GE 469 Instruction Manual
Read Online
Read the GE 469 Instruction Manual online using the built-in PDF viewer.
Text of the manual
Motor Management Relay
GE
Grid Solutions
Instruction Manual
Software Revision: 5.20
Manual P/N: 1601-0122-AJ
Manual Order Code: GEK-106474S
GE Grid Solutions
650 Markland Street
Markham, Ontario
Canada L6C 0M1
TELEPHONE:
Worldwide +1 905 927 7070
Europe/Middle East Africa +34 94 485 88 54
North America toll-free 1 800 547 8629
FAX:
+1 905 927 5098
E-MAIL:
Worldwide [email protected]
Europe [email protected]
HOME PAGE:
Internet: http://www.gegridsolutions.com/multilin
*1601-0122-AJ*
© 2016 GE Multilin Incorporated. All rights reserved.
GE Multilin 469 Motor Management Relay instruction manual for revision 5.20.
469 Motor Management Relay, is a registered trademark of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin. The content of this manual is for informational use only and is subject to
change without notice.
Part numbers contained in this manual are subject to change without notice, and should
therefore be verified by GE Multilin before ordering.
Part number: 1601-0122-AJ (February 2016)
Safety words and definitions
The following symbols used in this document indicate the following conditions:
Note
Indicates a hazardous situation which, if not avoided, will result in death or serious
injury.
Note
Indicates a hazardous situation which, if not avoided, could result in death or serious
injury.
Note
Indicates a hazardous situation which, if not avoided, could result in minor or
moderate injury.
Note
Indicates practices not related to personal injury.
NOTE
Indicates general information and practices, including operational information and
practices, that are not related to personal injury.
TABLE OF CONTENTS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
TOC–I
Table of Contents
1: GETTING STARTED
IMPORTANT PROCEDURES .......................................................................................................... 1-1
CAUTIONS AND WARNINGS ............................................................................................... 1-1
INSPECTION CHECKLIST ...................................................................................................... 1-1
MANUAL ORGANIZATION ................................................................................................... 1-2
USING THE RELAY ............................................................................................................................ 1-3
MENU NAVIGATION ............................................................................................................. 1-3
PANEL KEYING EXAMPLE .................................................................................................... 1-7
CHANGING SETTINGS .................................................................................................................... 1-9
INTRODUCTION ..................................................................................................................... 1-9
THE HELP KEY .................................................................................................................... 1-10
NUMERICAL SETTINGS ........................................................................................................ 1-10
ENUMERATION SETTINGS ................................................................................................... 1-11
OUTPUT RELAY SETTINGS .................................................................................................. 1-15
TEXT SETTINGS ..................................................................................................................... 1-15
APPLICATION EXAMPLE ................................................................................................................. 1-17
DESCRIPTION ........................................................................................................................ 1-17
INSTRUMENT TRANSFORMER DATA ................................................................................... 1-25
MOTOR PROTECTION .......................................................................................................... 1-25
S2 SYSTEM SETTINGS ......................................................................................................... 1-30
S3 DIGITAL INPUTS SETTINGS ........................................................................................... 1-32
S5 THERMAL MODEL .......................................................................................................... 1-33
S6 CURRENT ELEMENTS ..................................................................................................... 1-33
S7 MOTOR STARTING ......................................................................................................... 1-35
S8 RTD TEMPERATURE ...................................................................................................... 1-35
OTHER SETTINGS ................................................................................................................. 1-36
INSTALLATION ................................................................................................................................... 1-38
TESTING ................................................................................................................................ 1-38
2: INTRODUCTION
OVERVIEW ........................................................................................................................................... 2-1
DESCRIPTION ........................................................................................................................ 2-1
ORDERING INFORMATION ................................................................................................... 2-4
ORDER CODES ..................................................................................................................... 2-5
EXAMPLE ORDER CODES .................................................................................................... 2-5
ACCESSORIES ....................................................................................................................... 2-5
SPECIFICATIONS ............................................................................................................................... 2-6
INPUTS .................................................................................................................................. 2-6
OUTPUTS ............................................................................................................................... 2-7
PROTECTION ......................................................................................................................... 2-8
DIGITAL INPUTS ................................................................................................................... 2-11
MONITORING ........................................................................................................................ 2-12
POWER SUPPLY ................................................................................................................... 2-13
CPU ...................................................................................................................................... 2-14
WAVEFORM CAPTURE (TRACE MEMORY) ......................................................................... 2-14
TESTING ................................................................................................................................ 2-14
CERTIFICATION ..................................................................................................................... 2-15
PHYSICAL .............................................................................................................................. 2-16
ENVIRONMENTAL ................................................................................................................. 2-16
LONG-TERM STORAGE ........................................................................................................ 2-16
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
TABLE OF CONTENTS
3: INSTALLATION
MECHANICAL INSTALLATION ......................................................................................................3-1
DESCRIPTION ........................................................................................................................3-1
PRODUCT IDENTIFICATION ..................................................................................................3-2
INSTALLATION .......................................................................................................................3-3
UNIT WITHDRAWAL AND INSERTION ................................................................................3-5
ETHERNET CONNECTION ....................................................................................................3-7
DEVICENET CONNECTION ..................................................................................................3-8
TERMINAL LOCATIONS ........................................................................................................3-9
TERMINAL LIST .....................................................................................................................3-9
ELECTRICAL INSTALLATION .........................................................................................................3-11
TYPICAL WIRING ..................................................................................................................3-11
DESCRIPTION ........................................................................................................................3-12
CONTROL POWER ................................................................................................................3-12
CURRENT INPUTS .................................................................................................................3-13
VOLTAGE INPUTS .................................................................................................................3-17
DIGITAL INPUTS ...................................................................................................................3-18
ANALOG INPUTS ..................................................................................................................3-19
ANALOG OUTPUTS ..............................................................................................................3-19
RTD SENSOR CONNECTIONS ............................................................................................3-20
OUTPUT RELAYS ..................................................................................................................3-22
DRAWOUT INDICATOR ........................................................................................................3-24
RS485 COMMUNICATIONS PORTS ...................................................................................3-24
DIELECTRIC STRENGTH .......................................................................................................3-25
2-SPEED MOTOR WIRING ..................................................................................................3-27
4: INTERFACES
FACEPLATE INTERFACE .................................................................................................................4-1
DESCRIPTION ........................................................................................................................4-1
DISPLAY .................................................................................................................................4-1
LED INDICATORS .................................................................................................................4-2
RS232 PORT .......................................................................................................................4-3
KEYPAD .................................................................................................................................4-4
SETTINGS ENTRY ..................................................................................................................4-6
DIAGNOSTIC MESSAGES .....................................................................................................4-7
SELF-TEST WARNINGS .......................................................................................................4-8
FLASH MESSAGES ................................................................................................................4-9
ENERVISTA 469 SETUP SOFTWARE INTERFACE .................................................................4-10
OVERVIEW ............................................................................................................................4-10
HARDWARE ...........................................................................................................................4-11
INSTALLING THE ENERVISTA 469 SETUP SOFTWARE ....................................................4-13
CONNECTING ENERVISTA 469 SETUP TO THE RELAY ......................................................4-16
CONFIGURING SERIAL COMMUNICATIONS .......................................................................4-16
USING THE QUICK CONNECT FEATURE ............................................................................4-17
CONFIGURING ETHERNET COMMUNICATIONS .................................................................4-18
CONNECTING TO THE RELAY ..............................................................................................4-19
WORKING WITH SETTINGS AND SETTINGS FILES .............................................................4-22
ENGAGING A DEVICE ...........................................................................................................4-22
ENTERING SETTINGS ............................................................................................................4-22
FILE SUPPORT ......................................................................................................................4-23
USING SETTINGS FILES .......................................................................................................4-23
UPGRADING RELAY FIRMWARE .................................................................................................4-35
DESCRIPTION ........................................................................................................................4-35
SAVING SETTINGS TO A FILE ..............................................................................................4-35
TABLE OF CONTENTS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
TOC–III
LOADING NEW FIRMWARE ................................................................................................. 4-35
ADVANCED ENERVISTA 469 SETUP FEATURES ................................................................... 4-38
TRIGGERED EVENTS ............................................................................................................. 4-38
WAVEFORM CAPTURE (TRACE MEMORY) ......................................................................... 4-38
PHASORS .............................................................................................................................. 4-40
TRENDING (DATA LOGGER) ................................................................................................ 4-42
EVENT RECORDER ............................................................................................................... 4-44
MODBUS USER MAP ........................................................................................................... 4-46
VIEWING ACTUAL VALUES ................................................................................................. 4-46
USING ENERVISTA VIEWPOINT WITH THE 469 ................................................................... 4-49
PLUG AND PLAY EXAMPLE ................................................................................................. 4-49
5: SETTINGS
OVERVIEW ........................................................................................................................................... 5-1
SETTINGS MESSAGE MAP ................................................................................................... 5-1
TRIPS, ALARMS, AND BLOCKS ............................................................................................ 5-6
RELAY ASSIGNMENT PRACTICES ........................................................................................ 5-7
S1 469 SETUP .................................................................................................................................... 5-8
PASSCODE ............................................................................................................................ 5-8
PREFERENCES ....................................................................................................................... 5-9
COMMUNICATIONS .............................................................................................................. 5-11
REAL TIME CLOCK ............................................................................................................... 5-13
DEFAULT MESSAGES ........................................................................................................... 5-14
MESSAGE SCRATCHPAD ...................................................................................................... 5-15
CLEAR DATA ......................................................................................................................... 5-16
INSTALLATION ....................................................................................................................... 5-16
S2 SYSTEM SETUP ............................................................................................................................ 5-18
CURRENT SENSING .............................................................................................................. 5-18
VOLTAGE SENSING .............................................................................................................. 5-20
POWER SYSTEM ................................................................................................................... 5-20
COMMUNICATIONS CONTROL ............................................................................................ 5-21
REDUCED VOLTAGE ............................................................................................................. 5-22
PRESET MOTOR VALUES ..................................................................................................... 5-24
S3 DIGITAL INPUTS .......................................................................................................................... 5-26
DESCRIPTION ........................................................................................................................ 5-26
STARTER STATUS ................................................................................................................. 5-27
ASSIGNABLE INPUTS 1(4) ................................................................................................... 5-27
S4 OUTPUT RELAYS ......................................................................................................................... 5-36
DESCRIPTION ........................................................................................................................ 5-36
RELAY RESET MODE ............................................................................................................ 5-36
FORCE OUTPUT RELAY ....................................................................................................... 5-37
S5 THERMAL MODEL ...................................................................................................................... 5-38
MOTOR THERMAL LIMITS ................................................................................................... 5-38
THERMAL MODEL ................................................................................................................ 5-40
OVERLOAD CURVE SETUP .................................................................................................. 5-41
S6 CURRENT ELEMENTS ............................................................................................................... 5-60
SHORT CIRCUIT TRIP ........................................................................................................... 5-60
OVERLOAD ALARM .............................................................................................................. 5-61
MECHANICAL JAM ............................................................................................................... 5-61
UNDERCURRENT .................................................................................................................. 5-62
CURRENT UNBALANCE ....................................................................................................... 5-63
GROUND FAULT ................................................................................................................... 5-65
PHASE DIFFERENTIAL .......................................................................................................... 5-66
S7 MOTOR STARTING ..................................................................................................................... 5-68
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
TABLE OF CONTENTS
ACCELERATION TIMER .........................................................................................................5-68
START INHIBIT ......................................................................................................................5-68
JOGGING BLOCK ..................................................................................................................5-69
RESTART BLOCK ...................................................................................................................5-71
S8 RTD TEMPERATURE ...................................................................................................................5-72
RTD TYPES ...........................................................................................................................5-72
RTDS 1 TO 6 .......................................................................................................................5-73
RTDS 7 TO 10 .....................................................................................................................5-74
RTD 11 ................................................................................................................................5-75
RTD 12 ................................................................................................................................5-76
OPEN RTD SENSOR ............................................................................................................5-77
RTD SHORT/LOW TEMP ....................................................................................................5-77
S9 VOLTAGE ELEMENTS ................................................................................................................5-78
UNDERVOLTAGE ...................................................................................................................5-78
OVERVOLTAGE ......................................................................................................................5-80
PHASE REVERSAL .................................................................................................................5-80
FREQUENCY ..........................................................................................................................5-81
S10 POWER ELEMENTS .................................................................................................................5-82
POWER MEASUREMENT CONVENTIONS ...........................................................................5-82
POWER FACTOR ...................................................................................................................5-83
REACTIVE POWER ................................................................................................................5-84
UNDERPOWER ......................................................................................................................5-85
REVERSE POWER .................................................................................................................5-86
TORQUE SETUP ....................................................................................................................5-86
OVERTORQUE .......................................................................................................................5-87
S11 MONITORING ............................................................................................................................5-88
TRIP COUNTER .....................................................................................................................5-88
STARTER FAILURE ................................................................................................................5-88
DEMAND ...............................................................................................................................5-89
PULSE OUTPUT ....................................................................................................................5-91
LOSS OF COMMUNICATIONS ..............................................................................................5-92
S12 ANALOG INPUTS/OUTPUTS ................................................................................................5-94
ANALOG OUTPUTS 1 TO 4 .................................................................................................5-94
ANALOG INPUTS 1 TO 4 .....................................................................................................5-96
ANALOG INPUT DIFF 1-2 ...................................................................................................5-98
ANALOG INPUT DIFF 3-4 ...................................................................................................5-99
S13 469 TESTING .............................................................................................................................5-101
SIMULATION MODE .............................................................................................................5-101
PRE-FAULT SETUP ...............................................................................................................5-102
FAULT SETUP ........................................................................................................................5-103
TEST OUTPUT RELAYS .........................................................................................................5-104
TEST ANALOG OUTPUTS .....................................................................................................5-104
COMM PORT MONITOR .......................................................................................................5-105
GR MULTILIN USE ONLY ....................................................................................................5-105
S14 TWO-SPEED MOTOR ..............................................................................................................5-106
DESCRIPTION ........................................................................................................................5-106
SPEED2 UNDERCURRENT ...................................................................................................5-110
SPEED2 ACCELERATION ......................................................................................................5-110
6: ACTUAL VALUES
OVERVIEW ...........................................................................................................................................6-1
ACTUAL VALUES MAP .........................................................................................................6-1
DESCRIPTION ........................................................................................................................6-3
A1 STATUS ...........................................................................................................................................6-4
TABLE OF CONTENTS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
TOC–V
MOTOR STATUS ................................................................................................................... 6-4
LAST TRIP DATA ................................................................................................................... 6-4
ALARM STATUS .................................................................................................................... 6-6
START BLOCKS ..................................................................................................................... 6-8
DIGITAL INPUTS ................................................................................................................... 6-8
REAL TIME CLOCK ............................................................................................................... 6-9
LOSS OF COMMUNICATIONS .............................................................................................. 6-9
NETWORK STATUS .............................................................................................................. 6-9
A2 METERING DATA ........................................................................................................................ 6-11
CURRENT METERING ........................................................................................................... 6-11
TEMPERATURE ...................................................................................................................... 6-12
VOLTAGE METERING ........................................................................................................... 6-13
SPEED .................................................................................................................................... 6-13
POWER METERING .............................................................................................................. 6-14
DEMAND METERING ............................................................................................................ 6-15
ANALOG INPUTS .................................................................................................................. 6-15
PHASORS .............................................................................................................................. 6-16
A3 LEARNED DATA .......................................................................................................................... 6-27
MOTOR STARTING ............................................................................................................... 6-27
AVERAGE MOTOR LOAD ..................................................................................................... 6-27
RTD MAXIMUMS ................................................................................................................. 6-28
ANALOG INPUT MIN/MAX ................................................................................................. 6-29
A4 MAINTENANCE ........................................................................................................................... 6-30
TRIP COUNTERS ................................................................................................................... 6-30
GENERAL COUNTERS .......................................................................................................... 6-31
TIMERS .................................................................................................................................. 6-32
A5 EVENT RECORDER ..................................................................................................................... 6-33
EVENT 01 TO EVENT 256 .................................................................................................. 6-33
A6 PRODUCT INFO .......................................................................................................................... 6-36
469 MODEL INFORMATION ............................................................................................... 6-36
CALIBRATION INFORMATION .............................................................................................. 6-36
DIAGNOSTICS .................................................................................................................................... 6-37
DIAGNOSTIC MESSAGES ..................................................................................................... 6-37
FLASH MESSAGES ................................................................................................................ 6-38
7: TESTING
OVERVIEW ........................................................................................................................................... 7-1
TEST SETUP .......................................................................................................................... 7-1
HARDWARE FUNCTIONAL TESTING ......................................................................................... 7-3
PHASE CURRENT ACCURACY TEST .................................................................................... 7-3
VOLTAGE INPUT ACCURACY TEST ..................................................................................... 7-3
GROUND AND DIFFERENTIAL ACCURACY TEST ............................................................... 7-4
GE DIGITAL ENERGY 50:0.025 GROUND ACCURACY TEST ......................................... 7-5
RTD ACCURACY TEST ......................................................................................................... 7-5
DIGITAL INPUTS AND TRIP COIL SUPERVISION ................................................................ 7-7
ANALOG INPUTS AND OUTPUTS ........................................................................................ 7-8
OUTPUT RELAYS .................................................................................................................. 7-10
ADDITIONAL FUNCTIONAL TESTING ....................................................................................... 7-11
OVERLOAD CURVE TEST ..................................................................................................... 7-11
POWER MEASUREMENT TEST ............................................................................................ 7-11
UNBALANCE TEST ................................................................................................................ 7-12
VOLTAGE PHASE REVERSAL TEST ...................................................................................... 7-13
SHORT CIRCUIT TEST .......................................................................................................... 7-14
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
TABLE OF CONTENTS
8: APPENDIX
TWO-PHASE CT CONFIGURATION ............................................................................................8-1
DESCRIPTION ........................................................................................................................8-1
COOL TIME CONSTANTS ...............................................................................................................8-4
SELECTION OF COOL TIME CONSTANTS ...........................................................................8-4
CURRENT TRANSFORMERS .......................................................................................................... 8-6
GROUND FAULT CTS FOR 50:0.025 A CT ....................................................................8-6
GROUND FAULT CTS FOR 5 A SECONDARY CT .............................................................8-8
PHASE CTS ...........................................................................................................................8-8
EU DECLARATION OF CONFORMITY ........................................................................................8-10
EU DECLARATION OF CONFORMITY .................................................................................8-10
CHANGE NOTES ................................................................................................................................8-11
REVISION HISTORY ..............................................................................................................8-11
CHANGES TO THE 469 MANUAL ......................................................................................8-11
GE WARRANTY ..................................................................................................................................8-16
WARRANTY ...........................................................................................................................8-16
I: INDEX
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–1
469 Motor Management Relay
Chapter 1: Getting Started
GE
Grid Solutions
Getting Started
1.1
Important Procedures
1.1.1
Cautions and Warnings
Please read this chapter to guide you through the initial setup of your new relay.
Note
Before attempting to install or use the relay, it is imperative that all WARNINGS and
CAUTIONS in this manual are reviewed to help prevent personal injury, equipment
damage, and/or downtime.
Note
1.1.2
Inspection Checklist
•
Open the relay packaging and inspect the unit for physical damage.
•
View the rear nameplate and verify that the correct model has been ordered.
•
Ensure that the following items are included:
– Instruction Manual
– GE EnerVista CD (includes software and relay documentation)
– mounting screws
•
For product information, instruction manual updates, and the latest software updates,
please visit the GE Grid Solutions website at http://www.gegridsolutions.com.
NOTE
Note
If there is any noticeable physical damage, or any of the contents listed are missing, please
contact GE Grid Solutions immediately.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
1.1.3
Manual Organization
Reading a lengthy instruction manual on a new product is not a task most people enjoy. To
speed things up, this introductory chapter provides a step-by-step tutorial for a simple
motor application. Important wiring considerations and precautions discussed in Electrical
Installation on page 3–11 should be observed for reliable operation. Detailed information
regarding accuracy, output relay contact ratings, and so forth are detailed in Specifications
on page 2–6. The remainder of this manual should be read and kept for reference to
ensure maximum benefit from the 469 Motor Management Relay. For further information,
please consult your local sales representative or the factory. Comments about new
features or modifications for your specific requirements are welcome and encouraged.
settings and actual values are indicated as follows in the manual:
A3 LEARNED DATA AVERAGE MOTOR LOAD AVERAGE MOTOR LOAD LEARNED
This ‘path representation’ illustrates the location of an specific actual value or settings with
regards to its previous menus and sub-menus. In the example above, the AVERAGE MOTOR
LOAD LEARNED actual value is shown to be an item in the AVERAGE MOTOR LOAD sub-
menu, which itself is an item in the A3 LEARNED DATA menu, which is an item of ACTUAL
VALUES.
Sub-menu levels are entered by pressing the MESSAGE or ENTER key. When inside a
submenu, the MESSAGE or ESCAPE key returns to the previous sub-menu. The
MESSAGE and MESSAGE keys are used to scroll through the settings in a sub-menu.
The display indicates which keys can be used at any given point.
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–3
1.2
Using the Relay
1.2.1
Menu Navigation
The relay has three types of display messages: actual value, settings, and target messages.
A summary of the menu structure for settings and actual values can be found at the
beginning of chapters 5 and 6, respectively.
Settings are programmable settings entered by the user. These types of messages are
located within a menu structure that groups the information into categories. Navigating
the menu structure is described below.
Actual values include the following information:
1.
Motor and System Status:
a.
Motor status either stopped, starting, or running. It includes values such as motor
load, thermal capacity used, motor speed, and instantaneous values of power
system quantities.
b.
The status of digital inputs.
c.
Last trip information, including values such as cause of last trip, time and date of
trip, motor speed and load at the time of trip, pre-trip temperature measure-
ments, pre-trip analog inputs values, and pre-trip instantaneous values of power
system quantities.
d.
Active alarms.
e.
Relay date and time.
f.
Present blocking conditions.
g.
General system status indication including the status of output relays, active
pickup, alarm and trip conditions.
2.
Metering Data:
a.
Instantaneous current measurements including phase, differential, unbalance,
ground, average, and motor load.
b.
RTD Temperatures including hottest RTDs.
c.
Instantaneous phase to phase and phase to ground voltages (depending on the
VT connections), average voltage, and system frequency.
d.
Motor Speed
e.
Power Quantities including apparent, real and reactive power.
f.
Current and power demand including peak values.
g.
Analog inputs
h.
Vector information.
3.
Motor Learned Data:
a.
Learned and last acceleration time.
b.
Learned and last starting current.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
c.
Learned and last starting capacity.
d.
Average motor load.
4.
Maintenance data. This is useful statistical information that may be used for
preventive maintenance. It includes:
a.
Trip counters
b.
General counter such as number of motor starts, number of emergency restarts,
number of starter operations, digital counter for other purposes not listed above.
c.
Timers such as motor running hours, time between starts timer, and five start
timers used to calculate the average start time of the motor.
5.
RTD Learned Data, which includes the maximum temperature measured by each of
the 12 RTDs.
6.
Event recorder downloading tool.
7.
Product information including model number, firmware version, additional product
information, and calibration dates.
8.
Oscillography downloading tool.
Alarm, trip conditions, diagnostics, and system flash messages are grouped under Target
Messages.
Press the MENU key to access the header of each menu, which will
be displayed in the following sequence:
To access settings,
Press the MENU key until the display shows the header of the
Settings menu.
Press the MESSAGE or ENTER key to display the header for the
first Settings page.
The Settings pages are numbered, have an ‘S’ prefix for easy
identification and have a name which provides a general idea of the
settings available in that page.
Pressing the MESSAGE and MESSAGE keys will scroll through
all the available Settings page headers. Settings page headers look
as follows:
1. SETPOINTS
Press [] for more
2. ACTUAL VALUES
Press [] for more
3. TARGET MESSAGES
Press [] for more
SETPOINTS
[]
S1 469 SETUP
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–5
To enter a given Settings page,
Press the MESSAGE or ENTER key.
Press the MESSAGE or MESSAGE keys to scroll through sub-
page headers until the required message is reached.
The end of a page is indicated by the message END OF PAGE. The
beginning of a page is indicated by the message TOP OF PAGE.
To access actual values,
Press the MENU key until the display shows the header of the actual
values menu.
Press the MESSAGE or ENTER key to display the header for the
first actual values page.
The actual values pages are numbered, have an ‘A’ prefix for easy
identification and have a name, which gives a general idea of the
information available in that page.
Pressing the MESSAGE or MESSAGE keys will scroll through all
the available actual values page headers. Actual values page
headers look as follows:
To enter a given actual values page,
Press the MESSAGE or ENTER key.
Press the MESSAGE or MESSAGE keys to scroll through sub-
page headers until the required message is reached.
The end of a page is indicated by the message END OF PAGE. The
beginning of a page is indicated by the message TOP OF PAGE.
Similarly, to access additional sub-pages,
Press the MESSAGE or ENTER key to enter the first sub-page,
Press the MESSAGE or MESSAGE keys to scroll through the
available sub-pages, until the desired message is reached.
The process is identical for both settings and actual values.
The following procedure illustrates the key sequence to access the Current Demand actual
values.
Press the MENU key until you reach the actual values main menu.
Press MESSAGE or ENTER key to enter the first actual values
page.
Press the MESSAGE or MESSAGE key to scroll through pages,
until the A2 METERING DATA page appears.
ACTUAL VALUES
[]
A1 STATUS
ACTUAL VALUES
[]
A2 METERING DATA
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
Press the MESSAGE or ENTER key to display the first sub-page
heading for the Metering Data actual values page:
Pressing the MESSAGE or MESSAGE keys will scroll the display up and down
through the sub-page headers.
Pressing the MESSAGE or ESCAPE key at any sub-page heading will return the
display to the heading of the corresponding settings or actual value page.
Pressing it again, will return the display to the main menu header.
Press the MESSAGE key until the DEMAND METERING sub-page
heading appears.
At this point, pressing MESSAGE or ENTER key will display the messages under this
sub-page. If instead you press the MESSAGE key, it will return to the previous sub-
page heading. In this case,
When the symbols and [] appear on the top line, it indicates that additional sub-
pages are available and can be accessed by pressing the MESSAGE or ENTER key.
Press MESSAGE or ENTER while at the Demand Metering sub-
page heading to display the following:
Press MESSAGE key to return to the Demand Metering sub-page
heading.
Press the MESSAGE key to display the next actual value of this
sub-page.
Actual values and settings messages always have a colon
separating the name of the value and the actual value or settings.
This particular message displays the current demand as measured
by the relay.
The menu path to this value is shown as A2 METERING DATA DEMAND METERING
CURRENT DEMAND. Settings and actual values messages are referred to in this
manner throughout the manual.
For example, the A3 LEARNED DATA MOTOR STARTING LEARNED ACCELERATION
TIME path representation describes the following key-press sequence:
Press the MENU key until the actual value header appears on the
display, MESSAGE or ENTER key,
CURRENT
[]
METERING
DEMAND
[]
METERING
POWER
[]
METERING
CURRENT
DEMAND:
0 Amps
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–7
Press the MESSAGE key until the A3 LEARNED DATA message is
displayed.
Press the MESSAGE or ENTER key to display MOTOR STARTING
message.
Press the MESSAGE or ENTER key to reach the LEARNED
ACCELERATION TIME message and the corresponding actual value.
Press the MESSAGE key to display the next actual value message
as shown below:
Press the MESSAGE or MESSAGE keys to scroll the display up
and down through all the actual value displays in this corresponding
sub-page.
Press the MESSAGE key to reverse the process described above
and return the display to the previous level.
Press the MESSAGE key twice to return to the A3 LEARNED DATA
page header.
1.2.2
Panel Keying Example
The following figure gives a specific example of how the keypad is used to navigate
through the menu structure. Specific locations are referred to throughout this manual by
using a ‘path representation’. The example shown in the figure gives the key presses
required to read the learned starting current denoted by the path A3 LEARNED DATA
MOTOR STARTING LEARNED STARTING CURRENT.
Press the menu key until the relay displays the actual values page.
LEARNED STARTING
CURRENT:
0 A
MOTOR
[]
STARTING
ACTUAL VALUES
[]
A3 LEARNED DATA
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
ACTUAL VALUES
[]
Press the MESSAGE
or ENTER key
ACTUAL VALUES
[]
A1 STATUS
Press the MESSAGE
key
ACTUAL VALUES
[]
A2 METERING DATA
Press the MESSAGE
key
ACTUAL VALUES
[]
A3 LEARNED DATA
MESSAGE
MOTOR STARTING
[]
MESSAGE
LEARNED ACCELERATION
TIME:
0.0 s
MESSAGE
LEARNED STARTING
CURRENT:
0 A
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–9
1.3
Changing Settings
1.3.1
Introduction
There are several classes of settings, each distinguished by the way their values are
displayed and edited.
The relay's menu is arranged in a tree structure. Each setting in the menu is referred to as a
settings, and each settings in the menu may be accessed as described in the previous
section.
The settings are arranged in pages with each page containing related settings; for
example, all the Short Circuit Trip settings are contained within the same page. As
previously explained, the top menu page of each setting group describes the settings
contained within that page. Pressing the MESSAGE keys allows the user to move between
these top menus.
All of the 469 settings fall into one of following categories: device settings, system settings,
digital input settings, output relay settings, thermal model settings, current element
settings, motor starting settings, RTD temperatures settings, voltage element settings,
power element settings, monitoring settings, analog input/output settings, two speed
motor settings, and testing settings.
NOTE
Note
IMPORTANT: Settings are stored and used by the relay immediately after they are
entered. As such, caution must be exercised when entering settings while the relay is in
service. Modifying or storing protection settings is not recommended when the relay is
in service since any incompatibility or lack of coordination with other previously saved
settings may cause unwanted operations.
Now that we have become more familiar with maneuvering through messages, we can
learn how to edit the values used by all settings classes.
Hardware and passcode security features are designed to provide protection against
unauthorized settings changes. Since we will be programming new settings using the front
panel keys, a hardware jumper must be installed across the settings access terminals (C1
and C2) on the back of the relay case. Attempts to enter a new settings without this
electrical connection will result in an error message.
The jumper does not restrict settings access via serial communications. The relay has a
programmable passcode settings, which may be used to disallow settings changes from
both the front panel and the serial communications ports. This passcode consists of up to
eight (8) numeric characters.
The factory default passcode is “0”. When this specific value is programmed into the relay it
has the effect of removing all settings modification restrictions. Therefore, only the settings
access jumper can be used to restrict settings access via the front panel and there are no
restrictions via the communications ports.
When the passcode is programmed to any other value, settings access is restricted for the
front panel and all communications ports. Write Access via keypad is not permitted until
the passcode is entered via the keypad. Write access via communication port is not
permitted until the passcode is entered via that port. That is, the passcode must be
entered via the port from which access is desired.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
Entering the passcode on any communication port automatically restricts the other ports,
but does not restrict the keypad. For example, entering the passcode on computer RS485
permits settings write access on computer RS485, and restricts write access on computer
RS232, auxiliary RS485, and ethernet.
A front panel command can disable settings access once all modifications are complete.
For the communications ports, writing an invalid passcode disables access. In addition,
settings access is automatically disabled on an interface if no activity is detected for thirty
minutes.
The EnerVista 469 Setup software incorporates a facility for programming the relay's
passcode as well as enabling and disabling settings access. For example, when an attempt
is made to modify a settings but access is restricted, the software will prompt the user to
enter the passcode and send it to the relay before the settings is actually written to the
relay. If a SCADA system is used for relay programming, it is the programmer's
responsibility to incorporate appropriate security for the application.
1.3.2
The HELP Key
Pressing the HELP key displays context-sensitive information about settings such as the
range of values and the method of changing the settings. Help messages will
automatically scroll through all messages currently appropriate.
1.3.3
Numerical Settings
Each numerical settings has its own minimum, maximum, and step value. These
parameters define the acceptable settings value range. Two methods of editing and
storing a numerical settings value are available.
The first method uses the 469 numeric keypad in the same way as any electronic
calculator. A number is entered one digit at a time with the 0 to 9 and decimal keys. The
left-most digit is entered first and the right-most digit is entered last. Pressing ESCAPE
before the ENTER key returns the original value to the display.
The second method uses the VALUE key to increment the displayed value by the step
value, up to a maximum allowed value. Likewise, the VALUE key decrements the
displayed value by the step value, down to a minimum value. For example:
Select the S2 SYSTEM SETUP VOLTAGE SENSING MOTOR
NAMEPLATE VOLTAGE settings message.
Press the 1, 3, 8, 0, and 0 keys. The display message will change as
shown.
Until the ENTER key is pressed, editing changes are not registered by the relay.
MOTOR NAMEPLATE
VOLTAGE: 4000 V
MOTOR NAMEPLATE
VOLTAGE: 13800 V
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–11
Therefore, press the ENTER key to store the new value in memory.
This flash message will momentarily appear as confirmation of the
storing process.
1.3.4
Enumeration Settings
The example shown in the following figures illustrates the keypress sequences required to
enter system parameters such as the phase CT primary rating, ground CT primary rating,
bus VT connection type, secondary voltage, and VT ratio.
The following values will be entered:
Phase CT primary rating: 600 A
Motor Full Load Current: 318 A
Ground CT ratings: 50/5 A
Phase Differential CT: None
Voltage Transformer Connection Type: Open Delta
Motor Nameplate Voltage: 13800 V
VT Ratio: 115:1
To set the phase CT primary rating, modify the S2 SYSTEM SETUP CURRENT SENSING
PHASE CT PRIMARY settings as shown below.
Press the MENU key until the relay displays the Sepoints menu
header.
To set the phase Motor Full Load Amps FLA, modify the S2 SYSTEM SETUP CURRENT
SENSING MOTOR FULL LOAD AMPS FLA settings as shown below.
Press the MENU key until the relay displays the Setpoints menu
header.
NEW SETPOINT HAS
BEEN STORED
1. SETPOINTS
Press [] for more
Press MESSAGE or ENTER
SETPOINTS
[]
S1 469 SETUP
Press MESSAGE
SETPOINTS
[]
S2 SYSTEM SETUP
Press
MESSAGE
or ENTER
CURRENT
[]
SENSING
Press
MESSAGE
or ENTER
PHASE CT PRIMARY:
OFF
Press the VALUE keys until 600 A is displayed,
or enter the value directly via the numeric
keypad.
PHASE CT PRIMARY:
600 A
Press the ENTER key to store the settings. NEW SETPOINT HAS
BEEN STORED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
1. SETPOINTS
Press [] for more
Press MESSAGE or ENTER
SETPOINTS
[]
S1 469 SETUP
Press MESSAGE
SETPOINTS
[]
S2 SYSTEM SETUP
Press
MESSAGE
or ENTER
CURRENT
[]
SENSING
Press
MESSAGE
or ENTER
PHASE CT PRIMARY:
600 A
Press
MESSAGE
MOTOR FULL LOAD AMPS
FLA: OFF
Press the VALUE keys until 318 A is displayed,
or enter the value directly via the numeric
keypad.
MOTOR FULL LOAD AMPS
FLA: 318 A
Press the ENTER key to store the settings.
NEW SETPOINT HAS
BEEN STORED
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–13
To set the ground CT ratings, modify the S2 SYSTEM SETUP CURRENT SENSING GROUND
CT and the S2 SYSTEM SETUP CURRENT SENSING GROUND CT PRIMARY settings as
shown below.
Press the MENU key until the relay displays the Setpoints menu
header.
1. SETPOINTS
Press [] for more
Press MESSAGE or ENTER
SETPOINTS
[]
S1 469 SETUP
Press MESSAGE
SETPOINTS
[]
S2 SYSTEM SETUP
Press
MESSAGE
or ENTER
CURRENT
[]
SENSING
Press
MESSAGE
or ENTER
PHASE CT PRIMARY:
600 A
Press
MESSAGE
MOTOR FULL LOAD AMPS
FLA: 318 A
Press
MESSAGE
GROUND CT:
50:0.025
Press the VALUE keys until
“5 A Secondary” is displayed.
GROUND CT:
5 A Secondary
Press the ENTER key to store the settings. NEW SETPOINT HAS
BEEN STORED
Press
MESSAGE
GROUND CT PRIMARY:
100 A
Press the VALUE keys until 50 A is displayed, or
enter the value directly via the numeric
keypad.
GROUND CT PRIMARY:
50 A
Press the ENTER key to store the settings. NEW SETPOINT HAS
BEEN STORED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
To set the VT connection type and ratings, modify the S2 SYSTEM SETUP VOLTAGE
SENSING VT CONNECTION TYPE and the S2 SYSTEM SETUP VOLTAGE SENSING
VOLTAGE TRANSFORMER RATIO, and S2 SYSTEM SETUP VOLTAGE SENSING MOTOR
NAMEPLATE VOLTAGE settings as shown below.
Press the MENU key until the relay displays the Setpoints menu
header.
If an entered settings value is out of range, the relay displays the following message:
where 100 is the minimum settings value, 36000 is the maximum, and 1 is the step value.
To have access to information on maximum, minimum, and step value, press the HELP key.
1. SETPOINTS
Press [] for more
Press MESSAGE or ENTER
SETPOINTS
[]
S1 469 SETUP
Press MESSAGE
SETPOINTS
[]
S2 SYSTEM SETUP
Press
MESSAGE
or ENTER
CURRENT
[]
SENSING
Press
MESSAGE
VOLTAGE
[]
SENSING
Press
MESSAGE
or ENTER
VT CONNECTION TYPE:
None
Press the VALUE keys until
“Open Delta” is displayed.
VT CONNECTION TYPE:
Open Delta
Press the ENTER key to store the settings. NEW SETPOINT HAS
BEEN STORED
Press
MESSAGE
ENABLE SINGLE VT:
OPERATION: OFF
Press
MESSAGE
VOLTAGE TRANSFORMER
RATIO: 35.00 : 1
Press the VALUE keys until 115.00 : 1 is
displayed, or enter the value directly via the
numeric keypad.
VOLTAGE TRANSFORMER
RATIO: 115.00 : 1
Press the ENTER key to store the settings. NEW SETPOINT HAS
BEEN STORED
Press
MESSAGE
MOTOR NAMEPLATE
VOLTAGE: 4000 V
Press the VALUE keys until 13800 V is
displayed, or enter the value directly via the
numeric keypad.
MOTOR NAMEPLATE
VOLTAGE: 13800 V
Press the ENTER key to store the settings. NEW SETPOINT HAS
BEEN STORED
OUT-OF-RANGE! ENTER:
100-36000 by 1
“100-36000” indicates the range and “1” indicates the step
value
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–15
1.3.5
Output Relay Settings
Output relays (Trip or Alarm) can be associated to the Auxiliary Relays 2 and 3. Each can be
selected individually, or in combination, in response to customer specific requirements,
which can be initiated by any protection element or function, whose ASSIGN RELAYS
settings has them selected.
Select the S6 CURRENT ELEM. SHORT CIRCUIT TRIP ASSIGN TRIP
RELAYS settings message.
If an application requires the short circuit protection element to operate the Auxiliary
Output 3 relay,
Select this output relay by pressing the value key until the desired
combination appear in the display.
Press the ENTER key to store this change into memory.
As before, confirmation of this action will momentarily flash on the
display.
1.3.6
Text Settings
Text settings have data values which are fixed in length but user-defined in character. They
may be composed of uppercase letters, lowercase letters, numerals, and a selection of
special characters. The editing and storing of a text value is accomplished using the
decimal [.], VALUE, and ENTER keys.
For example:
Move to message S3 DIGITAL INPUTS ASSIGNABLE INPUT 1
INPUT 1 FUNCTION, and scrolling with the VALUE keys, select “General
Sw. A”.
The relay will display the following message:
Press the MESSAGE key to view the next settings, SWITCH NAME.
The name of this user-defined input will be changed in this example
from the generic “General Sw. A” to something more descriptive.
If an application is to be using the relay as a station monitor, it is more informative to
rename this input “Station Monitor”.
ASSIGN TRIP RELAYS:
Trip
ASSIGN TRIP RELAYS:
Trip & Auxiliary3
NEW SETPOINT HAS
BEEN STORED
INPUT 1 FUNCTION:
General Sw. A
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
Press the decimal [.] key to enter the text editing mode.
The first character will appear underlined as follows:.
Press the VALUE keys until the character “S” is displayed in the first
position.
Press the decimal [.] key to store the character and advance the
cursor to the next position.
Change the second character to a “t” in the same manner.
Continue entering characters in this way until all characters of the
text “Stn. Monitor” are entered.
Note that a space is selected like a character. If a character is
entered incorrectly, press the decimal [.] key repeatedly until the
cursor returns to the position of the error. Re-enter the character as
required.
Once complete, press the ENTER key to remove the solid cursor and
view the result. Once a character is entered, by pressing the ENTER
key, it is automatically saved in flash memory, as a new settings.
SWITCH NAME:
General Sw. A
SWITCH NAME:
Stn. Monitor
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–17
1.4
Application Example
1.4.1
Description
The 469 Motor Management Relay contains many features designed to accommodate a
wide range of motor management applications. This chapter is provided to guide you, the
first-time user, through a real-world application.
The following is typical example of how to determine the relay settings for a specific motor
that has been applied conservatively. This is only an example and may not address all
issues relating to your specific application. It is recommended that your local protection
engineer determine the settings for your motor protective relaying application. Refer to
following figures for schematic diagrams related to this example.
Important points to keep in mind before developing settings for any multifunction
numerical device like the 469 Motor Management Relay:
•
Gather system data, including, but not limited to:
– CT primary and secondary ratings for all the CTs used to feed the relay
– motor name plate data
– motor operating curves (typical set shown below)
FIGURE 1–1: Typical Motor Curves
806553A1.CDR
1.000
10.000
100.000
1000.000
0
500
1,000
1,500
2,000
2,500
Current (Amps)
Time (sec.)
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
– VT primary and secondary ratings
– System frequency
– System phase sequence
•
Define the protection elements that will be enabled. Prepare a list of protection
functions including the following information. By default, all the protection functions
must be assumed “Disabled”:
– Pickup parameter
– Operating curve, if applicable
– Time dial or multiplier
– Any additional intentional time delay
– Directionality, if applicable
•
Define how many output contacts will be energized in response to a given protection
function. Note that the 469 relay can be programmed to Trip or Alarm and, at the
same time, to energize one, a combination, or all the 2 auxiliary relays during the
process.
•
Define if the output relays will be set as failsafe type.
•
Define if the 469 relay will be used to start the motor. If so, gather information on the
required conditions to execute the command.
•
Define if the 469 will be involved in the motor starting process, particularly on reduced
voltage start applications.
•
Define if the 469 will be applied a multi speed applications.
•
Define if the relay will be used to monitor the status of the starter or breaker. It is
strongly recommended that the 469 be always programmed to monitor the status of
the disconnecting device, by means of a dry contact connected to one of the digital
inputs of the relay. Use an auxiliary contact from the breaker or starter either a
normally open contact, 52a, which is normally in open position when the
disconnecting device is open, or a normally closed contact, 52b, which is in close
position when the breaker or starter is open.
•
If the 469 will be used to respond to digital inputs, record the following information:
– Digital Input name
– Condition by which the digital input would be considered asserted
– Function that the digital input will initiate within the 469
•
If the 469 will be used to perform monitoring functions and act upon certain
conditions, record information such as:
– minimum and maximum values
– alarm and trip values
– time delays
•
It is important to familiarize yourself with the relay protection and control functions
before setting up the relay.
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–19
To begin, simply power on the unit and follow the instructions in this tutorial. Assume the
following system characteristics and that the 469 settings are unaltered from their factory
default values.
Refer to the following figures for schematics related to this application example.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
FIGURE 1–2: Typical Relay Connection Diagram
28
MOTOR
BEARING 2
36
32
34
35
33
30
31
29
STATOR
STATOR
STATOR
MOTOR
BEARING 1
PHASE C - 2
PHASE C - 1
PHASE B - 2
20
24
26
27
25
22
23
21
16
18
19
17
15
14
13
STATOR
STATOR
STATOR
PHASE B - 1
PHASE A - 2
PHASE A - 1
5
9
11
12
10
7
8
6
1
3
4
2
+
Comp
-
Shld
Comp
Shld
-
+
+
-
Shld
Comp
-
+
Comp
Shld
Shld
Comp
+
-
Comp
Shld
-
+
+
-
Shld
Comp
Comp
Shld
-
+
+
-
Shld
Comp
AMBIENT
MOTOR
806554A2.CDR
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–21
FIGURE 1–3: Typical Control Diagram
806552A2.CDR
COMMON
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
FIGURE 1–4: Typical Breaker Control Diagram
806551A1.CDR
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–23
FIGURE 1–5: Typical Relay Control Diagram
•
Power System Data
a) System: 3Φ, 4 wire
b) Frequency: 60 Hz
c) Line voltage: 600 V
•
Motor Data
As per the following motor data sheet information:
FIGURE 1–6: Motor Data Sheet Information
806555A2.CDR
COMMON
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
•
Motor Operating Curves
Motor operating curves as shown below:
FIGURE 1–7: Motor Operating Curves for Application Example
•
Control System Requirements
– All protection elements trip the breaker
– Breaker position monitoring via 52b contact only
– Only current metering is required
– Serial communication remote start from RTU
– Alarm after 100 s delay from station monitor. This is normally used to signal the
remote center when someone has gained access to the substation.
•
Contact Outputs
– Trip and close to breaker control circuit (Trip and Auxiliary2 relays)
– Relay failure alarm to RTU (self-test warning relay, no programming required)
– Alarm contact (setup in General Sw. A for “Station Monitor”)
– No data communications to other equipment.
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–25
•
RTDs
The motor is fitted with the following RTDs:
– RTD type: 100 Ω Platinum
– 6 Stator RTDs, 2 per phase
– 2 Bearing RTDs
– 1 Ambient RTD
Use the above data to set the output relays to achieve breaker control; to set digital inputs
for breaker status, remote operations, remote status, and alarm indication. Assume that
the communications between the station and the master control center will be done by the
RTU. Alarms, status indication, and breaker commands will be hard-wired from the relay to
the RTU. Similar information could be exchanged between the RTU and the relay via an
RS485 or RS422 Serial Link using the Modbus RTU protocol. Refer to GE Publication GEK-
106491C: 469 Communications Guide for additional information.
1.4.2
Instrument Transformer Data
•
Voltage Transformers
– 2 × Open Delta connected, ratio = 600:120 V
– Motor System Voltage = 575 V
•
Phase CTs
The phase CTs should be chosen such that the FLC is 50% to 100% of CT primary.
Since the FLC is 347.5A a 350:5, or 400:5 CT may be chosen; 400:5 is a standard
available size and so would probably be selected.
•
Ground CT
For high resistive grounded systems, sensitive ground detection is possible with the
50:0.025 CT. Use a 1 A or 5 A secondary CT on solidly grounded or low resistive
grounded systems where the fault current is much higher. If a residual connection is
chosen, pickup levels and timers must be set with respect to the acceleration time.
The chosen zero-sequence CT must be able to handle all potential fault levels without
saturating. In this example, 50:5A CT is selected.
•
Motor FLC
Set the motor full load current to 348 A, as specified by the data sheets.
Use the above data to set the relay system parameters, such as CT and VT
connections, VT secondary voltage, and CT and VT primary to secondary ratios.
1.4.3
Motor Protection
•
Overload Pickup
The overload pickup is set to the maximum allowed by the service factor of the motor.
Since this motor has RTDs and the relay will be using the RTD bias feature for
enhanced protection, set the overload pickup to the highest setting of 1.25 x FLC for
the motor service factor of 1.15. If service factor is unknown, assume 1.0.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
•
Overload Curve
Select the standard overload curve to be just below the cold thermal limit to give
maximum process uptime, without compromising protection.
The best fitting curve is curve 7 (see figure below)
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–27
FIGURE 1–8: Overload Curve Matching (Example)
469 Motor Management Relay
STANDARD OVERLOAD CURVES
x1
x15
100000
10000
1000
100
10
1.00
0.10
1.00
MULTIPLE OF FULL LOAD AMPS
TIME IN SECONDS
10
100
1000
806804A5.CDR
NOTE:
LOG CHART SCALED AS PER:
KEUFFEL & ESSER TIME-CURRENT CHARACTERISTIC PAPER
GE ORDER #: GES10083
THIS DRAWING IS PROPRIETARY INFORMATION
DRAWN BY/DATE:
ENG. APP./DATE:
MFG. APP./DATE:
SCALE:
DWG. SIZE: B
DWG. No.:
PART No.:
REV.
REV
DATE
ECO#
DWN APP
DESCRIPTION
A4
06/98
469-096
469-202
BA
JN
GE ORDER NUMBER ADDED
469 Motor Management Relay
STANDARD OVERLOAD CURVES
N/A
A5
JA/09/20/96
X
X
1:1
806804A5.CDR
TEL: (905)294-6222 FAX: (905)201-2098
INT: http://www.ge.com/edc/pm
215 ANDERSON AVENUE,
MARKHAM, ONT., CANADA, L6E 1B3
A5
12/99
WL
CD
Deleted “Multilin” from logo
Deleted “SR” from Heading
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
•
Short Circuit Trip
The short circuit trip should be set above the maximum locked rotor current but below
the short circuit current of the fuses. The data sheets indicate a maximum locked rotor
current of 630% FLC or 6.3 × FLC. A setting of 7 × FLC with a instantaneous time delay
will be ideal but nuisance tripping may result due to the asymmetrical starting
currents and DC offset. If asymmetrical starting currents limits the starting capability,
set the S/C level higher to a maximum of 11 × FLC to override this condition
(1.7 × 6.3 = 11.7 where 1.7 is the maximum DC offset for an asymmetrical current).
•
Ground Fault
Unfortunately, there is not enough information to determine a ground fault setting.
These settings depend on the following information:
1.
The ground fault current available.
2.
System grounding; for example, high resistive grounding or solidly grounded
3.
Ground fault CT used.
4.
Ground fault connection; for example, zero-sequence or residual connection
For the purpose of this example, assume a fault current of 10 Amps or 10/50 = 0.2 x
CT, no intentional time delay.
•
Unbalance Alarm and Trip
The unbalance settings are determined by examining the motor application and
motor design. The heating effect of unbalance will be protected by enabling
unbalance input to thermal memory; described in details in Chapter 5, Thermal Model.
A setting of 10% for the unbalance alarm with a delay of 10 seconds would be
appropriate and the trip can be set to 25% with a delay of 5 seconds.
•
Stopped and Running Cool Times
The motor manufacturer usually supplies this information as either cooling times, or
cooling time constants not provided in the data sheet issued with this motor. Since
RTDs are present and wired to the relay, biasing of the thermal model will be used so it
is not critical to have these cooling times from the manufacturer. The default values of
motor cooling time constants are 15 and 30 minutes, and can be used for the running
and stopped cool times respectively. If the manufacturer provides cooling times
instead, the approximate values of the cooling time constants is 1/5th the cooling
times provided by the manufacturer.
•
Acceleration Trip
This settings should be set higher than the maximum starting time to avoid nuisance
tripping when the voltage is lower or for varying loads during acceleration. If reduced
voltage starting is used, according to the acceleration curves, a setting of 18 seconds
would be appropriate, or if across the line starting is used, a setting of 13 seconds
would be appropriate.
•
Enable Start Inhibit
This function will limit starts when the motor is already hot. The relay learns the
amount of thermal capacity used at start. If the motor is hot, thus having some
thermal capacity used, the relay will not allow a start if the available thermal capacity
is less than the required thermal capacity for a start.
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–29
•
Starts/Hour
When available, set starts/Hour to the number of cold starts as per the data sheet.
•
Time Between Starts
In some cases, the motor manufacturer will specify the time between motor starts.
This information is not given so this feature can be left disabled. If the information is
available, the time provided on the motor data sheets should be programmed.
•
Stator RTDs
Set the RTD trip level at or below the maximum temperature rating of the insulation.
The data available shows class F insulation (temperature rating of 155°C), therefore
the Stator RTD Trip level should be set to between 140°C to 155°C, with 155°C being
maximum. The RTD alarm level should be set to provide a warning that the motor
temperature is rising. For this example, 135°C would be appropriate since this motor is
designed for class B rise, 130°C is it's normal hot operating temperature.
•
Bearing RTDs
The Bearing RTD alarm and trip settings will be determined by evaluating the
temperature specification from the bearing manufacturer.
•
Unbalance bias of thermal capacity
Enable the Unbalance Bias of Thermal Capacity so that the heating effect of
unbalance currents is added to the Thermal Capacity Used.
•
Unbalance bias K factor
The K value is used to calculate the contribution of the negative-sequence current
flowing in the rotor due to unbalance. It is defined as:
(EQ 1.1)
where:
Rr2 = rotor negative-sequence resistance
Rr1 = rotor positive-sequence resistance.
A formula based on empirical data states that K is equal to 230 divided by the per-unit
locked rotor current squared.
From the data sheet, the locked rotor amps = 631% FLA or 6.31 × FLA. Therefore,
(EQ 1.2)
•
Hot/cold curve ratio
The hot/cold curve ratio is calculated by simply dividing the hot safe stall time by the
cold safe stall time or use the motor thermal limits curve. For this example, both are
available. Using the data sheets the, safe stall time H/C or hot/cold curve ratio is given
as 16/18 = 0.89
•
Enable RTD Biasing
This will enable the temperature from the Stator RTD sensors, to be included in the
calculations of thermal capacity. This model determines the thermal capacity used
based on the temperature of the Stator and is separate from the overload model for
calculating thermal capacity used.
K
Rr2
Rr1
--------
=
K
230
(per-unit locked rotor amps)2
------------------------------------------------------------------------
230
6.312
-------------
≈ 6
=
=
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
RTD biasing is a back up protection element, which accounts for such things as loss of
cooling or unusually high ambient temperature. This measured temperature is used to
bias or modify the thermal capacity value stored in the relay.
RTD BIAS MINIMUM: Set to 40°C, which is the ambient temperature, obtained from the
data sheets.
RTD BIAS MID POINT: The center point temperature is set to the motor's hot running
temperature and is calculated as follows:
Temperature Rise of Stator + Ambient Temperature
The temperature rise of the stator is 80°C (class F rise by resistance) + 10% hot spot
allowance, obtained from the data sheets. Therefore, the RTD Center point
temperature is set to 90°C + 40°C or 130°C.
RTD BIAS MAXIMUM: This settings is set to the rating of the insulation or slightly less. A
class F insulation is used in this motor which is rated at 155°C, so the setting should be
“155”.
FIGURE 1–9: RTD Bias Example 1
You should now be familiar with maneuvering through and editing settings messages. As
such, we will now limit our discussion to just the values that must be programmed to meet
the requirements of the example application. Any settings not explicitly mentioned should
be left at the factory default value.
1.4.4
S2 System Settings
The S2 settings page contains settings for entering the characteristics of the equipment on
the motor electrical system. In our example, these characteristics are specified under the
Power System Data and Instrument Transformer Data headings in the previous sub-
section. From this information and the resulting calculations, program the page S2 settings
as indicated.
806550A1.CDR
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–31
For current transformers, make the following change in the S2 SYSTEM SETUP CURRENT
SENSING settings page:
PHASE CT PRIMARY: “400 A”
MOTOR FULL LOAD AMPS FLA: “348 A”
GROUND CT: “5 A Secondary”
GROUND CT PRIMARY: “50 A”
PHASE DIFFERENTIAL CT: “None”
ENABLE 2-SPEED MOTOR PROTECTION: “No”
For current transformers, make the following change in the S2 SYSTEM SETUP VOLTAGE
SENSING settings page:
VT CONNECTION TYPE: “Open Delta”
ENABLE SINGLE VT OPERATION: “Off”
VOLTAGE TRANSFORMER RATIO: “5 : 1”
(for a 600 V system, 600/120 V = 5, where 5 is the VT ratio)
MOTOR NAMEPLATE VOLTAGE: “575 V”
The 469 Motor Management Relay was designed with the ability to display primary system
values. Current and voltage measurements are performed at secondary levels, which the
relay transforms to primary values using CT and VT ratios, system voltage, as well as the
nominal secondary values.
In the case of the phase CTs, configuring the relay for current measurements is simple and
it only requires inputting the CT primary current. Phase CT inputs can be 1 A or 5 A, and
they must be specified when the relay is purchased.
There is more flexibility with regards to Ground CT inputs, as well as VT inputs, where
nominal values are not required ahead of time, before the relay is ordered; therefore more
settings are needed to set the relay for measurements.
Make the following change in the S2 SYSTEM SETUP POWER SYSTEM settings page to
reflect the power system:
NOMINAL SYSTEM FREQUENCY: “60 Hz”
SYSTEM PHASE SEQUENCE: “ABC”
The example calls for remote control via serial communications, received from the master
station, through the RTU. Motor starting and stopping is possible via any of the three 469
communication ports.
When a start command is issued, the auxiliary relay assigned for starting control is
activated for 1 second to complete the close coil circuit for a breaker application, or
complete the start control circuit for a contactor application. A contactor sealing contact
would be used to maintain the circuit. For details on issuing a start or stop command via
communications, refer to the GE Publication GEK-106491: 469 Communications Guide.
Make the following changes to the communications settings in the S2 SYSTEM SETUP
SERIAL COMM. CONTROL page.
SERIAL COMMUNICATION CONTROL: “On”
ASSIGN START CONTROL RELAYS: “Auxiliary2”
The Auxiliary 2 relay will be used to start the motor. Note that this auxiliary relay can not be
used for any other application.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
Once the signal is received the motor will be started across the line. Therefore, the
following settings are left with their default values. In the S2 SYSTEM SETUP REDUCE
VOLTAGE STARTING settings page:
REDUCE VOLTAGE STARTING: “Off”
ASSIGN CONTROL RELAYS: “Auxiliary3” (available for other use)
TRANSITION ON: “Current Only”
ASSIGN TRIP RELAYS: “Trip”
REDUCE VOLTAGE START LEVEL: “100% FLA”
REDUCE VOLTAGE START TIMER: “200 s”
1.4.5
S3 Digital Inputs Settings
The S3 settings page is for entering the characteristics of the digital inputs. In our example,
these characteristics are specified under the Control System Requirements heading.
Program the S3 settings as indicated.
Some of the functions assigned to the digital inputs of the 469 Motor Management Relay
are pre-defined functions, which can be selected from a list. There are four user-defined
functions, called General Switch A to D, associated to the assignable inputs. Set these
inputs to operate output relays, with or without delay, responding to the status change of
dry contacts connected to the digital input terminals. Use the following procedure to set
these functions:
Change the default names to meaningful values so they can be
easily identified, either via the LCD or when reviewing event reports.
Identify their asserted logic.
Define the functionality of the digital inputs.
All the other assignable input functions are pre-defined, and when selected, they can be
set to generate Trip or Alarms, as well as energize auxiliary outputs as needed.
For breaker position monitoring, set the following pre-defined Digital Input called “Starter
Status”. As per the information provided above, a 52b contact will be used, and must be
connected between terminals D16 to D23:
S3 DIGITAL INPUTS STARTER STATUS STARTER STATUS SW: “Starter Auxiliary b”
To set the relay to monitor access to the station, use Assignable Input 1 as “General Switch
A”, as follows. To define the digital input, enter the following data in the S3 DIGITAL INPUTS
ASSIGNABLE INPUT 1 settings page.
To identify the digital input:
INPUT 1 FUNCTION: “General Sw. A”
SWITCH NAME: “Stn. Monitor”
To define the asserted logic:
GENERAL SWITCH A: “Normally Open”
To define the functionality:
BLOCK INPUT FROM START: “0 s”
GENERAL SWITCH A ALARM: “Latched”
ASSIGN ALARM RELAYS: “Alarm”
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–33
GENERAL SWITCH A ALARM DELAY: “5.0 s”
GENERAL SWITCH A EVENTS: “On” so this event is registered.
GENERAL SWITCH A TRIP: “Off”
If the relay will not be used to trip the motor when someone gains unauthorized access to
the station, the next settings should be left at their default values:
GENERAL SWITCH A TRIP: “Off”
ASSIGN TRIP RELAYS: “Trip”
GENERAL SWITCH A TRIM DELAY: “5.0 s”
1.4.6
S5 Thermal Model
The S5 Thermal Model settings page contains settings for entering settings related to
protection of the motor during the starting process as well as during normal operation.
As per the information provided above, the settings for the Thermal Model are entered as
follows in the
SELECT CURVE STYLE: “Standard”
OVERLOAD PICKUP: “1.25 x FLA”
ASSIGN TRIP RELAYS: “Trip”
UNBALANCE BIAS K FACTOR: “6”
COOL TIME CONSTANT RUNNING: “15 min.”
COOL TIME CONSTANT STOPPED: “30 min.”
HOT/COLD SAFE STALL RATIO: “0.89”
ENABLE RTD BIASING: “Yes”
RTD BIAS MINIMUM: “40°C” – ambient temperature
RTD BIAS CENTER POINT: “130°C” – center value
RTD BIAS MAXIMUM: “155°C” – maximum value
THERMAL CAPACITY ALARM: “Unlatched” – recommended for early warning to take
corrective actions and prevent the interruption of the process.
ASSIGN ALARM RELAYS: “Alarm” – the Alarm contact could be use for local indication,
or to send a local signal to reduce load, before a trip is issued.
THERMAL CAP. ALARM LEVEL: “80%”
THERMAL CAPACITY ALARM EVENT: “Yes” – captures event in the event report.
As well, select the overload curve for the Thermal model with the following settings in the
S5 THERMAL MODEL OVERLOAD CURVE SETUP menu:
STANDARD OVERLOAD CURVE NUMBER: “7”
1.4.7
S6 Current Elements
The S6 Current Elements settings page contains settings for entering protection element
characteristics. In our example, these characteristics are specified under Motor Protection
heading.
From this data and the resulting calculations, program the S6 settings page as indicated.
When setting the relay for the first time, other settings not listed in this example should be
left disabled.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
For the Short Circuit element, enter the following values in the S6 CURRENT ELEMENTS
SHORT CIRCUIT TRIP page. Press the MESSAGE key after each settings is entered to
move to the next message.
SHORT CIRCUIT TRIP: “Latched”
SHORT CIRCUIT TRIP OVEREACH FILETER: “Off” - no filtering of DC component is
required (refer to Short Circuit Trip on page 5–60 for additional information)
ASSIGN TRIP RELAYS: “Trip”
SHORT CIRCUIT TRIP PICKUP: “11.7”
INTENTIONAL S/C TRIP DELAY: “0 ms” - Instantaneous trip is required.
SHORT CIRCUIT TRIP BACKUP: “On” - if the main disconnect device does not respond to
the trip command, a second signal will be initiated via an auxiliary relay to generate a
bus shot down; in most cases, the second trip command energizes a lock out relay (86)
which is used to trip the upstream breakers
ASSIGN BACKUP RELAYS: “Auxiliary3”
SHORT CIRCUIT TRIP BACKUP DELAY: “200 ms” - this time must be greater than the
total time required to trip the main breaker plus a margin
Since the specifications do not indicate values for the following features, they must be left
“Off”:
OVERLOAD ALARM: “Off”
MECHANICAL JAM: “Off”
UNDERCURRENT: “Off”
PHASE DIFFERENTIAL: “Off”
For the Ground Fault element, enter the following values in the S6 CURRENT ELEMENTS
GROUND FAULT page. Press the MESSAGE key after each settings is entered to move to
the next message.
GROUND FAULT OVERREACH FILETER: “Off” – no filtering of DC component is required
(refer to Ground Fault on page 5–65 for additional information)
GROUND FAULT ALARM: “Off” – default setting, no Alarm is required
ASSIGN ALARM RELAYS: “Alarm” – default setting
GROUND FAULT ALARM PICKUP: “0.10 x CT” – default setting
INTENTIONAL GF ALARM DELAY: “0 ms” – default setting
GROUND FAULT ALARM EVENTS: “Off” – default setting
GROUND FAULT TRIP: “Latched” – the output relay will remind energized until the Reset
command executed
ASSIGN TRIP RELAYS: “Trip”
GROUND FAULT TRIP PICKUP: “0.20 x CT”
INTENTIONAL GF TRIP DELAY: “0 ms”
GROUND FAULT TRIP BACKUP: “On”
ASSIGN BACKUP RELAYS: “Auxiliary3” - same relay assigned for the Short Circuit Trip
Backup
GROUND FAULT TRIP BACKUP DELAY: “200 ms” - same time delay assigned to the Short
Circuit Trip Backup
For the Current Unbalance element, enter the following values in the S6 CURRENT
ELEMENTS CURRENT UNBALANCE page. Press the MESSAGE key after each settings
is entered to move to the next message.
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–35
CURRENT UNBALANCE ALARM: “Unlatched”
ASSIGN ALARM RELAYS: “Alarm”
CURRENT UNBALANCE ALARM PICKUP: “10%”
CURRENT UNBALANCE ALARM DELAY: “10 s”
CURRENT UNBALANCE ALARM EVENTS: “On”
CURRENT UNBALANCE TRIP: “Latched” – the output relay will remind energized until the
Reset command executed
ASSIGN TRIP RELAYS: “Trip”
CURRENT UNBALANCE TRIP PICKUP: “20%”
CURRENT UNBALANCE TRIP DELAY: “5 s”
1.4.8
S7 Motor Starting
The S7 Motor Starting settings page contains additional settings used to complement the
Thermal Model. In our example, these characteristics are specified under Motor Protection
heading.
For the Acceleration Timer element, enter the following values in the S7 MOTOR STARTING
ACCELERATION TIMER page. Press the MESSAGE key after each settings is completed to
move to the next message.
ACCELERATION TIMER TRIP: “Latched”
ASSIGN TRIP RELAYS: “Trip”
ACCELERATION TIMER FROM START: “13 s” – as shown in the acceleration curves at
100% voltage
For the Start Inhibit element, enter the following values in the S7 MOTOR STARTING
START INHIBIT page. Press the MESSAGE key after each settings is completed to move
to the next message.
START INHIBIT BLOCK: “On”
TC USED MARGIN: “25%”
With these settings, the 469 relay prevents motor starting if there is insufficient thermal
capacity for a successful motor start. Refer to Start Inhibit on page 5–68 for additional
information.
There is not information available to set Starts/Hour, Time Between Starts, or the Restart
Block features. Therefore, the following settings must be disabled:
JOGGING BLOCK: “Off”
RESTART BLOCK: “Off”
1.4.9
S8 RTD Temperature
The S8 RTD Temperature page contains the settings for the twelve (12) field programmable
RTDs that are normally used for temperature monitoring. The temperature measured by
each RTD can be compared to pickup values, and set to energize Trip or Alarm outputs.
For proper temperature monitoring, enter the RTD types in the S8 RTD TEMPERTURE RTD
TYPES page. Press the MESSAGE key after each settings is completed to move to the
next message.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
STATOR RTD TYPE: “100 Ohm Platinum”
BEARING RTD TYPE: “100 Ohm Platinum”
AMBIENT RTD TYPE: “100 Ohm Platinum”
OTHER RTD TYPE: “100 Ohm Platinum” – default value
As per the information provided above, there will be six RTDs, two per phase located in the
Stator, and two Bearing RTDs, one to monitor the ambient temperature.
For Stator Overtemperature protection, enter the following settings in the S8 RTD
TEMPERTURE RTD 1 to RTD6 menus:
RTD #1 APPLICATION: “Stator”
RTD #1 NAME: “ST Ph A1”
RTD #1 ALARM: “Unlatched”
ASSIGN ALARM RELAYS: “Alarm”
RTD #1 ALARM TEMPERATURE: “135°C”
RTD #1 HIGH ALARM: “Off”
HIGH ALARM RELAYS: “Alarm” - default value
RTD #1 HIGH ALARM TEMPERATURE: “135°C” - default value
RTD #1 ALARM EVENTS: “On”
RTD #1 TRIP: “Latched”
RTD #1 TRIP VOTING: “RTD #5”
ASSIGN TRIP RELAYS: “Trip”
RTD #1 TRIP TEMPERATURE: “155°C”
The settings for the other RTDs are entered in similar fashion. Refer to S8 RTD Temperature
on page 5–72 for additional settings and additional information on RTD monitoring.
1.4.10 Other Settings
Undervoltage Protection
In addition to the settings illustrated above, there will be cases in motor applications where
additional settings will be required, to monitor other system parameters such as voltage
levels.
The following sub-section will illustrate the procedures to set the 469 Motor Management
Relay to meet those requirements.
Description
Using the same system information, the following example illustrates the steps to set the
469 for Undervoltage protection.
The following settings are provided:
Pickup: 70% of nominal voltage – starting
80% of nominal voltage – running
Time Delay: 13.0 s
Other Considerations
•
The function will be active only if there is voltage in the line feeding the motor, to avoid
nuisance trips due to the lack of voltage. The 469 will consider the bus energized only
CHAPTER 1: GETTING STARTED
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–37
if the measured voltage is greater than 20% of nominal voltage. A trip condition will be
initiated only if undervoltage is detected in all the phases.
•
In order to monitor for VT Fuse Failure or to monitor for undervoltage in one phase
only, set an Alarm when the voltage is 90% of nominal voltage both during start and
running.
For the Undervoltage element, enter the following values in the S9 VOLTAGE ELEMENTS
UNDERVOLTAGE settings page. Press the ENTER key to save, and then the MESSAGE key,
after each settings is completed, to move to the next message:
U/V ACTIVE ONLY IF BUS ENERGIZED: “Yes”
UNDERVOLTAGE ALARM: “Unlatched”
ASSIGN ALARM RELAYS: “Alarm”
UNDERVOLTAGE ALARM PICKUP: “0.9 x RATED”
STARTING U/V ALARM PICKUP: “0.9 x RATED”
UNDERVOLTAGE ALARM DELAY: “0.0 s”
UNDERVOLTAGE ALARM EVENTS: “Yes”
UNDERVOLTAGE TRIP: “Latched”
UNDRVOLTAGE TRIP MODE: “3-Phase”
ASSIGN TRIP RELAYS: “Trip”
UNDERVOLTAGE TRIP PICKUP: “0.8 x RATED”
STARTING U/V TRIP PICKUP: “0.7 x RATED”
UNDERVOLTAGE TRIP DELAY: “13.0 s”
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
1.5
Installation
1.5.1
Testing
Extensive commissioning tests are available in Chapter 7. Tables for recording required
settings are available in Microsoft Excel format from the GE Grid Solutions website at http:/
/www.gegridsolutions.com/. The website also contains additional technical papers and
FAQs relevant to the 469 Motor Management Relay.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–1
469 Motor Management Relay
Chapter 2: Introduction
GE
Grid Solutions
Introduction
2.1
Overview
2.1.1
Description
The 469 Motor Management Relay is a microprocessor based relay designed for the
protection and management of medium and large horsepower motors and driven
equipment. The 469 is equipped with six (6) output relays for trips, alarms, and start blocks.
Motor protection, fault diagnostics, power metering, and RTU functions are integrated into
one economical drawout package. The single-line diagram below illustrates the 469
functionality using ANSI (American National Standards Institute) device numbers
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
.
FIGURE 2–1: Single Line Diagram
Typical applications include: pumps, fans, compressors, mills, shredders, extruders,
debarkers, refiners, cranes, conveyors, chillers, crushers, and blowers.
Some of the protection highlights are detailed here; a complete list is shown below. Four
assignable digital inputs may be configured for a number of different features including
tachometer or generic trip and alarm with a programmable name. The thermal model
incorporates unbalance biasing, RTD feedback, and exponential cooling. In addition to the
15 standard overload curves, there is a custom curve feature and a curve specifically
designed for the starting of high inertia loads, when the acceleration time exceeds the safe
stall time. A second overload curve is provided for two-speed motors. Ground faults or
earth leakage as low as 0.25 A may be detected using the GE Grid Solutions 50:0.025
Ground CT. CT inputs for phase differential protection are also provided. The 12 RTD inputs
provided may be individually field programmed for different RTD types. Voltage
transformer inputs allow for numerous protection features based on voltage and power
quantities. Four 4 to 20 mA analog inputs may be used for tripping and alarming on any
transducer input such as vibration, pressure, flow, etc.
CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–3
FIGURE 2–2: Protection Features
Fault diagnostics are provided through pretrip data, event record, trace memory, and
statistics. Prior to issuing a trip, the 469 takes a snapshot of the measured parameters and
stores them with the cause of the trip. This pre-trip data may be viewed using the MENU
key, viewing the TARGET MESSAGES before the trip is reset, or by accessing the A1 STATUS
LAST TRIP DATA actual values. The 469 event recorder stores up to 256 time and date
stamped events including the pre-trip data. Each time a trip occurs, the 469 stores a trace
of 8 cycles pre-trip and 8 cycles post-trip for all measured AC quantities. Trip counters
record the number of occurrences of each type of trip. Minimum and maximum values for
analog inputs, along with maximum values for RTDs, are also recorded. These features
enable the operator to pinpoint a problem quickly and with certainty.
Power metering included with the 469 as a standard feature. The table below outlines the
metered parameters available either through the front panel or communications ports.
51
Overload
86
Overload Lockout
66
Starts/Hour & Time Between Starts
Restart Block (Anti-Backspin Timer)
50
Short Circuit & Short Circuit Backup
Mechanical Jam
37
32
Undercurrent/Underpower
Reverse Power
46
Current Unbalance
50G/51G
Ground Fault & Ground Fault Backup
87
Differential
Acceleration
49
Stator RTD
38
Bearing RTD
Other RTD & Ambient RTD
Open RTD Alarm
Short/Low RTD
27/59
Undervoltage/Overvoltage
47
Phase Reversal
81
Frequency
Reactive Power
55/78
Power Factor
Analog Input
Demand Alarm: A kW kvar kVA
SR469 Self-Test, Service
Trip Coil Supervision
Welded Contactor
Breaker Failure
Remote Switch
14
Speed Switch & Tachometer Trip
Load Shed Switch
Pressure Switch
Vibration Switch
19
Reduced Voltage Start
48
Over Torque
Remote Start/Stop
PROCTLA5.CDR
Incomplete Sequence (Reduced Voltage Start)
Forced Relay Operation
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
The 469 is equipped with 3 fully functional and independent communications ports. The
front panel RS232 port may be used for 469 settings programming, local interrogation or
control, and upgrading of 469 firmware. The Computer RS485 port may be connected to a
PLC, DCS, or PC based user interface program. The Auxiliary RS485 port may be used for
redundancy or simultaneous interrogation and/or control from a second PLC, DCS, or PC
software.
There are also four 4 to 20 mA or 0 to 1 mA (as specified with order) transducer outputs
that may be assigned to any measured parameter. The range of these outputs is scalable.
Additional features are outlined below.
METERING:
•
Voltage
•
Current and amps demand
•
Real power, kW demand, kW power consumption
•
Apparent power and kVA demand
•
Reactive power, kvar demand, kvar consumption/generation
•
Frequency
•
Power factor
•
RTD
•
Speed in RPM with a key phasor input
•
User-programmable analog inputs.
ADDITIONAL FEATURES:
•
Drawout case (for ease of maintenance/testing)
•
Reduced voltage starting control for single transition
•
Trip coil supervision
•
Flash memory for easy firmware updates
2.1.2
Ordering Information
All 469 features are standard; there are no options. The phase CT secondaries, control
power, and analog output range must be specified at the time of order. The 469 differential
CT inputs are field programmable for CTs with 1 A or 5 A secondaries. There are two
ground CT inputs, one for the GE Grid Solutions 50:0.025 core balance CT and one for a
ground CT with a 1 A or 5 A secondary, also field programmable. The VT inputs will
accommodate VTs in either a delta or wye configuration. The output relays are always
non-failsafe with the exception of the service relay. The EnerVista 469 Setup software is
provided with each unit. A metal demo case may be ordered for demonstration or testing
purposes.
CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–5
2.1.3
Order Codes
2.1.4
Example Order Codes
1.
The 469-P1-LO-A20-E code specifies a 469 Motor Management Relay with 1 A CT
inputs, 20 to 60 V DC or 20 to 48 V AC control voltage, 4 to 20 mA analog outputs, and
enhanced display option with larger LCD.
2.
The 469-P5-HI-A1-T-H code specifies a 469 Motor Management Relay with 5 A CT
inputs, 90 to 300 V DC or 70 to 265 V AC control voltage, 0 to 1 mA analog outputs,
enhanced display with Ethernet (10Base-T) communications, and a harsh
environment conformal coating.
2.1.5
Accessories
The following accessories are available for the 469 Motor Management Relay:
•
EnerVista 469 Setup software: No-charge software provided with each relay
•
Demo: Metal Carry Case in which 469 unit may be mounted
•
SR 19-1 Panel: Single cutout 19-inch panel
•
SR 19-2 Panel: Dual cutout 19-inch panel
•
SCI Module: RS232-to-RS485 converter box designed for harsh industrial
environments
•
Phase CT: 50, 75, 100, 150, 200, 250, 300, 350, 400, 500, 600, 750, 1000
•
HGF3, HGF5, HGF8: For sensitive ground detection on high resistance grounded
systems.
•
469 1-inch Collar: For shallow switchgear, reduces the depth of the relay by 1 3/8
inches
•
469 3-inch Collar: For shallow switchgear, reduces the depth of the relay by 3
inches
•
Optional Mounting Kit: Additional mounting support 1819-0030
Table 2–1: 469 Order Codes
469 –
*
–
*
–
*
–
*
–
*
Base Unit
469
|
|
|
|
|
469 Motor Management Relay
Phase Current Inputs
P1
|
|
|
|
1 A phase CT secondaries
P5
|
|
|
|
5 A phase CT secondaries
Control Power
LO
|
|
|
|
|
|
20 to 60 V DC;
20 to 48 V AC at 48 to 62 Hz
HI
|
|
|
|
|
|
90 to 300 V DC;
70 to 265 V AC at 48 to 62 Hz
Analog Outputs
A1
|
|
Four (4) 0 to 1 mA analog outputs
A20
|
|
Four (4) 4 to 20 mA analog outputs
Display
|
|
Discontinued: Basic display
E
|
Enhanced display, larger LCD
T
|
Enhanced with Ethernet (10Base-T)
D
|
Enhanced display with DeviceNet
Harsh Environment
H
Harsh (chemical) environment conformal
coating
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
2.2
Specifications
Specifications are subject to change without notice.
2.2.1
Inputs
ANALOG CURRENT INPUTS
Inputs:..................................................................0 to 1 mA, 0 to 20mA, or 4 to 20 mA (settings)
Input impedance: ..........................................226 Ω ±10%
Conversion range: .........................................0 to 21 mA
Accuracy:............................................................±1% of full scale
Type: .....................................................................passive
Analog in supply: ...........................................+24 V DC at 100 mA max.
Response time: .....................................≤100 ms
DIFFERENTIAL CURRENT INPUTS
CT primary:........................................................1 to 5000A
CT secondary: .................................................1 A or 5 A (settings)
Burden:................................................................<0.2 VA at rated load
Conversion range: .........................................0.02 to 1 × CT primary
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy:............................................................±0.5% of 1 × CT for 5 A
±0.5% of 5 × CT for 1 A
CT withstand: ..................................................1 second at 80 × rated current,
2 seconds at 40 × rated current, continuous at 3 × rated
current
DIGITAL INPUTS
Inputs:..................................................................9 opto-isolated inputs
External switch: ..............................................dry contact < 400 Ω, or open collector NPN transistor
from sensor; 6 mA sinking from internal 4 KΩ pull-up at
24 V DC with Vce < 4 V DC
See Digital Inputs on page 2–11 for additional specifications.
GROUND CURRENT INPUTS
CT primary:........................................................1 to 5000 A
CT secondary: .................................................1 A or 5 A (settings)
Burden:................................................................<0.2 VA at rated load for 1 A or 5 A; <0.25 VA for 50:0.025
CTs
at 25 A
Conversion range: .........................................0.02 to 1 × CT primary
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy:............................................................±0.5% of 1 × CT for 5 A CTs
±0.5% of 5 × CT for 1 A CTs
±0.125 A for 50:0.025 CTs
CT (1 A/5 A) withstand:.................................1 second at 80 × rated current,
2 seconds at 40 × rated current, continuous at 3 × rated
current
CT (50:0.025) withstand: ..............................continuous at 150 mA
PHASE CURRENT INPUTS
CT primary:........................................................1 to 5000 A
CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–7
CT secondary: .................................................1 A or 5 A (specify with order)
Burden:................................................................Less than 0.2 VA at rated load
Conversion range:..........................................0.05 to 20 × CT
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy: ...........................................................at < 2 × CT: ±0.5% of 2 × CT
at ≥ 2 × CT: ±1% of 20 × CT
CT withstand: ..................................................1 second at 80 × rated current,
2 seconds at 40 × rated current, continuous at 3 × rated
current
RTD INPUTS
3 wire RTD Types: ..........................................100 Ω Platinum (DIN.43760), 100 Ω Nickel, 120 Ω Nickel,
10 Ω Copper
RTD sensing current: ....................................5 mA
Isolation:.............................................................36 Vpk (isolated with analog inputs and outputs)
Range:..................................................................–50 to +250°C
Accuracy: ...........................................................±2°C
Lead resistance: .............................................25 Ω Max per lead for Pt and Ni type; 3 Ω Max per lead for
Cu type
No sensor:..........................................................>1000 Ω
Short/low alarm: ............................................<–50°C
TRIP COIL SUPERVISION
Applicable voltage: .......................................20 to 300 V DC / V AC
Trickle current: ................................................2 to 5 mA
VOLTAGE INPUTS
VT ratio:...............................................................1.00 to 300.00:1 in steps of 0.01
VT secondary: .................................................273 V AC (full-scale)
Conversion range: .........................................0.05 to 1.00 × full scale
Nominal frequency: ......................................20 to 70 Hz
Frequency range: ..........................................20 to 120 Hz
Accuracy: ...........................................................±0.5% of full scale
Max. continuous: ...........................................280 V AC
Burden:................................................................>500 kΩ
Sensor supply: ................................................+24 V DC at 20 mA max.
2.2.2
Outputs
ANALOG CURRENT OUTPUT
Type:.....................................................................Active
Range:..................................................................4 to 20 mA, 0 to 1 mA
(must be specified with order)
Accuracy: ...........................................................±1% of full scale
Max. load:...........................................................4 to 20 mA input: 1200 Ω
0 to 1 mA input: 10 kΩ
Isolation:.............................................................36 Vpk (isolated with RTDs and analog inputs)
4 Assignable Outputs:..................................phase A, B, and C current; three-phase average current;
ground current; phase AN (AB), BN (BC), and CN (CA)
voltages; three-phase average voltage; hottest stator
RTD; hottest bearing RTD, hottest other RTD; RTDs 1 to 12;
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
power factor; 3-phase real (kW), apparent (kVA), and
reactive (kvar) power; thermal capacity used; relay
lockout time, current demand; kvar, kW, and kVA demand;
motor load, torque
OUTPUT RELAYS
Relay contacts are unsafe to touch when the 469 is energized! If the output relay
contacts are required for low voltage accessible applications, it is the customer's
responsibility to ensure proper insulation levels.
Configuration: .................................................6 Electromechanical Form C
Contact material: ..........................................silver alloy
Operate time: ..................................................10 ms
Make/carry:.......................................................10 A continuous
30 A for 0.2 s
Max ratings for 100000 operations:
2.2.3
Protection
ACCELERATION TIMER
Pickup: .................................................................transition of no phase current to > overload pickup
Dropout:..............................................................when current falls below overload pickup
Time delay:........................................................1.0 to 250.0 s in steps of 0.1
Timing accuracy: ...........................................±100 ms or ±0.5% of total time (Note 1)
Elements:............................................................Trip
CURRENT UNBALANCE
Unbalance: ........................................................I2 / I1 if Iavg > FLA
I2 / I1 × Iavg / FLA if Iavg < FLA
Range:..................................................................0 to 100% UB in steps of 1
Pickup level:.......................................................4 to 40% UB in steps of 1
Time delay:........................................................1 to 60 s in steps of 1
Pickup accuracy: ...........................................±2%
Timing accuracy: ...........................................±0.5 s or ± 0.5% of total time (Note 1)
Elements:............................................................Trip and Alarm
FREQUENCY
Req’d voltage: .................................................>30% of full scale in phase A
Overfrequency pickup: ...............................25.01 to 70.00 Hz in steps of 0.01
Underfrequency pickup: ............................20.00 to 60.00 Hz in steps of 0.01
Accuracy:............................................................±0.02 Hz
Time delay:........................................................0.0 to 60.0 s in steps of 0.1
VOLTAGE
BREAK
MAX.
LOAD
DC
RESISTIVE
30 V
10 A
300 Ω
125 V
0.5 A
62.5 Ω
250 V
0.3 A
75 Ω
DC
INDUCTIVE L/
R=40ms
30 V
5 A
150 Ω
125 V
0.25 A
31.3 Ω
250 V
0.15 A
37.5 Ω
AC
RESISTIVE
120 V
10 A
2770 VA
250 V
10 A
2770 VA
AC
INDUCTIVE
P.F.=0.4
120 V
4 A
480 VA
250 V
3 A
750 VA
CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–9
Timing accuracy: ...........................................<100 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
GROUND INSTANTANEOUS OVERCURRENT
Pickup level: ......................................................0.1 to 1.0 × CT primary in steps of 0.01
Time delay:........................................................0 to 1000 ms in steps of 10
Pickup accuracy: ...........................................as per ground current input
Operate time (0 ms time delay): ..............<25 ms @ 60 Hz (I > 1.5 x Pickup)*
<30 ms @ 50 Hz (I > 1.5 x Pickup)*
Timing accuracy: ...........................................+50 ms
Elements:............................................................Trip and Alarm
* Applies if Voltage phase A detected, Motor Status Running and frequency within 5% of
nominal (<50ms if these conditions are not met).
JOGGING BLOCK
Starts/hour:.......................................................1 to 5 in steps of 1
Time between starts: ..................................0 to 500 min.
Timing accuracy: ...........................................±0.5 s or ± 0.5% of total time
Elements:............................................................Block
MECHANICAL JAM
Pickup level: ......................................................1.01 to 3.00 × FLA in steps of 0.01 of any one phase,
blocked on start
Time delay:........................................................1 to 30 s in steps of 1
Pickup accuracy: ...........................................as per phase current inputs
Timing accuracy: ...........................................±0.5 s (Note 1)
Elements:............................................................Trip
OVERLOAD / STALL PROTECTION / THERMAL MODEL
Overload curves: ...........................................15 standard overload curves, custom curve, voltage
dependent custom curve for high inertia starting (all
curves time out against average phase current)
Biasing:................................................................Phase unbalance
Hot/cold curve ratio
Stator RTD
Running cool rate
Stopped cool Rate
Line voltage
Overload pickup: ...........................................1.01 to 1.25 (for service factor)
Pickup accuracy: ...........................................as per phase current Inputs
Timing accuracy: ...........................................±100 ms or ±2% of total time (Note 1)
Elements:............................................................Trip and Alarm
OVERVOLTAGE
Pickup level: ......................................................1.01 to 1.10 × rated in steps of 0.01 of any one phase
Time delay:........................................................0.1 to 60.0 s in steps of 0.1
Pickup accuracy: ...........................................as per voltage inputs
Timing accuracy: ...........................................±100 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
PHASE DIFFERENTIAL INSTANTANEOUS OVERCURRENT
Pickup level:.......................................................0.05 to 1.0 × CT primary in steps of 0.01 of any one phase
Time delay:........................................................0 to 1000 ms in steps of 10
Pickup accuracy: ...........................................as per phase differential current inputs
Timing accuracy: ...........................................+50 ms
Elements:............................................................Trip
PHASE SHORT CIRCUIT
Pickup level:.......................................................2.0 to 20.0 × CT primary in steps of 0.1 of any one phase
Time delay:........................................................0 to 1000 ms in steps of 10
Pickup accuracy: ...........................................as per phase current inputs
Operate time (0 ms time delay): ..............<25 ms @ 60 Hz (I > 1.5 x Pickup)*
<30 ms @ 50 Hz (I > 1.5 x Pickup)*
Timing accuracy: ...........................................+50 ms
Elements:............................................................Trip
* Applies if Voltage phase A detected, Motor Status Running and frequency within 5% of
nominal (<50ms if these conditions are not met).
REDUCED VOLTAGE START
Transition level: ..............................................25 to 300% FLA in steps of 1
Transition time: ...............................................1 to 600 s in steps of 1
Transition control: .........................................Current, Timer, Current and Timer
RESTART BLOCK
Time delay:........................................................1 to 50000 s in steps of 1
Timing accuracy: ...........................................±0.5 s or ±0.5% of total time
Elements:............................................................Block
RTD
Pickup: .................................................................1 to 250°C in steps of 1
Pickup hysteresis: ..........................................2°C
Time delay:........................................................4 s
Elements:............................................................Trip and Alarm
UNDERCURRENT
Pickup level:.......................................................0.10 to 0.95 × CT primary in steps of 0.01 of any one
phase
Time delay:........................................................1 to 60 s in steps of 1
Block from start: ............................................0 to 15000 s in steps of 1
Pickup accuracy: ...........................................as per phase current inputs
Timing accuracy: ...........................................±0.5 s or ±0.5% of total time (Note 1)
Elements:............................................................Trip and Alarm
UNDERVOLTAGE
Pickup Level:
Motor starting: .............................................0.60 to 0.99 × Rated in steps of 0.01
Motor running: .............................................0.60 to 0.99 × Rated in steps of 0.01 of any one phase
Time delay:........................................................0.1 to 60.0 s in steps of 0.1
Pickup accuracy: ...........................................as per voltage inputs
Timing accuracy: ...........................................<100 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–11
VOLTAGE PHASE REVERSAL
Configuration: .................................................ABC or ACB phase rotation
Timing Accuracy: ..........................................500 to 700 ms
Elements:............................................................Trip
NOTE
NoteNote 1
NOTE 1
For Timing accuracy specifications marked (Note 1), setpoint "Motor Load Filter Interval"
may increase trip/alarm times. When setpoint is greater than 1 cycle, trip/alarm times
increase 16.7 ms for each additional cycle in the filter interval.
2.2.4
Digital Inputs
DIGITAL COUNTER
Configuration: .................................................assign to digital inputs 1 to 4
Frequency:.............................................≤50 times a second
Range:..................................................................0 to 1 000 000 000
Elements:............................................................Alarm
GENERAL PURPOSE SWITCH
Configuration: .................................................assign to digital inputs 1 to 4
Time delay:........................................................0.1 to 5000.0 s in steps of 0.1
Block from start: ............................................0 to 5000 s in steps of 1
Timing accuracy: ...........................................±250 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
LOAD SHED
Configuration: .................................................assign to digital inputs 1 to 4
Timing accuracy: ...........................................100 ms maximum
Elements:............................................................Trip
PRESSURE SWITCH
Configuration: .................................................assign to digital inputs 1 to 4
Time delay:........................................................0.1 to 100.0 s in steps of 0.1
Block from start: ............................................0 to 5000 s in steps of 1
Timing accuracy: ...........................................±250 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
REMOTE SWITCH
Configuration: .................................................assign to digital inputs1 to 4
Timing accuracy: ...........................................100 ms maximum
Elements:............................................................Trip and Alarm
SPEED SWITCH
Configuration: .................................................assign to digital inputs1 to 4
Time delay:........................................................1.0 to 250.0 s in steps of 0.1
Timing accuracy: ...........................................250 ms maximum
Elements:............................................................Trip
TACHOMETER
Configuration: .................................................assign to digital inputs 1 to 4
Range:..................................................................100 to 7200 RPM
Pulse duty cycle: ............................................>10%
Elements:............................................................Trip and Alarm
VIBRATION SWITCH
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
Configuration: .................................................assign to digital inputs 1 to 4
Time delay:........................................................0.1 to 100.0 s in steps of 0.1
Timing accuracy: ...........................................±250 ms or ±0.5% of total time
Elements:............................................................Trip and Alarm
2.2.5
Monitoring
DEMAND
Metering: ............................................................maximum phase current
three-phase real power
three-phase apparent power
three-phase reactive power
Measurement type: ......................................rolling demand
Demand interval: ...........................................5 to 90 min. in steps of 1
Update rate:......................................................1 minute
Elements:............................................................Alarm
METERED REACTIVE ENERGY CONSUMPTION
Description:.......................................................Continuous total reactive energy consumption
Range:..................................................................0 to 999999.999 Mvar·hours
Timing accuracy: ...........................................±0.5%
Update rate:......................................................5 seconds
METERED REACTIVE ENERGY GENERATION
Description:.......................................................Continuous total reactive energy generation
Range:..................................................................0 to 2000000.000 Mvar·hours
Timing accuracy: ...........................................±0.5%
Update Rate:.....................................................5 seconds
METERED REAL ENERGY CONSUMPTION
Description:.......................................................Continuous total real energy consumption
Range:..................................................................0 to 999999.999 MW·hours
Timing accuracy: ...........................................±0.5%
Update rate:......................................................5 seconds
MOTOR STATUS
Description:.......................................................Event record of motor start
Timing Accuracy:............................................+250 ms
OVERTORQUE
Pickup level:.......................................................0.1 to 999999.9 Nm/ft·lb in steps of 0.1; torque unit is
selectable under torque setup
Time delay:........................................................0.2 to 30.0 s in steps of 0.1
Pickup accuracy: ...........................................±2.0%
Time accuracy:................................................±100 ms or 0.5% of total time
Elements:............................................................Alarm (induction motors only)
POWER FACTOR
Range:..................................................................0.01 lead or lag to 1.00
Pickup level:.......................................................0.99 to 0.05 in steps of 0.01, lead and lag
Time delay:........................................................0.2 to 30.0 s in steps of 0.1
Block from start: ............................................0 to 5000 s in steps of 1
Pickup accuracy: ...........................................±0.02
Timing accuracy: ...........................................±100 ms or ±0.5% of total time (Note 1)
Elements:............................................................Trip and Alarm
CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–13
THREE-PHASE APPARENT POWER
Range:..................................................................0 to 65535 kVA
Accuracy: ...........................................................Iavg < 2 × CT: ±1% of
× 2 × CT × VT × VTfull scale
Iavg > 2 × CT: ±1.5% of
× 20 × CT × VT × VTfull scale
Elements:............................................................Trip and Alarm
THREE-PHASE REACTIVE POWER
Range:..................................................................0 to ±99999 kvar
Pickup level: ......................................................±1 to 25000 kvar in steps of 1
Time delay:........................................................0.2 to 30.0 s in steps of 0.1
Block from start: .............................................0 to 5000 s in steps of 1
Pickup accuracy: ............................................at Iavg < 2 × CT: ±1% of
× 2 × CT × VT × VTfull scale
at Iavg > 2 × CT: ±1.5% of
× 20 × CT × VT × VTfull scale
Timing accuracy: ...........................................±100ms or ± 0.5% of total time (Note 1)
Elements:............................................................Trip and Alarm
THREE-PHASE REAL POWER
Range:..................................................................0 to ±99999 kW
Pickup:.................................................................1 to 25000 kW in steps of 1
Time delay:........................................................1 to 30 s in steps of 1
Block from start: ............................................0 to 15000 s in steps of 1
Pickup Accuracy:............................................at Iavg < 2 × CT:±1% of
× 2 × CT × VT × VTfull scale
at Iavg > 2 × CT±1.5% of
× 20 × CT × VT × VTfull scale
Timing accuracy: ...........................................±0.5 s or ±0.5% of total time (Note 1)
NOTE
NoteNote 1
NOTE 1
For Timing accuracy specifications marked (Note 1), setpoint "Motor Load Filter Interval"
may increase trip/alarm times. When setpoint is greater than 1 cycle, trip/alarm times
increase 16.7 ms for each additional cycle in the filter interval.
2.2.6
Power Supply
CONTROL POWER
Options:...............................................................LO / HI (must be specified with order)
LO range:............................................................20 to 60 V DC
20 to 48 V AC at 48 to 62 Hz
HI range:.............................................................90 to 300 V DC
70 to 265 V AC at 48 to 62 Hz
Power:..................................................................45 VA (max), 25 VA typical
Total loss of voltage ride through time
(0% control power): 16.7 ms
FUSE (HI and LO VOLT)
Current rating: ................................................2.50 A
Type:.....................................................................5 × 20 mm SLO-BLO HRC Littelfuse, high breaking
capacity
Model no.:...........................................................215-02.5
NOTE
Note
An external fuse must be used if the supply voltage exceeds 250 V.
3
3
3
3
3
3
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
2.2.7
CPU
COMMUNICATIONS
RS232 port:........................................................1, front panel, non-isolated
RS485 ports:......................................................2, isolated together at 36 Vpk
Baud rates:........................................................300, 1200, 2400, 4800, 9600, and 19200 (for RS485);
9600 (for RS232)
Parity:...................................................................None, Odd, Even
Ethernet:.............................................................10Base-T RJ45 connector
Modbus TCP/IP
Version 2.0 / IEEE 802.3
MODBUS
Modbus: ..............................................................Modbus® RTU / half-duplex
DEVICENET
Baud rate: ..........................................................125K, 250K, 500K
MAC ID:................................................................0 to 63 range
Connection type: ...........................................Explicit Messages, Poll I/O, Change Of State
ODVA certified
CLOCK
Accuracy:............................................................±5 minutes/month
Supercap backup life: .................................45 days when control power is off
2.2.8
Waveform Capture (Trace Memory)
SAMPLING FREQUENCY
Frequency:.........................................................720 samples per second for 60 Hertz system
600 samples per second for 50 Hertz system
ANALOG WAVEFORMS
Analog Waveforms:.......................................Phase currents Ia, Ib, Ic
Phase differential currents Ia Diff., Ib Diff., Ic Diff.
Ground Current
Phase voltages Van(Vab), Vbn, Vcn(Vcb)
DIGITAL WAVEFORMS
Digital Waveforms:........................................TRIP RELAY
AUX RELAY 2
AUX RELAY 3
ALARM RELAY
BLOCK START RELAY
SELF TEST RELAY
2.2.9
Testing
TYPE TESTING
The table below lists the 469 type tests:
Standard
Test Name
Level
EIA 485
RS485 Communications Test
32 units at 4000 ft.
GE Digital
Energy
Temperature Cycling
–50°C / +80°C
CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–15
PRODUCTION TESTS
Thermal cycling: ............................................Operational test at ambient, reducing to –40°C and then
increasing to 60°C
Dielectric strength: .......................................(order code ’LO’) 550 VAC for 1 second
(order code ’HI’) 2200 VAC for 1 second
DO NOT CONNECT FILTER GROUND TO SAFETY GROUND DURING ANY PRODUCTION
TESTS!
2.2.10 Certification
CERTIFICATION
ACA:.......................................................................conforms to RF emissions for Australia, tick mark
CE:..........................................................................conforms to EN 55011/CISPR 11, EN 50082-2
EN: .........................................................................EN50263 EMC - CE for Europe
FCC:.......................................................................conforms to RF emissions for North America, part 15
IEC:.........................................................................conforms to 1010-1, LVD - CE for Europe
ISO:........................................................................Manufactured under an ISO9001 registered system.
UL:..........................................................................UL listed E83849 for the USA and Canada
IEC 60068-2-38
Composite Temperature/Humidity
65/–10°C at 93% RH
IEC 60255-5
Dielectric Strength
2300 V AC
IEC 60255-5
Impulse Voltage
5 kV
IEC 60255-5
Insulation Resistance
>100 MΩ / 500 V AC / 10 s
IEC 60255-21-1
Sinusoidal Vibration
2 g
IEC 60255-22-1
Damped Oscillatory Burst, 1 MHz
2.5 kV / 1 kV
IEC 60255-22-2
Electrostatic Discharge: Direct
8 kV
IEC 60255-22-3
Radiated RF Immunity
10 V/m
IEC 60255-22-4
Electrical Fast Transient / Burst Immunity
4 kV
IEC 60255-22-5
Surge Immunity
4 kV / 2 kV
IEC 60255-22-6
Conducted RF Immunity, 150 kHz to 80 MHz
10 V/m
IEC 60255-25
Radiated RF Emission
Group 1 Class A
IEC 60255-25
Conducted RF Emission
Group 1 Class A
IEC 60529
Ingress of Solid Objects and Water (IP)
IP40 (front), IP20 (back)
IEC 61000-4-11
Voltage Dip; Voltage Interruption
0%, 40%, 100%
IEEE C37.90.1
Fast Transient SWC
±4 kV
IEEE C37.90.1
Oscillatory Transient SWC
±2.5 kV
IEEE C37.90.3
Electrostatic Discharge: Air and Direct
15 kV / 8 kV
Standard
Test Name
Level
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
2.2.11 Physical
CASE
Type: .....................................................................Fully drawout (automatic CT shorts)
Seal: ......................................................................Seal provision
Mounting:...........................................................Panel or 19-inch rack mount
IP Class:...............................................................IP40-X
PACKAGING
Shipping box:....................................................12” × 11” × 10” (W × H × D)
30.5 cm × 27.9 cm × 25.4 cm
Shipping weight: ............................................17 lbs Max / 7.7 kg
TERMINALS
Low voltage (A, B, C, D terminals):
12 AWG maximum
High voltage (E, F, G, H terminals):
#8 ring lug, 10 AWG wire std.
2.2.12 Environmental
ENVIRONMENT
Ambient operating temperature:
–40°C to +60°C
Ambient storage temperature:
–40°C to +80°C
Humidity:............................................................up to 90%, non-condensing.
Altitude:...............................................................up to 2000 m
Pollution degree: ............................................2
NOTE
Note
At temperatures less than –20°C, the LCD contrast may be impaired.
2.2.13 Long-term Storage
LONG-TERM STORAGE
Environment: ....................................................In addition to the above environmental considerations,
the relay should be stored in an environment that is dry,
corrosive-free, and not in direct sunlight.
Correct storage:..............................................Prevents premature component failures caused by
environmental factors such as moisture or corrosive
gases. Exposure to high humidity or corrosive
environments will prematurely degrade the electronic
components in any electronic device regardless of its use
or manufacturer, unless specific precautions, such as
those mentioned in the Environment section above, are
taken.
NOTE
Note
It is recommended that all relays be powered up once per year, for one hour
continuously, to avoid deterioration of electrolytic capacitors and subsequent relay
failure.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–1
469 Motor Management Relay
Chapter 3: Installation
GE
Grid Solutions
Installation
3.1
Mechanical Installation
3.1.1
Description
The 469 is packaged in the standard GE Grid Solutions SR-series arrangement, which
consists of a drawout unit and a companion fixed case. The case provides mechanical
protection to the unit and is used to make permanent connections to all external
equipment. The only electrical components mounted in the case are those required to
connect the unit to the external wiring. Connections in the case are fitted with
mechanisms required to allow the safe removal of the relay unit from an energized panel
(for example, automatic CT shorting). The unit is mechanically held in the case by pins on
the locking handle that cannot be fully lowered to the locked position until the electrical
connections are completely mated. Any 469 can be installed in any 469 case, except for
custom manufactured units that are clearly identified as such on both case and unit, and
are equipped with an index pin keying mechanism to prevent incorrect pairings.
No special ventilation requirements need to be observed during the installation of the unit.
The 469 can be cleaned with a damp cloth.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
FIGURE 3–1: Dimensions
To prevent unauthorized removal of the drawout unit, a wire lead seal can be installed in
the slot provided on the handle. With this seal in place, the drawout unit cannot be
removed. A passcode or settings access jumper can be used to prevent entry of settings
but allow monitoring of actual values. If access to the front panel controls must be
restricted, a separate seal can be installed on the cover to prevent it from being opened.
Hazard may result if the product is not used for its intended purpose.
FIGURE 3–2: Seal on Drawout Unit
3.1.2
Product Identification
Each 469 unit and case are equipped with a permanent label. This label is installed on the
left side (when facing the front of the relay) of both unit and case. The case label details
which units can be installed.
The case label details the following information: model number, manufacture date, and
special notes.
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–3
The unit label details the following information: model number, type, serial number,
manufacture date, phase current inputs, special notes, overvoltage category, insulation
voltage, pollution degree, control power, and output contact rating.
FIGURE 3–3: Case and Unit Identification Labels
3.1.3
Installation
The 469 case, alone or adjacent to another SR-series unit, can be installed in the panel of a
standard 19-inch rack (see below for panel cutout dimensions). Provision must be made
when mounting for the front door to swing open without interference to, or from, adjacent
equipment. Normally the 469 unit is mounted in its case when shipped from the factory,
and should be removed before mounting the case in the supporting panel. Unit withdrawal
is described in the next section.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
FIGURE 3–4: Single 469 Cutout Panel
FIGURE 3–5: Double 469 Cutout Panel
After the mounting hole in the panel has been prepared, slide the 469 case into the panel
from the front. Applying firm pressure on the front to ensure the front bezel fits snugly
against the front of the panel, bend out the pair of retaining tabs (to a horizontal position)
from each side of the case as shown below. The case is now securely mounted, ready for
panel wiring. If additional support is desired, the SR optional mounting kit may be ordered.
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–5
FIGURE 3–6: Bend Up Mounting Tabs
3.1.4
Unit Withdrawal and Insertion
TURN OFF CONTROL POWER BEFORE DRAWING OUT OR RE-INSERTING THE RELAY TO
PREVENT MALOPERATION!
If an attempt is made to install a unit into a non-matching case, the mechanical key
will prevent full insertion of the unit. Do not apply strong force in the following step or
damage may result.
To remove the unit from the case:
Open the cover by grasping the center of the right side and then
pulling the cover, which will rotate about the hinges on the left.
Release the locking latch, located below the locking handle, by
pressing upward on the latch with the tip of a screwdriver.
FIGURE 3–7: Press Latch to Disengage Handle
808704A1.CDR
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
While holding the latch raised, grasp the locking handle in the center
and pull firmly, rotating the handle up from the bottom of the unit
until movement ceases.
FIGURE 3–8: Rotate Handle to Stop Position
Once the handle is released from the locking mechanism, the unit can freely slide
out of the case when pulled by the handle. It may sometimes be necessary to
adjust the handle position slightly to free the unit.
FIGURE 3–9: Slide Unit out of Case
To insert the unit into the case:
Raise the locking handle to the highest position.
Hold the unit immediately in front of the case and align the rolling
guide pins (near the hinges of the locking handle) to the guide slots
on either side of the case.
Slide the unit into the case until the guide pins on the unit have
engaged the guide slots on either side of the case.
Grasp the locking handle from the center and press down firmly,
rotating the handle from the raised position toward the bottom of
the unit.
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–7
When the unit is fully inserted, the latch will be heard to click, locking the handle in
the final position.
No special ventilation requirements need to be observed during the installation of the
unit. The unit does not require cleaning.
3.1.5
Ethernet Connection
If using the 469 with the Ethernet 10Base-T option, ensure that the network cable is
disconnected from the rear RJ45 connector before removing the unit from the case. This
prevents any damage to the connector.
The unit may also be removed from the case with the network cable connector still
attached to the rear RJ45 connector, provided that there is at least 16" of network cable
available when removing the unit from the case. This extra length allows the network cable
to be disconnected from the RJ45 connector from the front of the switchgear panel. Once
disconnected, the cable can be left hanging safely outside the case for re-inserting the unit
back into the case.
The unit may then be re-inserted by first connecting the network cable to the units' rear
RJ45 connector (see step 3 of Unit Withdrawal and Insertion on page 3–5).
Ensure that the network cable does not get caught inside the case while sliding in the
unit. This may interfere with proper insertion to the case terminal blocks and damage
the cable.
FIGURE 3–10: Ethernet Cable Connection
To ensure optimal response from the relay, the typical connection timeout should be set as
indicated in the following table:
TCP/IP sessions
Timeout setting
up to 2
2 seconds
up to 4
3 seconds
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
3.1.6
DeviceNet Connection
If using the 469 DeviceNet option (Refer to GEK-106491C: 469 Communications Guide),
ensure that the network cable is disconnected from the rear terminal block before
removing the unit out of the case to prevent any damage to the connector.
The unit may also be removed from the case with the network cable connector still
attached to the rear terminal block provided that there is at least 16" of network cable
available when removing the unit out of the case. This extra length will allow the network
cable to be disconnected from the terminal block from the front of the switchgear panel.
Once disconnected, the cable can be left hanging safely outside the case for re-inserting
the unit back into the case.
The unit may then be re-inserted by first connecting the network cable to the units' rear
terminal block (see step 3 of Unit Withdrawal and Insertion on page 3–5).
Ensure that the network cable does not get caught inside the case while sliding in the
unit. This may interfere with proper insertion to the case terminal blocks and damage
the cable.
The DeviceNet port has the following characteristics:
•
Connector type: 5-pin Phoenix connector
•
Baud rate: 125K, 250K or 500K baud
•
Protocol: DeviceNet
The following ports available simultaneously:
•
RS232, 2 × RS485/422 with no DeviceNet option
•
RS232, 1 × RS485/422 with DeviceNet option
The DeviceNet configuration is shown in the following table:
Pin
Signal
Description
1
V–
Negative supply voltage
2
CAN_L
CAN_L bus line
3
SHIELD
Cable shield
4
CAN_H
CAN_H bus line
5
V+
Positive supply voltage
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–9
3.1.7
Terminal Locations
FIGURE 3–11: Terminal Layout
3.1.8
Terminal List
Table 3–1: 469 Terminal List
Terminal
Description
Terminal
Description
A01
RTD #1 Hot
D21
Assignable Switch 3
A02
RTD #1 Compensation
D22
Assignable Switch 4
A03
RTD Return
D23
Switch Common
A04
RTD #2 Compensation
D24
Switch +24 V DC
A05
RTD #2 Hot
D25
Computer RS485 +
A06
RTD #3 Hot
D26
Computer RS485 –
A07
RTD #3 Compensation
D27
Computer RS485 Common
A08
RTD Return
E01
1 Trip NC
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
A09
RTD #4 Compensation
E02
1 Trip NO
A10
RTD #4 Hot
E03
2 Auxiliary Common
A11
RTD #5 Hot
E04
3 Auxiliary NC
A12
RTD #5 Compensation
E05
3 Auxiliary NO
A13
RTD Return
E06
4 Alarm COMMON
A14
RTD #6 Compensation
E07
5 Block Start NC
A15
RTD #6 Hot
E08
5 Block Start NO
A16
Analog Output Common –
E09
6 Service Common
A17
Analog Output 1 +
E10
not used
A18
Analog Output 2 +
E11
Coil Supervision +
A19
Analog Output 3 +
E12
469 Drawout Indicator
A20
Analog Output 4 +
F01
1 Trip Common
A21
Analog Shield
F02
2 Auxiliary NO
A22
Analog In 24 V DC Power Supply +
F03
2 Auxiliary NC
A23
Analog Input 1 +
F04
3 Auxiliary COMMON
A24
Analog Input 2 +
F05
4 Alarm NO
A25
Analog Input 3 +
F06
4 Alarm NC
A26
Analog Input 4 +
F07
5 Block Start Common
A27
Analog Input Common –
F08
6 Service NO
B01
RTD Shield
F09
6 Service NC
B02
Auxiliary RS485 +
F10
not used
B03
Auxiliary RS485 –
F11
Coil Supervision –
B04
Auxiliary RS485 Common
F12
469 Drawout Indicator
C01
Access +
G01
Phase VT Neutral
C02
Access –
G02
Phase A VT •
C03
469 Under Test +
G03
Differential A CT •
C04
469 Under Test –
G04
Differential B CT •
D01
RTD #7 Hot
G05
Differential C CT •
D02
RTD #7 Compensation
G06
Phase A CT •
D03
RTD Return
G07
Phase B CT •
D04
RTD #8 Compensation
G08
Phase C CT •
D05
RTD #8 Hot
G09
1A/5A Ground CT •
D06
RTD #9 Hot
G10
50:0.025 Ground CT •
D07
RTD #9 Compensation
G11
Filter Ground
D08
RTD Return
G12
Safety Ground
D09
RTD #10 Compensation
H01
Phase B VT •
D10
RTD #10 Hot
H02
Phase C VT •
D11
RTD #11 Hot
H03
Differential A CT
D12
RTD #11 Compensation
H04
Differential B CT
D13
RTD Return
H05
Differential C CT
D14
RTD #12 Compensation
H06
Phase A CT
D15
RTD #12 Hot
H07
Phase B CT
D16
Starter Status
H08
Phase C CT
D17
Emergency Restart
H09
1A/5A Ground CT
D18
Remote Reset
H10
50:0.025 Ground CT
D19
Assignable Switch 1
H11
Control Power –
D20
Assignable Switch 2
H12
Control Power +
Table 3–1: 469 Terminal List
Terminal
Description
Terminal
Description
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–11
3.2
Electrical Installation
3.2.1
Typical Wiring
FIGURE 3–12: Typical Wiring Diagram
���
��������
����������������
���������
����
����
����
�����
�
�
�
�
�
�
�
�
�
�
�
��
�
�
�
�
�
�
�
�
�
�
�
�
�
�
��
���������
�����
������
����
����
����
������
������
������
������
�������
�
�
�����
������������
������������������
�������
�������
���
���
���
���
���
���
�����
����
�����
����������
����������
����������
����������
����������
����������
����
����
���
���������
������������
��
��
���
��
��
��
��
��
��
����
���
��� ���
��
��
��
�����������
������
��
��
��
��
��
��
��
��
��
�������
�����������
�����
���������
�������
������
���
��������������
�������
��
���
�������
��
���
��
�����
��
�����
�������
��
���
��
�����
��
�����
�������������������
�������
�������
��
��
�����
��
��
�����
���
�������
�����
��
��
���
��
���
������
��
��
��
������
������
��
��
��
��
��
��
���
������
������
������
���
���
���
���
���
��
��
��������������
���
��
��
���
���
���
���
���
��
�
������������
�
������������������
������������������
������������������
������������������
�����������������
��������������
���
��
������
���
�
��������
�����
�����
���������
��
�
�
��
���
�
���
��
��
���
���
������
������
��
��
��
��
��
��
��
������
�������
���
���
���
���
���
���
��
���
��
����������
�
���
���
���
���
������
���
���
�������������
���
��
��
���
��
���
�������
�������
�����������������
����������������
�����
�����
�������
�����
������������������������
�����
�
�
�������
����
���
��
��������
������
������
�����
���
���
���
���
������
����������������
�����
�����������
��
������������
��������
��������
�����
���
���
���
������
�������
��������������
���
���
������������
����������
���
���
����������
����������
���
����������
���
����������
���
����������
���
����������
���
���
���
���
���
������
������������
������������
������������
������������
������������
������������
������������
������������
������������
������������
������������
������������
��
��
���
���
���������������������
�����������������
�
�
�����
�������
���������
�
�
��
��
������
����
�����
�������
�
�����
�������
�
�����
�������
�
�����
�������
�
�����
�������
�
�����
�������
�
�������
�����
�
�������
�����
�
����
�������
�
����
�������
�
����
����
�������
���
���
�����
��������
�
�
�
�
�����
��������
�
�
����
�
�
����
��������
��������
���
��
���
�������������
���
���
����������
���
���������������������
����������
�����
���
������
�
�
������
���
��
��
����
��
��������������
�
�
�
�
�
�
�������
�����
����������������������������������
�������
���
���������
���
�����������
���
���
���������
�������
���������������
�������������
�������������
��������������������
�������������
�����
�����
�����
����������������
������������������
������
���������������
������������
��������������������
�����������
�������������
����������������������
���
���
���
�������������������
���������������������
������
���
���
��
�����
������
�����
��
�
�
�
�
�
����������
��
���������
������
���
��������
����������
�����
�����������
��������������������������
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
3.2.2
Description
A broad range of 469 applications are available. Although it is not possible to present
typical connections for all possible schemes, this section will cover the interconnections of
instrument transformer inputs, other inputs, outputs, communications, and grounding. See
FIGURE 3–11: Terminal Layout on page 3–9 and Table 3–1: 469 Terminal List on page 3–9
for terminal arrangement.
3.2.3
Control Power
The order code from the terminal label on the side of the drawout unit specifies the
nominal control voltage as follows:
LO: 20 to 60 V DC; 20 to 48 V AC, or
HI: 90 to 300 V DC; 70 to 265 V AC
Ensure applied control voltage and rated voltage on drawout case terminal label match.
For example, the HI power supply will work with any DC voltage from 90 to 300 V, or AC
voltage from 70 to 265 V. The internal fuse may blow if the applied voltage exceeds this
range.
The 469 control power must match the installed switching power supply. If the applied
voltage does not match, damage to the unit may occur!
FIGURE 3–13: Control Power Connection
Extensive filtering and transient protection are built into the 469 to ensure proper
operation in harsh industrial environments. Transient energy must be conducted back to
the source through the filter ground terminal. A separate safety ground terminal is
provided for hi-pot testing.
All grounds MUST be hooked up for normal operation regardless of control power
supply type.
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–13
3.2.4
Current Inputs
Phase Current Inputs
The 469 has three channels for phase current inputs, each with an isolating transformer.
There are no internal ground connections on the current inputs. If the unit is withdrawn,
each phase CT circuit is shorted by automatic mechanisms on the 469 case. The phase CTs
should be chosen so the FLA is no less than 50% of the rated phase CT primary. Ideally, the
phase CT primary should be chosen such that the FLA is 100% of the phase CT primary or
slightly less, never more. This will ensure maximum accuracy for the current
measurements. The maximum phase CT primary current is 5000 A.
The 469 correctly measures up to 20 times the phase current nominal rating. Since the
conversion range is large, 1 A or 5 A CT secondaries must be specified at the time of order
to ensure the appropriate interposing CT is installed in the unit. The chosen CTs must be
capable of driving the 469 phase CT burden (see Specifications on page 2–6 for ratings).
Verify that the 469 nominal phase current of 1 A or 5 A matches the secondary rating
and connections of the connected CTs. Unmatched CTs may result in equipment
damage or inadequate protection. Polarity of the phase CTs is critical for Negative
Sequence Unbalance calculation, power measurement, and residual ground current
detection (if used).
See Two-Phase CT Configuration on page 8–1 for 2-phase CT information.
Ground Current Input
The 469 has a dual primary isolating transformer for ground CT connection. There are no
internal ground connections on the ground current inputs. The ground CT circuits are
shorted by automatic mechanisms on the 469 case if the unit is withdrawn. The 1 A / 5 A
tap is used either for zero-sequence / core balance applications or residual ground
connections where the summation of the three phase current CTs is passed through the
ground current input (see the figure below). The maximum ground CT primary current is
5000 A for the 1 A / 5 A tap. Alternatively, the 50:0.025 ground CT input has been designed
for sensitive ground current detection on high resistance grounded systems where the
GE Grid Solutions 50:0.025 core-balance CT is to be used. For example, in mining
applications where earth leakage current must be measured for personnel safety, primary
ground current as low as 0.25 A may be detected with the GE Grid Solutions 50:0.025 CT.
Only one ground CT input tap should be used on a given unit.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
FIGURE 3–14: Residual Ground CT Connection
The 469 measures up to 5 A secondary current if the 1 A / 5 A tap is used. Since the
conversion range is relatively small, the 1 A or 5 A option is field programmable. Proper
selection of this settings ensures proper reading of primary ground current. The 1 A / 5 A
ground CT chosen must be capable of driving the 469 ground CT burden (see Specifications
on page 2–6). The 469 measures up to 25 A of primary ground current if this tap is used in
conjunction with the GE Grid Solutions core balance CT.
NOTE
Note
The zero-sequence connection is recommended. Unequal saturation of CTs, size and
location of motor, resistance of power system and motor core saturation density, etc.,
may cause false readings in the residually connected GF circuit.
NOTE
Note
Only one ground input should be wired – the other input should be unconnected.
The exact placement of a zero-sequence CT to detect only ground fault current is shown
below. If the core balance CT is placed over shielded cable, capacitive coupling of phase
current into the cable shield during motor starts may be detected as ground current unless
the shield wire is also passed through the CT window. Twisted pair cabling on the zero-
sequence CT is recommended.
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–15
FIGURE 3–15: Core Balance Ground CT Installation – Unshielded Cable
FIGURE 3–16: Core Balance Ground CT Installation – Shielded Cable
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
Differential Current Inputs
The 469 has three channels for differential current inputs, each with an isolating
transformer. There are no internal ground connections on the current inputs. Each
differential CT circuit is shorted by automatic mechanisms on the 469 case if the unit is
withdrawn. The maximum differential CT primary current is 5000 A.
The 469 measures up to 5 A secondary current for the differential CT inputs. Since the
conversion range is relatively small, the 1 A or 5 A option is field programmable. Proper
selection of this settings ensures proper reading of primary phase differential current. The
1 A / 5 A differential CT chosen must be capable of driving the 469 differential CT burden
(see Specifications on page 2–6 for ratings).
The differential CTs may be core balance as shown in the first figure below. Alternatively,
the summation of two CTs per phase into the differential input will provide a larger zone of
protection. If the summation of two CTs is used, observation of CT polarity is important. The
summation method may also be implemented using the phase CTs as shown below. They
will have to have the same CT ratio.
FIGURE 3–17: Core Balance Method
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–17
FIGURE 3–18: Summation Method with Phase CTs
FIGURE 3–19: Summation Method without Phase CTs (Phase CTs wiring is shown in Figure 3-12)
3.2.5
Voltage Inputs
The 469 has three channels for AC voltage inputs, each with an isolating transformer. There
are no internal fuses or ground connections on the voltage inputs. The maximum VT ratio is
300.00:1. The two VT connections are open delta (see FIGURE 3–12: Typical Wiring Diagram
on page 3–11) or wye (see below). The voltage channels are connected in wye internally,
which means that the jumper shown on the delta-source connection of the typical wiring
diagram, between the phase B input and the 469 neutral terminal, must be installed for
open delta VTs.
C
B
A
COM
GROUND
CURRENT INPUTS
PHASE C
1A/5A
1A/5A
COM
PHASE A
COM
1A/5A
PHASE B
1A/5A
GROUND
COM
COM
DIFFERENTIAL INPUTS
PHASE A
COM
1A/5A
COM
1A/5A
PHASE B
806846A3.DWG
COM
1A/5A
PHASE C
H10
G8
G6
H6
G7
H7
H8
G9
H9
G10
PHASE C CT
PHASE A CT
PHASE B CT
MOTOR
H3
G3
G4
H4
G5
H5
PHASE B CT
DIFF.
PHASE A CT
PHASE C CT
DIFF.
DIFF.
50:.025
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
Polarity of the VTs is critical for correct power measurement and voltage phase reversal
operation.
A 1 A fuse is typically used to protect the inputs.
FIGURE 3–20: Wye Voltage Transformer Connection
3.2.6
Digital Inputs
NOTE
Note
The digital inputs of the 469 relay are designed for dry contact connection. In an
application where the contact inputs need to be connected to the 469 relay digital inputs
using long cable, it is recommended that you use interposing auxiliary contacts to
interface between the 469 relay and the long digital input cable. This will help prevent the
relay falsely sensing the digital input as "closed" due to induced voltage on the cables as a
result of the capacitive effect. It is recommended that you use shielded twisted pair wires
grounded at one end only, for digital inputs and avoid locating these wires in close to
current carrying cables, contactors or other sources of high EMI.
DO NOT INJECT VOLTAGES TO DIGITAL INPUTS. DRY CONTACT CONNECTIONS ONLY.
There are 9 digital inputs designed for dry contact connections only. Two of the digital
inputs (Access and Test) have their own common terminal; the balance of the digital inputs
share one common terminal (see FIGURE 3–12: Typical Wiring Diagram on page 3–11).
In addition, the +24 V DC switch supply is brought out for control power of an inductive or
capacitive proximity probe. The NPN transistor output could be taken to one of the
assignable digital inputs configured as a counter or tachometer. Refer to Specifications on
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–19
page 2–6 for maximum current draw from the +24 V DC switch supply.
3.2.7
Analog Inputs
The 469 provides terminals for four 0 to 1mA, 0 to 20mA, or 4 to 20mA current input signals
(field programmable). This current signal can be used to monitor external quantities such
as vibration, pressure, or flow. The four inputs share one common return. Polarity of these
inputs must be observed for proper operation The analog input circuitry is isolated as a
group with the analog output circuitry and the RTD circuitry. Only one ground reference
should be used for the three circuits. Transorbs limit this isolation to ±36 V with respect to
the 469 safety ground.
In addition, the +24 V DC analog input supply is brought out for control power of loop
powered transducers. Refer to Specifications on page 2–6 for maximum current draw from
this supply.
FIGURE 3–21: Loop Powered Transducer Connection
3.2.8
Analog Outputs
The 469 provides 4 analog output channels which may be ordered to provide a full-scale
range of either 0 to 1 mA (into a maximum 10 kΩ impedance) or 4 to 20 mA (into a
maximum 1200 Ω impedance). Each channel can be configured to provide full-scale
output sensitivity for any range of any measured parameter.
As shown in FIGURE 3–12: Typical Wiring Diagram on page 3–11, these outputs share one
common return. Polarity of these outputs must be observed for proper operation. Shielded
cable should be used, with only one end of the shield grounded, to minimize noise effects.
The analog output circuitry is isolated as a group with the Analog Input circuitry and the
RTD circuitry. Only one ground reference should be used for the three circuits. Transorbs
limit this isolation to ±36 V with respect to the 469 safety ground.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
If a voltage output is required, a burden resistor must be connected at the input of the
SCADA measuring device. Ignoring the input impedance of the input, Rload = Vfull scale / Imax.
For 0 to 1 mA, for example, if 5 V full scale is required to correspond to 1 mA, Rload = 5 V /
0.001 A = 5000 Ω. For 4 to 20 mA, this resistor would be Rload = 5 V / 0.020 A = 250 Ω.
3.2.9
RTD Sensor Connections
Description
The 469 monitors up to 12 RTD inputs for Stator, Bearing, Ambient, or Other temperature
monitoring. The type of each RTD is field programmable as 100 Ω Platinum (DIN 43760),
100 Ω Nickel, 120 Ω Nickel, or 10 Ω Copper. RTDs must be three wire type. Every two RTDs
shares a common return.
The RTD circuitry compensates for lead resistance, provided that each of the three leads is
the same length. Lead resistance should not exceed 25 Ω per lead for platinum/nickel
RTDs or 3 Ω per lead for copper RTDs. Shielded cable should be used to prevent noise
pickup in the industrial environment. RTD cables should be kept close to grounded metal
casings and away from areas of high electromagnetic or radio interference. RTD leads
should not be run adjacent to or in the same conduit as high current carrying wires.
FIGURE 3–22: RTD Wiring
NOTE
Note
IMPORTANT: The RTD circuitry is isolated as a group with the Analog Input circuitry and
the Analog Output circuitry. Only one ground reference should be used for the three
circuits. Transorbs limit this isolation to ±36 V with respect to the 469 safety ground.
Reduced RTD Lead Number Application
The 469 requires three leads to be brought back from each RTD: Hot, Return and
Compensation. This can be quite expensive. It is however possible to reduce the number of
leads required to 3 for the first RTD and 1 for each successive RTD. Refer to the figure
below for wiring configuration for this application.
�����
� ���� �������� �����
��� ���������
�� �����
������� ����� ���� ����������
�� ���� ��������� � ������ �����
� ���� ������� �����
����� ����� �� �������� ������� ����
������� �������� ����������
��� ��
�����
������
��
�������
������������
��
��
��
���
��
������������
������
�������
������
������
��� �������
��� ��
���
�����
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–21
FIGURE 3–23: Reduced Wiring RTDs
The Hot line would have to be run as usual for each RTD. The Compensation and Return
leads, however, need only be run for the first RTD. At the motor RTD terminal box, the RTD
Return leads must be jumpered together with as short as possible jumpers. The
Compensation leads must be jumpered together at the 469.
Note that an error is produced on each RTD equal to the voltage drop across the jumper on
the RTD return. This error increases with each successive RTD added.
VRTD1 = VRTD1
VRTD2 = VRTD2 + VJ3
VRTD3 = VRTD3 + VJ3 + VJ4, etc.
This error is directly dependent on the length and gauge of the wire used for the jumpers
and any error introduced by a poor connection. For RTD types other than 10 Ω Copper, the
error introduced by the jumpers is negligible. Although this RTD wiring technique reduces
the cost of wiring, the following disadvantages must be noted:
1.
There will be an error in temperature readings due to lead and connection resistances.
This technique is NOT recommended for 10 Ω Copper RTDs.
2.
If the RTD Return lead to the 469 or any of the jumpers break, all RTDs from the point
of the break will read open.
3.
If the Compensation lead or any of the jumpers break, all RTDs from the point of the
break will function without any lead compensation.
Two-Wire RTD Lead Compensation
An example of how to add lead compensation to a two wire RTD may is shown in the figure
below.
808722A2.CDR
Hot
Compensation
RTD Return
Compensation
Hot
Hot
Compensation
RTD Return
A1
A2
A3
A4
A5
A6
A7
A8
L1
L2
L3
L4
L5
L6
L7
No connection
469
J1
J2
Motor Control
Terminal Box
Motor
RTD1
+
–
RTD2
+
–
RTD3
+
–
J3
J4
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
FIGURE 3–24: 2-Wire RTD Lead Compensation
The compensation lead L2 is added to compensate for Hot (L1) and Return (L3), assuming
they are all of equal length and gauge. To compensate for leads RL1 and RL2, a resistor
equal to the resistance of RL1 or RL2 could be added to the compensation lead, though in
many cases this is unnecessary.
RTD Grounding
Grounding of one lead of the RTDs is done at either the 469 or at the motor. Grounding
should not be done in both places as it could cause a circulating current. Only RTD Return
leads may be grounded. When grounding at the 469, only one Return lead need be
grounded as they are hard-wired together internally. No error is introduced into the RTD
reading by grounding in this manner.
If the RTD Return leads are tied together and grounded at the motor, only one RTD Return
lead can be run back to the 469. See the figure below for a wiring example. Running more
than one RTD Return lead to the 469 causes significant errors as two or more parallel
paths for the return current have been created. Use of this wiring scheme causes errors in
readings equivalent to that in the Reduced RTD Lead Number application described earlier.
FIGURE 3–25: RTD Alternate Grounding
3.2.10 Output Relays
There are six (6) Form-C output relays (see Specifications on page 2–6 for details). Five of
the six relays are always non-failsafe; 6 SERVICE is always failsafe. As failsafe, the
6 SERVICE relay is normally energized and de-energizes when called upon to operate. It
also de-energizes when 469 control power is lost and will be in its operated state. All other
808719A1.CDR
469
Motor Control
Terminal Box
Motor
Hot
Compensation
RTD Return
A1
A2
A3
L1
L2
L3
Rcomp
RTD1
RL1
RL2
+
–
808720A2.CDR
469
Motor Control
Terminal Box
Motor
Hot
Compensation
RTD Return
A1
A2
A3
L1
L2
L3
Compensation
Hot
Hot
Compensation
RTD Return
A4
A5
A6
A7
A8
L4
L5
L6
L7
No connection
RTD1
+
–
RTD2
+
–
RTD3
+
–
J1
J2
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–23
relays, being non-failsafe, will normally be de-energized and energize when called upon to
operate. When the 469 control power is lost, these relays are de-energized and in their
non-operated state. Shorting bars in the drawout case ensure that no trip or alarm occurs
when the 469 is drawn out. However, the 6 SERVICE output will indicate that the 469 has
been drawn out. Each output relay has an LED indicator on the front panel that turns on
when the associated relay is in the operated state.
Relay contacts must be considered unsafe to touch when the 469 is energized! If the
output relay contacts are required for low voltage accessible applications, it is the
customer's responsibility to ensure proper insulation levels.
•
1 TRIP: The trip relay should be wired to take the motor off line when conditions
warrant. For a breaker application, the normally-open 1 TRIP contact should be wired
in series with the Breaker trip coil. For contactor applications, the normally-closed
1 TRIP contact should be wired in series with the contactor coil.
Supervision of a breaker trip coil requires that the supervision circuit be in parallel with
the 1 TRIP relay output contacts. With this connection made, the supervision input
circuits place an impedance across the contacts that draws a 2 mA current (for an
external supply voltage from 30 to 250 V DC) through the breaker trip coil. The
supervision circuits respond to a loss of this trickle current as a failure condition.
Circuit breakers equipped with standard control circuits have a breaker auxiliary
contact permitting the trip coil to be energized only when the breaker is closed. When
these contacts are open, as detected by the Starter Status Digital Input monitoring
breaker auxiliary contacts, trip coil supervision circuit is automatically disabled. This
logic allows the trip circuit to be monitored only when the breaker is closed.
•
2 AUXILIARY, 3 AUXILIARY: The auxiliary relays may be programmed for trip echo,
alarm echo, trip backup, alarm differentiation, control circuitry, and numerous other
functions. They should be wired as configuration warrants.
•
4 ALARM: The alarm relay should connect to the appropriate annunciator or
monitoring device.
•
5 BLOCK START: This relay should be wired in series with the start pushbutton in either
a breaker or contactor configuration to prevent motor starting. When a trip has not
been reset on a breaker, the block start relay prevents a start attempt that would
result in an immediate trip. Any lockout functions are also directed to the block start
relay.
•
6 SERVICE: The service relay operates if any of the 469 diagnostics detect an internal
failure or on loss of control power. This output may be monitored with an annunciator,
PLC or DCS. If it is deemed that a motor is more important than a process, the service
relay normally-closed contact may also be wired in parallel with the trip relay on a
breaker application or the normally-open contact may be wired in series with the trip
relay on a contactor application. This will provide failsafe operation of the motor; that
is, the motor will be tripped off line in the event that the 469 is not protecting it. If
however, the process is critical, annunciation of such a failure will allow the operator
or the operation computer to either continue, or do a sequenced shutdown. See the
following figure for details.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
FIGURE 3–26: Alternate Wiring for Contactors
3.2.11 Drawout Indicator
The Drawout Indicator is simply a jumper from terminals E12 to F12. When the 469 is
withdrawn from the case, terminals E12 and F12 are open. This may be useful for
differentiating between loss of control power as indicated by the 6 SERVICE relay and
withdrawal of the unit.
3.2.12 RS485 Communications Ports
Two independent two-wire RS485 ports are provided. Up to 32 469s can be daisy-chained
together on a communication channel without exceeding the driver capability. For larger
systems, additional serial channels must be added. Commercially available repeaters can
also be used to add more than 32 relays on a single channel. Suitable cable should have a
characteristic impedance of 120 Ω (e.g. Belden #9841) and total wire length should not
exceed 4000 ft. Commercially available repeaters will allow for transmission distances
greater than 4000 ft.
Voltage differences between remote ends of the communication link are not uncommon.
For this reason, surge protection devices are internally installed across all RS485 terminals.
Internally, an isolated power supply with an optocoupled data interface is used to prevent
noise coupling.
NOTE
Note
To ensure that all devices in a daisy-chain are at the same potential, it is imperative
that the common terminals of each RS485 port are tied together and grounded only
once, at the master. Failure to do so may result in intermittent or failed
communications.
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–25
The source computer/PLC/SCADA system should have similar transient protection devices
installed, either internally or externally, to ensure maximum reliability. Ground the shield at
one point only, as shown in the figure below, to avoid ground loops.
Correct polarity is also essential. The 469s must be wired with all the ‘+’ terminals
connected together and all the ‘–’ terminals connected together. Each relay must be daisy-
chained to the next one. Avoid star or stub connected configurations. The last device at
each end of the daisy chain should be terminated with a 120 Ω ¼-watt resistor in series
with a 1 nF capacitor across the ‘+’ and ‘–’ terminals. Observing these guidelines provides a
reliable communication system immune to system transients.
FIGURE 3–27: RS485 Communications Wiring
3.2.13 Dielectric Strength
It may be required to test a complete motor starter for dielectric strength (“flash” or “hipot”)
with the 469 installed. The 469 is rated for 1.9 kV AC for 1 second, or 1.6 kV AC for 1 minute
(per UL 508) isolation between relay contacts, CT inputs, VT inputs, trip coil supervision, and
the safety ground terminal G12. Some precautions are required to prevent damage to the
469 during these tests.
Filter networks and transient protection clamps are used between control power, trip coil
supervision, and the filter ground terminal G11. This is intended to filter out high voltage
transients, radio frequency interference (RFI), and electromagnetic interference (EMI). The
filter capacitors and transient suppressors may be damaged by continuous high voltage.
Disconnect the filter ground terminal G11 during testing of control power and trip coil
supervision. The CT inputs, VT inputs, and output relays do not require any special
precautions. Low voltage inputs (less than 30 V), RTDs, analog inputs, analog outputs,
digital inputs, and RS485 communication ports are not to be tested for dielectric strength
under any circumstance (see below).
������������
�����������������
�����������������
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
FIGURE 3–28: Testing for Dielectric Strength
CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–27
3.2.14 2-Speed Motor Wiring
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
4–1
469 Motor Management Relay
Chapter 4: Interfaces
GE
Grid Solutions
Interfaces
4.1
Faceplate Interface
4.1.1
Description
The front panel provides local operator interface with a liquid crystal display, LED status
indicators, control keys, and program port. The display and status indicators update alarm
and status information automatically. The control keys are used to select the appropriate
message for entering settings or displaying measured values. The RS232 program port is
also provided for connection with a computer running the EnerVista 469 Setup software.
4.1.2
Display
The 40-character liquid crystal display allows visibility under varied lighting conditions.
While the keypad and display are not being used, the screen will display system
information by scrolling through a maximum of 20 user-selected default messages. These
default messages will only appear after a user programmed period of inactivity. Pressing
any key during default message scrolling will return the display to the last message shown
before the default messages appeared. Any trip, alarm, or start block is displayed
immediately, automatically overriding the default messages.
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
4.1.3
LED Indicators
There are three groups of LED indicators. They are 469 Status, Motor Status, and Output
Relays.
FIGURE 4–1: 469 LED INDICATORS
469 Status LED Indicators
•
469 IN SERVICE: This LED indicates that control power is applied, all monitored
inputs/outputs and internal systems are OK, the 469 has been programmed, and
the 469 is in protection mode, not simulation mode. This LED flashes when the 469
is in simulation or testing mode.
•
SETPOINT ACCESS: This LED indicates that the access jumper is installed and
passcode protection has been satisfied; settings may be altered and stored.
•
COMPUTER RS232: This LED flashes when there is any activity on the
communication port. The LED remains on solid if incoming data is valid.
•
COMPUTER RS485: Flashes when there is any activity on the communication port.
Remains on solid if incoming data is valid and intended for the slave address
programmed in the relay.
•
AUXILIARY RS485: Flashes when there is any activity on the communication port.
Remains on solid if incoming data is valid and intended for the slave address
programmed in the relay.
•
LOCKOUT: Indicates start attempts will be blocked either by a programmed
lockout time or a condition that is still present.
•
RESET POSSIBLE: A trip or latched alarm may be reset. Press the RESET key to
clear the trip or alarm.
•
MESSAGE: Flashes when a trip, alarm, or start block occurs. Pressing the MESSAGE
keys scroll through diagnostic messages. This LED remains solid when settings and
actual value messages are being viewed. Pressing the RESET key returns the
display to the default messages. Under normal conditions, the default messages
selected during settings programming are displayed. If any alarm or trip condition
is generated, a diagnostic message overrides the displayed message and this
indicator flashes. If there is more than one condition present, MESSAGE can be
used to scroll through the messages. Pressing any other key return to the normally
displayed messages. While viewing normally displayed messages, the Message
LED continues to flash if any diagnostic message is active. To return to the
806977A1.CDR
CHAPTER 4: INTERFACES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
4–3
diagnostic messages from the normally displayed messages, press the MENU key
until the following message is displayed.
Now, press the MESSAGE key followed by the MESSAGE key to scroll through the
messages. Note that diagnostic messages for alarms disappear with the condition
while diagnostic messages for trips remain until cleared by a reset.
Motor Status LED Indicators
•
STOPPED: The motor is stopped based on zero phase current and starter status
auxiliary contact feedback.
•
STARTING: Motor is starting.
•
RUNNING: Motor is running normally below overload pickup level.
•
OVERLOAD: Motor is running above overload pickup.
•
UNBALANCE PICKUP: Level of current unbalance has exceeded the unbalance
alarm or trip level.
•
GROUND PICKUP: Level of ground current has exceeded the ground fault alarm or
trip level.
•
HOT RTD: One of the RTD measurements has exceeded its RTD alarm or trip level.
•
LOSS OF LOAD: Average motor current has fallen below the undercurrent alarm or
trip level; or power consumption has fallen below the underpower alarm or trip
level.
Output Relay LED Indicators
•
1 TRIP: The 1 TRIP relay has operated (energized).
•
2 AUXILIARY: The 2 AUXILIARY relay has operated (energized).
•
3 AUXILIARY: The 3 AUXILIARY relay has operated (energized).
•
4 ALARM: The 4 ALARM relay has operated (energized).
•
5 BLOCK START: The 5 BLOCK START relay has operated (energized).
•
6 SERVICE: The 6 SERVICE relay has operated (de-energized, 6 SERVICE is failsafe,
normally energized).
4.1.4
RS232 Port
This port is intended for connection to a portable PC. Settings files may be created at any
location and downloaded through this port with the EnerVista 469 Setup software. Local
interrogation of settings and actual values is also possible. New firmware may also be
downloaded to the 469 flash memory through this port. Upgrading of the relay firmware
does not require a hardware EPROM change.
3. TARGET MESSAGES
Press [] for more
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
4.1.5
Keypad
Description
The 469 display messages are organized into main menus, pages, and sub-pages. There
are three main menus labeled settings, Actual Values, and Target Messages.
Pressing the MENU key followed by the MESSAGE key scrolls through the three main
menu headers, which appear in sequence as follows:
Pressing the MESSAGE key or the ENTER key from these main menu pages will display
the corresponding menu page. Use the MESSAGE and MESSAGE keys to scroll
through the page headers.
When the display shows SETTINGS, pressing the MESSAGE key or the ENTER key will
display the page headers of programmable parameters (referred to as settings in the
manual). When the display shows ACTUAL VALUES, pressing the MESSAGE key or the
ENTER key displays the page headers of measured parameters (referred to as actual
values in the manual). When the display shows TARGET MESSAGES, pressing the
MESSAGE key or the ENTER key displays the page headers of event messages or alarm
conditions.
Each page is broken down further into logical sub-pages. The MESSAGE and
MESSAGE keys are used to navigate through the sub-pages. A summary of the settings
and actual values can be found in the chapters 5 and 6, respectively.
The ENTER key is dual purpose. It is used to enter the sub-pages and to store altered
settings values into memory to complete the change. The MESSAGE key can also be
used to enter sub-pages but not to store altered settings.
The ESCAPE key is also dual purpose. It is used to exit the sub-pages and to cancel a
settings change. The MESSAGE key can also be used to exit sub-pages and to cancel
settings changes.
The VALUE keys are used to scroll through the possible choices of an enumerated settings.
They also decrement and increment numerical settings. Numerical settings may also be
entered through the numeric keypad.
Pressing the HELP key displays context-sensitive information about settings such as the
range of values and the method of changing the settings. Help messages will
automatically scroll through all messages currently appropriate.
The RESET key resets any latched conditions that are not presently active. This includes
resetting latched output relays, latched Trip LEDs, breaker operation failure, and trip coil
failure.
1. SETPOINTS
Press [] for more
2. ACTUAL VALUES
Press [] for more
3. TARGET MESSAGES
Press [] for more
CHAPTER 4: INTERFACES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
4–5
The MESSAGE and MESSAGE keys scroll through any active conditions in the relay.
Diagnostic messages are displayed indicating the state of protection and monitoring
elements that are picked up, operating, or latched. When the Message LED is on, there are
messages to be viewed with the MENU key by selecting target messages as described
earlier.
Entering Alphanumeric Text
Text settings have data values that are fixed in length but user-defined in character. They
may be comprised of upper case letters, lower case letters, numerals, and a selection of
special characters. The editing and storing of a text value is accomplished with the use of
the decimal [.], VALUE, and ENTER keys.
Move to message S3 DIGITAL INPUTS ASSIGNABLE INPUT 1 INPUT
1 FUNCTION, and scrolling with the VALUE keys, select “General Sw.
A”.
The relay will display the following message:
Press the MESSAGE key to view the SWITCH NAME settings. The
name of this user-defined input will be changed in this example from
the generic “General Sw. A” to something more descriptive.
If an application is to be using the relay as a station monitor, it is more informative to
rename this input “Station Monitor”.
Press the decimal [.] to enter the text editing mode. The first
character will appear underlined as follows:
Press the VALUE keys until the character “S” is displayed in the first
position.
Press the decimal [.] key to store the character and advance the
cursor to the next position.
Change the second character to a “t” in the same manner.
Continue entering characters in this way until all characters of the
text “Stn. Monitor” are entered. Note that a space is selected like a
character.
If a character is entered incorrectly, press the decimal [.] key
repeatedly until the cursor returns to the position of the error. Re-
enter the character as required.
Once complete, press the ENTER key to remove the solid cursor and
view the result.
Once a character is entered, by pressing the ENTER key, it is
automatically saved in Flash Memory, as a new setting.
INPUT 1 FUNCTION:
General Sw. A
SWITCH NAME:
General Sw. A
SWITCH NAME:
Stn. Monitor
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
The 469 does not have ‘+’ or ‘–’ keys. Negative numbers may be entered in one of two
manners.
Immediately pressing one of the VALUE keys causes the settings to
scroll through its range including any negative numbers.
After entering at least one digit of a numeric settings value, pressing
the VALUE keys changes the sign of the value where applicable.
4.1.6
Settings Entry
To store any settings, terminals C1 and C2 (access terminals) must be shorted (a keyswitch
may be used for security). There is also a settings passcode feature that restricts access to
settings. The passcode must be entered to allow the changing of settings values. A
passcode of “0” effectively turns off the passcode feature - in this case only the access
jumper is required for changing settings. If no key is pressed for 5 minutes, access to
settings values will be restricted until the passcode is entered again. To prevent settings
access before the 5 minutes expires, the unit may be turned off and back on, the access
jumper may be removed, or the SETTINGS ACCESS settings may be changed to “Restricted”.
The passcode cannot be entered until terminals C1 and C2 (access terminals) are shorted.
When settings access is allowed, the settings Access LED indicator on the front of the 469
will be lit.
Settings changes take effect immediately, even when motor is running. However, changing
settings while the motor is running is not recommended as any mistake may cause a
nuisance trip.
The following procedure may be used to access and alter settings. This specific example
refers to entering a valid passcode to allow access to settings if the passcode was “469”.
Press the MENU key to access the header of each menu, which will
be displayed in the following sequence:
Press the MENU key until the display shows the header of the
Settings menu.
Press the MESSAGE or ENTER key to display the header for the
first settings page.
The set point pages are numbered, have an 'S' prefix for easy
identification and have a name which gives a general idea of the
settings available in that page. Pressing the MESSAGE or
MESSAGE keys will scroll through all the available settings page
headers. Settings page headers look as follows:
1. SETPOINTS
Press [] for more
2. ACTUAL VALUES
Press [] for more
3. TARGET MESSAGES
Press [] for more
SETPOINTS
[]
S1 469 SETUP
CHAPTER 4: INTERFACES
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
4–7
To enter a given Setpoints page, press the MESSAGE or ENTER key.
Press the MESSAGE or MESSAGE keys to scroll through sub-
page headers until the required message is reached.
The end of a page is indicated by the message END OF PAGE. The
beginning of a page is indicated by TOP OF PAGE.
Each page is broken further into subgroups.
Press MESSAGE or MESSAGE to cycle through subgroups until
the desired subgroup appears on the screen.
Press the MESSAGE or ENTER key to enter a subgroup.
Each sub-group has one or more associated settings messages.
Press the MESSAGE or ENTER key to enter the setting message.
Press the MESSAGE or MESSAGE keys to scroll through more
settings messages, if applicable.
The majority of settings are changed by pressing the VALUE keys until the desired value
appears, and then pressing ENTER. Numeric settings may also be entered through the
numeric keys (including decimals). If the entered settings is out of range, the original
settings value reappears. If the entered settings is out of step, an adjusted value will be
stored (e.g. 101 for a settings that steps 95, 100, 105 is stored as 100). If a mistake is made
entering the new value, pressing ESCAPE returns the settings to its original value. Text
editing is a special case described in detail in Entering Alphanumeric Text on page 4–5.
Each time a new settings is successfully stored, a message will flash on the display stating
NEW SETPOINT HAS BEEN STORED.
Press the 4, 6, 9 keys, then press ENTER. The following flash message
is displayed:
and the display returns to:
1.
Press ESCAPE or MESSAGE to exit the subgroup. Pressing ESCAPE or
MESSAGE numerous times will always return the cursor to the top of the
page.
4.1.7
Diagnostic Messages
Diagnostic messages are automatically displayed for any active conditions in the relay
such as trips, alarms, or asserted logic inputs. These messages provide a summary of the
present state of the relay. The Message LED flashes when there are diagnostic messages
available; press the MENU key until the relay displays TARGET MESSAGES, then press the
PASSCODE
[]
ENTER PASSCODE FOR
ACCESS:
NEW SETPOINT HAS
BEEN STORED
SETPOINT ACCESS:
Permitted
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
MESSAGE key, followed by the MESSAGE key, to scroll through the messages. For
additional information and a complete list of diagnostic messages, refer to Diagnostic
Messages in Chapter 6.
4.1.8
Self-Test Warnings
The 469 relay performs self test diagnostics at initialization (after power up) and
continuously as a background task to ensure the hardware and software is functioning
correctly. Self-test warnings indicate either a maintenance alert, or a minor or major
problem. Maintenance alerts and minor problems are problems that does not compromise
motor protection. Major problems are very serious problems that compromise all aspects
of relay operation. Upon detection of either a minor or a major problem the relay will:
•
De-energize the self-test warning relay
•
Light the self-test warning LED
•
Flash a diagnostic message periodically on the display screen
Upon detection of a maintenance alert, the relay will flash a diagnostic message on the
screen, or record an event. The self-test relay remains energized and the service LED
remains off.
Table 4–1: Self-Test Warnings
Message
Severity
Failure description
Self-Test Warning 1
Replace Immediately
Major
Caused by detection of a corrupted location in the
program memory as determined by a CRC error
check. Any function of the relay is susceptible to
malfunction from this failure.
Self-Test Warning 2
Replace Immediately
Major
Caused by a failure of the analog to digital
converter A/D1. The integrity of system input
measurements is affected by this failure.
Self-Test Warning 3
Replace Immediately
Major
Caused by a failure of the analog to digital
converter A/D2. The integrity of system input
measurements is affected by this failure.
Self-Test Warning 5
Replace Immediately
Major
Caused by out of range reading of self-test
RTD 13. The integrity of system input
measurements is affected by this failure.
Self-Test Warning 6
Replace Immediately
Major
Caused by out of range reading of self-test
RTD 14. The integrity of system input
measurements is affected by this failure.
Self-Test Warning 7
Replace Immediately
Major
Caused by out of range reading of self-test
RTD 15. The integrity of system input
measurements is affected by this failure.
Self-Test Warning 8
Replace Immediately
Major
Caused by out of range reading of self-test
RTD 16. The integrity of system input
measurements is affected by this failure.
Self-Test Warning 9
Maintenance
Alert
Occurs if the microprocessor has reset
unexpectedly and system input measurements
were interrupted for at least 2 seconds. This
warning appears in the event recorder.