Eliwell FREE Panel EVP 3300/C Installation Manual
Read Online
Read the Eliwell FREE Panel EVP 3300/C Installation Manual online using the built-in PDF viewer.
Text of the manual
An Invensys Company
CONTENTS
1
Introduction............................................................................................................................................................. 3
1.1
General description ......................................................................................................................................................................... 3
1.1.1
Specifications: ..................................................................................................................................................................................................................................... 4
1.2
Models and Features....................................................................................................................................................................... 4
2
Mechanical Installation ......................................................................................................................................... 5
3
Electrical connections ........................................................................................................................................... 6
3.1
General warnings.............................................................................................................................................................................. 6
3.1.1
Power supply....................................................................................................................................................................................................................................... 6
3.1.2
Analogue Inputs-Probes................................................................................................................................................................................................................... 6
3.1.3
Serial connections.............................................................................................................................................................................................................................. 6
3.2
Wiring diagrams................................................................................................................................................................................ 8
3.3
Analogue inputs................................................................................................................................................................................ 9
3.4
Connections.....................................................................................................................................................................................10
3.4.1
Example: RS485 connection (Field).............................................................................................................................................................................................10
3.4.2
CAN connection example (Field) ................................................................................................................................................................................................10
3.4.3
Example: RS485 connection with FREE Smart network.........................................................................................................................................................11
3.4.4
CANopen network connection example...................................................................................................................................................................................12
4
Technical Data.......................................................................................................................................................14
4.1
General Technical Data.................................................................................................................................................................14
4.2
I/O features......................................................................................................................................................................................14
4.3
Display...............................................................................................................................................................................................15
4.4
Serials ................................................................................................................................................................................................15
4.5
Transformer.....................................................................................................................................................................................15
4.6
Mechanical dimensions ................................................................................................................................................................15
4.7
Permitted use..................................................................................................................................................................................15
4.8
Improper Use ..................................................................................................................................................................................15
4.9
Disclaimer.........................................................................................................................................................................................15
5
User Interface........................................................................................................................................................16
5.1
Keys and LEDs .................................................................................................................................................................................16
5.2
First power on.................................................................................................................................................................................17
5.3
DIAGNOSTICS menu......................................................................................................................................................................17
5.3.1
BIOS parameters...............................................................................................................................................................................................................................17
5.3.2
HMI Management ............................................................................................................................................................................................................................18
5.3.3
Probe values ......................................................................................................................................................................................................................................18
Note: for offset programming see the section on Analogue Inputs in the Connections chapter.......................................................................................18
5.3.3.1
Date and time ........................................................................................................................................................................................................................18
5.4
Remote interface............................................................................................................................................................................18
5.4.1
Language.............................................................................................................................................................................................................................................18
5.4.2
........................................................................................................................................................................................................................................................ 18
5.4.3
HMI sel................................................................................................................................................................................................................................................ 18
5.4.3.1
COM Setting...........................................................................................................................................................................................................................19
5.4.3.2
HMI Management.................................................................................................................................................................................................................19
6
Parameters..............................................................................................................................................................20
6.1
Table of parameters......................................................................................................................................................................20
6.1.1
Table of parameters........................................................................................................................................................................................................................20
7
Models and Accessories......................................................................................................................................34
7.1
Models ..............................................................................................................................................................................................34
7.2
Accessories.......................................................................................................................................................................................35
To allow quick, easy reference, the guide has been designed with the following features:
References column:
A column to the left of the text contains references to subjects discussed in the text to help you locate the information you
need quickly and easily.
Cross references:
All words in italics are listed in the analytical index along with the page number where they are dealt with in more detail.
In the "on-line" (computer) manual, the words in italics are "hyperlinks" (i.e. mouse-clickable links), connecting up the
different parts of the manual and making it "navigable".
Some text passages are marked by icons in the references column, which have the following meanings:
Important! :
highlights information of which an incorrect understanding can impact negatively on the
system or result in risk to persons, instruments, data, etc.; users must read and take note of
these sections.
Note / highlight:
indicates further information on the subject concerned that the user should take into account.
Tip:
a suggestion that could help the user to understand and make better use of the information
provided.
1.1
General description
The FREE Panel (EVP) is a fully programmable panel mounting solution with LCD display made by Eliwell,
suitable for managing a wide range of HVAC/R and many other applications, from the simplest to the most complex.
The EVP can be used as a system controller, with gateway functions; used in combination with the FREE Evolution and
FREE Smart or third-party controllers it guarantees high performance in terms of memory, connectivity and user interface
as well as straightforward programming, maintenance and servicing.
The EVP is designed for panel mounting, and can also be wall-mounted using a special backplate, available as an accessory.
Programming of the EVP is managed via the FREE Studio development tool, which makes it possible to quickly and
reliably create and customise new programs for all types of application.
The use of several different programming languages in accordance with IEC61131-3 standard (industrial control
programming ), makes it possible to develop new algorithms or entire programmes totally unassisted, which can then be
uploaded to FREE Evolution modules via PC, guaranteeing maximum confidentiality with appropriate security.
The EVP can be used to:
manage a local menu created with the FREE Studio User Interface
manage up to 10 remote menus, created with the FREE Studio User Interface and uploaded from the
respective FREE Evolution devices connected to the network
share network variables (binding)
WEB functionalities
The FREE Panel (EVP) also features WEB functionalities (the FREE Panel product is also designated FREE WEB) offering
makers of machinery and systems integrators full remote access. Having a web-based connection in machines significantly
reduces support and maintenance costs by minimizing call-out charges. End users also benefit, as they can monitor their
own systems both locally and from distance, using the easy-to-understand graphics interface of any common browser via
smartphone, tablet or PC.
Main WEB functionalities
Web-based access.
Remote reading and support.
Local and remote system control, including alarms management.
Preventive and predictive maintenance.
Email alarm alerts.
Next generation system interface on PC, tablet and smartphone.
References
Cross references
Highlighting icons:
FREE Panel EVP 3300/C is equipped with serial CAN, RS485 and ETHERNET, 3 inputs (1 on-board NTC + 1 remote
configurable NTC/DI +1 remote current/voltage configurable).
FREE Panel EVP 3500/C/R is equipped with serial CAN, RS485 and ETHERNET, 3 inputs (1 on-board humidity module + 1
on-board NTC + 1 remote configurable NTC/DI) .
The EVP comes with a built-in 128x64px graphical user terminal.
- - -
24V~/c or 48Vc power supply.
1.2
Models and Features
- -> See Appendix A - Models and Accessories, and Technical Data section.
IMPORTANT! Always make sure the device is switched OFF before touching connections.
All operations must be carried out by qualified personnel.
Do not mount devices in extremely damp and/or dirt-laden areas; they are designed for use in places with ordinary or
normal levels of contamination.
Make sure the area near the cooling slots is ventilated.
Mounting the FREE Panel (EVP)
Designed for panel mounting.
Make a 138x68mm hole.
Remove the front panel (figure 1) and make 4 holes in the panel that the controller is to be mounted on (Figure 2, points
A/B/C/D) or two holes (Figure 2, points E/F) of dia. 2.7 mm at the specified spacing (Figure 2).
Insert the device, fixing it with the screws. Press the front of the remote terminal to close.
Figure 1
Cut out EVP
Figure 2
Cut out EVP
68
138
150
90
2.7
(x 6)
84
A
B
D
C
E
F
Before proceeding with any operation, make sure the device is connected to a suitable external transformer. The
following rules must be followed when connecting cards to each other and to the application:
Loads that exceed the maximum limits stated in this manual must not be applied to outputs.
When connecting loads, follow the circuit diagrams carefully.
To avoid unwanted couplings, wire all SELV (safety extra voltage) users separately from high voltage
users.
IMPORTANT!
Make sure the appliance is switched off before working on electrical connections. Operations must be carried out
by skilled personnel. To ensure proper connections, comply with the following:
Power supplies other than those specified can seriously damage the system.
Select cables of suitable section for the terminals used
Separate the cables of probes and digital inputs from inductive loads and high voltage connections to prevent
any electromagnetic interference. Do not place probe signal leads near other electrical equipment (switches,
meters, etc.)
Make connections as short as possible and do not wind them around electrically connected parts.
To avoid electrostatic discharges, do not touch the electronic components on printed circuit boards.
The device must be connected to a suitable transformer that complies with the specifications indicated in the
Technical Data chapter.
3.1.1
Power supply
Important!
Make sure that the power supply is of the correct voltage for the instrument.
3.1.2
Analogue Inputs-Probes
Probes have no connection polarity and can be extended using a normal two core cable (note that the extension of the
probes influences the electromagnetic compatibility (EMC) of the instrument: take great care with the wiring).
Important!
Pressure probes have a specific connection polarity, which must be observed.
Signal leads (temperature/pressure probes, digital inputs, RS-485/CAN-BUS serials and the electronic supply) must be
routed separately from power cables.
Use probes supplied by Eliwell. Contact Eliwell sales department for parts availability.
3.1.3
Serial connections
On-board CAN as standard
On-board RS485 as standard
On-board ETHERNET serial as standard
Pay special attention when connecting serial lines: Do not connect instruments that communicate using RS485 serial to
CAN terminals, or CAN instruments to RS485 terminals.
CAN
NOTE 1
Use a shielded and "twisted pair" cable with two 0.5mm2 conductors, plus braiding (ideally Belden cable model
3105A (characteristic impedance 120 Ohms) with PVC sleeve, 2 conductors plus braid, 22 AWG, nominal capacity
between conductors 36pF/m, nominal capacity between conductor and shielding 68pF/m).
Always follow regulations applicable to the routing and connection of cables. Make certain that data transmission
circuits are properly separated from power lines.
For connections over longer distances, it is better to end the line with resistors on both ends, inserting the two R
TERM jumpers (available on the terminal strip beside the CAN serial as the default factory configuration).
NOTE 2
The maximum distance depends on the baud setting.
Kb/s (Kbaud)
On-board
CAN
50 Kbaud
1000m
125 Kbaud
500m
250 Kbaud
250m
500 Kbaud
60m
NOTE 3
5-way terminal strip:
3-way ( “GS“, “H and “L”) serial CAN
2-way POWER supply
Temperature
probes
Pressure probes
CAN
INSTALLING THE RS-485 NETWORK
NOTE 1
Use a shielded and "twisted pair" cable with two 0.5mm2 conductors, plus braiding (ideally Belden cable model 8762 with
PVC sleeve, 2 conductors plus braid, 20 AWG, nominal capacity between conductors 89pF/m, nominal capacity between
conductor and shielding 161pF/m).
See EN 50174 standard on IT cabling for indications on how cables should be routed.
Make certain that data transmission circuits are properly separated from power lines.
An RS-485 network up to 1200m in length with a maximum of 256* devices can be connected straight to the controller.
*Note: example of Evolution Modbus Slave with single Master supervisor.
This length can be extended and the number of devices for each channel increased using appropriate repeater modules.
NOTE 2
Single terminal strip with 3 conductors: use all 3 conductors (“+”, “-“ for the signal and “GS” for the braid).
NOTE 3
Attach the 120 (Ohm) 1/4W resistors between the "+" and "-" terminals of the interface and the last controller in each
branch of the network.
NOTE 4
Maximum settable speed 57600 baud. Higher speeds are envisaged for local connection to FREE Studio Device and tests.
ETH
The Ethernet connection allows the FREE PANEL to communicate on an Ethernet network using TCP/IP protocol.
The connection allows:
connection of different controllers and/or applications exchanging variables and/or parameters (network).
connection of a supervision system using Modbus TCP/IP protocol
connection of an IEC 61131-3 Free Studio development system
NOTE: The Ethernet connector shield is internally connected to the earth of the instrument and therefore to the reference
of the input and output channels.
RS485
ETHERNET
24Va/c - 48Vc p o w
er
s u p p l
y
Pin POWER Vout on EVD/EVC
Max. distance 10m EVP-
EVD/EVC
CAN
GS H L
Isolated CAN serial
GS ground serial isolated
from G
R TERM termination resistors
for CAN
cross – cabling: incorrect cabling irreversibly damages EVP and FREE Evolution
RS485
GS - +
Isolated RS485 serial
GS ground serial isolated
from G
Apply 120 Ohm terminal
resistors
Ethernet
ETHERNET serial
Built-in AI1 NTC Sensor
On-board NTC sensor
AI2 Remote Probes
G
NTC, D.I. remote
Ground GND
Probe not included
AI3 Remote Probes
G
4...20mA/0-10V/0-5V
Ground GND
EVP3300/C
Probe not included
12V External power supply
Built-in AI4 RH Sensor
On-board RH% sensor
EVP3500/C/RH
RS485
CAN
+
-
GS
24 Va/c
48 Vc
RS485
CAN
GS H
L POWER
Ethernet
Remote
Probes
AI2 AI3
G
example of
Transducer
AI3
G
+12V External
Power Supply
AI2
G
Digital
input
AI2
G
NTC
RTERM
EVP3300/C
AI1
NTC Sensor Built-in
CAN
GS
H
L
POWER
OUT
POWER
CAN
R TERM
R TERM
RS485
GS
-
+
RS485
FREE EVOLUTION
EVD ● EVC
AI1
AI2
AI3
Remote Probes
Built-in Probe
WARNING
WHILE CABLING
CAN: max distance depending on baud rate
POWER : max distance
10m
RS485
CAN
+
-
GS
24 Va/c
48 Vc
RS485
CAN
GS H
L POWER
Ethernet
Remote
Probes
AI2 AI3
G
AI2
G
Digital
input
AI2
G
NTC
RTERM
EVP3500/C/RH
AI4
RH Sensor Built-in
AI1
NTC Sensor Built-in
CAN
GS
H
L
POWER
OUT
POWER
CAN
R TERM
R TERM
RS485
GS
-
+
RS485
FREE EVOLUTION
EVD ● EVC
AI1
AI2
AI4
Remote Probe
Built-in Probes
WARNING
WHILE CABLING
CAN: max distance depending on baud rate
POWER : max distance
10m
Inputs can be configured as specified in the table below.
Values
Parameter
Description
0
1
2
3
4
5
Cfg_AI1
Type of input
analogue
AI1
NTC
probe
(NK103)
Probe
configured
as voltage-
free digital
input
NTC
probe
(103AT-2)
-
-
-
Cfg_AI2
Type of input
analogue
AI2
NTC
probe
(NK103)
Probe
configured
as voltage-
free digital
input
NTC
probe
(103AT-2)
-
-
-
Cfg_AI3
Type of input
analogue
AI3
-
-
-
4-20
mA
0-10
V
0-5 V
Parameter
Range
Description
FullScaleMin_AI3
-9999…+9999
Analogue input AI3 start of scale value
FullScaleMax_AI3
-9999…+9999
Analogue input AI3 full scale value
The temperature and humidity measurement, as well as the corresponding precisions and tolerances, refer to the
application point of the probes inside the instruments.
If these same measurements are to be referred to air conditions outside of the instrument, e.g. ambient measurements,
account must be taken of offset (differential) parameters that depend on the installation and usage conditions of the
instrument itself.
The differentials e.g. Calibration parameters that can be set are
for on-board (built-in) sensors, 'compensation' parameters are also available
Factory
values
for
these
offsets
assume
a
typical
installation with wall mounted backplate in a non-ventilated environment and with the display backlighting mainly OFF. In
these conditions the following calibration values are obtained:
Compensation_AI1 = -12.0 °C
Compensation_AI4 = -10.5 °C
If the usage conditions require the backlight to be mainly ON, the values must be modified as follows:
Compensation_AI1 = -15.0 °C
Compensation_AI4 = -13.0 °C
For other mounting conditions, it is advisable to carry out calibration during installation, checking the temperature and
relative humidity differences between the external air and the internal probes and if necessary correcting the parameters
Compensation_AI1/ Compensation_AI4
In any case it is possible to achieve a precision of +- 1°C on the temperature measurement and +- 3%RH on the relative
humidity measurement.
Parameter
Description
Unit of Measure
range
Calibration_AI1
Analogue input AI1 differential
°C/10 or °F/10
-180 ... 180
Calibration_AI2
Analogue input AI2 differential
°C/10 or °F/10
-180 ... 180
Calibration_AI3
Analogue input AI3 differential
-1000 ... 1000
Calibration_AI4
Analogue input AI4 differential
-1000 ... 1000
Parameter
Description
Unit of Measure
range
Compensation_AI1
Internal compensation AI1
difference between external air
temperature and measurement
read by NTC sensor AI1
°C/10 or °F/10
-1000 ... 1000
Compensation_AI4
Internal compensation AI4
difference between external
temperature and T measurement
read by RH sensor AI4 (this
temperature is used to calculate
the relative humidity based on
psychrometric charts)
°C/10 or °F/10
-1000 ... 1000
Example: RS485 connection (Field)
1 FREE Panel EVP
Max 127 FREE Evolution EVE expansion modules connected in RS485
o
EVP is in Modbus RTU Master mode
o
EVEs are in Modbus RTU Slave mode
3.4.2
CAN connection example (Field)
1 FREE Panel EVP
Max 12 FREE Evolution EVE expansion modules connected in CAN
EVP
EVE
1
485 -
485 GS
485 +
485 -
485 GS
485 +
POWER IN
24Va/c
48Va
EVE
127
max 127
Switch/Router
Ethernet
FREE Studio / Supervisor
EVE
CAN GS
CAN H
CAN L
24Va/c
48Va
EVP
POWER IN
max 12
EVE
Example: RS485 connection with FREE Smart network
1 FREE Panel EVP
Max 127 FREE Evolution EVD/EVC or FREE Smart or Eliwell and/or third-party instruments equipped with
RS485 serial
o
EVP is in Modbus RTU Master mode
o
All devices equipped with RS485 are in Modbus RTU Slave mode (including the FREE Evolution
modules)
CAN network – see CAN connection example
CANopen network connection example
1 FREE Panel EVP
Max 10 FREE Evolution EVD/EVC
CAN network – see CAN connection example (Field)
HMI menu
EVP can be equipped with its own menu (named Network menu)
In this case EVP is programmed with the network menu, which can read variables present in the Evolution controller
network
EVP can operate from the terminal of the individual controllers and download up to 10 remote menus from the respective
Evolution controllers
In this case the remote menu allows 'local' navigation of the individual Evolution controller
PLC
The variables of the various controllers are shared (bound together)
A PLC present on EVP can use variables present in the network and share its own variables with other PLCs present on the
respective Evolution controllers
EVD
1
EVC
2
CAN GS
CAN H
CAN L
CAN GS
CAN H
CAN L
POWER
POWER
CAN
POWER OUT
24Va/c
48Va
EVC
10
EVP
Binding
max 10
EVE 1
EVE 127
485 GS
485 -
485 +
485 GS
485 -
485 +
485 GS
485 -
485 +
The FREE Panel product is also designated FREE WEB
The Ethernet connection also allows communication using HTTP protocol, i.e. access to a Web Server contained in FREE
Evolution.
FREE WEB
FREE Studio allows the creation and management of web pages internally of FREE WEB, i.e. a veritable website in miniature.
WEB functionalities allow complete local or remote access by way of an ordinary browser. Thanks to the web connection,
the system provides remote reading and support and remote diagnostics services, as well as e-mail alarm alerts.
Note. Connection to FREE WEB remains possible by way of FREE Studio.
NOTE: refer to the section on Parameters / ETHERNET PASSIVE PLUG-IN folder
BRIDGE
FREE Studio allows monitoring of FREE Smart tools or third party tools, typically Modbus/RTU slaves, where FREE WEB (or
FREE Evolution with Plug-In ETH) is the Master Modbus/RTU.
In a FREE Studio project, more exactly, FREE WEB is used as a Modbus/TCP to Modbus/RTU protocol conversion element
for Modbus 0x03 and 0x10 commands.
E.g. from FREE Studio, set the connection with FREE Smart as Modbus/TCP, inserting the FREE WEB IP address and the
Modbus/RTU address of the Smart slave.
TFTP (Trivial File Transfer Protocol)
Note. TFTP (Trivial File Transfer Protocol) can also be enabled for file transfer between PC and controller on an Ethernet
network.
FREE WEB
BRIDGE
TFTP
General Technical Data
Standard
Min.
Max.
Supply voltage*
24V~/c ±20%
or
48Vc ±20%
21V
60V
Power supply frequency
50Hz/60Hz
---
---
Power consumption
5W
Insulation class
2
---
---
Ambient operating temperature
25°C
-10°C
+55°C
Ambient operating temperature of EVK1000 terminal
25°C
-5°C
+55°C
Ambient operating humidity (non-condensing)
30%
10%
90%
Storage temperature
25°C
-20°C
+85°C
Ambient storage humidity (non-condensing)
30%
10%
90%
* powered via FREE Evolution EVD/EVC or directly via a transformer
Note: power cable must not be longer than 10m
Classification
The product meets the requirements of the following
European Community Directives
Directive 2006/95/EC
Directive 89/108/EC
and complies with the following harmonized
regulations
EN 60730-2-6 / EN 60730-2-9 / EN 60730-1
Use
in terms of construction, as an independently mounted
temperature-sensitive automatic electronic controller
Mounting
on DIN Omega bar support
Type of action
1.B
Pollution class
2 (normal)
Over voltage category
II
Nominal pulse voltage
2500V
Digital outputs
refer to the label on the device
Fire resistance category
D
Software class and structure
A
Type of disconnection or suspension for each circuit
Microswitch disconnection
PTI of materials used for insulation
PTI 250V
Period of electrical stress on the insulating parts
Long period
4.2
I/O features
Type and
Label
Analogue
inputs
probe
Description
Resolution
Accuracy
Measurement
range
Impedance 3300
/C
3500
/C
/RH
AI1
On-
board
NTC
0.1°C/°F
0.5% f.s + 1
digit
10KΩ
x
x
NTC 103AT
0.1°C/°F
0.5% f.s + 1
digit
–50…+110 °C
(-58...230°F)
10KΩ
NTC NK103
0.1°C/°F
0.5% f.s + 1
digit
-40…+150 °C
(-40...302°F)
10KΩ
AI2
configurable
Remote
NOT
included
D.I.**
20KΩ
x
x
4...20mA
1 digit
1% f.s +1
digit
0…1000
100Ω
0-5V*
1 digit
1% f.s +1
digit
0…1000
21KΩ
AI3
configurable
Remote
NOT
included
0..10V
1 digit
1% f.s +1
digit
0…1000
21KΩ
x
AI4
On-
board
On-board
%RH input
0.01%RH
(0%=0pt,
100% =
1000pt)
±3%
[20...80%]
±5% …] […
elsewhere
0-100 %RH
x
*50mA maximum current @5V; **Clean contact.
Note: Also see Electrical Connections chapter / Analogue Inputs paragraph for instructions on offsets and calibrations
backlit with LEDs +
3 LEDs
Note: LED and backlighting can be controlled from IEC application
Protection rating:
The single-mould plastic front cover allows for water resistant panel mounting that is
comparable to IP65 protection.
Display:
Monochromatic LCD graphic display 128x64px backlit with LEDs
Container:
backplate + frame in PC+ABS UL94 V-0 plastic resin, front cover in transparent
polycarbonate, polyester membrane keys
4.4
Serials
Serial
Description
Notes
CAN
Open opto-isolated serial CAN
max50m@500kpbs
200m@125kpbs
Note: 2 jumpers available for
CAN terminal resistance
RS-485
Opto-isolated RS-485 Modbus RTU serial
Pay special attention when
connecting serial lines: do not
cable RS485 in CAN port or
vice versa
ETHERNET
Modbus TCP/IP ETHERNET port
Pack includes MACADDRESS, in
barcode and
12-digit alphanumeric format
4.5
Transformer
The instrument must be connected to a suitable current transformer with the following features:
Primary voltage:
Depending on requirements of device and/or country of installation
Secondary voltage:
24V~/c - 48Vc ±20%
Power supply frequency V~:
50/60Hz
Power:
5W min.
4.6
Mechanical dimensions
Length (L) mm
Depth (d)
mm
Height (H) mm
Notes
Space required
160
10
96
Hole for panel mounting
68
/
138
(+0.2 mm /
-0.1 mm)
4.7
Permitted use
For safety reasons, the device must be installed and used according to the instructions provided. In particular, parts
carrying dangerous voltages must not be accessible in normal conditions.
The device must be adequately protected from water and dust with regard to the application, and must only be accessible
using tools (with the exception of the front panel).
The device is suitable for use in household and/or similar air conditioning appliances or installations and has been tested
for safety aspects in accordance with harmonized European reference standards.
4.8
Improper Use
Any use other than that expressly permitted is prohibited.
The relay contacts supplied are of the functional type and subject to fault (since they are electronically controlled they are
prone to short-circuiting or remaining open). Any protection devices specified in product standards or suggested by
common sense for obvious safety requirements must be installed externally to the device.
Eliwell is not liable for damage caused by:
Unspecified installation/use and, in particular, in contravention of the safety requirements of established legislation or
specified in this document;
Use on equipment which does not provide adequate protection against electrocution, water and dust in the actual
installation conditions;
Use on equipment in which dangerous components can be accessed without the use of specific tools;
Installation/use on equipment which does not comply with established legislation and standards.
4.9
Disclaimer
This document is the exclusive property of Eliwell Controls srl and may not be reproduced or circulated unless expressly
authorized by Eliwell Controls srl itself.
Every care has been taken in preparing this document; however, Eliwell Controls srl cannot accept liability for any
damage resulting from its use.
The interface, comprising the front cover of the controller, allows you to perform all operations needed to use the device.
EVP
5.1
Keys and LEDs
The LEDs can be programmed from the IEC application.
The keys can be programmed from the IEC application. By default, the device displays a short menu containing the
following default settings.
Key
Key
Press once
(press and release)
1
UP
Scroll up
Return to previous page (e.g. 2/10 3/10)
Increase / modify a value
Go to the next label
2
OK
Scroll down
Move to next level/menu (open folder, subfolder, parameter,
value)
Enter/exit edit mode
Confirm operation
3
>
Moves cursor to right in Edit Mode
4
DOWN
Scroll down
Move to the next page (e.g. 1/102/10)
Decrease / modify a value
Go to previous label
5
Exit
Exit menu page / go back to previous menu
Move cursor to left in Edit Mode
(press and hold) Exit Edit Mode without saving any changes
EVP is factory configured with a default DIAGNOSTICS (DIA) menu that appears when the instrument is powered on.
After uploading of an IEC application and/or a HMI menu from FREE Studio, the main display consists of the application
menu created with FREE Studio Interface.
In which case, to open the DIAGNOSTICS menu proceed as follows:
Key combination
Prolonged press (press and hold for
about 3 seconds)
DOWN
4+5
Exit
Open DIAGNOSTICS menu
To return to the IEC application menu open the ‘HMI Management’ page, select and press the OK key
See Remote Interface paragraph
DIA Menu
First power on
When the instrument is powered up for the first time, a few summary pages are displayed showing system status (SYSTEM
INFO)
SYSTEM INFO
HW
BIOS
DATE
BOOT
EEPROM
NOR FLASH
OK
NAND FLASH
OK
SDRAM
OK
BATRAM
OK
RTC
OK
The system will also search for the PLC application and the local menu…
If present, the menu will appear on the display
PLC searching
…
HMI searching
…
CON
loaded
5.3
DIAGNOSTICS menu
The DIAGONISTICS menu, native to EVP, is used to manage system parameters (BIOS parameters), remote interfaces (HMI)
and to display I/O values and clock
The DIA menu can be displayed in 5 languages: English, Italian, German, Spanish and French.
To change the default language, open BIOS Parameters > Display
EVP
BIOS parameters
HMI Management
Probe values
Date and time
5.3.1
BIOS parameters
Parameter configuration menu. See Parameters chapter.
Note: This menu is depopulated with respect to the parameters table contained in the corresponding chapter and in the
FREE Studio device
Language change example
BIOS parameters
Display
Buzzer
CAN
Display
1/3
Language
Italiano
BIOS parameters < OK key > Display 1/3 < OK key > Edit Mode < UP/DOWN key >
select language < OK key > < key >
Display
1/3
Language
English
See parameter Display/Hmi_Language
See Remote Interface paragraph
5.3.3
Probe values
Shows input values (read only)
EVP has 3 inputs. Example EVP3500/C/RH
Probes values
1/3
Probes values
2/3
Probes values
3/3
Internal NTC
External NTC
Humidity sensor
27.3
- - - - - - - - - - - - - -
43.38
°C, °F
°C, °F
RH%
Note: for offset programming see the section on Analogue Inputs in the Connections chapter
5.3.3.1
Date and time
Shows time (HH : MM : SS) and date (DD / MM / YY) of the internal clock
Date and time
14 : 45 : 45
20 / 07 / 11
Update
To edit the value press OK. Select the value that you want to modify
Press the OK key to enter Edit Mode. Use the UP and DOWN keys to modify value. Confirm with the OK key
Select ‘Update’ and press OK to update the clock
Date and time
16 : 50 : 56
20 / 07 / 11
Update
5.4
Remote interface
EVP
Language: 0
HMI sel: Network
COM setting
HMI Management
5.4.1
Language
This section is for setting the language of the remote menu, defined from the FREE Studio User Interface
The number of languages and the order are established by the corresponding application/menu
See parameter HMI Management/Hmi_Language
5.4.2
To return to the menu of the IEC application, move the cursor onto this symbol and press the OK key
See HMI sel
5.4.3
HMI sel
This section is for setting the menu to be shown on the display
By default HMI menus are NOT present (only the DIA menu is available)
Network: this is the EVP ‘local’ menu (local HMI)
rem1…rem10: menus located on max 10 Evolution devices connected to the network that can be ‘uploaded’ to EVP
EVP
EVP
EVP
HMI sel: Network
HMI sel: rem1
…
HMI sel: rem10
To move from one page to the next press the UP and DOWN keys
After selecting the desired menu move the cursor onto to view the menu
Launch remote page
Please Wait
If OK the display will show the selected menu (IEC application)
If the menu is not present, the following screen appears
Warning
Upload failed
Press OK
5.4.3.1
COM Setting
This read-only page shows the configuration of the EVP serial ports
EVP
CAN : 1 . 500000
485s : 1 . 38400.P81
ETH : 010.000.000.100
5.4.3.2
HMI Management
This page shows the configuration of the 10 remote pages
EVP
1/10
EVP
1/10
EVP 10/10
File: HMIREM.KBD
Id: 0
Id: 0
…
Id: 0
Com: CAN
Com: CAN
Com: CAN
Addr: 125
Addr: 000
Addr: 000
From these pages it is possible to ‘launch’ (run) the corresponding menu – if present
Move the cursor onto and press the OK key
Note: it will not be possible to launch the local (network) menu from this section
Note: in the example only one remote page is present
To ‘upload’ a remote page use
After selecting the desired menu move the cursor onto to view the menu
Upload remote page
Upload page?
The process cannot
be interrupted
Cancel OK
Press OK to upload or any other key to cancel
Upload remote page
Uploading…
80%
Note: the upload may take up to a minute
If there are no data to upload, the following screen displays
Attenzione
There are no remote
pages on the card
Press OK
User-parameterization renders the FREE Panel EVP fully configurable.
Parameters can be changed using:
Keys on the EVP front panel
PC and FREE Studio software
The following sections provide a detailed analysis of each parameter, divided into categories (folders).
6.1
Table of parameters
The following table contains all the device configuration parameters available in FREE Studio Device and in the
DIAGNOSTICS (DIA) / BIOS Parameters menu
Description of columns:
This indicates the label of the FREE Studio Device folder containing the parameter in question
A group of these parameters is available on the LCD display in the DIAGNOSTICS (DIA) menu
Refer also to the following table:
(x) if present (loaded to EVP)
The local menu - if present (uploaded to EVP) - is defined with the Network label
This indicates the label used to display the parameters
Indicates the address of the modbus register containing the resource to be accessed.
Indicates whether the device MUST be rebooted after the parameter has been changed.
Y=YES the device MUST be rebooted to save the change.
N=NO the device DOES NOT need to be rebooted after changing the parameter
Indicates if resources are read/write, read-only or write-only:
R
The resource is read-only
W
The resource is write-only
RW
The resource can be both read and written to
Indicates the size of the data in bits.
When the field indicates “-1”, the value read by the register requires conversion, because the value represents a number
with a sign. In other cases the value is always positive or null.
To carry out the conversion, proceed as follows:
If the value in the register is between 0 and 32.767, the result is the value itself (zero and positive values)
If the value in the register is between 32.768 and 65.535, the result is the value of the register – 65.536 (negative
values)
Describes the interval of values that can be assigned to the parameter. It can be correlated with other instrument
parameters (indicated in the parameter label).
Indicates the factory setting for the standard model of the instrument.
Unit of measure for values converted according to the rules indicated in the CPL column
The unit of measure shown is an example only, as it may change depending on the application (e.g. parameters with a U.M.
in °C/bar could also have %RH)
6.1.1
Table of parameters
(See next page)
FOLDER
FOLDER
EVP
EVP
DIA
ACKNOWLEDGEMENT
x
-
AI CALIBRATION
x
-
ANALOGUE INPUTS
x
-
ON-BOARD RS485
x
-
ON-BOARD CAN
x
x
ETHERNET
x
x
Display
x
x
All Parameters
Buzzer:
x
x
HMI management
x
x
HMI remote 1 (rem1)
x
(x)
…
x
(x)
HMI management
HMI remote 10 (rem10)
x
(x)
LABEL
VAL PAR ADDRESS
RESET (Y/N)
R/W
DATA SIZE
CPL
RANGE
DEFAULT
U.M.
RW Map code
Note: read/write parameter
0 … 65535
0
num.
ACKNOWLEDGEMENT
Par_POLI
15717
WORD
Y
RW Model Code
Note: read/write parameter
0 … 65535
1025
num.
ACKNOWLEDGEMENT
Par_PARMOD
15719
BOOL
RW
Parameter changed
Flag indicating change to default settings.
0= map not modified.
1= at least one parameter has been changed from the
original configuration.
0 … 1
0
num.
AI CALIBRATION
Gain_Ntc_AI1
15616
WORD
RW Ai1 NTC calibration gain
0 … 65535
32768
num.
AI CALIBRATION
Gain_Ntc_AI2
15617
WORD
RW Ai2 NTC calibration gain
0 … 65535
32768
num.
AI CALIBRATION
Gain_5V_AI3
15620
WORD
RW Ai3 0-5V calibration gain
0 … 65535
32768
num.
AI CALIBRATION
Gain_10V_AI3
15621
WORD
RW Ai3 0-10V calibration gain
0 … 65535
32768
num.
AI CALIBRATION
Gain_mA_AI3
15622
WORD
RW Ai3 4-20mA calibration gain
0 … 65535
32768
num.
AI CALIBRATION
Offs_Ntc_AI1
15650
WORD
-1
RW Ai1 NTC calibration offset
-32768 … 32767
0
num.
AI CALIBRATION
Offs_Ntc_AI2
15651
WORD
-1
RW Ai2 NTC calibration offset
-32768 … 32767
0
num.
AI CALIBRATION
Offs_5V_AI3
15654
WORD
-1
RW Ai3 0-5V calibration offset
-32768 … 32767
0
num.
AI CALIBRATION
Offs_10V_AI3
15655
WORD
-1
RW Ai3 0-10V calibration offset
-32768 … 32767
0
num.
AI CALIBRATION
Offs_mA_AI3
15656
WORD
-1
RW Ai3 4-20mA calibration offset
-32768 … 32767
0
num.
Temperature unit of measure
0 = °C;
1 = °F
0 ... 1
0
num.
ANALOGUE
INPUTS
Cfg_AI1
15726
WORD
RW
Type of analogue input Ai1
0= NTC (NK103)
1= DI
2= NTC (103AT)
0 ... 2
2
num.
ANALOGUE
INPUTS
Cfg_Ai2
15727
WORD
RW Type of analogue input Ai2
See Cfg_Ai1
0 ... 2
2
num.
ANALOGUE
INPUTS
Cfg_Ai3
15728
WORD
RW
Type of analogue input Ai3
3 = 4…20mA
4=0-10V
5=0-5V
3 ... 5
3
num.
ANALOGUE
INPUTS
Cfg_Ai4
15729
WORD
RW Type of analogue input Ai4
See Cfg_Ai3
3 ... 5
3
num.
ANALOGUE
INPUTS
FullScaleMin_Ai3
15736
WORD
-1
RW
Analogue input Ai3 start of scale value
N.B.: Minimum full scale: for current probes, value at 4mA,
for 0-10V voltage probes, value at 0V, 10% for ( 0-5V) probes,
value at 10% (corresponding to 0.5V).
-9999…+9999
0
ANALOGUE
INPUTS
FullScaleMAx_Ai3
15737
WORD
-1
RW
Analogue input Ai3 full scale value
N.B.: Maximum full scale for current probes, value at 20mA,
for 0-10V voltage probes, value at 10V, for (0-5V) probes,
value at 90% (corresponding to 4.5V).
-9999…+9999
1000
ANALOGUE
INPUTS
Calibration_Ai1
15748
WORD
-1
RW Analogue input Ai1 differential
-180 ... 180
0
°C/10
or
°F/10
ANALOGUE
INPUTS
Calibration_Ai2
15749
WORD
-1
RW Analogue input Ai2 differential
-180 ... 180
0
°C/10
or
°F/10
ANALOGUE
INPUTS
Calibration_Ai3
15750
WORD
-1
RW Analogue input Ai3 differential
-1000 ... 1000
0
ANALOGUE
INPUTS
Calibration_Ai4
15751
WORD
-1
RW Analogue input Ai4 differential
-1000 ... 1000
0
ANALOGUE
INPUTS
Compensation_AI1
15752
WORD
-1
RW Internal compensation AI1
-1000 ... 1000
0
°C/10
ANALOGUE
INPUTS
Compensation_AI4
15753
WORD
-1
RW Internal compensation AI4
-1000 ... 1000
0
°C/10
VAL PAR AdDRESS
DATA SIZE
CPL
RESET (Y/N)
R/W
DESCRIPTION
RANGE
DEFAULT
U.M.
RS485
ON BOARD
Addr_RS485_OB
15774
WORD
Y
RW
On-board RS485 serial address
The actual address is determined by the sum of this value +
the value of the dip switch.
0 ... 255
1
num.
RS485
ON BOARD
Proto_RS485_OB
15775
WORD
Y
RW
On-board RS485 protocol selection
2 = uNET
3 = Modbus/RTU
2 ... 3
2
num.
RS485
ON BOARD
Databit_RS485_OB
15776
WORD
Y
RW On-board RS485 data bit number
Fixed setting 8
8 ... 8
8
num.
RS485
ON BOARD
Stopbit_RS485_OB
15777
WORD
Y
RW
On-board RS485 stop bit number
1= 1 stop bit
2= 2 stop bit
1... 2
1
num.
RS485
ON BOARD
Parity_RS485_OB
15778
WORD
Y
RW
On-board RS485 protocol parity
0= NULL
1= ODD
2= EVEN
0 ... 2
2
num.
RS485
ON BOARD
Baud_RS485_OB
15779
WORD
Y
RW
On-board RS485 protocol baudrate
0=9600 baud
1=19200 baud
2=38400 baud
3=57600 baud
4=76800 baud
5=115200 baud
0 ... 5
2
num.
ON-BOARD
CAN
Addr_CAN_OB
15780
WORD
Y
RW
On-board CAN serial address
The actual address is determined by the sum of this value +
the value of the dip switch.
1 ... 127
1
num.
ON-BOARD
CAN
Baud_CAN_OB
15781
WORD
Y
RW
On-board CAN protocol baudrate
2=500 Kbaud
3=250 Kbaud
4=125 Kbaud
5=125 Kbaud
6=50 Kbaud
2 ... 6
2
num.
ON BOARD ETHERNET
WEB SERVER FUNCTIONALITY: For more details refer to document 9IS24252_Web_ApplicationNotes
The parameters necessary for the configuration of ports and protocols are these:
HTTP and TFTP ports
FREE WEB allows the use of HTTP and TFTP servers
HTTP HyperText Transfer Protocol.
An HTTP server generally listens on port 80 using TCP protocol.
TFTP Trivial File Transfer Protocol.
Protocol using basic FTP functionalities. Typical use: transfer of small files between hosts on a network. TFTP USES PORT 69
The parameters for configuring the PORTS are:
DHCP protocol
value
Port_HTTP
HTTP port
HTTP communication Port number
Default 0 corresponds to port 80
0
value
Port_TFTP
TFTP port
TFTP communication Port number
Default 0 corresponds to port 69
0
value
EnableDHCP_ETH
Enable DHCP
0 … 1 (False, True)
False
System for the conversion of host names, or network nodes, to IP addresses
Used by FREE Studio to send text e-mails (strings)
value
value
PriDNS_1_ETH
Primary DNS server
(part 1)
194
SecDNS_1_ETH
Secondary DNS server (part 1)
194
PriDNS_2_ETH
Primary DNS server
(part 2)
25
SecDNS_2_ETH
Secondary DNS server (part 2)
25
PriDNS_3_ETH
Primary DNS server
(part 3)
2
SecDNS_3_ETH
Secondary DNS server (part 3)
2
PriDNS_4_ETH
Primary DNS server
(part 4)
129
SecDNS_4_ETH
Secondary DNS server (part 4)
130
FOLDER
LABEL
PAR. VALUE
ADDRESS
DATA SIZE
CPL
RESET (Y/N)
R/W
DESCRIPTION
RANGE
DEFAULT
U.M.
ETHERNET
ON BOARD
Port_TFTP
15772
WORD
Y
RW
TFTP port
TFTP communication Port number Default 0 corresponds to
port 69
0 … 65535
0
num.
ETHERNET
ON BOARD
Port_HTTP
15796
WORD
Y
RW
HTTP port
HTTP communication Port number Default 0 corresponds to
port 80
0 … 65535
0
num.
ETHERNET
ON BOARD
Port_ETH
15797
WORD
Y
RW Port
TCP/IP Modbus communication port. Port 502 for example
0 … 65535
502
num.
ETHERNET
ON BOARD
Ip_1_ETH
15798
WORD
Y
RW On-board Ethernet passive IP address (part 1)
0 … 255
10
num.
ETHERNET
ON BOARD
Ip_2ETH
15799
WORD
Y
RW On-board Ethernet passive IP address (part 2)
0 … 255
0
num.
ETHERNET
ON BOARD
Ip_3ETH
15800
WORD
Y
RW On-board Ethernet passive IP address (part 3)
0 … 255
0
num.
ETHERNET
ON BOARD
Ip_4ETH
15801
WORD
Y
RW On-board Ethernet passive IP address (part 4)
0 … 255
100
num.
RW Default Gateway (part 1)
0 … 255
192
num.
ETHERNET
ON BOARD
DefGtwy_2_ETH
15803
WORD
Y
RW Default Gateway (part 2)
0 … 255
168
num.
ETHERNET
ON BOARD
DefGtwy_3_ETH
15804
WORD
Y
RW Default Gateway (part 3)
0 … 255
0
num.
ETHERNET
ON BOARD
DefGtwy_4_ETH
15805
WORD
Y
RW Default Gateway (part 4)
0 … 255
1
num.
ETHERNET
ON BOARD
NetMsk_1_ETH
15806
WORD
Y
RW Net mask (part 1)
0 … 255
255
num.
ETHERNET
ON BOARD
NetMsk_2_ETH
15807
WORD
Y
RW Net mask (part 2)
0 … 255
255
num.
ETHERNET
ON BOARD
NetMsk_3_ETH
15808
WORD
Y
RW Net mask (part 3)
0 … 255
255
num.
ETHERNET
ON BOARD
NetMsk_4_ETH
15809
WORD
Y
RW Net mask (part 4)
0 … 255
0
num.
RW Primary DNS server (part 1)
0 … 255
194
num.
ETHERNET
ON BOARD
PriDNS_2_ETH
15811
WORD
Y
RW Primary DNS server (part 2)
0 … 255
25
num.
ETHERNET
ON BOARD
PriDNS_3_ETH
15812
WORD
Y
RW Primary DNS server (part 3)
0 … 255
2
num.
ETHERNET
ON BOARD
PriDNS_4_ETH
15813
WORD
Y
RW Primary DNS server (part 4)
0 … 255
129
num.
ETHERNET
ON BOARD
SecDNS_1_ETH
15814
WORD
Y
RW Secondary DNS server (part 1)
0 … 255
194
num.
ETHERNET
ON BOARD
SecDNS_2_ETH
15815
WORD
Y
RW Secondary DNS server (part 2)
0 … 255
25
num.
ETHERNET
ON BOARD
SecDNS_3_ETH
15816
WORD
Y
RW Secondary DNS server (part 3)
0 … 255
2
num.
ETHERNET
ON BOARD
SecDNS_4_ETH
15817
WORD
Y
RW Secondary DNS server (part 4)
0 … 255
130
num.
ETHERNET
ON BOARD
EnableDHCP_ETH
15819
WORD
Y
RW Enable DHCP
0 … 1
(False, True)
False
flag
1 = English
2 = French
3 = German
4 = Spanish
0 … 65535
0
num.
Display
Par_ContrLCD
15723
WORD
Y
RW LCD Contrast
Allows adjustment of the LCD display contrast.
0 … 64
30
Num.
Display
Par_BackLightTime
15724
WORD
RW Backlight switch-on time
Allows adjustment of LCD display switch-on time.
0 … 3600
10
sec
Buzzer
Buzzer_Mode
15990
WORD
RW
Buzzer mode
0= always off
1= beep per key
0 … 1
0
num.
0= HMI remote 1
1= HMI remote 2
2= HMI remote 3
3= HMI remote 4
4= HMI remote 5
5= HMI remote 6
6= HMI remote 7
7= HMI remote 8
8= HMI remote 9
9= HMI remote 10
10 = not used
11= Local HMI
0 … 11
11
num.
NOTE: if HmiList_Current=11 the following folders/parameters are NOT USED
HMI remote 1
HmiList_ID_1
15821
WORD
RW HMI remote 1 navigation ID list
0 ... 254
0
num.
HMI remote 1
HmiList_Res_1
15833
WORD
RW
HMI remote 1 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 1
HmiList_Addr_1
15845
WORD
RW HMI remote 1 navigation resource address for CAN, RTU and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 1
HmiList_Addr_2
15846
WORD
RW HMI remote 1 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 1
HmiList_Addr_3
15847
WORD
RW HMI remote 1 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 1
HmiList_Addr_4
15848
WORD
RW HMI remote 1 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 1
HmiList_File_1
15893
15 byte
RW HMI remote 1 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 2
HmiList_ID_2
15822
WORD
RW HMI remote 2 navigation ID list
0 ... 254
0
num.
HMI remote 2
HmiList_Res_2
15834
WORD
RW
HMI remote 2 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 2
HmiList_Addr_1
15849
WORD
RW HMI remote 2 navigation resource address for CAN, RTU and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 2
HmiList_Addr_2
15850
WORD
RW HMI remote 2 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 2
HmiList_Addr_3
15851
WORD
RW HMI remote 2 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 2
HmiList_Addr_4
15852
WORD
RW HMI remote 2 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 2
HmiList_File_2
15901
15 byte
RW HMI remote 2 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 3
HmiList_ID_3
15823
WORD
RW HMI remote 3 navigation ID list
0 ... 254
0
num.
HMI remote 3
HmiList_Res_3
15835
WORD
RW
HMI remote 3 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 3
HmiList_Addr_1
15853
WORD
RW HMI remote 3 navigation resource address for CAN, RTU and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 3
HmiList_Addr_2
15854
WORD
RW HMI remote 3 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 3
HmiList_Addr_3
15855
WORD
RW HMI remote 3 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 3
HmiList_Addr_4
15856
WORD
RW HMI remote 3 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 3
HmiList_File_3
15909
15 byte
RW HMI remote 3 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 4
HmiList_ID_4
15822
WORD
RW HMI remote 4 navigation ID list
0 ... 254
0
num.
HMI remote 4
HmiList_Res_4
15836
WORD
RW
HMI remote 4 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 4
HmiList_Addr_1
15857
WORD
RW HMI remote 4 navigation resource address for CAN, RTU and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 4
HmiList_Addr_2
15859
WORD
RW HMI remote 4 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 4
HmiList_Addr_3
15859
WORD
RW HMI remote 4 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 4
HmiList_Addr_4
15860
WORD
RW HMI remote 4 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 4
HmiList_File_4
15917
15 byte
RW HMI remote 4 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 5
HmiList_ID_5
15825
WORD
RW HMI remote 5 navigation ID list
0 ... 254
0
num.
HMI remote 5
HmiList_Res_5
15837
WORD
RW
HMI remote 5 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 5
HmiList_Addr_1
15861
WORD
RW HMI remote 5 navigation resource address for CAN, RTH and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 5
HmiList_Addr_2
15862
WORD
RW HMI remote 5 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 5
HmiList_Addr_3
15863
WORD
RW HMI remote 5 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 5
HmiList_Addr_4
15864
WORD
RW HMI remote 5 navigation resource address for TCP
(IP part 4)
0 ... 255
0
num.
HMI remote 5
HmiList_File_5
15925
15 byte
RW HMI remote 5 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 6
HmiList_ID_6
15826
WORD
RW HMI remote 6 navigation ID list
0 ... 254
0
num.
HMI remote 6
HmiList_Res_6
15838
WORD
RW
HMI remote 6 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 6
HmiList_Addr_1
15865
WORD
RW HMI remote 6 navigation resource address for CAN, RTH and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 6
HmiList_Addr_2
15866
WORD
RW HMI remote 6 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 6
HmiList_Addr_3
15867
WORD
RW HMI remote 6 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 6
HmiList_Addr_4
15868
WORD
RW HMI remote 6 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 6
HmiList_File_6
15933
15 byte
RW HMI remote 6 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 7
HmiList_ID_7
15827
WORD
RW HMI remote 7 navigation ID list
0 ... 254
0
num.
HMI remote 7
HmiList_Res_7
15839
WORD
RW
HMI remote 7 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 7
HmiList_Addr_1
15869
WORD
RW HMI remote 7 navigation resource address for CAN, RTU and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 7
HmiList_Addr_2
15870
WORD
RW HMI remote 7 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 7
HmiList_Addr_3
15871
WORD
RW HMI remote 7 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 7
HmiList_Addr_4
15872
WORD
RW HMI remote 7 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 7
HmiList_File_7
15941
15 byte
RW HMI remote 7 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 8
HmiList_ID_8
15828
WORD
RW HMI remote 8 navigation ID list
0 ... 254
0
num.
HMI remote 8
HmiList_Res_8
15840
WORD
RW
HMI remote 8 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 8
HmiList_Addr_1
15873
WORD
RW HMI remote 8 navigation resource address for CAN, RTU and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 8
HmiList_Addr_2
15874
WORD
RW HMI remote 8 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 8
HmiList_Addr_3
15875
WORD
RW HMI remote 8 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 8
HmiList_Addr_4
15876
WORD
RW HMI remote 8 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 8
HmiList_File_8
15949
15 byte
RW HMI remote 8 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 9
HmiList_ID_9
15829
WORD
RW HMI remote 9 navigation ID list
0 ... 254
0
num.
HMI remote 9
HmiList_Res_9
15841
WORD
RW
HMI remote 9 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 9
HmiList_Addr_1
15877
WORD
RW HMI remote 9 navigation resource address for CAN, RTU and TCP
(IP part 1)
0 ... 255
0
num.
HMI remote 9
HmiList_Addr_2
15878
WORD
RW HMI remote 9 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 9
HmiList_Addr_3
15879
WORD
RW HMI remote 9 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 9
HmiList_Addr_4
15880
WORD
RW HMI remote 9 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 9
HmiList_File_9
15957
15 byte
RW HMI remote 9 navigation file (DOS 8.3 uppercase format)
********
string
HMI remote 10
HmiList_ID_10
15830
WORD
RW HMI remote 10 navigation ID list
0 ... 254
0
num.
HMI remote 10
HmiList_Res_10
15842
WORD
RW
HMI remote 10 navigation resource type
1=RTU (RS485 Modbus RTU)
2=TCP (Modbus TCP)
3=CAN (CANopen)
1 … 3
3
num.
HMI remote 10
HmiList_Addr_1
15881
WORD
RW HMI remote 10 navigation resource address for CAN, RTU and
TCP (IP part 1)
0 ... 255
0
num.
HMI remote 10
HmiList_Addr_2
15882
WORD
RW HMI remote 10 navigation resource address for TCP (IP part 2)
0 ... 255
0
num.
HMI remote 10
HmiList_Addr_3
15883
WORD
RW HMI remote 10 navigation resource address for TCP (IP part 3)
0 ... 255
0
num.
HMI remote 10
HmiList_Addr_4
15884
WORD
RW HMI remote 10 navigation resource address for TCP (IP part 4)
0 ... 255
0
num.
HMI remote 10
HmiList_File_10
15965
15 byte
RW HMI remote 10 navigation file (DOS 8.3 uppercase format)
********
string
MODELS AND ACCESSORIES
7.1
Models
----------------
(*) low voltage SELV: SAFETY EXTRA LOW VOLTAGE
(**) NOT INCLUDED - low voltage SELV: SAFETY EXTRA LOW VOLTAGE
/C indicates presence of RTC (Real Time Clock)
Accessories for Wall Mounting
Contact the Eliwell Sales Department for wall-mounting accessories.
Make 4 holes of diameter 4.2mm in the wall at the specified spacing, to fix the backplate. Alternatively use the two side
slots, one at the bottom and one at the top, under the corresponding break-open removable doors, preventing the
opening of holes in walls with recessed-wall wiring.
Make all the necessary connections, then insert the EVP terminal (without front) in the backplate, which serves as a panel,
following the instructions for panel mounting (see Mounting chapter).
Accessories for Wall Mounting
Code EVA00WMRC0000
Backplate for wall mounting
Model
Mounting
Dimensions
Display
On-board
Analogue
Inputs (*)
Remote
Analogue
Inputs
(**)
Power supply
Serials
EVP3300/C
Panel*
160x96x10mm
LCD
backlit
1x NTC
1xNTC/DI
1x4…20mA/
0-5V/
0..10V
24V~/c - 48Vc
CANopen
RS485
ETHERNET
TCP/IP
EVP3300/C/RH
Panel*
160x96x10mm
LCD
backlit
1 xNTC
1 x%RH
1xNTC/DI
24V~/c - 48Vc
CANopen
RS485
ETHERNET
TCP/IP
Dimensions of wall-mounting backplate
7.2
Accessories
Note: the photos are intended to show the accessories and are by way of example only. The dimensions shown in the
figures are not to scale.
Name
Code
Description
Documentation /
Notes
SAR0RA00X701
USB/485 MINI KIT converter
+ USB cable
Converters
and cables
EVA00USCA0000
USB/CAN converter
Cable
Contact Eliwell
Sales Department
Ethernet cable
TF111202
230V~/24V 25VA transformer
Note: cable must be no longer
than 10m
Transformer
TF111205
230V~/24V 35VA transformer
Note: cable must be no longer
than 10m
Mounting on DIN rail
59
83
90
160
80
57
90
R 1.5
mm
145
27
Ethernet
NTC probe NK103C1R1, 4m
Extended range
(polyester, 2-wire cable) IP65;
Instruction Sheet
SN8D6L4002 GB-I
SN691150
NTC probe 103AT, 1.5m (plastic
cap, 2-wire cable);
Instruction Sheet
SN8D6L4002 GB-I
Temperature
probes
SN8DED11502C0
NTC temperature probe 5X20
1.5m TPE IP68
Instruction Sheet
SN8T6H1502 GB-I
Name
Code
Description
Documentation /
Notes
Pressure
transducers
(1)
Pressure transducer 4…20mA
male or female connector
Range from -0.5/7bar to 0/50 bar
Depending on model
Instruction Sheet
9IS64173
EWPA
EN-IT-ES-DE-FR-RU
Code
Description
Documentation /
Notes
Software Tools
Contact Eliwell
Sales Department
FREE Studio
Contact Eliwell Sales
Department
Demo Case
VAL00033K
Demo case
FREE Evolution
Backplate
EVA00WMRC0000
Backplate for wall mounting
(1) Various items available. Contact the Sales Department
(2) Various lengths can be requested
GENERAL NOTES:
Eliwell can also supply a variety of different NTC probes depending on the cable type (PVC or silicon) and
length.
BIOS parameters ............................................................17
BRIDGE ............................................................................13
C
CAN......................................................................................6
CAN connection example (Field)................................10
CANopen network connection example...................12
COM Setting....................................................................19
Connections..................................................................... 10
Cross references..............................................................3
D
Date and time.................................................................18
DIA Menu.........................................................................16
DIAGNOSTICS menu...................................................... 17
Disclaimer........................................................................ 15
Display.............................................................................. 15
E
ELECTRICAL CONNECTIONS...........................................6
ETHERNET...........................................................................7
Example: RS485 connection (Field)............................10
Example: RS485 connection with FREE Smart
network........................................................................11
F
First power on ................................................................. 17
FREE WEB........................................................................13
G
General description...........................................................3
General Technical Data ............................................ 14
General warnings..............................................................6
H
Highlighting icons:............................................................3
HMI Management ..................................................18; 19
HMI sel..............................................................................18
I
I/O features......................................................................14
Improper Use.................................................................15
INTRODUCTION................................................................ 3
K
Keys and LEDs..................................................................16
L
Language..........................................................................18
M
Mechanical dimensions.............................................15
MECHANICAL INSTALLATION ................................... 5
Models..............................................................................34
MODELS AND ACCESSORIES .......................................34
Models and Features ....................................................... 4
N
Note: for offset programming see the section on
Analogue Inputs in the Connections chapter......18
P
PARAMETERS...................................................................20
Permitted use...................................................................15
Power supply ...................................................................6
Pressure probes ..............................................................6
Probe values.....................................................................18
R
References.........................................................................3
Remote interface ............................................................18
RS485..................................................................................7
S
Serial connections ............................................................6
Serials...............................................................................15
Specifications:.................................................................4
T
Table of parameters.......................................................20
TECHNICAL DATA...........................................................14
Temperature probes.........................................................6
TFTP ..................................................................................13
Transformer .....................................................................15
U
USER INTERFACE.............................................................16
W
Wiring diagrams............................................................... 8
Eliwell Controls S.r.l.
Via dell’ Industria, 15 Zona Industriale Paludi
32010 Pieve d’ Alpago (BL) Italy
Telephone +39 0437 986 111
Facsimile +39 0437 989 066
Sales:
+39 0437 986 100 (Italy)
+39 0437 986 200 (other countries)
[email protected]
Technical helpline:
+39 0437 986 250
E-mail [email protected]
www.eliwell.com
FREE Panel
2012/05/
Cod: 9MA10046
© Eliwell Controls s.r.l. 2011-12 All rights
reserved.