PolyPro Single-Wall Gas Vent
System for Category II & IV
Gas-Burning Appliances
A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE
TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO
COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE
THAT POLYPRO® BE INSTALLED ONLY IN ACCORDANCE WITH
THESE INSTRUCTIONS.
Dear Customer, Installer, or End User:
We welcome any comments regarding
matters pertaining to our DuraVent products.
We welcome any ideas, input or complaints
to help improve our product offering.
If you are searching for tech support or
product information, please phone us at
800-835-4429.
Or email us at:
[email protected]
•
Examine all components for possible
shipping damage prior to installation;
•
Read all instructions before beginning
the installation and follow these
instructions exactly as written.
•
Proper joint assembly is essential for a
safe installation. Check the integrity of
ALL joints upon completion of assembly
•
This venting system must be free to
expand and contract under normal
operation.
•
Assure unrestricted vent movement
where required through walls, ceilings
and roof penetrations.
•
This venting system must be supported
in accordance with these instructions.
•
Do not mix pipe, fittings, or joining
methods from different vent system
manufacturers. Do not use adhesives
of any kind with this venting system.
insurance and safety listing of your
appliance. Acceptance of the installed
system is dependant on full compliance
with these installation instrucitons
WARNING
Risk of carbon monoxide poisoning
or fire due to joint separation or pipe
breakage.
Keep these instructions for future
reference.
PolyPro® is one of M&G DuraVent's line of
products.
WARNING
CARBON MONOXIDE POISONING
HAZARD. Failure to follow the steps
outlined below for each appliance
connected to the venting system being
placed into operation could result in
carbon monoxide poisoning or death.
PolyPro Single-Wall Gas Vent System
For the most up-to-date installation instructions, see www.duravent.com
PolyPro®
CONTENTS
LISTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . 4
APPLICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . 4
PERMITS . . . .. . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . 4
GENERAL INSTALLATION NOTES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
CLEARANCES (TABLE 1). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . 4
CONDENSATE DRAIN . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . .5
EQUIVALENT LENGTH CHART (TABLE 2) . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . . 5
JOINT CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . .. . . . 6
APPLIANCE CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . 6
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
ENCLOSURE REQUIREMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
HORIZONTAL TERMINATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
WALL AND CEILING PENETRATION (TABLE 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
VERTICAL TERMINATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
MULTIPLE VENT RUNS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
WARRANTY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Listed to ULC S636
Rated Class IIA, IIB, and IIC vent system
maximum temperature 230°F (110 °C)
maximum positive pressure 15 in-w.c.
Massachusetts Plumbers Board,
# G1-0811-42
APPLICATION
ANSI Category II and IV gas-burning
appliances
Appliances specifically tested and listed to
use M&G DuraVent PolyPro Venting
PERMITS
Check with your local Building Official, Fire
Official, or other authority having jurisdiction
regarding permits, restrictions, and
installation inspections in your area.
GENERAL INSTALLATION NOTES
Read these instructions before beginning.
You must use only authorized M&G DuraVent
PolyPro vent parts, or other parts specifically
authorized in these instructions and/or listed
by the appliance manufacturer in order to
maintain a safe, approved system.
•
Do not fill any air space clearance
(Table 1) with insulation.
•
Do not mix parts or try to match with
other products or use improvised
solutions.
•
Do not install damaged or modified
parts.
•
Use soapy water to lubricate gaskets.
•
Never use Petroleum base lubricants.
If these directions and those of the appliance
manufacturer differ, follow the more
conservative requirements. If you have any
questions, contact either your dealer or M&G
DuraVent directly. A venting system must
not be routed into, through, or within any
other vent, such as an existing masonry or
factory-built chimney flue, unless that vent
or chimney is not being used to vent another
appliance and is only used as a conduit for
the gas-vent system. Plastic venting systems
shall not pass through fire rated separations
without approved firestopping.
PolyPro attains Flame Spread / Smoke
Developed ratings of <25 / <50 (per UL-723,
ASTM E-84 and ULC-S102) when used in
conjunction with the below noted materials:
•
3M Fire Barrier Plenum Wrap 5A+
•
Unifrax FyreWrap 0.5 Plenum Insulation
•
Knauf Insulation- Atmosphere Duct
Wrap with ECOSE
•
Alternate equivalent listed product
Always follow the particular installation
instructions from the insulation wrap
manufacturer, in addition to those for the
PolyPro vent system. The venting system
shall be securely supported using suitable
hangers installed after the pipe has been
properly wrapped. Hardware must not
deform or damage the vent or wrap.
Table 1
Clearance to Combustibles
VENT PIPE ORIENTATION
Single Wall
Vertical
Horizontal
Up to 190°F
0"
0"
Up to 230°F
0"
¼" (6mm) all around
Concentric
Up to 230°F
0"
0"
The vent system must be compliant in
accordance with local code requirements
and appropriate National Codes: In
the US: NFPA 54 / ANSI Z223.1 National
Fuel Gas Code or the International Fuel
Gas Code. In Canada: CAN/CGA-B149.1
Natural Gas Installation Code or CAN/CGA-
149.2 Propane Installation Code.
IMPORTANT
To prevent possible recirculation of flue
gases, the installer must consider the
effects of prevailing wind conditions,
eddy zones, nearby buildings,
obstructions, or other obstacles such as
shrubs when planning exhaust and air
intake locations. M&G DuraVent can not
be held responsible for poor appliance
performance or damage to buildings
due to an incorrect installation. The
minimum clearances detailed within our
instructions may not be adequate in some
circumstances depending on the specifics
of the installation. For this reason we
always recommend vertical venting.
Refer to the appliance manufacturer's
instructions for maximum and minimum
vent lengths permitted with your specific
appliance model. This information should
include guidance on the maximum number
of elbows and related pressure-drops. The
total vent length from the appliance to
the termination shall not be greater than
specified by the appliance manufacturer.
If specific guidance is not offered by the
appliance manufacturer as to Equivalent
Vent Lengths (EVL) for vent components, the
general guidelines in Table 2 can be used.
CONDENSATE DRAIN (Fig.1)
Refer to the appliance manufacturer’s
installation instructions for requirements of
condensate drainage. Ensure proper system
slope for drainage. (Fig.6)
Figure 1
SIPHON
Table 2 - Equivalent Length Chart
2" Equivalent
Length
3" Equivalent
Length
4" Equivalent
Length
5" Equivalent
Length
6" Equivalent
Length
8" Equivalent
Length
1-ft Vent Pipe
1-ft
1-ft
1-ft
1-ft
1-ft
1-ft
1-ft Flex Pipe
2-ft
(same diameter
as rigid)
2-ft
(same diameter
as rigid)
2-ft
(same diameter
as rigid)
2-ft
(same diameter
as rigid)
N/A
N/A
1-ft Flex Pipe
0.4-ft
(updsized one
diameter)
0.6-ft
(updsized one
diameter)
0.6-ft
(updsized one
diameter)
N/A
N/A
N/A
45 Elbow
3-ft
3-ft
5-ft
6-ft
6-ft
13-ft
90 Elbow
5-ft
7-ft
12-ft
14-ft
14-ft
19-ft
Tee
9-ft
12-ft
19-ft
21-ft
22-ft
29-ft
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow these installation
instructions could result in personal
injury or death
P-TRAP
APPLIANCE CONNECTION: 2" - 4"
1.
If the appliance has a PVC/CPVC female
outlet use the Appliance Adapter/ PVC
Adapter and Clamp. (Fig.3)
•
If the appliance has a PVC/CPVC
Male outlet use a matching PVC/
CPVC coupling to convert to a
female outlet.
2.
If the appliance outlet has a rubber
boot or Fernco-style appliance adapter,
then the PolyPro vent pipe may attach
directly to the appliance (Fig.4).
3.
If the appliance has a FasNSeal outlet
then use the FasNSeal to PolyPro
adapter.
6
Figure 4
APPLIANCE
OUTLET
POLYPRO
VENT PIPE
TIGHTEN CLAMPS ON
RUBBER COUPLER
ADAPTER OR FERNCO
STYLE ADAPTER TO
SECURE VENT
PIPE TO APPLIANCE
JOINT CONNECTIONS
Verify the gasket is seated evenly inside the
groove in the female end. For PP / Metal
pipe with a locking tab, slide Locking Band
on male pipe section Fig.2. Insert locking
tab into locking band recess, rotate button
away from Locking Band Clasp, insert pipe
sections, push lock band clamp downward
into socket, disengage socket / tab 1/4"-5/8"
from socket Fig.2. Screws are not allowed
for joint connection. Never penetrate the
wall of PolyPro vent pipe. (Exception- a SS
screw may be used outside the building on
exterior termination fittings to orient an
elbow, etc).
•
IMPORTANT: Locking bands are
mandatory on all exhaust vent joints
POLYPRO TO DURAVENT / SECURITY
CHIMNEY METAL VENT CONNECTION
Approved M&G Duravent / Security Chimney
1738/636 metal vent fittings can be used with
PolyPro. Follow the above (Fig.2) for PolyPro
(female) to Metal Vent (Male) connections.
Figure 3
POLYPRO PIPE
APPLIANCE
ADAPTER CLAMP
APPLIANCE ADAPTER/
PVC ADAPTER
APPLIANCE
EXHAUST OUTLET
OR PVC UNION
APPLIANCE
LOCKING
TAB
LOCKING
BAND RECESS
1/4"
CLICK!
LOCKING
BAND CLASP
VERIFY GASKET IS
SEATED IN FEMALE
END OF PIPE
Pipe lengths may be cut to length
(Fig.5). Use an alternate clamp (Fig.3-
PPS-PAC / PPS-LBC) for the connection
if a locking tab (Fig.2) is removed.
•
Cut square (not at an angle) to the
end of the pipe.
•
Remove burrs before assembly.
Figure 5
MARK
CUT WITH
HACKSAW
DEBURR
7
Figure 6
12"
5/8"
MIN
1/4" - 5/8"
(7.5mm - 15mm)
TO APPLIANCE
2.
Check with appliance manufacturer for
any restrictions or limits on vent length,
number of elbows, etc.
3.
The slope of the vent pipe must be at
least 3° (5/8" per ft, 50mm per meter)
back to the appliance. (Fig.6)
4.
Every horizontal section must be
supported. (Fig.7)
5.
The venting system shall be securely
supported using suitable hangers.
Duravent hardware is recommended; field
supplied support hardware suitable to
the AHJ is acceptable, hardware must not
deform or damage the vent. (Fig. 6 and 7)
Make sure the load of the vent system is not
supported by the appliance.
•
On Duravent and other certain clamp
styles, ¼” or greater All-thread may be
used as an extension.
6.
Vertical installations must be supported
every 10 feet (3 meters) or less. (Fig.7)
7.
Elbows and Tees are sufficiently supported
when a bracket is fixed at the female end of
the connected straight section. (Fig.7)
PP Pipe sections must be disengaged 1/4"-
5/8" per joint (to allow for expansion) and
sloped 3°(5/8"per ft) back to the appliance
per Fig.6 for proper condensate flow.
IMPORTANT
Figure 7
ALL-THREAD
WALL STRAP
(MINIMUM 1PER
HORIZONTAL PIPE
SECTION)
LOCKING BANDS
REQUIRED AT EVERY
EXHAUST JOINT
MAX
10FT
(3m)
8.
Vertical components can be insulated in
unconditioned space or when ran outside.
9.
Use black UV protected components on
venting installed on the exterior.
ENCLOSURE REQUIREMENTS
Through Rooms: Interior vents shall be
enclosed where they extend through closets,
storage areas, occupied spaces, or anyplace
where the surface of the vent could be
contacted by persons or combustible materials
except when installed in the room with the
appliance.
Multi-Story: Consult local building or other
applicable codes for requirements in your
area. In the U.S., NFPA 211 10.6.3 (2013)
states: “Vents that pass through the floors
of buildings requiring the protection of
vertical openings shall be enclosed within an
approved enclosure. The enclosure walls shall
have a fire resistance rating of not less than
1 hour where a vent is located in a building
less than four stories in height. The enclosure
walls shall have a fire resistance rating of not
less than 2 hours where a vent is located in a
building four or more stories in height."
FIRESTOPS (Fig. 8)
1.
Firestops are required at each ceiling/
floor penetration including an attic.
Firestops are not required at the roof
deck penetration.
2.
Cut and/or frame hole. (Table 3)
3.
Slide the two halves together and attach
to the ceiling.
Figure 9
ALIGN TABS WITH
MOUNTS
GASKET
EXTERIOR
WALL PLATE
INTERIOR
WALL PLATE
Figure 10
REMOVE GASKET
INSERT BIRD GUARD
TERMINATIONS:
Horizontal Single Pipe (Fig.9)
1.
Locate penetration in wall.
2.
Cut or cut and frame hole. (Table 3)
3.
Attach Inner Plate to wall.
4.
Attach / seal Outer Plate to outside wall.
5.
Line up keyway, slide black pipe (UV
Protected) or termination through
plates.
6.
If termination is used, attach with screws.
Align tabs with pipe mounts.
7.
Add additional components to raise vent
level if desired (vent to be 12" above
grade or average snow level).
8.
Remove gasket and install Bird Guard
into end of pipe. (Fig.10)
9.
Install Poly Pro venting system to/from
termination to appliance.
Figure 8
FIRESTOP
FIRESTOP
ENCLOSURE
FIRESTOP
Horizontal Twin Pipe (Fig.11)
1.
Locate penetration.
2.
Cut or cut and frame hole. (Table 3)
3.
Attach interior wall plate to inside wall.
4.
Attach and seal exterior wall plate to
outside wall.
Figure 11
POSITIONED
HORIZONTALLY
POSITIONED
VERTICALLY
AIR INLET PIPE
OUTER COVER PLATE
APPLY BEAD OF SILICON SEALANT
AROUND FEMALE END OF PIPE TO
SEAL AGAINST EXTERIOR WALL PLATE
INTERIOR
WALL PLATE
EXTERIOR WALL PLATE
EXHAUST TIP
EXHAUST PIPE
Table 3 - Wall & Ceiling Penetration Sizing Table
VENT DIAMETER
Termination
2"
3"
4"
5"
6"
8"
CONCENTRIC
VERTICAL OR HORIZONTAL
4 1⁄8"
105mm
5 1⁄8"
130mm
6 1⁄8"
155mm
N/A
N/A
N/A
TWIN PIPE HORIZONTAL
CLASS IIB
7 3⁄8" x 25⁄8"
187mm x
65mm
8 3⁄8" x 37⁄8"
212 x 85mm
9" x 43⁄8"
228 x 100mm
N/A
N/A
N/A
TWIN PIPE HORIZONTAL
CLASS IIC (Framing Dimensions)
8" x 3"
200 x 77mm
8 7⁄8" x 37⁄8"
225 x 98mm
9 3⁄8" x 4 3⁄8"
238 x 112mm
N/A
N/A
N/A
SINGLE HORIZONTAL
CLASS IIB
25⁄8"
65mm /
3 3⁄8" "
85mm
4" "
100mm
N/A
N/A
N/A
SINGLE HORIZONTAL
CLASS IIC (Framing Dimensions)
3"
77mm
3 7⁄8
98mm
4 3⁄8
112mm
N/A
N/A
N/A
SINGLE WALL W/ LOCKING BAND
VERTICAL
3 1⁄2"
4 1⁄4"
5 1⁄8"
6 1⁄2"
7 1⁄4"
9 1⁄4"
SINGLE PIPE NO LOCKING BANDS
VERTICAL
3"
3 3⁄4"
4 1⁄2"
5 3⁄4"
6 3⁄4"
7 3⁄4"
5.
Slide pipes through outer plate.
6.
Rotate pipes to slide pipe past keyway.
7.
Slide exhaust tip into exhaust pipe.
8.
Mount outer cover plate to exterior wall
plate.
9.
install Poly Pro venting system to/from
termination to appliance.
of the house, and rest between the two
outward beads.
2.
Install the termination assembly
in accordance with appliance
manufacturer’s instructions.
3.
Verify exhaust pipe cannot be removed
from termination cap.
Lochinvar / IPEX twin plate termination
connector- 3" & 4" installation (Fig.14)
1.
Slide PolyPro Pipe w/ PVC adapter into
small hole of retaining plate until it stops
on the adapter collar.
Figure 14
POLYPRO PIPE
W/PVC ADAPTER
(SUPPLIED WITH
TERMINATION KIT)
Figure 13
BRACKET
POLYPRO PIPE
W/PVC ADAPTER
(SUPPLIED WITH
TERMINATION KIT)
Figure 12
SCREW TO
TERMINATION
AIR INTAKE
EXHAUST
CO-LINEAR
ADAPTER
INSTALL
GASKETS
EXTERIOR
WALL PLATE
INTERIOR
WALL PLATE
HORIZONTAL
TERMINATION
Horizontal Concentric (Fig.12)
1.
Locate penetration.
2.
Cut hole. (Table 3)
3.
Attach and seal exterior exterior wall
plate onto outside wall.
4.
Slide cap through exterior wall plate into
hole from outside building. Cap must
not be installed sloped downward.
5.
Orient termination so air intake slots
face down.
6.
Seal termination to exterior wall plate
with silicone sealant.
7.
Slide interior wall plate over termination
and attach to wall from inside the room.
8.
Attach interior wall plate to termination
with provided hardware.
9.
Install gaskets into Co-Linear Adapter.
10. Attach Co-Linear Adapter to Horizontal
Termination.
11. Install Poly Pro venting system to/from
termination to appliance.
Lochinvar / IPEX twin plate termination
connector- 2" installation (Fig.13)
1.
Slide PolyPro pipe w/ PVC adapter into
oblong hole and down. Brackets will
point away from the wall, on the exterior
2.
Finish installing the termination
assembly in accordance with appliance
manufacturer’s instructions. PolyPro
pipe is to be installed on the exhaust
outlet.
3.
Once securely installed to exterior, verify
exhaust pipe cannot be removed from
termination cap.
Stainless Horizontal (Fig.15)
1.
Cut opening in the wall.
2.
Add Trim Plates and locking band (if
applicable) to final pipe length before
installing. Make sure flanges are facing
towards the wall. Use non-hardening
sealant where necessary.
3.
After exterior trim plate is mounted to
wall, measure 3" from exterior plate and
cut off female pipe end. Duburr. Seal
pipe to exterior plate. Slide Bird screen
over cut pipe end and tighten clamp.
Figure 18
EXHAUST
AIR INLET
Figure 17
TERMINATION
CAP
FLASHING
STORM COLLAR
SUPPORT CLAMP
Figure 16
CENTERLINE OF
EXHAUST OUTLET
OF APPLIANCE
Vertical Concentric (Fig.17)
1.
Locate penetration. (Fig.16)
2.
Cut hole in roof. (Table 3)
3.
Cut hole in ceiling above appliance.
•
Cut hole(s) big enough for pipe in all
ceilings above appliance if installing
in a multi story installation.
4.
Firestop each ceiling penetration.
5.
Attach flashing to roof. (Fig.17)
•
Slide storm collar onto flashing if
using the Adjustable Roof Flashing.
6.
Slide vertical termination into flashing
from above until seated on flashing.
7.
Plumb Termination and mount support
bracket to structure.
CUT LINE
THROUGH HOLE SIZING
4PPS: 4.125" 5PPS: 5.25"
6PPS: 6.125" 8PPS: 8.00"
EXTERIOR PLATE
INTERIOR PLATE
PP PIPE
INITIAL
FINAL
BIRD
SCREEN
CLAMP
FLANGES
Figure 15
Install gaskets into Co-Linear Adapter (if
applicable). (Fig.12)
9.
Connect Co-Linear Adapter to
termination (if applicable). (Fig.18)
10. Install Poly Pro venting system to/from
Co-Linear Adapter or termination to
appliance.
BLACK
UV PROTECTED PIPE
RUBBER FLASHING
Figure 19- Vertical Pipe Termination
RIGID BLACK
UV PROTECTED
POLYPRO
GASKET
PLATE
STAINLESS
RELINE
HANGER
BRACKET
RIGID
POLYPRO
STAINLESS
UPPER
SUPPORT
PLATE
GASKET PLATE
/ HANGER
MOUNT
HARDWARE
FLANGE
BIRD GUARD
Figure 20
CLEARANCE
HOLE
1.75" MAT'L
SPACE MIN
Upper supports may be field supplied and
listed, the listing requires: Min thickness of 24
ga (0.020") SS, no larger than 18" Dia or 18"
max length rectangle, 4 vent runs max per
support. The listing requires clearance holes
no larger than 5 1/8" Dia, with spacing 1 3/4"
apart.
The upper support plate (with a flange for
B vent and factory built chimney, Fig.21)
must be affixed to the top of the conduit via
screws. Anchor bolts must be used when
attaching a flat support plate to the top of
Masonry or other chase (not shown). Support
plate must be weather tight. The SS Hanger
Bracket is installed under the Gasket Plate
and affixed to the top of the support plate
with screws (Fig.21). Use non-hardening
sealant as required.
Vertical single pipe (Fig.19)
1.
Follow instructions for Vertical
Concentric Termination.
2.
Attach flashing to roof. (Fig.19)
•
Rubber boot flashing or similar,
ensure an effective, leak-proof seal
is maintained.
•
Use BLACK UV protected pipe.
3.
Maintain 12 in. (305mm) min. clearance
above highest anticipated snow level,
max 24 in. (610mm) above roof.
MULTIPLE VENTS IN ONE CONDUIT
(Fig.20)
Multiple PolyPro vent systems may be
installed within one conduit. Listed 2"-4"
M&G components must be used, and the
conduit (if pre-existing) must be inspected
and deemed sound.
The lower portion of the vent system must
be supported and firestopped per appliable
DuraVent instruction.
MAINTENANCE
Have your venting system checked annually.
This can be done easily by the same
technician who inspects & services the
appliance. Recommended areas to inspect
are as follows:
- Check areas of the Venting System which
are exposed to the elements for wear or
damage. If damage is found, the components
should be replaced immediately.
- Where possible, look into the Termination
Cap to verify no foreign material is there to
block the vent. Remove any foreign material
found.
- Where practical, inspect joints to verify
that no Pipe Sections or Fittings have been
disturbed, and consequently loosened. Also
check mechanical supports such as Wall
Straps, support plates, etc for rigidity.
Figure 21
HANGER
MOUNTED
TO TOP OF
SUPPORT,
BELOW
GASKET
PLATE
SEAL AS
REQ'D
PolyPro® is a registered trademark of M&G DuraVent, Inc.
All rights reserved, ©2014 M&G DuraVent is a member of M&G Group.
Customer Service Support 800-835-4429 707-446-4740 FAX www.duravent.com
820003161- L273 06/2016
POLYPRO WARRANTY
M&G DuraVent, Inc. (“DuraVent”) provides this warranty for PolyPro® for ten years. Subject to the limitations set forth below, DuraVent warrants that its
products will be free from defects in material or manufacturing, if properly installed, maintained and used. DuraVent products are fully warranted if installed
only by a professional installer. This Warranty is transferable from the original homeowner to the buyer of the home within the warranted ten years. This
warranty does not cover normal wear and tear, smoke damage or damage caused by chimney fires, acts of God, or any product that was: (1) purchased
other than from an authorized DuraVent dealer, retailer or distributor; (2) modified or altered; (3) improperly serviced, inspected or cleaned; or (4) subject to
negligence or any use not in accordance with the installation instructions included with the product as determined by DuraVent.
Installation instructions are available online at www.duravent.com under Support/Literature and through our Customer Service Department
800-835-4429
or [email protected].
DuraVent provides the following warranties for PolyPro: One Hundred Percent (100%) MSRP 10 years from the date of purchase.
All warranty obligations of DuraVent shall be limited to repair or replacement of the defective product pursuant to the terms and conditions applicable to
each product line. These remedies shall constitute DuraVent’s sole obligation and sole remedy under this warranty. This warranty provides no cash surrender
value. The terms and conditions of this warranty may not be modified, altered or waived by any action, inaction or representation, whether oral or in
writing, except upon the express, written authority of an executive officer of DuraVent.
This product is intended for venting only category II & IV appliances burning Natural Gas, Propane and Oil. All other fuels are not covered under this
warranty.
LIMITATIONS ON POLYPRO INTERNET SALES: Notwithstanding any other terms or conditions of this PolyPro Warranty, DuraVent provides no warranty for
PolyPro® if it is not installed by a qualified professional installer.
DuraVent must be notified and given the opportunity to inspect defective product prior to replacement under the terms of this limited lifetime warranty.
All warranty claims must be submitted with proof of purchase. Labor and installation costs are not covered under this warranty. To obtain warranty service
contact: DuraVent Warranty Service, 877 Cotting Ct., Vacaville CA 95688, or call 800-835-4429.
WHERE LAWFUL, DURAVENT DISCLAIMS ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT WILL DURAVENT BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, PUNITIVE OR SPECIAL DAMAGES OR
DIRECT OR INDIRECT LOSS OF ANY KIND, INCLUDING BUT NOT LIMITED TO PROPERTY DAMAGE AND PERSONAL INJURY. DURAVENT’S ENTIRE LIABILITY
IS LIMITED TO THE PURCHASE PRICE OF THIS PRODUCT. SOME STATES DO NOT ALLOW LIMITATIONS ON IMPLIED WARRANTIES, OR THE EXCLUSION OR
LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS AND EXCLUSIONS MAY NOT APPLY TO YOU. THIS LIMITED
WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS THAT VARY FROM STATE TO STATE.
For the most up-to-date installation instructions, see www.duravent.com