Micropilot FMR51, FMR52 FOUNDATION Fieldbus

154 Endress+Hauser Ramp at echo lost  Navigation  Setup → Advanced setup → Safety sett. → Ramp echo lost Prerequisite Output echo lost (→  153) = Ramp at echo lost Description Define the slope of the ramp in the case of a lost echo. User entry Signed floating-point number Factory setting 0.0 %/min Additional information t min 0% 100% A B C A0013269 A Delay time echo lost B Ramp at echo lost (→  154) (positive value) C Ramp at echo lost (→  154) (negative value) • The unit for the slope of the ramp i ...

Micropilot FMR51, FMR52 FOUNDATION Fieldbus

42 Endress+Hauser m If required: Is the protective earth connected correctly ? m If supply voltage is present: Is the device ready for operation and do values appear on the display module? m Are all housing covers installed and firmly tightened? m Is the securing clamp tightened correctly? ...

Micropilot FMR51, FMR52 FOUNDATION Fieldbus

Operating menu Endress+Hauser 149 Maximum value  Navigation  Setup → Advanced setup → Linearization → Maximum value Prerequisite Linearization type (→  146) has one of the following values: • Linear • Pyramid bottom • Conical bottom • Angled bottom • Horizontal cylinder • Sphere Description Specify the maximum content of the vessel (100%) measured in the units after linearization. User entry –50 000.0 to 50 000.0 % Factory setting 100.0 % Diameter  Navigation  Setup → Advanced setup → Linearization → ...

Micropilot FMR51, FMR52 FOUNDATION Fieldbus

50 Endress+Hauser 8.2.6 Write protection via write protection switch Unlike parameter write protection via a user-specific access code, this allows write access to the entire operating menu - except for the "Contrast display" parameter - to be locked. The parameter values are now read only and cannot be edited any more (exception "Contrast display" parameter): • Via local display • Via FOUNDATION Fieldbus + E – 2.5 Nm (1.84 lbf ft) 3 mm XXXXXXXXXXXXX WP CDI SIM ON WP SIM OFF A0021474 1. Loosen the securing clamp. 2. Unscrew ...

Micropilot FMR51, FMR52 FOUNDATION Fieldbus

Integration into a FOUNDATION Fieldbus network Endress+Hauser 63 9.4 Block model 9.4.1 Blocks of the device software The device has the following blocks: • Resource Block (device block) • Transducer Blocks – Setup Transducer Block (TRDSUP) – Advanced Setup Transducer Block (TRDASUP) – Display Transducer Block (TRDDISP) – Diagnostic Transducer Block (TRDDIAG) – Advanced Diagnostic Transducer Block (TRDADVDIAG) – Expert Configuration Transducer Block (TRDEXP) – Expert Information Transducer Block (TRDEXPIN) – Service Sensor Transduc ...

Commissioning via operating menu

Micropilot FMR51, FMR52 FOUNDATION Fieldbus 76 Endress+Hauser 11. When operating via local display: Navigate to: Setup → Mapping → Confirm distance  Compare distance indicated on the display to real distance in order to start the recording of an interference echo map. 12. When operating via operating tool: Navigate to: Setup → Confirm distance  Compare distance indicated on the display to real distance in order to start the recording of an interference echo map. 13. Navigate to: Setup → Advanced setup → Level → Level unit  Select level unit ...

Micropilot FMR51, FMR52 FOUNDATION Fieldbus

Operating menu Endress+Hauser 173 "Define access code" wizard The Define access code wizard is only available when operating via the local display. When operating via an operating tool, the Define access code parameter is located directly in the Administration submenu. The Confirm access code parameter is not available for operation via operating tool. Navigation  Setup → Advanced setup → Administration → Def. access code Define access code  Navigation  Setup → Advanced setup → Administration → Def. access code → Def. access co ...

Endress+Hauser Micropilot FMR51 user guide recommended for: Cerabar S, Nivotester FTL325N-**** Series, Liquicap M FTI51, Deltabar S PMD75, HART Field Xpert.

⚠️ Download Safety

The Radar Operating instructions manual (198 pages) is completely safe to download (last scan date: 04/12/2025).