DSE 8860 Installation Instructions Manual

Text of the manual

ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR

• Ensure the generator(s) is at rest and the module is in STOP mode by pressing the Stop/Reset button. • Press and hold the Stop button and Tick button together. • If a module security PIN has been set, the PIN number request is then shown. • Press , the first ‘#’ changes to ‘0’. Press (up) or (down) button to adjust it to the correct value. • Press (right) button when the first digit is correctly entered. The digit you have just entered will now show ‘#’ for security. • The other digits of the PIN number. You can press (left) button if you need to move back to adjust one of the previous digits. • When is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct, you must re-enter the PIN. • If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed. EDITING A PARAMETER • Enter the editor as described above. • Press the (up), (down), (left) and (right) to cycle to the section you wish to view/change. • Then press (up) or (down) to cycle to the parameter within the section you have chosen. • To edit the parameter, press to enter edit mode. The parameter is highlighted blue to indicate that you are editing the value. • Press the up or down buttons to change the parameter to the required value. • Press to save the value. The parameter ceases flashing to indicate that it has been saved. • To exit the editor at any time, press and hold the or button. NNNNO OO OTTTTEEEE:::: TTTThhhheeee PPPPIIIINNNN nnnnuuuum m m mbbbbeeeerrrr iiiissss nnnnooootttt sssseeeetttt bbbbyyyy DDDDSSSSEEEE w ww whhhheeeennnn tttthhhheeee m m m moooodddduuuulllleeee lllleeeeaaaavvvveeeessss tttthhhheeee ffffaaaaccccttttoooorrrryyyy.... IIIIffff tttthhhheeee m m m moooodddduuuulllleeee has a PIN has a PIN has a PIN has a PIN ccccooooddddeeee sssseeeetttt,,,, tttthhhhiiiissss hhhhaaaassss bbbbeeeeeeeennnn iiiim m m mpppplllleeeem m m meeeennnntttteeeedddd bbbbyyyy yyyyoooouuuurrrr ggggeeeennnneeeerrrraaaattttoooorrrr ssssuuuupppppppplllliiiieeeerrrr w ww whhhhoooo sssshhhhoooouuuulllldddd bbbbeeee ccccoooonnnnttttaaaacccctttteeeedddd iiiiffff yyyyoooouuuu rrrreeeeqqqquuuuiiiirrrreeee tttthhhheeee ccccooooddddeeee.... IIIIffff tttthhhheeee ccccooooddddeeee hhhhaaaassss bbbbeeeeeeeennnn ‘‘‘‘lllloooosssstttt’’’’ oooorrrr ‘‘‘‘ffffoooorrrrggggooootttttttteeeennnn’’’’,,,, tttthhhheeee m m m moooodddduuuulllleeee m m m muuuusssstttt bbbbeeee returned to the DSE factory to have the module’s code removed. A charge will be returned to the DSE factory to have the module’s code removed. A charge will be returned to the DSE factory to have the module’s code removed. A charge will be returned to the DSE factory to have the module’s code removed. A charge will be m m m maaaaddddeeee ffffoooorrrr tttthhhhiiiissss procedure. procedure. procedure. procedure. TTTThhhheeee PPPPIIIINNNN nnnnuuuum m m mbbbbeeeerrrr iiiissss aaaauuuuttttoooom m m maaaattttiiiiccccaaaallllllllyyyy rrrreeeesssseeeetttt w ww whhhheeeennnn tttthhhheeee eeeeddddiiiittttoooorrrr iiiissss eeeexxxxiiiitttteeeedddd ((((m m m maaaannnnuuuuaaaallllllllyyyy oooorrrr automatically) to ensure security. automatically) to ensure security. automatically) to ensure security. automatically) to ensure security. NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security. NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security. NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security. NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security. D E E P S E A E L E C T R O N I C S D S E 8 8 6 0 I N S T AL L AT I O N I N S T R U C T I O N S 053-139 ISSUE 1 TYPICAL WIRING DIAGRAM A larger version of the diagram is available in the products operators manual. DSE Part No: 057-173 DIMENSIONS AND MOUNTING For flat surface mounting in a Type 1 enclosure to meet UL requirements DIMENSIONS 245 mm x 184 mm x 50 mm (9.6” x 7.2” x 2.0”) PANEL CUTOUT 220mm x 160mm (8.7” x 6.3”)

AUTO TRANSFER SWITCH & MAINS

COLOUR CONTROL MODULE DSEGenset ® The DSE8860 is an easy-to-use single or multi-mains controller with automatic transfer switch capability. Designed to synchronise single or multiple DSE8810s with single or multiple mains (utility) supplies, the DSE8860 will automatically control the change over from mains (utility) to generator supply or run generators in synchronisation with the mains (utility) to provide no-break, peak lopping and peak shaving power solutions. The module can indicate operational status and fault conditions on the LCD screen (multiple languages available), by illuminated LED, audible sounder and SMS messaging. Comprehensive communications are also available via RS232, RS485 & Ethernet for remote PC control and monitoring, and integration into building management systems. The comprehensive event log will record up to 250 events to facilitate maintenance. An extensive number of fixed and flexible monitoring and protection features are included. Easy alteration of the sequences, timers and alarms can be made using the DSE PC Configuration Suite Software. Selected configuration is also available via the module’s front panel. With all communication ports capable of being active at the same time, the DSE8000 Series is ideal for a wide variety of demanding load share applications. KEY LOAD SHARE FEATURES: • Peak lopping • Sequential set start • Manual voltage/frequency adjustment • R.O.C.O.F. and vector shift • Generator load demand • Automatic hours run balancing • Mains (Utility) de-coupling • Mains (Utility) de-coupling test mode • Bus failure detection • Volts and frequency matching. FEATURES ENVIRONMENTAL TESTING STANDARDS ELECTRO MAGNETIC COMPATIBILITY BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment ELECTRICAL SAFETY BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment TEMPERATURE BS EN 60068-2-1 Ab/Ae Cold Test -30 oC BS EN 60068-2-2 Bb/Be Dry Heat +70 oC VIBRATION BS EN 60068-2-6 Ten sweeps in each of three major axes 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn HUMIDITY BS EN 60068-2-30 Db Damp Heat Cyclic 20/55 oC @ 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40 oC @ 93% RH 48 Hours SHOCK BS EN 60068-2-27 Three shocks in each of three major axes 15gn in 11mS DEGREES OF PROTECTION PROVIDED BY ENCLOSURES BS EN 60529 IP65 - Front of module when installed into the control panel with the supplied sealing gasket. COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF LOAD SHARE APPLICATIONS DSE2130 DSE2131 DSE2133 DSE2157 DSE2152 DSE2548 1ph 2ph 3ph 1ph 2ph 3ph N RS232 AND RS485 DSENET® EXPANSION USB PORT USB HOST CONFIGURABLE INPUTS DC POWER SUPPLY 8-35V 7 OTHER ETHERNET 12 232 2 x 485 8 PC MODBUS MODEM + N/C VOLT FREE OUTPUTS BUS SENSING N/O VOLT FREE OUTPUT MAINS (UTILITY) SENSING VOLTS CURRENT 1ph 2ph 3ph N 1ph 1 1 ISSUE 1 DSE8860 ANALOGUE SENDERS DC OUTPUTS LOAD CURRENT MSC 8x60 8x10 8x80 8x10 8x60

DEEP SEA ELECTRONICS PLC UK

Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 EMAIL [email protected] WEBSITE www.deepseaplc.com DEEP SEA ELECTRONICS INC USA 3230 Williams Avenue, Rockford, IL 61101-2668 USA TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708 EMAIL [email protected] WEBSITE www.deepseausa.com 055-139/7/12 (1) KEY FEATURES • Colour LCD graphical display • Configurable digital inputs (12) • Configurable outputs (10) • Configurable flexible sender inputs (2) • Comprehensive electrical protection • Comprehensive loadshare capabilities • Mains (utility) fail sensing • Multiple mains (utility) monitoring, when using multiple DSE8860s • Peak lopping • Peak shaving • RS232, RS485 & Ethernet remote communications • Modbus RTU/TCP support • Configurable display languages • Audible alarm • Reduced file transfer time • Fault condition notification to a designated PC • Compatible with DSE8700 & DSE8600 Series • Front panel editing with PIN protection • Configurable timers and alarms • Multiple date and time scheduler • Configurable event log (250) • Easy access diagnostic page • kW overload protection • Reverse power protection • Power monitoring (kW h, kV Ar, kV A h, kV Ar h) • USB connectivity • Backed up real time clock • Fully configurable via DSE Configuration Suite PC software • Advanced SMS messaging (additional external modem required) • Start & stop capability via SMS messaging • Additional display screens to help with modem diagnostics • DSENet® expansion compatible • Integral PLC editor KEY BENEFITS • Dual processor for improved response • RS232, RS485 & Ethernet can be used at the same time • High number of inputs and outputs • Worldwide language support • Data logging & trending • Harmonics display for clear monitoring • Modules can be integrated into building management systems (BMS) • Licence-free PC software • IP65 rating (with supplied gasket) offers increased resistance to water ingress • PLC editor allows user configurable functions to meet specific application requirements RELATED MATERIALS TITLE PART NO’S DSE8860 Installation Instructions 053-139 DSE8860 Operator Manual 057-173 DSE8860 PC Configuration Suite Software Manual 057-174 DSE8810 Data Sheet 055-116 DSE8860 AUTO TRANSFER SWITCH & MAINS COLOUR CONTROL MODULE ® DSEGenset FEATURES Registered in England & Wales No.01319649 VAT No.316923457 Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change the details shown on this data sheet without prior notice. The contents are intended for guidance only. SPECIFICATION DC SUPPLY CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous CRANKING DROPOUTS Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. MAXIMUM OPERATING CURRENT 600 mA at 12 V, 300 mA at 24 V MAXIMUM STANDBY CURRENT 330 mA at 12 V, 160 mA at 24 V MAINS (UTILITY) AND BUS VOLTAGE RANGE 15 V to 333 V AC (L-N) FREQUENCY RANGE 3.5 Hz to 75 Hz OUTPUTS OUTPUTS C & D 8 A at 250 V AC (Volt free) AUXILIARY OUTPUTS E,F,G,H,I,J,K & L 2 A DC at supply voltage DIMENSIONS OVERALL 245 mm x 184 mm x 50 mm 9.6” x 7.2” x 2” PANEL CUT-OUT 220 mm x 160 mm 8.7” x 6.3” MAXIMUM PANEL THICKNESS 8 mm 0.3” STORAGE TEMPERATURE RANGE -40 oC to +85 oC

DSE8860 Operators Manual ISSUE 1

DEEP SEA ELECTRONICS PLC DSE8860 Controller Operators Manual Document Number: 057-173 Author: Ashley Senior

DSE8860 Operators Manual

2 DEEP SEA ELECTRONICS PLC Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail : [email protected] Website : www.deepseaplc.com DSE8860 Operators Manual © Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC. Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice. Amendments List Issue Comments Minimum Module Version Required 1 Initial release Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion. Clarification of notation used within this publication. NOTE: NOTE: NOTE: NOTE: High High High Highlights an essential element of a procedure to ensure correctness. lights an essential element of a procedure to ensure correctness. lights an essential element of a procedure to ensure correctness. lights an essential element of a procedure to ensure correctness. CAUTION! CAUTION! CAUTION! CAUTION! Indicates a procedure or practice, which, if not strictly observed, could Indicates a procedure or practice, which, if not strictly observed, could Indicates a procedure or practice, which, if not strictly observed, could Indicates a procedure or practice, which, if not strictly observed, could result in damage or destruction of equipment. result in damage or destruction of equipment. result in damage or destruction of equipment. result in damage or destruction of equipment. WARNING! WARNING! WARNING! WARNING! Indicates a procedure or practice, which co Indicates a procedure or practice, which co Indicates a procedure or practice, which co Indicates a procedure or practice, which could result in injury to uld result in injury to uld result in injury to uld result in injury to personnel or loss of life if not followed correctly. personnel or loss of life if not followed correctly. personnel or loss of life if not followed correctly. personnel or loss of life if not followed correctly.

Other Controller Manuals