ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR
•
Ensure the generator(s) is at rest and the module is in STOP mode by pressing the Stop/Reset
button.
•
Press and hold the
Stop button and
Tick button together.
•
If a module security PIN has been set, the PIN number request is then shown.
•
Press
, the first ‘#’ changes to ‘0’. Press
(up) or
(down) button to adjust it to the correct
value.
•
Press
(right) button when the first digit is correctly entered. The digit you have just entered will
now show ‘#’ for security.
•
The other digits of the PIN number. You can press
(left) button if you need to move back to
adjust one of the previous digits.
•
When
is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.
•
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed.
EDITING A PARAMETER
•
Enter the editor as described above.
•
Press the
(up),
(down),
(left) and
(right) to cycle to the section you wish to
view/change.
•
Then press
(up) or
(down) to cycle to the parameter within the section you have chosen.
•
To edit the parameter, press
to enter edit mode. The parameter is highlighted blue to indicate
that you are editing the value.
•
Press the up or down buttons to change the parameter to the required value.
•
Press
to save the value. The parameter ceases flashing to indicate that it has been saved.
•
To exit the editor at any time, press and hold the
or
button.
NNNNO
OO
OTTTTEEEE:::: TTTThhhheeee PPPPIIIINNNN nnnnuuuum
m
m
mbbbbeeeerrrr iiiissss nnnnooootttt sssseeeetttt bbbbyyyy DDDDSSSSEEEE w
ww
whhhheeeennnn tttthhhheeee m
m
m
moooodddduuuulllleeee lllleeeeaaaavvvveeeessss tttthhhheeee ffffaaaaccccttttoooorrrryyyy.... IIIIffff tttthhhheeee m
m
m
moooodddduuuulllleeee
has a PIN
has a PIN
has a PIN
has a PIN ccccooooddddeeee sssseeeetttt,,,, tttthhhhiiiissss hhhhaaaassss bbbbeeeeeeeennnn iiiim
m
m
mpppplllleeeem
m
m
meeeennnntttteeeedddd bbbbyyyy yyyyoooouuuurrrr ggggeeeennnneeeerrrraaaattttoooorrrr ssssuuuupppppppplllliiiieeeerrrr w
ww
whhhhoooo sssshhhhoooouuuulllldddd bbbbeeee
ccccoooonnnnttttaaaacccctttteeeedddd iiiiffff yyyyoooouuuu rrrreeeeqqqquuuuiiiirrrreeee tttthhhheeee ccccooooddddeeee.... IIIIffff tttthhhheeee ccccooooddddeeee hhhhaaaassss bbbbeeeeeeeennnn ‘‘‘‘lllloooosssstttt’’’’ oooorrrr ‘‘‘‘ffffoooorrrrggggooootttttttteeeennnn’’’’,,,, tttthhhheeee m
m
m
moooodddduuuulllleeee m
m
m
muuuusssstttt bbbbeeee
returned to the DSE factory to have the module’s code removed. A charge will be
returned to the DSE factory to have the module’s code removed. A charge will be
returned to the DSE factory to have the module’s code removed. A charge will be
returned to the DSE factory to have the module’s code removed. A charge will be m
m
m
maaaaddddeeee ffffoooorrrr tttthhhhiiiissss
procedure.
procedure.
procedure.
procedure. TTTThhhheeee PPPPIIIINNNN nnnnuuuum
m
m
mbbbbeeeerrrr iiiissss aaaauuuuttttoooom
m
m
maaaattttiiiiccccaaaallllllllyyyy rrrreeeesssseeeetttt w
ww
whhhheeeennnn tttthhhheeee eeeeddddiiiittttoooorrrr iiiissss eeeexxxxiiiitttteeeedddd ((((m
m
m
maaaannnnuuuuaaaallllllllyyyy oooorrrr
automatically) to ensure security.
automatically) to ensure security.
automatically) to ensure security.
automatically) to ensure security.
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
D E E P S E A E L E C T R O N I C S
D S E 8 8 6 0 I N S T AL L AT I O N I N S T R U C T I O N S
053-139
ISSUE 1
TYPICAL WIRING DIAGRAM
A larger version of the diagram is available in the products operators manual. DSE Part No: 057-173
DIMENSIONS AND MOUNTING
For flat surface mounting in a Type 1 enclosure to meet UL requirements
DIMENSIONS
245 mm x 184 mm x 50 mm (9.6” x 7.2” x 2.0”)
PANEL CUTOUT
220mm x 160mm (8.7” x 6.3”)
AUTO TRANSFER SWITCH & MAINS
COLOUR CONTROL MODULE
DSEGenset
®
The DSE8860 is an easy-to-use
single or multi-mains controller with
automatic transfer switch capability.
Designed to synchronise single or
multiple DSE8810s with single or
multiple mains (utility) supplies, the
DSE8860 will automatically control
the change over from mains (utility)
to generator supply or run generators
in synchronisation with the mains
(utility) to provide no-break, peak
lopping and peak shaving power
solutions.
The module can indicate operational
status and fault conditions on the
LCD screen (multiple languages
available), by illuminated LED,
audible sounder and SMS
messaging.
Comprehensive communications
are also available via RS232, RS485
& Ethernet for remote PC control
and monitoring, and integration into
building management systems.
The comprehensive event log will
record up to 250 events to facilitate
maintenance.
An extensive number of fixed and
flexible monitoring and protection
features are included. Easy
alteration of the sequences, timers
and alarms can be made using the
DSE PC Configuration Suite
Software. Selected configuration is
also available via the module’s front
panel.
With all communication ports
capable of being active at the same
time, the DSE8000 Series is ideal for
a wide variety of demanding load
share applications.
KEY LOAD SHARE FEATURES:
• Peak lopping
• Sequential set start
• Manual voltage/frequency
adjustment
• R.O.C.O.F. and vector shift
• Generator load demand
• Automatic hours run balancing
• Mains (Utility) de-coupling
• Mains (Utility) de-coupling
test mode
• Bus failure detection
• Volts and frequency matching.
FEATURES
ENVIRONMENTAL TESTING STANDARDS
ELECTRO MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for the
Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30
oC
BS EN 60068-2-2
Bb/Be Dry Heat +70
oC
VIBRATION
BS EN 60068-2-6
Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
HUMIDITY
BS EN 60068-2-30
Db Damp Heat Cyclic 20/55
oC @ 95% RH 48
Hours
BS EN 60068-2-78
Cab Damp Heat Static 40
oC @ 93% RH 48
Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15gn in 11mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
COMPREHENSIVE FEATURE LIST TO SUIT A WIDE
VARIETY OF LOAD SHARE APPLICATIONS
DSE2130
DSE2131
DSE2133
DSE2157
DSE2152
DSE2548
1ph
2ph
3ph
1ph
2ph
3ph
N
RS232 AND
RS485
DSENET®
EXPANSION
USB
PORT
USB
HOST
CONFIGURABLE
INPUTS
DC POWER
SUPPLY 8-35V
7
OTHER
ETHERNET
12
232
2 x 485
8
PC
MODBUS
MODEM
+
N/C VOLT FREE
OUTPUTS
BUS
SENSING
N/O VOLT
FREE OUTPUT
MAINS (UTILITY) SENSING
VOLTS
CURRENT
1ph
2ph
3ph
N
1ph
1
1
ISSUE 1
DSE8860
ANALOGUE
SENDERS
DC OUTPUTS
LOAD
CURRENT
MSC
8x60
8x10
8x80
8x10
8x60
DEEP SEA ELECTRONICS PLC UK
Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303
EMAIL [email protected] WEBSITE www.deepseaplc.com
DEEP SEA ELECTRONICS INC USA
3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL [email protected] WEBSITE www.deepseausa.com
055-139/7/12 (1)
KEY FEATURES
• Colour LCD graphical display
• Configurable digital inputs (12)
• Configurable outputs (10)
• Configurable flexible sender inputs
(2)
• Comprehensive electrical
protection
• Comprehensive loadshare
capabilities
• Mains (utility) fail sensing
• Multiple mains (utility) monitoring,
when using multiple DSE8860s
• Peak lopping
• Peak shaving
• RS232, RS485 & Ethernet remote
communications
• Modbus RTU/TCP support
• Configurable display languages
• Audible alarm
• Reduced file transfer time
• Fault condition notification to
a designated PC
• Compatible with DSE8700 &
DSE8600 Series
• Front panel editing with PIN
protection
• Configurable timers and alarms
• Multiple date and time scheduler
• Configurable event log (250)
• Easy access diagnostic page
• kW overload protection
• Reverse power protection
• Power monitoring (kW h, kV Ar, kV
A h, kV Ar h)
• USB connectivity
• Backed up real time clock
• Fully configurable via DSE
Configuration Suite PC software
• Advanced SMS messaging
(additional external modem
required)
• Start & stop capability via SMS
messaging
• Additional display screens to help
with modem diagnostics
• DSENet® expansion compatible
• Integral PLC editor
KEY BENEFITS
• Dual processor for improved
response
• RS232, RS485 & Ethernet can be
used at the same time
• High number of inputs and outputs
• Worldwide language support
• Data logging & trending
• Harmonics display for clear
monitoring
• Modules can be integrated into
building management systems
(BMS)
• Licence-free PC software
• IP65 rating (with supplied gasket)
offers increased resistance to
water ingress
• PLC editor allows user
configurable functions to meet
specific application requirements
RELATED MATERIALS
TITLE
PART NO’S
DSE8860 Installation Instructions
053-139
DSE8860 Operator Manual
057-173
DSE8860 PC Configuration Suite Software Manual
057-174
DSE8810 Data Sheet
055-116
DSE8860
AUTO TRANSFER SWITCH & MAINS
COLOUR CONTROL MODULE
®
DSEGenset
FEATURES
Registered in England & Wales No.01319649
VAT No.316923457
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change the
details shown on this data sheet without prior notice. The contents are intended for guidance only.
SPECIFICATION
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
and supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
MAXIMUM OPERATING CURRENT
600 mA at 12 V, 300 mA at 24 V
MAXIMUM STANDBY CURRENT
330 mA at 12 V, 160 mA at 24 V
MAINS (UTILITY) AND BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUTS C & D
8 A at 250 V AC (Volt free)
AUXILIARY OUTPUTS E,F,G,H,I,J,K & L
2 A DC at supply voltage
DIMENSIONS
OVERALL
245 mm x 184 mm x 50 mm
9.6” x 7.2” x 2”
PANEL CUT-OUT
220 mm x 160 mm
8.7” x 6.3”
MAXIMUM PANEL THICKNESS
8 mm
0.3”
STORAGE TEMPERATURE RANGE
-40
oC to +85
oC
DSE8860 Operators Manual ISSUE 1
DEEP SEA ELECTRONICS PLC
DSE8860 Controller Operators Manual
Document Number: 057-173
Author: Ashley Senior
DSE8860 Operators Manual
2
DEEP SEA ELECTRONICS PLC
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND
Sales Tel: +44 (0) 1723 890099
Sales Fax: +44 (0) 1723 893303
E-mail : [email protected]
Website : www.deepseaplc.com
DSE8860 Operators Manual
© Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents
Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to Deep Sea Electronics Plc at the address above.
The DSE logo is a UK registered trademarks of Deep Sea Electronics PLC.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.
Amendments List
Issue
Comments
Minimum Module
Version Required
1
Initial release
Typeface: The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The numeral
1 has a top serif to avoid this confusion.
Clarification of notation used within this publication.
NOTE:
NOTE:
NOTE:
NOTE:
High
High
High
Highlights an essential element of a procedure to ensure correctness.
lights an essential element of a procedure to ensure correctness.
lights an essential element of a procedure to ensure correctness.
lights an essential element of a procedure to ensure correctness.
CAUTION!
CAUTION!
CAUTION!
CAUTION!
Indicates a procedure or practice, which, if not strictly observed, could
Indicates a procedure or practice, which, if not strictly observed, could
Indicates a procedure or practice, which, if not strictly observed, could
Indicates a procedure or practice, which, if not strictly observed, could
result in damage or destruction of equipment.
result in damage or destruction of equipment.
result in damage or destruction of equipment.
result in damage or destruction of equipment.
WARNING!
WARNING!
WARNING!
WARNING!
Indicates a procedure or practice, which co
Indicates a procedure or practice, which co
Indicates a procedure or practice, which co
Indicates a procedure or practice, which could result in injury to
uld result in injury to
uld result in injury to
uld result in injury to
personnel or loss of life if not followed correctly.
personnel or loss of life if not followed correctly.
personnel or loss of life if not followed correctly.
personnel or loss of life if not followed correctly.