Eliwell FREE Panel EVP 3300/C Installation Manual

Specifications

Brand: Eliwell
Category: Controller
Model: FREE Panel EVP 3300/C (Installation Manual)
File Type: PDF
File Size: —
Pages: 39

Read Online

Read the Eliwell FREE Panel EVP 3300/C Installation Manual online using the built-in PDF viewer.

Text of the manual

An Invensys Company

CONTENTS 1 Introduction............................................................................................................................................................. 3 1.1 General description ......................................................................................................................................................................... 3 1.1.1 Specifications: ..................................................................................................................................................................................................................................... 4 1.2 Models and Features....................................................................................................................................................................... 4 2 Mechanical Installation ......................................................................................................................................... 5 3 Electrical connections ........................................................................................................................................... 6 3.1 General warnings.............................................................................................................................................................................. 6 3.1.1 Power supply....................................................................................................................................................................................................................................... 6 3.1.2 Analogue Inputs-Probes................................................................................................................................................................................................................... 6 3.1.3 Serial connections.............................................................................................................................................................................................................................. 6 3.2 Wiring diagrams................................................................................................................................................................................ 8 3.3 Analogue inputs................................................................................................................................................................................ 9 3.4 Connections.....................................................................................................................................................................................10 3.4.1 Example: RS485 connection (Field).............................................................................................................................................................................................10 3.4.2 CAN connection example (Field) ................................................................................................................................................................................................10 3.4.3 Example: RS485 connection with FREE Smart network.........................................................................................................................................................11 3.4.4 CANopen network connection example...................................................................................................................................................................................12 4 Technical Data.......................................................................................................................................................14 4.1 General Technical Data.................................................................................................................................................................14 4.2 I/O features......................................................................................................................................................................................14 4.3 Display...............................................................................................................................................................................................15 4.4 Serials ................................................................................................................................................................................................15 4.5 Transformer.....................................................................................................................................................................................15 4.6 Mechanical dimensions ................................................................................................................................................................15 4.7 Permitted use..................................................................................................................................................................................15 4.8 Improper Use ..................................................................................................................................................................................15 4.9 Disclaimer.........................................................................................................................................................................................15 5 User Interface........................................................................................................................................................16 5.1 Keys and LEDs .................................................................................................................................................................................16 5.2 First power on.................................................................................................................................................................................17 5.3 DIAGNOSTICS menu......................................................................................................................................................................17 5.3.1 BIOS parameters...............................................................................................................................................................................................................................17 5.3.2 HMI Management ............................................................................................................................................................................................................................18 5.3.3 Probe values ......................................................................................................................................................................................................................................18 Note: for offset programming see the section on Analogue Inputs in the Connections chapter.......................................................................................18 5.3.3.1 Date and time ........................................................................................................................................................................................................................18 5.4 Remote interface............................................................................................................................................................................18 5.4.1 Language.............................................................................................................................................................................................................................................18 5.4.2  ........................................................................................................................................................................................................................................................ 18 5.4.3 HMI sel................................................................................................................................................................................................................................................ 18 5.4.3.1 COM Setting...........................................................................................................................................................................................................................19 5.4.3.2 HMI Management.................................................................................................................................................................................................................19 6 Parameters..............................................................................................................................................................20 6.1 Table of parameters......................................................................................................................................................................20 6.1.1 Table of parameters........................................................................................................................................................................................................................20 7 Models and Accessories......................................................................................................................................34 7.1 Models ..............................................................................................................................................................................................34 7.2 Accessories.......................................................................................................................................................................................35

To allow quick, easy reference, the guide has been designed with the following features:

References column: A column to the left of the text contains references to subjects discussed in the text to help you locate the information you need quickly and easily. Cross references: All words in italics are listed in the analytical index along with the page number where they are dealt with in more detail. In the "on-line" (computer) manual, the words in italics are "hyperlinks" (i.e. mouse-clickable links), connecting up the different parts of the manual and making it "navigable". Some text passages are marked by icons in the references column, which have the following meanings: Important! : highlights information of which an incorrect understanding can impact negatively on the system or result in risk to persons, instruments, data, etc.; users must read and take note of these sections. Note / highlight: indicates further information on the subject concerned that the user should take into account. Tip: a suggestion that could help the user to understand and make better use of the information provided. 1.1 General description The FREE Panel (EVP) is a fully programmable panel mounting solution with LCD display made by Eliwell, suitable for managing a wide range of HVAC/R and many other applications, from the simplest to the most complex. The EVP can be used as a system controller, with gateway functions; used in combination with the FREE Evolution and FREE Smart or third-party controllers it guarantees high performance in terms of memory, connectivity and user interface as well as straightforward programming, maintenance and servicing. The EVP is designed for panel mounting, and can also be wall-mounted using a special backplate, available as an accessory. Programming of the EVP is managed via the FREE Studio development tool, which makes it possible to quickly and reliably create and customise new programs for all types of application. The use of several different programming languages in accordance with IEC61131-3 standard (industrial control programming ), makes it possible to develop new algorithms or entire programmes totally unassisted, which can then be uploaded to FREE Evolution modules via PC, guaranteeing maximum confidentiality with appropriate security. The EVP can be used to:  manage a local menu created with the FREE Studio User Interface  manage up to 10 remote menus, created with the FREE Studio User Interface and uploaded from the respective FREE Evolution devices connected to the network  share network variables (binding) WEB functionalities The FREE Panel (EVP) also features WEB functionalities (the FREE Panel product is also designated FREE WEB) offering makers of machinery and systems integrators full remote access. Having a web-based connection in machines significantly reduces support and maintenance costs by minimizing call-out charges. End users also benefit, as they can monitor their own systems both locally and from distance, using the easy-to-understand graphics interface of any common browser via smartphone, tablet or PC. Main WEB functionalities  Web-based access.  Remote reading and support.  Local and remote system control, including alarms management.  Preventive and predictive maintenance.  Email alarm alerts.  Next generation system interface on PC, tablet and smartphone. References Cross references Highlighting icons:

FREE Panel EVP 3300/C is equipped with serial CAN, RS485 and ETHERNET, 3 inputs (1 on-board NTC + 1 remote

configurable NTC/DI +1 remote current/voltage configurable). FREE Panel EVP 3500/C/R is equipped with serial CAN, RS485 and ETHERNET, 3 inputs (1 on-board humidity module + 1 on-board NTC + 1 remote configurable NTC/DI) . The EVP comes with a built-in 128x64px graphical user terminal. - - - 24V~/c or 48Vc power supply. 1.2 Models and Features - -> See Appendix A - Models and Accessories, and Technical Data section.

IMPORTANT! Always make sure the device is switched OFF before touching connections.

All operations must be carried out by qualified personnel. Do not mount devices in extremely damp and/or dirt-laden areas; they are designed for use in places with ordinary or normal levels of contamination. Make sure the area near the cooling slots is ventilated. Mounting the FREE Panel (EVP) Designed for panel mounting. Make a 138x68mm hole. Remove the front panel (figure 1) and make 4 holes in the panel that the controller is to be mounted on (Figure 2, points A/B/C/D) or two holes (Figure 2, points E/F) of dia. 2.7 mm at the specified spacing (Figure 2). Insert the device, fixing it with the screws. Press the front of the remote terminal to close. Figure 1 Cut out EVP Figure 2 Cut out EVP 68 138 150 90 2.7 (x 6) 84 A B D C E F

Before proceeding with any operation, make sure the device is connected to a suitable external transformer. The

following rules must be followed when connecting cards to each other and to the application:  Loads that exceed the maximum limits stated in this manual must not be applied to outputs.  When connecting loads, follow the circuit diagrams carefully.  To avoid unwanted couplings, wire all SELV (safety extra voltage) users separately from high voltage users. IMPORTANT! Make sure the appliance is switched off before working on electrical connections. Operations must be carried out by skilled personnel. To ensure proper connections, comply with the following:  Power supplies other than those specified can seriously damage the system.  Select cables of suitable section for the terminals used  Separate the cables of probes and digital inputs from inductive loads and high voltage connections to prevent any electromagnetic interference. Do not place probe signal leads near other electrical equipment (switches, meters, etc.)  Make connections as short as possible and do not wind them around electrically connected parts.  To avoid electrostatic discharges, do not touch the electronic components on printed circuit boards.  The device must be connected to a suitable transformer that complies with the specifications indicated in the Technical Data chapter. 3.1.1 Power supply Important! Make sure that the power supply is of the correct voltage for the instrument. 3.1.2 Analogue Inputs-Probes Probes have no connection polarity and can be extended using a normal two core cable (note that the extension of the probes influences the electromagnetic compatibility (EMC) of the instrument: take great care with the wiring). Important! Pressure probes have a specific connection polarity, which must be observed. Signal leads (temperature/pressure probes, digital inputs, RS-485/CAN-BUS serials and the electronic supply) must be routed separately from power cables. Use probes supplied by Eliwell. Contact Eliwell sales department for parts availability. 3.1.3 Serial connections  On-board CAN as standard  On-board RS485 as standard  On-board ETHERNET serial as standard Pay special attention when connecting serial lines: Do not connect instruments that communicate using RS485 serial to CAN terminals, or CAN instruments to RS485 terminals. CAN NOTE 1  Use a shielded and "twisted pair" cable with two 0.5mm2 conductors, plus braiding (ideally Belden cable model 3105A (characteristic impedance 120 Ohms) with PVC sleeve, 2 conductors plus braid, 22 AWG, nominal capacity between conductors 36pF/m, nominal capacity between conductor and shielding 68pF/m).  Always follow regulations applicable to the routing and connection of cables. Make certain that data transmission circuits are properly separated from power lines.  For connections over longer distances, it is better to end the line with resistors on both ends, inserting the two R TERM jumpers (available on the terminal strip beside the CAN serial as the default factory configuration). NOTE 2 The maximum distance depends on the baud setting. Kb/s (Kbaud) On-board CAN 50 Kbaud 1000m 125 Kbaud 500m 250 Kbaud 250m 500 Kbaud 60m NOTE 3 5-way terminal strip:  3-way ( “GS“, “H and “L”) serial CAN  2-way POWER supply Temperature probes Pressure probes CAN

INSTALLING THE RS-485 NETWORK

NOTE 1 Use a shielded and "twisted pair" cable with two 0.5mm2 conductors, plus braiding (ideally Belden cable model 8762 with PVC sleeve, 2 conductors plus braid, 20 AWG, nominal capacity between conductors 89pF/m, nominal capacity between conductor and shielding 161pF/m). See EN 50174 standard on IT cabling for indications on how cables should be routed. Make certain that data transmission circuits are properly separated from power lines. An RS-485 network up to 1200m in length with a maximum of 256* devices can be connected straight to the controller. *Note: example of Evolution Modbus Slave with single Master supervisor. This length can be extended and the number of devices for each channel increased using appropriate repeater modules. NOTE 2 Single terminal strip with 3 conductors: use all 3 conductors (“+”, “-“ for the signal and “GS” for the braid). NOTE 3 Attach the 120 (Ohm) 1/4W resistors between the "+" and "-" terminals of the interface and the last controller in each branch of the network. NOTE 4 Maximum settable speed 57600 baud. Higher speeds are envisaged for local connection to FREE Studio Device and tests. ETH The Ethernet connection allows the FREE PANEL to communicate on an Ethernet network using TCP/IP protocol. The connection allows:  connection of different controllers and/or applications exchanging variables and/or parameters (network).  connection of a supervision system using Modbus TCP/IP protocol  connection of an IEC 61131-3 Free Studio development system NOTE: The Ethernet connector shield is internally connected to the earth of the instrument and therefore to the reference of the input and output channels. RS485 ETHERNET

24Va/c - 48Vc p o w

er s u p p l y Pin POWER Vout on EVD/EVC Max. distance 10m EVP- EVD/EVC CAN GS H L Isolated CAN serial GS ground serial isolated from G R TERM termination resistors for CAN cross – cabling: incorrect cabling irreversibly damages EVP and FREE Evolution RS485 GS - + Isolated RS485 serial GS ground serial isolated from G Apply 120 Ohm terminal resistors Ethernet ETHERNET serial Built-in AI1 NTC Sensor On-board NTC sensor AI2 Remote Probes G NTC, D.I. remote Ground GND Probe not included AI3 Remote Probes G 4...20mA/0-10V/0-5V Ground GND EVP3300/C Probe not included 12V External power supply Built-in AI4 RH Sensor On-board RH% sensor EVP3500/C/RH RS485 CAN + - GS 24 Va/c 48 Vc RS485 CAN GS H L POWER Ethernet Remote Probes AI2 AI3 G example of Transducer AI3 G +12V External Power Supply AI2 G Digital input AI2 G NTC RTERM EVP3300/C AI1 NTC Sensor Built-in CAN GS H L POWER OUT POWER CAN R TERM R TERM RS485 GS - + RS485 FREE EVOLUTION EVD ● EVC AI1 AI2 AI3 Remote Probes Built-in Probe WARNING WHILE CABLING CAN: max distance depending on baud rate POWER : max distance 10m RS485 CAN + - GS 24 Va/c 48 Vc RS485 CAN GS H L POWER Ethernet Remote Probes AI2 AI3 G AI2 G Digital input AI2 G NTC RTERM EVP3500/C/RH AI4 RH Sensor Built-in AI1 NTC Sensor Built-in CAN GS H L POWER OUT POWER CAN R TERM R TERM RS485 GS - + RS485 FREE EVOLUTION EVD ● EVC AI1 AI2 AI4 Remote Probe Built-in Probes WARNING WHILE CABLING CAN: max distance depending on baud rate POWER : max distance 10m

Inputs can be configured as specified in the table below.

Values Parameter Description 0 1 2 3 4 5 Cfg_AI1 Type of input analogue AI1 NTC probe (NK103) Probe configured as voltage- free digital input NTC probe (103AT-2) - - - Cfg_AI2 Type of input analogue AI2 NTC probe (NK103) Probe configured as voltage- free digital input NTC probe (103AT-2) - - - Cfg_AI3 Type of input analogue AI3 - - - 4-20 mA 0-10 V 0-5 V Parameter Range Description FullScaleMin_AI3 -9999…+9999 Analogue input AI3 start of scale value FullScaleMax_AI3 -9999…+9999 Analogue input AI3 full scale value The temperature and humidity measurement, as well as the corresponding precisions and tolerances, refer to the application point of the probes inside the instruments. If these same measurements are to be referred to air conditions outside of the instrument, e.g. ambient measurements, account must be taken of offset (differential) parameters that depend on the installation and usage conditions of the instrument itself. The differentials e.g. Calibration parameters that can be set are for on-board (built-in) sensors, 'compensation' parameters are also available Factory values for these offsets assume a typical installation with wall mounted backplate in a non-ventilated environment and with the display backlighting mainly OFF. In these conditions the following calibration values are obtained: Compensation_AI1 = -12.0 °C Compensation_AI4 = -10.5 °C If the usage conditions require the backlight to be mainly ON, the values must be modified as follows: Compensation_AI1 = -15.0 °C Compensation_AI4 = -13.0 °C For other mounting conditions, it is advisable to carry out calibration during installation, checking the temperature and relative humidity differences between the external air and the internal probes and if necessary correcting the parameters Compensation_AI1/ Compensation_AI4 In any case it is possible to achieve a precision of +- 1°C on the temperature measurement and +- 3%RH on the relative humidity measurement. Parameter Description Unit of Measure range Calibration_AI1 Analogue input AI1 differential °C/10 or °F/10 -180 ... 180 Calibration_AI2 Analogue input AI2 differential °C/10 or °F/10 -180 ... 180 Calibration_AI3 Analogue input AI3 differential -1000 ... 1000 Calibration_AI4 Analogue input AI4 differential -1000 ... 1000 Parameter Description Unit of Measure range Compensation_AI1 Internal compensation AI1 difference between external air temperature and measurement read by NTC sensor AI1 °C/10 or °F/10 -1000 ... 1000 Compensation_AI4 Internal compensation AI4 difference between external temperature and T measurement read by RH sensor AI4 (this temperature is used to calculate the relative humidity based on psychrometric charts) °C/10 or °F/10 -1000 ... 1000

Example: RS485 connection (Field)

 1 FREE Panel EVP  Max 127 FREE Evolution EVE expansion modules connected in RS485 o EVP is in Modbus RTU Master mode o EVEs are in Modbus RTU Slave mode 3.4.2 CAN connection example (Field)  1 FREE Panel EVP  Max 12 FREE Evolution EVE expansion modules connected in CAN EVP EVE 1 485 - 485 GS 485 + 485 - 485 GS 485 + POWER IN 24Va/c 48Va EVE 127 max 127 Switch/Router Ethernet FREE Studio / Supervisor EVE CAN GS CAN H CAN L 24Va/c 48Va EVP POWER IN max 12 EVE

Example: RS485 connection with FREE Smart network

 1 FREE Panel EVP  Max 127 FREE Evolution EVD/EVC or FREE Smart or Eliwell and/or third-party instruments equipped with RS485 serial o EVP is in Modbus RTU Master mode o All devices equipped with RS485 are in Modbus RTU Slave mode (including the FREE Evolution modules)  CAN network – see CAN connection example

CANopen network connection example

 1 FREE Panel EVP  Max 10 FREE Evolution EVD/EVC  CAN network – see CAN connection example (Field) HMI menu EVP can be equipped with its own menu (named Network menu) In this case EVP is programmed with the network menu, which can read variables present in the Evolution controller network EVP can operate from the terminal of the individual controllers and download up to 10 remote menus from the respective Evolution controllers In this case the remote menu allows 'local' navigation of the individual Evolution controller PLC The variables of the various controllers are shared (bound together) A PLC present on EVP can use variables present in the network and share its own variables with other PLCs present on the respective Evolution controllers EVD 1 EVC 2 CAN GS CAN H CAN L CAN GS CAN H CAN L POWER POWER CAN POWER OUT 24Va/c 48Va EVC 10 EVP Binding max 10 EVE 1 EVE 127 485 GS 485 - 485 + 485 GS 485 - 485 + 485 GS 485 - 485 +

The FREE Panel product is also designated FREE WEB

The Ethernet connection also allows communication using HTTP protocol, i.e. access to a Web Server contained in FREE Evolution. FREE WEB FREE Studio allows the creation and management of web pages internally of FREE WEB, i.e. a veritable website in miniature. WEB functionalities allow complete local or remote access by way of an ordinary browser. Thanks to the web connection, the system provides remote reading and support and remote diagnostics services, as well as e-mail alarm alerts. Note. Connection to FREE WEB remains possible by way of FREE Studio. NOTE: refer to the section on Parameters / ETHERNET PASSIVE PLUG-IN folder BRIDGE FREE Studio allows monitoring of FREE Smart tools or third party tools, typically Modbus/RTU slaves, where FREE WEB (or FREE Evolution with Plug-In ETH) is the Master Modbus/RTU. In a FREE Studio project, more exactly, FREE WEB is used as a Modbus/TCP to Modbus/RTU protocol conversion element for Modbus 0x03 and 0x10 commands. E.g. from FREE Studio, set the connection with FREE Smart as Modbus/TCP, inserting the FREE WEB IP address and the Modbus/RTU address of the Smart slave. TFTP (Trivial File Transfer Protocol) Note. TFTP (Trivial File Transfer Protocol) can also be enabled for file transfer between PC and controller on an Ethernet network. FREE WEB BRIDGE TFTP

General Technical Data

Standard Min. Max. Supply voltage* 24V~/c ±20% or 48Vc ±20% 21V 60V Power supply frequency 50Hz/60Hz --- --- Power consumption 5W Insulation class 2 --- --- Ambient operating temperature 25°C -10°C +55°C Ambient operating temperature of EVK1000 terminal 25°C -5°C +55°C Ambient operating humidity (non-condensing) 30% 10% 90% Storage temperature 25°C -20°C +85°C Ambient storage humidity (non-condensing) 30% 10% 90% * powered via FREE Evolution EVD/EVC or directly via a transformer Note: power cable must not be longer than 10m Classification The product meets the requirements of the following European Community Directives Directive 2006/95/EC Directive 89/108/EC and complies with the following harmonized regulations EN 60730-2-6 / EN 60730-2-9 / EN 60730-1 Use in terms of construction, as an independently mounted temperature-sensitive automatic electronic controller Mounting on DIN Omega bar support Type of action 1.B Pollution class 2 (normal) Over voltage category II Nominal pulse voltage 2500V Digital outputs refer to the label on the device Fire resistance category D Software class and structure A Type of disconnection or suspension for each circuit Microswitch disconnection PTI of materials used for insulation PTI 250V Period of electrical stress on the insulating parts Long period 4.2 I/O features Type and Label Analogue inputs probe Description Resolution Accuracy Measurement range Impedance 3300 /C 3500 /C /RH AI1 On- board NTC 0.1°C/°F 0.5% f.s + 1 digit 10KΩ x x NTC 103AT 0.1°C/°F 0.5% f.s + 1 digit –50…+110 °C (-58...230°F) 10KΩ NTC NK103 0.1°C/°F 0.5% f.s + 1 digit -40…+150 °C (-40...302°F) 10KΩ AI2 configurable Remote NOT included D.I.** 20KΩ x x 4...20mA 1 digit 1% f.s +1 digit 0…1000 100Ω 0-5V* 1 digit 1% f.s +1 digit 0…1000 21KΩ AI3 configurable Remote NOT included 0..10V 1 digit 1% f.s +1 digit 0…1000 21KΩ x AI4 On- board On-board %RH input 0.01%RH (0%=0pt, 100% = 1000pt) ±3% [20...80%] ±5% …] [… elsewhere 0-100 %RH x *50mA maximum current @5V; **Clean contact. Note: Also see Electrical Connections chapter / Analogue Inputs paragraph for instructions on offsets and calibrations

backlit with LEDs +

 3 LEDs Note: LED and backlighting can be controlled from IEC application Protection rating: The single-mould plastic front cover allows for water resistant panel mounting that is comparable to IP65 protection. Display: Monochromatic LCD graphic display 128x64px backlit with LEDs Container: backplate + frame in PC+ABS UL94 V-0 plastic resin, front cover in transparent polycarbonate, polyester membrane keys 4.4 Serials Serial Description Notes CAN Open opto-isolated serial CAN max50m@500kpbs 200m@125kpbs Note: 2 jumpers available for CAN terminal resistance RS-485 Opto-isolated RS-485 Modbus RTU serial Pay special attention when connecting serial lines: do not cable RS485 in CAN port or vice versa ETHERNET Modbus TCP/IP ETHERNET port Pack includes MACADDRESS, in barcode and 12-digit alphanumeric format 4.5 Transformer The instrument must be connected to a suitable current transformer with the following features:  Primary voltage: Depending on requirements of device and/or country of installation  Secondary voltage: 24V~/c - 48Vc ±20%  Power supply frequency V~: 50/60Hz  Power: 5W min. 4.6 Mechanical dimensions Length (L) mm Depth (d) mm Height (H) mm Notes Space required 160 10 96 Hole for panel mounting 68 / 138 (+0.2 mm / -0.1 mm) 4.7 Permitted use For safety reasons, the device must be installed and used according to the instructions provided. In particular, parts carrying dangerous voltages must not be accessible in normal conditions. The device must be adequately protected from water and dust with regard to the application, and must only be accessible using tools (with the exception of the front panel). The device is suitable for use in household and/or similar air conditioning appliances or installations and has been tested for safety aspects in accordance with harmonized European reference standards. 4.8 Improper Use Any use other than that expressly permitted is prohibited. The relay contacts supplied are of the functional type and subject to fault (since they are electronically controlled they are prone to short-circuiting or remaining open). Any protection devices specified in product standards or suggested by common sense for obvious safety requirements must be installed externally to the device. Eliwell is not liable for damage caused by:  Unspecified installation/use and, in particular, in contravention of the safety requirements of established legislation or specified in this document;  Use on equipment which does not provide adequate protection against electrocution, water and dust in the actual installation conditions;  Use on equipment in which dangerous components can be accessed without the use of specific tools;  Installation/use on equipment which does not comply with established legislation and standards. 4.9 Disclaimer This document is the exclusive property of Eliwell Controls srl and may not be reproduced or circulated unless expressly authorized by Eliwell Controls srl itself. Every care has been taken in preparing this document; however, Eliwell Controls srl cannot accept liability for any damage resulting from its use.

The interface, comprising the front cover of the controller, allows you to perform all operations needed to use the device.

EVP 5.1 Keys and LEDs The LEDs can be programmed from the IEC application. The keys can be programmed from the IEC application. By default, the device displays a short menu containing the following default settings. Key Key Press once (press and release) 1 UP  Scroll up  Return to previous page (e.g. 2/10 3/10)  Increase / modify a value  Go to the next label 2 OK  Scroll down  Move to next level/menu (open folder, subfolder, parameter, value)  Enter/exit edit mode  Confirm operation 3 >  Moves cursor to right in Edit Mode 4 DOWN  Scroll down  Move to the next page (e.g. 1/102/10)  Decrease / modify a value  Go to previous label 5  Exit  Exit menu page / go back to previous menu  Move cursor to left in Edit Mode  (press and hold) Exit Edit Mode without saving any changes EVP is factory configured with a default DIAGNOSTICS (DIA) menu that appears when the instrument is powered on. After uploading of an IEC application and/or a HMI menu from FREE Studio, the main display consists of the application menu created with FREE Studio Interface. In which case, to open the DIAGNOSTICS menu proceed as follows: Key combination Prolonged press (press and hold for about 3 seconds) DOWN 4+5  Exit Open DIAGNOSTICS menu To return to the IEC application menu open the ‘HMI Management’ page, select  and press the OK key See Remote Interface paragraph DIA Menu

First power on

When the instrument is powered up for the first time, a few summary pages are displayed showing system status (SYSTEM INFO) SYSTEM INFO HW BIOS DATE BOOT EEPROM NOR FLASH OK NAND FLASH OK SDRAM OK BATRAM OK RTC OK The system will also search for the PLC application and the local menu… If present, the menu will appear on the display PLC searching … HMI searching … CON loaded 5.3 DIAGNOSTICS menu The DIAGONISTICS menu, native to EVP, is used to manage system parameters (BIOS parameters), remote interfaces (HMI) and to display I/O values and clock The DIA menu can be displayed in 5 languages: English, Italian, German, Spanish and French. To change the default language, open BIOS Parameters > Display EVP BIOS parameters HMI Management Probe values Date and time 5.3.1 BIOS parameters Parameter configuration menu. See Parameters chapter. Note: This menu is depopulated with respect to the parameters table contained in the corresponding chapter and in the FREE Studio device Language change example BIOS parameters Display Buzzer CAN Display 1/3 Language Italiano BIOS parameters  < OK key > Display 1/3  < OK key > Edit Mode < UP/DOWN key > select language < OK key > <  key > Display 1/3 Language English See parameter Display/Hmi_Language

See Remote Interface paragraph

5.3.3 Probe values Shows input values (read only) EVP has 3 inputs. Example EVP3500/C/RH Probes values 1/3 Probes values 2/3 Probes values 3/3 Internal NTC External NTC Humidity sensor 27.3 - - - - - - - - - - - - - - 43.38 °C, °F °C, °F RH% Note: for offset programming see the section on Analogue Inputs in the Connections chapter 5.3.3.1 Date and time Shows time (HH : MM : SS) and date (DD / MM / YY) of the internal clock Date and time 14 : 45 : 45 20 / 07 / 11 Update To edit the value press OK. Select the value that you want to modify Press the OK key to enter Edit Mode. Use the UP and DOWN keys to modify value. Confirm with the OK key Select ‘Update’ and press OK to update the clock Date and time 16 : 50 : 56 20 / 07 / 11 Update 5.4 Remote interface EVP Language: 0  HMI sel: Network COM setting HMI Management 5.4.1 Language This section is for setting the language of the remote menu, defined from the FREE Studio User Interface The number of languages and the order are established by the corresponding application/menu See parameter HMI Management/Hmi_Language 5.4.2  To return to the menu of the IEC application, move the cursor onto this symbol and press the OK key See HMI sel 5.4.3 HMI sel This section is for setting the menu to be shown on the display By default HMI menus are NOT present (only the DIA menu is available) Network: this is the EVP ‘local’ menu (local HMI) rem1…rem10: menus located on max 10 Evolution devices connected to the network that can be ‘uploaded’ to EVP EVP EVP EVP HMI sel: Network HMI sel: rem1 … HMI sel: rem10

To move from one page to the next press the UP and DOWN keys

After selecting the desired menu move the cursor onto  to view the menu Launch remote page Please Wait If OK the display will show the selected menu (IEC application) If the menu is not present, the following screen appears Warning Upload failed Press OK 5.4.3.1 COM Setting This read-only page shows the configuration of the EVP serial ports EVP CAN : 1 . 500000 485s : 1 . 38400.P81 ETH : 010.000.000.100 5.4.3.2 HMI Management This page shows the configuration of the 10 remote pages EVP 1/10 EVP 1/10 EVP 10/10 File: HMIREM.KBD    Id: 0  Id: 0  … Id: 0  Com: CAN Com: CAN Com: CAN Addr: 125 Addr: 000 Addr: 000 From these pages it is possible to ‘launch’ (run) the corresponding menu – if present Move the cursor onto  and press the OK key Note: it will not be possible to launch the local (network) menu from this section Note: in the example only one remote page is present To ‘upload’ a remote page use  After selecting the desired menu move the cursor onto  to view the menu Upload remote page Upload page? The process cannot be interrupted Cancel OK Press OK to upload or any other key to cancel Upload remote page Uploading…  80% Note: the upload may take up to a minute If there are no data to upload, the following screen displays Attenzione There are no remote pages on the card Press OK

User-parameterization renders the FREE Panel EVP fully configurable.

Parameters can be changed using:  Keys on the EVP front panel  PC and FREE Studio software The following sections provide a detailed analysis of each parameter, divided into categories (folders). 6.1 Table of parameters The following table contains all the device configuration parameters available in FREE Studio Device and in the DIAGNOSTICS (DIA) / BIOS Parameters menu Description of columns: This indicates the label of the FREE Studio Device folder containing the parameter in question A group of these parameters is available on the LCD display in the DIAGNOSTICS (DIA) menu Refer also to the following table: (x) if present (loaded to EVP) The local menu - if present (uploaded to EVP) - is defined with the Network label This indicates the label used to display the parameters Indicates the address of the modbus register containing the resource to be accessed. Indicates whether the device MUST be rebooted after the parameter has been changed.  Y=YES the device MUST be rebooted to save the change.  N=NO the device DOES NOT need to be rebooted after changing the parameter Indicates if resources are read/write, read-only or write-only: R The resource is read-only W The resource is write-only RW The resource can be both read and written to Indicates the size of the data in bits. When the field indicates “-1”, the value read by the register requires conversion, because the value represents a number with a sign. In other cases the value is always positive or null. To carry out the conversion, proceed as follows:  If the value in the register is between 0 and 32.767, the result is the value itself (zero and positive values)  If the value in the register is between 32.768 and 65.535, the result is the value of the register – 65.536 (negative values) Describes the interval of values that can be assigned to the parameter. It can be correlated with other instrument parameters (indicated in the parameter label). Indicates the factory setting for the standard model of the instrument. Unit of measure for values converted according to the rules indicated in the CPL column The unit of measure shown is an example only, as it may change depending on the application (e.g. parameters with a U.M. in °C/bar could also have %RH) 6.1.1 Table of parameters (See next page) FOLDER FOLDER EVP EVP DIA ACKNOWLEDGEMENT x - AI CALIBRATION x - ANALOGUE INPUTS x - ON-BOARD RS485 x - ON-BOARD CAN x x ETHERNET x x Display x x All Parameters Buzzer: x x HMI management x x HMI remote 1 (rem1) x (x) … x (x) HMI management HMI remote 10 (rem10) x (x) LABEL VAL PAR ADDRESS RESET (Y/N) R/W DATA SIZE CPL RANGE DEFAULT U.M.

RW Map code

Note: read/write parameter 0 … 65535 0 num. ACKNOWLEDGEMENT Par_POLI 15717 WORD Y RW Model Code Note: read/write parameter 0 … 65535 1025 num. ACKNOWLEDGEMENT Par_PARMOD 15719 BOOL RW Parameter changed Flag indicating change to default settings.  0= map not modified.  1= at least one parameter has been changed from the original configuration. 0 … 1 0 num. AI CALIBRATION Gain_Ntc_AI1 15616 WORD RW Ai1 NTC calibration gain 0 … 65535 32768 num. AI CALIBRATION Gain_Ntc_AI2 15617 WORD RW Ai2 NTC calibration gain 0 … 65535 32768 num. AI CALIBRATION Gain_5V_AI3 15620 WORD RW Ai3 0-5V calibration gain 0 … 65535 32768 num. AI CALIBRATION Gain_10V_AI3 15621 WORD RW Ai3 0-10V calibration gain 0 … 65535 32768 num. AI CALIBRATION Gain_mA_AI3 15622 WORD RW Ai3 4-20mA calibration gain 0 … 65535 32768 num. AI CALIBRATION Offs_Ntc_AI1 15650 WORD -1 RW Ai1 NTC calibration offset -32768 … 32767 0 num. AI CALIBRATION Offs_Ntc_AI2 15651 WORD -1 RW Ai2 NTC calibration offset -32768 … 32767 0 num. AI CALIBRATION Offs_5V_AI3 15654 WORD -1 RW Ai3 0-5V calibration offset -32768 … 32767 0 num. AI CALIBRATION Offs_10V_AI3 15655 WORD -1 RW Ai3 0-10V calibration offset -32768 … 32767 0 num. AI CALIBRATION Offs_mA_AI3 15656 WORD -1 RW Ai3 4-20mA calibration offset -32768 … 32767 0 num.

Temperature unit of measure

 0 = °C;  1 = °F 0 ... 1 0 num. ANALOGUE INPUTS Cfg_AI1 15726 WORD RW Type of analogue input Ai1  0= NTC (NK103)  1= DI  2= NTC (103AT) 0 ... 2 2 num. ANALOGUE INPUTS Cfg_Ai2 15727 WORD RW Type of analogue input Ai2 See Cfg_Ai1 0 ... 2 2 num. ANALOGUE INPUTS Cfg_Ai3 15728 WORD RW Type of analogue input Ai3  3 = 4…20mA  4=0-10V  5=0-5V 3 ... 5 3 num. ANALOGUE INPUTS Cfg_Ai4 15729 WORD RW Type of analogue input Ai4 See Cfg_Ai3 3 ... 5 3 num. ANALOGUE INPUTS FullScaleMin_Ai3 15736 WORD -1 RW Analogue input Ai3 start of scale value N.B.: Minimum full scale: for current probes, value at 4mA, for 0-10V voltage probes, value at 0V, 10% for ( 0-5V) probes, value at 10% (corresponding to 0.5V). -9999…+9999 0 ANALOGUE INPUTS FullScaleMAx_Ai3 15737 WORD -1 RW Analogue input Ai3 full scale value N.B.: Maximum full scale for current probes, value at 20mA, for 0-10V voltage probes, value at 10V, for (0-5V) probes, value at 90% (corresponding to 4.5V). -9999…+9999 1000 ANALOGUE INPUTS Calibration_Ai1 15748 WORD -1 RW Analogue input Ai1 differential -180 ... 180 0 °C/10 or °F/10 ANALOGUE INPUTS Calibration_Ai2 15749 WORD -1 RW Analogue input Ai2 differential -180 ... 180 0 °C/10 or °F/10 ANALOGUE INPUTS Calibration_Ai3 15750 WORD -1 RW Analogue input Ai3 differential -1000 ... 1000 0 ANALOGUE INPUTS Calibration_Ai4 15751 WORD -1 RW Analogue input Ai4 differential -1000 ... 1000 0 ANALOGUE INPUTS Compensation_AI1 15752 WORD -1 RW Internal compensation AI1 -1000 ... 1000 0 °C/10 ANALOGUE INPUTS Compensation_AI4 15753 WORD -1 RW Internal compensation AI4 -1000 ... 1000 0 °C/10

VAL PAR AdDRESS

DATA SIZE CPL RESET (Y/N) R/W DESCRIPTION RANGE DEFAULT U.M. RS485 ON BOARD Addr_RS485_OB 15774 WORD Y RW On-board RS485 serial address The actual address is determined by the sum of this value + the value of the dip switch. 0 ... 255 1 num. RS485 ON BOARD Proto_RS485_OB 15775 WORD Y RW On-board RS485 protocol selection 2 = uNET 3 = Modbus/RTU 2 ... 3 2 num. RS485 ON BOARD Databit_RS485_OB 15776 WORD Y RW On-board RS485 data bit number Fixed setting 8 8 ... 8 8 num. RS485 ON BOARD Stopbit_RS485_OB 15777 WORD Y RW On-board RS485 stop bit number  1= 1 stop bit  2= 2 stop bit 1... 2 1 num. RS485 ON BOARD Parity_RS485_OB 15778 WORD Y RW On-board RS485 protocol parity  0= NULL  1= ODD  2= EVEN 0 ... 2 2 num. RS485 ON BOARD Baud_RS485_OB 15779 WORD Y RW On-board RS485 protocol baudrate  0=9600 baud  1=19200 baud  2=38400 baud  3=57600 baud  4=76800 baud  5=115200 baud 0 ... 5 2 num. ON-BOARD CAN Addr_CAN_OB 15780 WORD Y RW On-board CAN serial address The actual address is determined by the sum of this value + the value of the dip switch. 1 ... 127 1 num. ON-BOARD CAN Baud_CAN_OB 15781 WORD Y RW On-board CAN protocol baudrate  2=500 Kbaud  3=250 Kbaud  4=125 Kbaud  5=125 Kbaud  6=50 Kbaud 2 ... 6 2 num.

ON BOARD ETHERNET

WEB SERVER FUNCTIONALITY: For more details refer to document 9IS24252_Web_ApplicationNotes The parameters necessary for the configuration of ports and protocols are these: HTTP and TFTP ports FREE WEB allows the use of HTTP and TFTP servers HTTP HyperText Transfer Protocol. An HTTP server generally listens on port 80 using TCP protocol. TFTP Trivial File Transfer Protocol. Protocol using basic FTP functionalities. Typical use: transfer of small files between hosts on a network. TFTP USES PORT 69 The parameters for configuring the PORTS are: DHCP protocol value Port_HTTP HTTP port HTTP communication Port number Default 0 corresponds to port 80 0 value Port_TFTP TFTP port TFTP communication Port number Default 0 corresponds to port 69 0 value EnableDHCP_ETH Enable DHCP 0 … 1 (False, True) False

System for the conversion of host names, or network nodes, to IP addresses

Used by FREE Studio to send text e-mails (strings) value value PriDNS_1_ETH Primary DNS server (part 1) 194 SecDNS_1_ETH Secondary DNS server (part 1) 194 PriDNS_2_ETH Primary DNS server (part 2) 25 SecDNS_2_ETH Secondary DNS server (part 2) 25 PriDNS_3_ETH Primary DNS server (part 3) 2 SecDNS_3_ETH Secondary DNS server (part 3) 2 PriDNS_4_ETH Primary DNS server (part 4) 129 SecDNS_4_ETH Secondary DNS server (part 4) 130 FOLDER LABEL PAR. VALUE ADDRESS DATA SIZE CPL RESET (Y/N) R/W DESCRIPTION RANGE DEFAULT U.M. ETHERNET ON BOARD Port_TFTP 15772 WORD Y RW TFTP port TFTP communication Port number Default 0 corresponds to port 69 0 … 65535 0 num. ETHERNET ON BOARD Port_HTTP 15796 WORD Y RW HTTP port HTTP communication Port number Default 0 corresponds to port 80 0 … 65535 0 num. ETHERNET ON BOARD Port_ETH 15797 WORD Y RW Port TCP/IP Modbus communication port. Port 502 for example 0 … 65535 502 num. ETHERNET ON BOARD Ip_1_ETH 15798 WORD Y RW On-board Ethernet passive IP address (part 1) 0 … 255 10 num. ETHERNET ON BOARD Ip_2ETH 15799 WORD Y RW On-board Ethernet passive IP address (part 2) 0 … 255 0 num. ETHERNET ON BOARD Ip_3ETH 15800 WORD Y RW On-board Ethernet passive IP address (part 3) 0 … 255 0 num. ETHERNET ON BOARD Ip_4ETH 15801 WORD Y RW On-board Ethernet passive IP address (part 4) 0 … 255 100 num.

RW Default Gateway (part 1)

0 … 255 192 num. ETHERNET ON BOARD DefGtwy_2_ETH 15803 WORD Y RW Default Gateway (part 2) 0 … 255 168 num. ETHERNET ON BOARD DefGtwy_3_ETH 15804 WORD Y RW Default Gateway (part 3) 0 … 255 0 num. ETHERNET ON BOARD DefGtwy_4_ETH 15805 WORD Y RW Default Gateway (part 4) 0 … 255 1 num. ETHERNET ON BOARD NetMsk_1_ETH 15806 WORD Y RW Net mask (part 1) 0 … 255 255 num. ETHERNET ON BOARD NetMsk_2_ETH 15807 WORD Y RW Net mask (part 2) 0 … 255 255 num. ETHERNET ON BOARD NetMsk_3_ETH 15808 WORD Y RW Net mask (part 3) 0 … 255 255 num. ETHERNET ON BOARD NetMsk_4_ETH 15809 WORD Y RW Net mask (part 4) 0 … 255 0 num.

RW Primary DNS server (part 1)

0 … 255 194 num. ETHERNET ON BOARD PriDNS_2_ETH 15811 WORD Y RW Primary DNS server (part 2) 0 … 255 25 num. ETHERNET ON BOARD PriDNS_3_ETH 15812 WORD Y RW Primary DNS server (part 3) 0 … 255 2 num. ETHERNET ON BOARD PriDNS_4_ETH 15813 WORD Y RW Primary DNS server (part 4) 0 … 255 129 num. ETHERNET ON BOARD SecDNS_1_ETH 15814 WORD Y RW Secondary DNS server (part 1) 0 … 255 194 num. ETHERNET ON BOARD SecDNS_2_ETH 15815 WORD Y RW Secondary DNS server (part 2) 0 … 255 25 num. ETHERNET ON BOARD SecDNS_3_ETH 15816 WORD Y RW Secondary DNS server (part 3) 0 … 255 2 num. ETHERNET ON BOARD SecDNS_4_ETH 15817 WORD Y RW Secondary DNS server (part 4) 0 … 255 130 num. ETHERNET ON BOARD EnableDHCP_ETH 15819 WORD Y RW Enable DHCP 0 … 1 (False, True) False flag

1 = English

2 = French 3 = German 4 = Spanish 0 … 65535 0 num. Display Par_ContrLCD 15723 WORD Y RW LCD Contrast Allows adjustment of the LCD display contrast. 0 … 64 30 Num. Display Par_BackLightTime 15724 WORD RW Backlight switch-on time Allows adjustment of LCD display switch-on time. 0 … 3600 10 sec Buzzer Buzzer_Mode 15990 WORD RW Buzzer mode 0= always off 1= beep per key 0 … 1 0 num.

0= HMI remote 1

1= HMI remote 2 2= HMI remote 3 3= HMI remote 4 4= HMI remote 5 5= HMI remote 6 6= HMI remote 7 7= HMI remote 8 8= HMI remote 9 9= HMI remote 10 10 = not used 11= Local HMI 0 … 11 11 num. NOTE: if HmiList_Current=11 the following folders/parameters are NOT USED HMI remote 1 HmiList_ID_1 15821 WORD RW HMI remote 1 navigation ID list 0 ... 254 0 num. HMI remote 1 HmiList_Res_1 15833 WORD RW HMI remote 1 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 1 HmiList_Addr_1 15845 WORD RW HMI remote 1 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 1 HmiList_Addr_2 15846 WORD RW HMI remote 1 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 1 HmiList_Addr_3 15847 WORD RW HMI remote 1 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 1 HmiList_Addr_4 15848 WORD RW HMI remote 1 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 1 HmiList_File_1 15893 15 byte RW HMI remote 1 navigation file (DOS 8.3 uppercase format) ******** string HMI remote 2 HmiList_ID_2 15822 WORD RW HMI remote 2 navigation ID list 0 ... 254 0 num. HMI remote 2 HmiList_Res_2 15834 WORD RW HMI remote 2 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 2 HmiList_Addr_1 15849 WORD RW HMI remote 2 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 2 HmiList_Addr_2 15850 WORD RW HMI remote 2 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 2 HmiList_Addr_3 15851 WORD RW HMI remote 2 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 2 HmiList_Addr_4 15852 WORD RW HMI remote 2 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 2 HmiList_File_2 15901 15 byte RW HMI remote 2 navigation file (DOS 8.3 uppercase format) ******** string

HMI remote 3

HmiList_ID_3 15823 WORD RW HMI remote 3 navigation ID list 0 ... 254 0 num. HMI remote 3 HmiList_Res_3 15835 WORD RW HMI remote 3 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 3 HmiList_Addr_1 15853 WORD RW HMI remote 3 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 3 HmiList_Addr_2 15854 WORD RW HMI remote 3 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 3 HmiList_Addr_3 15855 WORD RW HMI remote 3 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 3 HmiList_Addr_4 15856 WORD RW HMI remote 3 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 3 HmiList_File_3 15909 15 byte RW HMI remote 3 navigation file (DOS 8.3 uppercase format) ******** string HMI remote 4 HmiList_ID_4 15822 WORD RW HMI remote 4 navigation ID list 0 ... 254 0 num. HMI remote 4 HmiList_Res_4 15836 WORD RW HMI remote 4 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 4 HmiList_Addr_1 15857 WORD RW HMI remote 4 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 4 HmiList_Addr_2 15859 WORD RW HMI remote 4 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 4 HmiList_Addr_3 15859 WORD RW HMI remote 4 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 4 HmiList_Addr_4 15860 WORD RW HMI remote 4 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 4 HmiList_File_4 15917 15 byte RW HMI remote 4 navigation file (DOS 8.3 uppercase format) ******** string HMI remote 5 HmiList_ID_5 15825 WORD RW HMI remote 5 navigation ID list 0 ... 254 0 num. HMI remote 5 HmiList_Res_5 15837 WORD RW HMI remote 5 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 5 HmiList_Addr_1 15861 WORD RW HMI remote 5 navigation resource address for CAN, RTH and TCP (IP part 1) 0 ... 255 0 num. HMI remote 5 HmiList_Addr_2 15862 WORD RW HMI remote 5 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 5 HmiList_Addr_3 15863 WORD RW HMI remote 5 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 5 HmiList_Addr_4 15864 WORD RW HMI remote 5 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 5 HmiList_File_5 15925 15 byte RW HMI remote 5 navigation file (DOS 8.3 uppercase format) ******** string

HMI remote 6

HmiList_ID_6 15826 WORD RW HMI remote 6 navigation ID list 0 ... 254 0 num. HMI remote 6 HmiList_Res_6 15838 WORD RW HMI remote 6 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 6 HmiList_Addr_1 15865 WORD RW HMI remote 6 navigation resource address for CAN, RTH and TCP (IP part 1) 0 ... 255 0 num. HMI remote 6 HmiList_Addr_2 15866 WORD RW HMI remote 6 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 6 HmiList_Addr_3 15867 WORD RW HMI remote 6 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 6 HmiList_Addr_4 15868 WORD RW HMI remote 6 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 6 HmiList_File_6 15933 15 byte RW HMI remote 6 navigation file (DOS 8.3 uppercase format) ******** string HMI remote 7 HmiList_ID_7 15827 WORD RW HMI remote 7 navigation ID list 0 ... 254 0 num. HMI remote 7 HmiList_Res_7 15839 WORD RW HMI remote 7 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 7 HmiList_Addr_1 15869 WORD RW HMI remote 7 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 7 HmiList_Addr_2 15870 WORD RW HMI remote 7 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 7 HmiList_Addr_3 15871 WORD RW HMI remote 7 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 7 HmiList_Addr_4 15872 WORD RW HMI remote 7 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 7 HmiList_File_7 15941 15 byte RW HMI remote 7 navigation file (DOS 8.3 uppercase format) ******** string HMI remote 8 HmiList_ID_8 15828 WORD RW HMI remote 8 navigation ID list 0 ... 254 0 num. HMI remote 8 HmiList_Res_8 15840 WORD RW HMI remote 8 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 8 HmiList_Addr_1 15873 WORD RW HMI remote 8 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 8 HmiList_Addr_2 15874 WORD RW HMI remote 8 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 8 HmiList_Addr_3 15875 WORD RW HMI remote 8 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 8 HmiList_Addr_4 15876 WORD RW HMI remote 8 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 8 HmiList_File_8 15949 15 byte RW HMI remote 8 navigation file (DOS 8.3 uppercase format) ******** string

HMI remote 9

HmiList_ID_9 15829 WORD RW HMI remote 9 navigation ID list 0 ... 254 0 num. HMI remote 9 HmiList_Res_9 15841 WORD RW HMI remote 9 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 9 HmiList_Addr_1 15877 WORD RW HMI remote 9 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 9 HmiList_Addr_2 15878 WORD RW HMI remote 9 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 9 HmiList_Addr_3 15879 WORD RW HMI remote 9 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 9 HmiList_Addr_4 15880 WORD RW HMI remote 9 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 9 HmiList_File_9 15957 15 byte RW HMI remote 9 navigation file (DOS 8.3 uppercase format) ******** string HMI remote 10 HmiList_ID_10 15830 WORD RW HMI remote 10 navigation ID list 0 ... 254 0 num. HMI remote 10 HmiList_Res_10 15842 WORD RW HMI remote 10 navigation resource type 1=RTU (RS485 Modbus RTU) 2=TCP (Modbus TCP) 3=CAN (CANopen) 1 … 3 3 num. HMI remote 10 HmiList_Addr_1 15881 WORD RW HMI remote 10 navigation resource address for CAN, RTU and TCP (IP part 1) 0 ... 255 0 num. HMI remote 10 HmiList_Addr_2 15882 WORD RW HMI remote 10 navigation resource address for TCP (IP part 2) 0 ... 255 0 num. HMI remote 10 HmiList_Addr_3 15883 WORD RW HMI remote 10 navigation resource address for TCP (IP part 3) 0 ... 255 0 num. HMI remote 10 HmiList_Addr_4 15884 WORD RW HMI remote 10 navigation resource address for TCP (IP part 4) 0 ... 255 0 num. HMI remote 10 HmiList_File_10 15965 15 byte RW HMI remote 10 navigation file (DOS 8.3 uppercase format) ******** string

MODELS AND ACCESSORIES

7.1 Models ---------------- (*) low voltage SELV: SAFETY EXTRA LOW VOLTAGE (**) NOT INCLUDED - low voltage SELV: SAFETY EXTRA LOW VOLTAGE /C indicates presence of RTC (Real Time Clock) Accessories for Wall Mounting Contact the Eliwell Sales Department for wall-mounting accessories. Make 4 holes of diameter 4.2mm in the wall at the specified spacing, to fix the backplate. Alternatively use the two side slots, one at the bottom and one at the top, under the corresponding break-open removable doors, preventing the opening of holes in walls with recessed-wall wiring. Make all the necessary connections, then insert the EVP terminal (without front) in the backplate, which serves as a panel, following the instructions for panel mounting (see Mounting chapter). Accessories for Wall Mounting Code EVA00WMRC0000 Backplate for wall mounting Model Mounting Dimensions Display On-board Analogue Inputs (*) Remote Analogue Inputs (**) Power supply Serials EVP3300/C Panel* 160x96x10mm LCD backlit 1x NTC 1xNTC/DI 1x4…20mA/ 0-5V/ 0..10V 24V~/c - 48Vc CANopen RS485 ETHERNET TCP/IP EVP3300/C/RH Panel* 160x96x10mm LCD backlit 1 xNTC 1 x%RH 1xNTC/DI 24V~/c - 48Vc CANopen RS485 ETHERNET TCP/IP

Dimensions of wall-mounting backplate

7.2 Accessories Note: the photos are intended to show the accessories and are by way of example only. The dimensions shown in the figures are not to scale. Name Code Description Documentation / Notes SAR0RA00X701 USB/485 MINI KIT converter + USB cable Converters and cables EVA00USCA0000 USB/CAN converter Cable Contact Eliwell Sales Department Ethernet cable TF111202 230V~/24V 25VA transformer Note: cable must be no longer than 10m Transformer TF111205 230V~/24V 35VA transformer Note: cable must be no longer than 10m Mounting on DIN rail 59 83 90 160 80 57 90 R 1.5 mm 145 27 Ethernet

NTC probe NK103C1R1, 4m

Extended range (polyester, 2-wire cable) IP65; Instruction Sheet SN8D6L4002 GB-I SN691150 NTC probe 103AT, 1.5m (plastic cap, 2-wire cable); Instruction Sheet SN8D6L4002 GB-I Temperature probes SN8DED11502C0 NTC temperature probe 5X20 1.5m TPE IP68 Instruction Sheet SN8T6H1502 GB-I Name Code Description Documentation / Notes Pressure transducers (1) Pressure transducer 4…20mA male or female connector Range from -0.5/7bar to 0/50 bar Depending on model Instruction Sheet 9IS64173 EWPA EN-IT-ES-DE-FR-RU Code Description Documentation / Notes Software Tools Contact Eliwell Sales Department FREE Studio Contact Eliwell Sales Department Demo Case VAL00033K Demo case FREE Evolution Backplate EVA00WMRC0000 Backplate for wall mounting (1) Various items available. Contact the Sales Department (2) Various lengths can be requested GENERAL NOTES:  Eliwell can also supply a variety of different NTC probes depending on the cable type (PVC or silicon) and length.

BIOS parameters ............................................................17

BRIDGE ............................................................................13 C CAN......................................................................................6 CAN connection example (Field)................................10 CANopen network connection example...................12 COM Setting....................................................................19 Connections..................................................................... 10 Cross references..............................................................3 D Date and time.................................................................18 DIA Menu.........................................................................16 DIAGNOSTICS menu...................................................... 17 Disclaimer........................................................................ 15 Display.............................................................................. 15 E ELECTRICAL CONNECTIONS...........................................6 ETHERNET...........................................................................7 Example: RS485 connection (Field)............................10 Example: RS485 connection with FREE Smart network........................................................................11 F First power on ................................................................. 17 FREE WEB........................................................................13 G General description...........................................................3 General Technical Data ............................................ 14 General warnings..............................................................6 H Highlighting icons:............................................................3 HMI Management ..................................................18; 19 HMI sel..............................................................................18 I I/O features......................................................................14 Improper Use.................................................................15 INTRODUCTION................................................................ 3 K Keys and LEDs..................................................................16 L Language..........................................................................18 M Mechanical dimensions.............................................15 MECHANICAL INSTALLATION ................................... 5 Models..............................................................................34 MODELS AND ACCESSORIES .......................................34 Models and Features ....................................................... 4 N Note: for offset programming see the section on Analogue Inputs in the Connections chapter......18 P PARAMETERS...................................................................20 Permitted use...................................................................15 Power supply ...................................................................6 Pressure probes ..............................................................6 Probe values.....................................................................18 R References.........................................................................3 Remote interface ............................................................18 RS485..................................................................................7 S Serial connections ............................................................6 Serials...............................................................................15 Specifications:.................................................................4 T Table of parameters.......................................................20 TECHNICAL DATA...........................................................14 Temperature probes.........................................................6 TFTP ..................................................................................13 Transformer .....................................................................15 U USER INTERFACE.............................................................16 W Wiring diagrams............................................................... 8

Eliwell Controls S.r.l.

Via dell’ Industria, 15 Zona Industriale Paludi 32010 Pieve d’ Alpago (BL) Italy Telephone +39 0437 986 111 Facsimile +39 0437 989 066 Sales: +39 0437 986 100 (Italy) +39 0437 986 200 (other countries) [email protected] Technical helpline: +39 0437 986 250 E-mail [email protected] www.eliwell.com FREE Panel 2012/05/ Cod: 9MA10046 © Eliwell Controls s.r.l. 2011-12 All rights reserved.

Other Controller Manuals