must remain active. If this input becomes inactive at any
time during the tightening, the tightening will be aborted and the tool will stop running.
At the end of tightening, a tightening can began only if signal falls and then rise.
After power-up, even if this signal is active, an edge is necessary to start tightening."
State
Toggle start stop
tightening on edge
This input is enabled for fixed tools only (tools without trigger).
Initiates or ends a fastening cycle.
A cycle can be initiated only if:
- the "Spindle validation forward" is active and required by the Tightening Unit
- the Pset is selected
If no tightening is currently executed, a rising edge will initiate a tightening.
A falling edge has no effect on the tightening to proceed.
If a tightening is in execution, a rising edge will stop it.
Rising edge
Reverse direction
When activated, the tool green & red lights are flashing to indicate that the Tightening Unit
reverse direction is selected.
This signal status is not controlled during a tightening but only when tool is not running.
State
Error acknowledge
Enables the "Reject lockout" function. When locked out, the tool cannot run until this input
is reset.
Rising edge
Reset
When input reset raises (and there is no cycle running):
- defaults are acknowledged
- batch counter of current Assembly Process is reset
- reports lights on controller and tool are set off
- result on display is erased but the last 5 result values on Vision display stay readable
- in Pset mode, Pset selected remains unchanged. In AP mode, AP is aborted.
- ready output stay on
- echo identifier is reset
When input reset raises (and there is cycle running):
- tightening is immediately stopped
- defaults are acknowledged
- batch counter of current Assembly Process is reset
- at tightening end, there is no report generated.
- at tightening end, it is impossible to start a new tight, reset input must be released first.
- in Pset mode, Pset selected remains unchanged. In AP mode, AP is aborted.
- ready output stay on
- echo identifier is reset
State
Reset only status
When the input "Reset" raises during the Pset running:
- tightening is immediately stopped
Resets only:
- Tightening OK/NOK/finished
- Tool OK/NOK
- Batch OK/NOK/Finished
The Assembly Process is not aborted.
Result values (angle, torque) are still present in Fieldbus.
LEDs on tool and controller are not affected.
State
Ack error message
Acknowledge error message displayed on HMI.
Rising edge
Force Pset mode
Forces the Tightening Unit to switch in Pset mode in order to temporary run Psets (nothing
saved).
When AP mode + input state high, then switch to Pset mode.
When Temporary Pset mode + input state low, then switch to AP mode.
Switching on the controller power with the input set will switch to Pset mode.
Other cases do nothing.
State
Ack result
Acknowledges the current result.
The tool is then unlocked and can tight again. Formerly dedicated to Fieldbus only, this
behaviour is now also available for IOs and Open Protocol.
Rising edge
Keep alive
Input used to check that the controller is still alive.
State of this input is copied to "Keep alive ack" output.
This input is also used by a PLC to inform the controller that Fieldbus communication is
working.
State
Time Synchro Trigger
Execute date & time synchronisation from Fieldbus (SYN in VWXML protocol)
Rising edge
Appendix - I/O and events_02/2017
- 25 -
Name
Description
Status
Enable access
manager
Enable/disable access manager
State
Lock display
Lock/unlock the controller display.
State
Restart Controller
Reboots the controller.
Everything must be done by the software before using this input
Rising edge
Reset identifiers
Erases all ongoing accepted identifiers fields from CVI3/tool memory in order to guarantee
a correct traceability
Rising edge
Tools commands
Tool validation
forward
Enables the tool to run the selected Pset. Note: the forward and reverse validation can be
done by setting both validations on the same input. When the validation signal falls down,
the tool stops.
State
Tool validation
reverse
Enables the tool run reverse. Note: the forward and reverse validation can be done by
setting both validations on the same input. When the validation signal falls down, the tool
stops.
State
Reset tool locks
Reset tool locks, only the none safety tool locks will be affected
Rising edge
Tool stop
Stops the tool.
Rising edge
Tool blue light ctrl
by IO
1 = Tool blue light is controlled by IO
0 = Tool blue light is managed by the controller
State
Tool blue light
If "Tool blue light ctrl by IO" is set to 1 (see upward) then:
1 = tool blue light is set to on
0 = tool blue light is set to off
State
Tool green light ctrl
by IO
1 = Tool green light is controlled by IO
0 = Tool green light is managed by the controller
State
Tool green light
If "Tool green light ctrl by IO" is set to 1 (see upward) then:
1 = tool green light is set to on
0 = tool green light is set to off
State
Tool red light ctrl by
IO
1 = Tool red light is controlled by IO
0 = Tool red light is managed by the controller
State
Tool red light
If "Tool red light ctrl by IO" is set to 1 (see upward) then:
1 = tool red light is set to on
0 = tool red light is set to off
State
Tool yellow light ctrl
by IO
1 = Tool yellow light is controlled by IO
0 = Tool yellow light is managed by the controller
State
Tool yellow light
If "Tool yellow light ctrl by IO" is set to 1 (see upward) then:
1 = tool yellow light is set to on
0 = tool yellow light is set to off
State
Tool white light ctrl
by IO
1 = Tool white light is controlled by IO
0 = Tool white light is managed by the controller
State
Tool white light
If "Tool white light ctrl by IO" is set to 1 (see upward) then:
1 = tool white light is set to on
0 = tool white light is set to off
State
Reset of redundancy
error
Resets redundancy error only.
State
Pset commands
Pset select bit (0..7)
Used to select Psets.
These inputs must be in the desired state BEFORE the activation of the cycle start input.
If the selected Pset is zero, there is no Pset selected.
State
Select previous Pset
Select lower number Pset.
Rising edge
Select next Pset
Select higher number Pset.
Rising edge
External stop abort
Pset
This input is used with proximity detectors to end immediately Pset running.
The user can choose which state or transition will stop the Pset: No, Rising, Falling,
Change, High, Low.
When a Pset is aborted with this input, the Pset result is NOK.
Rising edge
or state
External stop to next
step
This input is used with proximity detectors to end the running step.
The user can choose which state or transition will stop the Pset : No, Rising, Falling,
Change, High, Low.
The user can also choose the step result when the stop request occurs: OK, NOK,
Monitoring (Monitoring means that the result is computed depending on monitoring
requested).
Rising edge
or state
Synchro in
Step synchronisation input.
The step starts when a transition to 0 is detected.
State
External Tool inputs
bit (0..9)
Indicates that these inputs can be used by an external tool (to generate OK/NOK report for
example)
State
Appendix - I/O and events_02/2017
- 26 -
Name
Description
Status
Assembly Process commands
Assembly Process
selection bit (0-7)
Used to select an Assembly Process.
These inputs must be in the desired state BEFORE the activation of the assembly process
start input.
Rising edge
Abort assembly
process (tightening
unit)
The "Abort assembly process" input stops the Assembly Process being processed.
The Assembly Process is finished.
The Assembly Process result is memorized as "aborted" and “AP aborted” and "AP NOK"
events are set.
Rising edge
Batch-1
The "Batch-1" input allows the operator to select the previous operation of a batch
whatever the result of the next operation.
The batch counter is decremented.
The action is recorded OK or NOK according to the result and "Batch-1 event" is set.
Rising edge
Batch+1
In case you cannot complete the current operation of a batch, jump to the next one by
using the external input "Batch+1".
The action is declared as NOK and "Batch+1" event is set.
Rising edge
Restart batch
Restarts the current batch of the current Assembly Process step.
The "Restart batch" event is set.
Rising edge
Reset number of
retries
Reset the number of retries counter.
If the max counter has been reached, the tool is unlocked.
Rising edge
External inputs AP
External in AP bit
(0..9)
Inputs used in Assembly Process in start conditions or in assembly actions sense input
Rising edge
External inputs PLC
External In PLC bit
(0..9)
Indicates this input can be used by an PLC via Fieldbus (like a remote I/O).
For PLC side, it is an input.
State
External inputs OP
External In Open
Protocol 1-8
Inputs used in Open Protocol. They can be monitored from the Open Protocol client
by subscription. Theses DigIn are named "External monitored 1..8" in Open Protocol
specification.
State
Socket tray
Socket lifted bit (0..4)
Used with CVI II controllers only: 24V socket trays (BSD).
Informs which socket has been lifted.
State
Customized protocol commands
PFCS END OF
CYCLE
Input used in PFCS Chrysler to flush the result FIFO when the operator has completed the
work
Rising edge
SAS
Starts tightening job
State
RST
Resets any running tightening job
State
LSN
Disables reverse
State
TOL
Tool validation
State
STR
Tool start
State
EDZ
Resets results
State
XMS
Synchronous XML
State
XMA
XML activated
State
CVILOGIX
External In CVILogix
bit (0..100)
Indicates that this input can be used by an internal CVILOGIX application
State
Appendix - User info codes _02/2017
- 28 -
Type of
code
Code
no.
Description
Resolution procedure
Info
1
Tubenut open
1-Tubenut tool is detected as open
Info
2
Tool connected
1- The tool is connected and correctly recognized by the controller.
Info
3
No tool connected
1- Tool has been disconnected.
2- If the tool is not physically disconnected, check the tool cable.
Info
4
Span fail.
1- Span value from torque sensor is outside bounds.
2 -Try once again to start the tool with no mechanical constraints. If the
problem occurs again, contact your Desoutter representative for support
Info
5
Offset fail.
1- Offset value from torque sensor is outside bounds.
2- Try once again to start the tool with no mechanical constraints. If the
problem occurs again, contact your Desoutter representative for support.
Info
15
Tool lock on reject
1- The tool is locked forward after a NOK.
2- Unlock the tool in function of the "lock on reject option" selection i.e. by
reversing, loosening or input.
Info
16
Tool lock by OP
1- Tool has been locked by Open Protocol
2- Unlock the tool by sending an Enable tool message via Open Protocol
Info
17
Loosening prohibited
1- Loosening is prohibited
2- The loosening is disabled in the Assembly action
3- The batch count type OK + NOK is used
Info
21
Max retries reached
1- The number of retries max has been reached.
2- The tool is locked.
3- The running Assembly Process has to be aborted.
Info
22
Lock wait socket
1- The tool is locked. Put all sockets back and lift the correct socket(s)
combination.
Info
24
Loos. prohib. XML
1- Loosening is disabled by VWXML protocol
Info
25
Tight. prohib. XML
1- Tightening is prohibited by VWXML protocol
Info
26
Tool maint. alarm n1
1- Tool maintenance tightening counter has been reached
Info
27
Tool maint. alarm n2
1- Tool maintenance tightening counter has been reached
Info
38
Tool logs
1- Unexpected tool software exception
2- Log file has been generated by the tool
3-Contact your Desoutter representative for support
Info
40
Tool over speed
1- Motor speed exceeds 130% of its maximum value.
2- Check tool parameters.
3- Wrong motortune parameters. Contact your Desoutter representative
for support.
Info
42
Tool locked by GeoPos.
1- Tool has been locked by GeoPositioning
2- Unlock the tool by moving the tool in its defined area
Info
43
Tubenut maintenance
1- Tubenut settings need to be reconfigured. Please, use CVI Monitor
and refer to user's guide.
2- Contact your Desoutter representative for procedure
Info
44
GeoTracking/Positioning
learning mode ongoing
GeoTracking/Positioning learning mode
Info
46
Anormal battery current
1- Anormal battery current consumption, check your PSet settings.
2- This error can due to speed settings.
Info
50
Tool detection for pairing
No procedure
Info
51
ePOD connected
ePOD connected
Info
54
Pairing success
No procedure
Info
55
eDOCK already present on
controller
No procedure
Info
56
ePOD disconnected
ePOD disconnected
Info
57
Pairing error
No procedure
Info
58
Tool locked by GeoTrack.
1- Tool has been locked by GeoTracking
2- Unlock the tool by moving the tool in its defined are
Info
59
New tool detected
No procedure
Info
60
Tool synchro ongoing
No procedure
APPENDIX - USER INFO CODES
Info
For information only. No action is required.
Warning
The tool is locked. Tap the message to unlock the tool.
Error
The tool is locked. The issue has to be solved to unlock the tool and clear the error message.
Appendix - User info codes_02/2017
- 29 -
Type of
code
Code
no.
Description
Resolution procedure
Info
61
ExBC connection conflict
1- 2 ExBC are configured with the same network settings
2- Verify communication ports and IP addresses
Info
100
Cable id invalid param
1- Invalid tool cable parameter, check that the tool cable is Desoutter
certified
2- Contact your Desoutter representative for support
Info
101
Cable id not detected
1- Tool cable communication error, check that the tool cable is Desoutter
certified
2- Contact your Desoutter representative for support
Info
102
Cable id not certif
1- Tool cable authentification error, check that the tool cable is Desoutter
certified
2- Contact your Desoutter representative for support
Info
199
Console activated
1- The serial console is activated.
2- Warning, this console is dedicated only to debug purposes and should
not be used in production
Info
202
Fieldbus lost
1- Fieldbus connection with PLC is lost.
- no heartbeat is received from PLC
- the cable is broken or disconnected
- the PLC is off line or not powered
2- Check the Fieldbus configuration.
Info
204
Tool not validated
1- Tool locked by I/O.
2- Check the I/O settings: the "Tool validation" must be active to unlock the
tool.
Info
205
Torque settings
1-Invalid Torque setting, torque is greater than tool characteristics
2-Check Pset settings with the current tool characteristics
Info
206
Speed settings
1-Invalid speed setting, speed is greater than tool characteristics
2-Check Pset settings with the tool max. speed.
Info
207
Assembly done
1- Assembly Process is done, the tool is locked
2- Select new Assembly Process to unlock the tool
Info
208
Invalid run reverse param
1-Invalid Run reverse setting, torque or speed are greater than tool
characteristics or reverse strategy is not supported
2-Check Pset settings with the current tool characteristics
3-Reduce max number of turns
Info
209
Pset invalid parameters
1 - Software internal error.
2 - Pset is corrupted. Try to transfer it again to the controller.
3 - If the error persists contact your Desoutter representative for support.
Info
210
Invalid Pset selected
1- The Pset currently selected does not match the selectable one in the
Assembly Process.
Info
211
Invalid trigger conf
1- The tool currently connected to the CVI3 is not equipped with the trigger
required by the tool trigger configuration
2- Adjust your tool trigger configuration to the tool connected or change the
tool according to the expected trigger configuration
Info
215
Current calib. err.
1- Current calibration failed.
2- Try once again.
3- If the problem occurs again, contact your Desoutter representative for
support.
Info
224
IGBT too hot
1- Power electronics too warm.
2- Let the controller cool down.
Info
225
Err. angle
1- Tool communication error.
2- Check tool and cable connections. If the problem occurs again, contact
your Desoutter representative for support.
Info
226
Err. torque
1- Tool communication error. Check tool and cable connections.
2- Try once again, if the problem occurs again, contact your Desoutter
representative for support.
Info
234
Fieldbus mismatch
1-The Fieldbus module declared in configuration is not the same that the
one present in controller (e.g. Profibus declared but a Profinet module in
CVI3).
Info
237
Invalid data
1- The Fieldbus mapping has too many items.
Info
238
Invalid address
1- The device address affected to Fieldbus is invalid.
Info
239
Invalid com settings
1- Fieldbus communication settings are invalid
Info
241
CVINet FIFO alarm
1- The CVINet result FIFO has reached alarm threshold, the CVINet
connection has been lost
2- Check the CVI3 Ethernet cable
3- Check CVI3 Ethernet configuration
4- Check if CVINet is running correctly
Appendix - User info codes _02/2017
- 30 -
Type of
code
Code
no.
Description
Resolution procedure
Info
242
ToolsNet FIFO alarm
1- The ToolsNet result FIFO has reached alarm threshold, the CVINet
connection has been lost
2- Check the CVI3 Ethernet cable
3- Check CVI3 Ethernet configuration
4- Check if ToolsNet is running correctly
Info
244
Accessory disconnected
1- The accessory at the given address has been disconnected from the
eBUS of the CVI3.
2- Check the accessory cable.
Info
245
Wait report ack
Acknowledge report with its corresponding input
Info
251
No Pset selected
1- No Pset is selected
2- Select a Pset before start order
Info
254
Drive comm. error
1- Error detected in drive communication
2- Restart the controller
3- If the problem occurs again, contact your Desoutter representative for
support
Info
259
Reset input active
1- "Reset" input is active
2- The Tightening Unit will unlock when input switchs to inactive state.
Info
261
Locked by IPM
1- IPM protocol has locked the controller
2- Check the connection with the IPM gateway
3- Check CVI3 IPM configuration
Info
262
OP connect. lost
1- Open protocol connection has been lost
Info
263
Socket tray conflict
For this Tightening Unit, do not associate more than one socket
combination to a Pset
Info
264
Too many steps
Check that an ePOD3 is connected to the controller to enable more steps
per pset
Info
266
Message:
Incoming message received wth dynamic text
Info
269
Pset modified
No procedure
Info
270
Time settings
1-Invalid Time setting
2-Check Pset settings with correct time value settings
Info
271
External tool Pset selected
1- Tool is locked because of External tool Pset selection
Info
272
Debug UsrInfo
1- This UsrInfo is for debug. Contact dev team.
Info
310
Id OK :
1- An identifier has been received and accepted.
2- The identifier is matching an Assembly process start condition
Info
311
Id NOK :
1- An identifier has been received
2- The identifier does not match any Assembly process start condition
Info
312
Access expired
1- The access rights on the USB key cannot be read
2- Unplug the key and insert it again
3- If the issue is persistent, the access right file is probably corrupt
4- Contact your CVI Key administrator.
Info
313
Access invalid
1- The access rights on the USB key could not be read
2- Try unplugg the key and insert it again
3- If the issue is persistent, the access right file is probably corrupt contact
your CVI Key administrator
Info
314
CVIKey plugged
1- an access key has been plugged
Info
315
CVIKey unplugged
1- an access key has been unplugged
Info
316
Barcode lost
no procedure
Info
400
Default Ntwk Cfg
1- Network configuration has been set to default.
Info
401
Ntwk Cfg Error
1- Network configuration failed.
2- Check your settings.
3- If the problem occurs again, contact your Desoutter representative for
support.
Info
500
CVILogix user info
Message generated by CVILOGIX program
Info
888
Controller software updated
no procedure
Info
889
Device Software Updated
Device Software Updated
Info
891
Controller started
No procedure
Info
899
Downgrade not allowed
1- The SW downgrade is not allowed for this version
2- Check the CVI3 image version on your USB key
3- If the update is still failling, contact your Desoutter representative
Info
900
SW update failed
1- The SW upgrade failed
2- Do not remove the USB key and try to restart the CVI3
3- If the upgrade is still failing, contact your Desoutter representative
Appendix - User info codes_02/2017
- 31 -
Type of
code
Code
no.
Description
Resolution procedure
Info
901
SW not found
1- The SW upgrade failed, no CVI3 image (*.cvi3) was found at the USB
key root directory
2- Check your USB key, it must have only one CVI3 image
Info
902
SW invalid
1- The SW upgrade failed, the CVI3 image copied on your USB key is
corrupted
2- Remove and copy again your CVI3 image
3- Try another USB key
4- Contact your Desoutter representative for more information
Info
903
SW updater missing
1- The SW updater is not available or broken
2- Contact your Desoutter representative for more information
Info
904
Backup disabled
1- The save parameters utility is not available
2- Contact your Dessouter representative for upgrade
Info
905
USB key full
1- Your USB key is full, all data were not saved
2- Delete your old backup files and try again
Info
906
Save param. failed
1- An error occurred during backup, data were not saved.
2- Check the available space on your key, delete files and try again.
3- If the problem persists, contact the Desoutter support team.
Info
907
Wrong USB port
1- Your USB device is plugged into the wrong port
2- If your device is a USB key, plug it into the USB front port
3- If your device is a USB barcode reader or keyboard, plug it into the
bottom USB ports
Info
908
Too HID device
1- Too many USB devices (barcode reader or keyboard) are plugged to
the controller
2- Remove all devices and plug them again to the bottom USB ports only.
Info
909
HID device err
1- Your USB device is not supported by the CVI3 controller
2- Only USB barcode reader and USB keyboard are supported, if you use
one of them, contact your Dessouter representative for upgrade
Info
910
Save prg error
1- Plug a USB key to the front panel.
2- Check available space on your USB key, delete some old backup and
try again.
Info
911
Load prg error
1- Plug a USB key to the front panel.
2- The .zip file was not found, check that it is in the correct directory.
Info
912
Backup failed
1- Check the ePOD connection.
2- Contact your Desoutter representative for support.
Info
913
Restore failed
1- Check the ePOD connection.
2- Contact your Desoutter representative for support.
Info
914
Maintenance ongoing
Maintenance ongoing: Refer to user manual
Info
917
Acc conf err
1-The accessory configuration is not correct
2-Check type of elements and events associated
Info
920
Cvi3 reset
ePod automatic backup must be configure again if needed
Info
921
Pset execution not authorized
1-Check used features allowance
2-Contact your Desoutter representative for support
Info
922
Additional transducer span
fail.
1- Span value from additional torque sensor is outside bounds.
2 -Try once again to start the tool with no mechanical constraints. If the
problem occurs again, contact your Desoutter representative for support
Info
923
Additional transducer offset
fail.
1- Offset value from additional torque sensor is outside bounds.
2- Try once again to start the tool with no mechanical constraints. If the
problem occurs again, contact your Desoutter representative for support.
Info
924
Tool calibration required
1-Perform a calibration of the tool on CVI3
Warning
10
Tool calibration expired
1- The tool calibration date has expired.
2- A tool calibration procedure needs to be done to ensure the
measurement accuracy.
Warning
28
Battery tool version error
1 - Battery tool version and controller version are not compatible.
Warning
30
The battery is low
1- The battery is low.
2- Recharge the battery.
Warning
33
Tool time error
1- The tool time is not set correctly. The tightening results will not be time
stamped.
2- Connect the tool to the controller to set date and time.
Warning
36
Tool memory full
1- The tool memory is full.
2- Connect the tool to the controller to empty the memory.
Warning
39
Tightening Unit config err
1- Tightening Unit settings are invalid
Appendix - User info codes _02/2017
- 32 -
Type of
code
Code
no.
Description
Resolution procedure
Warning
41
Unauthorized tool
1- The tool connected to the controller is not authorized.
2 Maximum number of battery tool reached or tightening unit associated
doesn't exist anymore
3- Check the ePOD connection and capacity.
Warning
62
Overload of torque
1- Overload of the torque, could be a rehit
2- Check tool cable is not damaged
Warning
201
Replace RTC battery
1- The real time clock backup battery needs to be replaced.
Warning
212
Result not stored
1- It was not possible to persist the tightening result in the controller
2- Contact your Desoutter representative for support
Warning
214
Short circuit
1- Serial peripheral default.
2- Disconnect and reconnect.
3- Check the serial peripheral.
Warning
246
Synchro I/O problem
1- Error detected on synchronisation input
2- Check the configuration of I/O
3- Check the synchronisation cable
Warning
250
Pset corrupted
1- Pset is not defined correctly
2- Check the Pset
Warning
253
Incorrect tool Id
1- Pset is not defined correctly.
2- One tool declared in the Pset is not part of the tightening unit
3- Check the Pset.
Warning
257
Remote start error
1- Verify the tool trigger is correctly pushed
Warning
258
Calibration need Pset mode
1- For tool calibration, the Tightening Unit has to be in Pset mode
2- Change the Tightening Unit mode into Pset mode.
Warning
267
Result transfer error
Result transfer error
Warning
273
Debug UsrInfo
1- This UsrInfo is for debug. Contact dev team.
Warning
501
CVILogix user info
Message generated by CVILOGIX program
Warning
600
Controller disconnected
DCT_MOT_CONTROLLER_DISCONNECTED_PROCEDURE
Warning
601
RESULT NOT OK
Result not OK
Error
6
Rotor locked
1-Unable to start tool motor (rotor is locked), change your tool
2-Contact your Desoutter representative for support
Error
7
Motor too hot
1- Tool is locked because its maximum motor temperature has been
reached.
2- Tool will remain locked until the motor temperature comes back to its
normal value.
Error
8
Tool angle fault
1- Problem detected with the tool angle sensor
2- The tool needs maintenance.
3- Contact your Desoutter representative for support
Error
9
Tool invalid param
1- Please check the tool compatiblity.
2- The tool memory cannot be read or is invalid.
3- The tool needs maintenance. If the problem occurs again, contact your
Desoutter representative for support.
Error
12
Tool EEPROM error
1- The tool memory cannot be read or is invalid.
2- The tool needs maintenance. If the problem occurs again, contact your
Desoutter representative for support.
Error
13
Bad tool ground
1- Phase-phase or phase to ground shortcircuit.
2- Disconnect the tool. Contact your Desoutter representative for support.
Error
14
Tq. power default
1- The torque sensor is not corrrectly supplied
2- The tool needs maintenance. If the problem occurs again, contact your
Desoutter representative for support.
Error
18
Torque out of range !
1- The target torque value is above the tool max. torque.
2- Check Pset settings against tool characteristics.
Error
19
Tool comm. error
1- Tool communication error.
2- Check tool and cable connections. If the problem occurs again, contact
your Desoutter representative for support.
Error
20
Tool LED err.
1-Tool LED are not corrrectly supplied
2- Disconnect and reconnect the tool. If the problem occurs again, contact
your Desoutter representative for support.
Error
23
Unsupported tool
1- The tool connected to the controller is not supported.
2- Contact your Desoutter representative for more information.
Error
29
The battery is empty
1- The battery is discharged. The tool cannot tighten.
2- Recharge the battery.
Error
31
Battery error
1- Abnormal battery voltage, the tool cannot tighten.
2- Recharge the battery. If the problem occurs again, replace the battery.
Appendix - User info codes_02/2017
- 33 -
Type of
code
Code
no.
Description
Resolution procedure
Error
32
Tool display error
1- Board display malfunction.
2- Contact your Desoutter representative for support.
Error
34
Tool mem. err
1- The tool memory does not work properly.
2- Contact your Desoutter representative for support.
Error
35
Tool memory locked
1- The tool memory is locked to protect old data from rewriting.
2- Connect the tool to E-dock to retrieve old data.
Error
37
Tool trig err.
1- The tool trigger does not work properly.
2- Check and clean the trigger. If the problem occurs again, contact your
Desoutter representative for support.
Error
45
Anormal battery voltage
1- Anormal battery high voltage, check your battery.
2- This error can due to charger malfunction or end of life battery.
Error
47
Battery is too low
1- Battery is too low, check your battery.
2- If the problem occured again, change the battery with a new one.
Error
48
Battery type not allowed
1- Battery type not allowed.
2- Change your battery type or your configuration.
Error
200
Quick stop !
1- The quick stop has been activated
2- Check the Phoenix connector
Error
213
Drive Connect. Lost
1- Connection with the drive has been lost.
2- Reboot the controller.
3- If the issue remains, contact your Desoutter representative.
Error
216
Current high
1-Max current exceeded.
2-Contact your Desoutter representative for support
Error
217
Drive disabled
1-Drive disabled by external source.
2-Contact your Desoutter representative for support
Error
218
Drive power failure
1- Drive hardware failure.
2- Safety issue: contact your Desoutter representative for support
Error
219
Trig. safety fail.
1- Drive hardware failure.
2- Safety issue. Contact your Desoutter representative for support.
Error
220
Hardware trip
1- Drive hardware failure.
2- Safety issue. Contact your Desoutter representative for support.
Error
221
Drive check err.
1- Drive hardware failure.
2- Safety issue. Contact your Desoutter representative for support.
Error
222
Controller Too Hot
1- Heatsink too warm.
2- Let the controller cool down.
Error
223
Drive init error
1- Software failure.
2- Restart the controller.
3- If the problem occurs again, contact your Desoutter representative for
support.
Error
227
Motor stalled
1- Motor stalled (could be missing phase, wrong motortune or power
electronics failure)
2- Try once again, if the problem occurs again, contact your Desoutter
representative for support.
Error
228
Drive err.
1- Software failure
2- Restart the controller.
3- If the problem occurs again, contact your Desoutter representative for
support
Error
229
Err. ctrl. loop
1- Software failure.
2- Restart the controller.
3- If the problem occurs again, contact your Desoutter representative for
support.
Error
230
DC bus high
1- Max current exceeded. DC-bus voltage high
2- Contact your Desoutter representative for support
Error
231
DC bus too low
1- Power failure. DC-bus voltage low
2- Contact your Desoutter representative for support.
Error
232
Err. ID fieldbus
1- The Fieldbus module plugged in the controller cannot be run. It is not an
authorized Desoutter module.
2- Contact your Desoutter representative for more information.
Error
233
CVINET FIFO full
1- The CVINet result FIFO is full, the CVINet connection has been lost
2- Check the CVI3 Ethernet cable
3- Check CVI3 Ethernet configuration
4- Check if CVINet is running correctly
Appendix - User info codes _02/2017
- 34 -
Type of
code
Code
no.
Description
Resolution procedure
Error
236
ToolsNet FIFO full
1- The ToolsNet result FIFO is full, the CVINet connection has been lost
2- Check the CVI3 Ethernet cable
3- Check CVI3 Ethernet configuration
4- Check if ToolsNet is running correctly
Error
240
XML not authorized
1- The selected XML protocol is not authorized (check the ePOD
characteristics)
Error
243
PFCS not authorized
1- The selected PFCS protocol is not authorized (check the ePOD
characteristics)
Error
247
XML version conflict
1- Conflict detected in Audi / VW XML protocol version.
2- Check the coherence of the version between the controller and master
PC/PLC
Error
248
SAS order failed
1- Fieldbus SAS order has failed.
2- Check the value of RRGI, SIO, etc.
Error
249
XML PRG 0
1- The PRG value 0 has been set by Fieldbus.
Error
255
Drive choke too hot
1- Power electronics too warm.
2- Let the controller cool down.
Error
256
Motor too hot
1- Tool is locked because its maximum motor temperature has been
reached.
2- Tool will remain locked until the motor temperature comes back to its
normal value.
Error
260
IPM not authorized
1- The selected IPM protocol is not authorized (check the ePOD
connection)
Error
265
Socket(s) usable with more
than one TU
Reconfigure sockets combination to resolve conflicts
Error
268
CVI NET incompatible
CVI Net and CVI3 are incompatible. Please update CVI Net software
Error
502
CVILogix user info
Message generated by CVILOGIX program
Error
890
Device Software Error
Device Software Error
Error
915
Inconsistent version
1- The SW version of all CVI3 controllers must be identical
2- Update firmware
Error
916
Workgroup not authorized
1- You need to connect an epod3 on the Workgroup Primary controller
Error
918
Emergency stop !
1- The emergency stop has been activated
2- Check the M8 connector
Error
919
Additional transducer error
1- The additional transducer's maximum torque is lesser than the
embedded transducer's maximum torque
2- The Pset uses an additional transducer though non is installed on tool
Appendix - Connections_02/2017
- 36 -
APPENDIX - CONNECTIONS
1 - TOOL CONNECTOR
A
B
STA
STB
+15V
0V
Ground
Phase 1
Phase 2
Phase 3
(a)
(a)
(a)
(a)
(a)
(b)
(b)
1mm²
1mm²
0.25mm²/120Ω
0.25mm²/120Ω
0.35mm²
0.35mm²
1mm² or 2.5mm²
1mm² or 2.5mm²
1mm² or 2.5mm²
1mm² or 2.5mm²
(a)
E
F
A
B
4
1
2
3
E
F
A
B
4
1
2
3
2 - RS232 - SubD 9pt
RX1
TX1
TX2
GND
1
2
3
4
RX2
RTS1
CTS1
5
6
7
8
+5V
9
9
8
7
6
5
4
3
2
1
RS1
RS2
Serial ports
Barcode reader
Legend
A Connector 12 pts Male
B Connector 12 pts Female
a Ground shielded cable
b WARNING : Shielded insulate
STA
Twisted pairs: 2x0.25 mm²
at 10 MHz 65 Ω
STB
Cable
Color
STA
Red
STB
Red / Blue
+15V
Black / Blue
0V
Black
Ground
Yellow / Green
Phase 1
Black
Phase 2
Brown
Phase 3
Blue
Appendix - Connections_02/2017
- 37 -
3 - DIGITAL INPUTS (0 – 24V)
1
13
14
26
+24V controller
AGND
0VE controller
Quick Stop Channel 1
1
2
3
4
Input 1
Quick Stop Channel 2
Input 2
Input 3
5
6
7
8
Input 5
Input 4
Input 6
Input 7
9
10
11
12
Input 8
13
Example of connections:
Possibility to connect a 24V external supply in parallel of the
24V delivered by the controller:
+24V Ext
+24V Controller
0VE controller
15
2
3
16
4 - DIGITAL OUTPUTS (0 – 24V)
1
13
14
26
+24V controller
AGND
0VE controller
Common 1
14
15
16
17
Output 2
Output 1
Output 3
Output 4
18
19
20
21
Output 6
Output 5
Output 7
Output 8
22
23
24
25
Common 2
26
Example of connections:
Possibility to connect a 24V external supply in parallel of the
24V delivered by the controller:
+24V Ext
+24V Controller
Common 1
Output 1
Output 2
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
F2
0VE Controller
Common 2
F3
17
18
19
20
21
15
2
SG
26
22
23
24
25
SG
16
3
Appendix - Connections_02/2017
- 38 -
5 - Tightening flow chart and timing chart
Input/Output defined by default can be used to control
tightening operation from a PLC or other electronic device.
Here is an example of standard exchange between a CVI3
controller and a PLC.
5.1 - Tightening operation through IO flow-chart
Start
End
No
No
No
No
No
Ready = 1 ?
Reset = 0
Reset = 1
Tightening OK &
Tightening NOK
= 0 ?
Pset selected =
expected Pset ?
Tightening
running = 1 ?
Tightening
running = 0 ?
Select Pset number
Spindle validation = 1
(if necessary)
Start stop tightening
on state = 1
Start stop tightening
on state = 0
Read results
OK/NOK
Read (if necessary)
digital result
Appendix - Connections_02/2017
- 39 -
5.2 - Tightening operation through IO timing chart
1
2
3
4
5
Phases
READY (O)
PSET SELECT BIT 0 (I)
PSET SELECT BIT 1 (I)
PSET SELECT BIT 2 (I)
PSET SELECTED BIT 0 (O)
PSET SELECTED BIT 1 (O)
PSET SELECTED BIT 2 (O)
SPINDLE VALIDATION (I)
START/STOP TIGHTENINGON STATE (I)
TIGHTENING RUNNING (O)
TIGHTENING OK/NOK (O)
RESET (I)
Phase
Designation
1
The “Reset” signal is sent by the PLC. This leads to reset the report
(“Tightening OK/NOK”).
2
The controller receives the Pset no.1 selection. The command is
acknowledged by the “Pset Selected” signals.
3
The controller detects the “Start Stop Tightening On State” signal
transition. The tightening operation starts and “Tightening Running”
signal is set to 1.
4
At the end of the tightening operation, the controller sets "Tightening
OK" or "Tightening NOK" signals.
5
The "Tightening Running" signals returns to zero when all operations
are over.
Appendix - Connections_02/2017
- 40 -
6 - SYNCHRONIZING SINGLE-CHANNEL CONTROLLERS
It is necessary to wire a diode 1N4148 in serial with each synchro out signal.
GND
+24V
0VE
1
2
3
4
Stop 2
6
7
8
Stop 1
Stop 2
Stop 1
Stop 2
Stop 1
GND
+24V
0VE
2
3
4
5
5
5
5
6
7
8
COM2
1
COM1
GND
+24V
0VE
1
2
3
4
6
7
8
GND
+24V
0VE
2
3
4
5
6
7
8
COM2
1
COM1
GND
+24V
0VE
1
2
3
4
6
7
8
GND
+24V
0VE
2
3
4
5
6
7
8
COM2
1
COM1
2
3
4
5
6
7
8
COM2
1
COM1
2
3
4
5
6
7
8
COM2
1
COM1
Output
Input
Controller 1
Output
Input
Controller 2
Output
Input
Controller 3
Synchro
IN
Synchro
OUT
1N4148
Synchro
IN
Synchro
OUT
1N4148
Synchro
IN
Synchro
OUT
1N4148
7 - SYNCHRONIZING TWINCVI3 CONTROLLERS
It is necessary to wire a diode 1N4148 in serial with each synchro out signal.
GND
+24V
0VE
1
2
3
4
Stop 2
6
7
8
Stop 1
Stop 2
Stop 1
Stop 2
Stop 1
GND
+24V
0VE
2
3
4
5
5
5
5
6
7
8
COM2
1
COM1
GND
+24V
0VE
1
2
3
4
6
7
8
GND
+24V
0VE
2
3
4
5
6
7
8
COM2
1
COM1
GND
+24V
0VE
1
2
3
4
6
7
8
GND
+24V
0VE
2
3
4
5
6
7
8
COM2
1
COM1
2
3
4
5
6
7
8
COM2
1
COM1
2
3
4
5
6
7
8
COM2
1
COM1
Output
Input
Controller 1
Output
Input
Controller 2
Output
Input
Controller 3
Synchro
IN
Synchro
OUT
1N4148
Synchro
IN
Synchro
OUT
1N4148
Synchro
IN
Synchro
OUT
1N4148
Appendix - Connections_02/2017
- 41 -
8 - eBUS (for accessories)
B -
GND-EXT
AGND
2
3
B +
5
6
7
8
+24V-EXT
+24V
0V
9
1
4
9
8
7
6
5
4
3
2
1
9 - WORKGROUP
min. 5 mm
tool no. 2
tool no. 3
tool no. 4
tool no. 5
tool no. 1
Customer network
Workgroup network
For each secondary controller,
check that the quick stop is on
but inactive
Use «Eject» command before
disconnecting the ePOD.
ePOD3
SECONDARY CONTROLLERS
PRIMARY CONTROLLER
Appendix - ePOD_02/2017
- 42 -
APPENDIX - ePOD
The ePOD unlocks a specified level of functionality and acts as a back-up unit for the configuration of the CVI3 controllers.
It also increases the number of results, curves and logs in the controller.
There are different models of ePOD and specific ePOD designed for some specific protocols.
Model
ePOD1
ePOD2
ePOD3
ePOD2C
ePOD3C
ePOD4C
Part number
6159360750
6159360760
6159360770
6159363110
6159363180
6159363120
Backup
Complete backup of the controller
system
included
included
included
included
included
included
Results storage
Number of Pset results
10,000
20,000
20,000
20,000
20,000
20,000
Number of curves per tool
20
50
50
50
50
50
Number of Pset versions per Pset
10
20
20
20
20
20
Number of events in the event log
500
1,000
1,000
1,000
1,000
1,000
Basic functions
Number of steps per Pset:
- Tools with cable connection
15
15
40
15
15
40
- Wireless battery tools
10
10
10
10
10
10
CVILOGIX
-
included
included
included
included
included
Workgroup
-
-
included
-
-
included
Programming / Supervision / Controller backup
Results storage
-
included
included
included
included
included
Tightening units management (with CVI3 Vision controller only)
Maximum number of tightening units
2
2
2
3
3
4
Maximum number of wireless battery
tools
1
1
1
2
3
4
ePOD1
ePOD1 is a backup module for the controller result and configuration database.
- It can be used as real time backup module. In this case the ePOD1 must always be plugged to the controller.
- It also can be used as a manual backup that stores the configuration database, the results database and the firmware version of
the controller. ePOD1 gets a snapshot of the controller.
ePOD2
ePOD2 has all functionalities of ePOD1.
- ePOD2 activates CVILOGIX (Embedded PLC of CVI3 controllers).
ePOD3
ePOD3 has all functionalities of ePOD2.
- ePOD3 activates the workgroup configuration.
ePODxC
ePODxC has all functionalities of ePOD2 or ePOD3.
- It can be connected to CVI3 Vision controllers only.